QSE-CI-NWK-E Control Interface

QSE-CI-NWK-E Control Interface
QSE-CI-NWK-E
QS System
Control Interfaces
qse-ci-nwk-e-1 09.24.09
QSE-CI-NWK-E Control Interface
Description
The QSE-CI-NWK-E is a versatile integration access
point for Lutron’s QS-based systems. Through either
RS232 or TCP/IP over Ethernet, third-party devices can
control and/or monitor a QS system.
Key Features
• Easily integrate with touchscreens, PCs, A/V systems,
or other digital systems and devices.
• Control and monitor GRAFIK Eye® QS, Sivoia® QS, and
other products on the wired QS link.
• Monitor lighting scenes, levels, and shade positions.
• Up to ten (10) QSE-CI-NWK-E control interfaces are
allowed per QS link.
• The QSE-CI-NWK-E is QuantumTM compatible. Refer to
the QuantumTM System Specification Sheet for
compatibility details.
Requirements
• QS Link Power Supply, such as a:
- GRAFIK Eye QS.
- QS Link power supply, such as the QSPS-P1-1-50.
• QS Communication Link Wire (PELV, Class 2: USA)
- Two 18 AWG (1.0 mm2) conductors for control power.
- One twisted, shielded pair of 22 AWG (0.34 mm2) for
data link.
- Available from Lutron, part number GRX-CBL-346S;
check compatibility in your area.
Protocol
• Protocol document P/N 040-241 included on a CD
accompanying the packaged QSE-CI-NWK-E.
• Also available for download at www.lutron.com/qs
(search for 040-241).
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Job Number:
Model Numbers:
Page 1
QSE-CI-NWK-E
QS System
Control Interfaces
qse-ci-nwk-e-2 09.24.09
Dimensions
2.50 in.
(63.5 mm)
Mounting
Holes
PELV (Class 2: USA)
Wiring
Power (LED 1)
RS232 Link TX
(LED 4)
QS Link to other
wired QS system
devices
3.75 in.
(95.3 mm)
4.26 in.
(108.2 mm)
RS232 Link RX
(LED 5)
MUX Link TX
(LED 6)
Female 9-pin
RS232 Link
(to PC or AV
Equipment
5.26 in.
(133.6 mm)
1.06 in.
(26.9 mm)
Ethernet Link
(to PC or AV
Equipment
MUX Link RX
(LED 7)
DIP Switches
Ethernet Act
(LED 2)
Unused
(LED 3)
Mounting
• Mounts directly to the wall.
• 19 in. AV rack mountable with 1U rack shelf from Lutron
Model # LUT-19AV-1U.
• For conduit wiring options, use LUT-5x10-ENC.
LUT-19AV-1U
QSE-CI-NWK-E
Wall
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Job Number:
Model Numbers:
LUT-5x10-ENC
Page 2
QSE-CI-NWK-E
QS System
Control Interfaces
qse-ci-nwk-e-3 09.24.09
Specifications
Power
Ethernet Connection
• Low-voltage PELV (Class 2: USA).
• Operating Voltage: 24 V
60 mA.
• Uses two (2) power draw units on the QS link.
Environment
• 32 - 104 °F (0 - 40 °C). Relative humidity less than
90% non-condensing.
Integration Features
• Monitoring: Current scene, zone level, button
presses, shade group levels.
• Control: Scene selection, scene lockout, zone
lockout, sequencing, zone raise/lower, master
raise/lower,
set shade group level, simulate button press/release.
• Standard CAT5 (or better) cable, 100 m (328 feet)
maximum, connects the QSE-CI-NWK-E interface
to a PC or other Ethernet source.
• Supports MDI/MDIX auto-crossover (no crossover
cable needed).
• Auto-negotiation of 10 or 100 Mbps speed and
full- or half-duplex operation.
• Default IP address is 192.168.250.1. Can be
changed using the Lutron DeviceIP tool located
on the accompanying CD.
Note: Either the RS232 or the Ethernet can be
used, but not both.
For the full list of features and commands, please
refer to the protocol document on the
accompanying CD, also available at
www.lutron.com.
RS232 Connection
• Standard 9-pin female serial connector on interface.
Use the included serial cable with standard 9-pin
male connectors to connect to RS232 equipment.
• 50 foot (15 m) maximum serial cable length.
• Dip switches are set at factory, all Off.
• Dip switches are used to set RS232 baud rate:
DIP Switch Settings for RS232 Baud Rate
115200
(default)
38400
19200
9600
1 2 3 4 5 6 7 8
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Job Number:
Model Numbers:
Page 3
QSE-CI-NWK-E
QS System
Control Interfaces
qse-ci-nwk-e-4 09.24.09
RS232 Link Wiring
• 9-pin to 9-pin serial cable provided.
• Standard 9-pin serial connector plugs into RS232
equipment, and to QSE-CI-NWK-E.
• Must be 50 feet (15 m) or less.
RS232 Signals
Pin on 9-pin Cable
5
3
2
Signals
Com
TxD
RxD
Ethernet Link Wiring
• Standard CAT5 cable connects QSE-CI-NWK-E Interface to PC, router, or other
Ethernet source.
• No crossover cable needed.
• Must be 100 m (328 feet) or less.
• Ethernet network and cable provided by others.
Control Interface Wiring
CAT5 Cable
328 ft. (100 m)
Maximum
RS232 Cable
50 ft. (15 m)
RS232 Link
Maximum
COM To PC or AV
TxD Equipment
RxD
To external transformer
QS Link
4321
Rear View of GRAFIK Eye QS Control Unit
Do not connect #2 if
using external power
supply
1 2
A B C
1 2 3 4
Lutron Cable
GRX-CBL-346S
1 2 3 4 5 6 L N
To additional QS devices
QS Link:
1: Common
2: Power
3: MUX
4: MUX
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Job Number:
Model Numbers:
Page 4
QSE-CI-NWK-E
QS System
Control Interfaces
qse-ci-nwk-e-5 09.24.09
PELV (Class 2: USA) QS Link Low-Voltage Requirements and Wiring
•
•
•
•
•
System communication uses low-voltage wiring.
Wiring can be daisy-chained or T-tapped (see below).
Wiring must be run separately from line/mains voltage.
Each PELV (Class 2:USA) terminal accepts up to two 18 AWG (1.0 mm2) wires.
PELV (Class 2:USA) wiring link requires:
- Two 18 AWG (1.0 mm2) conductors for control power.
- One twisted, shielded pair of 22 AWG (1.0 mm2) for data link.
- Available from Lutron, P/N GRX-CBL-346S; check compatibility in your area.
• Total length of control link must not exceed 2,000 ft (610 m).
• Connect the terminal 1, 3, and 4 connections to all control units, wallstations, and control interfaces. See
Powering the QSE-CI-NWK-E for pin 2 connectivity.
Daisy-Chain Wiring Example
SeeTouch QS
wallstations
QS Control Unit
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
QSE-CI-NWK-E
LUTRON
LUTRON
Sivoia QS power panel
T-Tap Wiring Example
SeeTouch QS
wallstations
QS
Control
Unit
LUTRON
Sivoia QS
power panel
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
Sivoia QS
shade
QSE-CI-NWK-E
(powered separately)
LUTRON
Output
QSPS Power Supply
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Job Number:
Model Numbers:
Page 5
QSE-CI-NWK-E
QS System
Control Interfaces
qse-ci-nwk-e-6 09.24.09
PELV (Class 2: USA) Terminal Connections
When used with GRAFIK Eye QS Control Units
(terminal 2). Ensure that the
• Two 18 AWG (1.0 mm2) conductors for Common (terminal 1) and 24 V
terminal 2 connection is wired correctly. Refer to GRAFIK Eye QS Specification Submittal for more details.
• One shielded, twisted pair 22 AWG (0.5 mm2) for data link (terminals 3 and 4).
Data Link - (1) twisted, shielded
pair 22 AWG (0.5 mm2)
3: MUX
4: MUX
D: Drain/Shield
(2) 12 AWG
(2.5 mm2)
(1) 18 AWG
(1.0 mm2)
QSE-CI-NWK-E
PELV (Class 2: USA)
Control wiring
1: Common
2: 24 V
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Job Number:
Model Numbers:
(1) 18 AWG
(1.0 mm2)
(2) 12 AWG
(2.5 mm2)
Page 6
QSE-CI-NWK-E
QS System
Control Interfaces
qse-ci-nwk-e-7 09.24.09
Powering the QSE-CI-NWK-E
• The QSE-CI-NWK-E uses two (2) power draw units on the QS link.
Power for one QSE-CI-NWK-E counts as two devices toward the maximum of three devices per GRAFIK
Eye QS Wireless Control Unit when powered off of Pin 2 of the GRAFIK Eye QS.
• Another option is to power the QSE-CI-NWK-E from a QS Link power supply
(QSPS-P1-1-50, QSPS-P2-1-50, or QSPS-P3-1-50) or a QS shade panel power supply
(QSPS-P2-10-60 for 230 V , or QSPS-P1-10-60 for 120 V ).
Wiring Examples
QSE-CI-NWK-E Powered by a GRAFIK Eye® QS Wireless
Rear View of GRAFIK Eye QS Control unit
QS Link
4 3 2 1
1 2
A B C
1 2 3 4
Lutron Cable
GRX-CBL-346S
QS Link:
1: Common
2: Power
3: MUX
4: MUX
1 2 3 4 5 6L N
Wire strip length
3/8 in.
3/8(10in mm)
(10 mm)
QSE-CI-NWK-E Powered by a QSPS Power Supply
GRAFIK Eye QS
Control unit
SeeTouch QS
wallstations
LUTRON
LUTRON
QSE-CI-NWK-E
powered separately
by QSPS
LUTRON
LUTRON
QS Link: Lutron Cable GRX-CBL-346S
QSPS
power
supply
R
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Job Number:
Model Numbers:
Page 7
Was this manual useful for you? yes no