Fire-Lite MS5UD/10UD
PN: 52626:B
ECN 08-084
Fire Alarm Control Panels
MS-5UD Series
MS-10UD Series
Document
8/01/08
#52626
Revision:
B
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
age of flammable materials, etc.).
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/
applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD
02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F and at a relative humidity of
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD
02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications. This Class A
digital apparatus complies with Canadian ICES-003.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada. Cet
appareil numerique de la Classe A est conforme a la
norme NMB-003 du Canada.
Table of Contents
Product Description ................................................................................................................................................12
Product Features ................................................................................................................................................13
Specifications .....................................................................................................................................................14
Controls and Indicators ......................................................................................................................................16
Digital Alarm Communicator/Transmitter ........................................................................................................17
Components .......................................................................................................................................................18
Optional Modules and Accessories ...................................................................................................................18
Telephone Requirements and Warnings ............................................................................................................20
Telephone Circuitry ....................................................................................................................................20
Digital Communicator ................................................................................................................................20
Telephone Company Rights and Warnings ................................................................................................21
For Canadian Applications .........................................................................................................................22
Installation ...............................................................................................................................................................23
Backbox Mounting ............................................................................................................................................23
Operating Power ................................................................................................................................................26
Input Circuits .....................................................................................................................................................27
Output Circuits ..................................................................................................................................................29
Notification Appliance Circuits ..................................................................................................................29
Special Application DC Power Output Connections .................................................................................30
Relays - Programmable ..............................................................................................................................30
Remote Synchronization Output ................................................................................................................31
Power-limited Wiring Requirements .................................................................................................................32
Digital Communicator .......................................................................................................................................33
Installation of Optional Modules .......................................................................................................................34
CAC-5X Class A Converter Module ..........................................................................................................34
Installation ...........................................................................................................................................34
Wiring NACs and IDCs for Class A ...................................................................................................35
4XTMF Option Module .............................................................................................................................36
4XTMF Transmitter Module Installation ............................................................................................37
ANN-BUS Devices ............................................................................................................................................38
ANN-BUS Wiring ......................................................................................................................................38
Calculating Wiring Distance for ANN-BUS Modules ........................................................................38
Wiring Configuration ..........................................................................................................................40
Powering ANN-BUS Devices from Auxiliary Power Supply ............................................................41
ANN-BUS Device Addressing ...................................................................................................................41
ANN-80 Remote Fire Annunciator ............................................................................................................42
Specifications .............................................................................................................................................42
Installation ..................................................................................................................................................42
Mounting .............................................................................................................................................42
Opening/Closing Annunciator ............................................................................................................42
Wiring ANN-80 to FACP ...................................................................................................................43
ANN-S/PG Serial/Parallel Printer Interface Installation ............................................................................45
Specifications ......................................................................................................................................45
PRN-6F Printer Installation .................................................................................................................45
Connecting PRN-6F Printer ................................................................................................................46
Setting Printer Options ........................................................................................................................46
ANN-I/O LED Driver Module ...................................................................................................................47
ANN-I/O Board Layout ......................................................................................................................47
Specifications ......................................................................................................................................47
ANN-I/O Connection to FACP ...........................................................................................................48
ANN-I/O Module LED Wiring ...........................................................................................................49
ANN-LED Annunciator Module ................................................................................................................50
ANN-LED Board Layout ....................................................................................................................50
Specifications ......................................................................................................................................50
Mounting/Installation ..........................................................................................................................50
4
MS-5UD/MS-10UD P/N: 52626:B 8/01/08
Table of Contents
ANN-LED Connection to FACP ........................................................................................................51
ANN-RLY Relay Module ..........................................................................................................................52
ANN-RLY Board Layout ....................................................................................................................52
Specifications ......................................................................................................................................52
Mounting/Installation ..........................................................................................................................52
ANN-RLY Connection to FACP ........................................................................................................53
ANN-BUS Audio Panel ....................................................................................................................................54
Programming .........................................................................................................................................................55
User Programming ............................................................................................................................................55
Initial Power-up .................................................................................................................................................56
Programming Screens Description ....................................................................................................................56
Programming and Passwords ............................................................................................................................57
Master Programming Level ...............................................................................................................................58
Input Zones .................................................................................................................................................59
NAC (Notification Appliance Circuit) .......................................................................................................67
Enabled ................................................................................................................................................68
NAC Coding .......................................................................................................................................68
Two Stage Operation ..........................................................................................................................69
Synchronized NAC Operation ............................................................................................................69
Silence .................................................................................................................................................70
Auto Silence ........................................................................................................................................71
Silence Inhibited .................................................................................................................................71
Relays .........................................................................................................................................................71
System Setup ..............................................................................................................................................73
Timers .................................................................................................................................................74
PAS (Positive Alarm Sequence) Delay ...............................................................................................74
Pre-signal Delay ..................................................................................................................................74
Waterflow Delay .................................................................................................................................75
AC Loss Delay ....................................................................................................................................75
Banner .................................................................................................................................................76
Time-Date ...........................................................................................................................................77
Time ....................................................................................................................................................77
Date .....................................................................................................................................................78
Clock Format .......................................................................................................................................78
Daylight Savings Time ........................................................................................................................78
Trouble Reminder ...............................................................................................................................79
Canadian Option .................................................................................................................................79
Charger Disable ...................................................................................................................................79
Option Modules .........................................................................................................................................79
ANN-BUS ...........................................................................................................................................80
ANN-BUS Enabled .............................................................................................................................80
BUS Modules ......................................................................................................................................80
Auto-Configure ...................................................................................................................................81
ANN-S/PG Options Screen .................................................................................................................82
ANN-I/O LED Zone Assignments ......................................................................................................83
ANN-80 Options Screen .....................................................................................................................84
ANN-RLY Options Screen .................................................................................................................85
ANN-AUDIO Options Screen ............................................................................................................86
Onboard DACT ...................................................................................................................................87
Primary Phone .....................................................................................................................................87
Secondary Phone .................................................................................................................................87
Central Station .....................................................................................................................................88
Service Terminal .................................................................................................................................99
Supervised Phone Line ........................................................................................................................100
History ........................................................................................................................................................100
View Events ........................................................................................................................................101
MS-5UD/MS-10UD P/N: 52626:B 8/01/08
5
Table of Contents
Erase History .......................................................................................................................................101
Walktest ......................................................................................................................................................102
Clear Program .............................................................................................................................................103
Password Change .......................................................................................................................................103
Maintenance Programming Level .....................................................................................................................104
Input Zones - Enable/Disable .....................................................................................................................105
History ........................................................................................................................................................105
Walktest ......................................................................................................................................................106
Time-Date ...................................................................................................................................................107
Operating Instructions ...........................................................................................................................................108
Panel Control Buttons ........................................................................................................................................108
Acknowledge/Step ......................................................................................................................................108
Alarm Silenced ...........................................................................................................................................108
Drill/Hold 2 Sec ..........................................................................................................................................108
Reset ...........................................................................................................................................................108
LED Indicators ..................................................................................................................................................109
Normal Operation ..............................................................................................................................................109
Trouble Operation ..............................................................................................................................................110
Alarm Operation ................................................................................................................................................111
Supervisory Operation .......................................................................................................................................112
Process Monitor Operation ................................................................................................................................113
Hazard/Tornado Condition Operation ...............................................................................................................113
Medical Alert Condition Operation ...................................................................................................................113
Disable/Enable Operation ..................................................................................................................................114
Waterflow Circuits Operation ............................................................................................................................114
Detector Functions .............................................................................................................................................114
Time Functions: Real-Time Clock ....................................................................................................................114
Coded Operation ................................................................................................................................................114
Presignal ............................................................................................................................................................115
Positive Alarm Sequence ...................................................................................................................................115
Special System Timers ......................................................................................................................................116
Silence Inhibit Timer ..................................................................................................................................116
Autosilence Timer ......................................................................................................................................116
Trouble Reminder .......................................................................................................................................116
Waterflow Retard Timer .............................................................................................................................116
Alarm Verification (None or One Minute) .................................................................................................117
Walktest .............................................................................................................................................................117
Read Status ........................................................................................................................................................118
Input Zones .................................................................................................................................................119
NAC ............................................................................................................................................................119
Relays .........................................................................................................................................................120
System Settings ..........................................................................................................................................120
Timers .........................................................................................................................................................121
Daylight Savings ........................................................................................................................................121
History ........................................................................................................................................................122
Print ............................................................................................................................................................122
ANN-BUS ..................................................................................................................................................123
Central Station ............................................................................................................................................124
Phone Line ..................................................................................................................................................125
Service Terminal .........................................................................................................................................125
Central Station Communications ..........................................................................................................................126
Transmittal Priorities .........................................................................................................................................127
Local/Remote Site Upload/Download ...................................................................................................................129
Remote Download .............................................................................................................................................129
6
MS-5UD/MS-10UD P/N: 52626:B 8/01/08
Table of Contents
Transferring a Program ......................................................................................................................................131
Security Features ........................................................................................................................................131
Power Supply Calculations ....................................................................................................................................133
Overview ...........................................................................................................................................................133
Calculating the AC Branch Circuit ...................................................................................................................133
Calculating the System Current Draw ...............................................................................................................134
Overview ....................................................................................................................................................134
How to Use Table 7-3 on page 134 to Calculate System Current Draw ....................................................134
Calculating the Battery Size ..............................................................................................................................136
NFPA Battery Requirements ......................................................................................................................136
Selecting and Locating Batteries ................................................................................................................136
Ademco Contact ID Format Event Code Descriptions .......................................................................................137
Transmission Format Between DACT and Receiver ........................................................................................137
Ademco Contact ID Typical Printout ................................................................................................................137
NFPA Standard-Specific Requirements ...............................................................................................................142
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts ...........................................148
FACP with Keltron .................................................................................................................................................149
Wire Requirements .................................................................................................................................................150
MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring ...............................................................................................151
MS-5UD-7(C/E) & MS-10UD-7(C/E) NAC Wiring ........................................................................................151
MS-5UD/MS-10UD P/N: 52626:B 8/01/08
7
Notes
8
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•
Underwriters Laboratories Standards
•
NFPA 72 National Fire Alarm Code
•
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote
Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document
411UD Manual
411UDAC Manual
ANN-80 Product Installation Doc.
ANN-(R)LED Product Installation Doc.
ANN-I/O Product Installation Doc.
ANN-RLY Product Installation Doc.
ANN-S/PG Product Installation Doc.
ACC-25/50 Series Audio Panel
Document #15384
Document #50759
Document #51073
Document #52749
Document #53032
Document #151416
Document #53033
Document #151417
Document #51889
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
9
10
4
3
2
1
Power Supply Connector J15
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Supervision required.
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Special Application
DC Power Outputs (24 VDC)
Important! Removing Ground Fault
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
+
-
+
-
Notes:
1. MS-5UD-3(E) = 2.5 amps max. per NAC
MS-5UD-7(C/E)= 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-5UD-3(E): refer to “Remote
Synchronization Output” on page 31
3. 18 Amp Hour max. for MS-5UD-3(E)
26 Amp Hour max. for MS-5UD-7(C/E)
TB4
BATTERY
- +
J12
RST/NONRST
AUXPWR
3
2
1
JP31
OUT2
RST AUX
PWR
OUT1
TB7
J2
24 VDC, supervised,
nonpower-limited
ST
*
#
_/.
MODE
ESC
0
7 PRS 8 TUV 9
QZ_
CLEAR
2 ABC 3 DEF 1
AC POWER
4 GHI 5 JKL 6
1
J3
-
OUT4
+
DRILL
ENTER
RESET
ALARM
TROUBLE
FIRE ALARM
TB3
- +
ANN-BUS
GND PWR A B
Primary Phone
Active LED
- +
JP24
TB8
Secondary
J9
Secondary Phone
Active LED
Kiss-off LED
J6
(Nonpower-Limited)
DACT Phone Line Jacks
Primary
J8
JP30
J5
J4
J11
Cut this jumper to
enable Supervisory
relay when 4XTM
module is installed
NO NC C NO NC C NO NC C
Alarm* Trouble* Supervisory*
(*Factory default relay programming)
A Fail Safe Trouble NO NC C
relay switches to the
NC position during
trouble conditions and
under loss of all power.
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
J7
TB2
Special Application Power
24 VDC filtered, supervised
and power-limited.
0.040 amps maximum.
Requires 4.7K ELR.
Remote
Synchronization
Output (see note 2)
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
Class A Converter Module
OUT3
-
B B B B
+ - + 1 1 2 2
-
+
+
+ - + - + - + - + -
-
Battery (see note 3)
J15
TB9
TB5
+
+
B B
+ 1 1
+
+
+
+
+
+
+
+
+
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Initiating Device Circuits
B B B B
+ - + 1 1 2 2
+
+
NAC #1
Notification Appliance Circuits (see note 1)
Special Application Power
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
(See Style Z illustrated near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
NAC #3
NAC #4
NAC #2
PN 71252
4XTM OPT BD
Basic System Connections
5-Zone Panel
OUT
OUT2/4
2
TB4/
TB6
B B
+ 1 1
J2
Class A Converter Module
OUT
OUT1/3
B B
+ 1 1
TB1
Style D (Class A) IDC
USB Port for local programming using
a personal computer and PK-5X Utility
TB2
TB5/
TB7
+
+
+
Style Z (Class A) NAC
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
MS-5UD Series Main Circuit Board
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
4
3
Power Supply Connector J15
2
Nonresettable or Resettable Power
1
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Supervision required.
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Special Application
DC Power Outputs (24 VDC)
Important! Removing Ground Fault
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
+
-
+
-
Notes:
1. MS-10UD-3(E) = 2.5 amps max. per NAC
MS-10UD-7(C/E) = 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-10UD-3(E): refer to “Remote
Synchronization Output” on page 31
3. 18 Amp Hour max. for MS-10UD-3(E)
26 Amp Hour max. for MS-10UD-7(C/E)
TB4
BATTERY
- +
J12
RST/NONRST
AUXPWR
3
2
1
JP31
OUT2
RST AUX
PWR
OUT1
-
J2
24 VDC, supervised,
nonpower-limited
Battery (see note 3)
J15
TB9
TB5
+
0
#
_/.
MODE
ESC
QZ_
CLEAR
2 ABC 3 DEF 1ST
AC POWER
7 PRS 8 TUV 9
*
OUT4
-
DRILL
ENTER
RESET
ALARM
TROUBLE
FIRE ALARM
TB3
TB2
Primary Phone
Active LED
- +
- +
JP24
TB8
Kiss-off LED
Secondary
J9
Secondary Phone
Active LED
J6
(Nonpower-Limited)
DACT Phone Line Jacks
Primary
J8
JP30
J5
J4
J11
Cut this jumper to
enable Supervisory
relay when 4XTM
module is installed
NO NC C NO NC C NO NC C
Alarm* Trouble* Supervisory*
(*Factory default relay programming)
A Fail Safe Trouble NO NC C
relay switches to the
NC position during
trouble conditions and
under loss of all power.
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
J7
TB6
ANN-BUS
GND PWR A B
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
Class A Converter Module
OUT3
+
+ - + - + - + - + -
-
+
Special Application Power
24 VDC filtered, supervised
and power-limited.
0.040 amps maximum.
Requires 4.7K ELR.
Remote
Synchronization
Output (see note 2)
B B
+ 6 6
+
+
IDCs 6 through 10, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Initiating Device Circuits
B B B B
+ - + 3 3 4 4
+
+
+
+
TB7
4 GHI 5 JKL 6
1
J3
+ - + - + - + - + -
-
+
+
+
B B
+ 1 1
+
+
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Initiating Device Circuits
B B B B
+ - + 1 1 2 2
+
+
NAC #1
Notification Appliance Circuits (see note 1)
Special Application Power
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
(See Style Z illustrated near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
NAC #3 NAC #4
NAC #2
PN 71252
4XTM OPT BD
Basic System Connections
10-Zone Panel
OUT
OUT2/4
2
TB4/
TB6
B B
+ 1 1
J2
Class A Converter Module
OUT
OUT1/3
B B
+ 1 1
TB1
Style D (Class A) IDC
USB Port for local programming using
a personal computer and PK-5X Utility
TB2
TB5/
TB7
+
+
+
Style Z (Class A) NAC
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
MS-10UD Series Main Circuit Board
11
Product Description
SECTION 1
Product Description
The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone
FACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise
specified. The combination control and digital communicator panels provide reliable fire signaling
protection for small to medium sized commercial, industrial and institutional buildings. The FACP
is compatible with System Sensor’s i3 detectors which are conventional smoke detectors that can
transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a
supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of
approximately 45o F (refer to System Sensor i3 Installation and Maintenance Instructions). In
addition, the control panel is compatible with conventional input devices such as two-wire smoke
detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other
normally-open contact devices. Refer to Fire•Lite Device Compatibility Document for a complete
listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays
(factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application
resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery
level and telephone line integrity. Available accessories include local and remote upload/download
software, remote annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PS-Tools Upload/Download utility via the public switched telephone
network. Local programming interrogation is also possible using the PS-Tools and the USB port on
the FACP. Any personal computer with Windows™ XP or newer, compatible modem with a speed
of 2400 baud and PS-Tools may serve as a Service Terminal. This allows download of the entire
program or upload of the entire program, history file, walktest data and current status.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicating LED, display alarm
information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm
relay and operate an optional module used to notify a remote station or initiate an auxiliary control
function.
12
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Product Description
The following versions of the MS-5UD and MS-10UD are available:
FACP Version
MS-5UD-3
MS-5UD-7
MS-5UD-7C
MS-5UD-3E
MS-5UD-7E
MS-10UD-3
MS-10UD-7
MS-10UD-7C
MS-10UD-3E
MS-10UD-7E
Description
Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator.
This panel is approved for Canadian applications
Five Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
Five Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator.
This panel is approved for Canadian applications.
Ten Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
Note: Unless otherwise specified, the information in this manual applies to all versions of the
panels.
1.1 Product Features
•
•
•
Built-in DACT (Digital Alarm Communicator/Transmitter)
Style B (Class B) IDC (Initiating Device Circuit)
MS-5UD - five programmable IDCs
MS-10UD - ten programmable IDCs
Four Style Y (Class B) NAC (Notification Appliance Circuit)
- special application power
•
•
•
•
•
•
Three programmable Form-C relays
Built-in Programmer
Touchtone/Rotary dialing
Programmable Make/Break Ratio
Optional Dress Panel DP-51050
A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED
Annunciator module
•
•
•
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
ANN-BUS for connection to optional:
ANN-80 Remote LCD Annunciator
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Relay Module
ANN-LED Annunciator Module
80-character LCD display (backlit)
•
Real-time clock/calendar with daylight savings time control
•
History log with 256 event storage
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
13
Product Description
•
Control Buttons
ACK (Acknowledge)
Alarm Silence
System Reset/Lamp Test
Drill
•
LED Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Primary and Secondary Phone Line Active LEDs
•
Piezo sounder for alarm, trouble and supervisory
•
24 volt operation
•
Low AC voltage sense
•
Alarm Verification
•
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
•
Automatic battery charger with charger supervision
•
Silent or audible walktest capabilities
•
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of
program and data
•
Optional CAC-5X Class A Converter Module for NACs and IDCs
•
Optional 4XTMF Transmitter Module
1.2 Specifications
Note: For wiring specifications, refer to "Wire Requirements" on page 150.
AC Power
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-5UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-10UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Supervised, nonpower-limited
14
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Product Description
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-10UD-3(E) and 26
Amp Hour battery for MS-5UD-7(E), MS-10UD-7(E) [two 18 Amp Hour batteries can be
housed in FACP cabinet. Larger batteries require separate battery box such as BB-26 or BB-55]
Minimum Battery Size: 7 Amp Hour (12 Amp Hour for MS-5UD-7C & MS-10UD-7C)
Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)
Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD)
Alarm Zones 6 - 10 on TB6 (MS-10UD only)
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 2 mA
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB71
Four NACs
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum
per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see
note 1)
Power-limited Circuitry
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1. Total current for resettable power, nonresettable power and Notification Appliance Circuits
must not exceed 3.0 amps for the FACP versions which are powered by the FLPS-3 power
supply or 7.0 amps for the FACP versions which are powered by the FLPS-7 power supply.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
15
Product Description
Remote Sync Output - TB2
Remote power supply synchronization output, only required for the MS-5UD-3(E), MS-10UD3(E) [refer to "Remote Synchronization Output" on page 31]
24 VDC nominal special application power
Maximum current is 40 mA
End-of-Line Resistor: 4.7KΩ
Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an
external device for trouble conditions. It can be connected to the trouble bus of a peripheral,
such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
SYSTEM ALL NORMAL
10:00A 012105
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•
Acknowledge/Step
•
Alarm Silence
•
Drill
•
System Reset (lamp test)
16
•
Keys labeled 1 to 9
•
* key
•
# key
•
0 (recall) key
•
1st Event key
•
Clear key
•
Escape key
•
Mode key
•
Four cursor keys (up, down, left and right)
•
Enter key
9050udkypd.cdr
Service/program keys:
Figure 1.1 Membrane/Display Panel
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Product Description
LED Indicators
LEDs are provided to annunciate the following conditions:
•
Fire Alarm - red LED
•
Supervisory - yellow LED
•
AC Power - green LED
•
System Trouble - yellow LED
•
Alarm Silence - yellow LED
•
Primary Phone Line Active (on circuit board) - red LED
•
Secondary Phone Line Active (on circuit board) - red LED
•
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process
monitor and supervisory conditions as follows:
•
Alarm - on steady
•
Trouble - pulse 1 second on and 1 second off
•
Maintenance - pulse 1 second on and 1 second off
•
Supervisory - pulse ½ second on and ½ second off
•
Process Monitor - pulse ¼ second on and ¼ second off
1.4 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the
following functions:
•
Line Seizure: takes control of the phone lines disconnecting any premises phones
•
Off/On Hook: performs on and off-hook status to the phone lines
•
Listen for dial tone: 440 Hz tone typical in most networks
•
Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary
•
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
•
Communicate in the following formats:
Ademco Contact ID
SIA-DCS-8
SIA-DCS-20
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
17
Product Description
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and
wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
•
FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
•
FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied
standard with a modified dress panel and one ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.
1.6 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP
LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and
Supervisory. ANN-LED module is installed in dress panel for Canadian version.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system
wiring while allowing access to the membrane switch panel. The Canadian version is supplied
standard with a modified dress panel.
18
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Product Description
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the
cabinet.
Battery Box
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour.
The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly
from most IBM compatible personal computers (PC), running Windows™ XP (or newer). FACP
program files can also be created and stored on the PC and then downloaded later to the control
panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM
with on-line help file. A standard USB cable with male-A to male-B connectors, which must be
purchased separately, is required for local connection of the PC to the USB port J11 on the FACP
main circuit board. Remote programming requires that the PC have a 2400 baud (or faster)
modem.
Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to "Remote Download" on page 129). Remote interrogation of panel
programming, history logs, detector status, etc., is possible without enabling the remote download
option.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
19
Product Description
1.7 Telephone Requirements and Warnings
1.7.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone
line. Excessive RENs on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line as determined by the total RENs,
contact the telephone company to determine the maximum REN for the calling area.
1.7.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of
two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty
information, please contact:
Manufacturer:Fire•Lite Alarms
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Product Model Number: MS-5UD/MS-10UD
FCC Registration Number: 1W6AL00B10UD
Ringer Equivalence: 0.0B
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Note: This equipment complies with Part 68 of the FCC rules and the requirements
adopted by the ACTA. On the inside of the FACP door is a label that contains,
among other information, a product identifier in the format
US:AAAEQ##TXXXX. If requested, this number must be provided to the
telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency
situation. It must be able to do this even if other equipment (telephone, answering system,
computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment
must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of
all other equipment attached to the same telephone line. If there are any questions concerning these
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack
and alarm dialing equipment. Refer to "Digital Communicator" on page 33 for an illustration of
the proper installation of this equipment.
20
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Product Description
1.7.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or
make changes in its facilities, services, equipment or procedures which may affect the operation of
this control panel. However, the telephone company is required to give advance notice of such
changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right
to temporarily discontinue service. Advance notification will be provided except in cases when
advance notice is not practical. In such cases, notification will be provided as soon as possible.
The opportunity will be given to correct any problems and to file a complaint with the FCC if you
believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY
LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same
telephone line.
The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment
is designed to be connected to the telephone network or premises wiring using a compliant RJ31X
male modular plug and compatible modular jack that is also compliant.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
21
Product Description
1.7.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety
requirements as prescribed in the appropriate Terminal Equipment Technical Requirements
document(s). The Department does not guarantee the equipment will operate to the users’s
satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the
facilities of the local telecommunications company. The equipment must also be installed using an
acceptable method of connection. The customer should be aware that compliance with the above
conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility
designated by the supplier. Any repairs or alterations made by the user to this equipment, or
equipment malfunctions, may give the telecommunications company cause to request the user to
disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power
utility, telephone lines and internal metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate
electric inspections authority, or electrician.
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication
of the maximum number of terminals allowed to be connected to a telephone interface. the
termination of an interface may consist of any combination of devices subject only to the
requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise
emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian
Department of Communications.”
Representative:
NOTIFIER/FIRE•LITE, CANADA
10 Whitmore Road
Woodbridge, Ontario L4L7Z4
Phone: (905) 856-8733
FAX: (905) 856-9687
IC Certificate Number: 2132A-10UD
Ringer Equivalence Number (REN): 0.0B
Load Number: 2
22
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
SECTION 2
Installation
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the
installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots
at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the
cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed. Sufficient knockouts
are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors
into the box. All wiring should be in accordance with the National and/or Local codes for fire
alarm systems.
2.1 Backbox Mounting
!
The circuit board contains static-sensitive components. Always ground yourself with a proper wrist
strap before handling any boards so that static charges are removed from the body. Use static
suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main
circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top
flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis
assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
See Page
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2 on page 24
Install center top fastener in the wall with the screw head protruding
Place backbox over the top screw, level and secure
Mark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
Install remaining fasteners and tighten
MS-5UD Board on Chassis
mounting holes
mounting slots
mounting studs
mounting slots
MS-5UD Backbox
5UDBRDINBOX.CDR
grounding stud:
attach solid earth
ground wire (refer to
Figure 2.4 on page 26)
mounting tabs
Figure 2.1 Chassis Mounting in Backbox
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
23
Installation
Semi-Flush Mounting
Do not recess box more
than 3.875” into wall to
avoid covering venting
holes on top of box.
Hinge Slot for
optional Dress Panel
Mounting
slots for
optional
Trim Ring
SemiFlush
mounting
hole
9050UDencl.cdr
Hinge Slot for optional
Dress Panel
Figure 2.2 Cabinet Dimensions
24
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
9050UDcab.cdr
Installation
Figure 2.3 Backbox and Battery Box
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
25
Installation
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all
sources of power before servicing. The panel and associated equipment may be damaged by
removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Refer to AC Power in the
section titled "Specifications" on page 14, for power and current requirements for each FACP
version. Run a pair of wires (with ground conductor) from the protected premises main breaker
box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code,
use 14 AWG (2.00 mm2, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other
equipment may be connected to this circuit. In addition, this circuit must be provided with
overcurrent protection and may not contain any power disconnect devices. A separate Earth
Ground connection must be made to ensure proper panel operation and lightning and transient
protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm2)] to the grounding stud
in the backbox. Do not use conduit for the Earth Ground connection since this does not provide
reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit
board using the plug-in connector and cable provided. The battery charger is current-limited and
capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
FLPS-7
Power Supply
AC Power
Hot (L1)
Ground
Neutral (L2)
FLPS-3
Power Supply
AC Power
AC Hot
AC Neutral
Earth
Ground Wire
5ud_10udacpowr.c
!
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.
+
J12
Ground Wire
to batteries
-
+
J12
to batteries
Figure 2.4 Operating Power Connections
26
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.3 Input Circuits
The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs. Each
circuit is compatible with System Sensor’s i3 smoke detectors which generate a maintenance signal
when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient
temperature falls below the detector rating of approximately 45oF. The maximum loop resistance
limit for each IDC is 100 ohms. The field wiring for each zone is supervised for opens, shorts and
ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i3 smoke detectors, any
normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.
Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A
Converter module. Refer to "CAC-5X Class A Converter Module" on page 34.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
UL listed Power Supervision Relay
(refer to Device Compatibility Document for list of compatible relays)
UL listed compatible 4-wire smoke detector
UL listed compatible
2-wire smoke detectors
manual pull stations
heat detectors
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
ms-10UDidc.cdr
Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)
Figure 2.5 IDC Connections
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
27
Installation
Combination Waterflow/Supervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm
switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any
circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of
Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch
(tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch
(waterflow)
ms10udcomboIDC.cdr
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the InLine Resistor as shown in Figure 2.6
Program the FACP Initiating Device Circuit as a Combination circuit as described in
"Input Zones" on page 59. Note that since a Waterflow Supervisory Switch is included in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to
"Waterflow Delay" on page 75.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition
is cleared) if the Combo Autoresettable Supervisory type code is selected
28
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.4 Output Circuits
2.4.1 Notification Appliance Circuits
Total current drawn from the four Style Y (Class B) Notification Appliance Circuits as well as other
DC power outputs cannot exceed 3.0 amps for the MS-5UD-3(E), MS-10UD-3(E) [2.5 amp
maximum per NAC] powered by the FLPS-3 power supply or 7.0 amps for the MS-5UD-7(C/E),
MS-10UD-7(C/E) [3.0 amps maximum per NAC] powered by the FLPS-7 power supply (refer to
"Power Supply Calculations" on page 133). Each circuit is supervised, power-limited and provides
special application power. Refer to the Fire•Lite Device Compatibility Document for a listing of
compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing the optional Class A Converter
module. Refer to "CAC-5X Class A Converter Module" on page 34.
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Polarized Bell
Polarized Bell
Polarized Strobe
Polarized Horn-Strobe
Polarized Horn
Polarized Horn
Dummy load any unused circuits (P/N: 71245)
+
-
+
-
ms-10UDnac.cdr
Notification Appliance Circuit
polarity shown in alarm condition
Figure 2.7 NAC Connections
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
29
Installation
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and Nonresettable 24 VDC power is available on the MS-5UD and
MS-10UD control panel.
Special Application
Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be
obtained from these terminals (power-limited)
•
Jumper JP31 pins 1 & 2 for nonresettable power (as
illustrated in figure to right)
•
Jumper JP31 pins 2 & 3 for resettable power
- 4
+ 3
- 2
+ 1
ms-10UDtb9.cdr
Special Application
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors
can be obtained from these terminals (power-limited)
Figure 2.8 Special Application Auxiliary Power
2.4.3 Relays - Programmable
The MS-5UD and MS-10UD control panels provide a factory default programmed alarm relay, failsafe trouble relay and supervisory relay. Each relay can be programmed to activate for other
conditions (refer to "Relays" on page 71). Each Form-C relay is rated for 2 amps @ 30VDC
(resistive) and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
ms10udrelay.cdr
Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or
total power failure.
Figure 2.9 Relay Terminals
30
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.4.4 Remote Synchronization Output
Synchronization is a feature that controls the activation of notification appliances in such a way that
all devices will turn on and off at exactly the same time. This is particularly critical when
activating strobes which must be synchronized to avoid random activation and a potential hazard to
individuals. Devices connected directly to the control panel’s NAC can be synchronized as
described in "Synchronized NAC Operation" on page 69.
Notification appliances connected to remote power sources may require synchronization with the
FACP’s devices. For the MS-5UD-3(E), MS-10UD-3(E), this can be accomplished by connecting
the Remote Synchronization Output from TB2 of the FACP to a compatible sync input of a power
supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics
the signal on NAC 1 (Out 1). This allows the devices connected to the power supply to be
synchronized with the devices connected to Out 1 on the FACP.
For the MS-5UD-7(C/E), MS-10UD-7(C/E), the Remote Sync Output is not required.
Synchronization for remote power supplies is provided directly from NAC1 (Out 1). Note that
NAC 1 (Out 1) must be programmed for sync operation when used for this purpose.
The Remote Synchronization Output is power-limited and supervised and requires a 4.7KΩ ELR
resistor at the remote power supply end of the wiring.
Remote Power Supply
Sync Input
4.7KΩ ELR
Remote Sync Output
FACP main circuit board
Figure 2.10 Remote Sync Output
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
31
Installation
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpowerlimited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
Power-limited Circuits
(Class 2)
Power-limited Circuits (Class 2)
Power-limited
Circuits
(Class 2)
AC Power
CAC-5X
CAC-5X
Hot (L1)
Ground
Neutral (L2)
4XTMF
Nonpowerlimited
Circuit
earth
ground
Nonpowerlimited
Circuit
Power-limited
Circuit
(Class 2)
10udULwire.cdr
MS-10UD FACP
Figure 2.11 Typical UL Power-limited Wiring Requirements
32
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.6 Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/
command is made possible via double line seizure as well as usage of an RJ31X style
interconnection. Note that it is critical that the panel's digital communicator be located as the first
device on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Customer Premises Equipment and Wiring
Network
Service
Provider’s
Facilities
Computer
RJ31X
Jack
Unused
RJ-11 Jack
FACP with DACT
Telephone
Line
Telephone
Fax Machine
Telephone
Unused
RJ-11 Jack
Answering
System
Telephone
Figure 2.12 DACT Installation
9050ACTAdact.cdr
Network
Demarcation
Point
10UDJACK.cdr
The control panel's digital communicator is built into the main circuit board. Connection and
wiring of two phone lines is required as shown below.
Figure 2.13 Wiring Phone Jacks
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
33
Installation
2.7 Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
2.7.1 CAC-5X Class A Converter Module
2.7.1.1 Installation
The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to
Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). The module plugs into connector J2 which is located at the top left of the MS-5UD
and MS-10UD main circuit board and J7 which is located at the top center of the MS-10UD.
Note that two CAC-5X modules are required to convert all NACs and IDCs on the MS-10UD to
Class A circuits.
To install the CAC-5X in the MS-5UD or MS-10UD, remove the two main circuit board
mounting screws referenced in the following illustration and replace with the two supplied
male/female standoffs in the locations indicated in the following figure. Carefully align the
connector on the CAC-5X with J2 on the FACP main circuit board and press the module
securely into place. Make certain the pins are properly aligned to prevent bending or breaking
of any connector pins. Secure the CAC-5X to the standoffs with the screws that were just
removed.
To install the second CAC-5X on J7 of the MS-10UD, remove the main circuit board mounting
screw referenced in the following illustration and replace with the supplied male/female
standoff. Insert the supplied plastic standoff in the location indicated in the following
illustration. Carefully align the connector on the CAC-5X with J7 and press the module
securely into place. Make certain the pins are properly aligned to prevent bending or breaking
of any connector pins. Secure the CAC-5X to the metal standoff with the screw that was just
removed.
Installation in MS-5UD or MS-10UD
CAC-5X Module
CAC-5X Module
Metal
Standoff
Metal
Standoff
Plastic
Standoff
ms-10udcac5mnt.cdr
Metal
Standoff
Installation in MS-10UD
MS-10UD Main Circuit Board
Figure 2.14 CAC-5X Module Installation
34
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.7.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the MS-5UD/MS10UD and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits
using TB4 of the MS-5UD/MS-10UD and TB1 of the CAC-5X. Note that the wiring will be
identical when using TB7 NAC and TB6 IDC of the MS-10UD. Make certain to observe
polarity when connecting the devices to the circuits. The B+ and A+ terminals must comprise
the feed and return for the positive side of a device and the B- and A- terminals must comprise
the feed and return for the negative side of a device. To configure any of the zones for Class B
when the CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and
install the End-of-Line Resistor after the last device on the circuit. Do not wire to the
corresponding A+ and A- terminals on the CAC-5X module.
Class B (Style B) IDC - 4.7 KΩ
½ watt ELR resistor
P/N:71252 (supervised and power-limited)
Class A (Style D) IDC
(supervised and power-limited)
Smoke
Smoke
Pull Station
Pull Station
Class A (Style Z) NAC
(supervised and power-limited)
Polarized
Bell
Polarized
Strobe
Heat
Heat
Polarized
Horn
Circuit polarities
shown in alarm
condition
B+
B-
B+
B+ B- B+ B- B+ B- B+ B- B+ B-
B-
Dummy load all unused
circuits - 4.7 KΩ
½ watt resistor
(P/N: 71245)
MS-5UD
Circuit Board
A+
A-
A+
A-
A+
A- A+ A- A+ A- A+ A- A+ A-
ms10udclassa.cdr
CAC-5X Class A Converter Module
Figure 2.15 Wiring NACs and IDCs for Class A Operation
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
35
Installation
2.7.2 4XTMF Option Module
The 4XTMF module can be plugged into connectors J4 and J5 on the main circuit board.
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP30 on the main circuit board to allow the control panel to supervise the
placement of the 4XTMF option module
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide
the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP
main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the supplied screws
6. When the installation has been completed, connect the wiring to the modules as indicated in
the following sections
7. Test system for proper operation
Standoffs
J4
ms5udbord.cdr
J5
Note: This illustration shows the installation of the Option Module on the 5-zone
panel. The module is installed in the same location on the 10-zone panel.
Figure 2.16 4XTMF Option Module Connection to MS-5UD
36
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.7.2.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in
addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity
circuit to open with a system trouble condition if no alarm condition exists. A disable switch
allows disabling of the transmitter output during testing to prevent accidental calling of the
monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the FACP. In addition, the System Trouble LED will turn on to
indicate the Disconnect condition.
Note: the 4XTMF Module is not directly suitable for transmitting reverse polarity
supervisory signal. For an application of reverse polarity of a supervisory signal,
refer to the Appendix titled "FACP with Keltron" on page 149.
Polarities are shown for module activation
TB1
1+
23+
45
6+
7-
TBL Jumper
No connection
}Municipal Box (nonpower-limited)*
* Wiring from these terminals can
exit the protected premises.
Dummy load terminals 6 and 7
(4.7kΩ, ¼ watt resistor) if
Municipal Box is not connected.
TBL
4xtmf.cdr
J1
Disconnect
Switch
shown in
disconnect
position
}Remote Alarm - Class
2
(power-limited)*
}Remote Trouble - Class
2
(power-limited)*
J2
Disconnect LED
Connect to FACP Connectors J4 & J5
Figure 2.17 4XTMF Transmitter Module
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
37
Installation
2.8 ANN-BUS Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any
modules or wiring.
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit.
Compatible devices include:
•
ANN-80 LCD Annunciator
•
ANN-S/PG Serial/Parallel Printer Interface Module
•
ANN-I/O LED Driver Module
•
ANN-LED Annunciator Module
•
ANN-RLY Relay Module
2.8.1 ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B). The length of the 4-conductor wire run is governed by the power pair
loading as described below.
2.8.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the
maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is
necessary to calculate the total worst case current draw for all modules on a single 4-conductor
bus. The total worst case current draw is calculated by adding the individual worst case
currents for each module. The individual worst case values are shown in the following table:
Model Number
Worst Case Current Draw
ANN-80 LCD Annunciator
0.040 amps
ANN-S/PG Serial/Parallel Printer Interface Module
0.040 amps
ANN-I/O LED Driver Module
0.200 amps
ANN-LED Annunciator Module
0.068 amps
ANN-RLY Relay Module
0.075 amps
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.
38
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
After calculating the total worst case current draw, Table 2.1 specifies the maximum distance
the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire
gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more
than 6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is
shown in the note below.
24 VDC Power Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case
Current Draw (amps)
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
1,852 ft.
4,688 ft.
* 6,000 ft.
*6,000 ft.
0.200
926 ft.
2,344 ft.
3,731 ft.
5,906 ft.
0.300
617 ft.
1,563 ft.
2,488 ft.
3,937 ft.
0.400
463 ft.
1,172 ft.
1,866 ft.
2,953 ft.
0.500
370 ft.
938 ft.
1,493 ft.
2,362 ft.
Table 2.1 Wiring Distances
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms)
Maximum Wire Length (feet)
(6,000 feet maximum)
=
6.0 Volts
Total Worst Case Current Draw (amps)
=
Maximum Resistance (Ohms)
Rpu
*500
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire Gauge
22
18
16
14
Ohms per 1,000 feet (Rpu)
16.2
6.4
4.02
2.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring
limitations:
Wire Gauge
18
16
14
12
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Maximum Wire Length
312 feet
497 feet
787 feet
1,250 feet
39
Installation
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
•
2 ANN-80 Remote Fire Annunciators
•
1 ANN-S/PG Serial/Parallel Printer Interface Module
•
1 ANN-I/O LED Driver Module
The total worst case current is calculated as follows:
ANN-80 Current Draw
= 2 X 0.040 amps
= 0.080 amps
ANN-S/PG Current Draw
= 1 X.0.040 amps
= 0.040 amps
ANN-I/O Current Draw
= 1 X.0.200 amps
= 0.200 amps
Total Worst Case Current Draw
= 0.320 amps
Using this value and referring to the Wiring Distance Table 2.1 on page 39, it can be found that
the available options are:
463 feet maximum using 22 Gauge wire
1,172 feet maximum using 18 Gauge wire
1,866 feet maximum using 16 Gauge wire
2,953 feet maximum using 14 Gauge wire
2.8.1.2 Wiring Configuration
Figure 2.18 illustrates the wiring between the FACP and ANN-BUS devices.
FACP
TB3
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
Figure 2.18 FACP wiring to ANN-BUS Device
40
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.8.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 2.19 illustrates the powering of ANN-BUS devices from an auxiliary power supply such
as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANNBUS power requirements.
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
TB3
MS-5UD/MS-10UD
ANN-BUS
-24 VDC
ANN-80
+24 VDC
ANN-BUS and power wiring are
supervised and power-limited
FCPS-24FS6/8
Figure 2.19 Powering ANN-BUS Devices from FCPS-24FS6/8
2.8.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 80).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions.
Unless otherwise specified in the documentation supplied with each device, switch positions 6 and
above must be set to OFF.
Address
not valid
01
02
03
04
05
06
07
08
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Switch 4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Switch 3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
Switch 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
Switch 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
41
Installation
2.8.3 ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator which
mimics the FACP display. It also provides system status indicators for AC Power, Alarm, Trouble,
Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and FACP is
accomplished over a two wire serial interface employing the ANN-BUS communication format.
The devices are powered, via two additional wires, from either the host FACP or remote UL-listed,
filtered, power supply.
2.8.4 Specifications
•
Operating Voltage Range: 18 VDC to 28 VDC
•
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail ( not backlit): 15.0 mA
•
For use indoors in a dry location
2.8.5 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the
annunciator.
2.8.5.1 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical
box. Select and remove the appropriate knockout(s), pull the necessary wires through the
knockouts and mount the annunciator in or on the wall depending on the type of installation
desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the
annunciator to the electrical box/wall. The cover cannot be reattached or removed after the
annunciator has been mounted.
2.8.5.2 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the
terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Annunciator cover
with LCD display
Key switch shown
in ON position
42
Annunciator backplate
Press in latch
and
Pull annunciator
cover open
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.8.5.3 Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1
wiring channel
wires
TB1
2. Remove appropriate amount of wire insulation
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1
terminals 3 & 4. Make certain to connect A to A and B to B
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2
(+). Make certain to observe proper polarity
6. If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity
7. After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical
box
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
43
Installation
FACP
TB3
4 3 2 1
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
Figure 2.20 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the MS-5UD/MS-10UD.
MS-5UD/MS-10UD (TB3)
Terminal 4 GND (-)
Terminal 3 PWR (+)
Terminal 2 A (ANN-BUS)
Terminal 1 B (ANN-BUS)
ANN-80 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS" on page 80 in this manual for detailed programming information. Select the LCD
option for programming.
44
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.8.6 ANN-S/PG Serial/Parallel Printer Interface Installation
The ANN-S/PG Serial/Parallel Printer Interface module allows the ancillary connection of a serial
or parallel printer to the FACP for a real-time log of system events, detector status reports and event
history. Proceed with the installation as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 2.21
TB3
MS-5UD/MS-10UD
ANN-S/PG Module
Parallel
ANN-BUS and power wiring are
supervised and power-limited
Cable
Connectors for
connection to
printer
Serial
Figure 2.21 ANN-S/PG Connection to FACP
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number
(address) to the module
4. Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to "ANN-BUS" on page 80)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to "Auto-Configure" on page 81)
5. Connect a printer to the ANN-S/PG Parallel and/or Serial connectors (refer to Figure 2.21 on
page 45)
2.8.6.1 Specifications
•
Operating Voltage: 24 VDC
•
Current (Alarm and Standby): 45 mA
•
Ambient Temperature: 32oF to 120oF (0oC to 49oC)
•
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
•
Mounting: Surface
•
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
•
For indoor use in a dry location only
2.8.6.2 PRN-6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the
event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This
section contains information on connecting a printer to the control panel and setting the printer
options.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
45
Installation
2.8.6.2.1 Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.
The building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25
cable. One end of the cable will plug into the DB-25 connector on the PRN-6F printer and the
other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a
Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the
same time.
2.8.6.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN-6F printer for instructions on using the
printer menu controls. Set the printer options (under the menu area) as shown in the following
table:
Table 2.2 PRN-6F Setup Options
Option
Font
LPI
ESC Character
Bidirectional Copy
CG-TAB
Country
Auto CR
Color Option
Formien
Lines
Standard
46
Setting
HS Draft
6 LPI
ESC
ON
Graphic
E-US ASCII
OFF
Not Installed
6LPI=60
Exec 10.5
Option
CPI
Skip
Emulate
I/O
Buffer
Serial
Baud
Format
Protocol
Character Set
SI.Zero
Auto LF
PAPER
BIN 1
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
Setting
10CPI
0.5
Epson FX-850
40K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
On
12/72”
12/72”
12/72”
12/72”
12/72”
12/72”
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.8.7 ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The following sections describe hardware installation. Refer to the section titled "ANNBUS" on page 80 for programming information.
2.8.7.1 ANN-I/O Board Layout
Figure 2.22 illustrates the ANN-I/O board showing locations of screw terminals for connection
to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANNBUS ID number.
Terminals not used (future)
ANN-BUS (ID#)
Address DIP
switch
ANN-BUS Connector
Figure 2.22 ANN-I/O Board Layout
2.8.7.2 Specifications
•
Max. ANN-BUS Voltage: 28 VDC
•
Max. Current:
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
•
Operating Temperature: 32oF to 120oF (0oC to 49oC)
•
For indoor use in a dry location only
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
47
Installation
2.8.7.3 ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.23. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming.
TB3
MS-5UD/MS-10UD
ANN-I/O Module
ANN-BUS and power wiring are
supervised and power-limited
Figure 2.23 ANN-I/O Connection to FACP
48
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.8.7.4 ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized
so that there is approximately 10 mA of current for each LED. No series resistors are required.
LED outputs are mapped to output circuits. Refer to the section titled "ANN-I/O LED Zone
Assignments" on page 83 of this manual.
The LEDs are wired as illustrated in Figure 2.24. Note that the illustration depicts only
connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
Figure 2.24 ANN-I/O Board Layout
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
49
Installation
2.8.8 ANN-LED Annunciator Module
The ANN-LED annunciator module provides LED annunciation of general system faults and input
zones when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble
(yellow) and supervisory (yellow) indication for up to ten input zones.
Canadian Applications: The ANN-LED is supplied standard with the MS-5UD-7C and MS-10UD7C models. It is mounted to the dress panel included with these models.
2.8.8.1 ANN-LED Board Layout
Figure 2.25 illustrates the ANN-LED board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.25 ANN-LED Board Layout
2.8.8.2 Specifications
•
Max. ANN-BUS Voltage: 24 VDC
•
Max. Current:
Alarm: 68 mA
Standby: 28 mA
•
Operating Temperature: 32o F to 120o F (0o C to 49o C)
•
For indoor use in a dry location only
2.8.8.3 Mounting/Installation
Install the ANN-LED Module as described in the documentation supplied with the annunciator.
50
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.8.8.4 ANN-LED Connection to FACP
Figure 2.26 illustrates the ANN-LED board wiring connections to the FACP.
ANN-LED
FACP
-24 VDC
+24 VDC
ANN-BUS
Figure 2.26 ANN-LED Connection to FACP
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
51
Installation
2.8.9 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
2.8.9.1 ANN-RLY Board Layout
Figure 2.27 illustrates the ANN-RLY board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.27 ANN-RLY Board Layout
2.8.9.2 Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Relay Contact Ratings:
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
•
Operating Temperature: 32o F to 120o F (0o C to 49o C)
•
For indoor use in a dry location only
2.8.9.3 Mounting/Installation
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis.
52
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Installation
2.8.9.4 ANN-RLY Connection to FACP
Figure 2.28 illustrates the ANN-RLY board wiring connections to the FACP.
ANN-RLY
FACP
-24 VDC
+24 VDC
ANN-BUS
Figure 2.28 ANN-RLY Connection to FACP
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
53
Installation
2.9 ANN-BUS Audio Panel
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any
wiring.
The FACP must be enabled to communicate with the ACC-25/50ZS Audio Panel over the ANNBUS (refer to "ANN-BUS Enabled" on page 80). This is accomplished by programming the
Audio Panel ANN-BUS address into the FACP (refer to "BUS Modules" on page 80). For details
on setting the ANN-BUS address and programming the audio panel, refer to the ACC-25/50ZS
Series Audio Panel manual (document #51889).
The ACC-25/50ZS Series audio panel connects to the FACP via the ANN-BUS communication
circuit. The five input zones on the MS-5UD correspond to the first five ACC-25/50ZS Series
audio zones and the ten input zones on the MS-10UD correspond to the first ten ACC-25/50ZS
Series audio zones. The programmer can select which of the five audio messages at the audio panel
will play when an FACP input zone goes into alarm (refer to "ACC Message" on page 63). The
message will play over the corresponding audio panel output circuit. For example, if FACP Input
Zone 3 goes into alarm, the programmed message will play over the ACC-25/50ZS output circuit 3.
If two or more input zones are active at the same time, the highest priority message will turn on.
One of the FACP input zones can be programmed as an All-Call Zone. If this zone goes into alarm,
all ACC-25/50ZS Series audio zones will activate (refer to "ANN-AUDIO Options Screen" on
page 86).
A fault at the ACC-25/50ZS Series panel will cause the FACP to indicate a System Trouble and the
display will indicate a Voice Evac Fault.
The only connection between the MS-5UD/10UD and the ACC-25/50ZS audio panel is a pair of
communication wires connected between the A/B terminals on TB3 of the FACP and TB1
terminals 2 & 3 of the ACC-ZPMK module on the ACC-25/50ZS.
FACP
A (+)
B (-)
+
-
ANN-BUS
ACC-ZPMK
on ACC-25/50ZS
Figure 2.29 FACP Connection to ACC-25/50ZS Audio Panel
54
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
Programming
SECTION 3
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below:
Program feature
Permitted in
Settings permitted
Possible settings
or option
UL 864? (Y/N)
in UL 864
Refer to "Trouble Call Limit (Dialer Runaway Prevention)" on page 99.
Trouble Call Limit =
Trouble Call Limit
N
Trouble Call Limit = 0 (factory default): unlimited
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Refer to "Remote Download" on page 129.
Remote Download
Y
Remote Download - Proprietary No
Remote Download - Proprietary Yes
0 for unlimited Central Station trouble
calls
Remote Download
Proprietary Yes for
Proprietary system
intended to protect
only contiguous
properties
3.1 User Programming
!!
The MS-5UD/MS-10UD FACP is completely field programmable using the panel keypad and
requires no special software skills. While programming the FACP, the fire protection capabilities of
the control panel are enabled. Programming Mode times-out after 10 minutes of inactivity.
Site-specific programming may be accomplished in the following ways:
•
Manual programming or editing, using the FACP keypad
•
Remote Programming and Editing Feature - allows creation and editing of site-specific
custom programs using a Windows-based computer and modem. For programs requiring a
large amount of data entry, this method may be preferred. A PK-CD programming CD ROM
can be ordered for this purpose
•
Local Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and USB connection. For programs requiring a
large amount of data entry, this method may be preferred. A PK-CD programming CD ROM
can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
SYSTEM ALL NORMAL
10:00A 070707
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or
supervisory event exists at the panel, the event must be cleared before entering Programming mode.
To access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FUTURE USE
4=REMOTE DOWNLOAD
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
55
Programming
See Page
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read
Status Mode which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to "Read Status" on page 118 for a
detailed description of this feature.
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized
person. After pressing 2, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.
Pressing 4 will select Remote Download which allows the user to enable the remote programming
option. Refer to "Remote Download" on page 129.
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the
display reads System All Normal. Ten minutes of inactivity will also cause the panel to exit
Programming Mode Note that the data which is entered during Programming mode is not saved
until the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset key is
pressed or power is lost before exiting Programming mode, all data just entered will be lost.
User Programming Levels
There are two user programming levels:
•
•
User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.2 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has
not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition
will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an
example of a possible trouble message that may be displayed.
TROUBL
PULL STATION
ZONE 1 OPEN FAULT
09:03A 070707
3.3 Programming Screens Description
See Page
Three options are available when the Enter key is pressed: Read Status, Programming and Remote
Download Mode. The Read Status and Programming options have multiple functions or features
which may be chosen. To view all of the choices, it is necessary that the programmer scroll through
a number of additional subscreens. These selections are displayed on multiple screens to make
them more readable for the programmer. Refer to "Master Programming Level" on page 58, for
additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the
programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed
in the upper right corner of the screen being viewed. The programmer can then press the keypad
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the
programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.
56
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.4 Programming and Passwords
See Page
There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in
nonvolatile memory. The factory set passwords can be changed by the user as described in
"Password Change" on page 103. If an invalid password is entered, the blinking cursor will return
to the first password character position. To exit Programming or Read Status mode at any time,
press the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC
key in order to store the program data entered during this mode. If the Reset key is pressed or
power is lost before exiting Programming mode, the data just entered will not be saved.
To access user Programming mode, press the Enter or Mode key. The LCD will display the
following:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FUTURE USE
4=REMOTE DOWNLOAD
To enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
*****
Entering the Master level password (default 00000) will cause the following screen to appear:
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
If the Maintenance level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
57
Programming
3.5 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble LED flashes until Programming mode is exited. The following display will
appear:
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as
illustrated below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
58
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.1 Input Zones
The Input Zones option allows the user to initially program or change the programming for the five
input zones (circuits) on the MS-5UD or the ten input zones (circuits) on the MS-10UD. Pressing
1, while viewing Programming Screen #1, will select the Input Zones option and display a screen
similar to the following:
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
INPUT ZONES
1=ZONE 1
2=ZONE 2
3=ZONE 3
Input Zone Screen #1
Pressing the down arrow key will display additional screens for Input Zones 4 through 5 in the MS5UD or Input Zones 4 through 10 in the MS-10UD. To program a specific zone, press the number
key corresponding to the desired zone while viewing one of the Input Zone screens. To program
Input Zone 1, press the 1 key while viewing Input Zone Screen #1. The following screens will be
displayed:
Normal PULL STATION
**********************
ZONE 1
PRESS
TO EDIT
Edit Input Zone Screen #1
To change the programming for the displayed zone, press the keyboard ‘down’ arrow key to
view the Edit Zone screens.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
59
Programming
The following examples show the editing of Input Zone 1:
INPUT ZONE 1
1=ENABLED
YES
2=TYPE PULL STATION
3=VERIFICATION
NO
Edit Input Zone Screen #2
INPUT ZONE 1
1=PAS/PRE-SIG DELAY
NO DELAY
Edit Input Zone Screen #3
INPUT ZONE 1
1=FREEZE SUPV.
2=ACC MSG#
NO
2
Edit Input Zone Screen #4
INPUT ZONE 1
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Input Zone Screen #5
Enable/Disable Zone
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2.
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled
No is selected, the zone will be disabled by the control panel, preventing the circuit from
reporting alarms and troubles to the panel. The control panel LCD will display the zone which
has been disabled and FACP will turn on the Trouble LED.
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:
ZONE TYPE
1=PULL STATION
2=WATERFLOW
3=WATERFLOW NS
Zone Type Screen #1
60
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
Pressing the down arrow key will display additional zone types as indicated in the following
table.
Note: Some of the following Zone Types are not available for Canadian applications. Refer to
"Canadian Option" on page 79 for additional details.
Zone Type
Pull-Station
Waterflow
Waterflow Nonsilenceable
Combo
Combo AutoResettable
2-Wire Detector
Normally Open Contact
Fire
Tamper
Supervisory
Supervisory AutoResettable
Medic-Alert
Hazard-Alert
Tornado-Alert
Proc-Mon
Procmon-AR
AC-Loss-Mon
Ack-Switch
Sil-Switch
Drill-Switch
Reset-Switch
PAS-Bypass
Drill-Switch AutoResettable
Action When Activated
Fire Alarm
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm (uses waterflow delay)
Fire/Supervisory (uses waterflow delay)
Fire/Supervisory AR, nonlatching (uses waterflow delay)
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory
Supervisory, latching
Supervisory, nonlatching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Piezo
Piezo, nonlatching
Trouble
Acts like panel Acknowledge Key
Acts like panel Alarm Silence Key
Acts like panel Drill Key
Acts like panel Reset Key
Positive Alarm Sequence Disable
Acts like panel Drill Key, nonlatching
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
Note: Almost any Input Zone type can activate an ACC-25/50ZS audio zone and output an
assigned message with the exception of ACKNOWLEDGE, SILENCE, RESET and PAS
BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all of
the corresponding ACC-25/50ZS audio zones to go active and will output Message 1.
Verification
See Page
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition
and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Zone Screen
#2 so that the display reads Verification On. Each time the 3 key is pressed, the display will
toggle between Verification On and Verification Off. For a detailed description, refer to "Alarm
Verification (None or One Minute)" on page 117.
Note that verification can only be enabled for a zone that is programmed as a smoke detector
type. Zones programmed for any other type will not allow the Verification feature to be
enabled. Do not use the verification feature if a mix of smoke detectors and normally open
contact devices are connected to the same zone.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
61
Programming
PAS/Pre-Signal Delay
Pressing 1 while viewing Edit Input Zone Screen #3 will display the following screen:
PAS/PRE-SIG DELAY
1=NO DELAY
2=PRE-SIGNAL DELAY
3=PAS DELAY
INPUT ZONE #
1=PAS/PRE-SIG DELAY
NO DELAY
PAS/Pre-Signal Delay Screen
Edit Input Zone Screen #3
Pre-signal
See Page
The Pre-signal option programs the zone to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the
alarm relay and communicator will respond to the initial alarm immediately. To enable the Presignal feature, press 2 while viewing PAS/Pre-Signal Screen. Refer to "Presignal" on page 115.
PAS
See Page
The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time
of up to 3 minutes. To enable the PAS feature, press 3 while viewing the PAS/Pre-Signal
Screen. This option is available only for circuits programmed as smoke detector circuits. Refer
to "Positive Alarm Sequence" on page 115.
Freeze Supervision
Pressing 1 for Freeze Supv. while viewing Edit Input Zone Screen #4 programs the FACP to
supervise the devices connected to the selected zone for freeze conditions. Each press of the 1
key will toggle the display between Freeze Supv. Yes and No. The factory default setting is No
Freeze Supervision.
INPUT ZONE #
1=FREEZE SUPV.
NO
2=ACC MSG #
Edit Input Zone Screen #4
62
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
ACC Message
Pressing 2 for ACC MSG # while viewing Edit Input Zone Screen #4 will cause the following
screens to be displayed:
INPUT ZONE #
1=FREEZE SUPV.
ACC MSG NUMBER
1=NO MSG-ACTIVE
2=NO MSG-INACTIVE
3=MESSAGE 1
NO
2=ACC MSG #
Edit Input Zone Screen #4
ACC Message Screen #1
ACC MSG
1=MESSAGE
2=MESSAGE
3=MESSAGE
NUMBER
2
3
4
ACC Message Screen #2
ACC MSG NUMBER
1=MESSAGE 5
ACC Message Screen #3
Using these screens, the programmer can assign an audio message to each input zone. The NO
MSG-ACTIVE option is the factory default selection which means that no message has been
programmed for the input zone but its corresponding ACC-25/50ZS audio zone will turn on
when this input zone goes active (if an input zone with a programmed audio message goes
active, the message will also be played over this zone). The NO MSG-INACTIVE option will
not turn on the corresponding ACC-25/50ZS audio zone when this input goes active. If
MESSAGE 1 through 5 is the programmed option, the selected message will play when the
FACP is connected to an ACC-25/50ZS Audio Panel via the ANN-BUS and the corresponding
FACP input zone goes into alarm.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
detector currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #4 will
cause the following screen to be displayed:
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Edit Input Zone Screen #5
Noun/Adjective Screen
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
63
Programming
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective
screens. Press the number corresponding to the adjective that is to be used as a descriptor for
the location of the detector currently being programmed. When an adjective has been selected,
it will appear at the top of the display as indicated by the asterisks.
**********************
1=NORTH
2=SOUTH
3=EAST
**********************
1=3RD
2=4TH
3=5TH
Adjective Screen #1
Adjective Screen #5
**********************
1=WEST
2=FRONT
3=CENTER
**********************
1=FLOOR1
2=FLOOR2
3=FLOOR3
Adjective Screen #2
Adjective Screen #6
**********************
1=REAR
2=UPPER
3=LOWER
**********************
1=FLOOR4
2=FLOOR5
3=ROOM
Adjective Screen #3
Adjective Screen #7
*********************
1=MAIN
2=FIRST
3=2ND
Adjective Screen #4
64
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
Press the number corresponding to the noun that is to be used as a descriptor for the location of
the detector currently being programmed. When a noun has been selected, it will appear at the
top of the display as indicated by the asterisks.
Noun/Adjective Screen
**********************
1=BASEMENT
2=BOILER RM
3=CLASSROOM
Noun Screen #1
**********************
1=CLOSET
2=CORRIDOR
3=ELECTRIC RM
Noun Screen #2
**********************
1=ELEVATOR
2=ENTRANCE
3=FLOOR
Noun Screen #3
**********************
1=GARAGE
2=HALLWAY
3=HVAC RM
Noun Screen #4
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
**********************
1=KITCHEN
2=LOBBY
3=OFFICE
Noun Screen #5
**********************
1=PATIENT
2=RESTROOM
3=ROOM
Noun Screen #6
**********************
1=STAIRWAY
2=STOREROOM
3=WING
Noun Screen #7
**********************
1=ZONE
Noun Screen #8
65
Programming
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the
previous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns
which have been programmed into the control panel by the user utilizing the PK-CD
programming kit. These descriptors are selected as described in the previous sections.
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Description
The Description selection allows the programmer to enter additional information about the zone
currently being programmed. This information will be displayed as part of the device label on
the display. Pressing 2 while viewing Edit Input Zone Screen #4 will cause the following
screen to be displayed:
Noun/Adjective Screen
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
ZONE # DESCRIPTION
PRESS ENTER IF DONE
********************
Edit Input Zone Screen #4
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter
additional descriptive information about the device being programmed. This information will
appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric
characters from the keypad, repeatedly press the appropriate key until the desired character is
displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three
times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor
one position to the right and repeat the process to enter the next character. To enter a space,
press the * (QZ) key four times until a blank appears in the desired position. When all
characters have been entered, press the Enter key to store the information. The display will
return to the Edit Detector Screen #5, displaying the new information at the bottom of the
screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on
the first letter of the Description, Adjective or Noun field as follows:
66
•
If the zero key is pressed, a 0 is placed in the first letter position
•
If the zero key is then pressed a second time with no intervening key actions, the entire field
is replaced with the field entered for the previous device programmed, and the cursor moves
to the last character of the field (Recall function). The Recalled Adjective or Noun field may
now be changed letter-by-letter
•
If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last
character are also numbers, they are also incremented (overflow)
•
The above increment function may be repeated with each press of the zero key
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305
4. Press the Enter key to store the information
3.5.2 NAC (Notification Appliance Circuit)
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
The options for the NACs on the control panel main circuit board can be configured by pressing 2
while viewing Programming Screen #2. The following screens will be displayed:
Programming Screen #1
NACS
1=NAC 1
2=NAC 2
3=NAC 3
4=NAC 4
NAC Selection Screen
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3 or 4 for NAC 4.
To program an NAC circuit, press the number corresponding to the NAC to be programmed. The
following screens will be displayed for each selection:
NAC #
1=ENABLED
2=CODING
STEADY
YES
NAC Screen #1
NAC #
1=SILENCE
2=AUTO SILENCE
3=SIL INHIBITED
YES
NO
NO
NAC Screen #2
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
67
Programming
3.5.2.1 Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This
will prevent the selected main circuit board NAC from activating its devices. Each press of the
1 key will cause the display to toggle between Enabled Yes and Enabled No.
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is
enabled.
NAC #
1=ENABLED
2=CODING
STEADY
NAC Screen #1
3.5.2.2 NAC Coding
The Coding feature allows the programmer to select the type of output that the main circuit
board notification appliances will generate when activated. Pressing 2 while viewing NAC
Screen #1 will cause the following displays to appear:
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2
CODING
1=SYNC SYSTEM SENSR
2=SYNC WHEELOCK
3=SYNC GENTEX
Coding Screen #3
CODING
1=SYNC FARADAY
2=SYNC AMSECO
Coding Screen #4
68
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
The programmer can select the notification appliance output by pressing the number
corresponding to the desired output. The coding selections are:
•
•
•
•
•
•
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second
off
Two Stage 3 Minutes or 5 Minutes - refer to "Two Stage Operation" on page 69 for a
description of this feature
Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to
"Synchronized NAC Operation" on page 69 for additional information
Selection of one of the above options will cause the control panel to store the information in
memory and return the display to NAC Screen #1, which will display the new coding choice.
3.5.2.2.1 Two Stage Operation
Two Stage operation consists of the following:
•
1st stage output - 20 ppm (pulse-per-minute) coding
•
2nd stage output - Temporal coding as described above
If Two Stage operation is programmed as the Coding option, the following sequence of events
will occur during an alarm.
1. The on-board NACs will activate with a 1st stage output upon activation of any alarm
2. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not been
pressed, all NACs presently in 1st stage activation will go to 2nd stage activation
3. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation
will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already
in 2nd stage activation
4. If another alarm point is activated and the countdown timer is counting, the alarm point
will have no effect on the NACs
5. If another alarm point is activated and the countdown timer has stopped counting due to
the Acknowledge switch being pressed, the countdown timer will restart and the NACs
will respond as outlined in step 1. NACs already in 2nd stage activation will not be
affected
3.5.2.2.2 Synchronized NAC Operation
Synchronization is a panel feature that controls the activation of notification appliances in such
a way that all devices will turn on and off at exactly the same time. This is particularly critical
when activating strobes which must be synchronized to avoid random activation and a potential
hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s
devices.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
69
Programming
3.5.2.2.2.1 Maximum Number of Strobes for Synchronization
The maximum current draw for a Notification Appliance Circuit cannot exceed 2.5 amps for
models with the FLPS-3 power supply or 3.0 amps for models with the FLPS-7 power supply
(refer to the AC Power section under "Specifications" on page 14). Refer to the
manufacturer’s documentation supplied with the Strobes to determine the maximum current
draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that
can be attached to each circuit. Following is a list of the strobes that have been tested with this
FACP and the maximum number that can be connected to each NAC. Make sure that the NAC
maximum current is not exceeded:
Strobe Manufacturer
System Sensor
NAC #
1=SILENCE
YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
NAC Screen #2
FACP with FLPS-3 Power Supply:
Maximum Number of Strobes
FACP with FLPS-7 Power Supply:
Maximum Number of Strobes
35
46
Wheelock
24
50
Gentex
22
39
Faraday
22
33
Amseco
19
34
3.5.2.3 Silence
Pressing 1 while viewing NAC Screen #2 will cause the following screen to be displayed:
SILENCEABLE
1=SILENCEABLE
2=NON SILENCEABLE
3=SYNC MUTE
Silenceable Screen
Pressing 1 while viewing the Silenceable Screen will program the selected NAC as a
silenceable circuit. This will allow the NAC to be silenced by pressing the Alarm Silence key
or by the Auto Silence feature.
Pressing 2 while viewing the Silenceable Screen will program the selected NAC as a
nonsilenceable circuit. This will prevent the selected main circuit board NAC from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing 3 while viewing the Silenceable Screen will program the selected NAC as a
synchronized mute circuit. Refer to "Synchronized NAC Operation" on page 69 for a
description of synchronization.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for Sync Mute, only the audible devices will be turned off if the Silence key is
pressed or if the Autosilence feature is enabled. The visual devices (strobes, etc.) will continue
to operate.
70
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.2.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board
silenceable notification appliances after a programmed length of time. To enable this feature
and program the time delay before Auto Silence activation, press 2 while viewing NAC Screen
#2. The following screens will be displayed:
PROGRAM NAC #
1=SILENCEABLE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
NAC Screen #2
Auto Silence Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the
display will return to NAC Screen #1.
3.5.2.5 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit
board NAC for a period of one minute. Resetting the FACP will also be prevented for one
minute while the NAC programmed for silence inhibit is activated. Pressing 3 while viewing
NAC Screen #2 will cause the display to change from the factory default of Silence Inhibit No
to Silence Inhibit Yes. Each press of the 3 key will cause the display to toggle between the two
options.
3.5.3 Relays
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Pressing 3 while viewing Programming Screen #1 will allow the programmer to configure the three
main circuit board Form-C relays. The following screen will be displayed:
Programming Screen #1
RELAYS
1=RELAY 1
ALARM
2=RELAY 2
TROUBLE
3=RELAY 3
SUPERV
Relays Selection Screen
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
71
Programming
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following
screens will appear for each relay to be programmed:
RELAY TYPE
1=ALARM
2=TROUBLE
3=SUPERVISORY
Relay Screen #1
RELAY TYPE
1=COMM FAIL
2=MEDICAL
3=SILENCEABLE ALARM
Relay Screen #3
RELAY TYPE
1=PROCESS MONITOR
2=AC LOSS
3=HAZARD
Relay Screen #2
While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the Escape
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining
relays.
Note: A relay programmed with the Silenceable Alarm type will deactivate when the FACP Alarm
Silenced LED is illuminated.
72
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.4 System Setup
System Setup allows the programmer to configure the following control panel features:
•
•
•
•
•
•
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout, which is blank, to a user defined readout when the control panel is in
Normal condition
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The
piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If
the Trouble Reminder feature is not enabled and a trouble condition is not cleared within 24
hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the
central station if connected
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to "Canadian Option" on page 79).
Important! For Canadian Applications, this option must be set to ON prior to any other
panel programming.
Charger Disable: This option allows the programmer to disable the onboard battery charger
in the event an external battery charger is being used
Pressing 1 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
Programming Screen #2
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TROUBLE REMIND
NO
2=CANADIAN OPTION OFF
3=CHARGR DISABLE
NO
System Setup Screen #2
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
73
Programming
3.5.4.1 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1
while viewing System Setup Screen #1. The following screen will be displayed:
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
TIMERS
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLW DELAY
120
120
0
Timer Screen #1
TIMERS
1=AC LOSS DELAY
2
Timer Screen #2
TIMERS
1=PAS DELAY
120
2=PRE SIGNAL
120
3=WATERFLW DELAY
0
Timer Screen #1
3.5.4.1.1 PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180
seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The
following display will appear:
PAS DELAY
RANGE 000-180 SECONDS
PAS Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
3.5.4.1.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay
of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer
Screen #1. The following screen will be displayed:
PRESIGNAL DELAY
RANGE 000-180 SECONDS
Pre-signal Delay Screen
74
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
Note that the FACP can have both PAS and Pre-signal timers programmed with values but a
zone can only use either the PAS or Pre-signal feature, but not both.
TIMER
1=PAS DELAY
120
2=PRE SIGNAL
120
3=WATERFLW DELAY
0
Timer Screen #1
3.5.4.1.3 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any
built-in delays of the waterflow device. The factory default setting for Waterflow delay is 000
for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for
Waterflow delay, press 3 while viewing Timer Screen #1. The following screen will be
displayed:
WATERFLOW DELAY
RANGE 00-90 SECONDS
Waterflow Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the
time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
TIMER
1=AC LOSS DELAY 2
3.5.4.1.4 AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the
length of the desired delay. Press 1 while viewing Timer Screen #2 to display the following:
Timer Screen #2
AC LOSS DELAY
RANGE 00-24 HOURS
AC Loss Delay Screen #1
A flashing cursor will appear in the lower left corner of the display. The factory default setting
is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When
the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC
Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC
Loss Delay setting.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
75
Programming
3.5.4.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will
cause the following to be displayed:
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
SELECT BANNER
1=FACTORY BANNER
2=USER BANNER
System Setup Screen #1
Select Banner Screen
Pressing 1 while viewing the Select Banner Screen will display the following screen:
FACTORY BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
This screen allows the user to select the factory default Banner which will be displayed when
the system is in Normal Mode of operation. Press the Enter key to accept this as the default
display. Press the Escape key to cancel and return to the Select Banner Screen.
Pressing 2 wile viewing the Select Banner Screen will display the following screen:
USER BANNER-LINE 1
PRESS ENTER IF OK
User Defined Banner Screen
This screen allows the programmer to enter a custom banner. A flashing cursor will appear in
the bottom left corner of the display. A maximum of 20 characters (including spaces) can be
entered into the screen. After entering up to 20 characters in the screen, press Enter to store the
entry. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until
the desired character is displayed in the first position. For example, to enter the letter B, press
the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow
key to move the cursor one position to the right and repeat the process to enter the next
character. To enter a space, press the * (QZ) key four times to place a blank in the desired
position. When all characters have been entered, press the Enter key to store the information.
The display will return to the Select Banner Screen.
76
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
3.5.4.3 Time-Date
The control panel time and date can be changed by pressing 3 while viewing the System Setup
Screen #1. The following screen will be displayed:
System Setup Screen #1
TIME AND DATE
1=TIME
10:00 AM
2=DATE
07072007
3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE
1=DAYLIGHT SAVINGS
Time-Date Screen #2
3.5.4.3.1 Time
To change the time, press 1 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER TIME AS 12HRS
:
10:00 AM
1=AM
2=PM
Time Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
time. To change the time, enter the two-digit hours followed by the two-digit minutes. The
cursor will move one position to the right each time a digit is entered. After the last minutes
digit is entered, the cursor will again move one position to the right. At this point enter 1 for
AM or 2 for PM. The display will then return to the Time-Date Screen which will show the
new time entry. If an error is made while entering a digit, press the CLR key to delete the entire
entry and beginning again.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
77
Programming
3.5.4.3.2 Date
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER DATE
**-**-****
MONTH DAY YEAR
07-07-2007
Date Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
date. To change the date, enter the two-digit month followed by the two-digit day and then the
two-digit year (07 for 2007, 08 for 2008, etc.). The cursor will move one position to the right
each time a digit is entered. After the last year digit is entered, the display will return to the
Time-Date Screen which will show the new date entry. If an error is made while entering a
digit, press the CLR key to delete the entire entry and beginning again.
3.5.4.3.3 Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time.
Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR
and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
Note: If the clock is changed to 24 hour (military) format, the date will change to the European
standard of Day-Month-Year (for display purposes only).
3.5.4.3.4 Daylight Savings Time
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
TIME AND DATE
1=DAYLIGHT SAVINGS
DAYLIGHT SAVINGS
1=ENABLED
YES
2=START MONTH
MAR
3=START WEEK
WK 2
Daylight Savings Screen #1
Time & Date Screen #2
DAYLIGHT SAVINGS
1=END MONTH
NOV
2=END WEEK
WK 1
Daylight Savings Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows
the programmer to select the month that daylight savings time will begin. In this sub-screen,
pressing 1 will select March, 2 will select April and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will begin. In the
first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will
select the third week, while in the second sub-screen, pressing 1 will select the fourth week and
2 will select the last week of the selected month.
78
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows
the programmer to select the month that daylight savings time will end. In this sub-screen,
pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will end. In the first
sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select
the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will
select the last week of the selected month.
SYSTEM SETUP
1=TROUBLE REMIND NO
2=CANADIAN OPTION OFF
3=CHARGR DISABLE NO
3.5.4.4 Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 73, for
a detailed description of this feature. Pressing 1 while viewing System Setup Screen #2 will
cause the display to toggle to Trouble Rem Yes, which enables this feature. Each press of the 1
key will cause the display to toggle between Trouble Rem Yes and Trouble Rem No.
System Setup Screen #2
See Page
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for
more than 24 hours will cause the FACP to resound the trouble sounder.
3.5.4.5 Canadian Option
Pressing 2 while viewing System Setup Screen #2 will configure the FACP to comply with
Canadian requirements. The display will change to Canadian Opt. On. Each press of the 2 key
will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory
default setting is Canadian Opt. Off.
The Canadian Options configures the FACP with the following as required by Canada:
•
•
•
The following zone type codes are not available:
non-latching supervisory
non-latching drill
process monitor (latching or non-latching)
hazard
tornado
medical alert
combo autoresettable
The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm
signals will be turned off after 20 minutes of activation
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label, located on the FACP backbox door
3.5.4.6 Charger Disable
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or
disable the onboard battery charger. If an external battery charger is being used, the onboard
battery charger must be disabled. Each press of the 3 key will toggle between Chrgr Disable No
and Chrgr Disable Yes.
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
3.5.5 Option Modules
Options available for the FACP include annunciators, printer connection for acquiring hardcopy
printouts of panel data and onboard DACT.
Pressing 2 while viewing Programming Screen #2 will display the following screen:
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
79
Programming
3.5.5.1 ANN-BUS
Pressing 1 while viewing the Option Modules screen will cause the control panel to display the
following screens.
ANN-BUS
1=BUS ENABLED
2=BUS MODULES
3=AUTO CONFIGURE
NO
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS
1=ANN-AUDIO OPTIONS
ANN-BUS Screen #3
A variety of ANN-BUS option modules can be installed in the FACP. These devices
communicate with the FACP over the ANN-BUS terminals on the control panel.
3.5.5.1.1 ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANNBUS Enabled Yes and ANN-BUS Enabled No.
3.5.5.1.2 BUS Modules
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select
ANN-BUS addresses for the module(s). The following screen will be displayed.
ANN-BUS MODULES
1=ADDR. 1
NONE
2=ADDR. 2
NONE
3=ADDR. 3
NONE
On Board DACT Screen #1
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen
with technical information about the selected module.
80
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
In the technical information screen, pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80
3=ANN-I/O
Module Type Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
ANN-BUS MODULE TYPE
1=ANN-AUDIO MODULE
Module Type Screen #3
Press the number corresponding to the module type, if any, that is installed with the selected
address. This will enable the module.
3.5.5.1.3 Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and
automatically program the device type and address into the system. Pressing 3 while viewing
ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to
be displayed:
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
81
Programming
3.5.5.1.4 ANN-S/PG Options Screen
The Printer Option allows the user to configure the optional printer. Pressing 1 while viewing
the ANN-BUS Screen #2 will display the following screens:
PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-S/PG OPTIONS
1=PORT
PARALLEL
2=PRINTER SUPV
NO
3=OFFLINE TIMER
60
Printer Options Screen #1
ANN-BUS Screen #2
ANN-S/PG OPTIONS
1=BAUD RATE
N/A
2=DATA BITS
N/A
3=PARITY
N/A
Printer Options Screen #2
ANN-S/PG OPTIONS
1=STOP BITS
N/A
Printer Options Screen #3
Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select
between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the
display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that
the interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select
an offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print
Options screen #1. Each press of the 2 key will cause the display to toggle between Printer
Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option
is not selectable if the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by
pressing 3 while viewing Print Options screen #1. The resultant screen allows the programmer
to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer
supervision is reported as a trouble.
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be
available. The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the
Serial Port option has been selected.
Pressing 1 for Baud Rate while viewing Printer Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of 19200, 9600 or 2400.
Pressing 2 for Data Bits while viewing Printer Options screen #2 will cause screens to appear
which allow the user to select 5, 6, 7 or 8 Data Bits.
Pressing 3 for Parity while viewing Printer Options screen #2 will cause a screen to appear
which allows the user to select between No Parity, Even Parity or Odd Parity.
Pressing 1 for Stop Bits while viewing Printer Options screen #3 will cause a screen to appear
which allows the user to select between 0.5, 1.0 or 2.0 Stop Bits.
82
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.5.1.5 ANN-I/O LED Zone Assignments
The information displayed by LEDs on every ANN-I/O module is not programmable and will
therefore be as indicated in the following table.
LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Zone (any address)
AC Fault
General Alarm
General Supervisory
General Trouble
Alarm Silenced
Earth Fault
Battery Fault
Charger Fault
Disable
Maintenance
Zone 1 Alarm
Zone 2 Alarm
Zone 3 Alarm
Zone 4 Alarm
Zone 5 Alarm
Zone 6 Alarm
Zone 7 Alarm
Zone 8 Alarm
Zone 9 Alarm
Zone 10 Alarm
Zone 1 Trouble
Zone 2 Trouble
Zone 3 Trouble
Zone 4 Trouble
Zone 5 Trouble
Zone 6 Trouble
Zone 7 Trouble
Zone 8 Trouble
Zone 9 Trouble
Zone 10 Trouble
Zone 1 Supervisory
Zone 2 Supervisory
Zone 3 Supervisory
Zone 4 Supervisory
Zone 5 Supervisory
Zone 6 Supervisory
Zone 7 Supervisory
Zone 8 Supervisory
Zone 9 Supervisory
Zone 10 Supervisory
83
Programming
3.5.5.1.6 ANN-80 Options Screen
Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80
1=SIL BTN
2=RST BTN
3=DRL BTN
OPTIONS
ENABLE
ENABLE
ENABLE
ANN-80 Options Screen #2
The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options
Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not the ANN-80
annunciator must be unlocked by its key before any annunciator key presses will function.
Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock
position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display
to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn
Enable No (Ack/Step button never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether
the Silence button on any installed ANN-80 annunciator will function normally or always be
ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence
button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether
the Reset button on any installed ANN-80 annunciator will function normally or always be
ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset
button never functions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether
the Drill button on any installed ANN-80 annunciator will function normally or always be
ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill
button never functions).
84
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.5.2 ANN-RLY Options Screen
Pressing 3 for ANN-RLY Options while viewing ANN-BUS Screen #2 will cause the following
screen to be displayed:
PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-RLY OPTIONS
1=RELAY 1
IN ZONE 1
2=RELAY 2
IN ZONE 2
3=RELAY 3
IN ZONE 3
ANN-BUS Screen #2
ANN-RLY Options Screen
The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option
screen, press the number key corresponding to the relay to be programmed. Following is a list
of the available programming options for each relay:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
General Alarm
General Trouble
General Supervisory
AC Loss
Waterflow Delay
Input Zone 1
Input Zone 2
Input Zone 3
Input Zone 4
Input Zone 5
Input Zone 6
Input Zone 7
Input Zone 8
Input Zone 9
Input Zone 10
Silenceable Alarm
Not Assigned
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
85
Programming
PROGRAMMING
1=ANN-AUDIO OPTIONS
ANN-BUS Screen #3
3.5.5.3 ANN-AUDIO Options Screen
Pressing 1 for ANN-AUDIO Options while viewing ANN-BUS Screen #3 will cause the
following screen to be displayed:
ANN-AUDIO OPTIONS
1=ALL CALL ZONE
1
ANN-AUDIO Options Screen
This screen shows the Input Zone that has been assigned to be the All-Call Zone. In this
example, Zone 1 is the All-Call Zone. The All-Call Zone can be changed by pressing the 1 key
while viewing the ANN-AUDIO Options Screen. The following screens will be displayed.
ANN-AUDIO ALL CALL
1=NO ALL CALL ZONE
2=INPUT ZONE 1
3=INPUT ZONE 2
Printer Options Screen #1
ANN-AUDIO ALL CALL
1=INPUT ZONE 3
2=INPUT ZONE 4
3=INPUT ZONE 5
Printer Options Screen #2
ANN-AUDIO ALL CALL
1=INPUT ZONE 6
2=INPUT ZONE 7
3=INPUT ZONE 8
Printer Options Screen #2
ANN-AUDIO ALL CALL
1=INPUT ZONE 9
2=INPUT ZONE 10
Printer Options Screen #3
These screens allow the programmer to select which Input Zone will be assigned as the All-Call
Zone.
86
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.5.4 Onboard DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a
central station. Pressing 2 while viewing the Option Module Screen will cause the following
screens to be displayed:
ON BOARD DACT
1=PRIM PHONE
TCH TNE
2=SCND PHONE
TCH TNE
3=CENTRAL STATION
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT
Onboard DACT Screen 1
Option Module Screen
ON BOARD DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen 2
3.5.5.4.1 Primary Phone
Press 1 while viewing Onboard DACT Screen to program the type of primary phone line being
connected to the DACT. The following screen will be displayed:
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33 (EURO)
3=ROTARY 60/40 (U.S.)
Primary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33
or 3 to select Rotary dialing with a make/break ratio of 60/40.
3.5.5.4.2 Secondary Phone
Press 2 while viewing Onboard DACT Screen 1 to program the type of secondary phone line
being connected to the DACT. The following screen will be displayed:
ON BOARD DACT
1=PRIM PHONE
2=SCND PHONE
3=CENTRAL STATION
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33 (EURO)
3=ROTARY 60/40 (U.S.)
Onboard DACT 1
Secondary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33
or 3 to select Rotary dialing with a make/break ratio of 60/40.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
87
Programming
3.5.5.4.3 Central Station
Central Station programming configures the control panel DACT for contacting the central
station. Pressing 3 while viewing Onboard DACT Screen 1 will cause the following screens to
be displayed:
ON BOARD DACT
1=PRIM PHONE
2=SCND PHONE
3=CENTRAL STATION
Onboard DACT
CENTRAL STATION
1=REPORTING
NO
2=REPORT STYLE
FIRST AVAILABLE
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
0
Central Station Screen #2
3.5.5.4.3.1 Reporting
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing
Central Station Screen #1 so the display reads Reporting Yes. Each press of the 1 key will
toggle the display between Reporting Yes and Reporting No.
3.5.5.4.3.2 Report Style
The DACT can be programmed to transmit reports to primary and/or secondary central station
phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the
following screen:
REPORT STYLE
1=BACKUP ONLY
2=BOTH
3=FIRST AVAILABLE
Backup Reporting Screen
Press 1 to have all reports transmitted to the central station secondary phone number as a
backup only if the primary phone line fails, 2 to transmit all reports to both the primary and
secondary phone numbers all of the time or 3 to send reports to the first available phone
number.
88
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.5.4.3.3 Central Station Primary and Secondary Phone Numbers
Pressing 1 for Primary or 2 for Secondary, while viewing Central Station Screen #2, will display
the following screens.
Note that the following information must be entered for both the Primary and Secondary
Central Station Phone Numbers.
CENTRAL STATION #
1=TEST TIME INT
24
2=ACCOUNT CODE
0000
3=24HR T TIME
0000
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
Primary/Secondary Screen #1
Central Station Screen #2
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
CENTRAL STATION
1=COMM FORMAT
ADEMCO CONTACT ID
2=EVENT CODES
Primary/Secondary Screen #3
Test Time Interval
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be
displayed:
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24
hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens
shown above.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
89
Programming
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
ACCOUNT CODE
RANGE 0000-FFFF
Account Codes Screen
The Account Code, which is assigned by a Central Station, depends on the communication
format being used. The Account Code screen will have a flashing cursor in the lower left
corner. Program the supplied 4-digit account code using 0 - 9 and A - F keys. Enter the first
digit, then press the right arrow key to move the cursor to the right, one position. Repeat the
process until all digits are entered.
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
24 HOUR TEST TIME
ENTR USING 24HR TIME
RANGE 0000-2359
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR T TIME
24 Hour Test Time Screen
Primary/Secondary Screen #1
Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour
Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen.
Enter a four digit number representing the test time using military time (0000 = midnight and
2359 = 11:59PM).
Phone Number
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be
displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
The Phone Number screen is used to enter the Central Station phone number that the DACT
will be contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9
and A - C where A = *, B = # and C = look for secondary dial tone for up to 2 seconds (then dial
anyway).
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then
press the right arrow key to move the cursor to the right one position. Enter the second digit
and repeat the process until all digits are entered. Press the Enter key to store the phone number
in memory.
90
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
Enter the digits as you would like the number to be dialed. For example, if it’s necessary to dial
9 before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9
followed by D for a three second pause or E for a five second pause then the phone number
followed by an F to indicate the end of the number.
Communication Format
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be
displayed:
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA-DCS-8
3=SIA-DCS-20
CENTRAL STATION
1=COMM FORMAT
2=EVENT CODES
Primary/Secondary Screen #3
The Communication Format is determined by the type of receiver that the DACT is transmitting
to. Consult your Central Station for proper selection or consult our factory representatives.
For any format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
Comm Format screen. The following table describes each format:
Table 3.1 Communication Formats
Screen Selection
ADEMCO CONTACT ID
SIA-DCS-8
SIA-DCS-20
Communication Format Description
Contact ID, DTMF, 1400/2300 ACK
Security Industry Association, 8 messages per call
Security Industry Association, 20 messages per call
Event Codes
Pressing 2 while viewing Primary/Secondary Screen #3 will cause the following screen to be
displayed:
EVENT
1=ZONE
2=ZONE
3=ZONE
CODES
1 ALARM
2 ALARM
3 ALARM
Event Code Screen
Pressing the down arrow key allows viewing of all Events associated with the selected
Communication Format. Pressing the number corresponding to the event displayed in each
screen will display its default active and restoral event codes which can be customized by the
programmer.
For example, if Ademco Contact ID is the selected format, pressing 3 for Zone 3 Alarm will
display the following screen which allows the Event Code to be changed from the default value.
ZONE 3 ACTIVE
115
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
91
Programming
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10
and the corresponding Event Codes for Ademco Contact ID and SIA DCS Formats. Note that
Table 3.3 on page 93, Table 3.4 on page 94, Table 3.5 on page 95 and Table 3.6 on page 97 list
the default settings for Zone 1 through Zone 10. These can be changed to any of the Types
listed in Table 3.2 .
Note: The third character in the SIA-DCS Format (x in the table below) represents the zone
number.
Table 3.2 Zone Alarm Type Event Codes
Zone Alarm Type
Pull-Station
Waterflow
Waterflow Nonsilenceable
Combo
Combo AutoResettable Supervisory
2-Wire Detector
Normally Open Contact
Fire
Tamper
Supervisory
Supervisory AutoResettable
Medic-Alert
Hazard-Alert
Tornado-Alert
Proc-Mon
Procmon-AR
AC-Loss-Mon
Drill-Switch
Drill-Switch AutoResettable
Ademco Contact ID
Active
115
113
113
113
113
111
110
110
144
200
200
100
150
150
200
200
301
604
604
SIA-DCS Format
Active
Restoral
FAx
FHx
SAx
SHx
SAx
SHx
SAx
SHx
SAx
SHx
FAx
FHx
UAx
UHx
FAx
FHx
TAx
THx
FSx
FVx
FSx
FVx
MAx
MHx
PAx
PHx
PAx
PHx
IAx
IRx
IAx
IRx
ATx
ARx
FIx
FKx
FIx
FKx
The following tables list all of the Events and their default Event Codes for the Ademco Contact
ID and SIA-DCS Communication Formats.
Note: A detector freeze condition will be reported as a Supervisory Event Code.
92
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
Ademco Contact ID Format - Primary Central Station Phone Number
The information shown in Table 3.3 is automatically programmed for the Primary Central
Station phone number Event Codes when Ademco Contact ID Format is selected. To disable
event reporting, select the desired Event Code to be disabled and press 0 or Clear and then
Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save
the selection).
Table 3.3 Ademco Contact ID Primary # Event Codes
Event Description
Event Code Settings
Active
Primary # Zone 1 - 10 Alarm
115
Primary # Zone 1 - 10 Disabled
570
Primary # Drill
604
Primary # AC Fault
301
Primary # Zone 1 - 10 Fault
380
Primary # Zone 1 - 10 Dirty
380
Primary # Earth Fault
310
Primary # Low Battery Fault
302
Primary # No Battery Fault
311
Primary # Telco Primary Line Fault
351
Primary # Telco Secondary Line Fault
352
Primary # NAC #1 Fault
321
Primary # NAC #2 Fault
322
Primary # NAC #3 Fault
326
Primary # NAC #4 Fault
327
Primary # NAC #1 Disable
521
Primary # NAC #2 Disable
522
Primary # NAC #3 Disable
526
Primary # NAC #4 Disable
527
Primary # Charger Fault
300
Primary # Comm Trouble Primary #
354
Primary # Comm Trouble Secondary #
354
Primary # Printer Fault
336
Primary # ANN-Bus Fault
330
Primary # Option Card Fault
333
Primary # CS CALC Fault
304
Future
000
Primary # System Off Normal
308
Primary # System Test Message
602
Primary # System Abnormal Test Message
608
Primary # Upload/Download Request
411
Primary # Upload Successful
416
Primary # Download Successful
412
Primary # Upload/Download Failed
413
Primary # Voice EVAC Fault
330
Primary # Power Supply Sync Fault
300
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
93
Programming
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.4 is automatically programmed for the Secondary Central
Station phone number Event Codes when Ademco Contact ID Format is selected. To disable
event reporting, select the desired Event Code to be disabled and press 0 or Clear and then
Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save
the selection).
Table 3.4 Ademco Contact ID Secondary # Event Codes
Event Description
Event Code Settings
Active
94
Secondary # Zone 1 - 10 Alarm
115
Secondary # Zone 1 - 10 Disabled
570
Secondary # Drill
604
Secondary # AC Fault
301
Secondary # Zone 1 - 10 Fault
380
Secondary # Zone 1 - 10 Dirty
380
Secondary # Earth Fault
310
Secondary # Low Battery Fault
302
Secondary # No Battery Fault
311
Secondary # Telco Primary Line Fault
351
Secondary # Telco Secondary Line Fault
352
Secondary # NAC #1 Fault
321
Secondary # NAC #2 Fault
322
Secondary # NAC #3 Fault
326
Secondary # NAC #4 Fault
327
Secondary # NAC #1 Disable
521
Secondary # NAC #2 Disable
522
Secondary # NAC #3 Disable
526
Secondary # NAC #4 Disable
527
Secondary # Charger Fault
300
Secondary # Comm Trouble Primary #
354
Secondary # Comm Trouble Secondary #
354
Secondary # Printer Fault
336
Secondary # ANN-BUS Fault
330
Secondary # Option Card Fault
333
Secondary # CS CALC Fault
304
Future
000
Secondary # System Off Normal
308
Secondary # System Test Message
602
Secondary # System Abnormal Test Message
608
Secondary # Upload/Download Request
411
Secondary # Upload Successful
416
Secondary # Download Successful
412
Secondary # Upload/Download Failed
413
Secondary # Voice EVAC Fault
330
Secondary # Power Supply Sync fault
300
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
SIA-DCS Format - Primary Central Station Phone Number
The information shown in Table 3.5 is automatically programmed for the Primary Central
Station phone number Event Codes when SIA-DCS Format is selected. To disable event
reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to
disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the
selection).
Table 3.5 SIA-DCS Primary # Event Codes
Event Description
Event Code Settings
Active
Restoral
Primary # Zone 1 Alarm
FA1
FH1
Primary # Zone 2 Alarm
FA2
FH2
Primary # Zone 3 Alarm
FA3
FH3
Primary # Zone 4 Alarm
FA4
FH4
Primary # Zone 5 Alarm
FA5
FH5
Primary # Zone 6 Alarm
FA6
FH6
Primary # Zone 7 Alarm
FA7
FH7
Primary # Zone 8 Alarm
FA8
FH8
Primary # Zone 9 Alarm
FA9
FH9
Primary # Zone 10 Alarm
FA10
FH10
Primary # Zone 1 Disabled
FB1
FU1
Primary # Zone 2 Disabled
FB2
FU2
Primary # Zone 3 Disabled
FB3
FU3
Primary # Zone 4 Disabled
FB4
FU4
Primary # Zone 5 Disabled
FB5
FU5
Primary # Zone 6 Disabled
FB6
FU6
Primary # Zone 7 Disabled
FB7
FU7
Primary # Zone 8 Disabled
FB8
FU8
Primary # Zone 9 Disabled
FB9
FU9
Primary # Zone 10 Disabled
FB10
FU10
FI
FK
Primary # Drill
Primary # AC Fault
AT
AR
Primary # Zone 1 Fault
FT1
FJ1
Primary # Zone 2 Fault
FT2
FJ2
Primary # Zone 3 Fault
FT3
FJ3
Primary # Zone 4 Fault
FT4
FJ4
Primary # Zone 5 Fault
FT5
FJ5
Primary # Zone 6 Fault
FT6
FJ6
Primary # Zone 7 Fault
FT7
FJ7
Primary # Zone 8 Fault
FT8
FJ8
Primary # Zone 9 Fault
FT9
FJ9
Primary # Zone 10 Fault
FT10
FJ10
Primary # Zone 1 Dirty
FT1
FJ1
Primary # Zone 2 Dirty
FT2
FJ2
Primary # Zone 3 Dirty
FT3
FJ3
Primary # Zone 4 Dirty
FT4
FJ4
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
95
Programming
Table 3.5 SIA-DCS Primary # Event Codes (Continued)
Primary # Zone 5 Dirty
FT5
FJ5
Primary # Zone 6 Dirty
FT6
FJ6
Primary # Zone 7 Dirty
FT7
FJ7
Primary # Zone 8 Dirty
FT8
FJ8
Primary # Zone 9 Dirty
FT9
FJ9
Primary # Zone 10 Dirty
FT10
FJ10
Primary # Earth Fault
ET38
ER38
Primary # Low Battery Fault
YT0
YR0
Primary # No Battery Fault
YT0
YR0
Primary # Telco Primary Line Fault
LT1
LR1
Primary # Telco Secondary Line Fault
LT2
LR2
Primary # NAC #1 Fault
ET32
ER32
Primary # NAC #2 Fault
ET33
ER33
Primary # NAC #3 Fault
ET34
ER34
Primary # NAC #4 Fault
ET35
ER35
Primary # NAC #1 Disable
ET101
ER101
Primary # NAC #2 Disable
ET102
ER102
Primary # NAC #3 Disable
ET103
ER103
Primary # NAC #4 Disable
ET104
ER104
Primary # Charger Fault
YP
YQ
Primary # Comm Trouble Primary #
YC1
YK1
Primary # Comm Trouble Secondary #
YC2
YK2
Primary # Printer Fault
VT
VR
Primary # ANN-Bus Fault
ET61
ER61
Primary # Option Card Fault
ET
ER
Primary # CS CALC Fault
YF
000
Future
000
000
Primary # System Off Normal
LB
LX
Primary # System Test Message
RP
000
RP99
000
Primary # Power Supply Sync Fault
OU
OV
Primary # Upload/Download Request
RB
000
Primary # Upload Successful
RS
000
Primary # Download Successful
RS
000
Primary # Upload/Download Failed
RU
000
Primary # System Abnormal Test Message
96
Primary # Voice EVAC Fault
ET
ER
Primary # Power Supply Sync Fault
OU
OV
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
SIA-DCS Format - Secondary Central Station Phone Number
The information shown in Table 3.6 is automatically programmed for the Secondary Central
Station phone number Event Codes when SIA-DCS Format is selected. To disable event
reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to
disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the
selection).
Table 3.6 SIA-DCS Secondary # Event Codes
Event Description
Event Code Settings
Active
Restoral
Secondary # Zone 1 Alarm
FA1
FH1
Secondary # Zone 2 Alarm
FA2
FH2
Secondary # Zone 3 Alarm
FA3
FH3
Secondary # Zone 4 Alarm
FA4
FH4
Secondary # Zone 5 Alarm
FA5
FH5
Secondary # Zone 6 Alarm
FA6
FH6
Secondary # Zone 7 Alarm
FA7
FH7
Secondary # Zone 8 Alarm
FA8
FH8
Secondary # Zone 9 Alarm
FA9
FH9
Secondary # Zone 10 Alarm
FA10
FH10
Secondary # Zone 1 Disabled
FB1
FU1
Secondary # Zone 2 Disabled
FB2
FU2
Secondary # Zone 3 Disabled
FB3
FU3
Secondary # Zone 4 Disabled
FB4
FU4
Secondary # Zone 5 Disabled
FB5
FU5
Secondary # Zone 6 Disabled
FB6
FU6
Secondary # Zone 7 Disabled
FB7
FU7
Secondary # Zone 8 Disabled
FB8
FU8
Secondary # Zone 9 Disabled
FB9
FU9
Secondary # Zone 10 Disabled
FB10
FU10
Secondary # Drill
FI
FK
Secondary # AC Fault
AT
AR
Secondary # Zone 1 Fault
FT1
FJ1
Secondary # Zone 2 Fault
FT2
FJ2
Secondary # Zone 3 Fault
FT3
FJ3
Secondary # Zone 4 Fault
FT4
FJ4
Secondary # Zone 5 Fault
FT5
FJ5
Secondary # Zone 6 Fault
FT6
FJ6
Secondary # Zone 7 Fault
FT7
FJ7
Secondary # Zone 8 Fault
FT8
FJ8
Secondary # Zone 9 Fault
FT9
FJ9
Secondary # Zone 10 Fault
FT10
FJ10
Secondary # Zone 1 Dirty
FT1
FJ1
Secondary # Zone 2 Dirty
FT2
FJ2
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
97
Programming
Table 3.6 SIA-DCS Secondary # Event Codes (Continued)
Secondary # Zone 3 Dirty
FT3
FJ3
Secondary # Zone 4 Dirty
FT4
FJ4
Secondary # Zone 5 Dirty
FT5
FJ5
Secondary # Zone 6 Dirty
FT6
FJ6
Secondary # Zone 7 Dirty
FT7
FJ7
Secondary # Zone 8 Dirty
FT8
FJ8
Secondary # Zone 9 Dirty
FT9
FJ9
Secondary # Zone 10 Dirty
FT10
FJ10
Secondary # Earth Fault
ET38
ER38
Secondary # Low Battery Fault
YT0
YR0
Secondary # No Battery Fault
YT0
YR0
Secondary # Telco Primary Line Fault
LT1
LR1
Secondary # Telco Secondary Line Fault
LT2
LR2
Secondary # NAC #1 Fault
ET32
ER32
Secondary # NAC #2 Fault
ET33
ER33
Secondary # NAC #3 Fault
ET34
ER34
Secondary # NAC #4 Fault
ET35
ER35
Secondary # NAC #1 Disable
ET101
ER101
Secondary # NAC #2 Disable
ET102
ER102
Secondary # NAC #3 Disable
ET103
ER103
Secondary # NAC #4 Disable
ET104
ER104
YP
YQ
Secondary # Comm Trouble Primary #
YC1
YK1
Secondary # Comm Trouble Secondary #
YC2
YK2
Secondary # Printer Fault
VT
VR
ET61
ER61
Secondary # Option Card Fault
ET
ER
Secondary # CS CALC Fault
YF
000
Future
000
000
Secondary # System Off Normal
LB
LX
Secondary # System Test Message
RP
000
RP99
000
Secondary # Power Supply Sync Fault
OU
OV
Secondary # Upload/Download Request
RB
000
Secondary # Upload Successful
RS
000
Secondary # Download Successful
RS
000
Secondary # Upload/Download Failed
RU
000
Secondary # Voice EVAC Fault
ET
ER
Secondary # Power Supply Sync Fault
OU
OV
Secondary # Charger Fault
Secondary # ANN-Bus Fault
Secondary # System Abnormal Test Message
98
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
Central Station Screen #2
3.5.5.4.3.4 Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a
programmed amount between 0 and 99, for each unique trouble within a 24 hour period.
Separate limit counters keep track of each unique type of trouble. Note that the number of
phone line (communication) faults called to the Central Station are not limited by this feature.
No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose
call limit has been reached. Local DACT annunciation will still track the particular trouble and
restoral.
To set the Trouble Call Limit, press 3 while viewing Central Station Screen #2. The following
screen will be displayed.
TROUBLE CALL LIMIT
RANGE 00-99 TROUBLES
*
Backup Reporting Screen
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
Note: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the
Central Station an unlimited number of times. This is the factory default setting.
DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen #2
3.5.5.4.4 Service Terminal
The FACP can be programmed remotely from a PC using a modem and telephone line.
Information can also be retrieved from the FACP using the same method. The Upload/
Download option allows an operator to set the necessary parameters to allow the uploading and
downloading of data between the FACP and PC. The Service Terminal selection provides the
means for entering these parameters.
Pressing 1 while viewing Onboard DACT Screen #2 will cause the following screens to appear:
SERVICE TERMINAL
1=RING COUNT
0
Service Terminal Screen
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
99
Programming
SERVICE TERMINAL
1=RING COUNT
Service Terminal Screen #2
3.5.5.4.4.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel
will not answer an incoming call. This entry may be programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The
following screen will be displayed:
RING COUNT
RANGE 00-25 RINGS
Ring Count Screen
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring
count which can be a value between 00 and 25. After the second digit is entered, the display
will return to the Service Terminal screen.
3.5.5.4.5 Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2
by the DACT when using an alternate means of secondary transmission path. The factory
default setting is Phone Line 2 supervised.
DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the
following screen to be displayed:
Onboard DACT Screen #2
SUPERVISE PHONE LINE
1=PHONE LINE 2 YES
Each press of the 1 key while viewing this screen will toggle the option between Supervise
Phone Line 2 Yes and No.
3.5.6 History
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 3 while viewing Programming Screen #2 will display the History options
as shown in the following display:
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
100
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.6.1 View Events
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
Pressing 1 while viewing the History Screen will allow the user to select the events to be
viewed as illustrated in the following:
History Screen
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3
to view other events. Use the up and down arrow keys to scroll through all of the displayed
events.
3.5.6.2 Erase History
The Erase History option allows a user to erase all events from the history file. This will
provide a clean slate in order to use the history file to track future events. Pressing 2 while
viewing the History Screen will display the following screen:
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will erase all events from the History file.
After the History file has been erased, the display will return to the History Screen.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
101
Programming
3.5.7 Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Refer to the sections titled "Walktest" on page 106 and
"Walktest" on page 117 for additional information regarding the Walktest feature. Pressing 1 while
viewing the Programming Screen #3 will cause the following Walktest options to be displayed:
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Programming Screen #3
Walktest Screen
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed:
UNIT IN WALKTEST
Walktest Active Screen
The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the
walktest screen from an actual alarm screen.
ALARM ZONE 1
<ADJ> <NOUN>
Z01
10*00A 010805
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:
WALKTEST RESULTS
Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.
102
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.5.8 Clear Program
Pressing 2 while viewing Programming Screen #3, will select the Clear Program option. The
control panel will provide a warning to the user by prompting with the following display:
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES
2=NO
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will
prevent programming from being cleared.
3.5.9 Password Change
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 3 while viewing Programming Screen #3 will
cause the following screen to be displayed:
Programming Screen #3
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
3=REMOTE DOWNLOAD
Password Change Screen
Press 1 to change the Master Programming Level password, 2 to change the Maintenance Level
password or 3 to change the Remote Download password. Note that the passwords will not be
displayed on annunciators.
The following screen will appear when one of the change options is selected:
ENTER NEW FIVE DIGIT
PASSWORD
Enter Password Screen
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
VERIFY NEW
PASSWORD
Password Change Screen
The new five digit password must be re-entered to accept the change. The display will then return
to the initial Password Change Screen.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
103
Programming
3.6 Maintenance Programming Level
To access Maintenance Programming mode, press the Enter key. The LCD will display the
following:
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
To enter the Maintenance Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
When the Maintenance level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Note that in the preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key, as shown in the following screen.
PROGRAMMING
1=TIME-DATE
104
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.6.1 Input Zones - Enable/Disable
The Zone Setup option allows the user to enable or disable desired zones. Pressing 1 for Zone
Setup, while viewing Maintenance Screen #1 will cause the following screens to be displayed:
POINT PROGRAM
1=ZONE 1
2=ZONE 2
3=ZONE 3
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Maintenance Screen #1
Zone Select Screen
Pressing the down arrow key will display additional Zones (Zones 4 - 5 for MS-5UD and Zones 4 10 for MS-10UD). Select the number corresponding to the desired zone. A screen will appear
which will allow enabling or disabling of the selected zone, as illustrated in the following example:
ZONE 1
1=ENABLED
YES
Enable/Disable Select Screen
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.
3.6.2 History
Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
The History feature allows the operator to view control panel events which have been stored in a
history file in memory and erase the contents of the history file
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
105
Programming
Pressing 1 while viewing the History screen will cause the following screen to be displayed:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
To view all the events which have occurred in the control panel since the history file was last
erased, press 1 while viewing the Events screen. To view only alarms which have occurred, press 2
while viewing the Events screen. To view events other than alarms, press 3. The most recent event
will be displayed on the screen. To view all of the selected events, press the up or down arrow keys
to scroll through the list of events. If no events have occurred, the display will read NO EVENTS
IN HISTORY.
Pressing 2 while viewing the History Screen will cause the following screen to be displayed:
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. The
display will then return to the History Screen. Pressing 2 will cause the display to return to the
History Screen without erasing the History file.
3.6.3 Walktest
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Maintenance Screen #1
To perform a walktest, press 3 while viewing Maintenance Screen #1. The following screen will be
displayed:
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The
display will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the
walktest.
106
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Programming
3.6.4 Time-Date
To program the time and date into the control panel, press 1 while viewing Maintenance Screen #2.
The following display will appear:
TIME AND DATE
1=TIME
01:00 AM
2=DATE
01-01-2001
3=CLOCK FORMAT
12HRS
PROGRAMMING
1=TIME-DATE
Maintenance Screen #2
Time and Date Screen
To change the time, press 1 to display the following screen:
ENTER TIME AS 12HRS
:
01:00 AM
1=AM
2=PM
Time Screen
A flashing cursor will appear on the left side of the display. Enter the four digit number
corresponding to the time (0000 - 1259). When the fourth digit is entered, the cursor will move one
position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will
return to the Time and Date Screen displaying the new time.
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be
displayed:
ENTER DATE
**-**-****
MONTH DAY YEAR
01-01-2001
Date Screen
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit
day and four digit year. The cursor will move one position to the right after each entry. When the
fourth digit of the year has been entered, the display will return to the Time and Date Screen which
will show the new date.
To change between 12 hour and 24 hour format, press 3 while viewing the Time and Date screen.
Each press of the 3 key will toggle the display between 12 HR and 24 HR format.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
107
Operating Instructions
SECTION 4
Operating Instructions
4.1 Panel Control Buttons
4.1.1 Acknowledge/Step
The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to
steady and also changes the status field on the LCD display from capital letters to small letters
(TROUBL to Troubl). When the piezo is silenced, an acknowledge message is sent to the printer
and the history file. Acknowledge also sends a silence piezo command to the optional annunciators
connected to the FACP. The Acknowledge key will have no effect on the Notification Appliance
Circuits.
When more than one event exists, the first press of the Acknowledge/Step key functions as
described in the preceding paragraph. Subsequent pressing of the key steps through each active
event.
4.1.2 Alarm Silenced
The Alarm Silenced key performs the same functions as Acknowledge/Step except it will not step
through each event when multiple events are present at the panel. If an alarm exists, the Alarm
Silenced key turns off all silenceable NACs (Notification Appliance Circuits) and causes the Alarm
Silenced LED to turn on. It also sends an ‘alarm silenced’ message to the printer, history file and
optional annunciators. A subsequent new alarm will resound the system NACs. The Alarm
Silenced LED is turned off by pressing the Reset key, the Drill key or subsequent activation of the
NACs.
Note that if Silence Inhibit has been enabled, NACs cannot be silenced for one minute following
initiation of an alarm.
4.1.3 Drill/Hold 2 Sec
When the Drill key is held for a minimum of two seconds (time required to prevent accidental
activations), the FACP turns on all NAC outputs and turns off the Alarm Silenced LED if it was
previously on. The EVAC IN SYSTEM message is shown on the LCD display. The same message
is sent to the printer and history file. The Alarm Silence key can be used to turn off all silenceable
NAC outputs following activation by the Drill key.
4.1.4 Reset
Pressing and releasing the Reset key turns off all NACs, temporarily turns off resettable power to 4wire detectors, causes a RESET IN SYSTEM message to be displayed on the LCD and sends the
same message to the printer and history file. It also performs a lamp test by turning on all LEDs,
piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that
exists after a reset will resound the system.
Note that if Silence Inhibit has been enabled, the FACP cannot be reset for one minute following
initiation of an alarm.
108
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.2 LED Indicators
The five LED indicators, which are located on the front panel, operate as follows:
AC Power
This is a green LED which illuminates if AC power is applied to the FACP. A loss of AC power
will turn off this LED
Fire Alarm
This red LED flashes when one or more alarms occur. It illuminates steady when the Acknowledge/
Step or Alarm Silence key is pressed. The Fire Alarm LED turns off when the Reset key is pressed.
The LED will remain off if all alarms have been cleared.
Supervisory
This is a yellow LED that flashes when one or more supervisory conditions occur, such as a
sprinkler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm
Silence key is pressed. It turns off when the Reset key is pressed and remains off if all supervisory
alarms have been cleared.
Trouble
This is a yellow LED that flashes when one or more trouble conditions occur. It stays on steady
when the Acknowledge/Step or Alarm Silence key is pressed. The LED turns off when all trouble
conditions are cleared. This LED will also illuminate if the microprocessor watchdog circuit is
activated.
Alarm Silenced
This is a yellow LED that turns on after the Alarm Silence key is pressed while an alarm condition
exists. It turns off when the Drill or Reset key is pressed.
4.3 Normal Operation
With no alarms or troubles in the system, the display message is System All Normal along with the
current time and date as shown below. To set the time and date, refer to the appropriate section in
this manual.
SYSTEM ALL NORMAL
10:00A 070707
The FACP performs the following functions at regular intervals in Normal mode:
Monitors AC input voltage and battery voltage
Monitors and reports status option cards and control panel
Refreshes LCD display and updates time
Scans control panel keypad for key presses
Tests memory
Updates and reads all communications busses (EIA-485, etc.)
i3 smoke detectors will be polled for maintenance and freeze conditions on initial entry
into Normal mode. Thereafter, each device will be polled every hour for freeze and every
four hours for maintenance conditions
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five
minutes after the panel is reset, followed by a maintenance check. If there is no freeze or
maintenance condition, the panel will continue to monitor for freeze conditions every hour and
maintenance conditions every four hours.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
109
Operating Instructions
4.4 Trouble Operation
With no alarms in the system, the detection of a trouble will cause the following:
•
The piezo to pulse 1 second On and 1 second Off
•
The system Trouble LED to flash one second On and one second Off
•
The trouble relay to activate
•
TROUBL with device type, noun/adjective, address and trouble description will appear on
the LCD display
•
The same message, along with the time and date, is sent to the optional printer and the history
buffer.
•
Communicate the trouble conditions to the Central Station
•
Terminate upload or download communications
Note that specific troubles will initiate additional actions; for example, loss of AC power will turn
off the AC Power LED, etc.
Input Zone
For Input Zones, the following is a typical message that could appear on the LCD display for a
device trouble:
TROUBL PULL STATION
<ADJ> <NOUN>
ZONE 10 OPEN FAULT
10:00A 070707
The information displayed in the above example provides the following information:
•
First line in display:
The type of event; in this example OPEN indicating a circuit trouble
Device type identifier; in this example, PULL STATION indicates a manual device. Other
device type identifiers which can be displayed include SMOKE for Smoke Detector,
HEAT for Heat Detector, etc.
•
Second line in display:
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
•
Third line in display indicates Zone and the fault condition. Other possible troubles include:
U OPEN - indicating an open circuit
•
U DIRTY - maintenance alert indicating that an i3 detector is near but below the allowed
alarm limit and is in need of maintenance before the performance is compromised
Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 09 for September, 08 for the 8th
day of the month and 07 for the year 2007
110
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the
system Trouble LED to change from flashing to on steady. This block acknowledgment occurs
regardless of the number of troubles, alarms and supervisory events active in the system. When the
Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the
‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or
after the Acknowledge/Step key is pressed, the ‘clear trouble’ message is sent to the printer and
history file.
If all troubles clear and there are no supervisory or fire conditions active in the system, the system
returns to normal mode operation and the System All Normal message is shown on the LCD display
and sent to the history and printer files. The auto-restore feature will restore cleared troubles even
if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only
troubles exist in the system will have the same effect as pressing the Acknowledge/Step key except
the Alarm Silenced LED will light.
4.5 Alarm Operation
Alarm operation is similar to trouble operation with the following differences:
•
•
•
•
•
•
•
•
•
•
•
The piezo sounder produces a steady output as opposed to a pulsed output
The Fire Alarm LED flashes 1 second On and 1 second Off
The LCD displays Alarm along with the device name, type, adjective/noun, associated zones
and time/date
Communicate the alarm to the Central Station
Alarms latch and are not allowed to clear automatically
Timers for Silence Inhibit, Autosilence and Trouble Reminder are started
Alarms activate the alarm relay
Silenced alarms are resounded
The trouble relay is not activated
Store event in history buffer
Terminate upload or download communications
A typical alarm display would be as illustrated below:
ALARM PULL STATION
<ADJ> <NOUN>
ZONE 10
10:00A 070707
Note that the device type, which in this example is PULL STATION, can be any other
programmable alarm type.
The information displayed in the above example provides the following information:
•
First line in display:
•
The type of event; in this example ALARM indicating an alarm condition
Device type identifier; in this example, PULL STATION indicates a manual pull box.
Other device type identifiers which can be displayed include SMOKE for Smoke Detector,
HEAT for Heat Detector, etc.
Second line in display:
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
•
Third line in display: Zone 10 indicates the zone programmed to this device which, in this
example, is Input Zone 10.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
111
Operating Instructions
•
Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 09 for September, 08 for the 8th
day of the month and 07 for the year 2007
4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
•
The piezo sounder pulses ½ second On and ½ second Off
•
The Supervisory LED flashes ½ second On and ½ second Off
•
The LCD displays the status label Active Supervisory along with the device name, type,
adjective/noun, associated zones and time/date
•
Communicate the supervisory condition to the Central Station
•
The supervisory relay is activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
•
Terminate upload or download communications
A typical Supervisory event would be displayed as illustrated in the following:
FREEZE SUPERVISORY
<ADJ> <NOUN>
ZONE 05 FROZEN SUPRV
10:00A 070707
In the preceding example:
U FROZEN SUPRV - indicates zone detector is below approximately 45oF
Note that, like alarms, supervisory signals latch, except when programmed for supervisory
autoresettable. Supervisory activations do not cause silenced alarms to resound, as do other alarm
conditions. Open circuits in supervisory wiring are processed by the control panel the same way as
other trouble conditions. Refer to "Alarm Operation" on page 111, for a description of the
information displayed on the control panel LCD.
112
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
•
•
•
•
•
•
•
•
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type, adjective/
noun, associated zones and time/date
Communicate the process monitor condition to the Central Station
Relays programmed for process monitoring will be activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Note that, like supervisories, process monitor signals latch, except when programmed for process
monitor autoresettable.
4.8 Hazard/Tornado Condition Operation
Hazard/Tornado Condition operation will initiate the following events:
•
•
•
•
•
•
•
•
•
The piezo sounder pulses ½ second On, ½ second Off
The LCD displays a hazard message along with the device name, type, adjective/noun,
associated zones and time/date
Communicate the hazard condition to the Central Station
Relays programmed for hazard will be activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Supervisory LED flashes ½ second On, ½ second Off
Hazard conditions latch.
4.9 Medical Alert Condition Operation
Medical Alert Condition operation will initiate the following events:
•
•
•
•
•
•
•
•
•
The piezo sounder ½ second On, ½ second Off
The LCD displays a medical alert message along with the device name, type, adjective/noun,
associated zones and time/date
Communicate the medical alert condition to the Central Station
Relays programmed for medical alert will be activated
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Supervisory LED flashes ½ second On, ½ second Off
Medical alert conditions latch.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
113
Operating Instructions
4.10 Disable/Enable Operation
Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are
held in the off state. All disabled zones/NACs are treated as if they were in trouble, with the
exception being the status label that will be displayed is DISABL.
4.11 Waterflow Circuits Operation
If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will
not function.
4.12 Detector Functions
Maintenance Alert
i3 smoke detectors will be polled for maintenance and freeze conditions on initial entry into Normal
mode. Thereafter, each device will be polled every hour for freeze and every four hours for
maintenance conditions All alarm and system trouble conditions are annunciated on the control
panel’s LCD.
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five
minutes after the panel is reset, followed by a maintenance check. If there is no freeze or
maintenance condition, the panel will continue to monitor for freeze conditions every hour and
maintenance conditions every four hours.
System Alarm Verification
The control panel may be programmed to perform alarm verification to help eliminate the nuisance
of false alarms. Alarm verification applies to smoke detectors only.
4.13 Time Functions: Real-Time Clock
The FACP includes a crystal-based clock that provides time of day, date and day of week. Time is
displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time
change-over is programmable and automatic. If both AC and battery are lost, the time must be
reprogrammed.
4.14 Coded Operation
The NAC circuits resident on the control panel main circuit board can be programmed for coded
operation. The available pulse rates which can be programmed for coded operation are as follows:
114
•
•
•
Continuous:
March Time:
Temporal Code:
•
•
California Code:
Two-Stage
Steady output with no pulsing
Pulses at 120 ppm (pulses per minute)
Pulses at ½ second On, ½ second Off, ½ second On, ½
second Off, ½ second On, 1½ second Off
10 seconds On, 5 seconds Off
Pulses at 20 ppm (pulses per minute) for 3 or 5 minutes
and then changes to Temporal
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.15 Presignal
Presignal option programs an initiating device to delay the activation of NACs while allowing
visual verification by a person. Once a detector triggers an alarm, the onboard piezo sounds
immediately, but the NACs are not activated for a user programmed time duration of up to three
minutes. Note that the alarm relay and communicator will respond to the initial alarm immediately.
After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note
that if a second alarm occurs during the programmed time delay, the alarm will be processed
immediately, causing activation of the NACs. The events which occur upon Presignal activation
are as follows:
onboard piezo sounds immediately
control panel LCD display will indicate a presignal event and the active zone
annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone
LED
outputs (NACs) of associated zones will be inhibited from activating for a user
programmed time delay of up to three minutes
second alarm occurring anytime during the time delay will cause immediate activation of
all associated outputs
Presignal operation requires the approval of the local Authority Having Jurisdiction.
4.16 Positive Alarm Sequence
PAS (Positive Alarm Sequence) option will program a smoke detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds.
When a detector triggers an alarm, the onboard piezo sounds immediately, but the NACs are
prevented from activating for 15 seconds. This inhibit time is factory set and cannot be changed.
Pressing the Alarm Silence or Acknowledge/Step key during the 15 second inhibit time will silence
the piezo sounder and start a timer which prevents activation of NACs for an additional time
duration which can be user programmed for up to three minutes. After the programmed delay, the
NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs
during either time delay, the alarm will be processed immediately, causing activation of the NACs.
The events which occur upon PAS activation are as follows:
onboard piezo sounds immediately
control panel LCD display will indicate a PAS event and the active zone
annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone
LED
outputs (NACs) of associated zones will be inhibited from activating for a factory set
duration of 15 seconds
pressing the Alarm Silence or Acknowledge/Step key will start a timer which inhibits
output activation for additional time delay of up to three minutes which is user
programmable
second alarm occurring anytime during either time delay will cause immediate activation
of all associated outputs
PAS operation requires the approval of the local Authority Having Jurisdiction.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
115
Operating Instructions
4.17 Special System Timers
4.17.1 Silence Inhibit Timer
This option, if selected, prevents the Alarm Silenced and Reset keys from functioning for 60
seconds following an alarm. A new alarm during the initial 60 second period will not cause the
timer to restart with a new 60 seconds. Silence Inhibit operation requires the approval of the local
Authority Having Jurisdiction.
4.17.2 Autosilence Timer
If Autosilence is selected, the notification appliances, programmed as silenceable, will
automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the
Drill key will restart the timer. Autosilence operation requires the approval of the local Authority
Having Jurisdiction.
4.17.3 Trouble Reminder
If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the
Alarm Silence key is pressed) and every two minutes during a trouble condition (after the
Acknowledge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard piezo sounder
will occur until the alarm or fault is cleared.
Note that if Trouble Reminder feature is not selected and the trouble is not cleared within 24 hours,
the piezo will resound, indicating that the trouble condition still exists.
4.17.4 Waterflow Retard Timer
If selected, this option will delay the activation of a waterflow type alarm for a programmable time
duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow
device. This feature requires the approval of the local Authority Having Jurisdiction.
116
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.17.5 Alarm Verification (None or One Minute)
If alarm verification is selected, a smoke detector activation will cause the FACP to reset the
detector by removing power for 6 seconds. Power is reapplied and a 17 second retard period begins
which allows all detectors to stabilize. If no other detectors alarm, there will be no alarm indication
at the FACP during the 23 second Reset/Retard period. A Confirmation period of 60 seconds
follows, during which a subsequent alarm from the same detector will cause the panel to
immediately activate the appropriate outputs and indicate the alarm condition at the FACP. If a
different detector zone alarms any time during the first detector's Retard & Confirmation period,
the panel will immediately activate all appropriate outputs and indicate the alarm condition at the
FACP. If no additional detector alarms occur within 83 seconds of the first alarm (23 second Reset/
Retard plus 60 second Confirmation), the timer resets and the panel is ready to verify any new
detector alarms which may occur.
6 sec.
0 sec.
Detector Alarm
Verification (Reset/
Retard + Confirmation)
Detector Goes Into Alarm
RESET
23 sec.
RETARD
Alarm Ignored
Different Detector Alarms
During First Detector's
Verification Period
83 sec.
CONFIRMATION (60 seconds)
Control Panel Processes Alarm if Same Detector is Still in Alarm
Control Panel Immediately Processes Alarm
Note: Alarm Verification is available only for smoke detectors.
4.18 Walktest
Walktest is a feature which allows one person to test the fire alarm system. An audible walktest
will momentarily sound the Notification Appliance Circuits in the building and store the walktest
information in a file at the panel. A silent walktest will not sound the NACs but will store the
walktest information in a file which can be viewed at the panel. Disabled NAC devices will not
activate during walktest. In addition, i3 smoke detectors will enter their own test mode causing
their LEDs to flash twice every five seconds (refer to i3 specification document).
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its programmed
control outputs for four seconds, if those outputs have been programmed for silenceable activation.
It also stores each alarm in the walktest history file which can be sent to an optional printer. The
stored display will be the same as if the device actually activated except the colon (:) in the time
stamp is replaced with an asterisk (*).
Open Condition
IDCs and all main circuit board NACs are monitored for fault conditions during Walktest mode.
When an open condition occurs on an IDC, the FACP will activate all enabled NACs during an
audible Walktest and remain activated until the open condition is cleared.
While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of
the Program and status change operations). The alarm relay is not activated.
Note: In Walktest, an NAC open or short fault will not cause the NACs to activate.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
117
Operating Instructions
4.19 Read Status
Read Status functions do not require a password. The control panel will continue to provide fire
protection while in Read Status mode. This mode can be entered while the control panel is in alarm
or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to
prevent confusion.
Read Status Entry
When the operator presses the control panel Enter key, the LCD will display the following:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=REMOTE DOWNLOAD
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read
Status mode which allows the user to view and print the programmed features and status of the
control panel.
The following screens will be displayed:
READ STATUS
1=INPUT ZONES
2=NACS
3=RELAYS
Read Status Screen #1
READ STATUS
1=SYSTEM SETTINGS
2=TIMERS
3=DAYLIGHT SAVINGS
Read Status Screen #2
118
READ STATUS
1=HISTORY
2=PRINTER
3=ANN-BUS
Read Status Screen #3
READ STATUS
1=CENTRAL STATION
2=PHONE LINES
3=SERVICE TERMINAL
Read Status Screen #4
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.19.1 Input Zones
Pressing 1 while viewing Read Status Screen #1 will cause the following screens to be displayed:
ZONE STATUS
1=ZONE 1
2=ZONE 2
3=ZONE 3
READ STATUS
1=INPUT ZONES
2=NACS
3=RELAYS
Read Status Screen #1
Pressing the down arrow key will allow the selection of Zones 4-5 for the MS-5UD and Zones 4-10
for the MS-10UD.
The operator selects the zone which is to be viewed by pressing the number corresponding to the
desired zone in each screen. For example, if 1 is pressed, the display will change to a screen similar
to the following:
Normal PULL STATION
ZONE 1
PRESS
TO VIEW
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to
view additional programming information about the selected device, such as:
•
Enable/Disable Status
•
Device Type
•
Alarm Verification On/Off (for detectors)
•
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
•
Pre-Signal Yes/No (for detectors only)
•
Input Zone Freeze Supervision
•
Adjective/Noun descriptor
•
Silenceable Yes/No
4.19.2 NAC
Pressing 2 while viewing Read Status Screen #1 will display the following screen:
NAC STATUS
1=NAC 1
3=NAC 3
2=NAC 2
4=NAC 4
The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed
options for NAC 2, 3 to view the programmed options for NAC 3 or 4 to view the programmed
options for NAC 4.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
119
Operating Instructions
The resulting screens will display the following information:
•
Enable/Disable Status
•
Coding Selection (Temporal, Steady, etc.)
•
Silenceable/Nonsilenceable
•
Auto Silence Enable/Disable and time delay (in minutes)
•
Silence Inhibit Enabled/Disabled
4.19.3 Relays
READ STATUS
1=INPUT ZONES
2=NACS
3=RELAYS
Read Status Screen #1
Pressing 3 while viewing Read Status Screen #1 will display the following screen:
RELAY
1=RELAY 1
ALARM
2=RELAY 2
TROUBLE
3=RELAY 3
SUPERV
This screen allows the operator to view the programmed option for each relay.
4.19.4 System Settings
Pressing 1 while viewing Read Status Screen #2 will display the following screens:
READ STATUS
1=SYSTEM SETTINGS
2=TIMERS
3=DAYLIGHT SAVINGS
SYSTEM SETTINGS
TROUBLE REMIND
NO
CANADIAN OPTION
OFF
CHRGR DISABLE
NO
Read Status Screen #2
SYSTEM SETTINGS
USER BANNER:
XXX XXXXX XXXX XXXX
The operator can view the system settings options that have been programmed into the FACP.
120
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.19.5 Timers
Pressing 2 while Read Status Screen #2 will display the following screen:
TIMERS
PAS DELAY
PRE SIGNAL
WATERFLW DELAY
READ STATUS
1=SYSTEM SETTINGS
2=TIMERS
3=DAYLIGHT SAVINGS
120
120
0
Read Status Screen #2
TIMERS
AC LOSS DELAY
2
These screens allow the operator to view the various timer settings.
4.19.6 Daylight Savings
Pressing 3 while Read Status Screen #2 will cause the following screens to be displayed:
DAYLIGHT SAVINGS
ENABLED
NO
START MONTH
MAR
START WEEK
WK 3
DAYLIGHT SAVINGS
END MONTH
NOV
END WEEK
WK 3
These screens allow the operator to view settings that have been programmed for Daylight Savings
Time.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
121
Operating Instructions
4.19.7 History
Pressing 1 while viewing Read Status Screen #3 will display the following screens:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
READ STATUS
1=HISTORY
2=PRINTER
3=ANN-BUS
Read Status Screen #3
The operator can view all events which have been stored in the history file, only alarms or other
events, such as troubles or supervisories, by pressing the corresponding number key.
4.19.8 Print
To print program data or control panel status, press 2 while viewing Read Status Screen #3. The
following screens will be displayed:
PRINT
1=HISTORY
2=WALKTEST LOG
3=EXIT PRINTING
Print Screen #1
PRINT
1=PRINTER OPTIONS
Print Screen #2
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail
all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail
all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on
page 102 for additional information on the display.
Pressing 3 while viewing Print Screen #1 will exit the Print operation.
Pressing 1 while viewing Print Screen #2 allows the user to view the printer settings.
122
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.19.9 ANN-BUS
Pressing 3 while viewing Read Status Screen #3 will display the settings for the ANN-BUS options
as shown in the following screens:
ANN-BUS
BUS ENABLED
NO
1=BUS MODULES
2=ANN-S/PG OPTIONS
READ STATUS
1=HISTORY
2=PRINTER
3=ANN-BUS
Read Status Screen #3
ANN-BUS Screen #1
ANN-BUS
1=ANN-80 OPTIONS
2=ANN-RLY OPTION
3=ANN-AUDIO OPTIONS
ANN-BUS Screen #2
ANN-BUS Screen #1 indicates whether the ANN-BUS is enabled (Yes/No).
Pressing 1 while viewing ANN-BUS Screen #1 will display BUS Module addresses 1-8 and the
devices, if any, located at those addresses.
Pressing 2 while viewing ANN-BUS Screen #1 will display the printer settings for the printer
connected to the FACP. This information includes:
•
•
•
•
•
•
•
Serial or Parallel printer
Printer Supervision (Yes or No)
Off-line Timer setting
Baud Rate
Data Bits
Parity
Stop Bits
Pressing 1 while viewing ANN-BUS Screen #2 will display the programmed options for the ANN80 devices connected to the ANN-BUS. These include Piezo enable/disable, Lock enable/disable
and which buttons/keys on the annunciator are enabled/disabled.
Pressing 2 while viewing ANN-BUS Screen #2 will display the zone programming for each ANNRLY relay.
Pressing 3 while viewing ANN-BUS Screen #3 will display the zone, if any, that has been assigned
as the All-Call Zone.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
123
Operating Instructions
4.19.10 Central Station
Pressing 1 while viewing Read Status Screen #4 will display the following screens:
CENTRAL STATION
REPORTING
YES
REPORT STYLE
BOTH
READ STATUS
1=CENTRAL STATION
2=PHONE LINES
3=SERVICE TERMINAL
Central Station Screen #1
Read Status Screen #4
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
0
Central Station Screen #2
Central Station Screen #1 indicates whether the Central Station Reporting is enabled or disabled
and if the Reports will be sent to one or both the Primary and Secondary Central Station phone
numbers. Central Station Screen #2 provides information on the Primary and Secondary Central
Station programming which includes:
•
Test Time Interval
•
Account Code
•
24 Hour Test Time
•
Phone Number
•
Communication Format
•
Event Codes
This screen also displays the Call Limit for each unique DACT trouble call within a 24 hour period
124
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Operating Instructions
4.19.11 Phone Line
Pressing 1 while viewing Read Status Screen #4 will display the following screen:
PHONE LINES
PRIMARY
TCH TNE
SECONDARY
TCH TNE
3=SUPERV PHONE LINE
The second and third lines of this screen indicate that both the Primary and Secondary phone lines
have been configured for touchtone dialing operation.
Pressing 1 for Superv Phone Line will cause the following screen to be displayed:
SUPERVISE PHONE LINE
PHONE LINE 2
YES
This screen indicates whether or not Phone Line 2 is being supervised by the DACT. The factory
default setting is Phone Line 2 supervised (Yes).
4.19.12 Service Terminal
READ STATUS
1=CENTRAL STATION
2=PHONE LINES
3=SERVICE TERMINAL
Pressing 3 while viewing Read Status Screen #4 will display the following screens:
SERVICE TERMINAL
RING COUNT
Read Status Screen #4
Service Terminal Screen
The Ring Count is displayed as the first item in the Service Terminal Screen.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
125
Central Station Communications
SECTION 5
Central Station Communications
The control panel transmits zone and system status reports to Central Stations via the public
switched telephone network. Two supervised telephone line connections are made to interface the
control panel to the telephone lines. Two optional 7 foot telephone cords are available for this
purpose and can be purchased separately.
The control panel supervises both telephone lines for proper voltage. A delay of two minutes will
occur before a fault in either phone line connection is reported as a trouble. When a fault is
detected, an audible trouble signal will sound, the LCD display will indicate the phone line trouble
and the trouble condition will be reported to the Central Station over the remaining operational
phone line.
The control panel comes with line seizure capability provided for both the primary and secondary
telephone line interfaces. Any time that the control panel needs to make a call to a Central Station,
line seizure will disconnect any local premises phones sharing the same telephone line.
All transmissions to the Central Stations will be sent over the primary phone line. In the event of
noisy phone lines, transmissions will be sent over the backup secondary phone line.
Two phone numbers must be programmed, the primary Central Station phone number and the
secondary Central Station phone number. All system reports will be transmitted to the primary
Central Station phone number. Reports will automatically be sent to the secondary Central Station
phone number if attempts to transmits to the primary Central Station phone number are
unsuccessful. If 10 total attempts to communicate are unsuccessful, a Communicator Failure report
will be displayed. Note that as an option, all reports may also be sent to the secondary Central
Station phone number.
The FACP meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b)
condition and (c) location of the reporting premises. The general priority reporting structure is:
1. Zone Alarms and Restores
2. Zone Troubles and Restores
3. System Troubles and Restores
4. 24-hour Test
126
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Central Station Communications
5.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events, in terms of priority, are
listed below in descending order:
1. Alarms (highest priority level)
Pull stations
Waterflow
Smoke detector
Other alarm types
2. Supervisory Zone
3. System Troubles
Zone disabled
Fire drill
AC fail (after delay)
Zonal faults
Earth fault
Low battery
Telephone line fault
Notification Appliance Circuits fault
Communication trouble
Annunciator trouble
System off normal
4. Restoral Reports
Zone alarm
Supervisory
Zone(s) enabled
Fire drill
AC
Zone fault
Earth
Battery
Telephone line
Notification Appliance Circuits
Communication
Annunciator trouble
System off normal
5. 24 Hour Test (lowest priority)
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
127
Central Station Communications
The table below shows UL listed receivers which are compatible with the MS-5UD and MS-10UD.
FBI
CP220FB (10)
SurGard
MLR-2000 (9)
SurGard
System III (8)
Silent Knight
9800 (4)
SIA-DCS-8
1
SIA-DCS-20
2
Ademco Contact ID
Radionics
6600 (6)
Format
SurGard
MLR2 (7)
Silent Knight
9500 (3)
0
Ademco
685 (1)
Ademco
MX8000 (2)
Osborne Hoffman
2000E (5)
Table 5.1 Compatible UL Listed Receivers
1. With 685-8 Line Card with Rev. 4.4d software
2. With 124060V206B and 124063 Line Card Rev. B
3. With version V2.4 Receiver and 126047 Line Card Rev. G
4. With 124077V2.00 Receiver and 126047 Line Card Rev. M
5. With V.7301 Receiver S/W
6. With 01.01.03 Receiver S/W and Line Card 01.01.03
7. With software V1.86
8. With software V1.72
9. With DSP4016 and V1.6 Line Card
10. With software V3.9
IMPORTANT! It is the installer’s responsibility to ensure that the Digital Alarm Communicator/
Transmitter is compatible with the Central Station Receiver, utilized by the monitoring service,
prior to installation. The Compatibility Table provides a list of compatible receivers and
associated software versions for the receivers. Changes in the hardware and/or software by the
receiver manufacturers may affect the receiver compatibility with the FACP DACT. After
completing the installation, communication between the DACT and Central Station Receiver must
be tested and verified.
128
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Local/Remote Site Upload/Download
SECTION 6
Local/Remote Site Upload/Download
The control panel may be programmed or interrogated off-site via the public switched telephone
network or locally using a USB cable. Any personal computer with Windows™ XP or later, with a
2400 baud compatible modem or USB port and Upload/Download software PS-Tools on the CD
ROM P/N PK-CD, may serve as a Service Terminal. This allows download of the entire program
or upload of the entire program, history file, walktest data, current status, system voltages, time and
date.
Upload/Download Preparation
The PK-CD must be placed into the personal computer CD drive and the instructions that come
with it must be followed to install the PS-Tools utility onto the computer. Once the is done, the PSTools utility must be set up to communicate using either a USB serial port or a dial-up modem.
For local USB programming, a standard male-A to male-B USB cable must be connected from the
PC’s USB port to the fire panel’s USB port (J11).
For remote modem programming, you must have the fire panel’s primary line telephone number
entered in the PS-Tools site information screens for that site. You must also change the fire panel’s
ring count from zero (the default) to answer after at least one ring.
Important: Modification of FACP programming requires that the panel be enabled for download
(refer to "Remote Download" on page 129). Remote interrogation of panel programming, history
logs, detector status, etc., is possible without enabling the remote download option.
CAUTION: After successfully downloading a program, make certain to perform the following
steps:
1. Print out all programmed data via Print Mode or manually view programmed entries and
compare to intended program data
2. Test all affected panel operations
3. Immediately correct any problems found
6.1 Remote Download
NFPA 72 requirements state that a technician must be on-site and at the control panel whenever the
Programming Utility is used to download any information to the FACP. This applies to local and
remote programming. For this reason, a new option has been added to the FACP which allows an
individual at the FACP to enter a password and either enable the proprietary mode where
downloading will be allowed at any time or access a specific password protected screen where
downloading will be allowed regardless of the current proprietary setting. The Remote Download
option can be selected from the main menu screen as shown below:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=REMOTE DOWNLOAD
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
129
Local/Remote Site Upload/Download
Pressing 3 for Remote Download while viewing the main menu will cause the following screen to
be displayed:
REMOTE DOWNLOAD
ENTER PASSWORD
*****
The Remote Download password (default 00000) must be entered to access the Remote Download
feature. Note that the default password can be changed using the Password Change option (refer to
"Password Change" on page 103).
Entering the correct password will cause the following screen to be displayed:
REMOTE DOWNLOAD
1=PROPRIETARY
2=ACCEPT DOWNLOAD
NO
Pressing 1 for Proprietary No (factory default setting), while viewing the Remote Download
screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the
1 key will cause the display to toggle between Proprietary No and Proprietary Yes. Selecting
Proprietary Yes will program the FACP to allow remote programming downloads from the
programming utility at all times without the need to access the Remote Download screen.
Pressing 2 for Accept Download will cause the following screen to be displayed:
*ALLOWING DOWNLOADS*
IF YOU EXIT THIS
SCREEN DOWNLOADS
WILL BE DISABLED!
While this screen is displayed, remote programming downloads are allowed regardless of the
Proprietary setting. Exiting this screen will disable any further downloads to the FACP. Also,
following 30 minutes of inactivity (including up/downloading), the Accept Download screen will
time-out, causing the display to return to the System All Normal screen.
130
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Local/Remote Site Upload/Download
6.2 Transferring a Program
The first time that the control panel is contacted, a secret code is loaded in by a Service Terminal.
Future upload or download requests cause verification of the secret code by the control panel
before processing of data is allowed. If the secret code is not verified, the control panel will
terminate the request.
While the control panel is communicating with the remote Service Terminal, one of the DACT’s
red phone line active LEDs and the green Kissoff LED will remain on steady.
In order to download the panel (whether initiated at the jobsite or remotely), the following must be
true:
The control panel must be in the Normal Mode of operation. Downloading is not possible
if the panel is in any other mode
There cannot be any active communications ongoing with a Central Station receiver
All active events must be successfully 'kissed-off' by the Central Station(s). The
communicator must be in a standby state with no new information waiting to be
transmitted to a Central Station
6.2.1 Security Features
Upload and download with the control panel have been carefully designed to include key security
features to ensure proper functionality. Any time a transfer is initiated, the control panel and the
Service Terminal will communicate and transfer data before contacting a Central Station. When
the data transfers are completed and the control panel disconnects from the Service Terminal, the
control panel will call the Central Station and report one of the following conditions:
•
Upload/download request received
•
Upload and/or download request successful
•
Upload/download failed
The key features are listed and explained in the following sections.
Secret Code Verification
A secret code is stored in the control panel by a Service Terminal to prevent unauthorized access.
The secret code is created at the Service Terminal by the master user and cannot be viewed or
changed by anyone other than a master user. Viewing of the secret code is prohibited at the control
panel. Prior to allowing an upload or download of data, the control panel will verify the secret code
transmitted by the Service Terminal.
Time-out at Control Panel
Upon answering an incoming (modem) call on the primary Central Station phone line, the control
panel will listen for a modem connection signal. If this signal is not received within 50 seconds, the
control panel will disconnect the call. Upon successful connection (secret code verified), if no
communication occurs within 30 minutes, the panel will disconnect the call. Upon time-out,
transfer activity will be reported to the Central Station (if enabled) and the connection will be
terminated.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
131
Local/Remote Site Upload/Download
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If an error is
detected, the block is retransmitted until correct, up to a maximum of four times. If the Secret Code
is not verified and four errors occur, the call is disconnected and the report that the upload/
download was not successful is called to the Central Station(s).
Central Station Data Protection
The primary and secondary Central Station phone numbers, communications format, account code,
test time and programmable event codes are vital Central Station information. These blocks of data
are protected from partial programming due to faulty phone connections, line noise and other
errors. This prevents the panel from being confused due to a wrong phone number, account code,
test time and most critical formatting errors.
132
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Power Supply Calculations
Power Supply Calculations
SECTION 7
7.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
7.2
Calculating the AC Branch Circuit
The control panel requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,
from the power source to the control panel. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2)
wire with 600 volt insulation for this branch circuit.
Use Table 7-1 , to determine the total amount of current, in AC amperes (A), that must be supplied
to the system.
TABLE 7-1:AC Branch Circuit Requirements
Device Type
Number of
Devices
Current Draw
(AC amps)
MS-5UD-3/MS-10UD-3
or
MS-5UD-7(C)/MS-10UD-7(C)
Total Current
per Device
1.00
3.90
or
1
X
=
0.54
MS-5UD-3E/MS-10UD-3E
or
MS-5UD-7E/MS-10UD-7E
2.20
[
]
X
[
]
X
=
[
]
Sum Column for AC Branch Current Required
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
=
=
133
Power Supply Calculations
7.3
Calculating the System Current Draw
7.3.1 Overview
The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 7-3 on page 135. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 7-3 on page 135. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7-3 on page
135.
When calculating current draw and the battery size, note the following:
• ‘Primary’ refers to the main power source for the control panel
• ‘Secondary’ refers to the control panel’s backup batteries
• All currents are given in amperes (A). Table 7-2 shows how to convert milliamperes and
microamperes to full amperes.
TABLE 7-2:Converting to Full Amperes
To convert...
Multiply
Milliamperes (mA) to
amperes (A)
mA x 0.001
Microamperes (µA) to
amperes (A)
µA x 0.000001
Example
3 mA x 0.001 = 0.003A
300 µA x 0.000001 = 0.0003 A
7.3.2 How to Use Table 7-3 on page 135 to Calculate System Current Draw
Use Table 7-3 on page 135 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the Device Compatibility Document for
compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 7-4 on page 136
Following are the types of current that can be entered into Table 7-3 on page 135:
134
Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a non-fire
alarm condition during a loss of AC power.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Power Supply Calculations
Table 7-3 contains three columns for calculating current draws. For each column, calculate the
current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 7-4 on page 136.
TABLE 7-3:System Current Draw Calculations
Device Type
Calculation Column 1
Primary, Non-Fire Alarm Current
(amps)
Qty
Main Circuit Board
MS-5UD
or
MS-10UD
X[current draw]=
Calculation Column 2
Secondary, Fire Alarm Current
(amps)
Total
Qty
X[0.080]=
1
X [current draw] =
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
Total
Qty
X[0.235]1, 8=
1
X[current draw]=
X[0.100]=
1
X[0.265]1, 8=
X[0.085]=
Total
X[0.127]=
CAC-5X
[
]
X[0.001]=
[
]
X[0.001]=
]
X[0.001]=
4XTMF
[
]
1 max.
X[0.005]=
[
]
1 max.
X[0.011]1=
[
[
]
1 max.
X[0.005]=
X[0.015]=
ANN-80
[
]
X[0.037]=
[
]
X[0.040]=
[
]
ANN-I/O
[
]
X[0.035]=
[
]
X[0.200]=
[
]
X[0.035]=
ANN-RLY
[
]
X[0.015]=
[
]
X[0.075]=
[
]
X[0.015]=
ANN-(R)LED2
[
]
X[0.028]=
[
]
X[0.068]=
[
]
X[0.028]=
ANN-S/PG
[
]
X[0.045]=
[
]
X[0.045]=
[
]
X[0.045]=
2-wire Detector
Heads
[
]
X[
]3=
[
]9
X[0.040]=
[
]
X[
] 3=
4-wire Detector
Heads
[
]
X[
] 3=
[
]9
X[0.040]=
[
]
X[
] 3=
Power Supervision
Relays4
[
]
X[0.025]=
[
]
X[0.025]=
[
]
X[0.025]=
NAC #15
[
]
X[
]=
NAC #2
[
]
X[
]=
NAC #3
NAC #4
Current Draw from
TB9 (nonalarm6)
Sum each
column7 for
totals
[
]=
Primary Non-Alarm =
[
Secondary Alarm =
]=
[
]=
Secondary Non-Alarm =
Table Footnote
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output,
add another 0.005 amps.
2. ANN-LED is supplied standard with the MS-5UDC and MS-10UDC
3. Refer to the Device Compatibility Document for standby current.
4. Must use compatible listed Power Supervision Relay.
5. Current limitation of Terminal TB5 circuits is 2.5 amps per NAC for the MS-5UD-3(E), MS-10UD-3(E) and
3.0 amps per NAC for the MS-5UD-7(C/E), MS-10UD-7(C/E)
6. The total standby current must include both the resettable (TB9 Terminals 3 & 4) and nonresettable/
resettable (TB9 Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these
outputs during alarm does not exceed maximum ratings specified. Current limitations of TB9, Terminals 1 &
2 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10 mVRMS, nonresettable power and TB9,
Terminals 3 & 4 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10mVRMS, resettable power.
7. Total current draw listed above cannot exceed 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) or, 7.0 amps for
MS-5UD-7(C/E), MS-10UD-7(C/E).
8. The current draw shown represents one zone (IDC) on the main circuit board in alarm. One zone consumes
0.040 amps
9. Enter the number of IDCs used minus one
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
135
Power Supply Calculations
7.4
Calculating the Battery Size
Use Table 7-4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load
determines the battery size (in AH), required to support the control panel under the loss of AC
power. Complete Table 7-4 as follows:
1. Enter the totals from Table 7-3 on page 135, Calculation Columns 2 and 3 where shown
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm
ampere hours
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH)
5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet door
TABLE 7-4:Total Secondary Power Requirements at 24 VDC
Secondary Standby Load
(total from Table 7-3 Calculation
Column 3)
[
]
Required Standby Time
(24 hours)
Secondary Alarm Load
(total from Table 7-3 Calculation
Column 2)
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
[
X[
]
X[
]
]
Sum of Standby and Alarm Ampere Hours
=
AH
=
AH
=
AH
Multiply by the Derating Factor
X 1.2
Battery Size, Total Ampere Hours Required
=
AH
7.4.1 NFPA Battery Requirements
NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power
followed by 5 minutes in alarm
7.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 7-4 . The control
panel can charge batteries in the 7 AH to 26 AH range. The control panel cabinet is capable of
housing batteries up to 18 AH. Batteries larger than 18 AH require the BB-26, BB-55 or other UL
listed external battery cabinet.
For Canadian applications, the minimum battery size is 12 AH and the maximum battery size is
18AH.
136
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Ademco Contact ID Format Event Code Descriptions
Ademco Contact ID Format
Event Code Descriptions
APPENDIX A
This appendix describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format.
A.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC where
SSSS
= Four digit Subscriber ID Account Code
18
= Identifies transmission as Contact ID to the receiver at the Central Station
Q
= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ
= Event code
GG
= Group number
CCC
= Zone number
Notes:
1. 18, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.
2. GG Group Number is fixed at '00' and cannot be changed.
3. CCC for Zone Number is transmitted as ‘001’ for zone 1 up to ‘010’ for zone 10
A.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Time
Date
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
11:28
03/25
03/25
03/25
03/25
03/25
03/25
03/25
03/25
03/25
03/25
Rcvr/Line ID
11
11
11
11
11
11
11
11
11
11
SSSS
QXYZ
GG
CCCC
7777
7777
7777
7777
7777
7777
7777
7777
7777
7777
E110
E111
E380
E570
R110
R111
R380
R570
E158
E151
00
00
00
00
00
00
00
00
00
00
C001 - general fire alarm on zone one
C002 - smoke detector alarm on zone two
C003 - fault on zone three
C009 - Zone nine disabled
C001 - Zone one alarm restored
C002 - smoke detector zone two restored
C003 - zone three fault restored
C009 - zone nine reenabled
C006 - high temperature, zone six
C007 - gas detected, zone seven
Notes:
1. 11 is an example of a Receiver/Line Card, showing which receiver and line card the message
was transmitted to.
2. Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R for New Restore.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
137
Ademco Contact ID Format Event Code Descriptions
EVENT CODE CLASSIFICATIONS
100
ALARMS
Medical
Fire
Panic
Burglary
General
24 Hour
200
SUPERVISORY
Fire
300
TROUBLES
400
OPEN/CLOSE
REMOTE ACCESS
System
Sounder/Relay
System Peripheral
Communication
Protective Loop
Sensor
Open/Close
Remote Access
Access Control
System
Sounder/Relay
System Peripheral
Communication
600
TEST/
MISC.
Test
EVENT
Medical Alarms - 100
100 Medical
101 Pendant transmitter
102 Fail to report in
EMERG - Personal Emergency - #
EMERG - Personal Emergency - #
EMERG - Fail to Check-in - #
Fire Alarms - 110
110 Fire Alarm
111 Smoke
112 Combustion
113 Waterflow
114 Heat
115 Pull station
116 Duct
117 Flame
118 Near Alarm
FIRE - Fire Alarm - #
FIRE - Smoke Detector - #
FIRE - Combustion - #
FIRE - Waterflow - #
FIRE - Heat Sensor - #
FIRE - Pull Station - #
FIRE - Duct Sensor - #
FIRE - Flame Sensor - #
FIRE - Near Alarm - #
Panic Alarms - 120
120 Panic Alarm
121 Duress
122 Silent
123 Audible
PANIC - Panic - #
PANIC - Duress
PANIC - Silent Panic - #
PANIC - Audible Panic - #
Burglar Alarms - 130
130 Burglary
131 Perimeter
132 Interior
133 24-Hour
134 Entry/Exit
135 Day/Night
136 Outdoor
137 Tamper
138 Near Alarm
BURG - Burglary - #
BURG - Perimeter - #
BURG - Interior - #
BURG - 24-Hour - #
BURG - Entry/Exit - #
BURG - Day/Night - #
BURG - Outdoor - #
BURG - Tamper - #
BURG - Near Alarm - #
General Alarms - 140
140 General Alarm
141 Polling loop open
142 Polling loop short
143 Expansion module failure
144 Sensor tamper
145 Expansion module tamper
138
500
DISABLES/
BYPASSES
MESSAGE
ALARM - General Alarm - #
ALARM - Polling Loop Open - #
ALARM - Polling Loop Short - #
ALARM - Exp. Module Fail - #
ALARM - Sensor Tamper - #
ALARM - Exp. Module Tamper - #
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Ademco Contact ID Format Event Code Descriptions
EVENT
MESSAGE
24 Hour Non-Burglary - 150 and 160
150 24-Hour Non-Burg
ALARM - 24-Hr. Non-Burg - #
151 Gas detected
ALARM - Gas Detected - #
152 Refrigeration
ALARM - Refrigeration - #
153 Loss of heat
ALARM - Heating System - #
154 Water leakage
ALARM - Water Leakage - #
155 Foil break
ALARM - Foil Break - #
156 Day trouble
ALARM - Day Zone - #
157 Low bottled gas level
ALARM - Low Gas Level - #
158 High temp
ALARM - High Temperature - #
159 Low temp
ALARM - Low Temperature - #
161 Loss of air flow
ALARM - Air Flow - #
Fire Supervisory - 200 and 210
200 Fire supervisory
201 Low water pressure
202 Low CO2
203 Gate valve sensor
204 Low water level
205 Pump activated
206 Pump failure
SUPER. - Fire Supervisory - #
SUPER. - Low Water Pressure - #
SUPER. - Low CO2
SUPER. - Gate Valve - #
SUPER. - Low Water Level - #
SUPER. - Pump Activation - #
SUPER. - Pump Failure - #
System Troubles - 300 and 310
300 System trouble
301 AC loss
302 Low system battery
303 RAM checksum bad
304 ROM checksum bad
305 System reset
306 Panel program changed
307 Self-test failure
308 System shutdown
309 Battery test failure
310 Ground fault
311 No battery
TROUBLE - System Trouble
TROUBLE - AC Power
TROUBLE - System Low Battery
TROUBLE - Bad RAM Checksum (restore not applicable)
TROUBLE - Bad ROM Checksum (restore not applicable)
TROUBLE - System Reset (restore not applicable)
TROUBLE - Programming Changed (restore not applicable)
TROUBLE - Self Test Failure
TROUBLE - System Shutdown
TROUBLE - Battery Test Failure
TROUBLE - Ground Fault - #
TROUBLE - No Battery
Sounder/Relay Troubles - 320
320 Sounder/Relay
321 Bell 1
322 Bell 2
323 Alarm relay
324 Trouble relay
325 Reversing
326 Bell 3
327 Bell 4
TROUBLE - Sounder Relay - #
TROUBLE - Bell/Siren #1
TROUBLE - Bell/Siren #2
TROUBLE - Alarm Relay
TROUBLE - Trouble Relay
TROUBLE - Reversing Relay
TROUBLE - Bell/Siren #3
TROUBLE - Bell/Siren #4
System Peripheral Troubles - 330 and 340
330 System peripheral
TROUBLE - Sys. Peripheral - #
331 Polling loop open
TROUBLE - Polling Loop Open
332 Polling loop short
TROUBLE - Polling Loop Short
333 Expansion module failure
TROUBLE - Exp. Module Fail - #
334 Repeater failure
TROUBLE - Repeater Failure - #
335 Local printer paper out
TROUBLE - Printer Paper Out
336 Local printer failure
TROUBLE - Local Printer
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
139
Ademco Contact ID Format Event Code Descriptions
EVENT
MESSAGE
Communication Troubles - 350 and 360
350 Communication
TROUBLE - Communication Trouble
351 Telco 1 fault
TROUBLE - Phone Line #1
352 Telco 2 fault
TROUBLE - Phone Line #2
353 Long range radio xmitter fault TROUBLE - Radio Transmitter
354 Fail to communicate
TROUBLE - Fail to Communicate
355 Loss of radio supervision
TROUBLE - Radio Supervision
356 Loss of central polling
TROUBLE - Central Radio Polling
Protection Loop Troubles - 370
370 Protection loop
371 Protection loop open
372 Protection loop short
373 Fire Trouble
TROUBLE - Protection Loop - #
TROUBLE - Protection Loop Open - #
TROUBLE - Protection Loop Short - #
TROUBLE - Fire Loop - #
Sensor Troubles - 380
380 Sensor trouble
381 Loss of supervision - RF
382 Loss of supervision - RPM
383 Sensor tamper
384 RF transmitter low battery
TROUBLE - Sensor Trouble - #
TROUBLE - RF Sensor Supervision - #
TROUBLE - RPM Sensor Supervision - #
TROUBLE - Sensor Tamper - #
TROUBLE - RF Sensor Batt. - #
Open/Close - 400
400 Open/Close
401 Open/Close by user
402 Group Open/Close
403 Automatic Open/Close
404 Late Open/Close
405 Deferred Open/Close
406 Cancel
407 Remote arm/disarm
408 Quick arm
409 Keyswitch Open/Close
OPENING
CLOSING
OPENING - User #
CLOSING - User #
OPENING - Group User # CLOSING - Group User #
OPENING - Automatic CLOSING - Automatic
OPENING - Late
CLOSING - Late
Opening not used
Closing not used
OPENING - Cancel
Closing not used
OPENING - Remote
CLOSING - Remote
Opening not applicable CLOSING - Quick arm
OPENING - Keyswitch CLOSING - Keyswitch
Remote Access - 410
411 Callback request made
412 Success - download/access
413 Unsuccessful access
414 System shutdown
415 Dialer shutdown
416 Success - upload/access
REMOTE - Callback Requested
REMOTE - Successful Access
REMOTE - Unsuccessful Access
REMOTE - System Shutdown
REMOTE - Dialer Shutdown
REMOTE - Successful Access
Access Control - 420
421 Access denied
422 Access report by user
ACCESS - Access Denied - User # (restore not used)
ACCESS - Access Gained - User # (restore not used)
(restore not applicable)
(restore not applicable)
(restore not applicable)
(restore not applicable)
System Disables - 500 and 510
140
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Ademco Contact ID Format Event Code Descriptions
EVENT
Sounder/Relay Disables - 520
520 Sounder/Relay disable
521 Bell 1 disable
522 Bell 2 disable
523 Alarm relay disable
524 Trouble relay disable
525 Reversing relay disable
526 Bell 3 disable
527 Bell 4 disable
MESSAGE
DISABLE - Sounder/Relay - #
DISABLE - Bell/Siren - #1
DISABLE - Bell/Siren - #2
DISABLE - Alarm Relay
DISABLE - Trouble Relay
DISABLE - Reversing Relay
DISABLE - Bell/Siren - #3
DISABLE - Bell/Siren - #4
System Peripheral Disables - 530 and 540
Communication Disables - 550 and 560
551 Dialer disabled
DISABLE - Dialer Disable
552 Radio transmitter disabled
DISABLE - Radio Disable
Bypasses - 570
570 Zone bypass
571 Fire bypass
572 24-Hour zone bypass
573 Burglar bypass
574 Group bypass
BYPASS - Zone Bypass - #
BYPASS - Fire Bypass - #
BYPASS - 24-Hour Bypass - #
BYPASS - Burg. Bypass - #
BYPASS - Group Bypass - #
Test Misc. - 600
601 Manual trigger test
602 Periodic test report
603 Periodic RF transmission
604 Fire test
605 Status report to follow
606 Listen-in to follow
607 Walk test mode
608 System abnormal test
TEST - Manually Triggered
TEST - Periodic
TEST - Periodic Radio
TEST - Fire Test
STATUS - Status Follows
LISTEN - Listen-in Active
TEST - Walk Test Mode
TEST - System Abnormal Test
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
(restore not applicable)
(restore not applicable)
(restore not applicable)
(restore not used)
(restore not applicable)
(restore not applicable)
141
NFPA Standard-Specific Requirements
APPENDIX B
NFPA Standard-Specific Requirements
The MS-5UD/MS-10UD has been designed for use in commercial, industrial and institutional
applications and meets the requirements for service under the National Fire Protection Association
(NFPA) Standards outlined in this Appendix. The minimum system components required for
compliance with the appropriate NFPA standard are listed below:
MS-5UD/MS-10UD Control Panel
Contains the main control board, cabinet (backbox and door), main power supply and transformer.
Batteries
Refer to "Power Supply Calculations" on page 133, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:
NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service
Onboard Digital Alarm Communicator Transmitter for connection to a compatible
listed Central Station DACR or Protected Premises Receiving Unit. This unit must
be installed as outlined in "Digital Alarm Communicator/Transmitter" on page 17.
OR
411UD may be installed as illustrated in Figure B.1, “MS-5UD/MS-10UD FACP
Connection to 411UD,” on page 143.
OR
4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver.
See Figure B.3, “Remote Station Connection Using 4XTMF Module,” on page 146,
for installation instructions for this unit.
NFPA 72 Auxiliary Fire Alarm System
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled "4XTMF Transmitter Module
Installation" on page 37 and as outlined in Figure B.2, “Municipal Box Connected to 4XTMF
Transmitter Module,” on page 145.
NFPA 72 Proprietary Fire Alarm System
MS-5UD/MS-10UD Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See
Figure B.4, “Proprietary Protective Signaling System,” on page 147, for installation instructions for
this unit.
142
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
NFPA Standard-Specific Requirements
The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the MS-5UD/MS-10UD may be used to trip any dialer UL listed
for Central Station/Remote Station Reporting Services.
411UD
Channel1
Channel 2
Channel 3
Channel 4 (2.2K ELR)
Jumper -VDC to Trouble Relay contact
+ 24 VDC nonresettable power
- 24 VDC nonresettable power
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
J4 Not Installed
Relay Output (DACT Trouble) from 411UD
FACP Supervisory Relay
FACP Trouble Relay
FACP Alarm Relay
2.2K ELRs P/N 27070
123456789
FACP
Trouble Input
(non-supervised,
power-limited)
Figure B.1 MS-5UD/MS-10UD FACP Connection to 411UD
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
143
NFPA Standard-Specific Requirements
Alarm
Trouble
Supervisory
411UD
FACP
TB2-1
TB8-1
TB2-2
TB8-3
TB2-3
TB8-4
TB2-4
TB8-6
TB2-5
TB8-7
TB2-6
TB8-9
Table B.1 411UD Connections to FACP
Notes:
1. Reference the 411UD Manual for additional information
2. Program the 411UD for slave operation
3. The MS-5UD/MS-10UD must be programmed for AC Loss Reporting Delay This prevents
the immediate transmission of a trouble on the loss of AC power
4. All connections between the control panel and the 411UD must be in conduit, less than 20
feet (610 cm) in length, in the same room
5. Any zone of the 411UD can be wired to function as alarm, trouble or supervisory. In Figure
B.1 on page 143, Channel 1/Zone 1 is wired to the control panel’s alarm relay, Channel 2/
Zone 2 is wired to the control panel’s trouble relay and Channel 3/Zone 3 is wired to the
control panel’s supervisory relay
6. Nonresettable 24 VDC power is supplied to the 411UD via TB9 terminals configured for
nonresettable power on the FACP. Jumper J4 on the 411UD must be removed for 24 VDC
power
7. End-of-Line resistors must terminate all 411UD circuits, including unused circuits
8. A -VDC from the 411UD Trouble Contacts will activate the Trouble Input J6 on the FACP
144
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the MS-5UD/MS-10UD main circuit board to supervise placement of 4XTMF
module and circuit.
3. Cut JP24 on the MS-5UD/MS-10UD main circuit board to enable FACP Supervisory relay.
4. Refer to "4XTMF Transmitter Module Installation" on page 37 for detailed information.
FIRE
+
Municipal Box
Circuit
Gamewell Model M3456 Local Energy
Municipal Box
Polarities shown in alarm condition
Nonpower-limited
+
-
4XTMF
Figure B.2 Municipal Box Connected to 4XTMF Transmitter Module
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
145
NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the MS-5UD/MS-10UD main circuit board to supervise placement of
the 4XTMF module.
2. Refer to "4XTMF Transmitter Module Installation" on page 37 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver
Model RS82.
+
-
Polarity Shown is
Normal Standby
+
Power-limited
(Dummy load with a 4.7KΩ, ¼ watt
resistor when no connection is made)
Cutting TBL Jumper allows the
reverse polarity circuit to open
with a system trouble condition
if no alarm condition exists.
4XTMF Transmitter Module
Figure B.3 Remote Station Connection Using 4XTMF Module
146
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
NFPA Standard-Specific Requirements
NFPA 72 Proprietary Protective Signaling Systems
Fire Alarm Control Panel
FACP Main Board
Form-C Alarm contact programmed to
activate on General Alarm.
Form-C Trouble contact which will
automatically activate on any Trouble
condition.
Form-C relay contact programmed to
activate on Supervisory condition.
Notes:
1. Connection between the MS-5UD/MS-10UD
and the transmitter are supervised by the
transmitter.
2. This MS-5UD/MS-10UD Transmitter
arrangement can be employed for NFPA 72
Proprietary Protective Signaling System.
Figure B.4 Proprietary Protective Signaling System
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
147
NFPA Standard-Specific Requirements
B.1 Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts
The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/
Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined
by the Transmitter manufacturer. Power is also provided by the Central Station/Remote Station
Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter manufacturer’s
manual for details.
Typical Central Station/Remote Station Transmitter Module
Trouble*
Superv.
Alarm
Typical Input Zone Triggers
*Note: The Trouble Relay is a
fail-safe relay. With power
applied to the FACP and no
troubles in the panel, the wiring
should be connected to the NO
and C contacts as indicated in the
illustration.
Fire Alarm Control Panel
Figure B.5 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
148
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
FACP with Keltron
FACP with Keltron
APPENDIX C
The following figure illustrates the connections between the FACP and Keltron
Receiver/Transmitter.
CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron
modules are not shown in actual order. Follow Keltron manual and module markings
for exact terminal locations to prevent severe module damage!
IMPORTANT! All connections between the FACP and Keltron modules must be made
within 20 feet and enclosed within conduit or equivalently protected against mechanical
injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
*Note: For more information,
refer to Keltron manual.
Sprinkler Supervisory Signal
Alarm/Trouble Signal
4XTMF Module
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in
their actual positions in order to
clarify wiring connections)
Figure C.1 Keltron Wiring
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
149
Wire Requirements
Wire Requirements
APPENDIX D
Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each
circuit. Reference the chart below to specify wire requirements and limitations for each circuit.
Table D.1 FACP Wire Specifications
CIRCUIT CONNECTIONS
150
WIRE REQUIREMENTS
Circuit Type
Circuit Function
Wire Type and Limitations
Recommended
Max. Distance
Feet (meters)
Initiating Device
Circuit
(power-limited)
Connects to
Initiating Devices
Untwisted, unshielded wire
(maximum loop resistance
not to exceed 100 ohms)
Distance limitation
set by 100 ohm
resistance limitation
12-18 AWG (3.25 - 0.75 mm2)
ANN-BUS
(EIA-485)
power-limited
Communication
for ANN-BUS
annunciator and
relay modules
Twisted pair a maximum
loop resistance of 120 ohms
6,000 (1,800 m)
12-18 AWG (3.25 - 0.75 mm2)
ANN-BUS
Power
Power for
ANN-BUS
annunciators
24 VDC
Regulated,
resettable,
nonresettable
Power for
accessories and
4-wire devices
Untwisted, unshielded wire
Distance limitation
set by 4 volt
maximum line drop
12-18 AWG (3.25 - 0.75 mm2)
Auxiliary
Trouble Input
Open Collector
trouble input for
CHG-75,
CHG-120F, etc.
Single conductor
Distance limitation
20 feet in same
room
18 AWG (0.75 mm2)
Remote Sync
Output
Provides strobe
and normal sync
for remote NAC
power supplies
Untwisted, unshielded pair
wire
Distance set by 295
ohm resistance
limitation
12-18 AWG (3.25 - 0.75 mm2)
NAC Outputs
Connects to NAC
devices or Release
devices
Untwisted, unshielded pair
wire
Wire Gauge
Refer to "ANN-BUS Devices" on page 38 for information on device wiring
Refer to Section D.1 and Section D.2 on page 151.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Wire Requirements
D.1 MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring
The following table lists NAC wiring requirements for the MS-5UD-3(E) & MS10UD-3(E) FACP which utilizes the FLPS-3 power supply.
Table D.2 NAC Wiring Requirements for FACP with FLPS-3 Power Supply
NAC Load
(Amps)
Max.
allowable
total loop
resistance
(ohms)
CLASS-B
Max. allowable wire pair length
(feet)
AWG 12
solid
AWG 14
solid
AWG 16
solid
CLASS-A
Max. allowable wire pair length
(feet)
AWG 18
solid
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
0.25
9.60
2487
1564
982
618
1244
782
491
309
0.5
4.80
1244
782
491
309
622
391
245
154
0.75
3.20
829
521
327
206
415
261
164
103
1
2.40
622
391
245
154
311
195
123
77
1.25
1.92
497
313
196
124
249
156
98
62
1.5
1.60
415
261
164
103
207
130
82
51
1.75
1.37
355
223
140
88
178
112
70
44
2
1.20
311
195
123
77
155
98
61
39
2.25
1.07
276
174
109
69
138
87
55
34
2.5
0.96
249
156
98
62
124
78
49
31
Note: Calculations are based on Direct-Current Resistance data for uncoated copper
wire, per National Electrical Code (2005 Edition) Table 8, Conductor Properties.
D.2 MS-5UD-7(C/E) & MS-10UD-7(C/E) NAC Wiring
The following table lists NAC wiring requirements for the MS-5UD-7(C/E) & MS10UD-7(C/E) FACP which utilizes the FLPS-7 power supply.
Table D.3 NAC Wiring Requirements for FACP with FLPS-7 Power Supply
NAC Load
(Amps)
Max.
allowable
total loop
resistance
(ohms)
0.25
0.5
CLASS-B
Max. allowable wire pair length
(feet)
AWG 12
solid
AWG 14
solid
AWG 16
solid
13.60
3523
2215
6.80
1762
1107
0.75
4.53
1174
1
3.40
881
CLASS-A
Max. allowable wire pair length
(feet)
AWG 18
solid
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
1391
875
1762
1107
695
438
695
438
881
554
348
219
738
464
292
587
369
232
146
554
348
219
440
277
174
109
1.25
2.72
705
443
278
175
352
221
139
88
1.5
2.27
587
369
232
146
294
185
116
73
1.75
1.94
503
316
199
125
252
158
99
63
2
1.70
440
277
174
109
220
138
87
55
2.25
1.51
391
246
155
97
196
123
77
49
2.5
1.36
352
221
139
88
176
111
70
44
2.75
1.24
320
201
126
80
160
101
63
40
3
1.13
294
185
116
73
147
92
58
36
Note: Calculations are based on Direct-Current Resistance data for uncoated copper
wire, per National Electrical Code (2005 Edition) Table 8, Conductor Properties.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
151
Notes
152
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Index
Numerics
10 Zone Main Circuit Board 11
24 Hour Test Time 90
4XTM 146
4XTMF 146
installation 37
see also Transmitter module 18, 37
4XTMF installation 36
5 Zone Main Circuit Board 10
A
AC Loss Delay 75
AC power 26
AC power rating 14
AC power requirements 133
ACC audio messaage 63
ACC audio message 61
accessories 18
Account Code 90
ACK
see also Acknowledge 14
Acknowledge 14
Acknowledge/Step 16, 108
Ademco
contact ID format 137
Adjective
list 64
multiple entries 66
Alarm 111
alarm
piezo pulse rate 17
alarm relay 12, 30
contact rating 15
Alarm Silence 14, 16, 108
alarm verification 61, 114, 117
ANN-80 42
ANN-I/O
LED zone assignments 83
ANN-LED 51, 53
ANN-LED Annunciator Module 50
ANN-RLY 52
applications 12
Autosilence 116
NAC 71
auxiliary power 30
Auxiliary Trouble Input 16
B
backbox
dimensions 18
mounting 23
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Backup Reporting 88
Banner 73
setting 76
battery 18, 26
precautions 26
rating 15
battery box 19
mounting 24, 25
battery calculations 136
BB-55
see also battery box 19
buttons
see also control buttons 14
C
cabinet
mounting 23
CAC-5X 27
installation 34
Call Limit 99
call limit 55, 99
Canadian Applications 22
Canadian Option 73, 79
Central Station 88, 132
account code 90
communications 126
phone number 90
Phone Numbers 89
Central Station/Remote Station Reporting 143
charger capacity 15
Charger Disable 73
circuits 12
Class A 18, 27, 35
Class A Converter Module 18
installation 34
Class B 13, 15, 27
Clock Format 78
Coded Operation 114
Coding
NAC 68
coding
two stage operation 69
combination circuit 28
combination waterflow/supervisory 28
requirements 28
wiring 28
communications format 91
compatibility
see also device compatibility 12
contact ID 137
153
Index
Control Buttons 108
control buttons 14
controls 16
current
nonresettable power 30
resettable power 30
total output 29
current requirements for system 134, 135
D
DACT
onboard 87
Date setting 78
Daylight Savings Time 78
Description
detector label 66
description 12
Detector
adding description 63
enable/disable 60
device compatibility 12
dialer runaway 55, 99
Digital Communicator 20
dimensions
backbox 18
Downloading 131, 132
dress panel 13, 18
Drill 14, 16, 108
E
earth ground 26
edit
detector screens 59
Enable/Disable
zone 60
End-of-Line resistor
IDC 15, 27, 28
NAC 15, 29
Enter key 57
Erase History 101
Error Checking 132
event code classification 138
event codes 91
exiting
programming 56, 57
Read Status 56, 57
F
fail-safe
trouble relay 30
features 13
Form-C
154
see also relay 12
freeze 27
freeze signal
see also smoke detector monitoring 12
H
Hazard Condition 113
History 100
erase 101
Maintenance Level 105
view events 101
I
I3 detectors 27
IDC 13, 15, 27
alarm current 15
compatibility 27
End-of_Line resistor 28
End-of-Line resistor 15, 27
maximum loop resistance 15, 27
short circuit current 15
standby current 15
wiring 27
indicators 16
see also LED 14
Initiating Device Circuit 13, 15, 27
Class A 35
In-Line resistor
IDC combination circuit 28
Input Zones 59, 119
installation 23
CAC-5X 34
Class A Converter Module 34
option modules 34
Transmitter Module 36, 37
J
J4 and J5
option module connectors 36
JP30 jumper
placement supervision 36
K
Key Panel 16
function keys 16
service/program keys 16
L
lamp test 16
LCD display 13, 16
LED 14, 17
AC Power 14, 17, 109
Alarm Silence 14, 17
Alarm Silenced 109
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Index
Fire Alarm 14, 17, 109
Supervisory 14, 17, 109
System Trouble 17
Trouble 14, 109
Local Programming 55
M
main circuit board
see also 10 zone main circuit board 11
see also 5 Zone main circuit board 10
see also MS-10UD 11
maintenance 27
piezo pulse rate 17
Maintenance Alert 114
Maintenance Program Level 2 56, 104
maintenance signal
see also smoke detector monitoring 12
Manual programming 55
Master Program Level 1 56, 58
Medical Alert 113
Mode key 57
Mounting
main circuit board 23
mounting
cabinet 23
municipal box 37
municipal box transmitter
see also Transmitter module 18
N
NAC 12, 15, 67
Auto Silence 71
coded 114
coding 68
current 29
End-of-Line resistor 15, 29
maximum current 15
silence inhibit 71
silenceable 70
synchronized 69
wiring 29
NAC enable/disable 68
NFPA 72 Auxiliary Fire Alarm System 142,
145
NFPA 72 Central Station Service (Protected
Premises Unit) or Remote Station Service 142
NFPA 72 Proprietary Fire Alarm System 142
NFPA 72 Proprietary Protective Signaling Systems 147
NFPA 72 Remote Station Protective Signaling
System 146
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
NFPA Standard 142
nonpower-limited wiring 32
nonresettable power 12, 15, 30
current 30
maximum current 15
Normal 109
normal display 55
Notification Appliance Circuit 12, 15, 29, 67
Class A 35
Noun
list 65
multiple entries 66
Noun/Adjective 63, 65
O
Operating Instructions 108
Operation
alarm 111
disable/enable 114
hazard condition 113
medical alert 113
normal 109
process monitor 113
supervisory 112
trouble 110
waterflow 114
Option Modules 79
option modules 18
installation 34, 36
P
PAS 115
see also Positive Alarm Sequence 62
PAS timer 74
Password 57
change 103
Maintenance Level 2 57, 104
Master Level 1 57
Phone Number 90
piezo 17
alarm 17
maintenance 17
see also sounder 14
supervisory 17
trouble 17
polarity reversal circuit
see also Transmitter module 37
Positive Alarm Sequence 62, 115
power 15, 26, 30
primary 26
secondary
155
Index
see also battery 26
power supply calculations 133
power-limited wiring 32
Power-up
first time 56
Pre-signal 62
function 115
Pre-signal Delay timer 74
Pre-signal timer 74
Primary Phone 87
Process Monitor 113
Program
clear 103
program keys
see also Key Panel 16
Programming 55
autoprogramming 55
exiting 56
Level 1 56
Level 2 56
manual 55
Master Level 1 58
Programming Levels 56
Programming Screens 56
Proprietary Yes
see also Remote Upload 130
PS-Tools 19
R
Read Status 55, 118
annunciators 124, 125
exiting 56
history 122
input zones 119
NAC 119
Print 122
relay 120
Real-Time Clock 114
Recall/Increment Function 66
Receivers 128
Relay 71
Form-C 71
programming 72
relay 12, 17, 30
contact rating 15, 30
Remote Download 129
Remote Programming 55
remote station service 37
REN
see also Ringer Equivalence Number 20
156
Reporting Enable 88
Reset 14, 16, 108
resettable power 12, 15, 30
current 30
maximum current 15
reverse polarity circuit
see also Transmitter module 18
Ring Count 100
Ringer Equivalence Number 20
S
Secondary Phone 87
Secret Code 131
Security Features 131
Service Terminal 99
Silence Inhibit 71, 116
Silenceable
NAC 70
silenceable circuits
synchronized signals 70
sounder 14, 17
strobes 14, 70
Style B 15, 27
see also Class B 13
Style D 18, 27, 35
Style Y 15
see also Class B 13
Style Z 18, 35
subscreen 56
supervision
Transmitter option module placement 36
Supervisory 12, 112
supervisory
piezo pulse rate 17
supervisory relay 30
contact rating 15
synchronization 69
synchronized 69
synchronized signals 69
and silenceable circuits 70
system current calculations 134
System Setup 73
T
Telephone Circuitry 20
Telephone Company
Rights and Warnings 21
telephone line 33
Terminal 100
Test Time Interval 89, 90
Time setting 77
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Index
Time-Date
Maintenance Level 107
Time-Date setting 73, 77
Time-out 131
Timers 73
Transmittal Priorities 127
Transmitter Module 18
Transmitter module
operation 37
specifications 37
transmitter module 37
Transmitter option module
placement supervision 36
Trouble 110
trouble
piezo pulse rate 17
Trouble Call Limit 99
trouble call limit 55
Trouble Input
Auxiliary 16
trouble relay 12, 30
contact rating 15
fail-safe 30
Trouble Reminder 73, 116
two stage operation 69
Type
zone 60
U
UL
wiring requirements 32
Upload/Download 129
V
Verification
zone 61
View Events 101
W
Walktest 102
audible 102
Maintenance Level 106
operation 117
silent 102
Waterflow Delay timer 74, 75
Waterflow Retard Timer 116
Wire Requirements 150
wiring
CAC-5X 35
Class A Converter Module 35
Class A IDC 35
Class A NAC 35
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
combination waterflow/supervisory 28
IDC 27
NAC 29
nonpower-limited 32
power-limited 32
UL requirements 32
Z
Zone
type 60
verification 61
Zone Setup
Maintenance Level 105
157
Notes
158
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Limited Warranty
Honeywell International Inc. warrants products manufactured by it
to be free from defects in materials and workmanship for eighteen
(18) months from the date of manufacture, under normal use and
service. Products are date stamped at time of manufacture. The sole
and exclusive obligation of Honeywell International Inc. is to repair
or replace, at its option, free of charge for parts and labor, any part
that is defective in materials or workmanship under normal use and
service. All returns for credit are subject to inspection and testing at
the factory before actual determination is made to allow credit.
Honeywell International Inc. does not warrant products not
manufactured by it, but assigns to the purchaser any warranty
extended by the manufacturer of such products. This warranty is void
if the product is altered or repaired by anyone other than Honeywell
International Inc. or as expressly authorized by Honeywell
International Inc. in writing, or is serviced by anyone other than
Honeywell International Inc. or its authorized distributors. This
warranty is also void if there is a failure to maintain the products and
systems in which they operate in a proper and workable manner. In
case of defect, secure a Return Material Authorization form from our
Return Authorization Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products.
Honeywell
International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases
provide the protection for which they are installed or intended. Buyer
acknowledges that Honeywell International Inc., is not an insurer
and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS
BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC.
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY,
DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF
THE USE OF, OR INABILITY TO USE HONEYWELL
INTERNATIONAL INC.’S PRODUCTS.
FURTHERMORE,
HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE
COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL
OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by Honeywell International Inc. No increase or
alteration, written or verbal, of the obligation of this warranty is
authorized.
Warn-HL-05-2007.fm
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising