Installing the 4285/4286 VIP Module

Installing the 4285/4286 VIP Module
Section 3 - Installing the Control
Event Log Connections
3
4
1
2
3
4
5
6
7
8
9
J2 CONNECTOR
VIOLET
2
NOTES:
If you are using printer, field 3✳19 must = 1.
If you are using a serial printer, it must configured with
7 data bits, even parity, 1 stop bit, 1200 baud
GREY
Connect the 4142TR cable to J2 on the
control.
Connect the Violet and Red wires of the
4142TR to terminal 1 and 6 on the 4100SM,
respectively.
Connect terminals 8 and 7 of the 4100SM to
terminals 11 and 12 (aux. power (+) and (-)),
respectively of the control.
Connect the serial printer to the 4100SM.
NOTE: The 4100SM Module is supplied with
a 10-foot RS232 cable. A longer cable can be
used if the VISTA-128FBP/VISTA-250FBP is
separated from the serial printer by more
than 10 feet, but the total cable length should
be less than 50 feet.
Connect the printer according to the
instructions that accompany the APM.
WHITE
1
2
YELLOW
Action
Connect the APM to the control (see
Installing the Alpha Pager Module previously
in this section).
RED
Step
1
GREEN
Using the 4100SM
To connect a serial printer using the 4100SM, refer to
Figure 3-33 and perform the following steps:
Action
BLUE
•
When using a printer, field 3*19 must be
programmed for RS232 input (1).
If you are using a serial printer, J2 pins 5 &
9 on the control panel cannot be used to
interface with Automation software.
Step
BROWN
•
Using the Alpha Pager Module (APM)
To connect a printer using the Alpha Pager Module,
perform the following steps:
BLACK
This system has the ability to record up to 1000 events
of various categories in the Event Log (history log).
Each event is recorded with the time and date of its
occurrence (if real-time clock is set).
The categories are Alarm, Supervisory/Check, Bypass,
Open/Close, System and Test conditions. The log may
be viewed on an alpha keypad, the AUI or printed on a
serial printer.
4142TR CABLE (SUPPLIED WITH 4100SM)
To TB11 Aux. Power (+)
(25mA current draw)
To TB12 Aux. Power (-)
4100SM SERIAL MODULE
8
+ PWR
7
- (GND)
6
RXD
5
not used
4
not used
3
TXD
2
not used
DTR
1
RED
USE GENDER CHANGER
SUPPLIED WITH 4100SM
IF PRINTER HAS DB25
MALE CONNECTOR
BLUE
WHITE
3M
Cable
Supplied with
4100SM
COLOR
FUNCTION
PIN #
RED
BLUE
WHITE
CD
CTS
DSR
8
5
6
SERIAL PRINTER
SET FOR: 8 DATA BITS
EVEN PARITY
STOP BIT
300/1200 BAUD
4100SM-012-V0
4100SM JUMPERS
(CUT TO SET RESPECTIVE SIGNAL FLOATING)
Figure 3-33: Printer Connections to the 4100SM
NOTE: See the 4100SM Installation Instructions for
details concerning the serial printer operation.
Installing the 4285/4286 VIP Module
The 4285/4286 VIP Module is an add-on accessory that
permits the user to access the security system (and
relays) via a TouchTone telephone. This may be done
either from the premises or by calling the premises
from a remote location. Only one VIP Module can be
used in a security system. This module must be
enabled as Device Address 4 in the Device
Programming in #93 Menu Mode, and must be assigned
to a partition.
UL
The 4285/4286 VIP Module is not permitted in
UL installations.
Detailed operating instructions for phone access
to the security system are provided with the VIP
Module.
The 4285/4286 VIP Module features:
•
Allows the user to receive synthesized voice
messages over the phone regarding the status of
the security system.
•
Allows the user to arm and disarm the security
system and perform most other commands using
the telephone keypad.
•
Allows the user to control relays using the
telephone keypad.
3-27
VISTA-128FBP/VISTA-250FBP Installation and Setup Guide
•
Provides voice annunciation over the phone to
confirm any command that is entered.
•
Announces many of the same words that would
normally be displayed on an alpha keypad under
the same system conditions. Refer to the words in
bold on the Alpha Vocabulary list found in the #93
Menu Mode Programming in the Programming
Guide.
•
Can be supervised for connection to control panel
(annunciated and reported as Zone 804).
The 4285/4286 is wired between the control panel and
the premises’ handset(s) (see Figure 3-34). It listens for
TouchTones on the phone line and reports them to the
control panel. During on-premises phone access, it
powers the premises phones; during off-premises phone
access, it seizes the line from the premises phones and
any answering machines.
• The VIP module will not operate until the
device address (04) is enabled in the control’s
Device Programming in #93 Menu Mode.
• Do not mount the VIP Module on the cabinet
door or attempt to attach it to the PC board.
To install the VIP module, perform the following steps:
Step
Action
1
Mount the module in the control cabinet if
space is available or, if this is not possible, on
the side of the cabinet or adjacent to it.
If you mount the VIP Module inside the
control cabinet, attach it to the cabinet’s
interior surface with 2-faced adhesive tape.
You may leave the module’s cover off if it is
mounted within the cabinet.
If you mount the module outside the
cabinet, use the screw holes at the rear to
mount horizontally or vertically (2-faced
adhesive tape may be used, if preferred).
2
Affix the 4285/4286 connections label
(supplied separately) to the inside of the VIP
Module’s cover, if the cover is used.
Otherwise, affix the label to the inside of the
control cabinet’s door.
3
Make 12V (+) and (–) and data-in and dataout connections from the VIP Module to the
control, using the connector cable supplied
with the VIP Module. These are the same
connections as for remote keypads.
3-28
Step
Action
4
Connect the module to the phone line as
shown below. See Figure 3-34.
4285/4286 Terminal
Connects to:
1. Phone In (Tip)
green wire of directconnect cord
2. Phone In (Ring)
red wire of directconnect cord
3. Phone Out (Tip)
brown wire of directconnect cord
4. Phone Out (Ring)
gray wire of directconnect cord
5. No Connection
6. Audio Out 1∗
Speaker
7. Audio Out 1∗
Speaker
∗Supported by the 4286 only
Use an RJ31X Jack with the phone cable
supplied with the control to make connections
to the VIP module. Make connections exactly
as shown in Figure 3-34. This is essential,
even if the system is not connected to a
central station. The 4285/4286 will not
function if this is not done.
• If touch-tones are not present following phone
access to the security system via an onpremises phone, try reversing the pair of
wires connected to terminals 3 and 4 on the
4285/4286.
• If the phone plug is disconnected from the
control, the premise’s phones will not operate.
Section 3 - Installing the Control
SPEAKER NOTE: IF CONNECTING SINGLE SPEAKER, USE 8-ohm
SPEAKER ONLY.
IF CONNECTING 2 SPEAKERS, USE 4-ohm OR
8-ohm SPEAKERS AND CONNECT IN SERIES.
GREEN
RED
RJ31X
JACK
CONTROL PANEL
CALLER
ID UNIT
BROWN
JACK
GRAY
MAIN
DIALER
JACK
INCOMING TELCO LINE
8-CONDUCTOR
DOUBLE PLUG CORD
(SUPPLIED)
4500
THERMOSTAT
RED
KEYED
HEADER
DIRECT
CONNECT
CORD
BROWN
RJ31X
JACK
TO CONTROL PANEL
KEYPAD CONNECTIONS
PREMISES
ANSWERING
MACHINE AND
PHONES
ANSWERING
MACHINE
YELLOW
NO CONNECTION
RED
BLACK
GREEN
IMPORTANT NOTE FOR EXISTING INSTALLATIONS:
EXISTING WIRES CONNECTED TO THE "HANDSET"
TERMINALS ON CONTROL MUST BE MOVED FROM
THERE TO TERMINALS 3 AND 4 ON THE 4286.
U.S. PATENT NO. 4791658
THIS DEVICE COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC3USA-74659-KX-N
RINGER EQUIVALENCE: 1.0B
4286_wiring-003-V0
GREEN
GRAY
BROWN
RED
GREEN
GRAY
NO CONNECTION
YELLOW
5 6 7
SPEAKER
VOLUME
CONTROL
1 2 3 4
NOTE:
4286 DEVICE
ADDRESS IS
SET TO "4".
GREEN
SEE SPEAKER NOTE
4286 VIP MODULE
Figure 3-34: 4285/4286 VIP Module Connections
Installing the Audio Alarm Verification Module
Audio Alarm Verification (AAV) is not permitted
in UL installations.
UL
•
•
685 Receiver software must be rev. 4.6 or
higher. Earlier versions will not hold the
phone line connection.
Contact ID code for “Listen-in to Follow” is
606. Contact ID is the only reporting format
that will send a “Listen-in to Follow.”
NOTES:
•
When the AAV indicates that the audio alarm
verification session is completed, all keypad sounds
are restored. Sirens are restored if the alarm
timeout period has not expired.
•
As part of its fail-safe software, the control limits
all audio alarm verification sessions to 15 minutes.
This is because once the session begins, the AAV
Module controls the duration.
•
If a new Fire alarm should occur during a session,
the control breaks the phone connection and sends
the new Fire Alarm report, then re-triggers the
AAV Mode. All other dialer messages triggered
during ongoing conversation are held until either
the AAV Module signals that it is inactive, or the
15-minute timeout occurs.
To install the Eagle 1250 AAV module to the control,
perform the following steps:
Step
Action
1
Mount the module in the control cabinet if
space is available or, if this is not possible,
on the side of the cabinet or adjacent to it.
2
Connect the Eagle 1250 Module terminals 7
and 8 to the control’s zone 5 terminals 22
and 23.
The purpose of this connection is to silence
and restore the sounders at the premises. It
is also used to postpone noncritical dialer
reports while the AAV session is in progress.
Program zone 5 with a response type (e.g.,
10 Interior w/Delay). Field 1✴60 must be
enabled to silence sounders on the premises.
Zone 5 is no longer available as a protection
zone.
3
4
Connect the AAV module’s falling-edge
trigger input (terminal 5 on Eagle model
1250) to a 4204 relay module, as shown in
Figure 3-35.
Program the start and stop system operation
as 60 for the 4204 relay, in Output
Programming in the #93 Menu Mode.
If the phone plug is disconnected from the
control, the premise’s phones will not operate.
3-27
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising