Hirschmann Automation and Control GmbH

Hirschmann Automation and Control GmbH
Product information
OZD Profi 12M G11
Fiber Interfaces:Fieldbus Repeater:Profibus LWL-Repeater:OZD Profi 12M G11
http://www.e-catalog.beldensolutions.com/link/57078-57141-57128-57129-38147/en/conf/uistate
Name
OZD Profi 12M G11
interface converter electrical/optical for PROFIBUS-field bus networks; repeater function; for quartz glass FO; approval for Ex-zone 2 (Class 1, Div. 2)
Delivery informations
Availability
available
Product description
Description
interface converter electrical/optical for PROFIBUS-field bus networks;
repeater function; for quartz glass FO; approval for Ex-zone 2 (Class 1, Div. 2)
Port type and quantity
1 x optical: 2 sockets BFOC 2.5 (STR); 1 x electrical: Sub-D 9-pin, female, pin assignment according to EN 50170 part 1
Type
OZD Profi 12M G11
Order No.
943 727-221
Electrical interface
Signal type
PROFIBUS (DP-V0, DP-V1, DP-V2 und FMS)
Bit rate
9.6; 19.2; 45.45; 93.75; 187.5; 500 kbit/s;
1.5; 3; 6; 12 Mbit/s (automatic setting)
Signal delay time (optional input/output)
<= 6.5 bit times
Input/output signal
RS 485 level
Input voltage range
-7 V ... +12 V
Galvanic isolation
no
Optical interface
Wavelength
860 nm
Cascadibility
not limited
More Interfaces
Power supply
5-pin terminal block, screw mounting
Signaling contact
5-pin terminal block, screw mounting
Measuring outputs "Optical input power"
2 mm sockets
Network size - length of cable
Single mode fiber (SM) 9/125 µm
-
Multimode fiber (MM) 50/125 µm
3000 m
13 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve
Multimode fiber (MM) 62.5/125 µm
3000 m
15 dB link budget at 860 nm; A = 3.5 dB/km, 3 dB reserve
Multimode fiber HCS (MM) 200/230 µm
1000 m
18 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve
Multimode fiber POF (MM) 980/1000 µm
-
Power requirements
Operating voltage
18 ... 32 VDC, typ. 24 VDC
Galvanic isolation
yes
Current consumption
max. 200 mA
Power consumption
4.8 W
Output voltage/output current (pin6)
5 VDC +5%, -10%, short circuit-proof/90 mA
Redundancy
Redundancy functions
redundant 24 V infeed
Ambient conditions
Operating temperature
0 ºC to +60 ºC
Storage/transport temperature
-40 ºC to +70 ºC
Relative humidity
<95% (non-condensing)
Hirschmann Automation and Control GmbH www.beldensolutions.com
08-03-2012
Page 1 of 2
Fiber Interfaces:Fieldbus Repeater:Profibus LWL-Repeater:OZD Profi 12M G11
http://www.e-catalog.beldensolutions.com/link/57078-57141-57128-57129-38147/en/conf/uistate
Mechanical construction
Dimensions (W x H x D)
40 x 140 x 77.5 mm
Mounting
DIN rail or mounting plate
Weight
500 g
Protection class
IP 40
Housing material
die-cast zink
Approvals
Issued or requested approvals
FM Class 1, Div. 2; C-Tick; according to directive 94/9/EG (ATEX 95): Ex II 3 G (Zone 2)
Scope of delivery and accessories
Scope of delivery
device, start-up instructions
Accessories to order separately
manual, order no. 039 629-001
For more information please contact:
Hirschmann Automation and Control GmbH
Stuttgarter Strasse 45-51
72654 Neckartenzlingen
Germany
Phone: +49 7127/14-1809
E-Mail: inet-sales@belden.com
The information published in the websites has been compiled as carefully as possible. It is subject to alteration without notice in technical as well as in price-related/commercial respect.
The complete information and data were available on user documentation. Mandatory information can only be obtained by a concrete query.
Hirschmann Automation and Control GmbH www.beldensolutions.com
08-03-2012
Page 2 of 2