FIRE - City of Daytona Beach
CITY OF DAYTONA BEACH
DEVELOPMENT SERVICES DEPARTMENT
PERMIT & LICENSING DIVISION
BUILDING PERMIT
PERMIT TYPE:
FIRE
PERMIT NUMBER: C1503-083
ALARM
job address:
2461 N Atlantic Av
PARCEL/TAX ID NO: 25143201120010
New fire alarm for Marshalls #228
SUBDIVISION:
APPLICATION DATE
03/19/2015
APPROVAL DATE
03/23/2015
PERMIT/ISSUE DATE
03/26/2015
LOT:
BLOCK: 01-12
CONSTRUCTION TYPE:
CONTACT INFORMATION
Owner:
G&l VII BELLAIR PLAZA LLC
Mailing Addr:
Applicant:
Phone:
220 E 42ND ST NEW YORK NY 10017
Fax:
Seminole Safety Systems Inc (E
Mailing Addr:
Phone:
Casselberry FL
Fax:
Contractor Seminole Safety Systems Inc (E
Phone:
Mailing Addr:
Fax:
FEES
CONDITIONS
(407) 830-5330
Casselberry FL
(407) 830-5330
ESTIMATED VALUATION
FEES
PAID
AMOUNT DUE
$15,500.00
$234.56
$234.56
$0.00
This permit is issued pursuant to the attached conditions. Failure to comply may result in suspension or revocation of
this permit or other penalty. Permit expires 180 days from date issued unless otherwise noted or governed by law.
INSPECTIONS
Inspection requests made before 9pm can be scheduled for next business day.
By Phone: 386-671-8140, option 3. Permit number and 3-digit inspection code required.
By Website: www.codb.us, click ePermits link then Permit Seach to locate permit and schedule.
AGREEMENT
The Applicant agrees to comply with Municipal Ordinances and with the conditions of this permit; understands that
the issuance of the permit creates no legal liability, expressed or implied, of the Department, Municipality, Agency, or
Inspector; and certifies that all of the above information is accurate.
Signal
/>^?
Date
File Copy
~JtL3&jZA.
The CITY OF DAYTONA BEACH
Permits & Licensing Division - City Hall - Room 127
301 S Ridgewood Ave, Daytona Beach Florida
Phone: 386-671-8178
Fax: 386-671-8149
INVOICE
Mail To: PO Box 2451
Daytona Beach, FL 32115-2451
ro
•&.
PERMIT TYPE:
FIRE
'ARCEI/lAX ID NO: 25143201120010
PERMIT NO: C1503-083
O)
Z
ALARM
>
applicant:
Seminole Safety Systems Inc (E
March 25,2015
•-*
Q)
2461 N Atlantic Av
3
i-h
DAYTONA BEACH, FL 32118
GL Account
Fee Description
Amount Due
FIRE
FIRE ALARM SYSTEMS
160-322003
104.05
160-322001
120.10
160-341325
10.41
INSPECTION FEES
REQUIRED INSPECTIONS
MISCELLANEOUS FEES
TECHNOLOGY SURCHARGE-FR
TOTAL FEES DUE
234.56
PAID
MAR 26 2015
Position 3
The City of Daytona Beach
Printed: 3/25/2015 by MC1
File Copy
>
<
oSl
Permit and T ippnsinp" Division
Current Code FFPC 2010
City of Daytona Beach
Phone (386) 671-8140
Fax(386) 671-8149
Post Office Box 2451, Daytona Beach, Florida 32115-2451
FIRE PERMIT APPLICATION
P££PVED
Parcel No.
Date _
Job Address
Permit No. C (DOJ " C>&3
25143201120010
Job Name Marshalls #228
2461 North Atlantic Ave
Owner The TJX ComPanies
Address
Phone
Cjly
770 Cochituate Rd
Contractor Seminole Safety Systems, Inc
Address 40 Cotillion Ct
Contractors License No.
Framingham
Statc MA Zip
/in 01701
Phone 407-830-5330
Fax 407*260-8374
city Casselberry
State FL_ zip 32707
EF00QQ018
Email rick@seminolesafety.com
Designer
Address
Improvement Type:
0New •Addition
QRcpair ^Renovation [^Replacement OTemporary
•Commercial
Total Valuation:
Type of Work:
Parent Permit
$15,500.00
0Fire Alarm
I [Residential
Building Use: Retail
I iFire Suppression
| lOther
Fire Suppression Type: QClean Agent QWet Chemical QSprinkler/Standpipe ^Underground Main* ON/A
No. of Sprinkler Heads:
No. of Hydrants:
Construction Type
No. of Pumps:
Occupancy
Total Sq. Ft.
Units
Floors
Description of Work:
New Fire Alarm
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction.
kAll installations must adhere to the DRC approved site plans. If a water main tap is required, determination of
public or private water main is required. Contact the Water Distribution Division at (386) 671-8530 for
scheduling of taps to any City owned water main.
Print Applicant's Name
FAILURE TO COMPLY WITH THE MECHANIC'S
Applicant's Signature
PAYING TWICE FOR BUILDING IMPROVEMENTS
LIEN LAW CAN RESULT IN PROPERTY OWNER
INTELLIKNIGHT FIRE ALARM CONTROL PANEL
SILENT
KNIGHT
by Honeywell
IntelliKnight® Model 5700
Single Loop Addressable
Fire Alarm Control System
The affordable addressable fire
alarm control panel solution.
IntelliKnight Model 5700 is a class leading single loop addressable fire alarm control/communicator system.
5700 provides you with the revolutionary value and performance of addressable sensing technology combined
with exclusive, built-in digital communication, distributed intelligent power, that includes an easy to use interface.
Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from
Silent Knight.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1-800-328-0103.
Description
The basic IntelliKnight 5700 system can be enhanced by
adding modules such as 5860 remote annunciator, 5824
serial/parallel printer interface module (for printing
system reports), and 5496 intelligent power module.
5700 supports SD or SK devices. 5700 also features a
powerful built-in dual line fire communicator that allows
for reporting of all system activity to a remote monitoring
location.
Features
• Built-in support for up to 50 SK detectors and 50 SK
modules creating a total point capacity of 100 points
• Built in support for up to 50 SD devices
• Up to 125 zones and 125 output groups
• Uses standard wire—no shielded or twisted pair
required
• Built-in digital communicator
• Central station reporting by point or by zone
• Supports Class B (Style 4) and Class A (Style 6 or 7)
configuration for SLC
• Drift compensation
• 13 pre-programmed output cadences (including ANSI3.41) and 4 programmable outputs
• Notification circuits configurable as 1 Class A (Style Z)
or 2 Class B (Style Y), or auxiliary power for resettable,
constant, or door holder power
• Built-in synchronization for AMSECO, Gentex®,
Faraday, System Sensor® and Wheelock® appliances
• Built-in annunciator with 80-character LCD display
• RS-485 bus provides communication to system
Model 5700
• Improvements in SKSS deliver five times faster
upload/downloads
• Built-in RS-232 interface for programming via PC
• Built-in Form C trouble relay rated at 2.5A at 27.4
VDC
• Programmable date setting for Daylight Saving
Time
Compatibility
The 5700 signal line circuit (SLC) supports multiple
device types of the same protocol:
SK
REVIEWED FOR CODE COMPLIANCE
Ycu
cannot mix SD aJ$SKSfi($, devices on a FACP.
accessories
• Upload or download programming, event history, or
detector status onsite or from a remote location using
a PC and 5660 Silent Knight Software Suite (SKSS)
• Two built-in Form C programmable relays rated at 2.5A
at 27.4 VDC
FILE COPY
city ofpmmmiM beach
©iiU14 Honeywell International Inc.
INTELLIKNIGHT FIRE ALARM CONTROL PANEL
Model 5700
Fire Alarm Control Panel
IIU
WH«l»H
Specifications
S-BUS Accessories
Electrical
Primary AC: 120 VAC, 60 Hz, 1.5A
Total Accessory Load: 2.5A @ 27.4 VDC
5860/R Remote Fire Annunciator
Notification Power: 2.5A @ 27.4 VDC,
power-limited
Standby Current: 200 mA
Features the same 80 character backlit LCD
display keypad and firefighter's key switch
as the 5700. The system can be fully
programmed and operated from any 5860.
5860 is gray and 5860R is red.
Alarm Current: 365 mA
Notification/Aux Power Circuits:
2.5A @ 27.4 VDC per circuit,
power-limited
Battery Charging Capacity: 7.0-35.0 AH
Battery Size: 7 AH max. allowed in FACP
cabinet. Larger capacity batteries can be
5496 Intelligent Power Module
A 6 amp notification power expander that
provides four additional power-limited
notification appliance circuit outputs.
5880 LED/IO Module
5670 Silent Knight Software Suite
End-user facility management software
allows viewing of detector status and event
history via modem or direct connection.
RBB
Remote Battery Box Accessory Cabinet. Use
if backup batteries are too large to fit into
FACP cabinet. Dimensions:
16" Wx 10"Hx6"D
(406 mm W x 254 mm H x 152 mm D
SK-SCK
Seismic Compliance Kit.
housed in an RBB accessory cabinet.
Features 40 LED outputs, 8 normally open
SD505-DTS-K
Physical
dry contact inputs and one piezo output.
Remote test switch that provides remote key
Dimensions:
5865-3 and 5865-4
12.75" Wx 15.2" Hx 3.4" D
Remote LED Annunciator
(32.39 W x 38.42 H x 8.57 D cm)
Features 30 Programmable LED (15 red and
15 yellow) outputs and a piezo sounder. The
Weight: 11.5 lbs. (5.2 kg)
5865-4 adds a silence and reset switch to
Color: Red
the package.
Telephone Requirements:
FCC Part 15 and Part 68 approved
Type of Jack: RJ31X (two required)
5883 Relay Board
Features 10 general purpose Form C relays.
Listings
5824 Serial/Parallel Printer
NFPA 13, NFPA 15, NFPA 16, NFPA70, &
NFPA 72: Central Station; Remote
Interface Module
Provides one parallel and one RS-232 serial
port for connecting a printer to 5808. Use to
print a real-time log of system events,
detector status reports, and event history.
Interfaces with building control system.
Signalling; Local Protective Signalling
Systems; Auxiliary Protected Premises Unit;
& Water Deluge Releasing Service. Suitable
for automatic, manual, waterflow, sprinkler
supervisory (DACT non-coded) signalling
Used with 5880 module.
services.
Miscellaneous Accessories
Other Approvals: UL Listed;
5660 Silent Knight Software Suite
CSFM 7170-0559: 144; MEA429-92-E Vol.
XVI; OSHPD (CA) OSP-0065-10
SILENT
operated test function and annunciation of
detector alarm with SD505-DUCTR.
SP-TR
Small panel trim ring. Use to flush mount the
panel. 16.975" H x 14.630" W.
SD and SK Devices
See the data sheets listed below for a
complete listing of the SD and SK devices.
53624
SD Devices data sheet
53623
SK Devices data sheet
User-friendly Windows software for remote
programming of 5700s using a PC. Upload
and view panel account information, event
history, and detector status.
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all
KNIGHT specific applications or anticipate all requirements. All specifications are subject
to change without notice. For more information, contact Silent Knight 12
Clintonville Road, Northford, CT 06472-1610 Phone: (800) 328-0103,
by Honeywell
Fax: (203) 484-7118. For Technical Support, Please call 800-446-6444.
www.silentknight.com
Assembled In America
FIRE SYSTEM ACCESSORY
T
5496 Intelligent
SILENT
KNIGHT
by Honeywell
Power Module
A dynamic combination of power and
intelligence for your notification
expansion needs.
The Model 5496 Intelligent Power Module by Silent Knight is the most-powerful and cost-effective power supply
available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for
appliances from System Sensor®, Gentex®, Faraday, AMSECO and Wheelock® —what you need to drive
power-hungry components like ADA notification appliances. The 5496's advanced microprocessor design is
years ahead ofthe competition. Its switch mode power supply design is up to 50% more efficient than
competitive linear mode power supplies.
For the most sophisticated and cost-effective notification power supply available, you need Model 5496. Call
Silent Knight today for more information at 1-800-328-0103.
power
Model 5496
Intelligent Power Module
The model 5496 is a 6 amp notification
power expander that provides its own
AC power connection, battery charging
circuit, and backup battery for use with
fire and security controls such as the
IntelliKnight Model 5808 Fire Control
/Communicator. The 5496 is the cost-
effective solution for powering
notification appliances required by the
Americans with Disabilities Act (ADA).
The 5496 has built-in ANSI cadence
pattern, which can upgrade older
control panels that lack cadence
capability. The Output circuits can be
programmed as Notification Appliance
Circuits, or as Auxiliary Power
(configurable for, constant, resettable,
or door holder power).
Features
• UL Listed for 6 amps of notification
power
• Power supply's advanced switch
mode design reduces damaging
heat and manages power up to 50%
more efficiently than other systems
• Built-in synchronization for
appliances from AMSECO, Gentex®,
Faraday, System Sensor®, and
Wheelock®
• 3 amps per output circuit
•
Ground fault detector
•
Communicates to the FACP via 4-
wire SBUS (wire runs up to 6000 ft)
• AC loss delay option shuts off power
to non-essential high-current
accessories like magnetic door
holders
• Lightweight design adds to ease of
installation and reduces shipping
costs
• UL 864,1481 & 1971 listed
• ANSI Cadence pattern output
capability built-in
Specifications
AC Input: 120 VAC at 2.7 A
Current:
Standby 40 mA
32° to 120° F(0°to49°C)
Dimensions:
Notiflcation/Aux.Power circuits: 4
Output configuration:
- 2 Class A (Style Z)
- 4 Class B (Style Y) (1 Class A & 2
Class B)
Amps per output circuit:
3.0 (6.0 amps total)
Notification circuit output:
• Four power-limited notification
outputs; 2 Class A or 4 Class B, or 1
20.4 to 27.3 VDC, 3.0 amps each,
4.7k EOL resistor required on each
Class A and 2 Class B
Ambient Temp.:
Alarm 160 mA
• 24 VDC filtered output voltage
• NACs are programmable as
Notification Appliance Circuits, or as
auxiliary power to be used as
constant, resettable, or door holder
5496 Intelligent Power Module
Output: 24 VDC at 6 amps
Class B circuit
Battery charging capacity: 35.0 AH
12.25" Wx 16" Hx3"D
(30.88 Wx 40.64 H x7.62 D cm)
Listings:
UL
CSFM
MEA 429-92-E vol. XIV
Compatible FACPs
•
•
•
•
IntelliKnight 5700
IntelliKnight 5808
IntelliKnight 5820XL
IntelliKnight 5820XL-EVS
FIRE SYSTEM ACCESSORY
Firepower 5496
Distributed Power Module
Engineering Specifications
The contractor shall supply a power module compatible with the Silent Knight FACP. The power module must
have 6.0 amps of output power. The power module shall connect to the main FACP via an RS 485 system bus
(SBUS). The Outputs shall be programmable as Notification Appliance Circuits, or as Auxiliary Power
(configurable for, constant, resettable, or door holder power). The power module shall have four separate
outputs.
The power module RS 485 bus shall be optically isolated providing ground loop isolation and transient
protection.
4 Outputs Programmable
as Notification Appliance Circuits,
or as Auxiliary Power
SBUS Communication
Output 1
To a Compatible
Silent Knight FACP
Output 2
Output 3
Output 4
Auxiliary Power Can Be
Programmed To Be Constant,
Resettable, or Door Holder Power
This document is not intended to be used for installation purposes. We try
SILENT
to keep our product information up-to-date and accurate. We cannot cover
KNIGHT all specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact
by Honeywel
Silent Knight 12 Clintonville Road, Northford, CT 06472-1610
Phone: (800) 328-0103, Fax: (203) 484-7118. For Technical Support,
Please call 800-446-6444. www.silentknight.com
MADE IN AMERICA
FORM# 350387 Rev E
@2Q1 g Honeywel| international Inc.
INTELLIKNIGHT ACCESSORY
SILENT
KNIGHT
by Honeywell
5860 Remote Annunciator
Bring the power to control an IntelliKnight
fire alarm control panel to every
area within your facility
Now you can operate and program your IntelliKnight system from up to twelve locations throughout your facility.
The 5860 remote annunciator provides the same advanced, easy-to-use interface found on the IntelliKnight
panel's built-in annunciator. The 80-character display and ergonomically designed keypad allow for simple and
error-free system operation. All operations—including reset, silence, detector status checking, fire drill, and
programming—are identical.
Access to the system is through a firefighter's key or an access code. For security, a special installation code is
needed for programming functions. The 5860 connects to the IntelliKnight panel via the RS-485 system bus.
Wire runs can be up to 6000 feet from the panel.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1-800-328-0103.
Description
Features include an 80-character
backlit LCD providing easy-tounderstand system messages. The
annunciator is ergonomically
designed with over-sized buttons
for the most frequently used
features, like Reset and Silence.
In addition to status messages
displayed on the LCD, there are
five LEDs for alarm, supervisory,
trouble, silence, and AC power
status.
The annunciator is available in gray
to match virtually any decor and
red for applications where the
annunciator must stand out. The
annunciator enclosure can be
surface or flush mounted. A trim
ring kit is available for surface
mounting.
• Available in red or light gray
• Support for simultaneous use of
multiple 5860s
• RS-485 interface to panel
• Operation and appearance is
identical to 5860 built-in
annunciator
• On-board piezo sounder audibly
indicates alarms, troubles, and
supervisories
• Five status LEDs for alarm,
supervisory, trouble, silence and
AC power conditions
• Wiring lengths up to 6000 ft. from
the FACP (depending on wire
gauge and number of devices on
SBUS)
• UL listed, complies with NFPA 72
• CSFM approved
Electrical Specifications
Operating Voltage: 24 VDC
Standby Current: 20 mA max
Features
Alarm Current: 25 mA
• 80-character backlit LCD display
(4 lines with 20 characters on
each line)
Wiring Distance: 6,000 max. from
FACP (depending on wire gauge
• Tactile and audible feedback
SBUS)
• Accepts user codes or fire
fighter's key
• Larger keypad buttons for system
reset and silence
• Install up to twelve 5860s per
5820XL/EVS or 5808 system
• Install up to eight 5860s per 5700
system
and number of devices on the
Mechanical Specifications
Physical 9.1" W x 7.4" H x 1.5" D
(23.1 Wx 18.8 Hx 3.8 D cm)
5860
Environmental
Operating Temperature: 32°F 120°F(0°C-49°C)
Humidity: 10% - 93% noncondensing
Compatibility
The 5860 is compatible with the
following FACP's:
• 5820XL Addressable Fire Control
Panel
• 5820XL-EVS Fire Control Panel
with Emergency Voice System
• 5808 Addressable Fire Control
Panel
• 5700 Addressable Fire Control
Panel
Shipping Weight: 2.8 lbs (1.3 kg)
Color
5860R: Red
5860: Gray
PN 350224 Rev G
© 2014 Honeywell International Inc
INJELLiKNIGHT ACCESSORY
5860 Remote Annunciator
Engineering Specifications
The main control must have a built-in annunciator and must support up to 12 remote annunciators. Remote
annunciators shall have the same control and display layout so as to match the appearance of the built-in
annunciator. Remote annunciators shall be available in two colors, red or light gray.
Remote annunciators shall have identical functionality and operation as the built-in annunciator. All annunciators
must have an 80-character LCD display and must feature five LEDs for: General Alarm, Supervisory, System
Trouble, System Silence, and System Power.
All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a
travel of .040 inches. No membrane style buttons will be permissible.
The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator
keypad or by using a firefighter's key. The annunciator must have two levels of user codes that will limit the
operating system programming to authorized individuals. The control panel must allow all annunciators to
accommodate multiple user input simultaneously.
Wire Runs Up to 6000 Feet From FACP
5860
5860
• Up to 12 5860s Per IFP-100/ECS or
IFP-1000/ECS System
• Up to Eight 5860s Per 5700 System
Compatible IntelliKnight FACP
Listings
Ordering Information
NFPA 72; UL Listed;
CSFM 7170-0559: 135;
MEA429-92-E Vol. IX;
5860R
Remote Annunicator four line LCD
annunciator with 20 characters per line.
Red
FM Approved
5860
Remote Annunciator four line LCD
annunciator with 20 characters per line.
Gray
Accessories
5860TR
Red Trim Ring for surface mounting
5860TG
Gray Trim Ring for surface mounting
This document is not intended to be used for installation purposes. We try to
SILENT
keep our product information up-to-date and accurate. We cannot cover all
KNIGHT
by Honeywell
specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact Silent Knight
12 Clintonville Road, Northford, CT 06472-1610. Phone: (800) 328-0103,
Fax: (203) 484-7118. For Technical Support, Please call 800-446-6444.
www.silentknight.com
Assembled in America
INTELLIKNIGHT ACCESSORY
SD500-PS and SD500-PSDA
Addressable Pull-Station
IntelliKnight's addressable pull stations
combine fast response with pin-point
location ID.
The SD500-PS and SD500-PSDA are a single action or dual action addressable manual fire alarm pull station
for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SD500-PS/PSDA
provides a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes
each manual pull station by its specific address saving precious seconds in determining the location of an alarm.
The SD500-PS/PSDA mounts to a single gang box and features a rugged metal construction that lasts and
lasts.
Combine all this with the features you've come to expect from Silent Knight - easy installation and stable
operation - and it adds up to a flexible solution for all your fire protection needs.
Model SD500-PS &
• Extremely easy to operate
SD500-PSDA
• Corrosion-resistant gold-plated
Addressable Pull
Station
The SD500-PS is a single action
addressable fire pull station, and
the SD500--PSDA is a dual action
addressable fire pull station. The
SD500-PS/PSDA feature rugged
metal construction A terminal strip
on back of the pull station allows
interconnection of the pull station to
the SLC of an IntelliKnight control
panel. The SD500-PS/PSDA is
designed for indoor use in nonexplosive environments. The
normally open initiating point
contacts are gold-plated to avoid
risk of corrosion. The SD500-
PS/PSDA has been tested by UL
for compliance to the requirements
contacts.
•
Reflective label makes it easier
4
PULL 4
to locate in low light
Operation
The SD500-PS/PSDA single action
pull stations are operated by a pull
on the front pull cover of the
station. A plunger switch, wired to
>
a self contained addressable
module, is released as the pull
station opens to initiate the alarm.
Once operated, the cover hangs
down and can be seen up to 100
feet away. The pull station is reset
by returning the front cover to the
normal upright position and
relocking the station with a reset
key. The reset keys are the same
keys used on Silent Knight
Bfv
FIRE
)
ALARM
1$ KNIGHT
enclosures.
of the Americans with Disabilities
The SD500-PS/PSDA includes a
ACT (ADA).
status LED which blinks, indicating
Features
that the addressable module is
Ambient Temperature:
communicating with the loop. The
status LED lights continuously
during an alarm. A dip switch on
Mounting:
•
UL Listed
•
CSFM listed
• ADA compliant
• Key reset (Same key as Silent
Knight enclosures)
•
Surface mount back box
available
• Terminals - accept up to 14
gauge wire
the addressable module is used to
SD500-PS
32°F to 120°F
(0°C to 49°C)
Single gang
box -
Optional Red Surface Mount Box PS-SMBB
set the unique address.
Specifications
Operating Voltage:
24VDC
Standby Current:
.55mA
Alarm Current:
.55mA
SILENT
KNIGHT
INTELLIKNIGHT ACCESSORY
SD500-PS and SD500-PSDA
Addressable Pull-Station
Engineering Specifications
Manual pull station shall be addressable Module SD500-PS/SD500-PSDA. Equipment shall be made of 14
gauge C.R.S.(Cold Rolled Steel), painted with a red enamel . The label shall contain the words Fire Alarm and
be made of a reflective material embossed text 3/8 inches tall. Operating instruction shall be clearly visible on
the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the
key shall match the control panel.
Manual station shall contain four terminal blocks with two connected to the addressable module and two connect
to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip
switch settings .
Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the
American Disabilities Act.
FACP
- *.
Wiring
H h
Mounting to Optional
Mounting to Single
Gang Electrical Box
Surface Mount Box
SD500-PSDA
Installing SD500-LK
Electrical Box must be
atieail 1-112" Deep
Dimensions
SILENT
KNIGHT
7550 Meridian Circle, Maple Grove, MN 55369-4927
800-446-6444 or in Minnesota 763-493-6435
MADE IN AMERICA
FORM# 350342, Rev. 09/03
FAX: 763-493-6475
World Wide Web: http://www.silentknight.com
Copyright © 2003 Silent Knight
INTELLIKNIGHT ACCESSORY
SILENT
SD500-AIM & SD500-MIM
KNIGHT
Addressable Input Modules
by Honeywell
IntelliKnight's addressable contact
monitor modules combine fast
response with pinpoint location ID. A
combination that saves lives and property.
The SD500-AIM and SD500-MIM are addressable input modules for use with Silent Knight IntelliKnight fire
alarm control panels (FACP). The SD500-AIM and SD500-MIM are designed to be used with pull stations, water
flow switches, and other applications requiring dry contact alarm initiation devices.
The SD500-AIM addressable input module mounts to a 4"-square box. The SD500-MIM mini input module fits
inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister,
they monitor for alarm contact closures and for open circuit wiring fault conditions.
The SD500-AIM and SD500-MIM offer a compact design for adaptability and pleasing aesthetics as well as easy
installation and stable operation—a flexible solution for all your fire protection needs.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1-800-328-0103.
Description
The SD500-AIM and SD500-MIM are
addressable input modules for use with
the Intelliknight fire alarm control
panels (FACPs). The SD500-AIM
addressable input module mounts to a
4"-square box. The SD500-MIM mini
input module fits inside a single gang
box. Both input modules are designed
to be used with pull stations, water flow
switches, and other applications
requiring dry contact alarm initiation
• DIP switch programmable for fast
installation
• Up to 2500 ft wiring distance from
either input module to contact
• Use up to 14 gauge wire
• UL listed
Electrical Specifications
Standby Current: 0.55 mA
Alarm Current: 23 mA max for one
device; 46 mA max for two devices;
0.55 mA for each additional device
devices.
These modules are supervised, single
input contact monitors. Using an EOL
resistor, they monitor for alarm contact
closures and for open circuit wiring
Line Resistance: 50z max
Mechanical Specifications
SD500-AIM Physical Description
Dimensions:
fault conditions. If a fault occurs in the
4.9" Wx 4.9" Hx1" D
wiring, the module alerts the FACP.
Each addressable input module is
programmed with a unique signal line
circuit (SLC) loop address.
(12.4 Wx 12.4 Hx 2.5 D cm)
Weight: 3.6 oz (120.1 g)
Color: Ivory cover plate
SD500-MIM Physical Description
Features
Dimensions:
• Single contact monitor
1.5"Wx2.5"Hx0.7"D
• SD500-AIM supports Class A (Style
D) or Class B (Style B) contact
monitor wiring
• SD500-MIM support for Class B
(Style B) contact monitor wiring
• Attractive ivory cover plate with the
SD500-AIM
• Small and lightweight size allows for
flexible mounting options with the
SD500-MIM
(3.8 Wx6.4Hx1.8Dcm)
Weight: 1.6 oz (45.4 g)
Environmental
Operating Temperature:
32oF-120°F(0°C-49oC)
Humidity:
10% - 93% non-condensing
SD500-MIM
Approvals
NFPA 71 & NFPA 72
UL864
CSFM 7300-0559: 132
MEA 429-92-E Vol. IX
FM Approved for use with the 5820XL
INTELLIKNIGHT ACCESSORY
SD500-AIM & SD500-MIM
Addressable Input Modules
Engineering Specifications
The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight
SD500-AIM or SD500-MIM. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight
FACPs.
The SD500-MIM shall fit inside a single gang electrical box. The SD500-AIM shall be supplied with a plastic
cover and shall be suitable for mounting to a 4"-square or double gang electrical box. The SD500-AIM
addressable input module must provide a monitor LED that is visible from outside the cover plate
Compatible FACPs
Ordering Information
5820XL
SD500-AIM Input Module
Addressable input module with ivory
cover plate.
5820XL-EVS
5808
SD500-MIM Input Module
Addressable mini input module.
5700
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all
KNIGHT specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact Silent Knight
by Honeywell
12 Clintonville Road, Northford, CT 06472-1610.Phone: (800) 328-0103
Fax: (763) 493-6475 For Technical Support, Please call 800-446-6444.
.www.silentknight.com
SILENT
MADE IN AMERICA
FORM# 350231 Rev. F
©2013 Honeywell International Inc
INTELLIKNIGHT ACCESSORY
Model SD505-DUCTR
SILENT
KNIGHT
and
SD505-DTS-K
by Honeywell
Detect smoke in air handling systems and
prevent re-circulation with Silent Knight's
addressable duct smoke detector
The SD505-DUCTR addressable duct smoke detector detects smoke and products of combustion present in air
moving through an HVAC air handling system. The SD505-DUCTR is a heavy duty metal housing with a
pre-installed SD505-APS photoelectric smoke detector and relay module. When smoke is detected in a duct, the
unit communicates the condition to the IntelliKnight control panel. The panel, in turn, depending on programming
and wiring, turns off fans, blowers, and other devices.
Now there's even more power and flexibility available to the IntelliKnight family of products. For more information
on this product or to locate your nearest source, please call 800-328-0103.
Model SD505-DUCTR
Analog Duct Smoke
Detector with Relay
Module
The Model SD505-DUCTR
Addressable Duct Smoke Detector
with Relay provides early detection
of smoke and products of
combustion present in air moving
through an HVAC duct to prevent
re-circulation of smoke into the air
Features
Two-wire connection to SLC
Detects and limits spread of smoke
LED alarm indication and
communication on sensor head
Rugged steel backbox with clear
plastic cover
Installation template included
No screens or filters to clean
Detector pre-installed
handling system. The SD505DUCTR is a heavy duty metal
housing with a pre-installed
SD505-APS Analog Photo Electric
Smoke Sensor and relay module.
3 standard tube lengths
When smoke is detected in a duct,
FM Approved
the unit communicates the
condition to the IntelliKnight FACP.
The built-in relay module, in turn,
UL listed, complies with NFPA 72
and 101
CSFM listed
MEA Approved 429-92-E, Vol 9
Specifications
Physical
turns off fans, blowers, and other
Dimensions: 2Va H x 9" L x VAT W
devices.
Weight: 3lbs
Operation
Air sampling is accomplished by
two tubes which protrude into the
duct. An exhaust tube of one
standard length (7.5") is provided
with the detector housing. Intake
sampling tubes (ordered
separately) are supplied in three
standard lengths. Duct mounting is
accomplished through a template
and 4 sheet metal screws
(provided).
SD505-DUCTR
SD505-APS Photoelectric Smoke
Electrical
Operating Voltage: 24 VDC
Alarm Relay Contact rating:
10A@24VDC;10A@ 115 VAC;
10A@240 VAC
Trouble Relay Contact Rating:
2.5A @ 30 VDC
Aux. Power Input Current:
20mA Standby, 62 mA Alarm
SLC Input Current: 0.5 mA
Max. SLS resistance: 50 Ohms
SD505-DTS-K
Environmental
Operating Temp: 32°F to 100°F
(0°C to 37°C)
Humidity: 10%-85% non-condensing
Other Ratings:
Air Velocity 300 - 4000 ft/min
Sampling Tubes:
SD505-T2
2.5ft sampling tube
SD505-T5
5ft sampling tube
SD505-T10
10ft sampling tube
IHTELtlKNIGHT ACCESSORY
Model SD505-DUCTR and SD505-DTS-K
Duct Smoke Detector with Relay and Remote Test Switch
Engineering Specifications
The air duct smoke detector shall be Silent Knight Model SD505-DUCTR and remote test switch shall be
SD505-DTS-K. The housing shall contain a Silent Knight model SD505-APS, Photoelectric Smoke Sensor.
The duct detector shall be of metal construction. Complete mechanical installation must be able to be performed
without removal of the detector cover. Terminal connections shall be screw type using a minimum of #6 screw.
FACP/5815XL
Connection
Class A (Style 6)
FACP/5815XL
Connection
DTS-K connection
.in
re;—
nil
Class B (Style 4)
This document is not intended to be used for installation purposes. We try to
SILENT
keep our product information up-to-date and accurate. We cannot cover all
KNIGHT specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact Silent Knight
by Honeywell
Zl i« .
•„ r? _. li _«_« j --r nr,7o 4„„ nu
/onn\ ooo rv-ino
12 Clintonville Road. Northford, CT 06472-1610 Phone:(800)328-0103,
Fax: (203) 484-7118. www.silentknight.com
MADE IN AMERICA
.
FORM# 350005 Rev B
' rniTu""~~Iii iZ*«Z,~t;r.n«i !„,-
Copynght © 2011 Honeywell International Inc.
yy
INTELLIKNIGHT ACCESSORY
SILENT
KNIGHT
Addressable Photoelectric
Smoke Detector
by Honeywell
Detect smoldering fires quickly and
get help fast with IntelliKnight®
photoelectric smoke detectors.
IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where
smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505-APS
photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds
are wasted in determining location of an alarm.
The SD505-APS compensates automatically for contamination in the environment. And detector testing is
simple—even from a remote site. Like other IntelliKnight detector models, the SD505-APS offers a low profile for
pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model
SD505-6AB, allowing complete application and placement flexibility. Combine all this with the features you've
come to expect from Silent Knight smoke detectors—easy installation, stable operation, RF/transient protection,
and vandal-resistant locking—and it adds up to a flexible solution for all your fire protection needs.
Model SD505-APS
Analog / Addressable
Photoelectric Type
Smoke Detector
The SD505-APS is particularly
suited to detecting dense smoke
typical of fires involving materials
such as soft furnishings, plastic,
foam or other similar materials
which tend to smolder and produce
large visible particles.
approximately every 15 seconds,
indicating that the head is
communicating with the loop. The
LED lights continuously during the
alarm period.
Features
• Low profile, 2 inches, including
without mechanical switches
The detector features automatic
Operation
The SD505-APS units made up of
an LED light source and a silicon
photo diode receiving element. In a
normal standby condition, the
receiving element receives no light
from the pulsing light source. In the
event or fire, smoke enters the
detector and light is reflected from
the smoke particles to the receiving
element.
The light received is converted into
an electronic signal. Under normal
conditions, the status LED blinks
•••••
• Simple and reliable addressing
• Automatic compensation for
compensation for contamination
and a simple detector calibration
test procedure that can be run from
the panel or remotely (using the
Windows™ based downloading
software).
•
base
sensor contamination
•
Built-in fire test feature
• Simple detector calibration
testing through the control panel
or remotely through a
Windows™ based computer
SD505-APS Smoke Detector
Specifications
Operating Voltage:
Current Consumption
Standby:
.55 mA
Alarm:
.55 mA
Ambient Temperature :32°Fto 120°F
software.
• Vandal-resistance locking
features
•
(0°C to 49°C)
Mounting:
Field cleanable
• UL listed, meets NFPA 72 Ch 7
requirements
• CSFM approved
• MEA approved
• FM Approved
17-41 VDC
4" Square, 4"
OCT, Single
gang mud ring
Relative Humidity:
85%
noncondensing
Air Velocity:
0 - 300 FPM
Compatible Bases:
(Sold Separately)
SD505-6AB
SD505-6IB
SD505-6RB
SD505-6SB
TNTELLIKNIGHT ACCESSORY
Model SD505-APS
Addressable Photoelectric
Smoke Detector
Engineering Specifications
The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector
Silent Knight SD505-APS. The combination detector head, and twist-lock base, shall be UL® listed compatible
with Silent Knight's IntelliKnight fire control panels.
The base shall permit direct interchange with Silent Knight SD505-AIS Ionization Smoke Detector, or SD505AHS Heat Detector. Base shall be the appropriate twist-lock base SD505-6AB.
The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the
flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch.
The calibration of the detector shall be capable of being selected and measured by the control panel without the
need for external test apparatus.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The
locking feature shall be field selectable as required.
The SD505-APS shall automatically perform a functional test of the detector. The test method shall simulate
effects of products of combustion in the chamber to ensure testing of detector circuits.
Diameter = 5-15/16"
Diameter = 3-15/16"
Height = 2 inches,
including base
Model SD505-6AB Detector Base
Model SD505-APS Detector Head
(front view)
(front view)
SILENT
This document is not intended to be used for installation purposes. We try
to keep our product information up-to-date and accurate. We cannot cover
KNIGHT all specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact Silent
by Honeywell
Knight 12 Clintonville Road, Northford, CT 06472-1610
Phone: (800) 328-0103, Fax: (203) 484-7118. www.silentknight.com
MADE IN AMERICA
FORM# 350225 Rev D
©2010 Honeywell International Inc.
HN Series
Effective October 2014
Technical Data TD001017EN
Supersedes May 2013
HS Series
ST Series
Exceder Strobe, Horn Strobe, and
Horn Notification Appliances
Description
The Wheelock Exceder Series of notification appliances
feature a sleek modern design that will please building owners
with reduced total cost of ownership. Installers will benefit from
its comprehensive feature list, including the most candela options
in one appliance, low current draw, no tools needed for setting
changes, voltage test points, 12/24 VDCoperation, universal
mounting base and multiple mounting options for both new and
retrofit construction.
The Wheelock Exceder Series incorporates high reliability and high
efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe
models feature an industry first of 8 candela settings on a single
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of a tool and are located behind the appliance to prevent tampering.
Wall models feature voltage test points to take readings with a
voltage meter for troubleshooting and AHJ inspection.
The Wheelock Exceder Series of wall and ceiling notification
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting base
can be pre-wired to allow full testing of circuit wiring before the
appliance is installed and the surface is finished. It comes complete
with a Contact Cover for protection against dirt, dust, paint and
damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre-wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while it
is on the UMB. When the Contact Cover is removed the circuit will
show an open until the appliance is installed. The UMB allows for
consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra
secure installation, while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
F:T«
Powering Business Worldwide
Technical Data TD001017EN
HN Series
Effective October 2014
HS Series
ST Series
• Environmentally friendly
Features
•
•
Sleek modern aesthetics
Low current draw
• Up to 9 models now in 1 appliance draw©
• Finger slide switches
• 12/24VDC on a single appliance
• Voltage test points
• Easy to remember model numbers
• Multiple voltages
© Patented
• 3 Audible settings
Note: All CAUTIONS and WARNINGS are identified by the symbol A. All
. 90, 95, 99 dB
warnings are printed in bold capital letters.
• Industry leading—8 candela settings on 1 device
• Wall: 15/1575/30/75/95/110/135/185
. Ceiling: 15/30/60/75/95/115/150/177
A
WARNING
PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION
INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING
THIS PRODUCT.VISIT WWW.C00PERN0TIFICATI0N.COM OR CONTACT
COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURETO COMPLY WITH ANY OFTHESE INSTRUCTIONS, CAUTIONS OR
WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION
AND/OR OPERATION OFTHESE PRODUCTS IN AN EMERGENCY SITUATION,
WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
General Notes
• Strobes are designed to flash at 1 flash per second minimum over
their "Regulated Voltage Range'.'
• All candela ratings represent minimum effective strobe intensity
based on UL Standard 1971.
• Series Exceder Strobe products are Listed under UL Standards
1971 and 464 for indoor use with a temperature range of 32°F to
120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) UL
Universal mouting base
- Ceiling and wall
464(85% UL 1971).
• Mounts to 5 backbox types: 1 gang, 2 gang, 4" square,
3.5" octal. &4" octal. (100mm for international customers)
Universal mounting base
•
Series Exceder horns are under UL Standard 464 for audible
signal appliances (Indoor use only).
Contact cover
Compatibility and requirements
• Synchronize using the Wheelock® Sync Modules or panels with
built-in Wheelock3 Patented Sync Protocol
• Compatible with UL "Regulated Voltage" using filtered VDC or
unfiltered VRMS input voltage
• Strobes produce 1 flash per second over the "Regulated
Voltage" range
Common base for wall and ceiling with 5 mounting options
Voltage test points for quick troubleshooting and easy spot
checking (wall models only)
Compliance
•
• ADA/NFPA/ANSI/OSHA
•
EATON www.eaton.com
UL 1971, UL 464, ULC, CSFM, FM
RoHS
Technical Data TD001017EN
HN Series
HS Series
Effective October 2014
ST Series
Table 1. Strobe Ratings per UL Standard 1971
UL Max Current©
12 VDC
24 VDC/24 FWR
Regulated Voltage
Model
Range VDC
15
15/75
30
ST
8.0-33.0
0.057
0.070
0.085
STC
8.0-33.0
0.061
60
—
0.103
0.08b
—
75
95
110
0.135
0.163
0.182
0.135
0.163
115
0.205
0.182
—
135
—
177
150
—
0.253
0.205
—
185
15
15/75
0.253
0.110
0.140
—
0.110
—
—
Table 2. Horn Strobe Ratings per UL 1971 & Anechoic at 24 VDC
UL Max Current© at Anechoic 99 dBA
24 VDC
Regulated Voltage
Range VDC
15
15/75
30
HS
8.0-33.0
0.082
0.095
0.102
HSC
8.0-33.0
0.082
Model
60
—
0.102
—
0.141
75
95
110
0.148
0.176
0.197
0.148
0.176
115
0.197
—
135
0.242
—
150
177
—
—
0.242
—
0.282
185
15
15/75
0.282
0.125
0.159
0.125
—
—
UL Max Current© at Anechoic 95 dBA
Regulated Voltage
Model
Range VDC
15
15/75
30
HS
8.0-33.0
0.073
0.083
0.087
HSC
8.0-33.0
0.073
—
60
—
0.087
0.128
75
95
no
0.139
0.163
0.186
0.139
0.163
115
—
0.186
—
150
135
0.230
—
0.230
—
185
15
15/75
0.282
0.122
0.153
177
—
0.272
—
0.122
—
UL Max Current© at Anechoic 90 dBA
12 VDC
24 VDC
Regulated Voltage
Model
Range VDC
15
15/75
30
HS
8.0-33.0
0.065
0.075
0.084
HSC
8.0-33.0
0.065
—
60
—
0.084
0.120
75
95
110
0.136
0.157
0.184
0.136
0.157
115
—
0.184
—
135
0.226
—
150
177
—
—
0.267
0.226
185
15
15/75
0.267
0.120
0.148
0.120
—
—
© UL max current rating is themaximum RMS current within thelisted voltage range (16-33 VDC for 24VDC units). For strobes theUL max current is usually at theminimum listed voltage (16 VDC for 24 VDC
units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24VDC units). For unfiltered ratings, see installation instructions.
Model Legend
Table 3. Horn Ratings per UL Anechoic
Regulated Voltage
Model
Range VDC
99 dB
95 dB
90 dB
HN
=
Horn
R
0.022
ST
=
Strobe
A
0.022
HS
=
Horn Strobe
AL
= Alert Lettering (strobes only)
= Ceiling Mount
N
= No Lettering (strobesonly)
=
HN
16-33.0
0.064
0.044
HNC
16-33.0
0.084
0.044
HN
8.0-17.5
0.047
0.026
0.017
C
HNC
8.0-17.5
0.047
0.026
0.017
W
Sync w/ DSM or
Strobe Candela
Red
White
Example 1: STRC = Strobe, Red, Ceiling Mount
Example 2: HSR = Horn Strobe, Red,Wall Mount
Example 3: HSW= Horn Strobe, White, Wall Mount
Table 4. Specification & Ordering Information
Model
=
= Agent Lettering (strobes only)
Wheelock Power
12/24
Supplies
VDCG Options
Mounting
Example 4: STW-AL = Strobe,White, Wall Mount, AlertLettering
Horn Strobes
HSR
15/1575/30/75/95/110/135/185
X
X
UMB®
HSW
15/1575/30/75/95/110/135/185
X
X
HSRC
15/30/60/75/95/115/150/177
X
X
HSWC
15/30/60/75/95/115/150/177
X
X
UMB®
UMB®
UMB®
Strobes
STR
15/1575/30/75/95/110/135/185
X
X
STW
15/1575/30/75/95/110/135/185
X
X
STRC
15/30/60/75/95/115/150/177
X
X
STWC
15/30/60/75/95/115/150/177
X
X
HNR
X
X
HNW
X
X
HNRC
X
X
HNWC
X
X
UMB®
UMB®
UMB®
UMB®
Horn
UMB®
UMB®
UMB®
UMB®
Example: HSR
Example: HSWC
© 12VDC models feature15 &15/75settings
© UMB = Universal Mounting Base
EATON www.eaton.com
HN Series
HS Series
ST Series
Technical Data TD001017EN
Effective October 2014
Architects and Engineers Specifications
The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances. Series ST Visual Strobe appliances and Series
HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the
Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective
Signaling}. All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity
supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall
incorporate voltage test points for easy voltage inspection.
The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage
Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design. Where multicandela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela
for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper
resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required
(e.g., ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed.
The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal
(Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance
wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any
notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall
result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same base among all horn,
strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24" H x
4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series HNC ceiling
shall have a diameter of 6.68" x 1.50" D.
When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies or other
manufacturer's panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during
operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1) flash per second
over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe
activation when used with Wheelock synchronization protocol.
Wall Appliances: UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS
Ceiling Appliances: UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS
Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper
Wheelock Inc., dba Cooper Notification standard terms and conditions.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Eaton
1000 Eaton Boulevard
Cleveland. OH 44122
United States
Eaton.com
Eaton
Cooper Notification
273 Branchport Ave.
Long Branch, NJ 07740
CooperNotification.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No.TD001017EN
Powering BusinessWorldwide
October 2014
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
ELK Sealed Lead Acid Battery
Two-Year Warranty
ELK Sealed Lead Acid Batteries are excellent for the following applications with regard to size, amp hour rating, and
proper terminal connections: battery backup (for access control systems, fire alarm systems, and security alarm
systems), electrically motorized vehicles, emergency lights, lighted exit signs, and uninterruptible power supplies.
12V, 8 Ah
ELK-1280
SPECIFICATIONS:
TO
\
Nominal Voltage
12 Volts
Rated Capacity
8 Ah (20 hour rate)
Length
5.94" (151 mm)
Width
2.56" (65 mm)
Height
3.98" (101 mm)
Weight (Approximate)
5.6 lbs (2.5 kg)
Terminals
F1 FastonTab(.187")
UL Recognized
Component
97% Recyclable
ELECTRICAL SPECIFICATIONS:
Capacity
'
20 hour rate (0.375A)
10 hour rate (0.71 A)
5 hour rate (1.27A)
1 hour rate (4.5A)
77T(25°C)
Dimensions(mm)
8Ah
Fl
7.1Ah
4 n
6.37Ah
...<
4.5Ah
e
Capacity affected
by Temperature
104°F(40°C)
77"F (25"C)
32*F(0°C)
5°F(-15°C)
(20 hour rate)
102%
100%
j^
85%
T
:
65%
Cycle:
Initial Charging Current less than 2.25A
Voltage 14.4V -15.0V at 770F(25"C)
Standby: Voltage 13.5V -13.8V at 77°F(25°C)
Charge Constant
Voltage
DischargeCharacteristics (2()T, 68*F)
\
no
\
\
\
,
127A 0.7
s,
\\
•,
\
\
\
t:
^
^
"N
Discharge Characteristics (0oC732"F.40oc/l(MuF)
V\
A 0.37 >A
2A
\
\
\
\
\
-1 SA
a
<-"«"
ireo
, I
•
3
5
10
(mini
20
7
5A
JO
W
I04T)
V\
LA _L_
37 5A . OA 22.5 A ISA
•\
W)
1
Discharge Time
2
3
5
(h)
10
20
30
1
1IHI5IMI
1mA)
III
1
15
111
(A)
1
Discharge Current
*l«
^SM mm
For more information, including details on recycling ELK batteries and MSDS for
this product, please visit www.elkproducts.com or call us at (828) 397-4200.
PRODUCTS
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising