Kaco Powador 00 Series Inverters without transformers

Kaco Powador 00 Series Inverters without transformers
...................................................................................................................................................................
Single-phased
GRID-CONNECTED INVERTERS
...................................................................................................................................................................
Kaco Powador 00 Series
Inverters without transformers
Higher efficiency
Without transformers, the inverters of the Kaco 00
series achieve optimal efficiency. As a specialist for
inverters without transformers, Kaco has equipped all
devices of the 00 series with a full bridge and omitted
the boost converters. The self-controlled devices emulate the sinus voltage curve of the public power grid
using a H4 bridge. Prerequisite for using the 00 series
inverters is an input voltage higher than the grid peak
voltage.
rent-operated protective device, facilitates the grid
connection, even in the case of systems with several
inverters.
Long service life
All inverters operate up to outputs of 8 kW with silent
and purely passive cooling. The lost heat is optimally
dissipated by the cooling element on the back. This
cooling without mechanical fans reduces error sources
and thus achieves a long life-cycle of the devices.
Simple installation
100 % feed-in
The Powador 3200 – 5500 without transformers can be single-phase connected individually, due to their nominal output.
The single-phase Powador 6600 – 9600 have a nominal output of more than 5 kW; for this reason the unbalanced load
between feed-in phases should be considered during the
dimensioning.
With a MPP range of 350 to 600 V and an off-load
voltage of 800 V the conditions for a simple system
dimensioning are ideal. The devices are connected to
the grid by screw terminals. The redundant 3-phase
monitoring, including an AC/DC sensitive residual-cur-
The Kaco Powador 7900 was specifically developed for
applications with connections limits of 20 kW. Due to
the 100 % symmetrical feed-in of 20 kW, not one watt
of power is wasted, not even in Spain, Italy or Greece.
...................................................................................................................................................................
GRID-CONNECTED INVERTERS
Single-phased
...................................................................................................................................................................
Art. No.
0201462
0201463
0201464
0201465
0201466
Model
Kaco Powador 3200
DCS INT
350 - 600 V
800 V
8.6 A
2600 W
3200 W
1 pc.
190 - 264 V
0.8 inductive,
0.8 capacitive
50 Hz
<3%
96.6 %
95.8 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:200602, VDE AR-N 4105
Two-line LC display
PCB clip up to max.
10 mm²
Aluminium
500 mm / 340 mm /
200 mm
19 kg
10 years
DIN VDE 0126-1-1:200602, EN 50178, DIN EN
50178, IEC 62103, RAL
seal of approval (RAL
GZ 966), VDE AR-N 4105
Kaco Powador 4400
DCS INT
350 - 600 V
800 V
12.0 A
3600 W
4400 W
1 pc.
190 - 264 V
0.8 inductive,
0.8 capacitive
50 Hz
<3%
96.5 %
95.9 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:200602, VDE AR-N 4105
Two-line LC display
PCB clip up to max.
10 mm²
Aluminium
550 mm / 340 mm /
220 mm
21 kg
10 years
DIN VDE 0126-1-1:200602, EN 50178, DIN EN
50178, IEC 62103, RAL
seal of approval (RAL
GZ 966), VDE AR-N 4105
Kaco Powador 5300
DCS INT
350 - 600 V
800 V
14.5 A
4400 W
5300 W
1 pc.
190 - 264 V
0.8 inductive,
0.8 capacitive
50 Hz
<3%
96.4 %
95.8 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:200602, VDE AR-N 4105
Two-line LC display
PCB clip up to max.
10 mm²
Aluminium
550 mm / 340 mm /
220 mm
26 kg
10 years
DIN VDE 0126-1-1:200602, EN 50178, DIN EN
50178, IEC 62103, RAL
seal of approval (RAL
GZ 966), VDE AR-N 4105
Kaco Powador 5500
DCS INT
350 - 600 V
800 V
15.2 A
4600 W
5500 W
1 pc.
190 - 264 V
0.8 inductive,
0.8 capacitive
50 Hz
<3%
96.3 %
95.7 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:200602, VDE AR-N 4105
Two-line LC display
PCB clip up to max.
10 mm²
Aluminium
600 mm / 340 mm /
220 mm
28 kg
10 years
DIN VDE 0126-1-1:200602, EN 50178, DIN EN
50178, IEC 62103, RAL
seal of approval (RAL
GZ 966), VDE AR-N 4105
Kaco Powador 6600
DCS INT
350 - 600 V
800 V
18.0 A
5500 W
6600 W
1 pc.
190 - 264 V
0.8 inductive,
0.8 capacitive
50 Hz
<3%
96.3 %
95.8 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:200602, VDE AR-N 4105
Two-line LC display
PCB clip up to max.
10 mm²
Aluminium
600 mm / 340 mm /
220 mm
30 kg
10 years
DIN VDE 0126-1-1:200602, EN 50178, DIN EN
50178, IEC 62103, RAL
seal of approval (RAL
GZ 966), VDE AR-N 4105
MPP voltage range
Open circuit voltage
Max. input current
Nominal output
Max. DC power
MPP tracker
Output voltage
Power factor cos phi
Frequency
Harmonic distortion
Max. efficiency
Euro efficiency
Night-time consumption
Ambient temperature
Heat dissipation
Protection mode
Circuit type
DC load disconnector
Grid monitoring
Display
Connection
Casing
Dimensions (W / H / D)
Weight
Warranty
Norms
Continued on next page
TRITEC Group www.tritec-energy.com | © 20141218-1 | The content of this datasheet is subject to change without prior notice
...................................................................................................................................................................
Single-phased
GRID-CONNECTED INVERTERS
...................................................................................................................................................................
Art. No.
0201467
0201468
0201469
0201470
Model
MPP voltage range
Open circuit voltage
Max. input current
Nominal output
Max. DC power
MPP tracker
Output voltage
Power factor cos phi
Frequency
Harmonic distortion
Max. efficiency
Euro efficiency
Night-time consumption
Ambient temperature
Heat dissipation
Protection mode
Circuit type
Kaco Powador 7700 DCS INT
350 - 600 V
800 V
19.0 A
6400 W
7700 W
1 pc.
190 - 264 V
0.8 inductive, 0.8 capacitive
50 Hz
<3%
96.6 %
96.2 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:2006-02,
VDE AR-N 4105
Two-line LC display
PCB clip up to max. 10 mm²
Aluminium
810 mm / 340 mm / 220 mm
38 kg
10 years
DIN VDE 0126-1-1:2006-02, EN
50178, DIN EN 50178, IEC
62103, RAL seal of approval
(RAL GZ 966), VDE AR-N 4105
Kaco Powador 7900 DCS INT
350 - 600 V
800 V
19.7 A
6650 W
7900 W
1 pc.
190 - 264 V
0.8 inductive, 0.8 capacitive
50 Hz
<3%
96.7 %
96.2 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:2006-02,
VDE AR-N 4105
Two-line LC display
PCB clip up to max. 10 mm²
Aluminium
810 mm / 340 mm / 220 mm
38 kg
10 years
DIN VDE 0126-1-1:2006-02, EN
50178, DIN EN 50178, IEC
62103, RAL seal of approval
(RAL GZ 966), VDE AR-N 4105
Kaco Powador 8600 DCS INT
350 - 600 V
800 V
21.4 A
7200 W
8600 W
1 pc.
190 - 264 V
0.8 inductive, 0.8 capacitive
50 Hz
<3%
96.6 %
96.2 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:2006-02,
VDE AR-N 4105
Two-line LC display
PCB clip up to max. 10 mm²
Aluminium
810 mm / 340 mm / 220 mm
38 kg
10 years
DIN VDE 0126-1-1:2006-02, EN
50178, DIN EN 50178, IEC
62103, RAL seal of approval
(RAL GZ 966), VDE AR-N 4105
Kaco Powador 9600 DCS INT
350 - 600 V
800 V
24.0 A
8000 W
9600 W
1 pc.
190 - 264 V
0.8 inductive, 0.8 capacitive
50 Hz
<3%
96.6 %
96.2 %
0W
-20 to +60 °C
Free convection / no fan
IP54
Self-controlled, transformerless
Integrated
DIN VDE 0126-1-1:2006-02,
VDE AR-N 4105
Two-line LC display
PCB clip up to max. 10 mm²
Aluminium
810 mm / 340 mm / 220 mm
38 kg
10 years
DIN VDE 0126-1-1:2006-02, EN
50178, DIN EN 50178, IEC
62103, RAL seal of approval
(RAL GZ 966), VDE AR-N 4105
DC load disconnector
Grid monitoring
Display
Connection
Casing
Dimensions (W / H / D)
Weight
Warranty
Norms
TRITEC Group www.tritec-energy.com | © 20141218-1 | The content of this datasheet is subject to change without prior notice
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising