FCM-1(A) - Control Fire Systems Ltd.
DN-6724:B3
FCM-1(A) & FRM-1(A)
Series
Control and Relay Modules
Intelligent / Addressable Devices
General
FCM-1(A) Control Module: The FCM-1(A) Addressable Control Module provides Notifier intelligent fire alarm control panels a circuit for Notification Appliances (horns, strobes,
speakers, etc.). Addressability allows the FCM-1(A) to be activated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay
Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers,
control equipment, etc. Addressability allows the dry contact to
be activated, either manually or through panel programming,
on a select basis.
7000cov.JPG
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater than
five times that of other designs.
FCM-1(A)
Features
• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire
SLC loop. The FCM-1(A) module requires power (for horns,
strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is
received from the control panel and turns on in steady red
when activated.
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI).
• The FCM-1(A) may be used to switch 24-volt NAC power,
audio (up to 70.7 Vrms).
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct-dial entry of address 01– 159 for FlashScan loops,
01 – 99 for CLIP mode loops.
• Speaker, and audible/visual applications may be wired for
Class B or A (Style Y or Z).
Applications
The FCM-1(A) is used to switch 24 VDC audible/visual power,
high-level audio (speakers). The FRM-1(A) may be programmed to operate dry contacts for applications such as door
holders or Air Handling Unit shutdown, and to reset four-wire
smoke detector power.
• The FCM-1(A) is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
• The FRM-1(A) provides two Form-C dry contacts that
switch together.
Operation
Each FCM-1(A) or FRM-1(A) uses one of 159 possible module
addresses on a SLC loop (99 on CLIP loops). It responds to
regular polls from the control panel and reports its type and
status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll
received. On command, it activates its internal relay. The
FCM-1(A) supervises Class B (Style Y) or Class A (Style Z)
notification or control circuits.
Upon code command from the panel, the FCM-1(A) will disconnect the supervision and connect the external power supply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication
to the panel that the control relay actually turned ON. The
external power supply is always relay isolated from the communication loop so that a trouble condition on the external
power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE (not settable) will identify the module to the control panel, so as to differentiate between a module and a sensor address.
NOTE: Refer to the SLC Manual (PN 51253) for details regarding
releasing applications with the FCM-1(A). Refer to the FCM-1-REL
datasheet (DN-60390) for new FlashScan® releasing applications.
Specifications for FCM-1(A)
Construction
Maximum current draw: 6.5 mA (LED on).
• The face plate is made of off-white heat-resistant plastic.
• Controls include two rotary switches for direct-dial entry of
address (01-159).
Average operating current: 350 μA direct poll, 375 μA group
poll with LED flashing, 485 μA Max. (LED flashing, NAC
shorted.)
Normal operating voltage: 15 to 32 VDC.
DN-6724:B3 • 2/17/2011 — Page 1 of 2
Maximum NAC Line Loss: 4 VDC.
External supply voltage (between Terminals T10 and
T11): Maximum (NAC): Regulated 24 VDC; Maximum
(Speakers): 70.7 V RMS, 50W.
Drain on external supply: 1.7 mA maximum using 24 VDC
supply; 2.2 mA Maximum using 80 VRMS supply.
Max NAC Current Ratings: For class B wiring system, the
current rating is 3A; For class A wiring system, the current rating is 2A.
Temperature range: 32°F to 120°F (0°C to 49°C).
Contact Ratings for FRM-1(A)
Current
Rating
Maximum
Voltage
30 VDC
Resistive
Non-Coded
2A
30 VDC
Resistive
Coded
.9 A
110 VDC
Resistive
Non-Coded
.9 A
125 VDC
Resistive
Non-Coded
.5 A
30 VDC
Inductive
(L/R=5ms)
Coded
1A
30 VDC
Inductive
(L/R=2ms)
Coded
.3 A
125 VAC
Inductive
(PF=0.35)
Non-Coded
1.5 A
25 VAC
Inductive
(PF=0.35)
Non-Coded
.7 A
70.7 VAC
Inductive
(PF=0.35)
Non-Coded
2A
25 VAC
Inductive
(PF=0.35)
Non-Coded
Accessories: SMB500 Electrical Box; CB500 Barrier
Specifications for FRM-1(A)
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 230 μA direct poll; 255 μA group
poll.
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 49°C).
Application
3A
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Load
Description
NOTE: Maximum (Speakers): 70.7 V RMS, 50 W
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest listing status.
•
•
•
•
•
•
UL: S635
ULC: S3705 (A version only)
FM Approved
CSFM: 7300-0028:0219
MEA: 14-00-E
FDNY: COA #6067, #6065
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FCM-1(A): Intelligent Addressable Control Module.
FRM-1(A): Intelligent Addressable Relay Module.
A2143-20: Capacitor, required for Class A (Style Z) operation
of speakers.
SMB500: Optional Surface-Mount Backbox.
CB500: Control Module Barrier — required by UL for separating power-limited and non-power limited wiring in the same
junction box as FCM-1(A).
NOTE: For installation instructions, see the following documents:
• FCM-1(A) Installation document I56-1169.
• FRM-1(A) Installation document I56-3502.
• Notifier SLC Wiring Manual, document 51253.
Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6724:B3 • 2/17/2011
DN-60390:B • H-235
FCM-1-REL(A)
Releasing Control Module
Intelligent/Addressable Devices
General
The FCM-1-REL Releasing Control Module is specifically
designed for fire suppression releasing applications in FlashScan® systems. Power to the release agent solenoid(s) runs
through the module for full-time monitoring and supervision.
NOTE: FCM-1-REL is required for all new FlashScan-mode
releasing applications with NFS2-3030 (version 14.0 or higher),
NFS2-640 (version 12.0 or higher) and NFS-320(E)(C) (version
12.0 or higher) panels. Use FCM-1 for releasing applications on
NFS-640, NFS-3030, and all CLIP mode panels.
Features
•
•
•
•
•
•
•
•
•
•
•
Redundant protocol for added protection
Configurable for Class A or Class B operation
External supply voltage monitoring
Can power one 24V or two 12V solenoids
SEMS screws for easing wiring
Panel controlled status LED
Analog communications
Rotary address switches
Low standby current
Mounts in standard 4" (10.16 cm) junction box
FlashScan operation
Specifications
GENERAL SPECIFICATIONS
• Operating Voltage: 15 to 32 VDC
• Communication Line Loop Impedance: 40 Ohm max.
• Temperature Range: 14°F to 140°F (-10° to 60°C)
• Relative Humidity: 10% to 95% noncondensing
• Shipping Weight: 5.5 oz (156 g)
• Dimensions: 4.275" W × 4.675" H × 1.400" D
(10.86 cm W × 11.87 cm H × 3.56 cm D)
60390cov.jpg
The FCM-1-REL Releasing Control Module uses a redundant protocol; the module must be armed with a pair of signals in order to activate. It will then enter a 3-second window
awaiting a pair of confirmation signals. If no confirmation is
received, the module will automatically reset. It also supervises the wiring to the connected load and reports the status
to the panel as NORMAL, OPEN, or SHORT CIRCUIT. The
module has two pairs of output termination points available
for fault-tolerant wiring and a panel-controlled LED indicator.
The module may be connected to either one 24VDC solenoid
or up to two 12VDC solenoids (in series). To ensure proper
operation, this module shall be connected to a compatible
Notifier system control panel only (list available from Notifier).
In addition, please refer to Notifier Device Compatibility Document PN 15378 for the list of compatible solenoids.
FCM-1-REL
EXTERNAL SUPPLY
• Normal Operating Voltage: 24 VDC Nominal
• Maximum Line Loss: 2.3 VDC (total allowable loss from
power supply to module and from module to solenoid)
• Minimum Operating Voltage to Activate Solenoid:
18 VDC (at solenoid)
• Standby Current: 6.4 mA
• Activation Current: 10 mA
SOLENOID
• Supervisory Loop Voltage: 3.3 V
• Supervisory Loop Current (Normal): 30 mA
• Maximum Activation Current: 2 A
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FCM-1-REL(A): Releasing Control Module.
SMB500: Optional Surface-Mount Backbox.
CB500: Control Module Barrier — required by UL for separating power-limited and non-power limited wiring in the
same junction box as FCM-1-REL.
SLC
• Average Operating Current: 700 µA max @ 24 VDC
(one communication every 5 sec. with LED enabled)
• Maximum Activation Current: 9.0 mA (LED on)
DN-60390:B • 05/20/2009 — Page 1 of 2
Agency Listings and Approvals
These listings and approvals apply to the modules specified
in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listings may be in process. Consult factory for latest listing
status.
•
•
•
•
UL Listed: S635
ULC Listed: (FCM-1-RELA)
FM Approved
CSFM: 7300-0028:249
Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-60390:B • 05/20/2009
DN-6720:C • H-220
FMM-1(A), FMM-101(A),
FZM-1(A) & FDM-1(A)
Monitor Modules with FlashScan®
Intelligent/Addressable Devices
General
Four different monitor modules are available for Notifier’s intelligent control panels for a variety of applications. Monitor modules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1(A)).
FMM-1(A) is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Style D (Class
A) or Style B (Class B) circuit of dry-contact input devices.
FMM-101(A) is a miniature monitor module a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices.
Its compact design allows the FMM-101(A) to be mounted in a
single-gang box behind the device it monitors.
FDM-1(A) is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class
B) dry-contact initiating device circuits (IDCs) at two separate,
consecutive addresses in intelligent, two-wire systems.
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER that greatly increases the speed
of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other designs.
FMM-1(A) Monitor Module
• Built-in type identification automatically identifies this device
as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power
required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
• LED flashes green during normal operation (this is a programmable option) and latches on steady red to indicate
alarm.
The FMM-1(A) Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1(A) can be used to replace MMX-1(A)
modules in existing systems.
6999cov.jpg
FZM-1(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style
D (Class A) or Style B (Class B) circuit.
FMM-1(A) (Type H)
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
FMM-1(A) OPERATION
Each FMM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limitations on the loop).
FMM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 μA (LED flashing), 1 communication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
FMM-1(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normallyopen dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
DN-6720:C • 10/06/2010 — Page 1 of 4
FMM-101(A) Mini Monitor Module
• Built-in type identification automatically identifies this device
as a monitor module to the panel.
• Powered directly by two-wire SLC loop. No additional power
required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
FZM-1(A) Interface Module
6720m101.wmf
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power
source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops,
01 – 99 on CLIP loops.
• LED flashes during normal operation; this is a programmable option.
• LED latches steady to indicate alarm on command from
control panel.
The FZM-1(A) Interface Module is intended for use in intelligent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor twowire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The FZM-1(A)
can be used to replace MMX-2(A) modules in existing systems.
FZM-1(A) APPLICATIONS
The FMM-101(A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The FMM-101(A) is intended for use in intelligent,
two-wire systems where the individual address of each module
is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm and
security devices. The FMM-101(A) can be used to replace
MMX-101(A) modules in existing systems.
FMM-101(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterflow devices, or
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
A 47K ohm End-of-Line Resistor (provided) terminates the circuit.
Use the FZM-1(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B
(Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K
ohm End-of-Line Resistor (provided) terminates the end of the
Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for
Style D application.
FZM-1(A) OPERATION
Each FZM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limitations on the loop).
FZM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
FMM-101(A) OPERATION
Maximum current draw: 5.1 mA (LED on).
Each FMM-101(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC).
Maximum IDC wiring resistance: 25 ohms.
FMM-101(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 μA, 1 communication every
5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC
Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 μA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Page 2 of 4 — DN-6720:C • 10/06/2010
Average operating current: 300 μA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
FDM1(A) Dual Monitor Module
– 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1)
– 161.002/42/1 (NFS-640: FMM-1/-101)
• Lloyd’s Register:
– 03/60011/E1 (FMM-1/-101, FZM-1)
– 94/60004/E2 (AFP-200: except FDM-1)
– 02/60007 (NFS-640: FDM-1)
• FDNY: COA #6038 (NFS2-640, NFS-320), COA# 6058
(NFS2-3030)
The FDM-1(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices; or either normally open or normally closed security devices. The module has a single panelcontrolled LED.
NOTE: The FDM-1(A) provides two Style B (Class B) IDC circuits
ONLY. Style D (Class A) IDC circuits are NOT supported in any
application.
Product Line Information
FDM-1(A) SPECIFICATIONS
NOTE: “A” suffix indicates ULC-listed model.
Normal operating voltage range: 15 to 32 VDC.
FMM-1(A): Monitor module.
Maximum current draw: 6.4 mA (LED on).
FMM-101(A): Monitor module, miniature.
Average operating current: 750 μA (LED flashing).
FZM-1(A): Monitor module, two-wire detectors.
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
FDM-1(A): Monitor module, dual, two independent Class B circuits.
Maximum IDC Current: 240 μA
SMB500: Optional surface-mount backbox.
EOL resistance: 47K ohms.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51253.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
FDM-1(A) AUTOMATIC ADDRESSING
The FDM-1(A) automatically assigns itself to two addressable
points, starting with the original address. For example, if the
FDM-1(A) is set to address “26”, then it will automatically
assign itself to addresses “26” and “27”.
NOTE: “Ones” addresses on the FDM-1(A) are 0, 2, 4, 6, or 8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.
!
CAUTION:
Avoid duplicating addresses on the system.
Installation
FMM-1(A), FZM-1(A), and FDM-1(A) modules mount directly
to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep,
electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform
to applicable local codes, ordinances, and regulations. These
modules are intended for power-limited wiring only.
The FMM-101(A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest listing status.
•
•
•
•
•
•
UL: S635
ULC: S635
FM Approved
CSFM: 7300-0028:0219
MEA: 457-99-E
U.S. Coast Guard:
DN-6720:C • 10/06/2010 — Page 3 of 4
FlashScan® and NOTIFIER® are registered trademarks and FireWatch™ is
a trademark of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4 — DN-6720:C • 10/06/2010
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising