Victron MultiPlus Compact Installation Manual
DATA SHEET |
DECLARATION OF CONFORMITY | INSTALLATION MANUAL
Advanced Battery Back-Up Systems
VICTRON MULTIPLUS INVERTERS
MultiPlus Compact 12/800/35 & 12/1200/50
Rev 1.0 - 17 June 2014
PRODUCT CODE - BB1 & BB2
NEWTON
SYSTEM 500
© Newton Waterproofing Systems
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
© Newton Waterproofing Systems
2
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
CONTENTS
Warranty Statement
Page 3
Dimensions
Page 3
Information
Page 4
Safety Instructions
Page 4
Inverter Sizing
Page 5
Introduction
Page 5
Installation
Page 6
Quick Install Guide
Page 9
Optional Connections
Page 9
Configuration
Page 10
Battery Selection
Page 10
Operation
Page 10
Maintenance
Page 10
Technical Data
Page 10
Trouble Shooting
Page 11
DIMENSIONS
375mm high x 214mm wide x 110mm deep. Weight - 10kg
WARRANTY STATEMENT
The Victron Inverter/Chargers are covered by a 2-year warranty. Warranty includes next-day on-site replacement
(delivery and collection, not decommission and installation) of the Inverter/Charger units by a temporary
replacement of the same model. If the warranty claim is upheld, this temporary unit will be exchanged with
a new unit. If the warranty claim is not upheld, the client must decide the course of action, which will include
purchase of a new replacement unit, purchase of the temporary replacement unit or return of the original unit.
Limited Product Warranties: 2-year limited product warranty from date on delivery note or invoice to the customer.
What is covered by this limited hardware warranty?
This limited warranty covers replacement (Newton Waterproofing Systems) only for defects in materials and
workmanship.
What is not covered by this limited hardware warranty?
• Products the supplier has not received payment for
• Normal wear & tear
• Failure to follow product installation instructions and user instructions
• Usage that is not in accordance with the product instructions
• Servicing not authorised by the manufacturer
• Problems caused by connecting devices not supplied or authorised by the manufacturer
Warranty Information
This warranty gives you specific legal rights, and you may also have other rights which may vary from area to area
(or jurisdiction to jurisdiction). The manufacturer’s responsibility for malfunctions and defects in the product is
limited to repair and replacement as set forth in this warranty statement. All expressed and implied warranties for
the product, including but not limited to any implied warranties and conditions of merchantability and fitness for
a particular purpose, are limited in time to the term of the limited warranty which is the 2-year period reflected on
your delivery note or invoice. No warranties, whether expressed or implied, will apply after the limited warranty
period has expired.
We do not accept liability beyond the remedies provided for in this limited product warranty or for consequential
or incidental damages, including without limitation, any liability for third-party claims against you, for damages for
products not being available for use. Our liability will be no more than the amount you paid for the product that is
the subject of a claim. This is the maximum amount for which we are responsible. Newton Waterproofing Systems
reserve the right to change the product specification at any time.
© Newton Waterproofing Systems
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
3
INFORMATION
This Installation Manual is written by Newton Waterproofing Systems specifically for the use of the Victron Inverter
Charger units used with Newton Pumping Systems to ensure continued pumping during power outages. The original
Victron Installation Manual may be used for reference but contains no specific information on the use of the unit as a
Newton Battery Back-up System and does mention uses that are not applicable to the Newton System and so may be
confusing when read in isolation.
SAFETY INSTRUCTIONS
General
Please familiarise yourself with the safety features and instructions by first reading this document before using the
equipment. This product has been designed and tested in accordance with international standards. The equipment must
be used exclusively for the purpose for which it was designed.
WARNING: ELECTRIC SHOCK HAZARD.
The product is used in conjunction with wall mains, a permanent energy source (battery). Input and/or output terminals
may still be dangerously energized, even when the equipment is switched off. ALWAYS SWITCH OFF THE AC IN SUPPLY
AND DISCONNECT FROM MAINS AND BATTERY WHEN INSTALLING, MAINTAINING OR SERVICING THIS SYSTEM.
The product has no internal user-serviceable components. Do not remove the front plate or operate the product if any
panels have been removed. All servicing must be undertaken by qualified personnel.
Never use the product where there is a risk of gas or dust explosions. Consult the battery manufacturer’s information
to ascertain that the product is intended for use in conjunction with the battery. Always comply with the battery
manufacturer’s safety instructions.
WARNING: Do not lift heavy loads without assistance.
Installation
Read these installation instructions in full before installing the equipment. This is a Safety Class I product (supplied with
a protective grounding terminal for safety purposes). Uninterrupted protective grounding must be provided at the
AC input and/or output terminals. Alternatively the grounding point located externally on the product may be used.
Whenever it is likely that the grounding protection has been damaged, the product must be turned off and secured
against unintended operation; please contact qualified service staff.
Ensure that the DC and AC input cables are fused and fitted with circuit breakers. Never replace a safety component with
a different type.
Before applying power, ensure that the available power source matches the configuration settings of the product. This
manual is to be used with the Victron MultiPlus 12/800/35 & 12/1200/50. 12/xxxx/xxx denotes the charging volts - use
with 12V batteries only. xx/800 or 1200/xx denotes the AC output capacity in VA. xx/xxxx/35 or 50 denotes the charging
current in Ah.
Ensure that the equipment is used under the correct ambient conditions (refer to data sheet for unit temperature
operating parameters). Never operate the product in a wet or dusty environment. Ensure there is adequate free
space for ventilation around the product and check that the ventilation vents are not blocked.
Ensure that the required system voltage does not exceed the product’s capacity.
Transport and Storage
Ensure that the mains power and battery leads have been disconnected before storing or transporting the
product.
No liability can be accepted for any transport damage if the equipment is shipped in non-original packaging.
Store the product in a dry environment; the storage temperature must be between -20°C and 60°C.
Consult the battery manufacturer’s manual in respect of transport, storage, charging, recharging and disposal of
the batttery(s) and ancillary products.
© Newton Waterproofing Systems
4
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
IMPORTANT - INVERTER SIZING
This Installation Manual is for the Victron MultiPlus Compact Inverter/Charger units 12/800/35 & 12/1200/50.
The maximum pump size that can be connected to these units is:
12/800/35 - 250W - Newton Pumps NP150 & CP250
12/1200/50 - 400W - Newton Pumps CP400, NP400 and NP400W
For confirmation of the correct size of Inverter for the Newton pump being used please refer to the Victron
Inverters Data Sheet.
INTRODUCTION
The Victron range of Inverter/Chargers provide advanced solutions to ensure that Newton Pumping Systems
continue pumping during power interruption by inverting 12V DC power from a battery (or multiple batteries) to
clean and efficient 230V power.
The MultiPlus Compact is a powerful pure sine wave inverter, a sophisticated battery charger that features adaptive
charge technology and a high-speed AC transfer switch in a single compact enclosure.
Below is a typical setup as part of a Newton System 500 waterproofing system which can be used as a quick install
schematic. If a control panel is not used the pumps will be automatic versions and each pump will have just one
cable coming up from the conduit. Connect pump 1 directly to the mains and pump 2 to the MultiPlus Compact.
Example 1 - 2 x Automatic Pumps - No Pump Control Panel - No Inverter/Charger Control Panels
© Newton Waterproofing Systems
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
5
Example 2 - 2 x Manual Pumps - Pump Control Panel - No Inverter/Charger Control Panels
INSTALLATION
The Inverter/Charger units are mains powered and should be installed by persons who are electrically competent by
way of appropriate training to either fit a fused plug or wire directly to a fused spur. Knowledge of DC input by battery
and the connection of DC batteries leads to both the battery(s) and the Inverter/Charger is required.
The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a
clear space of at least 100mm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
•
•
•
Reduced service life.
Reduced charging current.
Reduced peak capacity, or shutdown of the inverter.
The unit must be installed in a vertical position. Never mount the appliance directly above the batteries.
© Newton Waterproofing Systems
6
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
Example 3- 2 x Automatic Pumps - 1 x Pump Control Panels - 1 x Inverter/Charger Control Panels - 1 x
Battery Monitor Module
Positioning
NOTE: ALL POWER INVERTERS NEED TO BE INSTALLED INTERNALLY IN A DRY AND WELL VENTILATED SPACE
• The product is suitable for wall mounting.
• Do not place the battery directly below the MultiPlus Compact
• The appliance can be mounted horizontally as well as vertically; vertical mounting is preferable. The vertical
position offers optimum cooling.
• Please note: All aspects of the installation must be done without AC being connected to mains until all
components of the system have been installed.
• The interior of the product must remain accessible after installation.
• Use only the DC cables supplied with the unit to minimize cable voltage losses.
• For safety purposes, this product should be not be installed close to chemicals, synthetic components,
curtains or other textiles, etc.
© Newton Waterproofing Systems
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
7
Fixing to the wall
Fix the provided blue top fixing bracket to the wall via the 3 pre-drilled drilled holes. Screws are provided. It is
important to fix the bracket level. Attach the MultiPlus to the top support bracket using the lugs on the rear
of the unit. Complete the fix by screwing the bottom of the MultiPlus to the wall via the bottom 2 holes using
the screws provided. Carefully mark out the hole centres then take the MultiPlus off the wall to drill the holes.
Note: Rawl plugs will be required for the screws for certain wall types (not supplied).
CONNECTION OF BATTERY CABLES
Use an insulated box spanner in order to avoid shorting the battery. Avoid shorting the battery cables.
Connect the battery cables: the + (red) and the - (black), to the battery. Reverse polarity connection (+ to – and – to +)
will cause damage to the product and will void the warranty.
Secure the nuts tightly in order to reduce the contact resistance as much as possible.
n
T-SENSE
+
-
CH-COM-IN
REMOTE SWITCH
NO COM NC
Pre-wired
MultiPlus Compact 12/800/35
MultiPlus Compact12/1200/50
(Battery cables pre-connected)
STEP 4. STEP 7.
AC
IN
AC
OUT
STEP 3. STEP 6.
Connect to negative battery terminal
Pre-wired
Pre-wired
Black
Red
Pump (Automatic) or Control panel (Manual)
Mains
ofing detail. For the design of the structure, please use a professional designer. We strongly recommend that Newton waterproofing systems are installed by our NSBC registered contractors who will guarantee, insure and accept liability for both the de
of our systems Please refer to product data sheets before installation of our products. John Newton reserves the right to update drawings.
NEWTON
Waterproofing Systems

17 - 19 Sovereign Way, Tonbridge, TN9 1RH
Tel: 01732 360095 Fax: 01732 359033
www.newton-membranes.co.uk - sales@newton-membranes.co.uk
© Newton Waterproofing Systems
8
Scale
Ref
Not to scale
MultiPlus 800 & 1200
Date
Designed by
14/05/2014
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
AJB
Drawn by
AJB
CONNECTION OF THE AC CABLING
This is a Safety Class I product (supplied with a protective grounding terminal). Uninterrupted protective grounding
must be provided at the AC input and/or output terminals and/or chassis grounding point located externally on the
product.
The MultiPlus Compact is provided with a ground relay that automatically connects the Neutral output to the chassis
if no external AC supply is available. If an external AC supply is provided, the ground relay H will open before the input
safety relay closes. This ensures the correct operation of an earth leakage circuit breaker that is connected to the output.
An uninterrupted grounding can also be secured by means of the grounding wire of the AC input. Otherwise the casing
must be grounded.
The mains input & output terminal connector can be found on the bottom of the MultiPlus Compact. The mains
cable must be connected to the connector with a three-wire cable. Use correctly rated cable.
Procedure
Proceed as follows to connect the AC cables:
The AC output cable is connected directly to the male-connector, (the connector pulls out). The terminal points
are indicated clearly. From left to right: “N” (neutral), earth, and “L1” (phase).
The AC input is connected directly to the female-connector, (the connector pulls out). The terminal points are
indicated clearly. From left to right: “L1” (phase), earth, and “N” (neutral).
Push the “input” connector into the AC-in connector (near to rear-side).
Push the “output” connector into the AC-out connector (near to front-side).
QUICK INSTALL GUIDE
The steps in bold are indicated on the figure on page 8.
1. Screw the top bracket to a suitably strong substrate using the screws provided. Rawl plugs will be required
for the screws for certain wall types (not supplied).
2. Place unit onto the bracket using the lugs to the rear of the unit. Screw the bottom of the unit to the wall.
3. Remove the left (AC IN) wiring block from the base of the inverter.
4. Wire AC IN with correctly rated mains cable. Add 3-pin mains plug or wire to a switched fused spare,
both of which should be fitted with a 13amp fuse. Do not plug in or turn on at the spur at this stage.
5. Plug in the AC IN wiring block back into the AC IN socket.
6. Remove the right (AC OUT) wiring block from the base of the inverter.
7. Wire AC OUT with correctly rated mains cable from either a Newton automatic pump, or from the
‘pump 2’ connection of the CP2 or CP9 control panel
8. Plug in the AC OUT wiring block back into the AC OUT socket.
9. Connect the black battery cable and the temperature sensor cable to the negative terminal on the battery.
10. Connect the red battery cable to the positive terminal on the battery.
11. The system will start running off the batteries.
12. Plug the AC IN into mains power or switch on the fused spur.
OPTIONAL CONNECTIONS
A number of optional connections are possible:
Undo the four screws at the front of the enclosure and remove the front panel.
NOTE: ALL 230v & 12V POWER must be fully isolated and turned off prior to removing the cover of this unit. ONLY
TECHNICALLY COMPETENT AND TRAINED technicians should alter and install any additional products features to
the unit.
Temperature Sensor
The temperature sensor supplied with the product may be used for temperature-compensated charging. The sensor is
insulated and must be mounted on the batteries negative terminal. Default output voltages for Float and Absorption are
at 25°C. In adjust mode temperature compensation is disabled. The Temperature Sensor is pre-wired as shown on the
wiring diagram on page 8.
© Newton Waterproofing Systems
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
9
VICTRON BMV600S BATTERY MONITOR
The BMV600S provides real time information for the battery or bank of multiple batteries:
• Battery voltage
• Discharge current
• Capacity as a %
Please refer to product installation manual.
VICTRON BLUE POWER PANEL
The Blue Power Panel provides control and monitoring of the Victron Inverter/Charger. Features include on/off
control of MultiPlus Inverter/Charger units and graphic illustration of system charge/discharge, capacity in % real
time and time to go until discharged. Please refer to product installation manual.
VICTRON COLOR CONTROL PANEL
The Color Control Panel adds a number of extra features over the Blue Power Panel such as Ethernet or Sim Card
internet capability with remote monitoring via web portal and data storage on SD card. Please refer to product
installation manual.
CONFIGURATION
•
•
•
Settings should be carried out by a competent person
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during charging and not directly below the
MultiPlus.
Standard settings: ready for use
On delivery, the MultiPlus Compact is set to standard factory values ready for use as part of a Newton Pumping
System with charging voltages set for the three batteries supplied by Newton Waterproofing Systems for use
within power supplies of 230V input voltage and 50Hz frequency. Inverter output voltage is set to 230V AC.
There is no need to change any of the default settings for use within the UK.
BATTERY SELECTION
The following batteries have been selected to be used with the MultiPlus Compact Inverter/Charger units:
• ABX-AGM M31-800 - 90Ah Deep cycle battery - 12V - Purchase code B20
• Odyssey PC2150 - 100Ah Extra long life battery - 12V - Purchase code B21
• Odyssey PC1800 - 214Ah Extra long life battery - 12V - Purchase code B22
Multiple batteries can be used in parallel to increase the charge of the 12V supply to the inverter. Please refer to
the data sheet for further information. The maximum sized battery bank that can be used with each MultiPlus
Compact is:
• MultiPlus Compact 12/800/35 - 400Ah
• MultiPlus Compact 12/1200/50 - 700Ah
OPERATION
On/Off/Charger Only Switch
For all operation as a battery back up system the switch should be in the “on”, position meaning the product is
fully functional - powering the pumps with through power during times of normal power supply, inverter power
during power outage. When mains power is not interrupted, the unit will charge the batteries also.
Charge States (see LED Indications on page 10 also)
• Bulk - Heavy and fast charge for batteries that are very or fully depleted
• Absorption - Final top up charge at a lower charge rate than Bulk
• Float - Trickle charge for when batteries are fully charged to replace charge that is lost over time. This
ensures that the batteries are always fully charged.
If the voltage at the “AC-in” terminal is not within specifications, during a power outage, for example, the
inverter will switch on.
© Newton Waterproofing Systems
10
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
LED Indications
inverter
on
charger
off
charger only
alarm
inverter
on
charger
off
charger only
alarm
inverter
on
charger
off
Unit switched on & connected to the mains. Pumps are
powered by the mains through the MultiPlus Compact. Charger
is operating in Bulk (heavy charge) or Absorption (top up
charge) mode. Charger light is on.
Unit switched on & connected to the mains. Pumps are
powered by the mains through the MultiPlus Compact. Charger
is operating in Float (trickle charge) mode. Charger light is
flashing.
Unit switched on. Power is interrupted. Pumps are powered by
the batteries through the inverter. No charging is taking place.
Inverter light is on.
charger only
alarm
inverter
on
charger
off
charger only
alarm
inverter
on
charger
off
charger only
alarm
Unit switched on. Power is interrupted. Pumps are powered by
the batteries through the inverter. No charging is taking place.
Inverter light is on. Alarm light is flashing. Pre Alarm: Unit is
overloaded or battery voltage is low or Inverter temperature is
too high.
Unit switched on. Power is interrupted. Inverter circuit has
been suspended. The pumps are not powered. No charging is
taking place. Inverter light is on. Alarm light is on. Full Alarm:
Unit is overloaded or battery voltage is very low or Inverter
temperature is too high.
There is no need to switch the unit to “charger only” mode.
MAINTENANCE
The unit does not require specific maintenance. All connections should be checked once a year as part of the
pump servicing regime. Avoid moisture and oil/soot/vapours, and keep the device clean.
TECHNICAL DATA
All technical data is available on page 2 of the Data Sheet.
TROUBLESHOOTING
The following table provides a quick reference of the more common faults. Disconnect the battery(s) and pumping
Problem
Cause
Solution
The inverter fails to
operate
Processor in ‘no function mode’
Disconnect from mains. Switch off. Wait 4
seconds. Switch on again.
The charger is not
functioning
The thermal breaker has tripped
Reset the 16A thermal circuit breaker
The battery is not being
fully charged
Defective battery connection
Check the battery terminals
The internal DC fuse is defective
Damaged inverter. Requires engineer
repair.
The battery is
overcharged
Defective battery(s)
Replace battery(s)
© Newton Waterproofing Systems
(a trading name of John Newton & Co. Ltd.)
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk
11
Newton Waterproofing Systems
(A Trading Name Of John Newton & Co Ltd)
Newton House
17-19 Sovereign Way
Tonbridge, Kent TN9 1RH
T: 01732 360 095 F: 01732 359 033
E: info@newtonwaterproofing.co.uk W: www.newtonwaterproofing.co.uk
© Newton Waterproofing Systems
(a improvement
trading name of John
Newton &
Co.right
Ltd.) to change our specifications at any time”
“As part of our policy of continuous product
we reserve
the
Newton House, 17-19 Sovereign Way, Tonbridge, Kent, TN9 1RH
T: +44 (0)1732 360 095 W: www.newtonwaterproofing.co.uk E: info@newtonwaterproofing.co.uk