Multi Digital Temp Controller (FX3D SERIES)

Multi Digital Temp Controller (FX3D SERIES)
REV. 2009.11.06
Multi Digital Temp Controller (FX3D SERIES)
Connection Diagram
FX3D
OPTION
MODULE
10A, 250Vac
OUT1
OUT2
POWER
VDC+
L1 VDC-L2
1
COM
c
2
3
4
5
6
7
8
mA
+VDC
9 10 11
+
+ -
AC100 - 240 V ~
50/60Hz
DC12V
NTC
Transmitter
ㅇ OUT1 : Cooling/Heating #1 ON/OFF output
ㅇ OUT2 : Cooling/Heating #2 ON/OFF output
ㅇ COM : Signal input common terminal
ㅇ NTC : Temp. sensor input
ㅇ mA : 4~20mA signal input
ㅇ +VDC : 4~20mA sensor power (12Vdc)
PreCaution for Use
1. This product may cause an electric shock in handling. Please do not attempt to open it with
power turned on.
2. This product should be installed in a place fixed secured by a rack or panel.
3. This product can be used under the following environmental condition
① Indoor ② Pollution Degree ③ At an altitude of 2000m or below ④ Installation Category Ⅱ
4. To turn on or turn off power supply for this product, please the circuit breaker or switch of
a standard product of IEC 60947-1 or IEC 60947-3 product and install it within a close distance
allowing convenient operation by user.
5. Please be understood that if this product is dismantled or modified discretionary,
after sales service will not be able to be provided.
6. An output wire to be used for this product should be inflammable grade FV1
(V-1 grade or above), he thickness of the wire should be AWG No. 20 or above. (0.50㎟)
7. In order to prevent it from an inductive noise, please maintain the high-voltage wire and
power wire separated.
8. Please avoid installing the product in a place where a strong magnetism, noise,
severe vibration and impact exist.
9. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.
10. The sensor wire and signal wire should be away from the power and load wires using
conduits separately installed.
11. Please avoid using the product near a device generating strong high frequency noise
(high-frequency welding machine, high-frequency sewing machine, high-frequency
radiotelegraph, high capacity SCR controller)
12. Product’s damages other than those decribed in the guarantee conditions provided by
the manufacturer shall not be respoinsible by us.
13. Please use with being attached to a dual safety device in case of using for controlling instruments
which could be effective to human life or property (eg: controlling atomic energy, medical
instruments, cars, trains, flights, burners, amusement instruments or safety machinery)
NTC
ㅇ Sensor
ㅇ Option
NTC temp. sensor
connection
4~20mA signal input
COM
NTC
COM
8
9
8
NTC
4~20mA loop
power sensor connection
mA
mA
9 10
+VDC
10 11
RS-485 COMM.
OPTION MODULE
RS-232 COMM.
OPTION MODULE
4~20mA Output
OPTION MODULE
1
1
1
2
TRX
2
RXD
2
4~20mA
3
TRX
3
TXD
3
4~20mA
Basic Specification
4
SG
4
GND
4
SG
Model
FX3D
Power
AC100 - 240V~, 50/60Hz
DC12V
4~20mA Output & RS-485 COMM.
OPTION MODULE
Current
Max 4VA
1
TRX
Connector
Input / Output
Screw Bolt Connector (1.5㎟ Wire Use Possibility)
2
TRX
WHITE
Relay output 2p (250Vac/10A)
3
4~20mA
GREEN
Operation
Temp. -10~50℃, Humidity Under 90%RH
4
4~20mA
BLACK
Storage
Temp. -20~60℃, Humidity Under 90%RH
Sensor
Temp. sensor : DOTECH Standard NTC sensor DPR-TH1
5kΩ at 25℃, Limit : -50 ~ 105℃, Accuracy : ±0.3℃ at 25℃
Temp. sensor : DOTECH Standard NTC sensor DPR-TH2
10kΩ at 25℃, Limit : -50 ~ 150℃, Accuracy : ±1.5℃ at 25℃
※ The Aforementioned precautions must be observed, and if you fail to do so,
it may cause a product’s breakdown.
Temp. sensor input 1p / 4~20mA input 1p(Built-in sensor power supply)
RED
Constitution (Function of Display Lamp and Button)
FX3D
OUT1
OUT2
Order Information
FX3D – 00 : Basic Model (DPR-TH1-ET sensor is provided basically)
FX3D – R4 : RS-485 Comm. model (Comm. function MODBUS RTU MODE) ※
FX3D – R2 : RS-232 Comm. model (Install log printer, Trans text message) ※
FX3D – A1 : 4~20mA Trans output model
FX3D – A1R4 : 4~20mA Trans output & RS-485 Comm. model ※
※ Comm. cable is provided basically
Dimensions and Panel Cut-Out Form
OUT1
Turn on when output #1 is ON (Flickering at standby)
OUT2
Turn on when output #2 is ON (Flickering at standby)
Display temp. value
8
70
78
ON at trip, Flickering at alarm
FX3D
OUT1
OUT2
35
28
over
Use at program setup
Move between menus &
Increase setup value
Execute selected menu or
Input setup value
Move between menus &
Decrease setup value
Initializing
setup value
If pushing for 10 sec. at the same time ,
setup value is initialized
over
Confirm
temp. sensor
At the same time, it displays the 1st decimal
place for the current temp.
Unit
DOTECH,INC l http://www.dotech21.com
business@dotech21.com
6F, JOONGANG-ILBO 778 Wonsi-Dong, Danwon-Gu, Ansan-Si,
Gyeonggi-Do, Korea TEL : +82-31-495-3767 / FAX : +82-31-495-3917
1
Temperature Setting Group
Simple Trouble Check Point
In case of error occurring, the following messages are flickering at every 0.5 sec intervals.
Display Current Temp.
Run Mode
In Case of change of set value by an unknown case.
In Case of Input Sensor Open Wire (Normal operation after sensor connecting)
●
Push for 3 sec.
intervals and this set point can be established by using the
▲ key or ▼ key.
After changing set point, it displays the current temp.
In Case of Sensor Short Circuit
Lower Sensor Input than Measuring Range (SL)
Output #1 setup value
Set output #1 setup value.
Higher Sensor Input than Measuring Range (SH)
Lower Low Limit Alarm than Low Limit Alarm Value (ALL)
Higher High Limit Alarm than High Limit Alarm Value (ALH)
※In case of the above-mentioned error, it will be normally operated with cancelling error status
if the reason of error is solved.
Output #2 setup value
Set output #2 setup value.
● If there’s no input made for a period of 60 seconds during the setting,
then it returns back to the run mode automatically.
Setting 1 Group
Run Mode
Display Current Temp.
Push for 3 sec.
Push for 3 sec.
Select Control Type #1
Set control function of control output #1.
Select Control Type #2
Set control function of control output #2.
No use output function
(Use display mode only.)
No use output function
(Use display mode only.)
Use cooling control only
(Use OVER temperature sensing only.)
Use cooling control only
(Use OVER temperature sensing only.)
Use heating control only
(Use UNDER temperature sensing only.)
Use heating control only
(Use UNDER temperature sensing only.)
Control Deviation Value #1
Control Deviation Value #2
Set control sensitivity of control output #1.
Setting Range 0.1 ~ 99.9℃.
Set control sensitivity of control output #2.
Setting Range 0 ~ 19.9℃.
ON Delay Time #1
ON Delay Time #2
Output after delaying during
setting delay time
in case of control output #1 ON.
Output after delaying during
setting delay time
in case of control output #2 ON.
Minimum OFF Time #1
Minimum OFF Time #2
No output within Min. OFF time
after control output #1 OFF.
No output within Min. OFF time
after control output #2 OFF.
Minimum ON Time #1
Minimum ON Time #2
Maintain ON in spite of OFF condition
during Min. ON time after ON.
Maintain ON in spite of OFF condition
during Min. ON time after ON.
Select Deviation Type #1
Select Deviation Type #2
Select deviation type of control output #1.
+ Deviation control
Select deviation type of control output #2.
+ Deviation control
± Deviation control
± Deviation control
e.g)Condition : Cooling mode,
setting temp.10.0℃, deviation 1.0℃.
+Deviation control : ON at 11.0℃ , OFF at 10.0℃.
±Deviation control : ON at 10.5℃ , OFF at 9.5℃.
e.g)Condition : Cooling mode,
setting temp.10.0℃, deviation 1.0℃.
+Deviation control : ON at 11.0℃ , OFF at 10.0℃.
±Deviation control : ON at 10.5℃ , OFF at 9.5℃.
Max. Set Point #1
Set a maximum value of the set temperature
available to be set by user.
Min. Set Point #1
Set a minimum value of the set temperature
available to be set by user.
Max. Set Point 21
Set a maximum value of the set temperature
available to be set by user.
Min. Set Point #2
Set a minimum value of the set temperature
available to be set by user.
2
2
Setting 2 Group
Run Mode
Analogue Trans. Output
(4~20mA) Mode (-A1 model)
Display Current Temp.
Current Temp.
Push for 5 sec.
Push for 3 sec.
Select Lock Function
Heating proportional Control
Select lock function
Lock cancel
Cooling proportional Control
Setting 1group
Set value Temp.#1
Setting 1, 2 group lock
Set value Temp.#2
Setting 1, 2group,
temp. setup lock
Setup Value Unification Mode
Unify required setup value of
output#1 and output#2
Separate use at OFF
Unified use at ON
Select Sensor Type
Select temp. sensor type
Use DPR-TH1 sensor
(Range -50~105℃)
Use DPR-TH2 sensor
(Range -50~150℃)
Output #2, Select Extended Function
Use 4~20mA input sensor
(Range SL ~ SH)
Select extended function of output#2
Use Output#1 Set value
(Range UL I~UH I )
Alarm output function OFF
Use Output#2 Set value
(Range UL2~UH2 )
Output ON at sensor alarm
+ high limit alarm
Use Output#1, #2 Set value
with sensor input ON/OFF
Output ON at sensor alarm
+ low limit alarm
Max. Sensor Input Range
Set maximum sensor input range
Output ON at sensor alarm
+ high/low limit alarm
Output ON & manual reset
at sensor alarm + high limit alarm
Output ON & manual reset
at sensor alarm + low limit alarm
Min. Sensor Input Range
Output ON & manual reset
at sensor alarm + high/low limit alarm
Set minimum sensor input range
Regular cycle timer function
Use as heater defrost function
Use as hot gas defrost function
Display Unit
Output #2, Timer OFF Time (Defrost Cycle)
Display celsius
Maintain OFF condition during timer
OFF time or defrost cycle.
(* Unit : minute)
Display fahrenheit
Decimal Point Display
Select decimal point display method
Display 1st decimal place
Output #2, Timer ON time (Defrost Time)
Display computing of 1/10
Maintain ON condition during timer
ON time or defrost cycle.
(* Unit : minute)
Correct Temp. Sensor
Correct the accuracy of the temp. sensor
e.g) If displayed temp. is
19℃ and I/O temp is 18℃,
it is corrected by inputting -1.0 ℃
Alarm Range High Limit
Set high limit of alarm range.
Sensor Input Filter
Set a sensor input filter value.
In case of frequent hunting of the
current temp., it is corrected by
increasing filter value.
Alarm Range Low Limit
Set low limit of alarm range.
Sensor Value Display Cycle
Set the current temp. display cycle.
Alarm Sensing Hysteresis
Set hysteresis (sensibility) reset
of alarm range breakaway
Operation Cycle Output at
Error Occurrence #1
Set ON/OFF cycle of output #1 at
sensor error.
No operate at OFF
Operation Ratio Output at
Error Occurrence #1
Set ON/OFF ratio of output #1 at
sensor error
No display when CL1 is OFF
Communication Address (FX3D-R4)
1
Set communication address.
Setting 1 Group Table
NO
002
DESCRIPTION
CODE
UNIT
STEP
Output1 Select Control Type
MIN.
MAX.
: Cooling mode
: No use
0.1
0.1
99.9
1.0
ON Delay Time
Sec
1
0
999
1
Minimum OFF Time( ※1)
Sec
1
0
999
0
Minimum ON Time(※2)
Sec
1
0
999
5
Control Deviation Value
004
005
006
007
Select Deviation Type(※3)
008
Max. Set Point
℃
1
UL 1
009
Min. Set Point
℃
1
SL
Output2
: +Deviation
: ±Deviation
: Cooling mode
: No use
Select Control Type
SH
100
UH 1
-45
: Heating mode
K
0.1
0.1
20.0
1.0
ON Delay Time
Sec
1
0
999
2
013
Minimum OFF Time(※1)
Sec
1
0
999
0
014
Minimum ON Time(※2)
Sec
1
0
999
5
015
Select Deviation Type(※3)
016
Max. Set Point
℃
1
UL2
SH
100
017
Min. Set Point
℃
1
SL
UH2
-45
011
012
Control Deviation Value
USER SETUP
: Heating mode
K
003
010
DEFAULT
: +Deviation
: ±Deviation
※1) Min OFF Time : It doesn’t make it output within Min. OFF Time after output is OFF. During Min OFF Time, output lamp is turned on with output after it flickers every 1 second intervals.
※2) Min ON Time : It is for avoiding frequent ON/OFF of control output and maintains ON condition in spite of OFF condition during Min ON Time after being turned on.
※3) Select Deviation Type : It selects deviation type. e.g) Condition (Cooling, Setup value 10.0, Deviation 1.0)
In case of +deviation -> Operate at ON (11.0) / OFF (10.0)
In case of ±deviation -> Operate at ON (10.5) / OFF (9.5)
Setting 2 Group Table
NO
300
DESCRIPTION
Select Lock Function
CODE
UNIT
STEP
MIN.
:: Setting 1 group lock
:: Setting 1, 2 group lock
:: Setting 1, 2 group, temp. setup lock
: DPR-TH1 (-50~105℃)
Select Sensor Type
302
Max. Sensor Input Range ( ※1)
-
1
SL
303
Min. Sensor Input Range ( ※1)
-
1
-19.9
304
Display Unit
: 4~20mA signal input (In case of connecting with press.&humidity sensor)
: UL1 ~ UH1
105
SH
-50
:℉
0.1 : 0.1
1:1
0.1
-19.9
+19.9
0.0
Sensor Input Filter
Sec
0.1
0.1
5.0
2.0
Sensor Value Display Cycle
Sec
0.1
0.0
5.0
0.5
Operation Cycle Output at Error
Occurrence #1 (※2). Display TY1as C, H
Min
1
0
999
Operation Ratio Output at Error
Occurrence #1 (※2). Display TY1as C, H
%
1
0
100
308
312
: ℃,
+999
0.1
Correct Temp. Sensor
311
: ST1 or ST2
K
307
310
: UL2 ~ UH2
Decimal Point Display ( ※6)
306
309
DEFAULT
: DPR-TH2 (-50~150℃)
301
305
MAX.
: Lock cancel
Analogue Trans. Output(4~20mA) Mode
(-A1 model)
: Current Temp.
H : Heating proportional control
Cooling proportional control ST1,ST2 : Set value Temp.#1,2
PV
C:
Setup Value Unification Mode ( ※6)
50
PV
0N : : Unification mode
: Output #1 / output #2 separation mode
: Control output operate as the function set at TY2
Manual rest alarm (※4)
Automatic rest alarm
:
313
Output #2, Select Extended Function.
Display TY2 as OFF
:
:
: Output ON at sensor alarm
+ high limit alarm
: Output ON at sensor alarm
+ low limit alarm
: Output ON at sensor alarm
+ high/low limit alarm
:
:
:
: Output ON & manual reset
at sensor alarm + high limit alarm
: Output ON & manual reset
at sensor alarm + low limit alarm
: Output ON & manual reset
at sensor alarm + high/low limit alarm
: Timer output (Regular cycle timer output)
: Timer output (Regular cycle timer output : heater defrost)
: Timer output (Regular cycle timer output : hot gas defrost)
314
Output #2, Timer OFF Time (Defrost Cycle)
Min
1
0
999
315
Output #2, Timer ON time (Defrost Time)
Min
1
0
999
30
316
Alarm Range High Limit (※5)
-
0.1
ALL
SH
30.0
317
Alarm Range Low Limit (※5)
-
0.1
SL
ALH
-10.0
318
Alarm Sensing Hysteresis
K
0.1
0.0
99.9
1.0
319
Communication Address (FX3D-R4) (※7)
-
1
-64
64
360
1
※1) In case of low pressure control (pressure sensor range : -1~9bar), SH is set as ‘9’, SL is set as ‘-1’. In case of high pressure control (pressure sensor range : 0~30bar),
SH is set as ‘30’, SL is set as ‘0’.
In case of humidity control (humidity sensor range : 0~100%), SH is set as ‘100’, SL is set as ‘0’. In case of high temperature sensor, SH is set as ‘150’, SL is set as ‘-40’.
※2) Control Output Operation at Error Occurrence : When error occurs, control output repeatedly operates OFF/ON until error is reset.
e.g) In case of setting of operation cycle : 60minutes, ON ratio 20%, it repeatedly operates a cycle of OFF (48 minutes) / ON (12 minutes).
※3) Setup Value Unification Mode : In case of setting this function as ON, setup value is unified and controlled as 1 case.
※4) Manual Reset alarm : In case of selecting manual reset alarm, it is reset by re-inputting power or pushing PRG button rapidly 2 times.
※5) In case of occurrence of high or low limit alarm, it doesn’t affect control output #1 at all.
※6) Decimal point display : It sets the current value display unit as 0.1/1. i.e. In case of setting as ‘1’, it displays the current value with cutting the decimal place.