Owner`s Manual

Owner`s Manual

Owner’s Manual
Revision 4.01 Option 1
Special Version of the
SW series Inverter / Charger
for Motor Coach Applications
Trace Engineering Company, Inc.
5916 - 195th Street N.E.
Arlington, WA 98223
TEL (360) 435 - 8826
FAX (360) 435 - 2229
Part # 2031-7 (Supplement to Normal Manual)
Effective Date: April 17, 1996
Trace Engineering SW Series Inverter/Charger
-
REV 4.01 Option 1 -
4/22/96 - Page 2
Motor Coach Software (Revision 4.01 Option 1)
Notes on Changes
The Motor Coach software for the Trace Engineering SW series Inverter/Charger has been specifically
developed to meet the operational requirements of vehicle applications. The new software includes
several changes to the inverter/charger’s basic operation in addition to changes to the default settings.
The Motor Coach version is an option for the new Revision 4.01 software, introduced in April of 1996 on
all of the SW series. It is available in 12 VDC and 24 VDC versions.
The changes can be divided into two groups - changes to the basic operation and changes to the default
settings. Both groups should be examined together with the changes made in the new Rev. 4.01 software
compared to the previous Rev. 3.0 software. Some additional user programming of the inverter and
charger settings may be required for your application.
Important Revision 4.01 Changes
The new Rev 4.01 software includes many improvements and new abilities. The most substantial
changes for Motor Coach applications are summarized here. A copy of the new Revision 4.01 manual
should be reviewed for more information on these and other changes.
•
Menu System - The new Rev 4.01 software divides the menu system into two parts - a USER menu
and a SETUP menu. This simplifies the menu system for the system user and reduces problems with
accidental changes to the inverter/charger settings.
•
Generator Start System - The new Rev 4.01 software now includes two different start routines. The
system itself has been made more fault tolerant and has additional error indications.
•
Control Panel Operation - The red and green buttons now also are able to select the desired setting
from the menu item displayed. The “action” of the buttons has been improved. The “reset to factory
default button” now can be used to reset the display. This button now only resets the default settings
from a specific menu item location.
Important Operational Changes for the Motor Coach Version
The Motor Coach version includes several changes in the basic operation of the inverter from the
standard operation of the Rev 3.0 and Rev 4.01 software previously shipped.
•
AC2 Priority - The AC2 input (generator) is now the priority. If the AC1 (grid) is energized from the
shore cord being plugged in, then it will be disconnected when the generator is started. The transfer
from shore cord to generator may take 8 seconds or more. (The terminal block on the inverter still
lists AC1 as the priority - the change was made in the software only for the Motor Coach version.)
•
No Cool Down - The Rev 4.01 software includes a cool-down period for the generator after it was
operated. This is not included in the Motor Coach software.
Trace Engineering SW Series Inverter/Charger
-
REV 4.01 Option 1 -
4/22/96 - Page 3
Important Default Setting Changes for the Motor Coach Version
The Motor Coach version includes several changes to the default setting of the Rev 4.01 software. Any
unnecessary menu headings have also been eliminated to reduce the complexity of the menu system.
•
Shore Cord Size - A new menu item, SET SHORE CORD AMPS AC, has been included in the
USER menu under the SET INVERTER (1) menu heading to allow adjustment of the SET GRID
(AC1) AMPS AC menu item in the SETUP menu. This makes it easier for the user to change the
setting based on the hook-up capacity. It should be set to match the shore cord being used by the
coach user when connecting the coach to utility power.
•
Battery Charging - The software is programmed to have the default settings be appropriate with
sealed gel cell or AGM type batteries. The equalization system has been defeated.
•
Generator Starting - The software defaults to a new generator start routine designed for use with
Onan and many diesel generators. See the Rev 4.01 manual for more information. The warm-up
period for the generator has been reduced to 16 seconds. The exercising system has been disabled.
•
Low Battery Cut Out - The default settings have been changed to allow greater use of the batteries.
The LBCO setting is now also used by the generator start system to signal the generator to start if the
battery reaches the LBCO setting for 30 seconds continuously.
Identification and Compatibility
The Motor Coach version can be identified by checking for the REVISION 4.01 OPTION 1 menu item
display under the TRACE ENGINEERING (3) menu heading. This assures that the inverter includes the
new software.
The Motor Coach software is compatible with all SW series inverter/chargers built by Trace Engineering.
The software must be configured for the DC input and AC output voltage involved before the “chips” are
programmed. To change the software, the cover of the inverter must be removed and the top needs
good access. This may require removal of the inverter/charger from the vehicle.
Series II Inverter/Chargers
The Motor Coach version also includes changes to the inverter/charger itself. All currently manufactured
units now include:
•
Series II Chassis - A new chassis is being used on all SW series inverter/chargers. It features
improved AC wiring access and a easier to remove cover for upgrading software.
•
High Visibility Display - The LCD display now is backlit and has greater visibility from the sides and
below.
•
Larger AC Input Contactors - The relays which connect the generator or utility grid ac sources to the
inverter have been changed to a larger, heavier duty relay. This change has eliminated the problem
with stuck relays previously encountered.
AC Input Provisions and Ground Bonding
Neither the Motor Coach version or the standard version of the SW series inverter/charger includes
ground switching or bonding. This must be added externally to the inverter/charger.
DO NOT CONNECT BOTH THE GENERATOR AND THE UTILITY GRID TO THE SAME AC INPUT
TERMINALS - THIS IS NOT ACCEPTABLE A WILL VOID THE WARRANTY IF FOUND. The SW
series includes two AC inputs - each must be used as intended.
Trace Engineering SW Series Inverter/Charger
ON /OFF MENU
Set Inverter
OFF SRCH ON CHG
GEN MENU
Set Generator
OFF AUTO ON EQ
-
User Menu
-
REV 4.01 Option 1 -
4/22/96 - Page U1
This button provides direct access to the SET INVERTER menu item from anywhere in the user menu.
Pressing this red button again selects the next setting to the right, as indicated by the position of the
cursor under the first letter. You can also use the SET POINT buttons to move the cursor right or left.
This button provides direct access to the SET GENERATOR menu item from anywhere in the user menu.
Pressing this green button again selects the next setting to the right, as indicated by the position of the
cursor under the first letter. You can also use the SET POINT buttons to move the cursor right or left.
MENU HEADINGS
Inverter Mode
2
1
Set Inverter
OFF SRCH ON CHG
Set Shore Cord
Size Amps AC 50
CHG avail. Only
in FLT mode.
Press red or
setpoint button
to move cursor.
Move cursor to
Inverter OFF to
resetOverCurrent
Set Generator
OFF AUTO ON EQ
Gen under/over
speed
NO
Generator start
error
NO
Generator sync
error
NO
Gen max run time
error
NO
Load Amp Start
ready
Voltage Start
ready
Exercise Start
ready
Move cursor to
GEN OFF to reset
generator error.
If no start in 5
trys then error.
If Gen starts &
runs for 5 min
MENU
ITEMS
then stops the
inverter will
not attempt
restart until
Gen auto start
conditions are
again satisfied.
If Gen runs for
more than max
run time then
error.
Trace
Engineering
Meters
Error Causes
3
4
5
Press reset now
for defaults
Inverter/charger
amps AC
00
Over Current
Revision 4.01
Option 1
Input
amps AC
00
5916 195th St NE
Arlington, WA
Load
amps AC
00
98223 USA
Ph 360-435-8826
Fax 360-435-2229
Time of Day
00:00:00
6
Generator Timer
7
NO
Set Clock hour
00:00:00
Start Quiet
time h:m 08:00
Transformer
overtemp
NO
Set Clock minute
00:00:00
End
time
Heatsink
overtemp
NO
Set Clock second
00
Gen doesn’t run
during quiet
Battery actual
volts DC
25.2
High Battery
voltage
NO
time unless batt
volts is less
Battery TempComp
volts DC
25.2
Low Battery
voltage
NO
than LBCO volts
for 30 seconds
Inverter
volts AC
00
AC source wired
to output
NO
To defeat timers
set start = end.
Grid (AC1)
volts AC
00
External error
(stacked)
NO
If exercise days
set to 1 then
Generator (AC2)
volts AC
00
Generator start
error
NO
gen will always
start @ endquiet
Read Frequency
Hertz
60
Generator sync
error
NO
AC1 & AC2 volts
valid only when
Gen max run time
error
NO
inverter synced
to that input.
Gen under/over
speed
NO
Batt volt actual
is used for
Inverter breaker
tripped
NO
Quiet
h:m 08:00
END USER MENU
8
LBCO,HBCO,LBX,
LBCI,sell volts
and gen starting
Batt volt temp
comp is used for
float,bulk,eq &
aux relays
Menu Heading
Menu Item
Setpoint
Values shown are
defaults for 24 vdc
120 vac / 60 Hz
models
Information
Under/Over speed
will cause a
sync error in 10
minutes.
REVMCUS..DOC
Generator Mode
Trace Engineering SW Series Inverter/Charger - Setup Menu - REV 4.01 Option 1 - 4/17/96 - Page S1
To access the Setup Menu, press the RED and GREEN buttons at the same time. To exit the Setup Menu, press the red
ON/OFF MENU button or use the down MENU HEADING button until you reach the User Menu (menu headings 1 - 8).
MENU HEADINGS
Inverter Setup
Gen Auto Start
setup
12
Gen starting
details
13
Auxiliary Relays
R9 R10 R11
14
Set Grid (AC1)
amps AC
50
Set Load Start
amp AC
33
Set RY7 Function
GlowStop Run
Set Relay 9
volts DC
29.0
Set Absorption
time h:m
02:00
Set Gen (AC2)
amps AC
30
Set Load Start
delay min
5.0
Set Gen warmup
seconds
16
R9 Hysteresis
volts DC
02.0
Set Low battery
cut in VDC 23.0
Set Float
volts DC
27.6
Set Input lower
limit VAC
105
Set Load Stop
delay min
5.0
Set Pre Crank
seconds
10
Set Relay 10
volts DC
29.5
Set High battery
cut out VDC 30.0
Set Equalize
volts DC
28.4
Set Input upper
limit VAC
132
Set 24 hr start
volts DC
24.6
Set Max Cranking
seconds
10
R10 Hysteresis
volts DC
02.0
Set search
watts
48
Set Equalize
time h:m
00:10
Set 2 hr start
volts DC
23.6
Set Post Crank
seconds
30
Set Relay 11
volts DC
30.0
Set search
spacing
59
Set Max Charge
amps AC
15
Set 15 min start
volts DC
22.6
R11 Hysteresis
volts DC
02.0
Set Temp Comp
LeadAcid NiCad
Read LBCO 30 sec
start VDC
20.0
close on batt
>setpoint
Set Exercise
period days
00
open on batt
<setpoint - Hys
Set Maximum run
time h:m
08:00
relays have 2
second delay on
Set Max Run time
to 0 to defeat
close, 0.1 sec
delay on open
Battery Charging
10
AC Inputs
Set Low battery
cut out VDC 20.0
Set Bulk
volts DC
28.4
Set LBCO delay
minutes
5
9
11
Set Exercise to
0 to defeat
Menu Heading
Menu Item
Setpoint
Information
Values shown are
defaults for 24 vdc
120 vac 60 Hz
models
MENU
ITEMS
REVMCSU.DOC