SNAP PAC S-SERIES
CONTROLLER
USER’S GUIDE
SNAP-PAC-S1
SNAP-PAC-S2
SNAP-PAC-S1-FM
SNAP-PAC-S1-W
SNAP-PAC-S2-W
SNAP PAC S-SERIES CONTROLLER
USER’S GUIDE
SNAP-PAC-S1
SNAP-PAC-S2
SNAP-PAC-S1-FM
SNAP-PAC-S1-W
SNAP-PAC-S2-W
Form 1592-170105—January 2017
43044 Business Park Drive
•
Temecula
•
CA 92590-3614
Phone: 800-321-OPTO (6786) or 951-695-3000
Fax: 800-832-OPTO (6786) or 951-695-2712 www.opto22.com
Product Support Services
800-TEK-OPTO (835-6786) or 951-695-3080
Fax: 951-695-3017
Email: [email protected]
Web: support.opto22.com
SNAP PAC S-Series User’s Guide
Form 1592-170105—January 2017
Copyright © 2008–2017 Opto 22.
All rights reserved.
Printed in the United States of America.
The information in this manual has been checked carefully and is believed to be accurate; however, Opto 22 assumes no responsibility for possible inaccuracies or omissions. Specifications are subject to change without notice.
Opto 22 warrants all of its products to be free from defects in material or workmanship for 30 months from the manufacturing date code. This warranty is limited to the original cost of the unit only and does not cover installation, labor, or any other contingent costs. Opto 22 I/O modules and solid-state relays with date codes of 1/96 or newer are guaranteed for life. This lifetime warranty excludes reed relay, SNAP serial communication modules, SNAP PID modules, and modules that contain mechanical contacts or switches. Opto 22 does not warrant any product, components, or parts not manufactured by Opto 22; for these items, the warranty from the original manufacturer applies. Refer to Opto 22 form
1042 for complete warranty information.
Wired+Wireless controllers and brains are licensed under one or more of the following patents: U.S. Patent No(s). 5282222,
RE37802, 6963617; Canadian Patent No. 2064975; European Patent No. 1142245; French Patent No. 1142245; British Patent
No. 1142245; Japanese Patent No. 2002535925A; German Patent No. 60011224.
Opto 22 FactoryFloor, groov, Optomux, and Pamux are registered trademarks of Opto 22. Generation 4, groov Server, ioControl, ioDisplay, ioManager, ioProject, ioUtilities, mistic, Nvio, Nvio.net Web Portal, OptoConnect, OptoControl,
OptoDataLink, OptoDisplay, OptoEMU, OptoEMU Sensor, OptoEMU Server, OptoOPCServer, OptoScript, OptoServer,
OptoTerminal, OptoUtilities, PAC Control, PAC Display, PAC Manager, PAC Project, PAC Project Basic, PAC Project Professional,
SNAP Ethernet I/O, SNAP I/O, SNAP OEM I/O, SNAP PAC System, SNAP Simple I/O, SNAP Ultimate I/O, and Wired+Wireless are trademarks of Opto 22.
ActiveX, JScript, Microsoft, MS-DOS, VBScript, Visual Basic, Visual C++, Windows, and Windows Vista are either registered trademarks or trademarks of Microsoft Corporation in the United States and other countries. Linux is a registered trademark of Linus Torvalds. ARCNET is a registered trademark of Datapoint Corporation. Modbus is a registered trademark of Schneider Electric, licensed to the Modbus Organization, Inc. Wiegand is a registered trademark of Sensor Engineering
Corporation. Allen-Bradley, CompactLogix, ControlLogix, MicroLogix, SLC, and RSLogix are either registered trademarks or trademarks of Rockwell Automation. CIP and EtherNet/IP are trademarks of ODVA. Raspberry Pi is a trademark of the
Raspberry Pi Foundation.
groov includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit. (http://www.openssl.org)
All other brand or product names are trademarks or registered trademarks of their respective companies or organizations.
Opto 22
Automation Made Simple.
ii
SNAP PAC S-Series User’s Guide
Table of Contents
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SNAP PAC S-Series User’s Guide iii iii
Configuring RS-485 Connections on SNAP-PAC-S1 Controllers . . . . . . . . . . . . . . . . . . . . 21
Configuring RS-485 Connections on SNAP-PAC-S2 Controllers . . . . . . . . . . . . . . . . . . . . 21
iv SNAP PAC S-Series User’s Guide
Disabling or Enabling Firmware and Strategy Updates Via the Card . . . . . . . . . . . . . . . . 62
Appendix A: Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
SNAP PAC S-Series User’s Guide v v
vi SNAP PAC S-Series User’s Guide
Chapter 1
1: Overview
Introduction
The SNAP PAC S-series programmable automation controllers provide powerful, real-time control and communication to meet your industrial control, monitoring, and data acquisition and exchange needs. As part of the
Opto 22 SNAP PAC System, one of these compact, industrially hardened controllers can handle multiple control, automation, and data tasks involving digital and analog control, serial string handling, PID, and enterprise connectivity.
Connecting to Opto 22 serial- and
Ethernet-based I/O systems, a SNAP PAC
S-series controller runs control programs written in Opto 22’s PAC Control
™
software to
SNAP-PAC-S2 controller
monitor and control a wide range of devices and equipment. SNAP PAC S-series controllers are well suited to original equipment manufacturers (OEMs), system integrators, and end-users in process control, discrete manufacturing, or hybrid industries and applications.
A SNAP PAC S-series controller simultaneously runs up to 32 PAC Control flowcharts, although a
PAC Control strategy can actually contain a much larger number of flowcharts. The total number of flowcharts is limited only by the controller memory available for strategy storage.
Two S-series PACs of the same part number can be used together as redundant controllers. One controller runs the strategy while the other runs in tandem, ready to take over if the first one fails.
Ethernet Communication
All SNAP PAC S-series programmable controllers communicate over standard 10/100 Mbps Ethernet networks and can be attached to an existing wired Ethernet network or wireless LAN (local area network). The controllers can also be used in an independent control network built with standard, off-the-shelf Ethernet hardware.
SNAP PAC S-Series User’s Guide
1
1
INTRODUCTION
SNAP PAC S-series controllers include two 10/100 Mbps Ethernet interfaces for networking through an Ethernet switch to Ethernet hosts, as well as SNAP PAC brains and I/O, which provide local intelligence and the connections to digital and analog sensors and actuators as well as serial devices. These independent Ethernet ports have separate IP addresses that can be used with PAC
Project
™
Professional software to set up redundant network links to safeguard the availability and reliability of an I/O system, or to segment a control system’s network from the enterprise LAN.
Supported protocols over Ethernet include EtherNet/IP
™
, Modbus
®
/TCP, SMTP, SNMP, FTP, and
OptoMMP.
•
Using EtherNet/IP, SNAP PAC S-series controllers can share data with Allen-Bradley
®
Logix PLCs and other PLC systems based on the EtherNet/IP protocol.
•
Using Modbus/TCP, S-series PACs can share data with Ethernet-based Modbus hardware and software.
•
SMTP (Simple Mail Transfer Protocol) is used for email, and SNMP (Simple Network
Management Protocol) lets the network monitor the PAC just as it would monitor network computer hardware.
•
FTP can be used to manipulate files and data in the PAC’s file system.
•
OptoMMP is an open, documented protocol used by all Opto 22 Ethernet-based controllers and brains.
Wired+Wireless
™
Communication
SNAP-PAC-S1-W and SNAP-PAC-S2-W controllers add wireless capability to communications. In addition to the two wired network interfaces, these models have a wireless network interface as well, so each PAC has a total of three separate IP addresses—two wired and one wireless.
Wired+Wireless PACs can be used wirelessly or on a wired network, or both at once.
For flexibility in designing your wireless network, wireless communication includes support for 802.11a, b, and g standards. Wired+Wireless PACs can be used with a variety of wireless switches and other infrastructure hardware. For the best security, the 802.11i WPA2/AES standard is supported, while older WPA and WEP security standards are included for backwards compatibility.
Just like a laptop computer with a wireless connection, all functionality remains the same whether the Wired+Wireless
PAC is used wirelessly or as part of a wired network. Supported protocols remain the same. Control programs run the same on both networks without reprogramming.
A Wired+Wireless S-series PAC can communicate with both wired and wireless SNAP PAC I/O units. (See “I/O Units
Supported” on page 3 for details.) If desired, the PAC can segment a wireless network from a wired one.
2
SNAP PAC S-Series User’s Guide
CHAPTER 1: OVERVIEW
Serial Communication
SNAP PAC S-series controllers provide RS-232 and RS-485 communication as follows:
•
The SNAP-PAC-S1, SNAP-PAC-S1-FM, and SNAP-PAC-S1-W have two RS-232 serial ports that support general-purpose communication with serial devices; you can send and receive data from one or two serial devices connected directly to the controller. By default, Port 0 is set to be connected to a modem using Point-to-Point Protocol (PPP) for creating TCP/IP networks over serial or PSTN (Public Switched Telephone Network) lines. To connect Port 0 to serial devices, change the port configuration in PAC Manager.
The S1 PACs also have one pluggable two-wire RS-485 port that can be used for SNAP PAC
SB-series serial brains and legacy Opto 22 mistic
™
I/O units, including the serial B3000 brain and remote mistic bricks. The SNAP-PAC-S1-FM is Factory Mutual approved.
•
The SNAP-PAC-S2 and SNAP-PAC-S2-W have four serial ports that can each be configured using PAC Manager as either RS-232 or RS-485 (2-wire or 4-wire). These ports can be used for either I/O or general-purpose serial communication. Configured as RS-232, the ports support remote serial device communication, and any one of the ports can be configured as a PPP modem connection. Configured as RS-485, the serial ports connect to SNAP PAC serial brains and to mistic I/O units.
If you have a substantial number of serial I/O units, the PAC S2 is the controller to use. For the default configuration settings of these ports, see
“Assigning Serial Ports on SNAP-PAC-S2
.
For additional serial interfaces, you can add one or more SNAP serial communication modules on attached SNAP Ethernet-based I/O units.
I/O Unit Compatibility
The combination of Ethernet (both wired and wireless) and serial network interfaces gives SNAP PAC
S-series controllers the ability to control current and many legacy Opto 22 I/O units. All S1s have one
RS-485 port, and S2s can be configured with up to four.
The following table lists I/O units supported by S-series controllers:
S-Series Controller On a Wireless LAN On a Wired Ethernet Network On a Serial Network
SNAP-PAC-S1
SNAP-PAC-S1-FM
SNAP-PAC-S2
SNAP-PAC-S1-W
SNAP-PAC-S2-W
---none---
SNAP-PAC-R1-W
SNAP-PAC-R2-W
SNAP-PAC-EB1-W
SNAP-PAC-EB2-W
SNAP-PAC-R1
SNAP-PAC-R1-B
SNAP-PAC-R1-FM
SNAP-PAC-R2
SNAP-PAC-R2-FM
SNAP-PAC-EB1
SNAP-PAC-EB1-FM
SNAP-PAC-EB2
SNAP-PAC-EB2-FM
SNAP-UP1-ADS*
SNAP-B3000-ENET*
SNAP-ENET-D64*
SNAP-ENET-S64*
SNAP-ENET-RTC*
* Legacy I/O processors; not recommended for new development
SNAP-PAC-SB1
SNAP-PAC-SB2
B3000*
B3000-B*
SNAP-BRS*
B100*
B200*
G4D16R*
G4D32RS*
G4A8R*
SNAP PAC S-Series User’s Guide
3
3
PAC PROJECT SOFTWARE
This connectivity with legacy serial-based I/O systems, combined with PAC Control Professional software’s ability to import control programs (or strategies) written in OptoControl™ software, provides a migration path to integrate older Opto 22 I/O systems into modern control hardware running on Ethernet networks.
For detailed information on updating control strategies and integrating legacy control hardware into modern systems, see Opto 22 form 1692, the
FactoryFloor to PAC Project Migration Technical
Note
.
Redundant Controllers
Two identical SNAP PAC S-series controllers can be used in a redundant system, where one controller actively runs the control program and the other is ready to take over if the first one should
Project Software,” below) and the SNAP PAC Redundancy Option Kit.
The PAC Control Professional strategy developed for a redundant system makes use of special redundancy features, such as checkpoint blocks and persistent/redundant variables. The developer has complete flexibility in programming, tagging specific data for redundancy and placing checkpoint blocks at precise points in the logic where synchronization is to occur.
See
for a diagram of a redundant system. Also see Opto 22 form 1901, the
SNAP PAC
Redundancy Option Kit Data Sheet
, and Opto 22 form 1831, the
SNAP PAC System Redundancy User’s
Guide
.
PAC Project Software
PAC Project
SNAP PAC controllers use Opto 22’s PAC Project™ Microsoft® Windows®-compatible automation software for programming, human-machine-interface (HMI) development, and OPC connectivity.
Two versions of PAC Project are available:
•
PAC Project Basic includes PAC Control™ for developing control programs, PAC Display™ for creating operator interfaces, and PAC Manager™ configuration software.
PAC Project Basic is included with SNAP PAC controllers and is a free download from the
Opto 22 website.
•
PAC Project Professional adds expanded versions of PAC Control and PAC Display, plus
OptoOPCServer
™
software for exchanging data with OPC 2.0-compliant client software applications and OptoDataLink
™
for exchanging SNAP PAC System data with databases
(including Microsoft SQL Server®, Microsoft Access®, and MySQL®), text files, and email systems).
PAC Project Professional is available for purchase and download from the Opto 22 website, www.opto22.com. You can also purchase PAC Control Professional, PAC Display Professional,
OptoOPCServer, and OptoDataLink separately. For details, see Opto 22 form 1699, the
PAC
Project Data Sheet
.
4
SNAP PAC S-Series User’s Guide
CHAPTER 1: OVERVIEW
PAC Control Basic
is a graphical, flowchart-based programming tool for machine control and process applications. Using PAC Control, you create, download, and run strategies on a SNAP PAC controller. In addition to flowchart programming with subroutine capability, PAC Control includes a powerful, built-in scripting language based on C and other procedural languages.
PAC Control Professional adds the ability to import legacy OptoControl strategies, support for older mistic™ serial I/O units, and support for the dual independent Ethernet ports on a SNAP PAC controller. A SNAP R-series controller simultaneously runs up to 16 PAC Control flowcharts, although the PAC Control strategy can actually contain a much larger number of flowcharts. The total number of flowcharts is limited only by the memory available for strategy storage.
PAC Display Basic is an intuitive HMI package for building operator interfaces, or projects, for communicating with a SNAP PAC controller. PAC Display offers a full-featured HMI including alarming, trending, and a built-in library of 3,000 industrial automation graphics.
PAC Display Professional adds the ability to import projects created in OptoDisplay, part of the legacy Opto 22 FactoryFloor
®
software suite, and using redundant Ethernet communication links on
SNAP PAC controllers. PAC Display Professional can also connect to Ethernet-based FactoryFloor controllers running OptoControl strategies.
OptoOPCServer is a fast, efficient OPC 2.0-compliant server for communicating with many Opto 22 products, including SNAP PAC controllers and I/O units, plus legacy Opto 22 Ethernet-based controllers and I/O. Using OptoOPCServer, you can consolidate data from all these Opto 22 systems into the OPC client software of your choice, such as third-party HMI and data acquisition packages, and custom software applications you create with tools such as Visual C++
®
.
OptoDataLink is a software application that makes it easy to share data from the SNAP PAC System with commonly used databases, including Microsoft SQL Server, Microsoft Access, and MySQL, as well as text files. The I/O points and strategy variables already created in your PAC Control strategy are automatically available for OptoDataLink to use for data exchange.
PAC Manager
is a utility application for assigning IP addresses to SNAP PAC controllers and brains, reading or changing basic controller configuration, and configuring and testing I/O.
For Developers: SNAP PAC REST API
If you’re a developer who’d like to use PAC Control strategy tags in communications with other devices, the Opto 22 SNAP PAC REST API is a secure and powerful way to do just that. The API is available in SNAP PAC R-series and S-series controllers with PAC firmware R9.5a and higher. To configure https access to your PAC’s RESTful server and learn how to call the API, visit developer.opto22.com
.
Architectural Diagrams
Because SNAP PAC S-series controllers have multiple Ethernet and serial interfaces, these controllers are suitable for use in a variety of system layouts and architectures.
Dual independent Ethernet interfaces, for example, let you configure a network for link redundancy or segmented networking. A PPP serial interface provides a dial-up modem link for remotely located
SNAP PAC S-Series User’s Guide
5
5
ARCHITECTURAL DIAGRAMS control systems, while two-wire RS-485 support integrates existing Opto 22 mistic serial-based I/O units into contemporary Ethernet-based systems.
On Wired+Wireless models, the additional wireless LAN interface offers even more flexibility in system design.
Basic Control System
In this basic system, the SNAP-PAC-S1 controls several SNAP PAC I/O units, some on a wired Ethernet network and some on a serial network. PAC Project Basic is all you need.
SNAP PAC EB brains providing distributed control on an Ethernet network
PC used to develop the
PAC Control strategy.
After development, the strategy is downloaded to the controller and runs independently.
PC running
PAC Display HMI
(operator interface)
SNAP-PAC-S1 controller running the PAC Control strategy and controlling all I/O units, both
Ethernet and serial
SNAP PAC SB brains providing distributed control on a serial network
6
SNAP PAC S-Series User’s Guide
CHAPTER 1: OVERVIEW
Segmented Wired Networks
The following diagram shows Opto 22 I/O units connected together over an Ethernet network and controlled by a SNAP PAC S-series controller running a PAC Control strategy. The controller is also connected to a larger, separate enterprise Ethernet network to provide data to two PCs running
PAC Display HMI software and OptoOPCServer. Sitting between the two networks, the SNAP PAC
S-series controller segments enterprise traffic from the control network.
For this system, PAC Display must be configured to access the I/O through the controller rather than directly from the I/O units, since they are on a separate network.
Enterprise Network
PC running PAC
Display Professional
PC running
OptoOPCServer and OptoDataLink
Ethernet switch, network #1
SNAP PAC S-series controller communicates with host computers through one network interface and controls
I/O with other devices through the other interface.
Ethernet switch, network #2
Control Network
I/O units are controlled by the controller on an isolated segment.
Sensors and actuators, location #1
Sensors and actuators, location #2
SNAP PAC S-Series User’s Guide
7
7
ARCHITECTURAL DIAGRAMS
Wired and Wireless Networks
The network shown in this diagram requires a Wired+Wireless S-series controller (SNAP-PAC-S1-W or SNAP-PAC-S2-W). The PAC runs a PAC Control strategy and controls remote I/O units via a wireless access point. The controller is also connected to a separate, wired enterprise network through one of its wired Ethernet network interfaces.
The controller could just as easily talk to the I/O units through a wired network and segment the enterprise PCs on a wireless LAN. In addition, because the Wired+Wireless PAC has two wired interfaces plus the wireless one, it could segment three networks—for example, a wired control network, a wired enterprise network, and a wireless connection with a laptop for maintenance or testing purposes.
Control Network
Wireless LAN access point
SNAP-PAC-S1-W segments the enterprise network
(wired) from the control network
(wireless).
Wired+Wireless I/O units controlled by the PAC-S1-W
Enterprise Network
PC running
PAC Control
PC running
PAC Display
Ethernet switch for wired network
8
SNAP PAC S-Series User’s Guide
CHAPTER 1: OVERVIEW
Connections to Legacy Serial-based I/O Units
In the following diagram, a SNAP PAC S-series controller is connected to Opto 22 legacy serial-based
I/O units over an RS-485 serial network. The controller is also connected to a larger, separate enterprise Ethernet network to provide process data to a PC running Opto 22’s PAC Display HMI software.
RS-485 serial network
PC running PAC
Display Professional
PC running PAC
Control Professional
Ethernet switch
SNAP PAC S-series controller controls all I/O units.
I/O units are connected via a 2-wire RS-485 serial network and are running the mistic protocol. Each I/O unit is connected to its own group of sensors and actuators, and all I/O units are controlled by the SNAP PAC S-series controller.
Sensors and actuators, location #1
Sensors and actuators, location #2
Sensors and actuators, location #3
SNAP PAC S-Series User’s Guide
9
9
ARCHITECTURAL DIAGRAMS
SNAP-PAC-S2 Connections to Serial-based I/O Units
The following diagram shows a SNAP-PAC-S2 controller connected to multiple Opto 22 serial-based
I/O units over two RS-485 serial networks, a remote a SNAP Ethernet-based I/O unit over a modem using the Point-to-Point Protocol (PPP), and a serial-based industrial scale.
PC running PAC
Display Professional
PC running PAC
Control Professional
Ethernet switch
RS-485 serial networks
SNAP-PAC-S2 controller controls all I/O units and processes data from the scale.
PPP connection
Modem
Scale
Sensors and actuators, location #1
Modem
PPP connection to SNAP-PAC-R1
Sensors and actuators, location #2
I/O units are connected via a 2-wire RS-485 serial network and are controlled by the
SNAP PAC S-series controller. Each I/O unit is connected to its own group of sensors and actuators.
Sensors and actuators, location #3
10
SNAP PAC S-Series User’s Guide
Sensors and actuators, location #4
Sensors and actuators, location #5
CHAPTER 1: OVERVIEW
Ethernet Link Redundancy
The following diagram shows a SNAP PAC S-series controller connected to two separate Ethernet network links. This configuration addresses the concern that an Ethernet network may fail or need maintenance, leaving the PC running OptoOPCServer, the PC running PAC Display, the controller, and the I/O units unable to communicate. In this configuration, if one link goes down, devices can still communicate on the other. Each PC has two network interface cards (NICs), and the SNAP PAC
S-series controller and the I/O units (SNAP-PAC-R1 and -R2 controllers) have two network interfaces as well.
For an example of controller redundancy, see the following page.
Opto 22 Redundant Network
PC with two NICs running
PAC Display Professional
PC with two NICs running
OptoOPCServer
Ethernet switch, network #1
SNAP PAC S-series controller controls all I/O units.
I/O units are all connected by the controller.
Each I/O unit is connected to its own group of sensors and actuators, but all are connected to the same two networks.
Sensors and actuators, location #1
SNAP PAC R-series controller
SNAP PAC R-series controller
Sensors and actuators, location #2
Ethernet switch, network #2
SNAP PAC S-Series User’s Guide
ARCHITECTURAL DIAGRAMS
Controller Redundancy
In this diagram, two S-series controllers are operating redundantly. One is the active controller, while the other acts as a backup, ready to take over should the first one fail.
Controller redundancy requires PAC Project Professional 9.0 or newer and the Redundancy Option
Kit, which includes the arbiter and the redundant power switch in the diagram below. PAC
Redundancy Manager, a software utility for setting up and maintaining the system, is included in
PAC Project Pro. The two controllers you use must be exactly the same part number (for example, two SNAP-PAC-S2 controllers or two SNAP-PAC-S1-W controllers).
As you can see, one advantage of an Opto 22 redundant system is that it uses standard PACs, standard cabling, and standard I/O. Another advantage is that either controller can act as the active or backup controller; you can switch their roles at any time for maintenance, for example. For detailed information on redundancy, see Opto 22 form 1831, the
SNAP PAC System Redundancy
User’s Guide
.
PC running PAC Project Professional
SNAP PAC I/O units
Arbiter
RS-485
Ethernet switch
Redundant power switch
SNAP PAC controller
Ethernet crossover cable connects the
PAC S2s on ENET2
RS-485
Power control
Power
SNAP PAC controller
12
SNAP PAC S-Series User’s Guide
CHAPTER 1: OVERVIEW
Remote Host and I/O Unit Connections Using PPP
For remote monitoring and control, you can use a SNAP PAC S-series controller to connect to a remote host such as a PC or to a SNAP Ethernet-based I/O unit using a dial-up link. For this use, the controller communicates using the Point-to-Point Protocol (PPP) over a modem.
Enterprise Network
PC running PAC
Display Professional
PC running
OptoOPCServer and OptoDataLink
Ethernet switch
SNAP PAC S-series controller uses a PPP dial-up telephone connection to communicate with
I/O units at a remote location.
Dial-up modem
Dial-up modem at remote location
Sensors and actuators at remote location
SNAP I/O unit at remote location is connected to sensors and actuators.
SNAP PAC S-Series User’s Guide
ABOUT THIS GUIDE
About This Guide
See the following sections for basic information on setting up and maintaining a SNAP PAC S-series controller:
—installing and configuring SNAP PAC S-series controllers.
Chapter 3: Maintenance and Troubleshooting
—troubleshooting problems while installing or
using the SNAP-PAC-S1 controller on an Ethernet or serial network; getting device information, loading new firmware, changing the controller’s IP address, and other maintenance procedures.
Appendix A: Technical Specifications
—specifications, connectors, indicators, pinouts, and
dimensions.
Related Documentation
You may also need the following documentation, depending on your application
For this information
Configuring I/O points and system functions
See this guide
PAC Manager User’s Guide *
PAC Control User’s Guide *
Designing flowchart-based control programs for the system
PAC Control Command Reference *
PAC Control Commands Quick Reference
Card *
Securely accessing data in the PAC via its REST API
developer.opto22.com
Writing programs for Opto 22 memory-mapped devices using OptoMMP
OptoMMP Protocol Guide
Form #
1704
1700
1701
1703
n/a
1465
Using redundant controllers
Installing and using SNAP PAC R-series controllers
SNAP PAC R-series Controller User’s Guide
1595
Installing and using SNAP PAC EB and
SB-series brains
SNAP PAC Brains User’s Guide
1690
Communicating with I/O units using OPC
Communicating with I/O units using Modbus/TCP
SNAP PAC System Redundancy User’s
Guide
OptoOPCServer User’s Guide
Modbus/TCP Protocol Guide
EtherNet/IP for SNAP PAC Protocol Guide
1831
1439
1678
1770 Communicating with I/O units using EtherNet/IP
Programming your own applications for S-series controllers using the OptoMMP Communication Toolkit (previously called the SNAP Ethernet I/O Driver
Toolkit) or the OptoMMP memory-mapped protocol
Moving to the SNAP PAC System with older hardware and software
OptoMMP Protocol Guide
SNAP PAC System Migration Technical Note
1465
1688
* If you are using SNAP PAC S-series controllers with legacy I/O units (for example, mistic I/O units or Ultimate
I/O), use the Legacy versions of these documents instead:
Legacy Edition, PAC Manager User’s Guide
, form 1714
Legacy Edition, PAC Control User’s Guide
, form 1710
Legacy Edition, PAC Control Command Reference
, form 1711
Some documents are on the CD that came with the controller; all forms are available on our website
( www.opto22.com
) for downloading. The easiest way to find one is to search on the form number.
14
SNAP PAC S-Series User’s Guide
CHAPTER 1: OVERVIEW
For Help
If you have problems installing or using a SNAP PAC S-series controller and cannot find the help you need in this guide, contact Opto 22 Product Support.
Phone:
800-TEK-OPTO (800-835-6786 toll-free in the U.S. and Canada)
951-695-3080
Monday through Friday,
7 a.m. to 5 p.m. Pacific Time
NOTE: Email messages and phone calls to Opto 22 Product Support are grouped together and answered in the order received.
Fax:
Email:
951-695-3017 [email protected]
Opto 22 website:
www.opto22.com
When calling for technical support, you can help us help you faster if you can provide the following information to the Product Support engineer:
•
Opto 22 hardware part numbers or models that you’re working with
•
Software version (available by clicking Help > About in the application’s menu bar)
•
Firmware version
•
Specific error messages you saw
•
Version of your computer’s operating system
SNAP PAC S-Series User’s Guide
FOR HELP
16
SNAP PAC S-Series User’s Guide
Chapter 2
2: Quick Start
What You Will Need
•
PC running Microsoft Windows
10, 8.1, or 7 Professional (32-bit or 64-bit) or Windows
Vista Business (32-bit)
, with a 10/100 MB Ethernet interface, the TCP/IP protocol installed, and a valid IP address, on the same subnet as the controller
•
Crossover cable (for direct connection to the PC) or an available connection to a standard
10BASE-T or 100BASE-TX Ethernet network
•
SNAP PAC S-series controller
•
CD that came with the controller or PAC Project Professional CD (purchased separately)
•
8–32 VDC power supply (see
“Power Supply Recommendations” on page 18 for specific
information and recommendations)
•
Small flathead screwdriver
•
One or more of the following, depending on your I/O system requirements:
– Opto 22 SNAP PAC I/O units on the same Ethernet network as the controller.
– For Wired+Wireless PACs, a wireless local area network (WLAN) and Wired+Wireless SNAP
PAC I/O units
– Opto 22 legacy SNAP Ethernet-based I/O units—SNAP Simple I/O, SNAP Ethernet I/O, or
SNAP Ultimate I/O units—on the same Ethernet network as the controller.
– Opto 22 RS-485 serial-based I/O units—SNAP PAC serial brains, serial B3000, SNAP-BRS,
B100/B200 brains, or mistic remote bricks (G4D16R, G4D32RS, G4A8R)—on a two-wire
RS-485 network.
Installing Software
In your CD-ROM drive, insert the CD that came with the SNAP PAC S-series controller. The installation wizard should start automatically. If it doesn’t, use Windows Explorer to navigate to your
CD-ROM drive and then double-click setup.exe.
SNAP PAC S-Series User’s Guide
POWER SUPPLY RECOMMENDATIONS
Power Supply Recommendations
Opto 22 recommends that the SNAP PAC S-series controller be powered with an Opto 22
SNAP-PS24 or SNAP-PS24U power supply. In place of one of these power supplies, Opto 22 recommends an 8-32 VDC linear supply with adequate current ratings for the load. For more information on power requirements, see
Appendix “A: Technical Specifications”
.
Change to SNAP-PAC-S1 Power Input Range
Current SNAP-PAC-S1 controllers have an 8–32 VDC input range, but earlier SNAP-PAC-S1 controllers use an 8–24 VDC input range. Before applying power to the controller, confirm that the input
voltage is within the voltage range shown on the faceplate.
The voltage input rating can also be determined based on the SNAP-PAC-S1’s serial number as follows:
•
SNAP-PAC-S1 controllers with serial number 500000 and higher have an 8–32 VDC voltage input rating.
•
SNAP-PAC-S1 controllers with serial numbers lower than 500000 have an 8–24 VDC input rating. Using an input voltage above this range will cause damage that is not covered
by the warranty.
The SNAP-PAC-S1 serial number appears on the sticker on the side of the unit. The input voltage rating is shown on the top cover of the controller.
IP Address IP Address
MAC 1: 00-A0-3D-00-XX-XX MAC 1: 00-A0-3D-00-XX-XX
CC
501023
SNAP-PAC-S1 serial number
SNAP-PAC-S1 input voltage rating
Installing Hardware
NOTE: If you are using redundant controllers, see steps in the SNAP PAC System Redundancy User’s Guide.
1.
Install Opto 22 I/O units according to instructions in the brain’s user’s guide.
This guide is on the CD that was shipped with the I/O unit’s brain; it is also available from our website at www.opto22.com
.
2.
Choose a convenient mounting location for the SNAP PAC S-series controller and either panel-mount or DIN-rail mount it according to the diagrams on
and
.
3.
Confirm that the power supply to be used with the controller is turned off or unplugged, and discharge any residual charge that may remain in the power supply.
4.
With the power supply off or unplugged, connect the power supply to the controller.
CAUTION: Reversing wire polarity may cause damage to your controller. This damage is not covered by Opto 22’s warranty. If you are not certain about the polarity of the wires on your power supply, check with a meter.
18
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START a.
With the power supply off or unplugged, connect the + (positive) lead from the power supply (normally red) to the + (positive) terminal on the face of the controller. b.
Connect the COM wire from the power supply (normally black) to the – (negative) terminal on the face of the controller.
c.
Connect a lead from a known chassis ground to the (ground) terminal on the face of the controller.
IMPORTANT:
Do not turn on power to the controller.
5.
Using Category 5 or superior solid unshielded twisted-pair cable, connect the SNAP PAC
S-series controller using Ethernet port ENET 1 in one of the following ways:
– (Recommended for initial configuration) Connect to a PC directly, using an Ethernet crossover cable.
NOTE: If you use a crossover cable, make sure to assign a fixed IP address to the network card (NIC) on your computer. Otherwise, if your network card is configured to get its IP address via DHCP, when you unplug the computer from the network, the computer will no longer have an IP address. When you are finished using the crossover cable, you can change the setting back to DHCP.
NOTE: Wired+Wireless models must be initially configured using a wired interface. After you’ve assigned IP addresses and configured wireless communication parameters, you can communicate with the PAC on the wireless LAN.
– Connect to a standard 10BASE-T or 100BASE-TX Ethernet network that has a PC on the same subnet as the controller and does NOT have a Dynamic Host Configuration Protocol
(DHCP) server.
NOTE: When connecting the controller to a managed switch, make sure the managed switch's port configuration is set to Auto for the Duplex setting and Auto for the Speed setting.
Maximum cable or segment length is 100 meters; minimum cable length is one meter.
6.
If the controller will connect to I/O units on an RS-485 serial network, connect the serial cable
following the instructions in “RS-232 and RS-485 Serial Networking” below.
IMPORTANT:
Do not turn on power to the controller.
7.
Before turning on power to the controller, follow steps in Opto 22 form 1704, the
PAC Manager
User’s Guide
, to assign the controller an IP address.
This guide is in Adobe Acrobat PDF format on the CD that came with the controller and is also available from our website, www.opto22.com
. Note that you can use PAC Manager to assign IP addresses to the controller and I/O units at the same time.
SNAP PAC S-Series User’s Guide
RS-232 AND RS-485 SERIAL NETWORKING
RS-232 and RS-485 Serial Networking
SNAP PAC S-series controllers provide both RS-232 and RS-485 serial communication interfaces. For
.
RS-232 Connections
You can use the RS-232 ports on a SNAP PAC S-series controller to:
•
Direct connect to a device that supports RS-232 communication.
•
Connect to a modem and make a serial Point-to-Point Protocol (PPP) connection to a remote
PC or other device that supports PPP.
Use PAC Manager to configure the RS-232 ports for the way you want to use them. (For instructions, see Opto 22 form 1704, the
PAC Manager User’s Guide
.) Note that the controller cannot make a direct
RS-232 serial connection with an Opto 22 I/O unit; however, it is possible to connect to an Opto 22
I/O unit that supports PPP communications.
Attaching a Modem to the Controller
To work properly with the SNAP PAC S-series controller, a modem must be able to store settings in non-volatile RAM (NVRAM) and default to those settings on reset.
IMPORTANT:
Any modem used with the controller must implement the Carrier Detect (CD) signal or use a custom cable that connects CD to Data Terminal Ready (DTR).
1.
Connect the modem to the controller using a modem cable with female DB-9 connector. If
necessary, see “Connectors, Indicators, and Pinouts” on page 24
for pinout details.
2.
Store configuration settings to the modem’s NVRAM, following instructions in the user’s guide for your modem.
NOTE: Configuration settings must be stored to the modem’s NVRAM so they will be loaded when the controller sends a reset command to the modem.
RS-485 Connections
You can use an RS-485 serial port on a SNAP PAC S-series controller to connect to Opto 22 I/O units on a two-wire, RS-485 serial network. These I/O units include SNAP PAC SB-series brains, serial B3000 brains, and mistic remote bricks such as the G4D16R, G4D32RS, and the G4A8R. Both the PAC S1 and
PAC S2 support optional mistic signal interrupts. In addition, on the SNAP-PAC-S2 controller you can use PAC Manager to configure up to four RS-485 ports either as 2-wire or 4-wire connections.
Bias and Termination
Bias: Bias the RS-485 network at one location (device) only. This is typically done at the device that is the RS-485 master, which is normally the controller.
20
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
Termination: Configure termination at the devices that are located at both ends of the RS-485 network. For more information, please see the appropriate data sheet or user’s guide for configuring the I/O unit or brain that is at the end of the link.
NOTE: Bias and termination settings on S-series controllers take effect immediately.
Configuring RS-485 Connections on SNAP-PAC-S1 Controllers
RS-485 bias and termination settings are configured using two DIP switches located on the top of the controller.
Switch Position
ENABLE
Description
Bias: active
BIAS
DISABLE Bias: inactive
SNAP PAC S-series controller location on RS-485 network
RS-485 termination
TERM
ENABLE Termination: active
DISABLE Termination: inactive
Termination
Active
DIP switches
At the End
Termination
Inactive
In the Middle
(floating)
(Portion of top view
Configuring RS-485 Connections on SNAP-PAC-S2 Controllers
The serial ports on SNAP-PAC-S2 controllers are software configurable using PAC Manager. This includes mode, termination, and bias. For more information, see the PAC Manager User’s Guide. See
also, “Assigning Serial Ports on SNAP-PAC-S2 Controllers” on page 32
.
Wiring the 10-pin Serial Connector on SNAP-PAC-S1 Controllers
Serial ports1 and 2 on SNAP-PAC-S1 controllers share a 10-pin pluggable connector (Phoenix
Contact, part number FK-MC 0.5 - 2.5, supplied with the controller). When inserting and removing wire leads into this connector, do the following:
1.
Completely depress the small orange tab for the appropriate opening with a small screwdriver.
Hole
2.
While holding the tab down with the screwdriver, insert or remove the wire as needed.
3.
Release the orange tab.
Orange tab
For a pinout of the connector, see
Indicators, and Pinouts” on page 24 .
Pin 1
SNAP PAC S-Series User’s Guide
RS-232 AND RS-485 SERIAL NETWORKING
Wiring the 7-pin Serial Connector on SNAP-PAC-S2 Controllers
Each of the four serial ports on SNAP-PAC-S2 controllers uses a 7-pin pluggable connector supplied with the controller (EBY part number EB1381M-07-500 or equivalent). Using the screws on the side of the connector, insert or remove the wires as needed.
For a pinout of this connector, see “Connectors, Indicators, and Pinouts” on page 24
.
Pin 1
CAUTION: Do not use communication port connectors from a legacy OptoControl controller*. Legacy connectors will fit in a
SNAP-PAC-S2, but the pin orientation is different. Instead, use the connectors supplied with the SNAP-PAC-S2 controller.
*Legacy OptoControl Controllers
G4LC32
G4LC32SX
G4LC32ISA
G4LC32ISA-LT
M4
M4IO
M4RTU
SNAP-LCM4
SNAP-LCSX/PLUS
22
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
Guidelines for Grounding SNAP PAC Brains and Controllers
Power supply side: The DC output of the power supply to the I/O unit (or controller) should be
"floating,” which means the negative output terminal is not tied to ground.
RS-485 serial cable side: Connect the signal common from the controller to the signal common on each of the I/O units using an insulated wire that is part of the serial cable. Though sometimes hard to find, there are cables that have a twisted pair for serial communication plus an additional insulated wire for common. However, it might be easier to obtain a cable that has an extra twisted pair and then use one of the wires from this extra pair for the signal common connections.
RS-485 data pair
Use one of the wires from an extra twisted pair for the signal common
Connect the cable shield drain wire to chassis ground
NOTE: Make sure there are enough wires in the cable for a separate insulated signal common wire. Do not connect the signal common wire to chassis ground. Do not use the overall cable shield drain wire as the signal common.
Connect the cable shield drain wire of the serial cable to chassis ground at one location only. If the shield is not continuous from one I/O unit to the next, then the shield of each segment will need to be tied to chassis ground at one location only per segment.
SNAP PAC S-Series User’s Guide
CONNECTORS, INDICATORS, AND PINOUTS
Connectors, Indicators, and Pinouts
SNAP-PAC-S1 and SNAP-PAC-S1-FM
Controller reset button
DIP switches for RS-485 serial link
Bias
Termination
Port 2 for RS-485 serial communications (pins 1–5 of pluggable 10-pin connector)
Port 1 for RS-232 serial communications (pins 6–10 of pluggable 10-pin connector)
Port 0 for RS-232 serial communications (DB-9 connector) with handshaking. Supports PPP by default; for use with serial devices, configure the port in PAC Manager.
Status and Activity LEDs
Indicator
S0
Description
RS-232 serial activity on port 0
S1
S2
STAT
RS-232 serial activity on port 1
RS-485 serial activity
Startup status and control program operational status
ACT
LINK
Ethernet network activity
Link established with
Ethernet network
Port 0 for RS-232 serial
(DB-9 connector)
Pin Description Signal
Direction
3
4
1
2
DCD
RX
TX
DTR
In
In
Out
Out
5
6
7
8
9
COM
DSR
RTS
CTS
RI*
In
Out
In
In
* RI signal does not occur on
PACs with a microSD card slot
Activity LED (Yellow)
Link LED (Green)
Independent 10/100 Mbps Ethernet interfaces (RJ-45 connectors)
MicroSD card slot
STAT LED
8–32 VDC input power
(pluggable 3-pin connector)
Ports 1 and 2 for RS-485
and RS-232 serial
5
8
9
6
7
Pin Description Signal
Direction
3
4
1
2
TX/RX+
TX/RX–
SIG COM*
IRQ+
In/Out
In/Out
In
IRQ–
TX
RX
GND
RTS
In
Out
In
Out
In 10
* Isolated ground
CTS
24
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
SNAP-PAC-S1-W (Wired+Wireless)
Controller reset button
DIP switches for RS-485 serial link
Bias
Termination
Port 2 for RS-485 serial communications (pins 1–5 of pluggable 10-pin connector)
Port 1 for RS-232 serial communications (pins 6–10 of pluggable 10-pin connector)
Port 0 for RS-232 serial communications (DB-9 connector) with handshaking. Supports PPP by default; for use with serial devices, configure the port in PAC Manager.
Wireless LAN antenna
Activity LED (Yellow)
Link LED (Green)
Independent 10/100 Mbps Ethernet interfaces (RJ-45 connectors)
MicroSD card slot
WLAN LED
STAT LED
8–32 VDC input power
(pluggable 3-pin connector)
Status and Activity LEDs
LED
S0
S1
S2
Description
RS-232 serial activity on port 0
RS-232 serial activity on port 1
RS-485 serial activity
STAT
Startup status and control program operational status
ACT Ethernet network activity
LINK
Link established with Ethernet network
WLAN Wireless LAN status
Port 0 for RS-232 serial
(DB-9 connector)
Pin Description
7
8
5
6
3
4
1
2
DCD
RX
TX
DTR
COM
DSR
RTS
CTS
9 NC*
* No connection
Signal
Direction
In
In
Out
Out
In
Out
In
Ports 1 and 2 for RS-485
and RS-232 serial
5
8
9
6
7
Pin Description Signal
Direction
3
4
1
2
TX/RX+
TX/RX–
SIG COM*
IRQ+
In/Out
In/Out
In
IRQ–
TX
RX
GND
RTS
In
Out
In
Out
In 10
* Isolated ground
CTS
SNAP PAC S-Series User’s Guide
CONNECTORS, INDICATORS, AND PINOUTS
SNAP-PAC-S2
Serial activity LEDs
Ports 0 - 3 are each software configurable as either
RS-232 (TX, RX, COM, DTR, DCD
RTS, CTS), or
RS-485 (2-wire, 4-wire, optional termination, optional biasing).
Configure ports in PAC Manager.
Activity LED (Yellow)
Link LED (Green)
Independent 10/100 Mbps Ethernet interfaces (RJ-45 connectors)
Controller reset button
MicroSD card slot
STAT LED
8–32 VDC input power
(pluggable 3-pin connector)
Serial activity LEDs
RS-485 and RS-232 Ports
1
Pin
5
6
7
3
4
1
2
RS-232
TX
RX
COM
2
RTS
CTS
DTR
DCD
Signal
Direction
Out
In
Out
In
Out
In
RS-485
TX/RX+
TX/RX–
COM
2
RX+ (4 wire)
RX- (4 wire)
IRQ+
IRQ–
Signal
Direction
In/Out
In/Out
In
In
In
In
1
CAUTION: Do not use communication port connectors from a
legacy OptoControl controller*. Legacy connectors will fit in a
SNAP-PAC-S2, but the pin orientation is different. Instead, use the connectors supplied with the SNAP-PAC-S2 controller.
2
Isolated ground. (Each channel is isolated from the others.)
*Legacy OptoControl Controllers:
G4LC32
G4LC32SX
G4LC32ISA
G4LC32ISA-LT
M4
M4IO
M4RTU
SNAP-LCM4
SNAP-LCSX/PLUS
Status and Activity LEDs
Indicator Description
TX0/RX0 Serial activity on port 0
TX1/RX1 Serial activity on port 1
TX2/RX2 Serial activity on port 2
TX3/RX3 Serial activity on port 3
STAT
ACT
Startup status and control program operational status
Ethernet network activity
LINK
Link established with
Ethernet network
26
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
SNAP-PAC-S2-W (Wired+Wireless)
Wireless LAN antenna
Serial activity LEDs
Ports 0 - 3 are each software configurable as either
RS-232 (TX, RX, COM, DTR, DCD
RTS, CTS), or
RS-485 (2-wire, 4-wire, optional termination, optional biasing).
Configure ports in PAC
Manager.
Activity LED (Yellow)
Link LED (Green)
Independent 10/100 Mbps Ethernet interfaces (RJ-45 connectors)
Controller reset button
MicroSD card slot
WLAN LED
STAT LED
8–32 VDC input power
(pluggable 3-pin connector)
Serial activity LEDs
RS-485 and RS-232 Ports
1
Pin
5
6
7
3
4
1
2
RS-232
TX
RX
COM
2
RTS
CTS
DTR
DCD
Signal
Direction
Out
In
Out
In
Out
In
RS-485
TX/RX+
TX/RX–
COM
2
RX+ (4 wire)
RX- (4 wire)
IRQ+
IRQ–
Signal
Direction
In/Out
In/Out
In
In
In
In
1
CAUTION: Do not use communication port connectors from a
legacy OptoControl controller*. Legacy connectors will fit in a
SNAP-PAC-S2, but the pin orientation is different. Instead, use the connectors supplied with the SNAP-PAC-S2 controller.
2
Isolated ground. (Each channel is isolated from the others.)
*Legacy OptoControl Controllers:
G4LC32
G4LC32SX
G4LC32ISA
G4LC32ISA-LT
M4
M4IO
M4RTU
SNAP-LCM4
SNAP-LCSX/PLUS
Status and Activity LEDs
Indicator Description
TX0/RX0 Serial activity on port 0
TX1/RX1 Serial activity on port 1
TX2/RX2 Serial activity on port 2
TX3/RX3 Serial activity on port 3
STAT
ACT
Startup status and control program operational status
Ethernet network activity
LINK
WLAN
Link established with Ethernet network
Wireless LAN status
SNAP PAC S-Series User’s Guide
PAC S1 SERIAL WIRING DIAGRAMS
PAC S1 Serial Wiring Diagrams
Pin 1
NOTE: SNAP-PAC-S1 controllers support only 2-wire
RS-485.
Make sure to verify the location of pin 1, which is indicated on the controller with a label or a small triangle. To be certain of pin 1’s locations, insert the connector into the controller and then mark the location of pin 1 on the connector itself.
Wiring a PAC S1 Controller to SB-Series Brains
TX/RX +
TX/RX –
COM
9
10
7
8
5
6
3
4
1
2
PAC S1
Chassis GND
PAC SB
TX/RX +
TX/RX –
COM
2-wire, middle of link
All switches OFF
PAC SB
TX/RX +
TX/RX –
COM
2-wire termination, end of link
Switches 3 & 2 OFF
Switch 1 ON
Wiring a PAC S1 Controller to B3000 mistic Brains with an
Interrupt Line
TX/RX +
TX/RX –
COM +
IRQ +
IRQ –
9
10
7
8
5
6
3
4
1
2
PAC S1
Chassis GND
NOTE: To set bias and termination on a B3000-B, see Opto 22 form
1927, Configuring the B3000-B
.
B3000 B3000
28
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
PAC S2 Serial Wiring Diagrams
Make sure to verify the location of pin 1, which is indicated on the controller with a label or a small triangle. To be certain of pin 1’s locations, insert the connector into the controller and then mark the location of pin 1 on the connector itself.
Pin 1
Brains in the middle of the link should not be biased or terminated. The devices at both ends of the network should be terminated. In addition, the RS-485 link should be biased at one location only, which is typically at the controller.
PAC S2 Controller to B3000 mistic Brains with an Interrupt Line
Two-wire
5
6
7
3
4
1
2
PAC S2
TX/RX +
TX/RX –
COM
IRQ +
IRQ –
Chassis GND
NOTE: To set bias and termination
on a B3000-B, see form 1927,
Configuring the B3000-B
.
B3000 B3000
Four-wire
NOTE: The connector pins on an actual SNAP-PAC-S2 are in a different order than shown here.
2
6
3
1
7
4
5
PAC S2
RX+
RX-
COM
TX/RX +
TX/RX –
IRQ+
IRQ-
Chassis GND
NOTE: To set bias and termination
on a B3000-B, see form 1927,
Configuring the B3000-B
.
B3000 B3000
SNAP PAC S-Series User’s Guide
PAC S2 SERIAL WIRING DIAGRAMS
PAC S2 Controller to G4 mistic Bricks
To locate pin 1 on the PAC S2, see
.
See also, “Connectors, Indicators, and Pinouts” on page 24
.
PAC S2 to SBTA
5
6
7
2
4
3
1
PAC S2
COM
TX +
TX –
IRQ +
IRQ –
COM
TH
IRQ
SBTA connected to a G4 mistic brick
PAC S2 to G4TERMR or G4TERML
3
4
5
6
7
1
2
PAC S2
TX +
TX –
IRQ +
IRQ –
COM
TH+
TH–
IRQ+
IRQ–
COM
G4TERM connected to a G4 mistic brick
NOTE: For termination information, see form 595, the
Mistic Installation Guide
.
30
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
PAC S2 Controller to PAC SB-Series Brains
To locate pin 1 on the PAC S2, see
.
See also, “Connectors, Indicators, and Pinouts” on page 24
.
Two-wire
6
7
4
5
1
2
3
PAC S2
TX/RX +
TX/RX –
COM
TX/RX +
TX/RX –
COM
TX/RX +
TX/RX –
COM
Chassis GND
PAC SB
2-wire, middle of link
All switches OFF
PAC SB
2-wire termination, end of link
Switches 3 & 2 OFF
Switch 1 ON
Four-wire
NOTE: The connector pins on an actual SNAP-PAC-S2 are in a different order than shown here.
3
1
4
5
2
RX +
RX –
COM
TX/RX +
TX/RX –
TX/RX +
TX/RX -
COM
RX +
RX -
PAC S2
TX/RX +
TX/RX -
COM
RX +
RX -
Chassis GND
PAC SB
4-wire, middle of link
All switches OFF
PAC SB
4-wire termination, end of link
Switch 3 OFF
Switches 2 & 1 ON
Assigning an IP Address
See instructions in Opto 22 form 1704, the
PAC Manager User’s Guide
, to assign IP addresses to the
SNAP PAC S-series controller using a wired Ethernet connection. (If you are using redundant controllers, use the PAC Redundancy Manager utility instead of PAC Manager. The PAC Redundancy
Manager is part of PAC Project Professional 9.0 and newer.)
SNAP PAC controllers have two independent Ethernet network interfaces, labeled on the top of the controller as ENET1 and ENET2. Wired+Wireless PACs have a third network interface for the wireless
LAN. You can use these separate interfaces to segment the control network from the company network or for other purposes. Use PAC Manager to assign the secondary and wireless addresses and configure settings. Make sure each interface is on a separate IP subnet and receives a unique IP address.
SNAP PAC S-Series User’s Guide
ASSIGNING SERIAL PORTS ON SNAP-PAC-S2 CONTROLLERS
Assigning Serial Ports on SNAP-PAC-S2 Controllers
See instructions in Opto 22 form 1704, the
PAC Manager User’s Guide
, to configure serial ports for
SNAP-PAC-S2 controllers.
Each of the four serial ports on a SNAP-PAC-S2 can be configured either as an RS-232 serial port or an RS-485 serial port. Up to four ports on the SNAP-PAC-S2 can be used for I/O, and up to four ports can be used for general purpose serial communication. Only one port on the SNAP-PAC-S2 can be used for PPP communication.
By default the serial ports are as follows:
Port
0
1
2
3
Factory Default Mode
RS-232 (PPP)
RS-232 (not PPP)
RS-485 (2-wire 485 with termination and bias)
RS-485 (2-wire 485 with termination and bias)
32
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
Mounting the Controller
The SNAP PAC S-series controller can be panel mounted or mounted on a DIN rail. DIN-rail mounting requires an adapter clip, part number SNAP-PSDIN (not included).
Panel Mounting and Dimensions
SNAP-PAC-S1, SNAP-PAC-S1-FM, SNAP-PAC-S1-W
Use two screws on each side of the SNAP-PAC-S1 controller to mount it to a panel.
See the next page for antenna dimensions on the
SNAP-PAC-S1-W.
SNAP PAC S-Series User’s Guide
MOUNTING THE CONTROLLER
SNAP-PAC-S1-W Antenna Dimensions
34
SNAP PAC S-Series User’s Guide
SNAP-PAC-S2 and SNAP-PAC-S2-W
Use one screw on each side of the SNAP-PAC-S2 controller to mount it to a panel.
See the next page for antenna dimensions on the
SNAP-PAC-S2-W.
CHAPTER 2: QUICK START
SNAP PAC S-Series User’s Guide
MOUNTING THE CONTROLLER
SNAP-PAC-S2-W Antenna Dimensions
36
SNAP PAC S-Series User’s Guide
DIN-Rail Mounting and Dimensions
SNAP-PAC-S1, SNAP-PAC-S1-FM, and SNAP-PAC-S1-W
DIN-rail mounting requires an adapter clip, part number
SNAP-PSDIN (not included).
For DIN-rail mounting, remove the four screws that fasten the panel mounting base plate to the controller. Save screws.
Remove the base plate.
Use the four screws to fasten the DIN-rail adapter clip to the bottom of the controller, as shown.
Antenna dimensions for the SNAP-PAC-S1-W are on page 34 .
Optional DIN-rail adapter clip
CHAPTER 2: QUICK START
SNAP PAC S-Series User’s Guide
MOUNTING THE CONTROLLER
DIN-Rail Mounting and Dimensions (continued)
SNAP-PAC-S2 and SNAP-PAC-S2-W
DIN-rail mounting requires an adapter clip, part number
SNAP-S2DIN (not included).
For DIN-rail mounting, remove the four screws that fasten the panel mounting base plate to the controller. Save
screws. Remove the base plate.
Use the four screws to fasten the DIN-rail adapter clip to the bottom of the controller, as shown.
SNAP-PAC-S2-W antenna dimensions are on
38
SNAP PAC S-Series User’s Guide
CHAPTER 2: QUICK START
About the Controller’s Memory Map
Like SNAP Ethernet-based brains, a SNAP PAC S-series controller uses a memory mapped system for storing data and making that data available to other devices on the Ethernet network. This data includes configuration data, status information about the controller itself, and PAC Control strategy variable data that may be needed by a peer on the network.
Although SNAP PAC S-series controllers are designed to run PAC Control strategies, you can also write your own software applications to communicate with the controller’s memory map, either instead of or in addition to using PAC Control. You can use the OptoMMP Communication Toolkit or the IEEE 1394-based protocol for writing your applications. Both are explained in Opto 22 form 1465, the
OptoMMP Protocol Guide
, which also includes complete details of the memory map. Although this guide is written for I/O units, you can use the same information for a SNAP PAC S-series controller. Just be aware that many sections do not apply, since the controller’s memory map doesn’t include any I/O point or related information.
The SNAP PAC S-series controller’s memory map includes only the following areas:
Status Area Read
Communications Port Configuration
Date and Time Configuration
Status Area Write
Security Configuration
Scratch Pad
PPP Configuration
PPP Status microSD Card
IP Settings
WLAN Configuration
WLAN Status
Using Data for Peer-to-Peer Communication
Scratch Pad areas within the SNAP PAC S-series controller’s memory map provide a way for other devices on the Ethernet network to access data in the controller. For descriptions of the Scratch Pad areas—bits, integers, floats, and strings—see the PAC Manager User’s Guide. For help in using PAC
Control commands to access Scratch Pad areas, see “I/O Unit—Scratch Pad Commands” in Chapter
10 of the PAC Control User’s Guide.
If you are not using PAC Control but writing your own software applications to access the Scratch
Pad areas, see the OptoMMP Protocol Guide. This guide is written primarily for I/O units, but much of the same information on programming applies to SNAP PAC S-series controllers. The Scratch Pad areas of the memory map are described in the programming guide’s appendix.
If you’re communicating between an Allen-Bradley Logix-based PLC and an S-series PAC, see the
EtherNet/IP for SNAP PAC Protocol Guide.
SNAP PAC S-Series User’s Guide
WHAT’S NEXT?
What’s Next?
Your controller is now ready for use.
•
To create PAC Control strategies to run on the controller, see Opto 22 form 1700, the
PAC Control
User’s Guide
, and Opto 22 form 1701,
PAC Control Command Reference
. Both are available for download from the Opto 22 website at www.opto22.com
.
•
To securely access data from I/O points and variables in the PAC’s control strategy, visit developer.opto22.com
, where you’ll find instructions to set up the PAC’s HTTP/HTTPS server and complete documentation for the RESTful API.
•
See Opto 22 form 1704, the
PAC Manager User’s Guide
, for instructions to work with:
– Secondary and wireless network interfaces
– File system and FTP
– Security settings
– Port configuration
40
SNAP PAC S-Series User’s Guide
Chapter 3
3: Maintenance and
Troubleshooting
To troubleshoot problems that may have occurred, see “Troubleshooting,” below.
For maintenance information about the SNAP PAC S-series controller, see the section
“Maintaining the Controller” on page 46 .
Troubleshooting
If you encounter a problem while installing or using the SNAP PAC S-series controller, check the information in this section. To contact Opto 22 Product Support, see
Checking Power
When troubleshooting any problem with your controller, first check that the required power is correctly supplied.
IMPORTANT: The current version of the SNAP PAC S-series standalone controller requires 8–32 VDC power ,
not the 5 VDC power used by previous SNAP controllers and controller/brains. If you are replacing an older
SNAP controller or controller/brain with a SNAP PAC S-series controller, make sure that 8–32 VDC power is supplied. Note that S-series controllers with serial numbers below 500,000 use 8–24 VDC.
1.
Review the information in
“Power Supply Recommendations” on page 18
and the power requirements listed in
. Confirm that the power supply used with the SNAP PAC
S-series controller meets these requirements.
2.
Confirm that all leads connected to the controller and the power supply are securely attached.
These connections are described in “Installing Hardware” on page 18 .
3.
Verify that the controller’s ground terminal is connected to a known chassis ground as
described in “Installing Hardware” on page 18 .
4.
Confirm that two Phillips-head screws are installed on the wide sides of the case, one screw per side. (These screws secure and ground the controller’s internal components.)
Communicating on a Wired Ethernet Network
If you attempt to connect to the controller using its IP address and you cannot, first check the following:
SNAP PAC S-Series User’s Guide
TROUBLESHOOTING
•
Make sure the controller has been turned on, the STAT LED is lit and not blinking, and the LNK
LEDs for the connected Ethernet interfaces are lit. (See LED information on pages
Indicators, and Pinouts” on page 24
.)
•
Verify that you typed in the correct address for the controller. Check the label on the side of the controller, where the IP address should be written.
•
Make sure the controller has been assigned a valid IP address and subnet mask. SNAP PAC
S-series controllers come from the factory with a default IP address of 0.0.0.0, which is invalid.
The default subnet mask is 255.255.255.0. To assign IP address and subnet mask, see the PAC
Manager User’s Guide.
•
Make sure you have up-to-date drivers installed on your computer’s Network Interface Card
(NIC). Contact your system administrator or the manufacturer of the card for help.
•
Make sure any firewall in the computer (such as the built-in firewall in Windows XP) is temporarily disabled before you try to assign or change IP addresses, load firmware using PAC
Manager’s Maintenance window, or work with files on the controller. BootP and FTP cannot function through a firewall in the PC. Firewalls in a router are less likely to be a problem unless certain ports (such as FTP client) have been blocked, either by default or on purpose.
Pinging the Controller
If you still cannot communicate with the controller after you have checked these items, try to reach it using the PING application.
1.
Choose Start
Run and type cmd to open a command prompt.
2.
At the prompt, type:
ping [controller’s IP address]
For example, type:
ping 10.192.54.40
At this point be sure to check for other devices on the Ethernet network that may have the same IP address.
If the controller responds, go to
“Maintaining the Controller” on page 46
.
If the PING command cannot be found, choose Start
Control Panel
Network. Make sure
TCP/IP is configured as a protocol and that an IP address and subnet mask are assigned.
If you see the message “Destination host route not defined,” the controller probably has an inappropriate IP address and subnet mask. Make sure the IP address and subnet mask on the controller are compatible with those on the computer. Follow directions in the PAC Manager User’s
Guide to check the IP address and subnet mask on the controller and change them if necessary.
If you see the message “No response from host,” check the following:
•
Are the computer and controller correctly connected? Is the controller turned on?
•
Are the IP address and subnet mask on the controller compatible with those on the computer?
•
Is the controller in bootloader mode? (If the reset button is held down for too long, the controller will enter bootloader mode, which is indicated by the STAT LED blinking seven times quickly.)
If you still cannot ping the controller, contact Opto 22 Product Support. (See
for contact information.)
42
SNAP PAC S-Series User’s Guide
Ethernet Errors
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
Solving Network Problems
If there are recurring problems in communicating with the controller, check your network. The wires, switches, and other parts in your Ethernet network are not part of the Opto 22 hardware, but any problems in your network may affect communication with Opto 22 products.
Create a Network Diagram
First, create a network diagram and verify the following:
•
Cable connectors are firmly inserted.
•
The switch has power. Switch LEDs indicate that the connection is up.
•
Neither the PC nor the controller unit uses the switch’s uplink port.
•
The controller’s LNK LED is lit.
Check Ethernet Errors
Next, use PAC Manager to check any Ethernet errors reported. These errors indicate network problems. You will need to know the controller’s IP address.
1.
Choose Start
Programs
Opto 22
PAC Project Software
PAC Manager.
2.
In the PAC Manager main window, click the Inspect icon .
3.
In the IP Address field, type the IP address of the controller. Click Status Read.
4.
Scroll down until you see the items Ethernet Errors: Late Collisions, Ethernet Errors: Excessive
Collisions, and Ethernet Errors: Others.
All three of these items should have a value of zero. If any of these items has a value other than zero, you may have a network problem.
SNAP PAC S-Series User’s Guide
TROUBLESHOOTING
Analyze Communication Packets
If it appears that you have network problems, Opto 22 recommends using the open-source network protocol analyzer (or “packet sniffer”) Wireshark (www.wireshark.org) to log and analyze network communication packets on your network.
Have Your Network Certified
If you suspect network problems, you may need to have your network professionally certified.
Opto 22 does not offer network validation or certification services, but many network hardware manufacturers do. Contact the manufacturer of your Ethernet network hardware to have them diagnose, fix, and certify your network.
If you continue to have problems communicating with the controller or I/O units after your network is certified, contact Opto 22 Product Support. (See
TCP Settings
Retransmit timeout (RTO) refers to the length of time the controller waits while communicating before timing out. The RTO is determined by the controller’s TCP/IP stack, and the stack continually recalculates the RTO based on recent network traffic. If the network becomes busier, for example, the stack automatically adjusts the RTO to a higher value.
If the TCP/IP stack times out while trying to transmit data, it doubles the current RTO and tries again.
This process continues for five retries; after that, the controller stops trying and sends a timeout message.
If you are receiving frequent timeout messages from the SNAP PAC S-series controller, you can change the TCP parameters in PAC Manager.
1.
Choose Start
Programs
Opto 22
PAC Project Software
PAC Manager.
2.
In the PAC Manager main window, click the Inspect icon .
3.
In the IP Address field, type the IP address of the controller. Click Status Write.
44
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
CAUTION:
Note the following recommended settings:
TCP Minimum Retransmission Timeout (msec):
TCP Initial Retransmission Timeout (msec):
TCP Retransmission Attempts:
TCP Idle Session Timeout (msec):
250
3000
5
240,000
If you set these fields too low, you may not be able to communicate with the controller at all, even though PAC Manager, to fix the settings. Then you would have to reset the controller to factory defaults.
4.
Change these four fields as necessary:
TCP Minimum Retransmission Timeout sets an absolute minimum value for the RTO. The controller’s calculated RTO will never go below this value.
TCP Initial Retransmission Timeout sets the RTO for the first communication try. Be careful: since all future tries are based on this value, if you set it too low for network conditions, a connection will never be made.
TCP Retransmission Attempts sets the number of times the controller retries communication. Larger, busier networks need a higher number of retransmits than smaller networks with less traffic.
TCP Idle Session Timeout sets how long (in milliseconds) the controller allows a session to remain open without any activity. After this time, the controller closes the unused session. The default is 240,000 milliseconds, or four minutes.
5.
Click the Apply button to write your changes to the controller.
6.
In the Operation Commands list, highlight Store configuration to flash. Click Send Command.
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
7.
In the Operation Commands list, highlight Restart I/O Unit from powerup. Click Send
Command.
The new TCP parameters are set.
Communicating on a Serial Network
If a SNAP PAC S-series controller fails to connect using either an RS-232 serial interface for PPP host communication or an RS-485 serial interface for I/O unit communication, check the following:
Indicators—Depending on the port(s) being used on a SNAP-PAC-S1 controller, LED S0, S1, or S2 should be red (for receive data) and green (for transmit data). On a SNAP-PAC-S2, there are separate
LEDs for Transmit and Receive for each port. Green indicates activity.
Power—Make sure that both the controller and the device it is connected to have been turned on.
Physical Connections—Check that the connectors on each end of the serial link are firmly attached to the controller and the other connected device.
RS-232 Configuration—RS-232 communication on a SNAP PAC S-series controller is configured using PAC Manager software, and ports must be configured correctly for their use, or they won’t work. See “Configuring Direct Communication to Serial Devices” in the PAC Manager User’s Guide.
NOTE: Port 0 is set by default to communicate using PPP. If you’re connecting to serial devices with Port 0, you must change its configuration in PAC Manager.
RS-485 Configuration—On a SNAP-PAC-S1, RS-485 serial network bias and termination are configured using DIP switches on the top of the unit. Confirm that DIP switches are set to the correct positions for the controller’s location in the RS-485 network. See
“RS-485 Connections” on page 20
for information. On a SNAP-PAC-S2, all port configuration is performed using PAC Manager. For details, see Opto 22 form 1704, the
PAC Manager User’s Guide
.
Maintaining the Controller
Backup Battery
SNAP-PAC-S1 controllers with a serial number of 625654 or higher, and all SNAP-PAC-S2 controllers, have a rechargeable battery that receives charging current whenever the brain has power. It will retain data for up to one year with the power off.
SNAP-PAC-S1 controllers with a serial number of 625653 or lower have a user-replaceable 3.6-volt TL
5242 /W lithium battery that will retain data for a minimum of 10 years. Replacement part number is
G4BATT32.
Getting Device and Firmware Information
If you need to contact Opto 22 Product Support for assistance in using a controller, it is helpful to have device and firmware information at hand before you call.
1.
Choose Start
Programs
Opto 22
PAC Project Software
PAC Manager.
46
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
2.
In the PAC Manager main window, click the Inspect icon .
3.
In the IP Address field, type the IP address of the device. Click Status Read.
This example shows a SNAP-PAC-S1; other devices are similar.
Keep this window open on your screen when you call Product Support. See the note on the next page.
NOTE: Because the Status Read area is used for both standalone controllers and Ethernet-based I/O units, some items apply to some devices and not others. The following items do not apply to standalone controllers:
Degrees F/C
Comm Watchdog Time (msec.)
Scanner Flags
Digital Scan Counter
Analog Scan Counter
PID Loops
Smart Modules Present
Arcnet data
Digital resets and failures since powerup
For detailed information about items in the Status Read area, see the PAC Manager User’s Guide.
Changing the Controller’s IP Address
If you know the SNAP PAC S-series controller’s IP address, see the PAC Manager User’s Guide for instructions to change it. (If you are using redundant controllers, use the PAC Redundancy Manager instead of PAC Manager.)
If you do not know the IP address, first check the label on the side of the controller in case the IP address has been written there. If you still don’t know the controller’s IP address, reset the controller
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER to factory default settings following the instructions in
“Resetting the Controller” on page 48 and
then set the IP address as described in the PAC Manager User’s Guide.
Resetting the Controller
1.
Carefully insert a straightened paperclip or stiff wire into the small hole labeled RESET. Inside the hole you can feel the paperclip push down on a button that resets the controller.
CAUTION:
Do not power on the controller while holding down the reset button. This will deactivate battery power, which will cause the loss of contents in battery-backed RAM and stop the real-time clock.
2.
Depending on the type of reset you need, press and hold down the reset button as described below. DO NOT hold the button down too long.
NOTE: Do not reset the brain to hardware test mode unless Opto 22 Product Support tells you to.
Reset type
Simple reset
Restore factory defaults
Failsafe bootloader mode
How to use the reset button
Press and release immediately
What happens
Controller restarts.
Any files and the strategy are erased unless they have been stored to flash memory. Archived strategies are not erased.
Notes
Press just until STAT LED turns solid green (1-2 sec)
Controller restarts.
If a microSD card is present and contains configuration, firmware, and/or strategy files—Files on the microSD card overwrite what is in flash memory and other files in flash memory are not erased.
Data files on the card are not affected.*
If no microSD card is present containing configuration, firmware, or strategy files—All files, strategy, archived strategy, persistent variables, and
I/O configuration are erased from RAM and flash memory, and IP addresses are reset to 0.0.0.0 and subnet masks to 255.255.255.0.
If no microSD card is present containing configuration, firmware, or strategy files, you must reassign the IP address and subnet mask.
Press and wait while LED turns solid green. Release when LED starts to blink (2-5 sec)
Controller restarts.
Any files and the strategy are erased unless they have been stored to flash memory. Archived strategies are not erased.
Cycle power to recover.
Result is the same as a simple reset.
Hardware test mode
Press and hold until LED starts blinking orange rapidly and continuously (> 5 sec)
Controller restarts.
Any files, strategy, archived strategy, and persistent variables in RAM and flash memory are erased. I/O configuration in flash is erased
(R-series).
Data files on a microSD card are not affected.
IP addresses are reset to 0.0.0.0 and subnet masks to 255.255.255.0.
To recover, restore to factory defaults as described above. You also must reassign the IP address and subnet mask.
* Example of Restoring factory defaults when a microSD card is present: Suppose the card contains a firmware file but no configuration or strategy files. Restoring to factory defaults will leave the controller with the firmware from the card and configuration and strategy files from flash memory. You will not have to reassign an IP address or download a strategy.
48
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
Loading New Firmware
Each SNAP PAC S-series controller contains firmware (sometimes referred to as the kernel), which is similar to an operating system. If the firmware should become damaged, or if a new version of the firmware is released, you can load new firmware to the controller following instructions in the PAC
Manager User’s Guide. You can also load new firmware via the microSD card, if the controller has one.
See “Updating Firmware” on page 49 .
CAUTION: Loading new firmware deletes your PAC Control strategy (even if stored to flash
memory) and your persistent variables. Make sure you have
archived your strategy before
loading new firmware.
Using the microSD Card Slot
SNAP PAC controllers with a manufacturing date code of 11/08 (November 2008) and newer have a microSD card slot in the top of the controller’s case. On a controller with a microSD card slot, the STAT LED blinks briefly about once every five seconds, indicating that the controller is checking to see if a card is in place.
IMPORTANT:
Since the first release, card behavior has changed. If you are using firmware older than
9.0a, follow instructions in form 2018, Using microSD with Older Controller Firmware Technical Note,
instead of this document.
To determine firmware version, see page 53
. To download the latest firmware (recommended), go to www.opto22.com/site/downloads and filter by Firmware.
Card Type and Format
Use only cards with the microSD or microSDHC logos (shown above right). Also, be aware that card capacity, formatting, and filename limits vary depending on your controller, its firmware and loader, and the card type you are using:
Controller firmware
Firmware 9.4a or higher
and
loader 6.1a or higher
Compatible cards
microSDHC microSD
Card format
FAT32
FAT32 or FAT16
Max card capacity
32 GB
2 GB
Filename limits
Long names OK
Long names OK
9.0a to 9.3e
Lower than 9.0** microSD microSD
FAT16
FAT16
2 GB
2 GB
8 dot 3*
8 dot 3*
* All files stored on the microSD card must be named with a maximum of eight characters in the name plus three characters in the extension (8 dot 3 format), for example: datafile.txt
** The card behaves differently using firmware lower than 9.0. Follow instructions in form 2018,
“Using microSD with Older Controller Firmware Technical Note,” instead of this document.
IMPORTANT: Minimum controller firmware version R9.4a and loader version R6.1a are required to use microSDHC cards. For more information, see OptoKnowledgeBase article KB83929 .
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
MicroSD/SDHC Card Uses
Note minimum requirements in the table above. The card can be used for several purposes:
•
To store data or files, which you can access using PAC Control commands or an FTP client. (PAC
Manager cannot be used to access data, because it cannot see the card’s directory.)
•
To quickly commission a replacement controller in the unlikely event that a controller fails.
•
To update firmware on the controller. The card provides a convenient way to update firmware on non-networked controllers. It’s also useful if PAC Manager is not available to update firmware.
•
To temporarily boot the controller from firmware on the microSD card rather than from the firmware in the controller, for example to test new firmware.
•
To update, run, or test new PAC Control strategies if the controller is not on the network, if PAC
Control isn’t available, or if you want to test a new strategy without erasing the existing one.
The following table summarizes how to use the card; see the page in the last column for steps.
To do this
Store/access data
Replace failed controller using a prepared card
Try out controller firmware without replacing current firmware
When
Anytime
In advance
Put card in...
Controller
Use this method
Automate data storage and retrieval in PAC
Control logic: Use PAC Control commands and file communication handles. Or use PAC Control FTP communication handles.
See pg
Controller
1
PC with card reader
From a PC, use an FTP client.
Use Windows Explorer.
Controller
1
PC with card reader
1. Use PAC Manager Inspect window to store
IP address and configuration data to card.
2. Use PAC Control to make controller download (.cdf) file.
3. Create a command file to load firmware.
4. Copy .cdf file, command file, and firmware file to card.
If controller fails
In advance
To use
Controller
Controller
1. Replace failed controller with a new one
(must be exactly same part number; must have minimum firmware 9.x and loader 6.x).
2. Insert prepared card and turn on power.
3. Use controller’s Reset button to reset to defaults from card. Strategy is saved to flash memory.
Controller
1
or
PC with card reader
Use Windows Explorer or FTP client to copy new firmware to card.
Insert prepared card into controller and cycle power. Controller runs firmware on card.
To go back to older firmware, remove card and cycle power again.
50
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
To do this
Try out new strategy without replacing current strategy
4
Update non-networked controller with new firmware
4
When
In advance
To use
In advance
To use
Put card in...
Controller
Use this method
Controller
1
or
PC with card reader
Use PAC Control to make controller download
(.cdf) file; then use Windows Explorer or FTP client to put .cdf file on the card.
Insert prepared card into controller and cycle power. Controller runs strategy from card.
To go back to older strategy, remove card and cycle power again.
PC with card reader
Create command file; copy it and the firmware file to card.
Controller
Insert card into controller.
Controller runs firmware from card until reset.
Use controller’s Reset button to save firmware to flash.
2
See pg
In advance
PC with card reader
Use PAC Control to make controller download
(.cdf) file; then use Windows Explorer to copy
.cdf file to the card.
Update non-networked controller with new strategy
4
To use Controller
Insert card into controller and cycle power.
Controller runs new strategy from card until reset. Use controller’s Reset button to save strategy to flash memory.
2, 3
1 Controller must be on same network segment as PC.
2 CAUTION: Before resetting, make sure you know what is on the card! ALL IP address and configuration information, firmware, and strategy that exist on the card are saved to flash memory.
3 If you have firmware 9.x but a loader older than 6.x, the controller runs the new strategy from card until reset, but the strategy cannot be saved to flash memory.
4 CAUTION: Persistent variables will be deleted.
Storing and Accessing Data or Files
When inserted into the controller and accessed from a PC using FTP or PAC Control, the card appears as a directory in the controller’s file system named:
sdcard0
Just like a PC might show a thumb drive as a directory named Removable Disk (E:), for example, the controller shows the card as a directory named sdcard0.
IMPORTANT:
Do NOT try to create this directory. When you look at the card in the controller, the card appears as a directory named sdcard0. When you look at the card in a card reader attached to your PC, you see the card reader’s directory instead. When the card is in a card reader, you are already in the root of the card (that is, you are already inside the sdcard0 directory).
For example, suppose you are looking at a card in a SNAP PAC controller with IP address
10.192.54.241. You can see that this controller has three files in its regular file system, plus the card:
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
Files in PAC’s file system microSD/SDHC card
Within the
sdcard0 directory on the controller (or the root if the card is in a card reader), you can create other directories and create or add files. For a card formatted with FAT16, you can have up to
512 files or directories in the root directory, and each subdirectory can have up to 65,534 files. Cards formatted with FAT32 have no restrictions on the number of files in the root. Note filename requirements in
“Card Type and Format” on page 49
.
When the card is in the controller, you can access files on the card through PAC Control commands and from a PC using FTP.
Use PAC Control commands just as you would with any other file in the controller’s file system. For help, see Chapter 10, “Using the Control Engine’s File System” in form 1700, PAC Control User’s Guide.
Remember to include the card’s directory name in the path in the file communication handle, for example:
file:a,/sdcard0/VoltLog.txt
Note that the path separator is a forward slash (/), not a backward slash (\).
You can also use the FTP communication handle in PAC Control to manipulate files. See the section
“Moving Files via FTP,” also in Chapter 10 of the PAC Control User’s Guide.
To move files to or from a PC, use any standard FTP software. (Don’t use PAC Manager as the FTP client, as it cannot see directories within the controller’s file system). Remember to include the card’s directory name, for example: ftp://192.168.1.1/sdcard0/
NOTE: If you access the card when it is not in the controller (for example, in a card reader), the sdcard0
directory does not appear. Do NOT create it. The controller treats the card as a folder in the controller’s file system.
Displaying Free Space on the Card
If you need to know how many free bytes are left on a microSD/SDHC card, you can use PAC Control or PAC Manager to read this data from an address in the controller’s memory map. In a PAC Control strategy, for example, you could notify an operator if the card needs replacing, based on the number of bytes still unused.
1.
Make sure the card is in the controller.
52
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
2.
In PAC Control, use the command Read Number from I/O Unit Memory Map to read memory map address F7002204. Use Integer 32 Variable in Argument 2.
For more information, see “I/O Unit—Memory Map Commands” in Chapter 10 of the PAC
Control User’s Guide, and see “Read Number from I/O Unit Memory Map” in the Command
Reference or Help.)
3.
In PAC Manager, open the Inspect window for the controller. Click Other and choose Generic
Read/Write from the popup menu. In the Address field, type F7002204. From the Type dropdown list, choose 32-bit Integer. Leave the Length as 1. Click Refresh.
The number of bytes appears in the Value column.
Checking Firmware and Loader Versions
Compatible cards and card functions depend on the controller’s firmware and loader versions. Here’s how to check them. The controller must be on the same network segment as the PC with PAC
Manager.
1.
Open PAC Manager and click the Inspect icon .
2.
In the Device Name field, enter the controller’s name or IP address, or choose it from the dropdown list. Click Status Read.
Loader and firmware version numbers appear near the center of the window:
New firmware versions and some new loader versions are available from our website, www.opto22.com. To update the loader, see form 1789,
Updating the Loader on a SNAP Device
.
For firmware, see “Loading New Firmware” on page 48
“Loading New Firmware” on page 49 .
Contact Opto 22 Product Support with any questions.
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
Replacing a Controller
A microSD/SDHC card can be used to quickly commission a replacement controller in the unlikely event that an existing controller fails. The card rapidly configures the replacement with the original controller’s IP address, firmware, configuration, and strategy.
Preparing the card requires PAC Manager 9.0 or higher. You must prepare the card in advance and then keep it in a safe place in case the controller fails.
The replacement controller must have exactly the same part number as the old controller (for example, a SNAP-PAC-S1-W must be replaced by a SNAP-PAC-S1-W), and it must have minimum
firmware 9.0a and loader 6.0a. See page 53 to check versions.
CAUTION:
Use the commissioning card only to replace a controller; it assigns the new PAC controller the same IP address as the old one.
Prepare the Card In Advance.
1.
Put a blank card into the controller that you may need to replace.
2.
Copy configuration data as follows:
a.
Open PAC Manager if needed. In the main window, click the Inspect icon .
b.
In the Device Name field, type the name (or IP address) of the device. Click Status Write.
c.
In the Operation Command list, highlight Store configuration and IP settings to microSD.
d.
Click Send Command.
The controller’s IP settings and all configuration data are saved to the card in a file located at /sdcard0/opto22/config/config.cfg.
3.
Prepare the strategy file:
54
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
a.
Open your strategy in PAC Control. In Configure mode, choose File
Strategy Options. Click the Download tab.
b.
Check the Set autorun flag after download box. Click OK.
c.
Choose one of the following:
– If you’re using Secure Strategy Distribution (SSD), follow steps in form 1762,
PAC Terminal SSD Technical Note, to create a download file with the file extension .ssd.
– Otherwise, compile the strategy as a Control Engine Download file (.cdf ) by right-clicking the name of the control engine in the Strategy Tree and choosing
Compile Control Engine Download File from the pop-up menu.
The file is created in the same folder as the strategy, with a .cdf extension and a filename consisting of the strategy’s name and the control engine’s name (for example,
MyStrategy.MyEngine.cdf ).
d.
(Firmware below 9.4a only): Rename the .cdf or .ssd strategy file to fit the 8 dot 3 filename format for the microSD card (see
“Card Type and Format” on page 49
).
IMPORTANT:
You must retain the correct file extension (.cdf or .ssd).
4.
Remove the card from the controller and put it in a card reader attached to the PC. Prepare the firmware file:
a.
Locate the firmware file you want to upgrade to.
b.
(Firmware below 9.4a only): Rename the file to fit the 8 dot 3 filename format.
For this file, do not keep the same file extension. Recommended naming scheme:
PPP-TMM.mmb where:
PPP
T
MM mm b
= controller type (R1, R2)
= R for release (or B for beta)
= major revision number
= minor revision number
= build letter
Example of an original firmware filename:
snap-pac-r2-R9.0a.bin
Example of the same firmware file, renamed:
R2-R9.0a
5.
Create the firmware command file:
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
a.
Using Notepad or a similar editor, create a text file named:
command
In the
command file, type the following command (CASE SENSITIVE):
Krn <file>
<file> is the firmware path and filename as the card sees it, so do not include the sdcard0 directory in the path. If you’re using Secure Strategy Distribution, <file> must include a valid signature. Here is a sample command file:
Krn R2-R9.0a
b.
In Windows Explorer, delete the
.txt extension from the command file. Then right-click the command file filename and choose Properties. In the General tab, click to put a checkmark in the Read-only box. Click OK.
6.
Copy files to the card:
a.
Copy the command file to the
sdcard0 directory in the controller’s file system.
b.
Copy the firmware file to the
sdcard0 directory. This directory must contain only one firmware file.
c.
In the
sdcard0 directory on the card, create a new directory and name it:
strategy
Copy the renamed strategy file (.cdf or .ssd) to the
sdcard0/strategy directory.
The card is now ready to be used as a commissioning card to replace the controller.
Replacing the Failed Controller.
Before you start, make sure that the replacement controller:
•
Has exactly the same part number as the old controller (for example, a SNAP-PAC-S1-W must be replaced by a SNAP-PAC-S1-W)
•
Has minimum firmware 9.0a and minimum loader 6.0a. To check firmware and loader versions in
PAC Manager, see page 53 . You can download new firmware from our website; if you need a
newer loader, contact Product Support.
Follow these steps to replace the failed controller:
7.
Turn off the controller that failed. Put the new controller in its place but DO NOT apply power.
Attach network cables.
8.
Insert the prepared microSD/SDHC card and turn on power to the controller.
9.
Without waiting, carefully insert a straightened paperclip or stiff wire into the small hole on the controller labeled R
ESET
.
Press and hold the Reset button just until the STAT LED turns solid green, and then immediately release the button.
The IP address is assigned to the controller, and firmware, configuration data, and strategy are loaded into RAM, in that order.
– In firmware 9.2c and newer, IP address, firmware, configuration, and strategy are stored to flash and the controller reboots running the new firmware. The STAT LED blinks steadily during this process and then blinks two sets of three blinks—green to indicate success, or red to indicate failure.
– In firmware 9.0–9.2b, IP address, firmware and configuration are stored to flash and the controller reboots running the new firmware and loads the new strategy. To store the strategy to flash, use the Reset button again in exactly the same way.
When finished, a folder named
backup is placed in the root directory of the card. The controller restarts.
56
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
10.
Wait until the STAT LED blinks only once every five seconds, and then remove the card.
Updating Firmware
The card can also be used to update firmware if the controller is not on the network, or if PAC
Manager isn’t available.
CAUTION:
Before updating firmware, make sure you know what is on the card! Any IP address, configuration data, and strategy on the card will be saved to flash memory along with the firmware. If you want only the firmware saved, delete configuration and strategy files from the card.
CAUTION:
Updating firmware deletes your PAC Control strategy (even if stored to flash memory) and your persistent variables. Make sure you have
archived
your strategy before loading new firmware.
1.
Obtain the correct firmware file from our website, www.opto22.com. If you are using Secure
Strategy Distribution (SSD), the firmware must have the correct signature.
2.
(Firmware below 9.4a only): Rename the firmware file to fit the 8 dot 3 filename format (see
“Card Type and Format” on page 49
).
The original file extension does not have to be retained. To make sure the file is clearly identified, we recommend a name such as the following:
PPP-TMM.mmb where:
PPP
T
MM mm b
= controller type (R1, R2)
= R for release (or B for beta)
= major revision number
= minor revision number
= build letter
Example of an original firmware filename:
snap-pac-r2-R9.0a.bin
Example of the same firmware file, renamed:
R2-R9.0a
3.
Copy the firmware file to a blank card. If you don’t have a blank card, delete the following directories and their contents if they appear on the card:
/sdcard0/strategy
/sdcard0/boot
/sdcard0/opto22/config
You can write to the card in one of two ways: either use your PC to FTP files to the card in the controller, or use a card reader with your PC and simply copy files with Windows Explorer.
4.
Using Notepad or a similar text editor, create a command file named
command.txt and save it in the root directory of the card. (If you are looking at the card in a card reader, save it in the root directory. If you are looking at the card in the controller, save it in the directory named sdcard0
).
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
5.
In the
command file, include the following command. All commands are CASE SENSITIVE.
To do this
Install controller firmware
Use command
Krn <file>
Details
<file> is the firmware path and filename as the card sees it, so do not include sdcard0 directory in the path. The firmware file can be compressed in gzip format or uncompressed.* If you’re using Secure Strategy Distribution,
<file> must include a valid signature.
NOTE: Controller firmware will be installed only if it differs from the current firmware.
* To gzip a file on Windows, use the utility at http://gnuwin32.sourceforge.net/packages/gzip.htm
.
SNAP PAC cannot decompress files that were compressed with WinZip
The following sample command file updates firmware on the controller.
Krn R2-R9.0a
6.
In Windows Explorer, delete the
.txt file extension from the file so that the complete filename is only:
command
Then right-click the command file and choose Properties. In the
General tab, click to put a checkmark in the Read-only box. Click OK.
CAUTION:
Make sure you know what is on the card before updating firmware! Any IP address, configuration, or strategy data that exists on the card will also be saved to flash memory along with the firmware.
7.
To update firmware, insert the card in the controller’s card slot. Carefully insert a straightened paperclip or stiff wire into the small hole on the controller labeled R
ESET
.
Press and hold the
Reset button just until the STAT LED turns solid green, and then immediately release the button.
Firmware is updated and saved to flash memory. (If IP address, configuration, or strategy files are on the card, they are also saved to flash memory.) When finished, a file named
response is placed in the root directory of the card; this file indicates the success or failure of commands in the command file. Then the controller restarts.
8.
Wait until the STAT LED blinks only once every five seconds, and then remove the card.
Booting from Firmware on the Card
You can also boot the controller from firmware on the card, rather than from the firmware in flash memory, for example to test new firmware before updating it on the controller.
You can write to the card in one of two ways: either use your PC to FTP files to the card in the controller, or use a card reader with your PC and simply copy files with Windows Explorer.
NOTE: Controllers configured for Secure Strategy Distribution (SSD) cannot boot from the card.
1.
Locate the firmware file you wish to boot from.
2.
58
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
Recommended naming scheme:
PPP-TMM.mmb where:
PPP
T
MM mm b
= controller type (R1, R2)
= R for release (or B for beta)
= major revision number
= minor revision number
= build letter
Example of an original firmware filename:
snap-pac-r2-R9.0a.bin
Example of the same firmware file, renamed:
R2-R9.0a
3.
Create a directory on the card in the root and name it:
boot
Remember, if you are looking at the card in the controller, you create the
boot directory in the sdcard0 directory. If you are looking at the card in a card reader, create the
boot directory at the top level. The controller’s file system treats the card as a directory named sdcard0.
4.
Copy the renamed firmware file to the
sdcard0/boot directory on the card.
Here’s how it might appear if you are looking at the card in the controller:
IMPORTANT:
The boot directory must contain only one firmware file. If it contains more than one, the wrong firmware may be loaded.
5.
If the card contains a command file or any other firmware files, delete them.
6.
To boot the controller from firmware on the card, turn the controller off and insert the card in the controller’s card slot. Turn the controller back on. (Or insert the card and then quickly push and release the controller’s Reset button.)
If the boot directory exists on the card, the STAT LED blinks green three times, quickly. Firmware is loaded. If the STAT LED blinks red, see “Blink Codes” in this chapter to determine the problem.
If the STAT LED blinks green two times, either the boot directory is not present, the firmware file is invalid or does not match the controller, or the controller is an SSD controller.
When the STAT LED no longer blinks steadily, but blinks only once every five seconds, you can remove the card. When the card is removed, the controller continues running the firmware on the card until power is cycled or the controller is reset. If you need to know whether the
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER controller booted from the card or from flash memory, use PAC Manager’s Inspect window to check the Status Read area. See the PAC Manager User’s Guide for instructions.
Updating, Running, or Testing a Strategy
The card can also be used to update, run, or test a PAC Control strategy. This ability is useful when the controller is not on the network or PAC Control isn’t available. Both regular strategies and Secure
Strategy Distribution (SSD) strategies can be used.
You can write to the card in one of two ways: either use your PC to FTP files to the card in the controller, or use a card reader with your PC and copy files with Windows Explorer.
CAUTION:
Before saving to flash memory, make sure you know what is on the card! ALL IP address, configuration data, and firmware on the card will be saved to flash along with the strategy. If you want only the strategy saved, delete configuration and firmware files from the card.
1.
In PAC Control Configure mode, choose File >
Strategy Options. Click the Download tab.
2.
If you want to set the strategy to autorun, check the box Set autorun flag after download.
Autorun works if you insert the card and then turn on the controller; it has no effect if you insert the card when the controller is already turned on. (If the controller is already turned on, the new strategy follows the status of the existing strategy: if the existing strategy was running when the card was inserted, the new strategy will run; otherwise, it will not.)
If you use background downloading, the controller will switch to the new strategy when the card is inserted.
3.
Click OK.
4.
Choose one of the following:
a.
If you’re using Secure Strategy Distribution, follow steps in form 1762, PAC Terminal SSD
Technical Note, to create a download file with the file extension .ssd.
b.
Otherwise, compile the strategy as a Control Engine Download file (.cdf ) by right-clicking the name of the control engine in the Strategy Tree and choosing Compile Control Engine
Download File from the pop-up menu.
60
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
The file is created in the same folder as the strategy, with a .cdf extension and a filename consisting of the strategy’s name and the control engine’s name (for example,
MyStrategy.MyEngine.cdf ).
5.
(Firmware below 9.4a only): Rename the .cdf or .ssd strategy file to fit the 8 dot 3 filename
format for the microSD card (see “Card Type and Format” on page 49 ).
IMPORTANT:
You must retain the correct file extension (.cdf or .ssd).
6.
Create a directory on the card in the root and name it:
strategy
Remember, if you are looking at the card in the controller, you create the
strategy directory in the
sdcard0 directory. If you are looking at the card in a card reader, create the
strategy directory at the top level. The controller’s file system treats the card as a directory named sdcard0.
7.
Copy the renamed strategy file to the
sdcard0/strategy directory on the microSD card.
Here’s an example of a strategy file in the strategy directory, looking at the card in the controller:
Strategy file
8.
If you plan to save the strategy to flash memory, delete the following files and directories if they are on the card:
Command file and firmware files
/sdcard0/boot
/sdcard0/opto22/config
NOTE: If the controller has firmware 9.0a or newer and a loader version older than 6.0a, you cannot save the strategy from the card to flash memory.
9.
To update, run, or test the strategy, turn off the controller, put the card in, and turn the controller back on.
The controller loads the strategy from the card (verifying the signature if it is an .ssd file), switches to the new strategy if you’re using background downloading, and runs the new
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER strategy if you set it to autorun. If it’s not set to autorun, you can start the strategy manually using PAC Control or PAC Terminal.
The STAT LED blinks steadily while the strategy is loading and then blinks two sets of three blinks—green to indicate success, or red to indicate failure. When the STAT LED no longer blinks steadily, but blinks only once every five seconds, it has finished.
10.
If you want to save the strategy to flash memory, carefully insert a straightened paperclip or stiff wire into the small hole on the controller labeled R
ESET
.
Press and hold the Reset button just until the STAT LED turns solid green, and then immediately release the button.
The strategy is saved to flash memory. (If IP address, configuration, or firmware files are on the card, they are also saved to flash memory.) Then the controller restarts.
11.
Wait until the STAT LED blinks only once every five seconds, and then remove the card.
Disabling or Enabling Firmware and Strategy Updates Via the Card
If you do not want anyone to be able to update firmware or strategies using a microSD/SDHC card, you can disable this feature in the controller. (Enabled is the default.)
1.
In PAC Manager, open the Inspect window for the controller.
2.
Click Other and choose Generic Read/Write from the popup menu.
3.
In the Address field, type F7002200. Choose 32-bit Integer as the Type.
4.
To disable firmware/strategy updates: In the Value column next to the address, type
0
(zero).
Click Apply.
5.
To enable firmware/strategy updates: In the Value column, type any value other than zero and click Apply.
Setting Time and Date
The SNAP PAC S-series controller’s built-in clock is set at the factory. To change the time and date, see the instructions in the PAC Manager User’s Guide.
STAT LED Blink Codes
The STAT LED on the top of the SNAP PAC S-series controller uses blink codes to indicate controller operation and status conditions. The blink codes can be useful during operation and in troubleshooting. When the STAT LED is on and remains green, it indicates that a flowchart is running and a user task is being executed. When the STAT LED is on and remains orange, it indicates that the controller is running, but no flowchart is running.
NOTE: If your S-series PAC has a microSD card slot, the STAT LED will briefly blink once every five seconds as it reads the card (or checks to see whether a card is present). For example, if the STAT LED is on and remains green or orange, it will still blink briefly every five seconds. When a microSD card is being read or written to,
the LED flashes. For more information on microSD, see “Using the microSD Card Slot” on page 49
.
Different blink codes can occur in sequence. For example, two fast green blinks followed by three slow red blinks show the firmware loading at startup followed by a firmware error.
62
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
If the STAT LED blinks green when the controller starts up, it indicates the following:
Number of
Blinks
Speed of
Blinks
2
5 fast fast
Means
Loading firmware (kernel) from Flash memory to SDRAM.
Default settings have been successfully restored.
7 fast
(Loader versions 5.1n and older) Entering failsafe boot-
loader mode (see “Resetting the Controller” on page 48 ).
If the STAT LED is blinking orange, it indicates the following:
Number of
Blinks
(continuous)
Speed of
Blinks
slow*
(continuous) fast
Means
There is a problem with the bootloader. Contact Product
Support.
No IP address is assigned to the controller. This may also indicate the controller is in hardware test mode.
* About once per second
If the STAT LED blinks red and green alternately, it indicates the following:
Number of
Blinks
Speed of
Blinks
(continuous) fast
Means
(Loader versions 5.1c and newer) Entering fail-safe bootloader mode. (See
“Resetting the Controller” on page 48
.)
If the STAT LED is blinking red, it indicates the following:
Number of
Blinks
Speed of
Blinks
2 slow
3
4
5
6
7 slow slow slow slow slow
Means Problem and Workaround
Flash programming failure
Invalid MAC address or hardware revision.
Flash chips failed to erase properly or program properly. Contact Product Support.
Firmware CRC check failed.
The firmware in the device is damaged. See Replacing Damaged Firmware in chapter 6 of Opto 22 form 1704, the
PAC Manager User’s Guide
.
Contact Product Support.
Fatal error
RAM error
Loader problem
Firmware or hardware problem. Check the power supply and connections before restarting. Call Product Support if the error is repeated.
Contact Product Support.
Firmware or hardware problem. Confirm Ethernet cables are connected. Try turning off power to the controller and turning it back on again. Call Product
Support if the error is repeated.
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
Number of
Blinks
Speed of
Blinks
8
11
12
13
16
17
18
19
21
22
23 slow slow slow slow slow slow slow slow slow slow slow
Means Problem and Workaround
WLAN failure
(Wired+Wireless models only) Try restoring the PAC
port.
Firmware failed to initialize communications on
ENET 1.
Firmware failed to initialize communications on
ENET 2.
Real-time clock failure
Serial EEPROM failure
Serial port 0 failure
Serial port 1 failure
Serial port 2 failure
I/O expander failure
Serial port 3 failure
Watchdog reset failure
Contact Product Support.
Contact Product Support.
Contact Product Support.
Contact Product Support.
Contact Product Support.
Contact Product Support.
This error appears if your PAC-S has a microSD card slot and you are using firmware R8.2 or lower. Follow steps in Opto 22 form 1704, the
PAC Manager
User’s Guide
, to install firmware version R8.3 or higher using Install Firmware via Failsafe Bootloader
Mode.
(PAC-S2) Contact Product Support.
(PAC-S2) Contact Product Support.
Contact Product Support.
Serial Port LEDs
The S0, S1, and S2 LEDs on a SNAP-PAC-S1 controller indicate serial port operation as follows:
•
Green—Transmit
•
Red—Receive
•
Amber—Transmit and Receive (the LED is actually changing rapidly between green and red, which appears amber)
Each serial port on a SNAP-PAC-S2 has two green LEDs to indicate Transmit and Receive activity for that port.
64
SNAP PAC S-Series User’s Guide
CHAPTER 3: MAINTENANCE AND TROUBLESHOOTING
WLAN LED (Wired+Wireless Models Only)
The WLAN LED on a SNAP-PAC-S1-W or SNAP-PAC-S2-W indicates wireless LAN status and activity:
Color of
LED
Red
Means
Orange
The controller is disconnected from the wireless LAN.
The wireless LAN interface is scanning, associating, and authenticating the wireless network.
Green The controller is connected to the wireless network.
Blinking green Wireless LAN activity
SNAP PAC S-Series User’s Guide
MAINTAINING THE CONTROLLER
66
SNAP PAC S-Series User’s Guide
Appendix A
A: Technical Specifications
Processor
Memory
Removable storage
Backup battery
Ethernet Communication
(wired) to host and I/O
Ethernet Communication
(wireless)*
266 MHz 32-bit ColdFire
®
5475 with integrated floating-point unit (FPU)
SNAP-PAC-S1 and SNAP-PAC-S2
Total RAM: 32 MB
Total RAM for PAC Control Strategies: 16 MB
Battery-backed RAM: 8 MB
RAM File Storage: 2.5 MB
Flash File Storage: 4 MB
SNAP-PAC-S1-W and SNAP-PAC-S2-W
Total RAM: 128 MB
Total RAM for PAC Control Strategies: 64MB
Battery-backed RAM: 8 MB
RAM File Storage: 16 MB
Flash File Storage: 4 MB
(Models with manufacture dates of June 2014 and newer. Requires firmware
R9.4a or higher and loader R6.1a or higher) MicroSD card slot: supports microSD or microSDHC cards to 32 GB.
(Models with manufacture dates of November 2008 through May 2014 with firmware R8.4 or higher) microSD card slot: supports microSD cards up to 2
GB.
SNAP-PAC-S1s with serial number 625654 or higher and all SNAP-PAC-S2s:
Rechargeable (recharges whenever the brain has power), 1-year power-off data retention (replacement part number: SNAP-PAC-BATTERY-ML2430).
SNAP-PAC-S1s with serial number 625653 or lower: User-replaceable 3.6-volt
TL 5242 /W lithium, 10-year minimum power-off data retention (replacement part number: G4BATT32).
Two independent 10/100 Mbps Ethernet network interfaces (RJ-45 connectors). Each interface has a separate IP address (separate subnet).
Wireless LAN interface with separate IP address.
Topologies: Infrastructure, Ad-Hoc
Security: 802.11i; AES - Compatible with WPA2 Personal, TKIP - Compatible with WPA Personal, WEP.
NOTE: TKIP/AES security is not supported in Ad-Hoc mode.
Frequency 802.11a: 5.180–5.240 GHz, 5.745–5.825 GHz
Frequency 802.11b/g: 2.412–2.472 GHz, 2.484 GHz
Transmit Power: 15 dBm maximum
Antenna Connector: Reverse polarity SMA (RP-SMA or RSMA)
Roaming: Supported within an SSID (Service Set Identifier) only
SNAP PAC S-Series User’s Guide
Serial Communication
SNAP-PAC-S1
RS-232 serial: Two RS-232 serial ports (one DB-9 and one pluggable connector); one port has full handshaking. PPP is supported only on port 0. Buffer size: 512 bytes each for RX and TX.
RS-485 serial: One RS-485 serial port (pluggable connector); two-wire
RS-485; optional mistic signal interrupts. Range (serial multidrop): 32 stations maximum on a segment (including PC, controller, and I/O units); up to 3000 ft
(914 m) on a segment. Buffer size: 512 bytes each for RX and TX.
Power requirements
SNAP-PAC-S2
Four serial ports that can be used as general purpose ports or for serial I/O units; each port is software configurable as either RS-232 (Tx, Rx, COM, DTR,
DCD, RTS, CTS) or as RS-485 (2-wire, 4-wire, optional termination, optional biasing); optional mistic signal interrupts. Buffer size: 512 bytes each for RX and TX.
8–32 VDC ±0.5, 11.3 VA maximum
(SNAP-PAC-S1 controllers with serial numbers below 500,000 use 8–24 VDC)
-20 °C to 60 °C
-40 °C to 85 °C
0% to 95% relative humidity, non-condensing
Operating temperature
Storage temperature
Humidity
Software
PAC Project Basic
PAC Project Professional
RESTful API**
Includes programming, HMI software, and configuration software; included with purchase of controller.
PAC Project Basic plus OPC 2.0-compliant OPC server, OptoControl strategy and OptoDisplay project importing, support for serial mistic I/O units, and
Ethernet link redundancy support.
Use HTTPS to access data (read/write or read-only) from controller tags using your chosen programming language. Data returned in JSON. More information at developer.opto22.com
Number of charts that can run simultaneously
32
Other features
Agency certifications
Multiple protocol support including TCP/IP, HTTP/HTTPS, FTP, SNMP v2.0c
(with firmware 8.2a), Modbus/TCP, EtherNet/IP™, and OptoMMP™
Real-time clock
FTP server/client with file system (in RAM and in removable storage)
Ethernet link redundancy or network segmenting
(-W models only) U.S., FCC Part 15 Subpart C; Canada, IC RSS-210
(-FM models only) Factory Mutual approved
All models: CE, RoHS, DFARS
Warranty 30 months from date of manufacture
* Requires a Wired+Wireless model (SNAP-PAC-S1-W or SNAP-PAC-S2-W)
** Requires firmware R9.5a or higher
68
SNAP PAC S-Series User’s Guide
Index
A
API
B
backup battery
bias and termination, PAC S1
switches
blink codes
brains supported
C
compatibility brains
connectors
controller information, getting
controller, redundant
D
developers
DIN-rail mounting
dimensions
PAC S1
PAC S2
DIP switches, PAC S1
E
environmental requirements
interfaces
F
Factory Mutual approval
files, in removable storage
firmware booting from microSD card
disabling/enabling microSD updates
H
hardware test mode
help
I
I/O units supported
indicators
PAC S1
PAC S1-W
PAC S2
PAC S2-W
installing software
interrupt line
SNAP PAC S-Series User’s Guide
J
JSON
L
LED blink codes
STAT
WLAN
legacy control hardware
M
microSD card
card type and format
disabling/enabling updates via card
storing data
updating strategy
mounting
DIN-rail
N
basic diagram
certification
redundant controllers
segmented
troubleshooting
wireless
70
SNAP PAC S-Series User’s Guide network protocol analyzer
networking serial
O
OPC
OptoMMP Communication Toolkit
P
PAC Control
PAC Manager
panel mounting
peer-to-peer communication
pinouts
PAC S1
PAC S1-W
PAC S2
PAC S2-W
power requirements
product support
PSTN
R
redundant controllers
redundant Ethernet links
replacing controller
reset button
resetting the controller
restoring factory defaults
RS-485, PAC S1 bias and termination
S
serial networking
serial number
serial ports
assigning
serial-based I/O units
SNAP PAC SB-Series Brain
SNAP-PAC-S1 dimensions
DIN-rail mounting and dimensions
LEDs
panel mounting
serial ports
termination settings
wiring diagrams
SNAP-PAC-S2 dimensions
DIN-rail mounting and dimensions
LEDs
mistic brain, connecting to
mode, termination, and bias
panel mounting
serial ports
software, installing
specifications
strategy
disabling/enabling microSD updates
system requirements
T
TCP/IP
settings
stack
termination settings, SNAP-PAC-S1
troubleshooting
U
utilities, packet sniffer
V
voltage range
W
wired+wireless communication
wireless LAN
diagram
specifications
wiring
SNAP-PAC-S1
SNAP-PAC-S2
SNAP PAC S-Series User’s Guide
72
SNAP PAC S-Series User’s Guide
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 8 Introduction
- 8 Ethernet Communication
- 9 Wired+Wireless™ Communication
- 10 Serial Communication
- 10 I/O Unit Compatibility
- 11 Redundant Controllers
- 11 PAC Project Software
- 11 PAC Project
- 12 For Developers: SNAP PAC REST API
- 12 Architectural Diagrams
- 13 Basic Control System
- 14 Segmented Wired Networks
- 15 Wired and Wireless Networks
- 16 Connections to Legacy Serial-based I/O Units
- 17 SNAP-PAC-S2 Connections to Serial-based I/O Units
- 18 Ethernet Link Redundancy
- 19 Controller Redundancy
- 20 Remote Host and I/O Unit Connections Using PPP
- 21 About This Guide
- 21 Related Documentation
- 22 For Help
- 24 What You Will Need
- 24 Installing Software
- 25 Power Supply Recommendations
- 25 Change to SNAP-PAC-S1 Power Input Range
- 25 Installing Hardware
- 27 RS-232 and RS-485 Serial Networking
- 27 RS-232 Connections
- 27 Attaching a Modem to the Controller
- 27 RS-485 Connections
- 27 Bias and Termination
- 28 Configuring RS-485 Connections on SNAP-PAC-S1 Controllers
- 28 Configuring RS-485 Connections on SNAP-PAC-S2 Controllers
- 28 Wiring the 10-pin Serial Connector on SNAP-PAC-S1 Controllers
- 29 Wiring the 7-pin Serial Connector on SNAP-PAC-S2 Controllers
- 30 Guidelines for Grounding SNAP PAC Brains and Controllers
- 31 Connectors, Indicators, and Pinouts
- 31 SNAP-PAC-S1 and SNAP-PAC-S1-FM
- 32 SNAP-PAC-S1-W (Wired+Wireless)
- 33 SNAP-PAC-S2
- 34 SNAP-PAC-S2-W (Wired+Wireless)
- 35 PAC S1 Serial Wiring Diagrams
- 35 Wiring a PAC S1 Controller to SB-Series Brains
- 35 Wiring a PAC S1 Controller to B3000 mistic Brains with an Interrupt Line
- 36 PAC S2 Serial Wiring Diagrams
- 36 PAC S2 Controller to B3000 mistic Brains with an Interrupt Line
- 37 PAC S2 Controller to G4 mistic Bricks
- 38 PAC S2 Controller to PAC SB-Series Brains
- 38 Assigning an IP Address
- 39 Assigning Serial Ports on SNAP-PAC-S2 Controllers
- 40 Mounting the Controller
- 40 Panel Mounting and Dimensions
- 44 DIN-Rail Mounting and Dimensions
- 46 About the Controller’s Memory Map
- 46 Using Data for Peer-to-Peer Communication
- 47 What’s Next?
- 48 Troubleshooting
- 48 Checking Power
- 48 Communicating on a Wired Ethernet Network
- 49 Pinging the Controller
- 50 Solving Network Problems
- 50 Create a Network Diagram
- 50 Check Ethernet Errors
- 51 Analyze Communication Packets
- 51 Have Your Network Certified
- 51 TCP Settings
- 53 Communicating on a Serial Network
- 53 Maintaining the Controller
- 53 Backup Battery
- 53 Getting Device and Firmware Information
- 54 Changing the Controller’s IP Address
- 55 Resetting the Controller
- 56 Loading New Firmware
- 56 Using the microSD Card Slot
- 56 Card Type and Format
- 57 MicroSD/SDHC Card Uses
- 58 Storing and Accessing Data or Files
- 59 Displaying Free Space on the Card
- 60 Checking Firmware and Loader Versions
- 61 Replacing a Controller
- 64 Updating Firmware
- 65 Booting from Firmware on the Card
- 67 Updating, Running, or Testing a Strategy
- 69 Disabling or Enabling Firmware and Strategy Updates Via the Card
- 69 Setting Time and Date
- 69 STAT LED Blink Codes
- 71 Serial Port LEDs
- 72 WLAN LED (Wired+Wireless Models Only)