1KVA to 3KVA 230VAC SINGLE PHASE 19″ Rackmount UPS

1KVA to 3KVA 230VAC SINGLE PHASE 19″ Rackmount UPS
EnPlusEVO UPS 1KVA to 3KVA
Astrid is proud to present the true online topology uninterruptable power supply, the EnPlus EVO
series. Designed rack mount form, the Enplus EVO series provides continuous sine-wave power
with its peak power factor of 0.9, double conversion technology, and high frequency design. With
its market leading performance, the Enplus EVO series is the ideal power solution for net-work
server rooms, cloud execution and storage systems, telecommunication centers, sensitive and
critical electronic systems, or any system requiring high capacity and stable power supply.
• Double conversion online topology with 0.9 power factor.
• Pure sine-wave output with less than 3% of THD.
• Energy-saving functions with high-efficiency mode, free-run mode, etc.
• Complete protections on short circuit, overload, surge and lighting, telecom ports, etc.
• Reliable design with Advanced Battery Management and Adjustable Cooling System.
• Multiple communication and remote monitoring via RS-232, USB, SNMP, etc
Techinical Data Sheet
Model
Nominal output power(0.9 PF)
Input
Voltage (Vac)
EnplusEVO-1KRM
EnplusEvo-1.5KRM
EnplusEVO-2KRM
EnplusEVO-3KRM
1000VA
1500VA
2000VA
3000VA
900W
1350W
1800W
2700W
220V/ 230V/ 240V
120V to 139V under 25% load, 140% to 159V under 50% load, 160V to 179V under 75% load,
180V to 278V with 100% load
Power Factor
50 - 60 ± 2.5Hz Auto sensing(45Hz to 65Hz User selectable)
>0.97
Voltage (Vac)
220 -230 -240 ± 2% (selectable)
Frequency (Hz)
50 / 60 Hz ±0.25%
< 3% for linear load , < 5% for non linear load
Frequency (Hz)
Harmonic Distortion (THDv)
Output
Phase
Single Phase
Waveform
Pure Sine Wave
Output Outlets
Efficiency (DC : AC)
Overload Protection
Protection
Short Circuit Protection
4 X IEC C13 Socket
>89%
UPS automatic power off if overload exceeds 106% to 120% of nominal for 30 seconds or
>121% to 150% for 10 seconds
UPS output cut off immediately or protected by input fuse or circuit breaker
Alarm
Buzzer beeps under Backup mode, Battery low, Battery charging fault and Overload.
Type
Sealed Maintenance-Free Lead Acid Battery
Typical recharge time
Battery
Battery Quantity
Backup time (100% load)
4 hours to 90%
12V 7AH x 3
12V 7AH x 4
12V 7AH x 6
12V 7AH x 6
3 to 5 minutes
3 to 5 minutes
3 to 5 minutes
3 to 4 minutes
Protection
Dimension (WxDxH ) -mm
Product Weight (kg)
General
Battery low cut-off without draining any current
428 x 425 x 84
428 x 500 x 84
15.2
20.8
428 x 635 x 84
29
30
Display(LED)
Line mode (Green), Bypass/Battery mode (yellow), Fault (red)
Display (LCD)
Input/Output voltage and frequency, On-line mode, Backup mode, Battery capacity, Load level
Communication Interface
Audible noise
Ambient Temperature (°C)
Storage Temperature (°C)
Humidity
RS232/ USB / RS485 (Modbus) / RJ45 (SNMP)
< 45 dbA (1m from surface)
< 50 dbA (1m from surface)
0 to 45
-15 to +50
< 95, Non - Condensing
Astrid Electronics (SEA) Pte Ltd
* Subject to changes without notice
51 Bukit Batok Crescent #05-15 Unity Center Singapore 658077
Tel: +65 67636511
Fax: +65 67646511
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement