GENERAL FEATURES 4-Zone Fire Alarm Control Panel

GENERAL FEATURES 4-Zone Fire Alarm Control Panel
December 17, 2001
DF-52266 A2-260
MS-4
4-Zone
Fire Alarm Control Panel
Section: Conventional
www.firelite.com
GENERAL
The Fire•Lite MS-4 Fire Alarm Control Panel brings the
latest in microprocessor technology to conventional fire controls. The MS-4 is compatible with the new I3 smoke detectors from System Sensor, and provide such advanced features as drift compensation, maintenance alert, and freeze
warning. Automatic synchronization of audio/visual devices
is provided, using three selections for manufacturer protocol. The NAC protocol includes the ability to silence audible
devices while strobes continue to flash, using only a single
pair of wires.
S624
7165-0075:200
The MS-4 also is compatible with conventional input devices such as two- and four-wire smoke detectors, pull
stations, waterflow devices, tamper switches and other normally-open contact devices. See the Fire•Lite Device Compatibility Document (Doc. No. 15384) for a complete list of
compatible devices.
FEATURES
• Four Style B (Class B) IDCs (Initiating Device Circuits).
• Two Style Y (Class B) NACs (Notification Appliance Cir-
•
•
•
I3 Technology features:
— Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused
by dust accumulation.
— Maintenance Alert LEDs (per zone) warn of excessive
dirt accumulation, preventing false alarms (meets NFPA
72, 7-3.2.1).
— Detector sensitivity is automatically measured by the
detector, which automatically adjusts its sensitivity
back to the factory settings when it becomes more
sensitive due to contaminents settling in the chamber.
— Wireless handheld sensitivity meter eliminates the
need for voltemeters, magnets and a physical connection to the detector. The reader displays sensitivity in
terms of percent per foot obscuration and provides text
status indication.
— Supervisory LED (per zone) provides warning if a
detector senses temperature approaching freezing.
— Special test protocol and LED indication allows quick
test of all detectors without need for a ladder.
NAC synchronization features:
— Provides synchronization of standard ANSI audible
signals as required by NFPA 72 (3-8.4.1.2.3).
— Provides synchronization of ADA compliant strobes
per NFPA 72 (4-4.4.1).
MS4.jpg
•
cuits).
Optional module that converts all 4 IDCs and 2 NACs to
Class A.
24VDC.
MS-4
— Selectable for System Sensor, Wheelock and Gentex
protocols.
— Selective Silence feature allows manual silence of
horns while strobes continue to flash on the same
NAC.
•
Silent or Audible Walk Test operation mode commanded
from the front keypad, with automatic return to normal
after 1 hour of inactivity.
•
Programmable for combination tamper supervisory monitor and waterflow alarm on one zone.
•
•
Alarm verification selectable per zone.
•
•
Disable switches provided per zone.
Each zone may be programmed for supervisory or fire,
with separate red and yellow LEDs.
NACs programmable for:
— Silence Inhibit
— Auto Silence
— Strobe Synchronization
— Selective Silence (horn-strobe mute)
— Temporal or Steady signal
— Silenceable or Nonsilenceable
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to
change without notice. For more information, contact Fire•Lite Alarms, One FireLite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll Free
FAX: (877) 699-4105, FAX Back:(888) 388-3299
Made in the U.S.A.
DF-52266 — Page 1 of 2
•
•
•
Form-C Alarm, Trouble and Supervisory relays.
3.0 amps total useable current .
6.0 amps total useable current available with optional
second transformer.
•
•
Optional dress panel (part no. DP-MS2/4).
•
LED indicators:
— Fire Alarm (one per zone)
— Supervisory (one per zone)
— Trouble (one per zone)
— Maintenance (one per zone)
— AC Power
Control buttons:
— ACK (Acknowledge)
— Alarm Silence
— Reset
— Walktest
— Zone Enable/Disable (one per zone)
—
—
—
—
—
—
—
—
—
—
•
•
•
•
NAC Disable
Zone Disable
NAC Fault
System Trouble
Power Trouble
Walktest
Alarm Silence
Earth Fault (on circuit board)
Battery Fault (on circuit board)
Charger Fault (on circuit board)
Piezo sounder for alarm, trouble, supervisory and maintenance.
Optional plug-in 4XTMF Transmitter module.
Optional plug-in 4XZMF Zone relay module.
Optional 4XLMF Transmitter module for RZA-4XF remote
LED annunciator.
OPERATION
Activation of a compatible smoke detector or any normallyopen fire alarm initiating device activates audible and visual
signaling devices, illuminates an indicating LED, sounds the
piezo sounder at the FACP, activates the FACP alarm relay
and operates an optional module used to notify a remote
station or initiate an auxiliary control function.
SPECIFICATIONS
AC Power - TB8: 120 VAC,2 50/60 Hz, 2.3 amps. Wire size:
minimum 14 AWG (2.0 mm ) with 600 V insulation.
Battery (Sealed Lead Acid Only) - J8: Maximum Charging
Circuit: Normal flat charge - 27.6 VDC @ 0.8 amp. Maximum Battery Charger Capacity: 18 amp hour battery (two 7
amp hour batteries can be housed in the FACP cabinet.
Larger batteries require a separate battery box such as the
Fire•Lite BB-17F).
Initiating Device Circuits - TB3: Alarm Zones 1 - 4. Powerlimited circuitry. Operation: All zones Style B (Class B).
Normal Operating Voltage: Nominal 22 VDC. Alarm Current: 15 mA minimum. Short Circuit Current: 40 mA maxi-
Page 2 of 2 — DF-52266
mum. Maximum Loop Resistance: 100 ohms. End-of-Line
Resistor: 4.7 k OHM, 1/2 watt (P/N 71252). Standby Current: 4 mA. Refer to Fire•Lite Device Compatibility Document (Doc. No. 51384) for listed compatible devices.
Notification Appliance Circuits - TB2: Two NACs on MS4. Power-limited circuitry. Normal Operating Voltage: Nominal 24 VDC. Maximum Signaling Current: 2.5 amps total
with standard transform. 5.0 amps total (2.5 maximum per
NAC) with optional transformer. End-of-Line Resistor: 4.7 k
OHM, 1/2 watt (P/N 71252). Refer to Fire•Lite Device Compatibility Document for listed compatible devices.
Form-C Relays: Trouble Relay TB5 (fail-safe). Alarm Relay
TB 6. Supervisory Relay TB7. Relay Contact Ratings: 2.0
amps @ 30 VAC (resistive).
AUXILIARY OUTPUTS
Resettable Power - TB1: Operating Voltage: Nominal 24
VDC. Maximum Available Current: 500 mA - appropriate for
powering 4-wire smoke detectors (see NOTES below).
Power-limited circuitry.
Nonresettable Power - TB1: Operating Voltage: Nominal
24 VDC. Maximum Available Current: 500 mA (see NOTES
below). Power-limited circuitry.
NOTES: 1) See the Device Compatibility Document (Doc.
No. 15384) for listed compatible devices .
2) Total current for nonresettable power, resettable power
and two NACs must not exceed 6 amps for the MS-4 (requires optional second transformer).
CABINET SPECIFICATIONS
Door: 15.342" (38.97 cm) high x 14.677" (37.28 cm) wide x
0.375" (0.95 cm) deep. Backbox: 15.0" (38.10 cm) high x
14.5" (36.83 cm) wide x 3.0" (7.62 cm) deep.
BACKBOX MOUNTING
The cabinet can be surface mounted. The door is removable during installation by opening and lifting it off the hinges.
The cabinet mounts using two key slots at the top of the
backbox and two additional 0.250” diameter holes at the
bottom.
PRODUCT LINE INFORMATION
MS-4
CAC-4
Four zone conventional addressable FACP.
Class A converter module. Used to convert
Style B (Class B) IDC to Style D (Class A) and
Style Y (Class B) NAC to Style Z (Class A). The
module connects to J1 on the MS-4 circuit board.
4XTMF
Transmitter module.
4XLMF
LED Interface module.
XRM-24
Transformer assembly increases power from 3
amps to 6 amps.
RZA-4XF Remote annunciator - mounts in a single-gang
box.
4XZMF
Zone relay module.
BB-17F
Battery box, required to house two (2) batteries
greater than 7 Amp Hour to a maximum of 18
Amp Hour.
411/ 411UD Three input (channel) 411 and four input
(channel) 411UD dual line Digital Alarm
Communicator/Transmitters, which can be used
as slave communicators with the MS-4 FACP.
DP-MS2/4 Dress panel.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising