masterys gp - Corecomm SI Kft.
MASTERYS GP
Three-phase UPS
High-efficiency protection without compromise
Green Power 2.0 range from 10 to 120 kVA/kW
The solution for
> Data centres
> Telecommunications
> Healthcare sector
> Service sector
> Infrastructure
> Industrial applications
Certifications
GAMME 125 B
GAMME 202 C
The MASTERYS GP series is
certified by TÜV SÜD with
regard to product safety
(EN 62040-1).
Advantages
Energy saving + Full rated power = reduced TCO
Energy Saving: high efficiency
without compromise
• Offers the highest efficiency in the market
using VfI – Double Conversion Mode, the
only UPS working-mode that assures total
load protection against all mains quality
problems.
• Ultra high efficiency output independently
tested and verified by an international
certification organization in a wide range of
load and voltage operating conditions, to
have the value in the real site conditions.
• Ultra high efficiency in VfI mode is
provided by an innovative topology (3-Level
technology) that has been developed for all
the Green Power 2.0 UPS ranges.
Full-rated power: kW=kVA
• No power downgrading when supplying the
latest generation of servers (leading or unity
power factor).
• Real full power, according to IEC 62040:
kW=kVA (unity power factor design) means
25% more active power available compared
to legacy UPS.
• Suitable also for leading power factor
loads down to 0.9 without apparent power
derating.
40
Catalogue 2015
Significant cost-saving (TCO)
• Maximum energy saving thanks to 96%
efficiency in true double conversion mode:
50% saving on energy losses compared
to legacy UPS gives significant savings in
energy bill.
• UPS “self-paying” with energy saving.
• Energy Saver mode for global efficiency
improvement on parallel systems.
• kW=kVA means maximum power available
with the same UPS rating: no overdesign
cost and therefore less €/kW.
• Upstream infrastructure cost optimization
(sources and distribution), thanks to high
performance IGBT rectifier.
• Battery configuration can be optimized,
thanks to a very wide DC range.
• Extended battery life and performance:
- long life battery,
- very wide input voltage and frequency
acceptance, without battery use.
• EBS (Expert Battery System) charging
management improves battery service life.
Better performance
than the EU Code of Conduct
on efficiency of AC UPS
MASTERYS GP
Three-phase UPS
Green Power 2.0 range from 10 to 120 kVA/kW
Standard electrical features
Electrical options
•
•
•
•
•
•
•
•
•
•
Dual input mains.
Internal maintenance bypass.
Backfeed protection: detection circuit.
EBS (Expert Battery System) for battery
management.
• Battery temperature sensor.
Standard communication
features
External maintenance bypass.
External battery cabinet.
Additional battery chargers.
Galvanic isolation transformer.
Parallel kit.
ACS synchronization system.
• User-friendly multilingual interface with color
graphic display.
• Commissioning wizard.
• 2 slots for communication options.
• MODBUS TCP.
• MODBUS RTU.
• Embedded LAN interface
(web pages, email).
Technical data
Sn [kVA]
Pn [kW]
Input / output 3/1
Input / output 3/3
Parallel configuration
INPUT
Rated voltage
Voltage tolerance
Rated frequency
Power factor / THDI
OUTPUT
Rated voltage
10
10
•
•
15
15
•
•
20
20
•
•
30
30
•
MASTERYS GP
40
40
•
up to 6 units
60
60
•
80
80
•
100
100
•
120
120
•
400 V 3ph+N
240 V to 480 V(1)
50/60 Hz ± 10%
> 0.99 / < 2.5%
1ph + N: 230 V (can be configured 220/240 V)
3ph + N: 400 V (can be configured 380/415 V)
static load ±1 % dynamic load in accordance with VFI-SS-111
50/60 Hz
± 2% (configurable for GenSet compatibility)
Voltage tolerance
Rated frequency
Frequency tolerance
Total output voltage distortion < 1%
linear load
Total output voltage distortion < 3%
non-linear load
Overload
125% for 10 minutes, 150% for 1 minute (1)
Crest factor
3:1
BYPASS
Rated voltage
rated output voltage
Voltage tolerance
± 15% (configurable from 10% to 20%)
Rated frequency
50/60 Hz
Frequency tolerance
± 2%
EFFICIENCY (TÜV SÜD verified)
Online mode @ 50 % of load
up to 96%
Online mode @ 75 % of load
up to 96%
Online mode @ 100 % of load
up to 96%
Eco Mode
up to 98%
ENVIRONMENT
Operating ambient temperature
from 0 °C up to +40(1) °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity
0% - 95% without condensation
Maximum altitude
1000 m without derating (max. 3000 m)
Acoustic level at 1 m (ISO 3746)
< 52 dBA
< 55 dBA
< 60 dBA
< 65 dBA
UPS CABINET
444 mm
600 mm
700 mm
W
D
795 mm
800 mm
Dimensions
H
800 mm
1000 mm
1400 mm
1930 mm
Weight
190 kg
195 kg
315 kg 320 kg 180 kg 200 kg 380 kg 460 kg
Degree of protection
IP20
Colours
RAL 7012
STANDARDS
Safety
IEC/EN 62040-1 (TÜV SÜD certified), EN 60950-1, AS 62040.1.1, AS 62040.1.2
EMC
IEC/EN 62040-2, AS 62040.2
Performance
VFI-SS-111 - IEC/EN 62040-3, AS 62040.3
Product declaration
CE, RCM (E2376)
Communication options
•
•
•
•
Dry-contact interface.
PROfIBUS.
BACnet/IP interface.
NET VISION: professional WEB/SNMP
interface for UPS monitoring and shutdown
management of several operating systems.
Remote monitoring service
• LINK-UPS, remote monitoring service that
connects your UPS to your Critical Power
specialist 24/7.
(1) Conditions apply.
Catalogue 2015
41
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising