Aperion - Evenlite

Aperion - Evenlite
Aperion
Emergency Lighting
Applications Guide
Architectural Recessed
Ceiling and Wall Mount Applications
Wall Mount Unit
Lamps are
independently adjustable
for optimum floor coverage
(see chart on page 2)
Lamp socket
rotates on 2nd axis
more than 90 deg.
to move beam center
to cover around corners
4 ft Egress Path
Ceiling Mount Unit
Multiple Unit Spacing 55 to 85 feet
Mounting Height 7 to 14 feet
(see chart on page 2)
Wall Mount Unit
Both lamp sockets
rotate on 2nd axis
to move beams out
from wall
More than 90 deg.
Both lamps
Lamps are
independently adjustable
for optimum floor coverage
(see chart on page 2)
Special Ceiling Mount Applications
Angled
Beam
Compliance with the Life Safety Code NFPA 101, Section 7.9.2.1 requires
even illumination, over a specified area of 1fc average with a minimum
illumination of 0.1fc at any point with a ratio of not more that 40 to 1.
To meet this requirement Aperion uses Superflux, high intensity, energy
efficient, Halogen Lamps to provide large area coverage in a small
package. Precision independently adjustable light beams allow precise
positioning for even coverage.
2575 Metropolitan Drive, Trevose, PA 19053 • USA
TEL: (800) 872 0879 • FAX:(215) 244 4208 • www.evenlite.com
Aperion
Top edge
of unit
Straight Beam
down stairwell
US Patent #7,654,710
Project name:
Approved By:
Catalog No:
Type No:
Aperion Retracted Recessed Emergency Light
Recommended center to center unit spacing – 25 watt MR11 lamp
STANDARD L110061 Lamp
Ceiling Mount
Wall Mount
(Angle away from wall – 4 degrees)
Ceiling Height
Vert. Aiming
Angle (Deg)
Unit Spacing
(Multiple Units)
Ceiling Height
Unit/Lamp
Height
Vert. Aiming
Angle (Deg)
Unit Spacing
(Multiple Units)
8
68
85
9
7
70
85
9
66
80
10
8
68
85
10
63
80
12
10
63
80
12
59
75
14
12
59
75
14
53
70
16
14
55
70
Recommended center to center unit spacing - 20 watt MR11 lamp
Optional L110060 Lamp
Ceiling Mount
Wall Mount
(Angle away from wall – 4 degrees)
Ceiling Height
Vert. Aiming
Angle (Deg)
Unit Spacing
(Multiple Units)
Ceiling Height
Unit/Lamp
Height
Vert. Aiming
Angle (Deg)
Unit Spacing
(Multiple Units)
8
61
65
9
7
64
65
9
58.5
65
10
8
61
65
10
55
60
12
10
55
60
12
50
60
14
12
50
60
14
45
55
16
14
45
55
•
Tables and Photometrics independently tested and compiled by ITL Boulder Testing Laboratories for Evenlite custom
lamps L110061 and L110060.
•
Recommended spacings based on requirements for meeting the Life Safety Standard minimum illuminance of 0.1 fc
and average illuminance of 1.0 fc. Assumes that the fixture is mounted in open room 200 ft wide by 200 ft long with
reflectance of 80/50/20 over 4 ft path of egress.
•
Note: Recommended spacings calculated from laboratory data taken under controlled conditions in accordance with
I.E.S. approved methods. Actual performance results will vary due to field conditions.
•
I.E.S. data is available from Evenlite Inc.
Isocurves of Beam Footcandles - 25 watt MR11 lamp
STANDARD L110061 Lamp
Isocurves of Beam Footcandles - 20 watt MR11 lamp
Optional L110060 Lamp
2575 Metropolitan Drive • Trevose, PA 19053 • USA
Tel: (800) 872-0879 • Fax: (215) 244-4208
www.evenlite.com
APR-APP 3/15