Locking a Door Unlocked by a Schedule using a Card

Locking a Door Unlocked by a Schedule using a Card
APPLICATION NOTE
DN1601-0411
Locking a Door Unlocked by a Schedule using a Card
Objective
This document shows you how to configure EntraPass to unlock a door using a schedule (with or without
the First Man In feature) and re-lock before the schedule ends by presenting a card to the reader and
pressing a button.
An external alarm system will be used to illustrate our purpose.
Requirements
•
Running EntraPass software with defined access levels
•
Door connected to a KT-300 controller
•
An external button installed next to the reader (or keypad button such as * or # with the P225KP or
P325KP)
•
2 pieces of wire (Jumpers)
Steps
1.
2.
3.
4.
5.
6.
Connect the hardware as shown below
Connect the controller, then configure the controller using the Express Setup utility
Define the desired schedules (Definition > Schedules
Define the required relays (Devices > Relays)
Define the required inputs (Devices > Inputs).
Define the door and external alarm system options (Devices >Doors).
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 1 / 8
APPLICATION NOTE
DN1601-0411
Step by Step Instructions
1.
Connect the external push button and the 2 jumpers as illustrated by the following diagram.
2.
Access EntraPass to configure the KT-300 controller and define door contacts and REX (refer to the
EntraPass reference manual for details on how to configure controllers using Express setup).
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 2 / 8
APPLICATION NOTE
DN1601-0411
3.
Define the schedule during which the door will be unlocked: Definition > Schedule.
4.
Define the two (2) onboard output relays: Devices > Relays. Identify the first one as Request to arm
(lock) and the second as Request to disarm (unlock) . Leave the default values.
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 3 / 8
APPLICATION NOTE
DN1601-0411
5.
Define the three (3) required inputs: Devices > Input. Assign an Always valid schedule to all the
defined inputs.
5.1
Select input # 5 and label it Request to arm input. Leave the default value unchanged and save.
5.2
Select input # 6 and identify it as an Arming status input , set it for normally Opened and save.
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 4 / 8
APPLICATION NOTE
DN1601-0411
5.3
5.4.
Select input # 7 and label it Shunt request to arm. Leave it to normally Closed.
Select the Relay and Input tab and select “relay 1” for the Activate relay field, then assign Input
6 as the Shunt input and save.
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 5 / 8
APPLICATION NOTE
DN1601-0411
6
Go to Devices > Door to bring up the door definition window. Select the door you want to define for
this application.
6.1
Assign the Unlock schedule for this door. This is the schedule defined earlier in Step 3. Select the
Options and alarm system tab.
6.2
Check the Unlock door by schedule after first access granted option.
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 6 / 8
APPLICATION NOTE
DN1601-0411
6.3
Click the External alarm system options button.
6.4
6.5
6.6
6.7
6.8
6.9
6.10
Assign Input 5 as the Arming request input.
Select the Always valid schedule as the Enable Arming request schedule.
Under the Arming access level field, select the access level or the group of access levels for the
cardholders who will have permission to relock the door after the door was unlocked by a schedule.
Check the Wait for access granted to arm checkbox.
Check the Re-Lock door on request to arm checkbox.
Select Input 6 as the External alarm system panel status input.
Select the Input tab.
6.11
Check the Shunted on exit and Shunted on disarm checkbox for “input 7”.
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 7 / 8
APPLICATION NOTE
DN1601-0411
6.12
Select the Postpone arming tab.
6.13
6.14
Assign the access level or group of access level of the cardholders who will be allowed to unlock
the door by schedule (first people in) under the Postpone or disarm access level field.
Select the Relay tab.
6.15
6.16
6.17
Assign “relay # 1” as the Arming alarm panel – Exit delay.
Assign “relay # 2” as the Disarming alarm panel – Entry delay.
Click OK and save the door definition.
Telephone: 1 (450) 444 2030 • Toll free: 1 888 222-1560 • Fax: 1 (450) 444 2029 • Internet: www.kantech.com
Copyright © 2004 Kantech Systems • All rights reserved • Specifications are subject to change without notice
page 8 / 8