Model FKB, FKD, FKM-F - Fuji Electric Corp. of America

Model FKB, FKD, FKM-F - Fuji Electric Corp. of America
ABSOLUTE, DIFFERENTIAL AND GAUGE PRESSURE
TRANSMITTER FOR REMOTE SEAL(S)
FKB, FKD, FKM...F
DATA SHEET
The FCX-AII series absolute, differential and gauge
pressure transmitters accurately measures and transmits
proportional 4 to 20 mAdc signal.
The transmitters utilize the unique micromachined capacitive silicon sensor with state-of-the-art microprocessor
technology to provide exceptional performance and
functionality.
FEATURES
1. High accuracy
0.065% accuracy is a standard feature for differential and
gauge pressure models and 0.2% accuracy for absolute
pressure models.
The microcapacitance silicon sensor assures this feature
for all elevated or suppressed calibration ranges without
additional adjustment.
2. Minimum inventory and design
Electronics unit, local indicators and electronics housing
are interchageable among all FCX-AII transmitters.
Our differential, gauge and absolute pressure transmitters
for remote seal(s) are welded design with reduced volume
flange welded on cell’s body to guarantee a perfect vaccum tightness and high pressure services.
0LQLPXPHQYLURQPHQWDOLQÀXHQFH
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in
DFWXDO¿HOGDSSOLFDWLRQV
4. Fuji/HART® bilingual communications protocol
FCX-AII series transmitter offers bilingual communications
to speak both Fuji proprietary protocol and HART ®. Any
HART® compatible devices can communicate with FCX-AII.
$SSOLFDWLRQÀH[LELOLW\
Various options that render the FCX-AII suitable for
almost any process applications include:
- Full range of hazardous area approvals
%XLOWLQ5),¿OWHUDQGOLJKWQLQJDUUHVWHU
- 5-digit LCD meter with engineering unit
- Stainless steel electronics housing
- Wide selection of materials
- High temperature, high vacuum seals
6. Programmable output Linearization Function
Output signal can be freely programmable. Up to 14 compensated points at approximation.
%XUQRXW FXUUHQW ÀH[LELOLW\ 8QGHU 6FDOH WR P$
Over Scale: 20.0 to 22.5 mA)
Burnout signal level is adjustable using Model FXW or Hand
Held Communicator (HHC) to comply with NAMUR NE43.
8. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level as
wet calibration.
Fuji Electric
SPECIFICATIONS
)XQFWLRQDOVSHFL¿FDWLRQV
Type:
- FKD : differential pressure transmitter with remote seal(s)
- FKB : gauge pressure transmitter with remote seal
- FKM : absolute pressure transmitter with remote seal
Service :
Liquid, gas, or vapour
Span, range, and overrange limit :
Model
F
F
F
F
F
D
D
D
D
D
3
5
6
8
9*
F
F
F
F
F
B
B
B
B
B
1
2
3
4
5
F
F
F
F
F
M
M
M
M
M
1
2
3
4
5
Span limits
Minimum
Maximum
FKD
(mbar)
(mbar)
3.2
320
13
1300
50
5000
300
30000
2000
200000
FKB
(bar)
(bar)
0,013
1,3
0,05
5
0,3
30
1
100
5
500
FKM
(bar abs)
(bar abs)
0,016
0,16
0,013
1,3
0,05
5
0,3
30
1
100
Range limits
(mbar)
± 320
± 1300
± 5000
± 30000
±200000
(bar)
-1 to + 1,3
-1 to + 5
-1 to + 30
-1 to + 100
-1 to + 500
(bar abs)
0 to +0,16
0 to +1,3
0 to +5
0 to +30
0 to +100
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
,PSRUWDQW)RU).'PD[SRVVLEOHRYHUORDGSUHVVXUHRQ/3VLGHPXVWEH”
100 bar. The accuracy is not guaranteed when used at negative DP.
EDSF6-05m
Date
October, 2015
FKB, FKD, FKM...F
Output signal :
4 to 20 mA DC (linear or square root) with digital
signal superimposed on the analogic signal
Power supply :
Transmitter operates on 10.5 to 45 V DC at transmitter terminals.
10.5 to 32 V DC for the units with optional arrester.
$XWKRULW\
ATEX
(X)
Load limitations : VHH¿JXUHEHORZ
Load resistance
R [:]
2000
When the upper limit of the saturation
current (Imax) is 21.6 mA
)DFWRU\
0XWXDO
1533
1500
Communication
range with HHC
1000
Operating
area
600
(D)
CSA
250
0
(E)
10.6
16.1 24
45
Power voltage
E [V]
Note) The load resistance varies with the upper limit
of the saturation current [I max]
R [Ω] =
E [V] -10.5
IECEx
Hazardous locations :
(R)
$XWKRULW\
'LJLW (K)
)DFWRU\
0XWXDO
+
,QWULQVLFVDIHW\
Ex II 1 G
([LD,,&7ƒ&”7D”ƒ&
([LD,,&7ƒ&”7D”ƒ&
,3
Entity Parameters:
8L”9GF,L”P$3L”:
&L Q)Q)IRUPRGHOVZLWKZLWKRXW$UUHVWHU
/L P+P+IRUPRGHOVZLWKZLWKRXW$QDORJ,QGLFDWRU
&ODVV,,,,,,
'LY*URXSV$%&'()*
7(QWLW\7\SH;
0RGHOFRGH
WKGLJLW
$%&'-
/30
461
()*+.
-
(J)
IECEx
(T)
WKGLJLW
<*1
<*1
<*1
<*1
:$'
ATEX
7DPE
-4ƒ&WRƒ&
ƒ&WRƒ&
ƒ&WRƒ&
-4ƒ&WRƒ&
ƒ&WR°C
([LD&ODVV,*URXSV$%&DQG'
&ODVV,,*URXSV()DQG*&ODVV,,,
3HUGUDZLQJ7&
7HPSFRGH7IRU7DPEPD[ ƒ&
7HPSFRGH7IRU7DPEPD[ ƒ&
Entity Parameters:
9PD[ 9GF,PD[ P$3PD[ :
&L Q)Q)IRUPRGHOVZLWKZLWKRXW$UUHVWHU
/L P+P+IRUPRGHOVZLWKZLWKRXW$QDORJ,QGLFDWRU
([LD,,&7ƒ&”7D”ƒ&
([LD,,&7ƒ&”7D”ƒ&
,3
Entity Parameters:
8L”9GF,L”P$3L”:
&L Q)Q)IRUPRGHOVZLWKZLWKRXW$UUHVWHU
/L P+P+IRUPRGHOVZLWKZLWKRXW$QDORJ,QGLFDWRU
)DFWRU\
0XWXDO
(H)
CSA
(J)
IECEx
(Q)
2
&ODVV,
'LY*URXSV%&'
77\SH;
&ODVV,,,,,
'LY*URXSV()*
77\SH;
7DPEPD[ °C
&ODVV,*URXSV&DQG'
&ODVV,,*URXSV()DQG*&ODVV,,,
0D[LPXPDPELHQWWHPSHUDWXUHƒ&
0D[LPXPZRUNLQJSUHVVXUH0SD
(OHFWULFDOUDWLQJV
0RGHO:LWKRXWDUUHVWHU
8L”9GFP$
0RGHO:LWKDUUHVWHU
8L”9GFP$
1RWH6HDOQRWUHTXLUHG
([G,,&7ƒ&”7D”ƒ&
([G,,&7ƒ&”7D”ƒ&
',3$,37ƒ&
DIP A21 IP66/67 T 100°C
(OHFWULFDOUDWLQJV
0RGHO:LWKRXWDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
0RGHO:LWKDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
$XWKRULW\
'LJLW (P)
Entity Parameters:
9PD[ 9,PD[ P$3L :
&L Q)/L P+
CSA
Ex II 2 GD
([G,,&7ƒ&”7D”ƒ&
([G,,&7ƒ&”7D”ƒ&
([W'$,37ƒ&
Ex tD A21 IP66/67 T 100°C
(OHFWULFDOUDWLQJV
0RGHO:LWKRXWDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
0RGHO:LWKDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
(I max [mA]+0.9)x10-3
Note: For communication with HHC(1)PLQRIŸLVUHTXLUHG
ATEX
)ODPHSURRI
7\SHQ
1RQLQFHQGLYH
Ex II 3 G
([Q$,,7ƒ&”7D”ƒ&
,3
(OHFWULFDOUDWLQJV
0RGHO:LWKRXWDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
0RGHO:LWKDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
2SWLRQDO$QDORJLQGLFDWRULVQRWDYDLODEOHIRUW\SHQ
&ODVV,,,,,,
'LY*URXSV$%&')*
7(QWLW\7\SH;
Model code
WKGLJLW
$%&'-
/30
461
()*+.
-
WKGLJLW
<*1
<*1
<*1
<*1
:$'
7DPE
-4ƒ&WRƒ&
ƒ&WRƒ&
ƒ&WRƒ&
-4ƒ&WRƒ&
ƒ&WR°C
&ODVV,
'LY*URXSV$%&'
&ODVV,,
'LY*URXSV()*
&ODVV,,,
'LY
7HPS&RGH7 7DPEPD[ ƒ&
7HPS&RGH7 7DPEPD[ ƒ&
(QWLW\3DUDPHWHUV
9PD[ 9GF,PD[ P$3PD[ :
&L Q)Q)IRUPRGHOVZLWKZLWKRXW$UUHVWHU
/L P+P+IRUPRGHOVZLWKZLWKRXW$QDORJ,QGLFDWRU
([Q$,,7ƒ&”7D”ƒ&
,3
(OHFWULFDOUDWLQJV
0RGHO:LWKRXWDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
0RGHO:LWKDUUHVWHU
8L”9GFP$ORRSSRZHUHG3L”:
2SWLRQDO$QDORJLQGLFDWRULVQRWDYDLODEOHIRUW\SHQ
Zero/span adjustment :
Zero and span are adjustable from the HHC(1). Zero and
span are also adjustable externally from the adjustment
screw.
Damping :
Adjustable from HHC or local adjustment unit with LCD
display.
The time constant is adjustable between 0,06 to 32 sec
Zero elevation/suppression :
Zero can be elevated or suppressed within the speci¿HGUDQJHOLPLWRIHDFKVHQVRUPRGHOEHWZHHQWR
+100% of URL for FKD.
FKB : -1 bar to 100% of URL.
Normal/reverse action :
Selectable from HHC(1).
Indication :
$QDORJLQGLFDWRURUGLJLW/&'PHWHUDVVSHFL¿HG
A plug-in analog indicator can be mounted on the electronics unit or the terminal block.
Burnout direction : Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog
signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Adjustable within the range 20.0 mA to 22.5 mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2 mA to 4.0 mA from HHC(1)
3.2
4
20
Damping
v
v
v
v
v
v
Linear
v
v
v
v
v
v
Square root
v
v
v
v
v
v
Burnout direction
v
v
v
v
v
v
Calibration
v
v
v
v
v
v
Output adjust
—
v
—
v
—
v
Data
v
—
v
—
v
—
Self diagnoses
v
—
v
—
v
—
Printer (In case of FXW
with printer option)
v
—
—
—
—
—
External switch lock
v
v
v
v
v
v
Transmitter display
v
v
v
v
v
v
Linearize*
v
v
—
—
—
—
Rerange
v
v
v
v
v
v
Saturate current
v
v
v
v
v
v
Write protect
v
v
v
v
v
v
v
v
v
—
v
v
v
—
v
v
v
—
Output
mode
History
– Calibration history
– Ambient temperature
history
(Note)
(1) HHC: Hand Held Communicator
/RFDOFRQ¿JXUDWRUZLWK/&'GLVSOD\RSWLRQ
/RFDO FRQ¿JXUDWRU ZLWK SXVK EXWWRQ DQG /&' GLVSOD\
can support all items (Fuji Protocol list) except “Linearize”
function.
Programmable output linearization function :
Output signal can be characterized with “14 points linear
approximation function” from HHC(1).
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Probable over range
3HUIRUPDQFHVSHFL¿FDWLRQV
Output Limits comforming the NAMUR NE43 by order.
Loop-check output :
7UDQVPLWWHUFDQEHFRQ¿JXUHGWRSURYLGHFRQVWDQWVLJQDO
3.2 mA through 22.5 mA by HHC(1).
Temperature limit :
Ambient: -40 to +85°C
-20 to +80°C (for LCD indicator)
-40 to +60°C (for arrester option)
-WRƒ&IRUÀXRULQDWHGRLO¿OOWUDQVPLWWHU
)RU H[SORVLRQSURRI XQLWV ÀDPHSURRI RU LQWULQVLF VDIHW\
DPELHQWWHPSHUDWXUHPXVWEHZLWKLQWKHOLPLWVVSHFL¿HGE\
each standard.
Process: &KHFNLQWKHVHDOGDWDVKHHWZLWKWKHVSHFL¿F
temperature conditions.
Storage: - 40 to +90°C
Humidity limit :
0 to 100% RH (Relative Humidity)
Communication :
With HHC (1) (model FXW, consult DS No.EDS8-47),
IROORZLQJLWHPVFDQEHUHPRWHO\GLVSOD\HGRUFRQ¿JXUHG
Note: HHC’s version must be higher than 7.0 (or
FXW
1– 4), for FCX -AII for supporting these items:
“Saturate current”, “Write protect”.
Items
Fuji Protocol
with FXW
Hart® Protocol
By local configurator (with 3 push
button), (LCD indicator)
Display
Set
Display
Set
Display
Set
Tag No.
v
v
v
v
v
v
Model No.
v
v
v
v
v
v
Serial No. & Software
Version
v
—
v
—
v
—
Engineering unit
v
v
v
v
v
v
Range limit
v
—
v
—
v
—
Measuring range
v
v
v
v
v
v
5HIHUHQFHFRQGLWLRQVVLOLFRQHRLO¿OO66/LVRODWLQJ
diaphragms, 4 to 20 mA analog output.
Accuracy rating :
(including linearity, hysteresis, and repeatability)
For span greater than 1/10 of URL :
± 0,065% of calibrated span (FKB & FKD)
± 0,1% of calibrated span for FKB 5VF
± 0,2% of calibrated span for FKM
For span smaller than 1/10 of URL :
± (0,015 + 0,05 x 0,1 x URL/span) % of span (FKB & FKD)
± (0,1+ 0,1 x 0,1 x URL/span) % of span (FKM)
Stability :
± 0.2% of upper range limit (URL) for 10 years.
Linearity :
0,05% of calibrated span (FKB & FKD)
0,1% of calibrated span (FKM)
Temperature effect :
Effect per 28°C change between - 40°C and +85°C
Model FKM :
Zero shift :
±(0,125 + 0,1 x URL/span) % of URL
Total effect :
±(0,15 + 0,1 x URL/span) % f URL
Model FKB & FKD :
Zero shift :
±(0,075 + 0,0125% URL/span) % of URL
Total effect :
±(0,095 + 0,0125 URL/span) % of URL
Static pressure effect (FKD) :
Zero shift : ± 0,035% of URL for 100 bar
Overrange effect (FKB & FKM) :
Zero shift : 0,2% of URL, for any overrange pressures
(limited to the max. overrange pressure)
3
FKB, FKD, FKM...F
Overrange effect (FKD) :
Zero shift : ± 0,15% of URL / 160 bar limit
Supply voltage effect :
Less than 0.005% of calibrated span per 1V
RFI effect :
< 0,2% of URL for the frequences of 20 to 1000 MHz and
¿HOG VWUHQJWK RI 9P ZKHQ HOHFWURQLF KRXVLQJ FRYHUV
DUH RQ &ODVVL¿FDWLRQ DEF RI VSDQ DFFRUGLQJ
SAMA PMC 33.1)
Update rate : 60 msec
Response time : (at 63,3% of output signal without damping)
Time constant : 300 msec (FKD span code “3“)
Time constant : 200 msec (other spans and FKB, FKM)
Dead time : 300 msec
Response time = time constant + dead time
Mounting position effect :
Zero shift : < 12 mm CE for 10° incline in any position. This
shift can be corrected with the zero adjustment.
7KLVHIIHFWLVGRXEOHGIRUÀXRULQDWHGRLO¿OOLQJ
1RLQÀXHQFHRQVSDQDGMXVWPHQW
Vibration effect :
< ±0,25% Of span for spans greater than 1/10 of URL.
Frequency 10 to 150 Hz, acceleration 39,2 m/sec2 .
These informations are available only for capillary mounting.
Material fatigue :
Please consult Fuji Electric
Dielectric strength:
500 V AC, 50/60 Hz 1 min., between circuit and earth.
Insulation resistance :
0RUHWKDQ0Ÿ9'&
,QWHUQDOUHVLVWDQFHIRUH[WHUQDO¿HOGLQGLFDWRU
ŸPD[LFRQQHFWHGWRWHVWWHUPLQDO&.DQG&.
Pressure equipment directive (PED) 97/23/EC
FKD: According to Article 3.3
FKB: Digit 6 code 1, 2, 3, 4 according to Article 3.3
Digit 6 code 5 : Category III module B
FKM: According to Article 3.3
Mass {weight} :
Refer to outline dimensions page 12 to 17.
Diaphragm seal(s) :
A comprehensive selection of seals can be chosen in
DFFRUGDQFHZLWKWKHVSHFL¿FVHDOVHHGDWDVKHHW
Optional features
Indicator :
A plug-in analog indicator (2.5% accuracy) can be housed
in the electronics compartment or in the terminal box of the
housing.
An optional 5 digit LCD meter with engineering unit is also
available.
/RFDOFRQ¿JXUDWRUZLWK/&'GLVSOD\
An optional 5 digits LCD meter with 3 push buttons can
support items as using communication with FXW.
Arrester :
A built-in arrester protects the electronics from lightning
surges.
Lightning surge immunity: 4 kV (1.2 × 50 μs)
1$&(VSHFL¿FDWLRQ
Metallic materials for all pressure boundary parts comply with NACE MR 0175/ISO 15156.
SS 660 bolts and nuts comply with NACE MR 0175/ISO
15156.
Optional tag plate :
An extra stainless steel tag for customer tag data is wired
to the transmitter.
Vacuum service : See Fig.1
6SHFLDOVLOLFRQHRLODQG¿OOLQJSURFHGXUHDUHDSSOLHG
[Torr]
FKB & FKD
type only
Sealing liquid:Silicone oil (Code Y)
3K\VLFDOVSHFL¿FDWLRQV
Electrical connections :
1/2“-14 NPT, Pg 13,5 or M20 x 1,5
Process-wetted parts material :
Diaphragm : SS 316L, Hastelloy-C, Monel, Tantalum, Titanium or Zirconium
Flange face : SS 316L, Hastelloy-C, Monel, Tantalum, Titanium or Zirconium
Extension : SS 316L, Hastelloy-C
(Refer to “Code symbols”)
Non-wetted parts material :
Electronics housing :
/RZFRSSHUGLHFDVWDOXPLQXPDOOR\¿QLVKHGZLWKSRO\HVWHUFRDWLQJVWDQGDUGRU66DVVSHFL¿HG
Bolts and nuts :
Standard : Cr-Mo alloy
2SWLRQ66/IRUSUHVVXUH”EDURU66IRU
pressure > 100 bar
)LOOÀXLG
Standard : Silicone oil
2SWLRQÀXRULQDWHGRLO
Mounting bracket :
SS 304L or SS 316L
Environmental protection :
IEC IP66/IP67 and NEMA4X
Mounting bracket:
Without : direct mounting
With (option) : On 50 mm (2”) pipe or direct wall mounting
4
Operating pressure
760
Operating area
150
Non
operating
area
30
20
–40
–15
60
Process temperature[°C ]
120
Fig. 1 Relation between process temperature and operating pressure
ACCESSORIES
Hand-held communicator :
(Model FXW, refer to Data Sheet No. EDS8-47)
CODE SYMBOLS - FKB
1
2
3
F
K
B
4
5
6
7
8
V
F
9
10
11
12
-
13
DESCRIPTION
Y
Type
Smart, 4-20 mAdc + Fuji/Hart® digital signal
Conduit connection
T
1/2"-14NPT
V
Pg 13.5
W
M20 x 1.5
Diaphragm seal rating
2
PN 25
4
PN 20 - 150 Lbs
6
PN 50 - 300 Lbs
8
PN 40
9
PN 16
L
PN 100 - 600Lbs
M
PN 150 - 900Lbs
N
PN 250 - 1500Lbs
P
PN 420 - 2500Lbs
(*1) Spans
1
(*2) 0 to 0.013/1.3 bar
2
(*3) 0 to 0.05/5 bar
3
0 to 0.3/30 bar
4
(*4) 0 to 1/100 bar
5
(*4) 0 to 5/500 bar
Indicator, arrester and initial setting
Indicator
Arrester
A
None
None
-
B
Analog, 0-100% linear scale
None
-
D
Analog, Custom scale
None
F
-
J
Analog, double scale
None
V
F
-
E
None
Yes
V
F
-
F
Analog, 0-100% linear scale
Yes
Hart® /Fuji
V
F
-
V
F
V
F
V
Initial setting
4-20mA DC
+
V
F
-
H
Analog, Custom scale
Yes
digital signal
V
F
-
K
Analog, double scale
Yes
"SMART''
V
F
-
L
Digital, 0-100%
None
V
F
-
P
Digital, Custom scale
None
V
F
-
Q
Digital, 0-100%
Yes
V
F
-
S
Digital, Custom scale
Yes
V
F
-
1
Digital, 0-100% with push button
None
V
F
-
2
Digital, Custom scale with push button
None
V
F
-
4
Digital, 0-100% with push button
Yes
V
F
-
5
Digital, Custom scale with push button
Yes
Approvals for hazardous locations (consult FUJI for availability)
A
None (Standard)
X
ATEX - Flameproof enclosures (digit 4 = "T" & "W" only)
ATEX - Intrinsic Safety
K
(*8) FM - Explosion-Proof (digit 4 = "T" only)
D
E
CSA - Explosion-Proof (digit 4 = "T" only)
H
FM - Intrinsic Safety and Non Incendive
J
CSA - Intrinsic Safety
P
ATEX - Type "n" (digit 9 = A, E, 1, 2, 3, 4 & 5 only)
Q
IECEx - Type "n" (digit 9 = A, E, 1, 2, 3, 4 & 5 only)
R
IECEx - Flameproof enclosures (digit 4 = "T" & "W" only)
T
IECEx - Intrinsic Safety
L
CSA - Explosion-Proof & Intrinsic Safety combined approval (digit 4 = "T" only)
M
ATEX - Flameproof enclosures & Intrinsic Safety combined approval (digit 4 = "T" & "W" only)
N
IECEx - Flameproof enclosures & Intrinsic Safety combined approval (digit 4 = "T" & "W" only)
FM - Explosion-Proof & Intrinsic Safety combined approval (digit 4 = "T" only)
V
(*5) Mounting design
Ambiant temperature correction
B
Capillary
Transmitter and diaphragm seal assembly
Transmitter and diaphragm seal assembly
L
Rigid - long design
M
Rigid - short design
Transmitter and diaphragm seal assembly
G
Capillary
Transmitter
S
Rigid - long design
Transmitter
T
Rigid - short design
Transmitter
Stainless Steel parts
Cell flange design
Tag plate
Housing & mounting bracket
1
Y
(*7)
(*6) S”EDU
none
None
None
2
Y
(*7)
(*6) S”EDU
none
Yes
None
3
Y
(*7)
(*6) S”EDU
none
None
Yes
4
Y
(*7)
(*6) S”EDU
none
Yes
Yes
Y
Y
(*7)
S”
carbon steel
None
None
B
Y
(*7)
S”
carbon steel
Yes
None
C
Y
(*7)
S”
carbon steel
None
Yes
E
Y
(*7)
S”
carbon steel
Yes
Yes
A
Y
(*7)
S”EDU
SS 316(L)/SS 316(L) None
None
D
Y
(*7)
S”EDU
SS 316(L)/SS 316(L) Yes
None
F
Y
(*7)
S”EDU
SS 316(L)/SS 316(L) None
Yes
G
Y
(*7)
S”EDU
SS 316(L)/SS 316(L) Yes
Yes
Operating pressure (bar)
Bolts/nuts
H
Y
(*7)
(*9) S”EDUPD[
SS 660/SS 660
None
None
J
Y
(*7)
(*9) S”EDUPD[
SS 660/SS 660
Yes
None
K
Y
(*7)
(*9) S”EDUPD[
SS 660/SS 660
None
Yes
L
Y
(*7)
(*9) S”EDUPD[
SS 660/SS 660
Yes
Yes
Notes* :
1- Turn down of 100:1 is possible, but should be used at the span greater than 1/10 of the maximum span for better performance.
&RQVXOW)8-,IRU\RXUDSSOLFDWLRQZLWKWKHVSHFL¿FRSHUDWLQJFRQGLWLRQV
)RU'1FRQVXOW)8-,IRU\RXUDSSOLFDWLRQZLWKWKHVSHFL¿FRSHUDWLQJFRQGLWLRQV
)ODQJHUDWLQJDFFRUGLQJPD[RSHUDWLQJSUHVVXUHIRU'1ÀDQJHVL]HDQGRU31!FRQVXOW)8-,
5- Transmitter with capilary design has a standard mounting bracket - Rigid monting design are always without monting bracket
6- Codify bolts and nuts for all mounting even if p < 50 bar
6WDQGDUG¿OOÀXLGRIPHDVXULQJFHOOVVLOLFRQHRLO2WKHU¿OOÀXLGVXSRQUHTXHVW
8- Code "D & V" FM approval only possible with electrical connection 1/2"-14 NPT
9- Our bolts/nuts in SS 660 are in conformity with the NACE MR 0175/ISO 15156 requirements and must be used for NACE MR 0175/ISO 15156 service.
5
FKB, FKD, FKM...F
CODE SYMBOLS - FKD
1
2
3
F
K
D
4
5
6
7
8
V
F
9
10
11
12
-
13
DESCRIPTION
Y
(*5) Type
Differential pressure transmitter - Smart, 4-20 mAdc + Fuji/Hart® digital signal
Conduit connection
T
1/2"-14NPT
V
Pg 13.5
W
M20 x 1.5
Diaphragm seal rating
2
PN 25
4
PN 20 - 150 Lbs
6
PN 50 - 300 Lbs
8
PN 40
9
PN 16
L
PN 100 - 600Lbs
M
PN 150 - 900 lbs
(*9) PN 250 - 1500 lbs
(*9) PN 420 - 2500 lbs
N
P
(*1) Spans
3
(*2) 0 to 3,2/320 mbar
5
(*2) 0 to 0,013/1,3 bar
6
0 to 0,05/5 bar
8
0 to 0,3/30 bar
9
0 to 2/200 bar
Indicator, arrester and initial setting
Indicator
Arrester
A
None
None
B
Analog, 0-100% linear scale
None
C
$QDORJ¥VFDOH
None
Analog, Custom scale
None
Initial setting
V
F
-
V
F
-
V
F
-
V
F
-
D
V
F
-
J
Analog, double scale
None
V
F
-
E
None
Yes
V
F
-
F
Analog, 0-100% linear scale
Yes
V
F
-
G
$QDORJ¥VFDOH
Yes
V
F
-
H
Analog, Custom scale
Yes
V
F
-
K
Analog, double scale
Yes
V
F
-
L
Digital, 0-100%
None
Hart /Fuji
V
F
-
P
Digital, Custom scale
None
digital signal
V
F
-
M
Digital, 0-100% ࠨ scale
None
"SMART''
V
F
-
Q
Digital, 0-100%
Yes
V
F
-
N
Digital, 0-100% ࠨ scale
Yes
4-20mA DC
+
®
Yes
V
F
-
S
V
V
F
F
-
1
2
Digital, Custom scale
Digital, 0-100% with push button
Digital, Custom scale with push button
None
V
F
-
3
Digital, 0-100% ࠨ scale with push button
None
V
F
-
4
Digital, 0-100% with push button
Yes
V
F
-
5
Digital, Custom scale with push button
Yes
V
F
-
6
Digital, 0-100% ࠨ scale with push button
Yes
None
Approvals for hazardous locations (consult FUJI for availability)
A
None (Standard)
X
ATEX - Flameproof enclosures (digit 4 = "T" & "W" only)
K
ATEX - Intrinsic Safety
D
(*7) FM - Explosion-Proof (digit 4 = "T" only)
E
CSA - Explosion-Proof (digit 4 = "T" only)
H
FM - Intrinsic Safety and Non Incendive
J
CSA - Intrinsic Safety
P
ATEX - Type "n" (digit 9 = A, E, 1, 2, 3, 4 & 5 only)
Q
IECEx - Type "n" (digit 9 = A, E, 1, 2, 3, 4 & 5 only)
R
IECEx - Flameproof enclosures (digit 4 = "T" & "W" only)
T
IECEx - Intrinsic Safety
L
CSA - Explosion-Proof & Intrinsic Safety combined approval (digit 4 = "T" only)
M
ATEX - Flameproof enclosures & Intrinsic Safety combined approval (digit 4 = "T" & "W" only)
N
IECEx - Flameproof enclosures & Intrinsic Safety combined approval (digit 4 = "T" & "W" only)
FM - Explosion-Proof & Intrinsic Safety combined approval (digit 4 = "T" only)
V
(*5) (*6) Mounting design (*3)
Ambiant temperature correction
B
Capillary on HP side
Transmitter and diaphragm seal assembly
C
Capillary on HP & LP side
Transmitter and diaphragm seal assembly
(*6) Rigid short design on HP & capillary on LP side
E
Transmitter and diaphragm seal assembly
G
Capillary on HP side
Transmitter
H
Capillary on HP & LP side
Transmitter
Cell flange design
Stainless Steel parts
Bolts/nuts
Tag plate
Housing
1
Y
(*4) S”EDU
None
None
None
2
Y
(*4) S”EDU
None
Yes
None
3
Y
(*4) S”EDU
None
None
Yes
4
Y
(*4) S”EDU
None
Yes
Yes
Y
Y
S”
Carbon steel
None
None
B
Y
S”
Carbon steel
Yes
None
C
Y
S”
Carbon steel
None
Yes
E
Y
S”
Carbon steel
Yes
Yes
A
Y
S”EDU
SS 316(L)/SS 316(L)
None
None
D
Y
S”EDU
SS 316(L)/SS 316(L)
Yes
None
F
Y
S”EDU
SS 316(L)/SS 316(L)
None
Yes
G
Y
S”EDU
SS 316(L)/SS 316(L)
Yes
Yes
H
Y
(*8) S”EDU
SS 660/SS 660
None
None
J
Y
(*8) S”EDU
SS 660/SS 660
Yes
None
K
Y
(*8) S”EDU
SS 660/SS 660
None
Yes
L
Y
(*8) S”EDU
SS 660/SS 660
Yes
Yes
Operating pressure (bar)
Notes* :
1- Turn down of 100:1 is possible, but should be used at the span greater than 1/10 of the maximum span for better performance
)RU'1 FRQVXOW)8-,IRU\RXUDSSOLFDWLRQZLWKWKHVSHFL¿FRSHUDWLQJFRQGLWLRQV
3- Transmitter with capilary design has a standard mounting bracket
4- If direct mounted seal design is required, bolts are necessary even when p < 50bar
6WDQGDUG¿OOÀXLGRIPHDVXULQJFHOOVVLOLFRQHRLO2WKHUV¿OOÀXLGVXSRQUHTXHVW
6- Transmitter with different diaphragm seals or capillary lenghtes on HP and LP side must be temperature corrected.
7- Code "D & V" FM approval only possible with electrical connection 1/2"-14 NPT.
8- Our bolts/nuts in SS 660 are in conformity with the NACE MR 0175/ISO 15156 requirements and must be used forNACE MR 0175/ISO 15156 service.
9- High static pressure DP measuring cell and M12 bolting required (upon request.
6
CODE SYMBOLS - FKM
1
F
2
K
3
M
4
5
6
7
8
V
F
9
10
11
12
-
13
DESCRIPTION
Y
Type
®
Smart, 4-20 mAdc + Fuji/Hart digital signal
Conduit connection
T
1/2"-14NPT
V
Pg 13.5
W
M20 x 1.5
Diaphragm seal rating
2
PN 25
4
PN 20 - 150 Lbs
6
PN 50 - 300 Lbs
8
PN 40
9
PN 16
(*1) Spans
1
(*2) 0 to 0.016/0.16 bar abs
2
(*3) 0 to 0.013/1.3 bar abs
3
0 to 0.05/5 bar abs
4
0 to 0.3/30 bar abs
5
0 to 1/100 bar abs
Indicator, arrester and initial setting
V
F
-
A
Indicator
Arrester
None
None
V
F
-
B
Analog, 0-100% linear scale
None
V
F
-
D
Analog, Custom scale
None
Initial setting
V
F
-
J
Analog, double scale
None
V
F
-
E
None
Yes
V
F
-
F
Analog, 0-100% linear scale
Yes
V
F
-
H
Analog, Custom scale
Yes
V
F
-
K
Analog, double scale
Yes
V
F
-
L
Digital, 0-100%
None
Hart® /Fuji
digital signal
V
F
-
P
Digital, Custom scale
None
V
F
-
Q
Digital, 0-100%
Yes
V
F
-
S
Digital, Custom scale
Yes
V
F
-
1
Digital, 0-100% with push button
None
V
F
-
2
Digital, Custom scale with push button
None
V
F
-
4
Digital, 0-100% with push button
Yes
V
F
-
5
Digital, Custom scale with push button
Yes
4-20mA DC
+
'SMART''
Approvals for hazardous locations (consult FUJI for availability)
A
None (Standard)
X
ATEX - Flameproof enclosures (digit 4 = "T" & "W" only)
K
ATEX - Intrinsic Safety
D
(*7) FM - Explosion-Proof (digit 4 = "T" only)
E
CSA - Explosion-Proof (digit 4 = "T" only)
H
FM - Intrinsic Safety and Non Incendive
J
CSA - Intrinsic Safety
P
ATEX - Type "n" (digit 9 = A, E, 1, 2, 3, 4 & 5 only)
Q
IECEx - Type "n" (digit 9 = A, E, 1, 2, 3, 4 & 5 only)
R
IECEx - Flameproof enclosures (digit 4 = "T" & "W" only)
T
IECEx - Intrinsic Safety
L
CSA - Explosion-Proof & Intrinsic Safety combined approval (digit 4 = "T" only)
M
ATEX - Flameproof enclosures & Intrinsic Safety combined approval (digit 4 = "T" & "W" only)
N
IECEx - Flameproof enclosures & Intrinsic Safety combined approval (digit 4 = "T" & "W" only)
V
FM - Explosion-Proof & Intrinsic Safety combined approval (digit 4 = "T" only)
Mounting design (*4)
Ambiant temperature correction
B
Capillary
Transmitter and diaphragm seal assembly
L
Rigid - long design
Transmitter and diaphragm seal assembly
M
Rigid - short design
Transmitter and diaphragm seal assembly
G
Capillary
Transmitter
S
Rigid - long design
Transmitter
T
Rigid - short design
Stainless steel parts
Transmitter
Operat. pressure (bar) Bolts/nuts
Tag plate
Housing & mounting bracket
1
Y
(*6)
(*5) S”EDU
None (capillary mounting)
None
None
2
Y
(*6)
(*5) S”EDU
None (capillary mounting)
Yes
None
3
Y
(*6)
(*5) S”EDU
None (capillary mounting)
None
Yes
4
Y
(*6)
(*5) S”EDU
None (capillary mounting)
Yes
Yes
Y Y
(*6)
S”
Carbon steel
None
None
B Y
(*6)
S”
Carbon steel
Yes
None
C Y
(*6)
S”
Carbon steel
None
Yes
E Y
(*6)
S”
Carbon steel
Yes
Yes
A Y
(*6)
S”EDU
SS 316(L)/SS 316(L)
None
None
D Y
(*6)
S”EDU
SS 316(L)/SS 316(L)
Yes
None
F Y
(*6)
S”EDU
SS 316(L)/SS 316(L)
None
Yes
G Y
(*6)
S”EDU
SS 316(L)/SS 316(L)
Yes
Yes
H Y
(*6)
(*8) p ” 100 bar
SS 660/SS 660
None
None
J
Y
(*6)
(*8) p ” 100 bar
SS 660/SS 660
Yes
None
K Y
(*6)
(*8) p ” 100 bar
SS 660/SS 660
None
Yes
L
(*6)
(*8) p ” 100 bar
SS 660/SS 660
Yes
Yes
Y
Notes* :
1Turn down of 100:1 is possible, but should be used at the span greater than 1/10 of the maximum span for better performance.
&RQVXOW)8-,IRU\RXUDSSOLFDWLRQZLWKWKHVSHFL¿FRSHUDWLQJFRQGLWLRQV
)RU'1 FRQVXOW)8-,IRU\RXUDSSOLFDWLRQZLWKWKHVSHFL¿FRSHUDWLQJFRQGLWLRQV
4Transmitter with capilary design has a standard mounting bracket - rigid monting design are always without monting bracket
)ODQJHUDWLQJDFFRUGLQJPD[RSHUDWLQJSUHVVXUHIRU'1ÀDQJHVL]HDQGRU31!FRQVXOW)8-,
6WDQGDUG¿OOÀXLGRIPHDVXULQJFHOOVVLOLFRQHRLORWKHU¿OOÀXLGVXSRQUHTXHVW
7Code “D & V” FM approval only possible with electrical connection 1/2”-14 NPT
8Our bolts/nuts in SS 660 are in conformity with the NACE MR 0175/ISO 15156 requirements and must be used for NACE MR 0175/ISO 15156 service.
7
FKB, FKD, FKM...F
DIAPHRAGM SEAL(S)
S
Diaphragm seals designed by Fuji Electric are used
to measure accurately liquid level, density on open
DQGFORVHGWDQNVRUÀRZPHDVXUHPHQWLQSLSHV7KH
use of the diaphragm seal(s) avoid(s) that the measuring cell is directly in contact with the process. The
welded seal construction assures excellent reliability
in high temperature and high corrosive, viscous, sticking, crystallizable and abrasive process conditions.
FEATURES
1- Construction
The diaphragm seals are mounted on differential, gauge and
absolute pressure transmitters of FCX-AII series.
The seal can be rigid, (direct) mounted on the transmitter or
with capillaries between the seal and the transmitter.
The construction is an all welded design without any gasket
EHWZHHQWKHVHDODQGWKHWUDQVPLWWHUGLDSKUDJPDQGLV¿OOHG
with the suitable oil for your application.
2- Operating principle
The measuring pressure is applied on the diaphragm seal and
WUDQVIHUUHGE\WKH¿OOLQJÀXLGWKURXJKWKHFDSLOODU\WXEHWRWKH
measuring cell of the pressure transmitter.
3- Parts materials
Wetted parts materials (diaphragm and gasket face) are in
stainless steel, Tantalum, Hastelloy, Monel, Titanium, Zirconium,
Nickel, depending on the application requirements.
Other parts are in stainless steel : capillary tube, reduced volume
ÀDQJHGLDSKUDJPVHDOERG\GLUHFWPRXQWLQJFRQQHFWLRQSDUWV
6WDQGDUG¿OOLQJÀXLGLVVLOLFRQHRLO
Fluorinated oil, sanitary oil, high temperature oil and vacuum
VHUYLFH¿OOLQJDUHDYDLODEOHWKURXJKPRGHOVHOHFWLRQ
4- Diaphragm seal types
According to the mounting and operating conditions different
seal types can be useful :
Flush mounting design from DN40 to DN100.
Seals with extensions (50 to 200 mm).
Flanged, screwed or weld neck adaptors
Seals for sanitary applications according DIN, SMS or TriClamp standards.
)RUVSHFL¿FVVHDOVSOHDVHFRQVXOW)XML(OHFWULF
SPECIFICATIONS
)XQFWLRQDOVSHFL¿FDWLRQV
Diaphragm seal application :
The seal(s) can be mounted direct or rigid on the transmitter
(for example for liquid level measurement at the bottom of
the tank) or capillary mounted to distance the measuring
point away from the transmitter (for example in case of
high process temperature). The rigid mounted seal can be
assembled in a long design or in a short (compact) design
according to the physical dimension requests of the customer
(see outline dimensions drawings).
FKB
FKM
FKD
Rigid mounting
short or long design
short or long design
see datasheet of level
transmitter (FKE)
Capillary mounting
HP side
HP side
HP and LP side
HP side
LP side
&DSLOODU\WXEHVSHFL¿FDWLRQV
Standard capillary lengthes :
1,5 / 3 / 6 m (other upon request)
Inside diameter :
1 mm standard
2 mm for vacuum service, high process temperature
applications, short response time requirements
Smallest bending radius of the capillary : 100 mm
Capillary tube sheald possibilities :
Temperature limit :
PVC sheald : -10 à 80°C
Stainless steel sheald : -40 à 350°C
Process connection possibilities :
The diaphragme seals can be:
- Flush mounting design
- Extension mounting
$GDSWRUVPRXQWLQJÀDQJHGVFUHZHGRUZHOGHGQHFN
The adaptors mounting can adapte the remote seals to
special connection and to increase the sensibilty of the
transmitter during special process conditions.
8
Temperature limits :
Ambiant temperature :
-40 to 85°C for transmitter
Process temperature :
-40 to 150°C for rigid mounting,
WRƒ&IRUFDSLOODU\GHVLJQDQGDFFRUGLQJWKH¿OOLQJ
ÀXLGOLPLWDWLRQV
Pressure limits :
Working pressure :
Limited by the static pressure or the working pressure of the
WUDQVPLWWHURUE\WKHQRPLQDOÀDQJHUDWLQJRIWKHGLDSKUDJP
seal (PN). (Please take the smallest of both)
Vacuum limit :
'HSHQGLQJRIWKHOLPLWRIWKHWUDQVPLWWHUDQGWKH¿OOLQJÀXLG
of the seal.
For a differential or gauge pressure transmitter the lowest
vaccum is 20 Torr or 27 mbar abs.
Only the absolute pressure transmitter can be used till
absolute zero (FKM).
For the utilization of vacuum service < 20 Torr, please
consult Fuji Electric.
The absolute pressure transmitter has to be used.
Process temperature effect : (mbar/10°C)
Seals
DN 50 / 2”
SS
for transmitters diaphragm
FKB/FKM
1.24
FKD
0.5
DN 80 / 3”
SS
diaphragm
0.17
0.09
DN 80 / 3”
Other diaph.
material.
0.73
0.22
DN 100 / 4”
SS
diaphragm
0.08
0.05
Adaptor
SS
diaphragm
0. 17
0.09
6WDWLFSUHVVXUHHIIHFWIRU¨3WUDQVPLWWHUZLWKVWDLQOHVVVWHHO
diaphragms (FKD transmitter with DN80 and DN100 seals) :
Zero shift :
“RI85/IRUÀDQJHUDWLQJXSWREDURUOEV
2LO¿OOLQJ
&RGH 'HQVLW\
digit 7 at 25°C
Std silicone oil
Fluorinated oil
Oil for vaccum or
high temperature
Y, G
W,A,D
U, X
0,95
1,84
1,07
5
HVSRQVHWLPH
0 to
0 to
320 mbar
1.3 bar
0,15
0,037
0,17
0,04
0,25
0,065
Response time : (mean values)
The indicated values are in seconds per meter of capillary
length with internal tube diameter Ø 1 mm.
The indicated response time is based on a pressure change
of 0 to 100% of the calibrated span at reference temperature
of 20°C.
The indicated values do not include the response time of
the transmitter.
)LOOLQJÀXLGRIWKHGLDSKUDJPVHDOV
3HUIRUPDQFHVSHFL¿FDWLRQV
To calculate the total performance, both the transmitter and the
diaphragm seals performances have to be added.
8QGHUUHIHUHQFHFRQGLWLRQV6LOLFRQHRLO¿OOLVRODWHGVHDOV66
316L, analogic output 4/20 mA at linear mode)
Accuracy :
The assembling of 1 or 2 diaphragm seals on a transmitter
increases the accuracy error at reference conditions of
0,1% of the span.
Ambiant temperature effect :
Effect when transmitter alone is corrected.
Code
Designation
GLJLW
Y
Silicone oil
W
Fluorinated oil
) 6DQLWDU\¿OOÀXLGH
V
Silicone oil
U
Silicone oil
X
Silicone oil
Temperature resistance (°C)
3DEV•EDU 3DEVEDU
-40 to 180
-40 to 120
-20 to 200
-20 to 120
WR
WR
20 to 200
0 to 300
20 to 200
-10 to 350
20 to 200
Density
ƒ&
0,95
1,84
1,07
1,07
1,09
The indicated values and limits are indicated for the most
FRPPRQDSSOLFDWLRQVVWDQGDUG¿OOLQJÀXLGV
Please consult Fuji Electric for special applications indicating
your temperature, pressure and vacuum conditions (vacuum
and temperature can occure together).
2WKHU¿OOLQJÀXLGVFDQEHXVHGIRU\RXUDSSOLFDWLRQV
(See digit 11 code G, S, T of the code symbols FKB and
FKM and code G, H of the code symbols FKD).
Seals
Transmitters
FKB/FKM gauge /abs
pressure
capillary(m)
FKD differential
pressure
capillary (m)
DN 50 / 2”
SS diaphr.
DN 80 / 3” DN 80 / 3”
DN 100 / 4” Adaptor
SS diaphr. other diaph. SS diaphr. SS diaphr.
materials
2.03
0.11
0.22
0.04
0.11
1.5
0.08
0.2
0.03
0.08
0.48
0.04
0.05
0.02
0.04
0.32
0.03
0.07
0.01
0.03
Note : the indicated values are in mbar/10°C for capillary
length of 1m and internal capillary tube ø of 1 mm
Effect when transmitter and the seal assembly is corrected.
6HHFRGHV%&/0GLJLWRIWKHFRGL¿FDWLRQ).%).'
and FKM).
According to the complete transmitter design (transmitter
and seals), a strong correction of the zero drift can be
realized by an additional temperature correction operation
on the complete transmitter unit (trasnmitter and seals).
A thermal isolation or a heating of the capillaries minimises
the ambient temperature effect.
9
S
FKB, FKD, FKM...F
CODE SYMBOLS - S
1
2
3
4
5
6
7
S
8
DESCRIPTION
A
Flanged axial diaphragm seal connection
R
Flanged radial diaphragm seal connection - Not possible with rigid mounting design digit 6 : code R
Wafer type - Not possible with rigid mounting design digit 6 : code R
W
(*1) Flanges RF (Flange size and rating)
4
ANSI-150LB 3''-ISO PN 20 DN 80
5
ANSI-150LB 4''-ISO PN 20 DN 100
6
ANSI-300LB 3"-ISO PN 50 DN 80
7
ANSI-300LB 4"-ISO PN 50 DN 100
8
DIN PN40 DN80
9
DIN PN16 DN100
H
(*2) ANSI-150LB 2''-ISO PN 20 DN 50
J
(*2) ANSI-300LB 2''-ISO PN 50 DN 50
G
(*2) DIN PN40 DN50
U
PN 25 / DN 50 - coupling nut
DIN 11851 design
V
PN 40 / DN 50 - coupling nut
SMS
material code "V" only
W
PN 40 / DN 50 - seal only
Clamp
material code "V" only
Sanitary
material code "V" only
X
No dead volume
material code "V" only
A
(*3) Flange adaptor PN 40 DN 25
B
(*3) Flange adaptor ISO PN 20 DN 25 (1"-150 ANSI)
material code "V" - others UR
material code "V" - others UR
C
(*3) Flange adaptor ISO PN 50 DN 25 (1"- 300 ANSI)
material code "V" - others UR
D
(*3) Flange adaptor PN 40 DN 40
material code "V" - others UR
E
(*3) Flange adaptor ISO PN 20 DN 40 (1"1/2 - 150 ANSI)
material code "V" - others UR
F
(*3) Flange adaptor ISO PN 50 DN 40 (1"1/2 - 300 ANSI)
material code "V" - others UR
S
(*3) Screwed 1/2 NPTE
material code "V" - others UR
T
(*3) To be welded (pipe 2"1/2)
material code "V" - others UR
Diaphragm seal material
V
Diaphragm
Flange raised face
SS 316 L
SS 316 L
SS 316 L
Flange
H
(*7) Hastelloy-C
Hastelloy-C
SS 316 L
B
(*7) Monel
Monel
SS 316 L
T
(*7) Tantalum
Tantalum
SS 316 L
P
(*9) (*7) Titanium
Titanium
SS 316 L
R
(*9) (*7) Zirconium
Zirconium
SS 316 L
(*7) SS 316 L + gold coat
C
(*4) (*7) SS 316L + PFA lining
F
SS 316 L
SS 316 L
SS 316 L + PFA lining
SS 316 L
Diaphragm seal design
Y
Flush mounting
A
Diaphragm extension 50 mm
B
Diaphragm extension 100 mm
C
Diaphragm extension 150 mm
D
Diaphragm extension 200 mm
E
Diaphragm extension 50 mm
F
Diaphragm extension 100 mm
G
Diaphragm extension 150 mm
H
Diaphragm extension 200 mm
J
Diaphragm extension 50 mm
K
Diaphragm extension 100 mm
L
Diaphragm extension 150 mm
M
Diaphragm extension 200 mm
P
Diaphragm extension 50 mm
R
Diaphragm extension 100 mm
S
Diaphragm extension 150 mm
T
Diaphragm extension 200 mm
material code "V" - digit 4
material code "H" - digit 4
material code "B" - digit 4
material code "T" - digit 4
Transmission diaphragm seal to measuring cell
Mounting design
Capillary length
Capillary design
A
Capillary
1,5 m
PVC protection
B
Capillary
3m
PVC protection
C
Capillary
6m
PVC protection
D
Capillary
Upon request
PVC protection
G
(*5)
Capillary
1,5 m
SS sheald
H
(*5)
Capillary
3m
SS sheald
K
(*5)
Capillary
6m
SS sheald
L
(*5)
Capillary
Upon request
SS sheald
R
Rigid design - not possible with digit 2 = R, W - max. process temperature : 150°C
Special applications and fill fluid for the diaphragm seal only
Treatment
Fill fluid
Y
None (standard)
Silicone oil
W
None (standard)
Fluorinated oil
F
None (standard)
Sanitary fill fluid
D
Chlorine service
Fluorinated oil
G
Degreasing
Silicone oil
A
Oxygen service
Fluorinated oil - material code ''V'' only
N
NACE
Silicone oil
Silicone oil
V
(*6)
Vacuum - max temperature 200°C
U
(*6)
Very high temperature (0 to 300°C) - No vacuum
X
(*6)
Very high temperature (20 to 350°C) - No vacuum
Special options or design
-
10
*
(*8)
Special, no code available
* Notes :
'LIIHUHQWÀDQJHPDFKLQLQJVUHFHVVJURRYHFRQVXOW)8-,(OHFWULF *2 Only available with span higher than : 0 to 0,5/5 bar - max process temperature : 150°C - or ask FUJI with operating conditions
*3 Axial diaphragm seal connection - no extension possible
*4 Not possible with digit 7 : V, H, T
*5 Recommended for Vacuum or High Temperature applications T > 120°C - (Capillary internal diameter = 2mm)
&RQVXOW)8-,IRU\RXUDSSOLFDWLRQZLWKWKHVSHFL¿FRSHUDWLQJFRQGLWLRQV $GGYDOXHVIRUPDWHULDORSWLRQVIRU '131$16,/%
ÀDQJHUDWH'1RU´DGGYDOXHVDYDLODEOHXSRQUHTXHVW
*8 When no code can be found in the current code symbols, place "*" in concerned code digit(s)and add "*" in 8th digit
*9 Max process temperature 150 °C
EMC Directive (2004/108/EC)
All models of FCX series transmitters type FCX-AII are in accordance with :
• the harmonized standards:
- EN 61326-1 : 2006 (Electrical equipment for measurement, control and laboratory use - EMC requirements).
(13DUW3DUWLFXODUUHTXLUHPHQWV7HVWFRQ¿JXUDWLRQRSHUDWLRQDOFRQGLWLRQVDQGSHUIRUPDQFH
criteria for tranducers with integrated or remote signal conditioning)
Emission limits : EN 61326-1 : 2006
Frequency range (MHz)
30 to 230
Limits
Basic standard
40 dB (μV/m) quasi peack, measured at 10m distance
EN 55011 / CISPR 11
Group 1 Class A
230 to 1000
47 dB (μV/m) quasi peack, measured at 10m distance
Immunity requirements : EN 61326-1 : 2006 (Table 2)
Phenomenon
Test value
Electrostatic discharge (EDS)
(OHFWURPDJQHWLF¿HOG
Basic standard
Performance criteria
4 kV (Contact)
EN 61000-4-2
B
8 kV (Air)
IEC 61000-4-2
9PWR0+]
(1
3 V/m (1.4 to 2.0 GHz)
IEC 61000-4-3
A
30 A/m
EN 61000-4-8
A
0DJQHWLF¿HOG
,(&
Burst
2 kV (5/50 NS, 5 kHz
EN 61000-4-4
Surge
1 kV Line to line
EN 61000-4-5
2 kV Line to line
IEC61000-4-5
Conducted RF
3 V (150 kHz to 80 MHz)
EN 61000-4-6
1 V/m (2.0 to 2.7 GHz)
Rated power frequency
B
IEC 61000-4-4
B
A
IEC61000-4-6
Performance criteria :
A'XULQJWHVWLQJQRUPDOSHUIRUPDQFHZLWKLQWKHVSHFL¿FDWLRQOLPLWV
B : During testing, temporary degradation or loss of function or performance which is self-recovering.
11
FKB, FKD, FKM...F
Outline dimensions for rigid mounted diaphragm seal on a gauge or an absolute pressure transmitter (unit:mm) - Dimensions of seals - Refer to page 18 and 19
G
Short mounting design
F
E
T
W
S
P
R
TROUS /
WEIGHT : 4 kg (WITHOUT OPTION)
ADD : - FLANGES WEIGHT (SEE TABLE)
- 0,8 kg FOR INDICATOR OPTION
- 2 kg FOR STAINLESS STEEL HOUSING OPTION
l
S A
12
R
S
Long mounting design
T
F
W
S
G
R
P
S
E
l
WEIGHT : 4 kg (WITHOUT OPTION)
ADD : - FLANGES WEIGHT (SEE TABLE)
- 0,8 kg FOR INDICATOR OPTION
- 2 kg FOR STAINLESS STEEL HOUSING OPTION
S A
13
FKB, FKD, FKM...F
Outline dimensions for capillary mounted diaphragm seal(s) on a differential
pressure transmitter (units:mm) - Dimensions of seals - Refer to page 18 and 19
)RU31”EDUUHGXFHGYROXPHÀDQJHVDUHZHOGHGRQWKHPHDVXULQJFHOO
Code X4
T
F
W
S
G
R
P
S
E
WEIGHT : 3,5 kg (WITH OPTION)
ADD : - FLANGES WEIGHT (SEE TABLE)
- 1 kg PER 50 mm EXTENSION
- 0,8 kg FOR INDICATOR OPTION
- 2 kg FOR STAINLESS STEEL HOUSING OPTION
l
S A
14
S A
)RU31!EDUUHGXFHGYROXPHÀDQJHVDUHZHOGHGDQGEROWHGRQWKHPHDVXULQJFHOO
T
F
W
S
G
R
P
S
E
WEIGHT : 3,5 kg (WITH OPTION)
ADD : - FLANGES WEIGHT (SEE TABLE)
- 1 kg PER 50 mm EXTENSION
- 0,8 kg FOR INDICATOR OPTION
- 2 kg FOR STAINLESS STEEL HOUSING OPTION
l
S A
S A
15
FKB, FKD, FKM...F
Outline dimensions for capillary mounted diaphragm seal(s) on a gauge or an
absolute pressure transmitter (units:mm) - Dimensions of seals - Refer to page 18 and 19
)RU31”EDUUHGXFHGYROXPHÀDQJHVDUHZHOGHGRQWKHPHDVXULQJFHOO
ELECTRICAL CONNECTION
E
E
D
D
M
F
G
WEIGHT : 3,5 kg (WITHOUT OPTION)
ADD : - FLANGES WEIGHT (SEE TABLE)
- 0,8 kg FOR INDICATOR OPTION
- 2 kg FOR STAINLESS STEEL HOUSING OPTION
G
H
J
8
4
6
E
16
9
5
7
)RU31!EDUUHGXFHGYROXPHÀDQJHVDUHZHOGHGDQGEROWHGRQWKHPHDVXULQJFHOO
T
S
F
W
G
R
P
TROUS /
S
E
l
WEIGHT : 3,5 kg (WITHOUT OPTION)
ADD : - FLANGES WEIGHT (SEE TABLE)
- 1 kg PER 50 MM EXTENSION
- 0,8 kg FOR INDICATOR OPTION
- 2 kg FOR STAINLESS STEEL HOUSING OPTION
S A
17
FKB, FKD, FKM...F
Outline dimensions of the standard diaphragm seals - Flush/extension (units : mm)
DN 50, 80, 100
ØE
L
G
t
FLANGE DIMENSIONS ACCORDING DIN 2501 ET B16.5
ØH
ØF
ØD
DIN / ISO
PN DN
40 15
40 20
40 25
ANSI
NP NW ØD ØE
95 65
105 75
115 85
40 50
40 80
16 100
'1”RU´
ØF G ØH t N x Øh
45 2
22 4 x 14
58 2
22 4 x 14
68 2
22 4 x 14
165 125 102 3
200 160 138 3
220 180 158 3
15
20
25
150 lbs 1/2” 95 60,5
150 lbs 3/4” 100 70
150 lbs 1” 110 79,5
35
43
51
2
2
2
22
22
22
4 x 16
4 x 16
4 x 16
50
50
50
15
20
25
300 lbs 1/2” 95 66,5
300 lbs 3/4” 120 82,5
300 lbs 1” 125 89
35
43
51
2
2
2
22
22
22
4 x 16
4 x 20
4 x 20
4 x 20
4 x 20
8 x 20
20 50
20 80
20 100
150 lbs 2”
150 lbs 3”
150 lbs 4”
150 120,5 92 1,6 48 20
190 152,5 127 1,6 73 24
230 190,5 158 1,6 96 24
50 50
50 80
50 100
300 lbs 2”
300 lbs 3”
300 lbs 4”
165 127 92 1,6 48 22,5 8 x 20
210 168,5 127 1,6 73 29 8 x 22
255 200 158 1,6 96 32 8 x 22
Screwed adaptor
FLANGES DIMENSIONS
DIN
AINSI
ØD ØE
PN DN
40 25
20 25
50 25
40 40
20 40
50 40
18
Pe
DN
150
300
1”
1”
150 1 1/2”
300 1 1/2”
N
115 85 4
108 79,5 4
124 89 4
150 110 4
127 98,4 4
156 114,3 4
ØF Cmin
ØH
14 68 18
15,8 50,8 16
19 50,8 17,5
18 88 18
15,8 73 18
22,2 73 21
f1
A
ØM
2
1,6
1,6
3
16
1,6
83
81
86
85
85
91
72,2
72,2
72,2
72,2
72,2
72,2
4 x 18
8 x 18
8 x 18
20
20
20
Outline dimensions of diaphragm seals with adaptors (units : mm)
Flange adaptor
48 20
73 20
96 20
Outline dimensions of sanitary diaphragm (units : mm)
The seals for the sanitary and pharmaceutical applications are available DIN, SMS and Tri Clamp standards
Seals according DIN 11851 and SMS standard
2 different designs exist for DIN 11851 and SMS : (dM = diaphragm actif diameter)
Coupling nut design
DIN 11851
DN
PN (Max)
D
h
dM
G
25
40
63
36
25
Rd 52 x 1/6
32
40
70
36
32
Rd 58 x 1/6
40
40
78
36
40
Rd 65 x 1/6
50
40
112
36
52
Rd 78 x 1/6
65
40
112
36
65
Rd 95 x 1/6
80
40
127
36
76
Rd110 x 1/4
DN
PN (Max)
D
h
dM
G
25
40
51
38
25
Rd 40 x 1/6
32
40
60
38
32
Rd 48 x 1/6
38
40
74
38
40
Rd 60 x 1/6
51
40
84
38
52
Rd 70 x 1/6
63.5
40
100
38
65
Rd 85 x 1/6
76
40
114
38
76
Rd 98 x 1/4
Male thread design
h
SMS
dM
DN
G
Tri Clamp design
DN
PN (Max)
D
h
dM
1“1/2
40
50,5
35
32
2“
40
64
35
40
2“1/2
40
77,5
35
50
3“
40
91
35
65
Dead volume seal
53
43
ø43,7
DN25 NUT
(DIN 11851)
ø36
Diaphragm
ø40
19
FKB, FKD, FKM...F
CONNECTION DIAGRAM
Fuji Electric Corp. of America
Instrumentation & Control Division
50 Northfield Avenue Edison, NJ 08837 USA
Phone: 732-560-9410
x-fea-icsales@fujielectric.com
www.americas.fujielectric.com
Fuji Electric can accept no responsability for possible errors in catalogues, brochures and other printed material. Fuji Electric reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary
LQVSHFL¿FDWLRQVDOUHDG\DJUHHG$OOWUDGHPDUNVLQWKLVPDWHULDODUHSURSHUW\RIWKHUHVSHFWLYHFRPSDQLHVDOOULJKWVUHVHUYHG