Vive Comfort TP-N-851 Installation manual
Add to my manuals12 Pages
Vive Comfort TP-N-851 is a programmable thermostat compatible with various systems including gas or oil heat, electric furnace, heat pumps, and multi-stage systems. It features a user-friendly interface with a large LCD display, customizable temperature settings, and a filter change reminder. Its energy-saving capabilities allow for efficient temperature management, helping you save on utility bills. Additionally, the thermostat's compatibility with common wire and battery backup options provides added flexibility and reliability.
advertisement
INSTALLATION MANUAL
TM
C O M F O R T
TP-N-851
VIVE Comfort
1111 S. Glenstone Ave., Suite 2-100
Springfield, MO 65804
Toll-Free: 1-800-776-1635 Web: www.vivecomfort.com
Hours of Operation: M-F 9AM - 6PM Eastern
Thermostat Applications Guide
Description
Gas or Oil Heat
Electric Furnace
Heat Pump (No Aux. or Emergency Heat)
Heat Pump (with Aux. or Emergency Heat)
Multi-stage Systems
Heat Only Systems
Cool Only Systems
Millivolt
Table of Contents
Installation Tips
Thermostat Quick Reference
Subbase Installation
Wiring
Technician Setup
Mounting and Battery Installation
Specifications
Page
2
3
4
5-6
7-10
11
12
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Power Type
Battery Power
Hardwire (Common Wire)
Hardwire (Common Wire) with Battery Backup
A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
Una versión en español de este manual se puede descargar en la página web de la compañía.
Patents and Trademarks pending.
Copyright © 2013. All rights reserved.
Rev. 1341
1
INSTALLATION TIPS
Wall Locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
NO
NO
NO YES
Do not install thermostat in locations:
• Close to hot or cold air ducts
• That are in direct sunlight
• With an outside wall behind the thermostat
• In areas that do not require conditioning
• Where there are dead spots or drafts (in corners or behind doors)
• Where there might be concealed chimneys or pipes
Installation Tip
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
2
THERMOSTAT QUICK REFERENCE
Getting to know your thermostat
2
Indicates the current room temperature.
1
Use the “+” or “-” keys to select your desired room temperature. A copy of the Operating Manual can be downloaded at www.pro1iaq.com
3 4
Fan System
5
6
Low Battery Indicator:
Replace batteries when indicator is shown.
Displays the user selectable setpoint temperature.
System operation indicators:
The COOL, HEAT or FAN icon will display when the COOL,
HEAT or FAN is on.
NOTE: The compressor delay feature is active if these icons are flashing. The compressor will not turn on until the 5 minute delay has elapsed.
1
2
3
LCD Display
Glow in the Dark Light Button
Fan Switch
4
System Switch
5 Menu Button Access Door
6
Temperature Setpoint Buttons
Important:
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery with in 21 days, the thermostat display will only show the low battery indicator as a final warning before the thermostat becomes inoperable. The batteries are located on the back of the
Thermostat.
Removing the private label badge
Use the bevel on lower ridge
Magnet in door
About the Badge
All our thermostats use the same universal magnetic badge.
Visit our website to learn more about our dealer imprinting programs.
Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counter clockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily.
Do not use force.
3
Caution:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electric shock or equipment damage.
For vertical mount put one screw bottom.
For horizontal mount put one screw left and one screw right.
SUBBASE INSTALLATION
Mercury Notice:
All of the our thermostats are mercury free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and
Vertical Mount
Horizontal Mount
Horizontal Mount
Vertical Mount
4
WIRING
1
2
3
4
Power supply
Factory-installed jumper. Remove only when installing on 2-transformer systems
Use either O or B terminals for changeover valve
Optional 24 VAC common connection when thermostat is hardwired with battery backup mode.
Typical 2H/2C system: 1 transformer
C
L2
L1 (HOT)
RC
R
Y
C
W/E
G
W
Y2
6
2
COMPRESSOR
RELAY
HEAT RELAY
FAN RELAY
HEAT RELAY 2
R
1
COMPRESSOR
RELAY 2
RC
R
Y
C
W/E
G
W
Y2
Typical 3H/2C heat pump system
C
L2
L1 (HOT)
2
COMPRESSOR
RELAY
FAN RELAY
AUXILIARY
4
R
1
COOL CHANGE OVER
VALVE
HEATL CHANGE
OVER VALVE
COMPRESSOR RELAY
2
3
Typical heat-only system with fan
C
RC
R
Y
2
R
C
W/
G
4
FAN RELAY
1
L2
L1 (HOT)
HEAT RELAY
O
B
RC
R
Y
C
W/E
G
W
Y2
Typical 2H/2C system: 2 transformer
REMOVE JUMPER C
2
R
1
L2
L1 (HOT)
COMPRESSOR
RELAY
FAN RELAY
HEAT RELAY
HEAT RELAY 2
COMPRESSOR
RELAY 2
Typical cool-only system
RC
R
Y
C
W/
G
4
2
COMPRESSOR
RELAY
FAN RELAY
4
Typical heat-only system
RC
R
Y
C
W/
G
2
4
HEAT RELAY
C
R
1
L2
L1 (HOT)
C
R
1
L2
L1 (HOT)
C
R
1
L2
L1 (HOT)
NOTE:
In many systems with no emergency heat relay a jumper can be installed between E and W2.
5
WIRING
Wiring
1.
2.
If you are replacing a thermostat, make note of the terminal connections on the thermostat that is being replaced. In some cases the wiring connections will not be color-coded.
For example, the green wire may not be connected to the G terminal.
Loosen the terminal block screws. Insert wires then retighten terminal block screws.
3.
Place nonflammable insulation into wall opening to prevent drafts.
Warning
All components of the control system and the thermostat installation must conform to
Class II circuits per the NEC
Wire specifications
Use shielded or non-shielded
18-22 gauge thermostat wire.
Terminal Designations
This thermostat is shipped from the factory to operate a conventional heating and cooling system. This thermostat will also operate a heat pump system. See the “heat pump” configuration step on page 8 of this manual to configure the thermostat for heat pump applications.
Terminal
RC
B
O
RH
C
G
2 Heat 2 Cool
Conventional System
Transformer Power
(cooling)
Transformer Power
(heating)
Transformer common
Energized in heating
Energized in cooling
Fan relay
2 Heat 2 Cool
Heat Pump System
Transformer Power
(cooling)
Transformer Power
(heating)
Transformer common
Heat pump changeover valve energized in heating
Heat pump changeover valve energized in cooling
Fan relay
3 Heat 2 Cool
Heat Pump System
Transformer Power
(cooling)
Transformer Power
(heating)
Transformer common
Heat pump changeover valve energized in heating
Heat pump changeover valve energized in cooling
Fan relay
W/E
Y
First stage of heat
First stage of heat
Emergency heat relay
Y2
W2
First stage of cool
Second stage of cool
Second stage of heat
Wiring Tip
C terminal
The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.
First stage of cool
Second stage of cool
Auxiliary heat relay, second stage of heat
Note:
First stage of heat & cool
Second stage of cool
& second stage of heat
Auxiliary heat relay, thirdstage of heat
In many systems with no emergency heat relay, a jumper can be installed between E and W2.
6
TECHNICIAN SETUP MENU
Technician Setup Menu
This thermostat has a technician setup menu for easy installer configuration. To setup the thermostat for your particular application:
1.
+ seconds. This 3-second delay is designed so that homeowners do not accidentally access the installer settings.
2.
Configure the installer options as desired, using the table below.
3.
+ settings and the SYSTEM or FAN key to move from one option to another. Note:
To exit the Technician Setup options press and hold the & keys for 3 seconds.
+ -
Tech Setup Steps
Filter
Change
Reminder
Room
Temperature
Calibration
This feature will flash “FILT” in the display after the elapsed run time to remind the user to change the filter. A setting of
“OFF” will disable this feature.
This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70° and you would like it to read
72° then select +2.
Minimum
Compressor On
Time
This feature allows the installer to select the minimum run time for the compressor. For example, a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature.
LCD Will Show
Compressor
Short Cycle
Delay
The compressor short cycle delay protects the compressor from
“short cycling”. This feature will not allow the compressor to be turned on for 5 minutes after it was turned off.
Cooling
Swing
The swing setting often called “cycle rate”, “differential” or
“anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.
Heating
Swing
Keypad
Lockout
The swing setting often called “cycle rate”,
“differential” or
“anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.
Keypad lockout allows you to configure the thermostat so that none or some of the keys do not function.
Adjustment Options
You can adjust the filter change reminder from
“OFF” to 2000 hours of runtime in
50 hour increments.
You can adjust the room temperature display to ready -4°F to +4°F above or below the factory calibrated reading.
You can select the minimum compressor run time from “OFF”,
“3”, “4”, or “5” minutes.
If 3, 4, or 5 is selected, the compressor will run for at least the selected time before turning off.
Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Select “OFF” to remove this delay.
The cooling swing setting is adjustable from 0.2°F to 2°F.
For example: A swing setting of 0.5°F will turn the cooling on at approximately 0.5°F above the setpoint and turn the cooling off at approximately
0.5°F below the setpoint.
The heating swing setting is adjustable from 0.2°F to 2°F. For example: A swing setting of 0.5°F will turn the heating on at approximately 0.5°F below the setpoint and turn the heating off at approximately 0.5°F below the setpoint.
OF = keypad lockout has been disabled.
PA = partial keypad lockout, which locks all the keys except the
or keys.
FU = Full keypad lockout, which locks out all the keys.
Note: keypad lockout instructions are below.
Factory Default Setting
OFF
0 ºF
OFF ON
0.5 ºF 0.4 ºF 0ºF
Note:
To lock the keypad hold down the SYSTEM and FAN keys for 3 seconds. You will see a lock in the display. To unlock the keypad hold down SYSTEM and FAN keys for 3 seconds.
TECH SETUP
STEPS CONTINUED
ON THE NEXT PAGE
7
TECHNICIAN SETUP MENU
Tech Setup Steps (Continued from the previous page)
Heating
Temperature
Setpoint Limit
This feature allows you to set a maximum heat setpoint value. The setpoint temperature cannot be raised above this value.
Cooling
Temperature
Setpoint Limit
This feature allows you to set a minimum cool setpoint value. The setpoint temperature cannot be lowered below this value.
ºF or ºC
Select F for
Fahrenheit temperature read out or select C for Celsius read out.
Fan
Operation
Select GAS for systems that control the fan during a call for heat.
Select ELEC to have the thermostat control the fan during a call for heat.
Always On
Light Menu Setup
The display light can be configured to stay on at all times or come on when any key is pressed.
NOTE:
HARDWIRED ONLY
Keeping the display light continually “ON” will greatly reduce battery life.
Contractor Call
Number
On or Off
Allows you to select whether or not you want to add your phone number to the thermostat display.
You can choose ON or
OFF.
Contractor
Call Number
Allows you to put you phone number in the display.
LCD Will Show
Adjustment Options
Use the or key to select the maximum heat setpoint.
Use the or key to select the maximum cool setpoint.
º F for Fahrenheit
º C for Celsius
GAS or
ELEC
OFF configures display light to come on when the light key or any other key is pressed.
ON configures the display to stay on.
Use the or key to turn on or off.
If selected ON, you will see the input screen after pressing
SYSTEM key and moving to the next step.
See note below on operation.
Use the key to step through each number left to right and the key to cycle through each of the numbers.
Factory Default Setting
90
ºF
44
ºF ºF
GAS ON
Note:
If Contractor Call Number is selected ON, your phone number will show in the display if there has been a continuous call for heating or cooling for 24 hours or if the light button is held down for 3 seconds.
To remove the phone number from the display, hold the light button down for 3 seconds.
OFF
TECH SETUP
STEPS CONTINUED
ON THE NEXT PAGE
0000000000
A Note About Auto Changeover:
If in Auto you have the ability to switch between Auto Heat or Auto Cool by pressing the System key. This can be done once the current mode has reached its setpoint. For example: if in Auto
Heat, the heat setpoint must be satisfied before the thermostat will allow you to switch to Auto
Cool. You can switch out of Auto by holding down the System key. To get back into Auto, you must toggle the System key to Auto.
8
TECHNICIAN SETUP MENU
Tech Setup Steps (Continued from the previous page)
Beep Heat Pump System
Switch
When any key is pressed an audible beep will sound.
You can choose
ON or an OFF.
Gas Auxiliary for Heat Pump
Stages of Heat
When turned on the thermostat will operate a heat pump.
1. EM. Heat will show as an option in the system switch.
2. Y will be first stage of heat & cool,
W/E will be emergency heat relay & W2 will be auxiliary heat relay.
You can configure the system switch for the particular application:
Heat - Off- Cool
Heat – Off,
Cool – Off
Heat – Off – Cool-Auto
Gas Auxiliary for Heat
Pump
This option will turn the heat pump off 45 seconds after the auxiliary heat relay turns on.
Note: EM. Heat will show if in heat pump mode.
For 2 heat applications, the first stage will turn off 45 seconds after the auxiliary stage turns on.
For 3 heat applications, the first and second stage will turn off 45 seconds after the auxiliary stage turns on.
You can configure the thermostat to operate a 3 stage heat pump system.
2H 2C = 2 heat, 2 cool
3H 2C = 3 heat, 2 cool
Cooling Fan
Delay
The cooling fan delay setting will delay the fan from coming on in cool-mode and keep running after the compressor shuts off for a short time to save energy in some systems.
LCD Will Show
Adjustment Options
If ON is selected the beep will sound.
If OFF is selected there is no sound
OFF configures the thermostat for non heat pump systems.
ON configures the thermostat for heat pump systems.
Use the or key until the desired application is flashing.
For heat pump systems that are “dual fuel” (use a gas furnace for auxiliary stage heat) you can turn this feature on to turn off the heat pump when the auxiliary stage of heating has been called for.
Use the or key to change between 2 heat and 3 heat.
2 heat will use Y1 as first stage and W2 as auxiliary.
3 heat will use Y1 as first stage, Y2 as second stage and W2 as auxiliary.
You can select the
Cooling Fan Delay from “OFF”, “15”, “30”,
“60”, or “90” seconds.
If 15, 30, 60 or 90 is selected the fan will not turn on for that many seconds when there is a call for cool will run for that many seconds after satisfying a call for cool.
Factory Default Settings
ON OFF
Heat – Off – Cool
OFF
2 Stages OFF
TECH SETUP
STEPS CONTINUED
ON THE NEXT PAGE
Swing Setting Tip
The Second stage will turn on at 2x the swing setting. The second stage will turn off when the 1x the swing is reached. For example, if the swing setting is .8 degrees for heating and the thermostat is set at 70°F, the first stage will turn on at approximately 69.2°F. The second stage will turn on at 68.4°F. The second stage will turn off at 69.2°F and the first will turn off at 70.8°F. If third stage is used, it will turn on at 3x the swing and turn off at approximately 2x the swing.
9
TECHNICIAN SETUP MENU
Tech Setup Steps (Continued from the previous page)
Satisfy Setpoint
Staging Delay Humidity Pad
Reminder
This feature allows the thermostat to keep multiple stages of heat or cool energized until setpoint is satisfied.
This feature allows a delay to occur when a second and third stage is needed. This allows the previous stage extra time to satisfy setpoint.
This will remind the user to change the humidity pad.
UV Lamp
Reminder
Will remind the user to change the UV light bulb.
IAQ Cell Reminder
Will remind the user to change the IAQ
Cell after 25,000 hrs.
LCD Will Show
Adjustment Options
Use the or key to turn on or off.
Use the or key to select YES, 5,
10, 15, 30, 45, 60,
90.
Use the or key to select OFF,
600, 1000, 1500,
2000.
Use the or key to select OFF,
1YEAR, 2YEAR.
Use the or key to select OFF,
250. (Stands for
25000 hours)
Factory Default Settings
OFF
OFF OFF OFF OFF
10
MOUNT THERMOSTAT & BATTERY INSTALLATION
Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Battery Installation
Battery installation is optional if thermostat is hardwired (C terminal connected).
On the back of the thermostat insert 2
AA Alkaline batteries (included).
11
SPECIFICATIONS
Specifications
The display range of temperature
The control range of temperature
Load rating
Display accuracy
Swing (cycle rate or differential)
Power source
Operating ambient
Operating humidity
Dimensions of thermostat
41ºF to 95ºF (5ºC to 35ºC)
44ºF to 90ºF (7ºC to 32ºC)
1 amp per terminal, 1.5 amp maximum all terminals combined
± 1ºF
Heating is adjustable from 0.2ºF to 2.0ºF
Cooling is adjustable from 0.2ºF to 2.0ºF
18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire (common wire)
Battery power from 2 AA Alkaline batteries
32ºF to +105ºF (0º to +41ºC)
90% non-condensing maximum
5.7”W
x 4.4 ”H x 1.1”D
12
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project