Sigma CP-A
Sigma CP-A
Conventional Fire Control Panel
(KA11020M2, KA11040M2, KA11080M2)
Man-1138
Issue 08 May 2016
Contents
1. Introduction ......................................................................................................................... 4 2. Safety .................................................................................................................................. 4 4. Technical specification ........................................................................................................... 5 5. Control panel fascia............................................................................................................... 7 6. Connecting to the circuit board .............................................................................................. 8 7. Software revision number ...................................................................................................... 8 8. Detection zone wiring............................................................................................................ 9 9. Priority/Non-priority alarm settings......................................................................................... 9 10. Standard Sounder circuit wiring ........................................................................................... 9 11. Connection to remote control terminals .............................................................................. 10 12. Aux 24V DC supply ............................................................................................................ 10 13. Connection to relay contacts .............................................................................................. 10 14. Connection to Repeater panels........................................................................................... 11 15. Connection to Ancillary boards ........................................................................................... 12 16. Connection to 8 way Sounder boards ................................................................................. 12 17. Panel operation ................................................................................................................. 13 17.1 Normal condition ..................................................................................................................... 13 17.2 Fire condition (sounders set to priority alarm) ............................................................................ 13 17.3 Fire condition (sounders set to non-priority alarm)...................................................................... 13 17.4 Silence/sound alarms ............................................................................................................... 13 17.5 Reset ...................................................................................................................................... 13 17.6 Zone fault ............................................................................................................................... 13 17.7 Sounder fault .......................................................................................................................... 13 17.8 Power fault ............................................................................................................................. 13 17.9 System fault ............................................................................................................................ 13 17.10 Lamp test .............................................................................................................................. 13 17.11 Disablements ......................................................................................................................... 13 17.11.1 Disable zones...................................................................................................................... 14 17.11.2 Disable sounders .................................................................................................................................... 14 17.11.3 Activate delays ........................................................................................................................................ 14 17.11.4 Disable fault contact ............................................................................................................ 14 17.12 Test mode ............................................................................................................................. 14 18. Configuration options ................................................................................................................. 14 19. Watchdog reset switch ...................................................................................................... 17 20. Processor reset switch ....................................................................................................... 17 21. Internal indications – troubleshooting ................................................................................. 17 21.1 Mains fail ................................................................................................................................ 17 21.2 Batt fail ................................................................................................................................... 17 Man-1138_Sigma_CPA_Alarmsense_08
Page 2 of 22
21.3 CPU fault ................................................................................................................................ 18 21.4 Aux 24V fault .......................................................................................................................... 18 21.5 Batt low .................................................................................................................................. 18 21.6 Earth fault ............................................................................................................................... 18 21.7 Sys fuse fault .......................................................................................................................... 18 21.8 S1 fault and S2 fault ................................................................................................................ 18 21.9 Comms fault ............................................................................................................................ 18 22. Power supply .................................................................................................................... 19 23. Maintenance ..................................................................................................................... 20 24. Zone designation label....................................................................................................... 20 25. Record of Configuration ..................................................................................................... 21 Man-1138_Sigma_CPA_Alarmsense_08
Page 3 of 22
1. Introduction
The Sigma CP Alarmsense range consists of a series of conventional fire alarm control panels that comply with European
standards EN54-2 and EN54-4, Fire Detection and Fire Alarm systems - Control and Indicating Equipment.
The range consists of 2, 4 and 8 zone control panels.
The Apollo Alarmsense system allows compatible smoke and heat detectors, call points, sounders, sounder/ beacons and
alarm relays to be connected to a single pair of wires rather than having two pairs of wires, one for detection devices
and one for sounders and relays.
Wiring sounders to the detection circuits eliminates the need to install separate sounder circuit cables and also offers the
ability to provide zoned or two stage sounder operation.
The Alarmsense priority/non-priority sounder scheme makes the Alarmsense system ideal for protection of Houses of
Multiple Occupation. With appropriate settings on the sounder and sounder beacon devices it is possible to configure the
system such that when an alarm is detected, only the sounder local to the activated detector is operated to alert
occupants in that vicinity subject to a configurable alarm verification period. This functionality allows full compliance with
BS5839-6.
All control panels have an integral, mains powered battery charger and power supply.
In addition to the requirements of EN54-2 the control panel has the following facilities:
………….Test condition to allow the automatic resetting of zones in alarm for testing purposes. EN54-2 Section 10 option
with requirements.
………….Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a premises is
evacuated. EN54-2 Section 7.11 option with requirements.
………….Fire alarm devices to enable an audible warning to be sounded throughout a premises upon the detection of a
fire condition or the operation of a manual call point. EN54-2 Section 7.8 option with requirements.
Also in addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and local fire
which operate upon fire condition. These are to be used for local control and signalling.
NOTE: Some engineering functions can be set on this equipment which offer functionality not covered by
the EN54-2 standard. These functions are highlighted in this manual with the following symbol
2. Safety
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure as
reasonably as is practical that the article will be safe and without risk to health when properly used.
An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’ relating to
its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel in accordance with the
following:
(i)
IEE regulations for electrical equipment in buildings
(ii)
Codes of practice
(iii)
Statutory requirements
(iv)
Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that
you make any appropriate information about this product available to anyone concerned with its use.
This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As such it
must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible
double pole disconnect device meeting the requirements of EN60950/IEC950 which disconnects live and neutral
simultaneously shall be incorporated in the fixed wiring.
Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the
protective earth will render the equipment unsafe.
This control panel is designed for indoor use only and at temperatures between -50C (+/- 3) and +400C (+/- 2) and with
a maximum relative humidity of 95%.
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.
Man-1138_Sigma_CPA_Alarmsense_08
Page 4 of 22
3. Mounting
The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level position such that
the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all three mounting positions.
It should be positioned in an accessible position as agreed with the end user.
Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not liable to
move once fixed.
The control panel should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable entry points
are required, all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to
the panel.
4. Technical specification
Table 1 - Electrical specifications
Mains supply
Battery charge current
Battery fuse
Battery high impedance warning (Rimax)
Low battery voltage indication
Low battery shut off voltage
Maximum current draw from batteries
R0V output
Dedicated sounder outputs
230V AC +10% - 15% (100 Watts
maximum)
1.6Amp (F1.6A L250V)
3 Amps total including battery charge
28V +/ 2V
1.5 Volts
18.5 to 29V DC +/- 2%
400 milliamps
2.3 Amps
0.065A
Two 12 Volt sealed lead acid (7Ah
maximum)
27.6VDC nominal (temperature
compensated)
0.7A maximum
20mm, 3.15A glass
1.35 ohms max
21V +/- 2%
18.5V +/- 2%
3 Amps
Fused at 0.5A with electronic fuse
24V Fused at 500mA with electronic fuse
Zonal sounder outputs
24V rated at 200mA with electronic fuse
Alarm verification delay
Fault relay contact rating
30, 60 or 120 seconds
30VDC 1A Amp maximum for each
Fire relay contact rating
30VDC 1A Amp maximum for each
Local fire relay contact rating
30VDC 1A Amp maximum for each
Zone quiescent current
Terminal capacity
Number of detectors per zone
Number of sounders per common sounder
circuit
Detection circuit end of line
Sounder circuit end of line
No. of detection circuits
4mA maximum
0.5mm2 to 2.5mm2 solid or stranded wire
Up to 20
Dependent on type and current
consumption
3K3 5% ½ Watt resistor
10K 5% ¼ Watt resistor
(see table 2 for number of zones for
each model)
Switched -ve, max resistance 100 Ohms
FP200 or equivalent (maximum
capacitance 1uF maximum inductance 1
millihenry)
Mains supply fuse
Power supply rating
Maximum ripple voltage
Output voltage
Imax a
Imax b
Imin
Battery type (Yuasa NP)
Battery charge voltage
SIL, AL, FLT, RST inputs
Cabling
Man-1138_Sigma_CPA_Alarmsense_08
Page 5 of 22
Replace only with similar type
See table 2 for capacities
See table 3
Replace only with the same type
With main power source off
1.6 Amp total load over UallU
circuits
1.6 Amp total load over UallU
circuits
Configuarble
Maximum ratings not to be
exceeded
Maximum ratings not to be
exceeded
Maximum ratings not to be
exceeded
See table 4 for detector types
See table 6 for sounder types
Supplied in terminals
Supplied in terminals
Dependent on model
Metal cable glands must be used
Table 2 - Standby battery capacity required for fully loaded system
Panel model
KA11020 (2 Zones)
KA11040 (4 Zones)
KA11080 (8 Zones)
24 hours
standby
3Ah
3.3Ah
3.75Ah
48 hours
standby
4.6Ah
5.1Ah
5.95Ah
72 hours
standby
6.2Ah
6.9Ah
8.2Ah
Standby
current
0.065
0.075
0.093A
Max panel alarm
current
0.10A
0.21A
0.55A
Table 3 - Battery charge voltage versus temperature
Temperature
C
0
10
20
30
40
0
Battery charge voltage
29.2
28.56
27.99
27.55
27.13
Table 4 - Compatible detectors
Model
Type
55000-390
55000-190
55000-193
55000-391
OPTICAL
HEAT (A1R)
HEAT (CS)
INTEGRATING
OPTICAL
Manufactur
er
Apollo
Apollo
Apollo
Apollo
Maximum Number
per zone
20
20
20
20
Table 5 - Compatible detector bases and call points
Model
45681-244
55100-894
Type
AlarmSense mounting base
AlarmSense manual call
point
Manufacturer
Apollo
Apollo
Table 6 - Compatible AlarmSense sounder bases and relay
Model
Type
45681-510
45681-509
55000-017
AlarmSense Sounder base
AlarmSense Sounder Beacon base
Alarmsense Open Area Sounder
Beacon
Alarmsense Open Area sounder
Alarmsense Open Area Beacon
AlarmSense Alarm Relay
Sounder base cap white
Sounder base cap red
55000-018
55000-035
55000-835
45681-294
45681-295
Manufac
turer
Apollo
Apollo
Apollo
Maximum number per
zone
20
20
10
Apollo
Apollo
Apollo
Apollo
Apollo
10
10
20
N/A
N/A
Note: Alarmsense Open Area Sounders, Open Area Beacons and Open Area Sounder Beacons do not comply with
the requirements of EN54-2.
Table 7 - Compatible sounders for the two common sounder circuits
Model
BANSHEE
WAFER
FIRECRYER RANGE
KOBELL
ASKARI
ROSHNI
SQUASHNI
SYMPHONI
ELECTRONIC BELL
CFB BELLS
B6 AND B8 BELLS
Type
ELECTRONIC
ELECTRONIC
ELECTRONIC VOICE
MOTORISED
ELECTRONIC
ELECTRONIC
ELECTRONIC
ELECTRONIC
ELECTRONIC
MOTORISED
SOLENOID
Man-1138_Sigma_CPA_Alarmsense_08
Page 6 of 22
Manufacturer
VIMPEX
VIMPEX
VIMPEX
VIMPEX
FULLEON
FULLEON
FULLEON
FULLEON
FULLEON
FULLEON
FULLEON
Comments
Standard polarised type only
Standard polarised type only
Standard polarised type only
Standard polarised type only
Standard polarised type only
Standard polarised type only
Standard polarised type only
5. Control panel fascia
In addition to the mandatory controls and indications required by the EN54-2 standard, two, seven segment, LED
displays and MODE, SELECT and ENTER buttons are provided to allow easy entry and storage of codes to configure the
control panel to suit the requirements of the installation.
Removing the fascia
Before the fascia can be removed it will be necessary to unplug the three way terminal block on the left hand side of the
PCB.
The fascia of the control panel is held in place by countersunk screws. Undo the two screws and lift the fascia gently
away from the box towards you.
With the fascia removed there is much more room inside the panel for making off and dressing cables.
When cabling work is complete the fascia can be re-fitted with the two countersunk screws and the red, green/yellow
and black wires re-connected to the three way terminal block.
It is most important that the polarity of the red and black wires is observed as wrong connection of these
will damage the control panel.
Fire Alarm Control
Model: KA11080M2
Man-1138_Sigma_CPA_Alarmsense_08
Page 7 of 22
6. Connecting to the circuit board
All connections for field wiring are to a single row of terminals along the top of the circuit board.
The connections for the power cables are to a pluggable terminal block, which may be pulled off of the board to remove
the plate/PCB assembly. Remove this pluggable terminal only with mains power off.
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the panel.
The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded securely to
the enclosure via a metal gland.
Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the
appropriate terminals leaving only enough wire to ensure that there is no strain on the PCB.
Terminals are capable of accepting wires of up to 2.5mm2.
Terminal designations
Wiring must not go across the front of the circuit board plate or between the plate and the circuit board.
If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and well away
from the surface of the circuit board.
The space at the bottom of the enclosure is largely occupied by the standby batteries, so this must be borne in mind
when considering cable entries.
CORRECT
INCORRECT
INCORRECT
7. Software revision number
X1
X2
R166 R167
R99
C94
F12
R117
LED16
TR26
LED34
TR47
LED9
R103
TR 19
Z 11
REG1
LED13
D20
R55
R57
+
R98
C 51
F 11
R168
FB10
C109
FB1
FB2
C100
FB9
C108
FB4
R51
F9
R60
C30
R158
R54 R58 C19
R53 R69
R52
C55
C95
R102
R137
R128
+
New features may be added to fire control panels from time to time and when
this is done the operating software of the unit is updated. The software
revision can be located on the main processor by removing the plate holding
the PCB from the enclosure and turning it over. The software version will have
a number such as “SigXX.hex” and it is this number, which will determine
which features the panel has installed and its compatibility with Sigma CP
ancillary board, sounders boards, repeaters etc.
D 41
VR1
L1
R72
C43
C 25
Z 14
IC 5
R74
R88 R111 R114
C 82
LED14
C83 C81
R113 R62 R64
R112 R67 R61
R63
R110
R109 R66 R65
R118
R107
+
D 23
R 133 D 22
R 78
R 135
R71
C 41
D 10
R 130 D 13
R 131
IC 4
TR 28 R 126
TR 25
R 86 D 14
R 132
FB20
IC 1
D 15
C 27
+
D9
R 87 D 16
R 85
IC 10
C 24
D 30
R 129 TR 24
R 104
Sig27. hex
IC 6
Jason
TR9 D 11
R73
J1
FB21
TR 23
RL9
R56
IC 2
C 65
C105
D 32
C102
C99
FB5
LED10
D 12
+
C 73
R1
D1
+
C 66
REG3
+
C 67
XTL1
C45 C44
C 68
RL 10
LED12
TR2
C 75
C 74
D2
R 13
R7
D 34
D 33
R22A R21
R16F
R16E
R16D
R16C R17
R16B R15
R89
R16A
R10F
R10E
R10D R11
R10C R9
R10B
C42 R90
R10A
R4F
R4E R5
R4D R3
R4C
R4B
R116 C39 C38 C37 C40 C96
R4A
LED8
LED11 LED15
+
TR1
R19
D3
D 35
F 10
R2
C104
R157
R80 R156
R81 C103
C31 R155
R12
R6
F4
F3
RL 1
D4
TR3
C76
R14 R18
R8
F1
C 97 C 93
RL 2
RL3
VDR1
C101
FB3
VDR2
VDR3
C92
C98
F2
C 106 C 107
C 1 C 23 C 22 C 21 C 20 C127 C128 C 35 C 36 C 33 C 34 C 60 C 61
C3 C2
VDR4
FB7
C4
FB6
C5
FB8
C 7 C6
R 134
C 56
T3
SW2
SW1
SW4
SERIAL NUMBER
+
D 1008 ISSUE06
TH1
R 75
R 76
LED17
LED35
LED5
LED4
LED3
LED6
LED7
R 70
PANEL SOFTWARE VERSION LABEL
Man-1138_Sigma_CPA_Alarmsense_08
Page 8 of 22
8. Detection zone wiring
The detection zones provide a nominal 12V DC to power conventional Alarmsense detectors and call points as listed in
the compatibility tables on page 6.
Note:
Only Alarmsense detection devices and call points are compatible.
Kentec K14060 LCMU end of line monitoring devices are not compatible with Alarmsense panels.
To activate Alarmsense sounders connected to the zone wiring, the voltage is raised to 24V DC.
The wiring is monitored for open and short circuit fault conditions by removing the 3K3 end of line monitoring resistors
that are supplied fitted to the control panels’ terminals and placing them across the last device that is wired to the zone
circuit.
Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring
circuits to work correctly.
In order to comply with EN54-2 an Alarmsense sounder must be installed on each used detection zone.
9. Priority/Non-priority alarm settings
Alarmsense sounder and sounder beacon bases can be set as priority or non-priority via switch 1 on the DIL switch in
the base unit. When a sounder or sounder beacon base is set to non-priority, activation of a detector connected to the
base will not cause the panel to enter the alarm condition and will only activate the sounder to which the detector is
connected. After the configured alarm verification delay (30 seconds, 60 seconds or 120 seconds) the panel will reset the
activated detector. If smoke is no longer present, the system will revert to normal quiescent condition. If smoke is still
present and the detector activates again a fire condition will be indicated at the control panel and all sounders will
operate.
This functionality is particularly well suited to residential buildings such as Houses of Multiple Occupation because the
alarm is restricted to the local area before it is verified thus minimising disruption due to false alarms. This allows
compliance with the requirements of BS5839 part 6.
Note: Non –priority mode setting on DIL switch 1 of the base unit offers local alarm functionality not
covered by the requirements of EN54-2.
10. Standard Sounder circuit wiring
In addition to the ability to operate Alarmsense sounder and sounder beacons from the detection circuit, the control
panel also has two standard sounder outputs which provide 24V DC upon any alarm. All sounders connected to these
outputs must be of the polarised type. If non-polarised sounders are used, the control panel will permanently show a
fault condition. See table 7 for a list of compatible sounder types.
Sounder circuits are monitored for open and short circuit faults by placing the 10K end of line monitoring resistor that is
supplied fitted to the terminals in the control panel across the last sounder device on the circuit.
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit to
work correctly.
A maximum of 1.6 Amps is available for powering sounders including those connected to the detection zones with a
maximum load of 0.41 Amps on any one of the standard sounder circuits described here.
The sounder circuits are protected by 500 milliamp fuses.
+
POLARISED
SOUNDER
POLARISED
SOUNDER
+
+
+
+
IN
OUT
IN
OUT
S1
-
_
_
_
_
IN
OUT
IN
OUT
Man-1138_Sigma_CPA_Alarmsense_08
Page 9 of 22
10K end of line
resistor
11. Connection to remote control terminals
Some functions of the control panel can be controlled externally from the panel if required. Operation of these inputs
must be restricted by an access level 2 control as defined in EN54-2 These are abbreviated at the terminals block
as follows:
a)
b)
c)
d)
e)
Remote 0 V supply - ROV
Silence Alarm – SIL
Sound Alarm – AL
Fault – FLT
Reset – RST
To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch or
contact and via a resistance of no greater than 100 ohms.
All of the remote control inputs are non-latching.
12. Aux 24V DC supply
An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door release
controllers.
The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative terminal and is
the same terminal that should be used to switch the remote control terminals.
It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote, volt free
contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another system for example
to give an alert. See programming code 24.
The supply is fitted with an electronic self resetting fuse to protect the control panel’s 24V supply in the event of a wiring
fault.
Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times as standby
time will be significantly affected by even modest standing loads. It is recommended that the Aux24V output is not used
to power standing loads and not used to supply loads of greater than 300 milliamps
Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is imperative
that a suppression diode is fitted across the coil of the electromechanical device to prevent the generation of high
voltage transients back to the control panels power supply.
The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply should be used
for these.
13. Connection to relay contacts
Volt free changeover relay contacts are provided for local control and signalling if required. These contacts are rated for
switching signalling circuits only and the maximum ratings listed in table 1 on page 5 should not be exceeded under any
circumstances.
Fault relay
The fault relay is normally energised and will de-energise upon any fault condition including total loss of power.
Man-1138_Sigma_CPA_Alarmsense_08
Page 10 of 22
Local fire relay
The local fire relay will energise upon activation of a fire condition on any of the zones or pressing of the sound alarm
button on the front panel. The relay will remain activated until the alarm is silenced or the panel is reset. This relay will
not operate upon activation of the remote AL input or when a fire condition is triggered on a zone that is in test mode.
Fire relay
The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain activated until
the control panel is reset. This relay will NOT operate upon activation of the remote AL input. Individual zones can be
configured not to operate the Fire relay by setting configuration options E1 to E8.
14. Connection to Repeater panels
Repeater panels connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel
PCB. Up to 7 repeaters may be connected and each repeater has terminals for the incoming cables and outgoing cables.
All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper links J2
removed.
Set the repeater address using the DIP switch (SW7); ensure no two repeaters share the same address.
Apply power to main panel first and then all repeater panels. Turn on the Enable Control keyswitch and set the Write
Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the
main panel will show the addresses of the repeaters that were found on the display for instance r1 indicates that a
repeater at address 1 has been found.
Turn the write enable switch off, then on again and then press the ENTER button to accept each repeater that has been
found. When all repeaters have been added, set the main panel Write Enable switch to off. Press the Watchdog reset
switch on the main panel.
All repeaters are now configured and the main control panel will report a fault if any repeaters that have been accepted
become faulty or go off line.
For full details of commissioning procedures for repeaters see the Sigma CP Repeater Operation and maintenance
manual.
Man-1138_Sigma_CPA_Alarmsense_08
Page 11 of 22
15. Connection to Ancillary boards
Ancillary boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel
PCB. Up to 7 Ancillary boards may be connected and each board has terminals for the incoming cables and outgoing
cables. All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper
links J2 removed.
Set the ancillary board address using the DIP switch (SW7); ensure no two ancillary boards share the same address.
Apply power to main panel first and then all ancillary boards. Turn on the Enable Control keyswitch and set the Write
Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the
main panel will show the addresses of the ancillary boards that were found on the display for instance 01 indicates that
an ancillary board at address 1 has been found.
Turn the write enable switch off, then on again and then press the ENTER button to accept each ancillary board that has
been found. When all ancillary boards have been added, set the main panel Write Enable switch to off. Press the
Watchdog reset switch on the main panel.
All ancillary boards are now configured and the main control panel will report a fault if any ancillary boards that have
been accepted become faulty or go off line.
For full details of commissioning procedures for ancillary boards see the Sigma CP Ancillary board Operation and
maintenance manual.
16. Connection to 8 way Sounder boards
Sounder boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel
PCB. Up to 7 Sounder boards may be connected and each board has terminals for the incoming cables and outgoing
cables. All except the last Ancillary board, Sounder board or Repeater connected to the cable must have the jumper links
J2 removed. Sounder boards must be powered from a separate power supply which is suitably rated to supply the full
sounder load that is connected. This can be up to 4 Amps if all circuits are fully loaded.
Set the sounder board address using the DIP switch (SW7); ensure no two sounder boards share the same address.
Apply power to main panel first and then all sounder boards. Turn on the Enable Control keyswitch and set the Write
Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the
main panel will show the addresses of the sounder boards that were found on the display for instance b1 indicates that a
sounder board at address 1 has been found.
Turn the write enable switch off, then on again and then press the ENTER button to accept each sounder board that has
been found. When all sounder boards have been added, set the main panel Write Enable switch to off. Press the
Watchdog reset switch on the main panel.
All sounder boards are now configured and the main control panel will report a fault if any sounder boards that have
been accepted become faulty or go off line.
For full details of commissioning procedures for Sounder boards see the Sigma CP Sounder board Operation and
maintenance manual.
Man-1138_Sigma_CPA_Alarmsense_08
Page 12 of 22
17. Panel operation
17.1 Normal condition
Under normal conditions, control panels will have only the green, Power On LED lit.
17.2 Fire condition (sounders set to priority alarm)
Upon receipt of a fire condition by activation of a detector or call point, the Common Fire indicator will light and the
zonal Fire indicators will flash at around 2Hz. The zonal indicators can be used to differentiate call point and detector
activation by setting configuration option 28. If option 28 is set, and a call point is operated, the zonal indicator will flash
and if a detector is operated it will illuminate continuously.
The internal fire and local fire relays will also operate and signal any systems to which they are connected.
Any sounders connected to the detection zones or standard sounder circuits will operate in common, zonal or 2-stage
mode as selected by configuration options 10 to 12 (see table 8).
17.3 Fire condition (sounders set to non-priority alarm)
Upon receipt of a fire condition by activation of a detector, the sounder or sounder beacon to which the detector is
connected will sound. After two minutes, the control panel will reset the detector. If the detector is successfully reset the
panel will revert to the Normal condition. If the detector re-enters the alarm state, sounders and relays connected to the
detection zones will operate in common, zoned or two stage alarm mode depending on the setting of configuration
options 10 to 12 (see table 8), the internal fire and local fire relays will operate and the two standard 24V sounder
outputs will operate.
17.4 Silence/sound alarms
The Silence/Sound alarm button can only be operated at access level two which means that the Enable Control key must
be inserted.
To silence the sounders, insert the Enable Control key and press the Silence/Sound alarm button.
When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.
Pressing the Silence/Sound alarm whilst the control panel is in this silenced condition, will cause the sounders to operate
again.
The sounders can be toggled on and off with the Silence/Sound alarm button as required.
17.5 Reset
To reset the panel, insert the Enable key then press the Reset button.
17.6 Zone fault
Removal of a detector from its base or a fault on any of the zone wiring will cause the Fault LED and Zone Fault LEDs to
light indicating the zone in which the fault has occurred. All devices that are connected beyond the point where a
detector is removed from its base will continue to operate.
17.7 Sounder fault
A fault on the wiring to detection zones and sounder circuits will cause the Fault and Sounder Fault LEDs to light
indicating a fault on the wiring to the sounder circuits.
17.8 Power fault
Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit will cause the
Fault and Power Fault LEDs to light indicating an abnormality in the power supply to the control panel.
17.9 System fault
The System Fault LED will light if the configuration memory has not been set or has become corrupt.
17.10 Lamp test
All LED indicators can be tested at any time by pressing the Lamp Test button. The Enable Control key does not need to
be inserted to test the indicators.
The buzzer can be silenced at any time by pressing the Buzzer Silence button. The enable key does not need to be
inserted to silence the buzzer.
17.11 Disablements
It is possible to disable parts of the system. This may be required if there are works going on in a building which may
cause the fire alarm system to operate in error.
Man-1138_Sigma_CPA_Alarmsense_08
Page 13 of 22
17.11.1 Disable zones
To disable zones, the Enable Control key should be inserted and the mode button pressed until “d” appears in the first of
the two seven segment LED displays. The Select button should then be pressed to select the number of the zone which
is to be disabled in the second of the two seven segment displays. Once the desired zone is displayed, the enter button
should be pressed to confirm the disablement.
The Disable LED will light and the Zone Fault LED will light for each disabled zone.
When is a zone is disabled, all detectors, call points and sounders in the zone will be disabled.
A disabled zone is shown on the seven segment display as ‘dx.’ (where x is the zone number from 1-8). If the ‘x’ is
flashing, it means that there are activated devices in that zone and re-enabling it will put the
control panel into the fire condition.
The panel should be Reset before enabling any zone with a flashing “dx.” Indication.
Note: The flashing “dx” indicator will only appear on panels produced after January 2013.
17.11.2 Disable sounders
To disable sounder outputs, press the mode button to select “db” on the seven segment display. Pressing enter will
disable all sounders and cause the Disable and Sounder Fault LEDs to light.
Note: Non –priority mode setting on DIL switch 1 of the base unit offers local alarm functionality not
covered by the requirements of EN54-2.
17.11.3 Activate delays
To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears on the
seven segment LED display. When the enter button is pressed any zones that are set as delayed will have their alarm
outputs delayed by the time set in configuration options 00 to 09.
17.11.4 Disable fault contact
The fault relay can be disabled by selecting configuration option 22.
17.12 Test mode
Fire alarm systems must be tested regularly to ensure that they are functioning correctly. The Sigma CP range of panels
enable the system to be tested single handed by using a test mode. When in test mode, activation of a fire alarm will be
automatically reset after a few seconds to eliminate the need to return to the control panel to reset after every
activation.
Test mode is entered in a similar way to disablements. With the Enable Control key inserted, press the Mode button until
“t” appears in the first of the seven segment displays. Then press the Select button until the required zone number
appears. Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are
in test mode.
Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db" function
(for example) toggles between sounders disabled and sounders enabled.
18. Configuration options
The panel range has many configuration options which can be set at the time of commissioning to suit the requirements
of the installation. These options are normally set once and will rarely need to change. The configuration options are
only available at access level 3. To get to access level 3, CAREFULLY slide the Write Enable switch (located behind the
aperture in the panel plate) to the right position using a small screwdriver or similar. When the panel is at access level 3,
the buzzer will “pip” three times every few seconds as an indication that it is at this access level.
Configuration options are simple to enter using the codes in table 8 below. When the control panel is at access level 3,
the sub-text of the Mode and Select buttons is used to enter a number using tens (+10) and units (+1).
Man-1138_Sigma_CPA_Alarmsense_08
Page 14 of 22
When the required code number is displayed, pressing the enter button will cause the dot on the units, seven segment
display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8, C1 to
C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
ZONE 1 - ALARM
FROM DETECTOR
DELAYED
ZONE 1 - ALARM
FROM DETECTOR
NOT DELAYED
DOT
FLASHING
NO DOT
Table 8 – Configuration codes
COD
E
L0
FUNCTION
COMMENTS
NON-PRIORITY ALARM CONFORMATION TIME
30S
NON-PRIORITY ALARM CONFORMATION TIME
60S
NON-PRIORITY ALARM CONFORMATION TIME
120S
Sets time before detector resets and checks if smoke still
present at detector.
00
01
02
03
04
05
06
07
08
09
10
11
12
SOUNDER DELAY TIME = 30 SECONDS
SOUNDER DELAY TIME = 1 MINUTE
SOUNDER DELAY TIME = 2 MINUTES
SOUNDER DELAY TIME = 3 MINUTES
SOUNDER DELAY TIME = 4 MINUTES
SOUNDER DELAY TIME = 5 MINUTES
SOUNDER DELAY TIME = 6 MINUTES
SOUNDER DELAY TIME = 7 MINUTES
SOUNDER DELAY TIME = 8 MINUTES
SOUNDER DELAY TIME = 9 MINUTES
COMMON ALARM MODE (default)
TWO-STAGE ALARM MODE
ZONED ALARM MODE
Sets the time delay before sounders operate in
combination with configuration codes 31 to 48 and access
level 2 function AD.
21
DISABLE FIRE BUZZER
22
DISABLE FAULT OUTPUT
23
DISABLE EARTH FAULT MONITORING
24
PULSED REMOTE CONTROL OUTPUT
26
27
DISABLE FIRE OUTPUT
REMOVE AUX 24 UPON PANEL RESET
28
INDICATE CALL POINT ACTIVATION
29
DO NOT RE-SOUND ALARMS FROM ANOTHER
ZONE
L1
L2
Man-1138_Sigma_CPA_Alarmsense_08
All sounders operate upon any fire condition
Continuous sounders in activated zone, pulsing elsewhere
Only sounders connected to zone in alarm operate
Buzzer will not operate on fire condition
Fault relay will not operate except upon total power failure
Page 15 of 22
Connection of fire alarm wiring to earth will not announce
a fault
Aux 24V supply pulses 1 sec on/1 sec off
Fire relay will not operate upon any alarm
24V supply switches off for about 5 seconds when panel is
reset
Activation of an AlarmSense call point is indicated by a
flashing zone indicator and “Pu” on the 7 segment display.
Activation of a detector will be indicated by a steady zone
indicator and nothing on the 7 segment display.
Silenced sounders will not re-sound upon further zone
activations
31
32
33
34
35
36
37
38
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
41
42
43
44
45
46
47
48
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
CALL
CALL
CALL
CALL
CALL
CALL
CALL
CALL
51
52
53
54
55
56
57
58
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
61
62
63
64
65
66
67
68
FULL
FULL
FULL
FULL
FULL
FULL
FULL
FULL
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
POINT
POINT
POINT
POINT
POINT
POINT
POINT
POINT
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
1
2
3
4
5
6
7
8
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
81*
82*
83*
84*
85*
86*
87*
88*
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
91
92
93
94
95
96
97
98
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
DOES
DOES
DOES
DOES
DOES
DOES
DOES
DOES
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only.
Note access level 2 function Ad must be set for this to take
effect.
Zone contributes to ancillary board coincidence O/P. Any
number of zones can be selected to contribute.
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
COD
E
71
72*
73*
74*
75*
76*
77*
78*
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only.
Note: Access level 2 function Ad must be set for this to
take effect.
1
2
3
4
5
6
7
8
When this option is set, any detector activating on the
zone will put the panel into alarm. I.e. Non-priority setting
on sounder or sounder beacon bases will be ignored.
FUNCTION
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
COMMENTS
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
SOUND
SOUND
SOUND
SOUND
SOUND
SOUND
SOUND
SOUND
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
Changes the trigger threshold of the
zone so that the control panel can be
used on older systems that had no short
circuit monitoring. (Not for use if Alarmsense devices are
connected to the zone)
Renders the zone self-resetting so that
it can be used to receive signals from
other systems and will reset when the
input is removed.
Note: It can take up to 20 seconds for zone to reset itself
when sounders are operating.
(Not for use if Alarmsense devices are connected to the
zone)
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
Man-1138_Sigma_CPA_Alarmsense_08
Page 16 of 22
Prevents the zone from operating any sounders whether
connected the two common sounder outputs or to
detection zones.
A1*
A2*
A3*
A4*
A5*
A6*
A7*
A8*
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
ANY
ANY
ANY
ANY
ANY
ANY
ANY
ANY
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
Zone needs to be triggered for 30 seconds continuously
before an alarm is generated.
(Detectors fitted to Alarmsense non-priority sounders are
C1
C2
C3
C4
C5
C6
C7
C8
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
Enables individual zones to be configured not to operate
zonal sounders.
E1*
E2*
E3*
E4*
E5*
E6*
E7*
E8*
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
WILL
WILL
WILL
WILL
WILL
WILL
WILL
WILL
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
OPERTATE
OPERTATE
OPERTATE
OPERTATE
OPERTATE
OPERTATE
OPERTATE
OPERTATE
not delayed)
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
NOTE: Setting the options marked with
Enables individual zones to be selected to not operate the
fire relay. This is sometimes combined with the nonlatching function to prevent ring around on interconnected
panels.
does not comply with EN54-2
Once the required configuration options have been set, the Write enable switch must be returned to its normal position
to the right. The General fault indicator will remain lit if the Write enable switch is not turned off.
19. Watchdog reset switch
If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will attempt to restart
itself. This process is called a “watchdog” and the control panel must record and indicate these events.
If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front panel, the CPU
fault LED inside the panel.
This fault can only be cleared by pressing the WATCHDOG RESET button on the PCB inside the control panel. The
control panel buzzer cannot be silenced and will continue to sound until the watchdog activation is reset.
20. Processor reset switch
Once started, the microprocessor controlling the panel should continue to run continuously without interruption. If the
microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET button on the PCB inside the
control panel.
This should not normally be necessary but should be done as a matter of course if the system is behaving abnormally.
The system should resume normal operation within a couple of seconds of pressing the processor reset button.
21. Internal indications – troubleshooting
To assist in identifying fault conditions, which are not detailed on the front of the control panel, a number of internal
indicators are visible with the front cover removed as follows:
21.1 Mains fail
Indicates that the 230V AC supply is not present and the system is running on standby batteries.
If there is not a power cut, check the panels mains fuse.
21.2 Batt fail
Indicates that the standby battery has become disconnected or that the charging circuit of the control panel has a high
resistance or has failed. Check that both batteries are connected and linked together. Test battery. Disconnect battery
and ensure that 28 Volts can be measured on battery charger leads.
Man-1138_Sigma_CPA_Alarmsense_08
Page 17 of 22
21.3 CPU fault
Indicates that the central processor unit has failed to correctly execute code and has been re-started by the system
watchdog. The watchdog reset switch must be pressed to clear the CPU fault condition.
Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs the circuit
board replacing. (See maintenance section).
21.4 Aux 24V fault
The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire alarm ancillary equipment.
This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded.
The fuse is a self resetting type and the supply will resume when the fault condition is removed.
21.5 Batt low
Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the minimum
battery voltage).
21.6 Earth fault
Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect cables one at a
time until the earth fault returns. This will indicate which cable the earth fault is present on.
21.7 Sys fuse fault
Indicates that the total power rating of the power supply has been exceeded and that the system fuse has come into
operation. Remove and review all loads and re-connect one at a time until over rated circuit trips fuse to identify
troublesome circuit.
21.8 S1 fault and S2 fault
Indicates a short or open circuit on the standard 24V DC sounder outputs. Remove wiring and refit end of line resistors.
Check sounder circuit wiring.
21.9 Comms fault
Indicates that communication has been lost with a repeater panel or Ancillary board. Check for comms fault at all
repeaters and ancillary boards to identify the source of the problem.
Man-1138_Sigma_CPA_Alarmsense_08
Page 18 of 22
22. Power supply
The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply, which connects to the fused
terminal block labelled “230V”.
The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar type.
The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum 0.7A for
battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse rated at 4 Amps.
The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at least 50mm.
Mains wiring should include an earth conductor, which is securely bonded to the building earth and should enter the
enclosure as close as possible to the mains terminal block. Mains wires should be kept very short inside the enclosure
and secured together close to the mains terminal block with a cable tie.
The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see table 2 for
battery size required for each model).
The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps.
Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB is fitted with
a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit, which must only be replaced with one of the same
type.
It is most important that the polarity of the batteries is carefully observed when connecting.
When the batteries are discharged to a level at which a low battery indication is given, the BATT FAIL indicator will also
be lit.
Wrongly connected batteries could cause damage to the control panel.
MAINS
TERMINAL
KEEP MAINS WIRES AS SHORT AS POSSIBLE
AND SECURE ALL THREE WIRES CLOSE TO
THE TERMINAL BLOCK WITH A CABLE TIE
N
N
E
L
L
+
-
+
GREY LINK
RED BATTERY
LEAD TO +
TERMINAL
Man-1138_Sigma_CPA_Alarmsense_08
-
Page 19 of 22
BLACK BATTERY
LEAD TO TERMINAL
23. Maintenance
The control panels do not require any specific maintenance but should the control panel become dirty it can be wiped
over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or solvents should not be used to
clean the panel and care must be taken that water does not enter the enclosure.
The control panel contains sealed lead acid batteries to provide standby power in the event of a mains failure. The
batteries have a life expectancy of around 4 years. The control panel monitors the condition of the batteries and will
announce a fault if the battery impedance becomes too high.
It is recommended that these batteries be tested in accordance with the battery manufacturer’s recommendations
annually to determine their suitability for continued standby applications.
Routine testing of the fire alarm system in accordance with BS5839: Part 1: 2002 will identify any malfunction of the
control panel and any malfunction should be reported to the fire alarm maintenance company immediately.
Should the control panel become faulty the complete electronic assembly can be replaced.
To do this, any configured options should be noted then both mains and battery power should be removed before the
work is started.
The field wiring should be carefully labelled and removed from the terminals.
The PCB can now be taken out of the panel by removing the 2 M4 screws holding the plate in position.
Fitting the new PCB is the reverse of the procedure for removing the board.
24. Zone designation label
The control panels are supplied with a zone designation label onto which zone designations can be written.
This enables each zone to be given a text description allowing easier identification of any zones showing an alarm, fault
or disablement condition.
Man-1138_Sigma_CPA_Alarmsense_08
Page 20 of 22
25. Record of Configuration
Use the table below to record the configuration codes that have been set on the control panel for future reference. Place
a tick in the grey band for any configuration options that are set.
It is recommended that a copy of this table is left with the control panel under the supervision of the person responsible
for the fire detection system.
CODE
FUNCTION
L0
L1
L2
NON-PRIORITY ALARM CONFORMATION TIME 30S
NON-PRIORITY ALARM CONFORMATION TIME 60S
NON-PRIORITY ALARM CONFORMATION TIME 120S
00
01
02
03
04
05
06
07
08
09
10
11
12
SOUNDER DELAY TIME = 30 SECONDS
SOUNDER DELAY TIME = 1 MINUTE
SOUNDER DELAY TIME = 2 MINUTES
SOUNDER DELAY TIME = 3 MINUTES
SOUNDER DELAY TIME = 4 MINUTES
SOUNDER DELAY TIME = 5 MINUTES
SOUNDER DELAY TIME = 6 MINUTES
SOUNDER DELAY TIME = 7 MINUTES
SOUNDER DELAY TIME = 8 MINUTES
SOUNDER DELAY TIME = 9 MINUTES
COMMON ALARM MODE (default)
TWO-STAGE ALARM MODE
ZONED ALARM MODE
21*
22*
23
24
DISABLE FIRE BUZZER
DISABLE FAULT OUTPUT
DISABLE EARTH FAULT MONITORING
PULSED REMOTE CONTROL OUTPUT
26
27
28
29
DISABLE FIRE OUTPUT
REMOVE AUX 24 UPON PANEL RESET
INDICATE CALL POINT ACTIVATION
DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE
31
32
33
34
35
36
37
38
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
DETECTOR
41
42
43
44
45
46
47
48
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
FROM
CALL
CALL
CALL
CALL
CALL
CALL
CALL
CALL
51
52
53
54
55
56
57
58
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
COINCIDENCE
61
62
63
64
65
66
67
68
FULL
FULL
FULL
FULL
FULL
FULL
FULL
FULL
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
POINT
POINT
POINT
POINT
POINT
POINT
POINT
POINT
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
1
2
3
4
5
6
7
8
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
Man-1138_Sigma_CPA_Alarmsense_08
Page 21 of 22
TICK IF THIS
OPTION IS
SET
CODE
FUNCTION
71*
72*
73*
74*
75*
76*
77*
78*
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
81*
82*
83*
84*
85*
86*
87*
88*
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
NON-LATCHING
91
92
93
94
95
96
97
98
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
DOES
DOES
DOES
DOES
DOES
DOES
DOES
DOES
A1*
A2*
A3*
A4*
A5*
A6*
A7*
A8*
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
ANY
ANY
ANY
ANY
ANY
ANY
ANY
ANY
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
DELAYED
C1
C2
C3
C4
C5
C6
C7
C8
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
SOUNDERS
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
INHIBITED
E1*
E2*
E3*
E4*
E5*
E6*
E7*
E8*
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
ZONE
1
2
3
4
5
6
7
8
WILL
WILL
WILL
WILL
WILL
WILL
WILL
WILL
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
NOT
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
INDICATES
SOUND
SOUND
SOUND
SOUND
SOUND
SOUND
SOUND
SOUND
TICK IF THIS
OPTION IS
SET
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
OPERATE
OPERATE
OPERATE
OPERATE
OPERATE
OPERATE
OPERATE
OPERATE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
RELAY
NOTE: Setting the options marked with asterisks does not comply with EN54-2
Man-1138_Sigma_CPA_Alarmsense_08
Page 22 of 22
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising