Thermostats Limitem Rigid Bulb Thermostats

Thermostats Limitem Rigid Bulb Thermostats
356
Limitem Rigid Bulb Thermostats
356 Limitem Rigid Bulb Thermostat.
Applications
The 356 Limitem Rigid Bulb Thermostat is a pneumatically
operated, duct-mounted thermostat, which is available in
either direct or reverse acting in a variety of ranges.
The 356 Limitem Rigid Bulb Thermostat provides primary
control for unit ventilators, fan coils and other air handling
units. Can also be used as low limit control for air flow to a
controlled space.
Features
• Durable copper motor tube and steel rod temperature
sensing element
Application Drawings
Dotted lines are alternative control schemes.
• Two-valve design reduces air waste
• Duct mounting hardware included
• All metal construction
• 18" (46 cm) sensing tube
1-pipe.
2-pipe.
www.usa.siemens.com/hvac
A-21
Thermostats
Description
356 Limitem Remote Bulb Thermostat Specifications
Control Action . ..............................................................Direct or Reverse
Maximum Supply Air Pressure . .................................... 30 psi (207 kPa)
Sensitivity Range (adjustable) ..............0.25 to 2 psi/°F (3 to 25 kPa/°C)
Factory Sensitivity Setting ..................................1.25 psi/°F (15 kPa/°C)
Temperature Response . ................................................... 0.50°F (0.9°C)
Dial Graduations . ................................................ 5°F (2.7°C)/2°C (3.6°F)
Maximum Ambient Temperature
Case.................................................................................. 200°F (93°C)
Bulb (Direct Acting).......................................................... 225°F (107°C)
Bulb (Reverse Acting)...................................................... 250°F (121°C)
Nominal Air Supply Pressure .................... 18 to 25 psi (124 to 172 kPa)
Maximum External Pressure (on bulb) . ................... 250 psi (1722 kPa)
Mounting .....................................................................Flange or 3/8" NPT
Air Connections . ........................................................................ 1/8" NPT
Dimensions
Bulb Length........................................................................18" (457 mm)
Flange OD.........................................................................2.56" (65 mm)
Case........................................................................1.5" Diameter x 3" L
(33 mm Diameter x 76 mm L)
Shipping Weight ...............................................................2.0 lb. (0.91 kg)
356 Limitem Remote Bulb Thermostat Product Ordering
Control Action
Direct Acting
Direct Acting
Reverse Acting
Reverse Acting
Reverse Acting
Temperature Operating Range
0 to 100 °F (-18 to +38°C)
30 to 180°F (-1.11 to +82.2°C)
0 to 100°F (-18 to +38°C)
30 to 180°F (-1.11 to +82.2°C)
100 to 250°F (37.8 to 121°C)
Part No.
356-0012
356-0750
356-0013
356-1005
356-1006
A-22
Thermostats
Accessories & Service Kits
TECH TIP
When using the Limitem as a one-pipe device, a 40 scim (11 ml/s) restrictor will limit your output to 80% of supply.
A 20 scim (5 ml/s) restrictor will limit your output to 60% of supply.
Example: With a 20 scim (5 ml/s) restrictor and 25 psi (11.3 kPa) supply, your maximum output is 15 psi (6.8 kPa).
www.usa.siemens.com/hvac
A-75
357 D
Limitem Remote Bulb Thermostats
357 D Limitem Remote
Thermostat with an average bulb.
Description
Applications
The 357 D Limitem Remote Bulb Thermostat is a
pneumatically-operated thermostat that is gradual, direct
acting with a remote or averaging bulb.
The 357 D Limitem Remote Bulb Thermostat provides
primary monitoring and control for air handling units or a
low limit control.
• Direct acting only
Application Drawings
Dotted lines are alternative control schemes.
• Remote or averaging bulbs for flexibility in installation
• Liquid-filled sensing element for rapid response to
temperature changes
• Two-valve design reduces air waste
• Adjustable sensitivity
2-pipe.
1-pipe.
www.usa.siemens.com/hvac
Thermostats
Features
A-23
357 D Limitem Remote Bulb Thermostat Specifications
Control Action . .................................................................................Direct
Maximum Supply Air Pressure . ..................................... 30 psi (207 kPa)
Sensitivity Range (adjustable) ........... 0.33 to 3.5 psi/°F (4 to 43 kPa/°C)
Factory Sensitivity Setting .................................. 1.25 psi/°F (15 kPa/°C)
Bulb .......................................................................................... Liquid-filled
Temperature Response . ...................................................... 0.5°F (0.3°C)
Dial Graduations . ................................................ 5°F (2.7°C), 2°C (3.6°F)
Maximum Ambient Temperature (case) . ............................ 180°F (82°C)
Nominal Air Supply Pressure ..................... 18 to 25 psi (124 to 172 kPa)
Mounting ..........................................................................Bracket supplied
Air Connection . ...........................................................................1/8" NPT
Dimensions (Case) ...............................................1.75" Diameter x 3.5" H
(44.5 mm Diameter x 88.9 mm H)
Shipping Weight ................................................................. 2.0 lb. (0.9 kg)
357 D Limitem Remote Bulb Thermostat Product Ordering
Temperature
Operating Range
20 to 100°F (-6.7 to +37.8°C)
5 to 145°F (1.7 to 62.8°C)
120 to 230°F (48.9 to 110°C)
35 to 145°F (1.7 to 62.8°C)
Sensing Element
Remote Bulb
Averaging Bulb
Remote Bulb
Averaging Bulb
Capillary
8' (2.4 m)
40' (12.2 m)
40' (12.2 m)
6" (15 cm)
Bulb
3/8" x 4' (0.95 mm x 10.2 cm)
3/32" x 15' (0.24 mm x 457 cm)
3/8" x 4" (0.95 mm x 10.2 cm)
3/32" x 8' (0.24 mm x 244 cm)
Maximum
Ambient Temp.
201°F (94°C)
210°F (99°C)
261°F (127°C)
211°F (99.4°C)
Part No.
357-0003
357-0004
357-0005
357-0001
A-24
Thermostats
Accessories & Service Kits
www.usa.siemens.com/hvac
A-75
188
Unit Mounted Thermostats
188 Unit Mounted Thermostat.
Applications
The 188 Unit Mounted Thermostat is a gradual acting
thermostat with a remote bulb operating on the forcebalance principle, using pneumatic feedback to obtain
linearity and maintain selected room temperature by
positioning pneumatic devices to control heating or
cooling.
The 188 Unit Mounted Thermostats are designed primarily
for use in fan coil induction units and unit ventilators to
control the temperature within an occupied space. The
thermostat’s temperature range is limited to applications at
ambient temperatures.
Features
• Liquid-filled thermal system temperature
sensing element
Typical Connections
• Durable die-cast metal case with rugged setpoint knob
• Adjustable sensitivity
• Universal mounting bracket for easy installation
• Integral adjustable limit stops
•
Available as:
– Direct Acting only (Heating)
– Reverse Acting only (Cooling)
– Heat or Cool depending on supply air pressure
www.usa.siemens.com/hvac
A-25
Thermostats
Description
188 Unit Mounted Thermostat Specifications
Control Action . .............................. Heating/Cooling, Direct and Reverse;
Direct only; Reverse only
Operating Range ........................................... 60 to 85°F (15.5 to 29.4°C)
Operating Pressure ................................................30 psi (207 kPa) max.
Adjustment Sensitivity . .......................1 to 5.25 psi/°F (12 to 65 kPa/°C)
Factory Sensitivity Setting ..................................2.25 psi/°F (28 kPa/°C)
Temperature Response . ..................................................... 0.2°F (0.1°C)
Maximum Ambient Temperature
Case............................................................................... 135°F (57.2°C)
Bulb . ...............................................................................231°F (111°C)
Scale Graduations . .............................................................. 1°F (0.55°C)
Nominal Air Supply Pressure
Direct or Reverse Acting............................................... 25 psi (172 kPa)
Heating/Cooling.................................. 25 psi (172 kPa)/18 psi (124 kPa)
Average Air Usage
20 scim Restrictor....................................................... 25 scim (6.8 ml/s)
40 scim Restrictor..................................................... 45 scim (12.2 ml/s)
Air Connections . ........ 1/4" (6 mm) Brass barbed for polyethylene tubing
Bulb Size ............................................................. 3/8" Diameter x 3-1/2" L
(9.5 mm Diameter x 89 mm L)
Capillary Length ................................................... 48" (121.9 cm) approx.
Finish . ...............................................Corrosion-resistant Zinc Chromate
Dimensions (case)
Heating/Cooling, Reverse Acting.................... 3.1" W x 2.4" H x 2.13" D
(100 mm W x 61 mm H x 54 mm D)
Direct Acting.................................................... 3.1" W x 2.4" H x 1.38" D
(100 mm W x 61 mm H x 35 mm D)
Shipping Weight ...............................................................3.0 lb. (1.36 kg)
188 Unit Mounted Thermostat Product Ordering
A-26
Single Setpoint
Control Action
Direct Acting / 25 psi (172 kPa)
Changeover Pressure
—
Average Air Usage
40 scim (11 ml/s)
Part No.
188-0031
Single Setpoint
Reverse Acting (Cooling) 18 psi
—
20 scim (5 ml/s)
188-0024
—
40 scim (11 ml/s)
188-0030
15 psi (103 kPa)
40 scim (11 ml/s)
188-0033
17 psi (117 kPa)
40 scim (11 ml/s)
188-0034
Heat/Cool
Thermostats
Heat/Cool
Heat/Cool
Direct Acting / Reverse Acting (Cooling)
18 psi (124 kPa)
Retroline Direct Acting/Reverse Acting
18 psi (124 kPa) / 13 psi (90 kPa). Retroline
replacement for Honeywell LP916BXXXX.
Retroline Direct Acting/Reverse Acting
20 psi (138 kPa) / 15 psi (103 kPa). Retroline
replacement for Johnson Controls T-3300-2.
Accessories & Service Kits
www.usa.siemens.com/hvac
A-75
134
Pneumatic High and Low Temperature
Detection Thermostats
134 Pneumatic Low Temperature Detection Thermostat.
Applications
The 134 High and Low Temperature Detection Pneumatic
Thermostats automatically “lockout” at setpoint and require
manual reset.
The 134 Pneumatic High and Low Temperature Detection
Thermostats are used on pneumatic heating and cooling
systems in areas protected from the weather.
Features
On a typical high limit application, the thermostat shuts
down air conditioning or ventilating fans when the duct
temperature becomes excessively high. A normally closed
switch opens at setpoint.
• Snap-acting pneumatic switch
• Sight-set calibrated setpoint scale
• No leakage of air prior to reset of switch
• Easily adjustable settings
• Normally closed air valve; bleeds to less than 2 psi
(14 kPa) when supplied through a restrictor
On a typical low temperature application, the thermostat
stops the fan or closes a damper when the temperature
drops to the setpoint at any one foot (30.5 cm) or more of
the sensing element.
• Barb fitting for push-on connection of 1/4" (6 mm)
OD polyethylene tubing
• Holds dead-ended line to approximately 22 psi
(152 kPa) air pressure
Application Drawings
www.usa.siemens.com/hvac
A-27
Thermostats
Description
134 Pneumatic Thermostat Specifications
Part No. 134-1700
Part No. 134-1710
Ambient Temperature Range .............................Greater than setpoint to
140°F (60°C)
Pneumatic Switch . ..........................NC, 0.020" (0.6 mm) diameter bleed
Control Point Low
Temperature Thermostat ...............................Lowest temperature at any
one foot section of the sensing bulb
Case Finish ............................................................... Gray Baked Enamel
Shipping Weight .............................................................2.45 lb. (1.11 kg)
Ambient Temperature Range .............................................-40 to +140°F
(-40 to +60°C)
Pneumatic Switch . ............................NC, 0.02" (0.6 mm) diameter bleed
Control Point Low
Temperature Thermostat ...............................Lowest temperature at any
one foot section of the sensing bulb
Case Finish ............................................................... Gray Baked Enamel
Shipping Weight .............................................................2.38 lb. (1.08 kg)
134 Pneumatic Thermostat Product Ordering
Temp.
Thermostats
A-28
Temperature
Range
Differential
Max. Bulb
Temp.
Bulb & Capillary
Length
Switch Reclose
Part No.
Low
15 to 55°F
(-9 to +12.8°C)
with stop at
35°F (1.67°C)
5°F (2.8°C)
Non-Adjustable
400°F
(204°C)
20' (6 m)
Temperature must increase by
5°F (2.8°C) before pneumatic
switch can be reclosed.
134-1700
High
100 to 170°F
(38 to 77°C)
10°F (5.6°C)
Non-Adjustable
250°F
(121°C)
2.7" (69 mm) Dia. x 10"
(25.4 cm) L bulb with 6'
(183 mm) capillary
Temperature must drop 10°F
(5.6°C) before pneumatic switch
can be reclosed.
134-1710
Accessories & Service Kits
Dimensions
Dimensions shown in inches (mm).
www.usa.siemens.com/hvac
A-75
141
Electric Line Voltage Remote
Bulb Thermostats
141 Electric Line Voltage Remote Bulb Thermostat.
Applications
The 141 Electric Line Voltage Remote Bulb Thermostat
is a two-position electric line voltage thermostat with
remote bulb.
The 141 Electric Line Voltage Remote Bulb Thermostat
is used for temperature control in heating and cooling
application, typically to directly operate two-position
damper motor actuators, motor actuated valves, relays
and similar equipment. Typical applications includes
summer-winter change over and the direct control of
liquid or air temperatures where two position (ON-OFF)
control is acceptable.
Features
• Temperature sensitive, liquid-filled sensing element
• Single-pole, double-throw snap-acting switches
• Enclosed switches suitable for low or line voltage
power switching
• Gray baked enamel case
Typical Connections
CLOSE ON RISE
OF TEMPERATURE
YELLOW
BLUE
OPEN ON RISE
OF TEMPERATURE
RED (COM)
www.usa.siemens.com/hvac
A-29
Thermostats
Description
141 Electric Line Voltage Remote Bulb Thermostat Specifications
Inductive Amps
Full Load Amps
120 Vac...........................................................................................7.4
240 Vac...........................................................................................3.7
Locked Rotor Amps
120 Vac.........................................................................................44.5
240 Vac.........................................................................................22.2
Resistive Amps
120 Vac................................................................................................25
240 Vac................................................................................................20
Dimensions ..................................................... 2.5" W x 5.38" H x 2.31" D
(64 mm x (136 mm x 59 mm)
Shipping Weight ...............................................................1.8 lb. (0.82 kg)
141 Electric Line Voltage Remote Bulb Thermostat Product Ordering
Temperature Scale Range
Max. Bulb Temp.
Bulb Size
Switch Differential
Part No.
0 to 120°F (-7 to +49°C)
130°F (54°C)
.038" Diameter x 4.03" L
(9.9 mm Diameter x 102 mm L)
Capillary 6' (183 cm)
Adjustable 6 to 30°F
(3 to 16°C)
141-0520
100 to 240°F (38 to 110°C)
250°F (121°C)
.029" Diameter x 2.33" L
(7.4 mm Diameter x 59.2 mm L)
Capillary 6' (183 cm)
Adjustable 7 to 45°F
(14 to 25°C)
141-0521
Thermostats
A-30
Accessories & Service Kits
Part No. in black box
Ships same day when requested through Rapid ResponseTM shipping. See inside back cover for details.
A-75
134
Electric Line Voltage Room Thermostats
Heating/Cooling
134 Electric Line Voltage Room
Thermostat—Heating/Cooling.
Applications
The 134 Electric Line Voltage Room Thermostat is a
line voltage On/Off room thermostat for heating and
cooling applications.
The 134 Electric Line Voltage Room Thermostat
controls heating and cooling applications or year-round
air conditioning units in commercial, industrial, or
residential installations.
Models are available with SPST or SPDT contact action
and for standard, nominal 1/4 hp / 10 amps noninductive,
or heavy duty, nominal 1 hp / 22 amps noninductive
applications.
Typical Connections
Features
• Single setpoint dial
• Exposed bimetal thermometer
• Temperature range from 50 to 90°F (10 to 30°C)
• High and low limit stops
• Standard or heavy duty models
• Dual Fahrenheit/Celsius scale plate
www.usa.siemens.com/hvac
A-31
Thermostats
Description
134 Electric Line Voltage Room Thermostat Specifications
Part No. 134-1083
Part No. 134-1084
Motor Rating
120 Vac............................................................................................6.0 A
240 Vac............................................................................................3.7 A
Switch Action . .......................................SPST with “Auto-Off-Fan” switch
Dimensions ................................................... 2.78" W x 5.19" H x 1.88" D
(71 mm W x 132 mm H x 48 mm D)
Shipping Weight ...............................................................1.3 lbs. (0.6 kg)
Motor Rating
120 Vac............................................................................................6.0 A
240 Vac............................................................................................3.0 A
Resistive Rating
120 Vac...................................................................................10.0 amps
240 Vac...................................................................................10.0 amps
Switch Action . .................................................................................SPDT
Dimensions ........................................................ 3" W x 4.75" H x 1.44" D
(75 mm W x 120 mm H x 36 mm D)
Shipping Weight .................................................................1.0 lb. (0.6 kg)
Part No. 134-1086
Motor Rating
120 Vac............................................................................................6.0 A
240 Vac............................................................................................3.0 A
Switch Action . ................................................................................. SPST
Dimensions ........................................................ 3" W x 4.75" H x 1.44" D
(75 mm W x 120 mm H x 36 mm D)
Shipping Weight 1.3 lb. (0.6 kg)
Thermostats
A-32
Part No. 134-1085
Motor Rating
120 Vac............................................................16.0 Heating/8.0 Cooling
240 Vac..............................................................8.0 Heating/8.0 Cooling
Resistive Rating
120 Vac............................................................................... 22.0 Heating
240 Vac............................................................................... 22.0 Heating
Switch Action . .................................................................................SPDT
Dimensions ........................................................ 3" W x 4.75" H x 1.44" D
(75 mm W x 120 mm H x 36 mm D)
Shipping Weight .................................................................1.0 lb. (0.6 kg)
134 Electric Line Voltage Room Thermostat Product Ordering
Switch Action
Temp. Set Point Range
Temp. Set Point Adjustment
Temperature Difference
Part No.
SPST
40 to 90°F (5 to 30°C)
Concealed
1.8°F (1°C)
134-1083
SPST
40 to 90°F (5 to 30°C)
Concealed
1.8°F (1°C)
134-1086
SPDT
40 to 90°F (5 to 30°C)
Exposed Knob or Concealed1
1.8°F (1°C) Heating
2.31°F (1.3°C) Cooling
134-1084
SPDT
40 to 90°F (5 to 30°C)
Exposed Knob or Concealed1
3°F (1.7°C) Heating
3.5°F (2°C) Cooling
134-1085
Ordering Note
1. Each thermostat is shipped with a blank faceplate for use when concealed adjustment is desired.
Accessories & Service Kits
Part No. in black box
Ships same day when requested through Rapid ResponseTM shipping. See inside back cover for details.
A-75
RAA…
Electric Room Thermostats
RAA10C Fan Coil Thermostat
with concealed setpoint knob.
RAA20U Room Thermostat
with exposed setpoint knob.
Applications
Designed for simple heating or cooling or heating/cooling
applications, RAA… Electric Room Thermostats are an
attractive and economical solution that utilize two-wire,
gas membrane technology.
The RAA… Electric Room Thermostats are typically used
in public buildings, storage rooms, entrance hallways and
maintenance rooms where two-position (On/Off) control
is required.
RAA… Electric Room Thermostats are available in
single scale Fahrenheit or Celsius models, except the
RAA10C, with models for dry wall or electrical wall box
mounting. Models designed for wall box mounting
include wall box plate adapter and screws.
Descriptions of models are as follows:
Features
• Two-point control algorithm for on/off control
• 24 to 120, 277 Vac line
• Two mounting styles: electrical wall box or drywall
• Dual Fahrenheit/Celsius scale (RAA20U)
Options
• Tamperproof cover (concealed setpoint knob) noted
with a C
RAA10C model is a heating or cooling only thermostat
that has a concealed setpoint knob for use in areas where
setpoint adjustment is limited to authorized personnel.
Typical applications are frost and overheat protection and
temporary heat for buildings under construction.
RAA20U model is a heating or cooling only thermostat that
has an external setpoint knob for occupant adjustment.
Note:
ARG 70 wall plate is required in order to be UL compliant
for switching line voltage.
The RAA… Room Thermostats are designed for either
simple heating or cooling or for 2-pipe heating and cooling
systems where fan control is not required.
• Available with wall plate
www.usa.siemens.com/hvac
A-33
Thermostats
Description
RAA Electric Room Thermostat Specifications
Operating Voltage . ..................................................... 24 to 120, 277 Vac
Frequency ...............................................................................50 or 60 Hz
Setpoint Adjustment Range ............................... 50 to 85°F (10 to 29°C)
Switching Differential . ........................................................ < 1.8°F (1°C)
Switch Rating . ............................................ 6A RES, 3.5 A FLA, 12A LRA
Time Constant ...............................................................................14 min.
Switch Action Output ...................................SPDT Two-position (On/Off)
Operation–Conditions
Operating Temperature ..................................... 32 to 122°F (0 to 50°C)
Relative Humidity .................................................................... <95% RH
Transportation/Storage Conditions
Temperature ................................................-4 to +122°F (-20 to +50°C)
Relative Humidity .................................................................... <95% RH
Housing
Material ........................................................................................Plastic
Color . ........................................................................................... White
Bellows . .................................................... Environmentally-friendly gas
Wiring ............................................................ Screw terminals for wires of
2 x 16 AWG or 1 x 14 AWG, 20 AWG max.
Agency Listings . .......................................Conforms to CE requirements
UL listed to 873
cUL listed to Canadian standard C22.2 No. 24-93
Shipping Weight .............................................................0.31 lb. (0.14 kg)
RAA Electric Room Thermostat Product Ordering
Electric Wall Box1
Part No.
Dry Wall
Part No.
Thermostat for heating or cooling only
RAA10CW
RAA10C
Thermostat for heating or cooling only with exposed setpoint knob
RAA20UW
RAA20U
Description
Thermostats
A-34
Ordering Note
1. Includes wall plate, ARG70, to be UL compliant for switching line voltage.
Accessories & Service Kits
Part No. in black box
Ships same day when requested through Rapid ResponseTM shipping. See inside back cover for details.
A-75
RAA Electric Room Thermostat Dimensions
RAA20U... Thermostat
3.80
(96.4)
1.42
(36)
TH0497R2
TH0503R2
3.92
(99.6)
3.92
(99.6)
RAA10C... Thermostat
3.80
(96.4)
1.68
(42.8)
Wall Plate (ARG70) for Mounting
(RAA10CW and RAA20UW)
A-35
Thermostats
Dimensions shown in inches (mm).
www.usa.siemens.com/hvac
RAA Electric Room Thermostat Engineering Drawings
Wiring Diagrams
Operating Diagrams
Heating Mode
Heating Mode
Cooling Mode
RAA10C…/RAA20U…
Key
D1 Heating device
D2 Cooling device
L Operating voltage
N Neutral
N1 Room thermostat
S
T
W
Y
Thermostats
A-36
www.usa.siemens.com/hvac
On/Off switch
Thermostat
Heating control output
Cooling control output
Cooling Mode
RAA10C…/RAA20U…
Key
T Room temperature
SD Switching differential
SP Room temperature setpoint
W Heating output signal
Y Cooling output signal
Was this manual useful for you? yes no