RDY2000BN BACnet Thermostat Conventional Application 14900

Add to my manuals
42 Pages

advertisement

RDY2000BN BACnet Thermostat Conventional Application 14900 | Manualzz

RDY2000BN BACnet

Thermostat Conventional

Application 14900

Application Note

140-1231

2017-01-17

Building Technologies

Copyright Notice

Copyright Notice

Notice

Document information is subject to change without notice by Siemens Industry, Inc.

Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Industry, Inc.

All software described in this document is furnished under a license agreement and may be used or copied only in accordance with license terms.

For further information, contact your nearest Siemens Industry, Inc. representative.

Copyright 2017 Siemens Industry, Inc.

To the Reader

Your feedback is important to us. If you have comments about this manual, please submit them to: [email protected]

Other product or company names mentioned herein may be the trademarks of their respective owners.

Printed in the USA.

2

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Siemens Industry, Inc.

Table of Contents

Overview .............................................................................................................................. 4

BACnet ................................................................................................................................. 4

Hardware Inputs ................................................................................................................... 5

Hardware Outputs................................................................................................................. 5

I/O Mix (Relay Assignment Matrix) ....................................................................................... 6

Connection Diagram ............................................................................................................. 7

Ordering Notes ..................................................................................................................... 7

Sequence of Operation ......................................................................................................... 8

Control Temperature Setpoints ............................................................................................ 8

Effective Room Temperature ................................................................................................ 9

Heating/Cooling Switchover ................................................................................................. 9

Staging Control ................................................................................................................... 10

Compressor Operation ....................................................................................................... 10

Electric Heat (Optional) ...................................................................................................... 11

Gas Furnace (Optional) ...................................................................................................... 12

Operation Diagram – RTU with Three Cooling Stages and Three Heating Stages. .......... 13

Fan Operation ..................................................................................................................... 13

Wiring Diagram ................................................................................................................... 14

Auxiliary Sequences ........................................................................................................... 15

Humidification ................................................................................................................ 15

Dehumidification ............................................................................................................ 16

Occupancy Notification ....................................................................................................... 17

Economizer Enable ....................................................................................................... 18

Pre-Purge ...................................................................................................................... 18

Semi-Continuous Fan .................................................................................................... 19

Air Quality Management ..................................................................................................... 19

Service and Fault Messages............................................................................................... 20

Sensor Failure Handling ..................................................................................................... 20

I/O Test Mode ..................................................................................................................... 20

Overcurrent Protection ....................................................................................................... 21

BACnet Scheduler .............................................................................................................. 22

Application 14900 Point Database ...................................................................................... 23

Scheduling Examples ......................................................................................................... 40

Application Note, App 14900

3

140-1231

2017-01-17

Overview

BACnet

Overview

In Application 14900, the controller controls multiple compressors for cooling, and a multiple-stage heater for heating. This unit may be equipped with electric heat or a fossil fuel furnace. Typically, this US Room Temperature Unit (RTU) application fits most five-wire thermostats on the market.

Secondary features include: Demand Ventilation Control, Occupancy indication,

Economizer Enabling, and Humidification/Dehumidification Enabling a call for external equipment to energize.

4

Siemens Industry, Inc.

Figure 1: Hardware Diagram.

BACnet

The thermostat communicates on industry-standard BACnet MS/TP networks.

NOTE:

Bold, mixed case names = Exposed BACnet objects

All caps names = Internal variables that cannot be accessed through BACnet

Table 1: BIBB

Product Supported BIBBs BIBB Name

RDY2000BN DS-RP-B

DS-RPM-B

Data Sharing - Read Property-B

Data Sharing - Read Property Multiple-B

DS-WP-B

DS-WPM-B

DS-COV-B

SCHED-WS-I-B

DM-DDB-B

DM-DOB-B

DM-DCC-B

DM–PT–B

Data Sharing - Write Property-B

Data Sharing – Write Property Multiple - B

Data Sharing – Change of Value - B

Scheduling – Weekly Schedule Internal - B

Device Management - Dynamic Device Binding-B

Device Management - Dynamic Object Binding-B

Device Management - Device Communication Control-B

Device Management – Private Transfer - B

Application Note, App 14900 140-1231

2017-01-17

Product

Overview

Hardware Inputs

Supported BIBBs BIBB Name

DM-TS-B Device Management – Time Synchronization - B

DM-RD-B

DM-R-B

Device Management - Reinitialize Device-B

Device Management – Restart - B

Hardware Inputs

● Configurable input IN1

● Configurable input IN2

● Configurable input IN3

● Configurable input IN4

● Onboard space temperature

● Onboard space humidity

Configurable inputs can be configured to the following types:

1 = Indoor Temperature (Remote)

2 = Indoor Temperature (Average)

3 = Supply Temperature

4 = Return Temperature

5 = Outdoor Temperature

6 = Humidity (0-10V)

7 = CO2 (0-10V)

8 = Occupancy (DI)

9 = Fault

10 = Not Used

Hardware Outputs

● G Fan

● Y1 Compressor

● Y2 Compressor

● W1 Aux Heat 1

● W2 Aux Heat 2

● O/B may function as the third stage Cool or Heat. See

Matrix)

for more details.

I/O Mix (Relay Assignment

● Configurable relay output OUT1

● OUT1 can function as third stage Cool when both third stage Cool and third stage

Heat are available. See

I/O Mix (Relay Assignment Matrix)

for more details.

● Configurable relay output OUT2

● Configurable relay output OUT3

Siemens Industry, Inc. Application Note, App 14900

5

140-1231

2017-01-17

Overview

I/O Mix (Relay Assignment Matrix)

Configurable outputs can be configured to the following types:

1 = Humidification

2 = Dehumidification

3 = Occupied

4 = Air Quality

5 = Economizer Enable

6 = Not Used

I/O Mix (Relay Assignment Matrix)

In a conventional RTU application, the maximum number of compressors is three, with up to three stages of heat. The number of stages can be configured using the BACnet points HtgStg and CoolStg.

Heating

Stages

Cooling

Stages

Y1 Y2 W1 W2 O/B OUT1

(AuxOut1)

0 1 N/A N/A N/A N/A N/A

0 2

Stage 1

Cooling

Stage 1

Cooling

Stage 2

Cooling

N/A N/A N/A N/A

0

1

3

0

Stage 1

Cooling

N/A

Stage 2

Cooling

N/A

N/A N/A

N/A

Stage 3

Cooling

N/A

N/A

N/A

1

1

1

2

2

2

2

3

3

3

1

2

3

0

1

2

3

0

1

2

Stage 1

Cooling

Stage 1

Cooling

Stage 1

Cooling

N/A

Stage 1

Cooling

Stage 1

Cooling

Stage 1

Cooling

N/A

Stage 1

Cooling

Stage 1

Cooling

N/A

Stage 2

Cooling

Stage 2

Cooling

N/A

N/A

Stage 2

Cooling

Stage 2

Cooling

N/A

N/A

Stage 2

Cooling

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

Stage 1

Heating

N/A

N/A

N/A

Stage 2

Heating

Stage 2

Heating

Stage 2

Heating

Stage 2

Heating

Stage 2

Heating

Stage 2

Heating

Stage 2

Heating

N/A

N/A

Stage 3

Cooling

N/A

N/A

N/A

Stage 3

Cooling

Stage 3

Heating

Stage 3

Heating

Stage 3

Heating

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

6

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Overview

Connection Diagram

Heating

Stages

3

Cooling

Stages

3

Y1

Stage 1

Cooling

Y2

Stage 2

Cooling

W1 W2 O/B

Stage 1

Heating

Stage 2

Heating

Stage 3

Heating

OUT1

(AuxOut1)

Stage 3

Cooling

Connection Diagram

Table 2: Standard Conventional Connection Diagram

C HVAC Control Circuit Common

RC 24 Vac from Transformer on Cooling System

RH 24 Vac from Transformer on Heating System

G

Y1

Fan

First Stage Cooling

Y2 Second Stage Cooling

O/B Third Stage Heating (only when Third Stage Heating is enabled), or Third Stage Cooling.

(only when Third Stage Cooling is enabled and Third Stage Heating is not enabled)

W1 First Stage Heating

W2 Second Stage Heating

OUT1 Third Stage Cooling (only when both Third Stage Cooling and Heating are enabled)

OUT2 Configurable Output

OUT3 Configurable Output

INC Configurable Input Common

IN1 Configurable Input 1

IN2 Configurable Input 2

IN3 Configurable Input 3

IN4 Configurable Input 4

Ordering Notes

Part Number: RDY2000BN Siemens RDY2000 BACnet Thermostat

Siemens Industry, Inc. Application Note, App 14900

7

140-1231

2017-01-17

Sequence of Operation

Control Temperature Setpoints

Sequence of Operation

The following paragraphs show the sequence of operation for Application 14900.

Control Temperature Setpoints

This application has a number of different room temperature setpoints (ComfortHtgSP,

EconHtgSP, ComfortClgSP, and EconClgSP). The setpoint can be temporarily overridden for a period of time (default is 30 minutes). The application controls using the effective setpoint (EFF STPT). EFF STPT is set to different values depending on its

HVAC Mode (Cooling, Heating, or Neutral), override status, and the time of day.

CoolingSp : Cooling Setpoint

CoolingDB: Cooling Deadband

CoolingDB is divided equally above and below CoolingSp; therefore, (CoolingSp + 1/2

CoolingDB) is the switching on point of the first cooling stage, and (CoolingSp – 1/2

CoolingDB) is the switching off point of the first cooling stage.

HeatingSp: Heating Setpoint

HeatingDB: Heating Deadband

HeatingDB is divided equally above and below HeatingSp; therefore, (HeatingSp – 1/2

HeatingDB) is the switching on point of the first heating stage, and (HeatingSp + 1/2

HeatingDB) is the switching off point of the first heating stage.

StgDifCl: Cooling Inter-stage Differential

(CoolingSp + 1/2 CoolingDB+ StgDifCl) is the switching on point of the second cooling stage, and (CoolingSP – 1/2 CoolingDB+ StgDifCl) is the switching off point of the second cooling stage.

StgDifHt: Heating Inter-stage Differential

(HeatingSp – 1/2 HeatingDB – StgDifHt) is the switching on point of the second heating stage, and (HeatingSp + 1/2 HeatingDB – StgDifHt) is the switching off point of the second heating stage.

CLG SPAN: Cooling SPAN combined ∆T of all stages of cooling,

CLG SPAN is derived from other parameters. For single-stage cooling: CLG SPAN =

CoolingDB; For multi-stage cooling: CLG SPAN = CoolingDB + StgDifCl*n (where represents the number of stages of additional cooling.)

n

HTG SPAN: Heating SPAN combined ∆T of all stages of heating, HTG SPAN is derived from other parameters. For single-stage heating: HTG SPAN = HeatingDB; For multi-stage heating: HTG SPAN = HeatingDB + StgDifHt*n (where number of stages of additional heating.)

n

represents the

CLG SPAN or HTG SPAN indicates how the bias between room temperature and room setpoint could possibly be due to the characteristic of hysteresis control.

8

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Sequence of Operation

Effective Room Temperature

NOTE:

Effective Setpoint does not exist as a BACnet object. The controller determines what the Effective setpoint is by evaluating the value of ModeEff.

If ModeEff is Heating, EffectiveSetpoint is the value of HeatingSp.

If ModeEff is Cooling, EffectiveSetpoint is the value of CoolingSp.

The actual value used by HeatingSp or CoolingSp at any given time is determined by a number of factors. When operating without any external inputs, the thermostat’s schedule will determine the effective operating mode, RM OP MODE.

If RM OP MODE is set to Comfort, then HeatingSp controls ComfortHtgSP and the

CoolingSp controls ComfortClgSP. If RM OP MODE is set to Economy, then

HeatingSp controls EconHtgSP and the CoolingSp controls EconClgSP. If RM OP

MODE is set to Protection, then HeatingSp controls ProtHtgSP and the CoolingSp controls ProtClgSP.

NOTE:

You can override the effective setpoint through the local touchscreen interface or remotely through the BACnet network by commanding Multistate Value 24,

SchedMode. The local override is only effective for the period determined by

HrsOvrRide (default value is 2 hours).

Effective Room Temperature

IndoorTmpEff:

When an external temperature sensor is not installed, IndoorTmpEff is the onboard temperature measuring value.

When an external temperature sensor is installed, IndoorTmpEff can be configured to either use an external measuring value or the average of external and onboard measuring values.

The external temperature sensor can also be a network sensor. In this case, the external temperature sensor does not have to be physically installed.

The RDY2000BN supports controlling to sensor input over the network. For example, you can take one of the universal inputs, characterize it as a voltage input, remove it from service, and expose it to the network as writeable. Then, you can assign the value of another sensor over the network to this input.

If IndoorTmpEff does not read correctly, you can raise or lower it by changing the value of TmpOffset to the appropriate positive or negative value to make IndoorTmpEff read the correct value.

If the external temperature sensor fails, the unit can be manually switched to only use an onboard sensor.

If the onboard sensor fails, the unit stops running.

Siemens Industry, Inc.

Heating/Cooling Switchover

Auto Switchover enables the controller to automatically switch HVAC modes.

If IndoorTempEff > CoolingSp and Heating has turned off and has been off for the length of time set in ChgOvrDly, the controller switches to Cooling mode.

If IndoorTempEff < HeatingSp and Cooling has turned off and has been off for the length of time set in ChgOvrDly, the controller switches to Heating mode.

Application Note, App 14900

9

140-1231

2017-01-17

Sequence of Operation

Staging Control

ChgOvrDB: Change Over Deadband restricts how close CoolingSp and HeatingSp can be set. A minimum deadband (default is 5°F) must to be maintained. To separate the

CoolingSp and HeatingSp, one setpoint change may change the other setpoint to maintain a gap between them.

Staging Control

The RTU is controlled by a hysteresis loop (Step Control). Hysteresis prevents the compressor/heater from frequently switching on and off. When the room temperature reaches the corresponding switching on setpoint of a certain cooling/heating stage, that stage will be turned on. When the room temperature reaches the corresponding switching off setpoint of a certain cooling/heating stage, that stage is turned off.

For example, in Heating mode the thermostat switches the heater on when the temperature drops below A, but does not turn it off until the temperature rises above B, where B is greater than A.

If there is a call to turn on/off multiple stages, an Inter-stage delay will apply between the two stages being turned ON/OFF. For more information, see the

Compressor

Operation

section.

Compressor Operation

When the HVAC Mode is in Cooling mode, the cooling staging logic controls the compressor.

If a compressor has been ON, it will not shut OFF until its minimum ON timer has expired. Likewise, if a compressor has been OFF, it will not turn ON until its minimum

OFF timer has expired.

In addition to the above rules, there is a time-based separation of cooling stages --

Cooling Inter-stage Delay applies to the unit with multiple cooling stages. There is also a time-based separation of heating stages -- Heating Inter-stage Delay which applies to the unit with multiple heating stages.

The following paragraphs explain compressor staging:

If CoolStg = 0, the application does not control COMPRESSOR 1 (Y1).

If CoolStg ≥ 1, the application controls COMPRESSOR 1 (Y1) as follows:

● If IndoorTmpEff is greater than the switching on point of the first cooling stage

(CoolingSp + 1/2 CoolingDB), and the first compressor has been OFF for at least the time set in MIN OFF, COMPRESSOR 1 (Y1) is turned ON.

● If IndoorTmpEff is less than the switching off point of the first cooling stage

(CoolingSp – 1/2 CoolingDB), and the first compressor has been ON for at least the time set in MIN ON, COMPRESSOR 1 (Y1) is turned OFF.

If CoolStg ≤ 1, the application does not control COMPRESSOR 2 (Y2).

If CoolStg = 2, the application controls COMPRESSOR 2 (Y2) as follows:

● If IndoorTmpEff is greater than the switching on point of the second cooling stage

(CoolingSp + 1/2 CoolingDB + StgDifCl), the second compressor has been OFF for at least the time set in MIN OFF, and the Inter-stage Delay timer has expired,

COMPRESSOR 2 (Y2) is turned ON.

● If IndoorTmpEff is less than the switching off point of the second cooling stage

(CoolingSp – 1/2 CoolingDB + StgDifCl), and the second compressor has been ON for at least the time set in MIN ON, COMPRESSOR 2 (Y2) is turned OFF.

10

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Siemens Industry, Inc.

Sequence of Operation

Electric Heat (Optional)

● An Inter-stage Delay timer must be enforced between the second cooling stage

OFF and the first cooling stage OFF to ensure that the first compressor will not be turned off until the second compressor has been turned off for the time set in the

Inter-stage Delay.

If CoolStg = 3, the application controls COMPRESSOR 3 (O/B or AuxOut1) as follows:

● If IndoorTmpEff is greater than the switching on point of the third cooling stage

(CoolingSp + 1/2 CoolingDB + StgDifCl*2), the third compressor has been OFF for at least the time set in MIN OFF, and the Inter-stage delay timer has expired,

COMPRESSOR 3 (O/B or AuxOut1) is turned ON.

● If IndoorTempEff is less than the switching off point of the third cooling stage

(CoolingSp – 1/2 CoolingDB + StgDifCl*2), and the third compressor has been ON for at least the time set in MIN ON, COMPRESSOR 3 (O/B or AuxOut1) is turned

OFF.

● An Inter-stage Delay timer must be enforced between the third cooling stage OFF and the second cooling stage OFF to ensure that the second compressor will not be turned off until the third compressor has been turned off for the time set in the

Inter-stage Delay.

Electric Heat (Optional)

When the HVAC Mode is in heating mode, and the heating staging logic controls the electric heater, Parameter P105 (HTG FAN) in the Installer Setup Menu, Fan

Operation, FanOpr must be set to ELE.

If a heating stage has been ON, it will not shut OFF until its minimum ON timer has expired. Likewise, if a heating stage has been OFF, it will not turn ON until its minimum

OFF timer has expired.

In addition to above rules, a time-based separation of heating stages -- Heating Interstage Delay applies to the unit with multiple heating stages.

The following paragraphs explain the electric heater staging.

If HeatStg = 0, the application does not control HTG STG 1 (W1).

If HeatStg ≥ 1, the application controls HTG STG 1 (W1) as follows:

● If IndoorTmpEff is less than the switching on point of the first heating stage

(HeatingSp – 1/2 HeatingDB), and the first heating stage has been OFF for at least the time set in MIN OFF, HTG STG 1 is turned ON.

● If IndoorTmpEff is greater than the switching off point of the first heating stage

(HeatingSp + 1/2 HeatingDB), and the first heating stage has been ON for at least the time set in MIN ON, HTG STG 1 (W1) is turned OFF.

If HeatStg ≤ 1, the application does not control HTG STG 2 (W2).

If HeatStg ≥ 2, the application controls HTG STG 2 (W2) as follows:

● If IndoorTmpEff is less than the switching on point of the second heating stage

(HeatingSp – 1/2 HeatingDB – StgDifHt), the second heating stage has been OFF for at least the time set in MIN OFF, and Inter-stage Delay timer has expired, HTG

STG 2 (W2) is turned ON.

● If IndoorTmpEff is greater than the switching off point of the second heating stage

(HeatingSp + 1/2 HeatingDB – StgDifHt), and the second heating stage has been

ON for at least the time set in MIN ON, HTG STG 2 (W2) is turned OFF.

Application Note, App 14900

11

140-1231

2017-01-17

Sequence of Operation

Gas Furnace (Optional)

● An Inter-stage Delay (StgDlyHt) timer must be enforced between the third heating stage OFF and the second heating stage OFF to ensure that the second heating stage won’t be turned off until the third heating stage has been turned off for the time set in Inter-stage Delay timer.

If HeatStg = 3, the application controls HTG STG 3 (O/B) as follows:

● If IndoorTmpEff is less than the switching on point of the third heating stage

(HeatingSp – 1/2 HeatingDB- StgDifHt*2), the third heating stage has been OFF for at least the time set in MIN OFF, and Inter-stage Delay timer has expired, HTG

STG 3 (O/B) is turned ON.

● If IndoorTmpEff is greater than the switching off point of the third heating stage

(HeatingSp + 1/2 HeatingDB – StgDifHt*2), and the third heating stage has been

ON for at least the time set in MIN ON, HTG STG 3 is turned OFF.

Gas Furnace (Optional)

When the HVAC Mode is in heating mode, and the heating staging logic controls a furnace, Parameter P105 (HTG FAN) FanOpr in the Installer Setup Menu must be set to gAS.

If a heating stage has been ON, it will not shut OFF until its minimum ON timer has expired. Likewise, if a heating stage has been OFF, it will not turn ON until its minimum

OFF timer has expired.

In addition to above rules, a time-based separation of heating stages--Heating Interstage Delay--applies to the unit with multiple heating stages.

The following paragraphs explain the electric heater staging.

If HeatStg = 0, the application does not control HTG STG 1.

If HeatStg ≥ 1, the application controls HTG STG 1 as follows:

● If IndoorTempEff is less than the switching on point of the first heating stage

(HeatingSp – 1/2 HTG DB), and the first heating stage has been OFF for at least the time set in MIN OFF, HTG STG 1 (W1) is turned ON.

● If IndoorTempEff is greater than the switching off point of the first heating stage

(HeatingSp + 1/2 HeatingDB), and the first heating stage has been ON for at least the time set in MIN ON, HTG STG 1 (W1) is turned OFF.

If HeatStg ≤ 1, the application does not control HTG STG 2 (W2).

If HeatStg ≥ 2, the application controls HTG STG 2 (W2) as follows:

● If IndoorTempEff is less than the switching on point of the second heating stage

(HeatingSp – 1/2 HeatingDB - StgDifHt), the second heating stage has been OFF for at least the time set in MIN OFF, and the Inter-stage Delay timer has expired,

HTG STG 2 (W2) is turned ON.

● If IndoorTempEff is greater than the switching off point of the second heating stage

(HeatingSp + 1/2 HeatingDB – StgDifHt), and the second heating stage has been

ON for at least the time set in MIN ON, HTG STG 2 (W2) is turned OFF.

● An Inter-stage Delay (StgDlyHt) timer must be enforced between the third heating stage OFF and the second heating stage OFF to ensure that the second heating stage won’t be turned off until the third heating stage has been turned off for the time set in the Inter-stage Delay (StgDlyHt).

12

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Sequence of Operation

Operation Diagram – RTU with Three Cooling Stages and Three Heating Stages.

If HTG STG NUMBER = 3, the application controls HTG STG 3 (O/B) as follows:

● If IndoorTempEff is less than the switching on point of the third heating stage

(HeatingSp – 1/2 HeatingDB – StgDifHt*2), the third heating stage has been OFF for at least the time set in MIN OFF, and the Inter-stage Delay (StgDlyHt) timer has expired, HTG STG 3 (O/B) is turned ON.

● If IndoorTempEff is greater than the switching off point of the third heating stage

(HeatingSp + 1/2 HeatingDB – StgDifHt*2), and the third heating stage has been

ON for at least the time set in MIN ON, HTG STG 3 (O/B) is turned OFF.

Operation Diagram – RTU with Three Cooling Stages and

Three Heating Stages.

Siemens Industry, Inc.

Figure 2: RTU with Three Cooling Stages and Three Heating Stages.

Fan Operation

AUTO Mode – The fan relay is energized upon a call for heating or cooling per the operating sequence. When there is no demand for heating or cooling (none of heating/cooling stages are activated) the fan relay is de-energized.

The fan will turn ON when one of the following conditions has been met:

● In Heating mode, when the compressor or stage of electric heat is ON.

● In Cooling mode, 15 seconds before the first stage of cooling is energized.

The fan will turn OFF only after the following condition has been met:

● The compressor and stages of electric heat have been OFF for at least 30 seconds.

Application Note, App 14900

13

140-1231

2017-01-17

Sequence of Operation

Wiring Diagram

ON Mode – The fan relay is energized regardless of whether or not there is a call for heating or cooling, unless the unit is set to Unit Off.

Fan Opr - The fan relay can be set to be energized or not energized upon call for heat using Paramater P105 (HTG FAN). If P105 is set to ELE, the fan relay responds to the call for heat to energize. If P105 is set to gAS, the fan relay will not be energized upon a call for heat; instead the blower motor is energized by the furnace control board. The furnace control board provides fan delay on/off, protection, and provides other control functions as it directly interacts with the ignition/blower sequence.

Wiring Diagram

CAUTION

The thermostat’s digital outputs only control 24 Vac loads. The maximum rating is 1A

(24 VA) for each DO. Total maximum rating for the thermostat, including all energized

DOs is 4A (96 VA). Auxiliary Output 3 (OUT3) may be configured as a Dry Contact by removing jumper RC-C3 and connecting the controlled device to both terminals OUT3 and C3.

An external interposing relay is required for any of the following:

- VA requirements higher than the maximum

- 110 or 220 Vac requirements

- DC power requirements

Configurable Inputs are Off (default). See

RDY2000BN BACnet Enabled Commercial

Room Thermostat Installation Instructions

(125-1009), 300 Series Parameters to enable inputs. Temperature sensors that may be configured as Thermistor inputs are:

10K Type 2 (default) or 0 to 10V inputs. Humidity and CO2 sensors may be configured as 0 to 10V inputs. Occupancy and Fault sensors may be configured as digital inputs.

14

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Sequence of Operation

Auxiliary Sequences

Siemens Industry, Inc.

Figure 3: Wiring Schematic, Conventional.

Auxiliary Sequences

The RDY2000BN primary sequences are designed to control single and multi-stage heating/cooling systems to maintain a user-defined temperature setpoint.

The following auxiliary sequences are available to optimize occupant comfort and system efficiency:

Humidification

If one of the configurable digital outputs is configured for a humidification function, the corresponding relay will close and enable a 24 Vac output signal to be transmitted to the humidification device. Humidification and dehumidification relays, if configured as such, cannot be energized simultaneously.

● The humidification relay (monitored through HmdyOn) will be energized when measured humidity drops approximately 4% below setpoint (HmdySp) and will be de-energized when measured humidity reaches setpoint. Deadbands and proof timers are in force to prevent short cycling. The thermostat controls humidification only in Heating mode.

● You must enter a humidity setpoint (HmdySp). The valid range is 10 to 90%; the default value is 25%. If the humidity drops to 4% below setpoint, a 30-second proof timer engages. If the humidity is still 4% below the setpoint after the proof timer times out, the humidification relay energizes.

Application Note, App 14900

15

140-1231

2017-01-17

Sequence of Operation

Auxiliary Sequences

● If humidity rises above (setpoint – 4%) before the proof timer times out, the humidification relay does not engage and the proof timer is reset. If the humidity rises to setpoint, a 30-second proof timer engages. If the humidity is still above the setpoint after the proof timer times out, the humidification relay de-energizes.

● If Parameter P320 (IND HMDTY) is set to NO (default) then the humidification relay will not be enabled unless the heating relay is energized. If Parameter P320 is set to YES, then the humidification relay can be energized at any time, regardless of the heating status. The fan relay is not energized by the humidification sequence.

Dehumidification

If one of the configurable digital outputs is configured for a humidification function, the corresponding relay closes and enables a 24 Vac output signal to be transmitted to the dehumidification device. Humidification and dehumidification relays cannot be energized simultaneously.

● The dehumidification relay will energize when measured humidity rises approximately 4% above setpoint, and will de-energize when measured humidity reaches setpoint. Deadbands and proof timers are enforced to prevent short cycling. The thermostat defaults to control dehumidification in Cooling mode only.

● You must enter a humidity setpoint (HmdySp). The valid range is 10 to 90%; the default value is 50%. If the humidity rises to 4% above setpoint, a 30-second proof timer engages. If the humidity is still 4% above setpoint after the proof timer times out, the dehumidification relay energizes.

● If the humidity drops below (setpoint + 4%) before the proof timer times out, the dehumidification relay does not engage, and the proof timer is reset. If the humidity drops to setpoint, a 30-second proof timer engages. If the humidity is still below setpoint after the proof timer times out, the dehumidification relay de-energizes.

● If Parameter P320 (IND HMDTY) is set to NO (default), the dehumidification relay will not be enabled unless the cooling relay is energized. If Parameter P320 is set to YES, then the dehumidification relay can be energized at any time, regardless of the cooling status. The fan relay is not energized by the dehumidification sequence.

16

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Sequence of Operation

Occupancy Notification

Siemens Industry, Inc.

Figure 4: Humidification and Dehumidification Operation.

HmdySp: Humidification Setpoint, user-adjustable to desired level in Humidification mode.

DeHmdySp: Dehumidification Setpoint, user-adjustable to desired level in

Dehumidification mode.

HUSP DB: A deadband maintained between the HmdySp and the DeHmdySp. If one changes, the other dynamically shifts to maintain at least a 15% gap.

HU DB: Humidification/Dehumidification Deadband.

Occupancy Notification

Many internal control sequences rely on occupancy status, for example: room setpoint choice, fan operation, and economizer enable. Occupancy Notification also goes out from a configurable relay to enable external equipment. The space is assumed to be occupied when the schedule mode is set to Comfort. An optional occupancy sensor can also be used for definitive proof of occupancy (manual override to the room temperature setpoint is the evidence that the space is being occupied).

The thermostat uses three methods to determine if the space is occupied: scheduler, manual override, or occupancy sensor.

● To use the Occupancy functions, the thermostat must have an active schedule.

The local scheduler does not have the direct information about occupancy; instead, the space is assumed to be occupied when the schedule mode is set to Comfort.

● During periods in which the schedule indicates the space is unoccupied, any human interaction with the thermostat (for example, setpoint adjustment) will put the thermostat into Occupied mode.

Application Note, App 14900

17

140-1231

2017-01-17

Sequence of Operation

Occupancy Notification

● An optional occupancy sensor can be used in conjunction with the schedule. The thermostat will follow the assumptions above, but an input from the occupancy sensor during a scheduled unoccupied period will put the thermostat into Occupied mode for the duration of the timer set in Parameter P404 (OCC MRT) Occupancy

Min run Timer (OccMinRun). If the optional occupancy sensor is used, Parameter

P404 can be used to set a minimum run timer for any actions that are activated by occupancy, such as Economizer Enable, Control to occupied temperature setpoints, and so on. Note that many occupancy sensors also have onboard proof timers.

● If the unit does not have an active schedule, or if it has an active schedule set locally with the effective setpoint being overridden by BMS, the thermostat assumes that the space is always occupied.

Economizer Enable

The Economizer Enable relay energizes whenever a cooling relay is energized or the space is occupied. The space is assumed to be occupied when the schedule mode is set to Comfort. An optional occupancy sensor can also be used for definitive proof of occupancy.

An output configured for Occupancy Notification can also be used for Economizer

Enabling, for example, while working with Siemens POL 220 Series Economizer

Controller.

Economizer Enable relay (if configured) functions as follows:

● Occupied = Relay energized

● Unoccupied and no call for cooling = Relay not energized

● Unoccupied and call for cooling = Relay energized

● Fresh Air icon is activated

Pre-Purge

To enable the economizer and energize the fan relay prior to scheduled occupancy, set Parameter P403 (PRE OC PRG) PreOcpyPrg to the number of hours before scheduled occupancy for pre-purge to begin. This function requires a schedule to be configured.

Three conditions enable this functionality:

● Unit must have an active onboard scheduler.

● One of the outputs must be set to ECONOMIZER ENABLE.

● PRE-OCCUPANCY PURGE parameter must be greater than 0.

The Economizer Enable and fan relays energize at

X

number of hours before the first scheduled occupancy period. (where

X

is the value entered for PRE-OCCUPANCY

PURGE parameter). The Fresh Air and Fan icons are activated. Other icons are activated or deactivated per standard operation.

The pre-purge period stops when the first scheduled occupancy period starts. At that time, everything reverts to normal operation.

18

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Sequence of Operation

Air Quality Management

Semi-Continuous Fan

If Parameter P405 (CONT FAN) is selected in the set-up menu, the fan relay energizes any time the space is occupied as determined by the Scheduler, or input from the occupancy sensor.

Air Quality Management

If measured CO2 exceeds the setpoint (1000 ppm) by 200 ppm, after a proof timer of

60 seconds, or a CO2 concentration still exceeds the setpoint (1000 ppm) by 200 ppm, the Air Quality output relay energizes and the Fresh Air icon activates. The fan relay (G) energizes and the icon displays.

When measured CO2 falls below the setpoint (CO2Setpoint) after a proof timer of 60 seconds has expired, and the appropriate minimum run time has been met, the Air

Quality output relay de-energizes and the fan relay reverts to Normal operation.

The DCV Minimum run time is five minutes; DCV Minimum off time is five minutes.

Figure 5: Air Quality Management Operation.

Siemens Industry, Inc. Application Note, App 14900

19

140-1231

2017-01-17

Service and Fault Messages

Sensor Failure Handling

Service and Fault Messages

All of the three counters for the Service UV Lamp, Service Humidifier and Service Air

Filter are tied to the fan running and are based on calendar days.

● Service UV Lamp (SrvcUvLamp):

The UV Lamp counter keeps track of the run time of the fan calendar days since the UV Lamp service reminder was last acknowledged/cleared. The UV Lamp

Service reminder is triggered when the counter reaches the value set in the Service

UV Lamp parameter. The counter is reset while acknowledging/clearing the UV

Lamp service reminder.

● Service Humidifier (SrvcHmdy):

The Humidifier counter keeps track of the run time of the fan calendar days since the Humidifier service reminder was last acknowledged/cleared. The Humidifier service reminder is triggered when the counter reaches the value set in Service

Humidifier parameter. The counter is reset while acknowledging/clearing the

Humidifier service reminder.

● Service Air Filter (SrvcFilter):

The Air Filter counter keeps track of the run time of the fan calendar days since the

Air Filter service reminder was last acknowledged/cleared. The Air Filter service reminder is triggered when the counter reaches the value set in the Service Air

Filter parameter. The counter is reset while acknowledging/clearing the Air Filter service reminder.

Sensor Failure Handling

● Failure of external temperature sensor:

Stop control - manual change to internal sensor required

Control to onboard sensor, and activate SERVICE REQUIRED segment. Help text displays SNSR X FAIL.

● Failure of external humidity sensor:

Control to onboard sensor, and activate SERVICE REQUIRED segment. Help text displays SNSR X FAIL.

● Failure of onboard temp sensor:

Stop control and displays FAILURE

● Failure of onboard humidity sensor:

Stop humidity control, and activate SERVICE REQUIRED segment. Help text displays HUM FAIL.

● Failure of external CO2 sensor:

Stop Air Quality control, and activate SERVICE REQUIRED segment. Help text displays SNSR X FAIL.

I/O Test Mode

Certain expert menus, such as the P500 Series and P900 Series, can disrupt the normal operation and force the unit into Test mode, releasing all of the outputs.

Under the P900 Series menu, the outputs can be overridden by I/O test function and no minimum on/off timers are enforced.

After exiting the P500 Series and P900 Series menus, the unit goes back to normal operation from the Test mode, enforcing all minimum off timers first and then restarting all primary and secondary logic.

20

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Service and Fault Messages

Overcurrent Protection

Overcurrent Protection

If the sum of the current flowing through all of the relays exceeds 3A, all of the relays will revert to their OFF state and the OverCurrent binary value object will turn ON. The

RDY2000BN will remain in that state for four minutes. After that time, all of the relays that were placed in the OFF state will change to their ON state.

Then, the controller re-evaluates the overcurrent condition:

● If the sum of the current through the relays does not exceed 3A, the RDY2000BN controls normally, and the OverCurrent binary value turns OFF

● If the sum of the current through the relays exceeds 3A again, the process repeats itself, and the OverCurrent binary value turns ON.

Siemens Industry, Inc. Application Note, App 14900

21

140-1231

2017-01-17

BACnet Scheduler

BACnet Scheduler

The thermostat’s Scheduler functionality can be manually configured using the P107

SCHEDULER in the Wizard/Installer menu. This parameter simplifies the task of entering the local schedule using the touchscreen interface for cases where a day’s schedule may be identical to another day’s schedule. The local schedule can be disabled by setting P107 = OFF.

● By setting P107 = 1, all days will contain the same schedule.

● By setting P107 = 2, Monday through Friday will share a schedule and Saturday through Sunday will share another schedule.

● By setting P107 = 3, Monday through Friday will share a schedule, Saturday and

Sunday will each have a unique schedule.

● By setting P107 = 7, all seven days of the week will have individual schedules.

When editing a schedule through the local touchscreen interface, up to six events can be defined per schedule using the Scheduler menu. When editing a schedule over the

BACnet network, the client simply needs to write to the Weekly_Schedule property of

Schedule instance 0, WeeklySchedule_1.

NOTES:

1. When the schedule is edited using the BACnet network, P107 will be set to 7.

2. The local schedule will write to MultistateValue Instance 24, SchedMode.

This object may be overridden using the network to affect a “temporary exception mode”. Valid states include: Comfort (1), Economy (2) and Protection (3). The corresponding setpoints for each mode are set using AnalogValue instance 32,

ComfortClgSP, AnalogValue instance 33, ComfortHtgSP, AnalogValue instance 34,

EconClgSP, AnalogValue instance 35, EconHtgSP, AnalogValue instance 39,

ProtClgSP and AnalogValue instance 40, and ProtHtgSP. Local overrides will occur for a user-defined duration using the thermostat’s touchscreen interface. The local override will impact the effective runtime setpoints AnalogValue 30, HeatingSp and

AnalogValue 31, CoolingSp.

NOTES:

1. If an Occupancy sensor is configured, the Present_Value of the BinaryInput is evaluated after SchedMode’s Priority_Array arbitration, so the effective runtime operating mode MultistateValue 26, RM OP MODE, will ultimately indicate Comfort if the BinaryInput is active; otherwise, the Present_Value of SchedMode will take effect.

2. The RDY2000BN does not support BACnet schedule features such as exception schedules. Tridium Niagara users must set those unsupported parameters to Skip

Write before importing the schedule objects from the unit for editing. After editing, the parameters can be downloaded to the RDY2000BN. If Skip Write is not marked for those unsupported parameters, an error message displays that the writing failed.

22

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Application 14900 Point Database

Application 14900 Point Database

Table 3: Point Database.

Object Type 1 Object

Instance

(Point

Number)

Object Name

(Descriptor)

Factory

Default

(SI Units) 2

Eng Units

(SI Units)

State Text

Device

AnalogInput

4194303 RDY

0 UI1.NTC10K

4194303

0.0 DegF/DegC

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

BinaryInput

BinaryInput

BinaryInput

BinaryInput

BinaryOutput 3

BinaryOutput 3

BinaryOutput 3

BinaryOutput 3

BinaryOutput 3

BinaryOutput 3

BinaryOutput 3

1

2

3

4

5

6

7

UI1.10V

UI2.NTC10K

UI2.10V

UI3.NTC10K

UI3.10V

UI4.NTC10K

UI4.10V

OnbrdTmp

OnbrdRH

DI1

DI2

DI3

DI4

O/B

FanCmd

Y1

Y2

W1

W2

AuxOutput1

4

5

6

1

2

3

3

0

1

2

8

9

0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0

0

0

0

0

0

0

0

0

0

0.0

0.0

0

Enumerations/Notes

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

%RH

DI1 inactive/DI1 active

DI2 Inactive/DI2 active

DI3 Inactive/DI3 active

DI4 Inactive/DI4 active

RelayOff/Relay On

For troubleshooting purposes only.

For troubleshooting purposes only.

For troubleshooting purposes only.

RelayOff/Relay On

RelayOff/Relay On

RelayOff/Relay On

RelayOff/Relay On

RelayOff/Relay On

RelayOff/Relay On OUT1

For troubleshooting purposes only.

For troubleshooting purposes only.

For troubleshooting purposes only.

For troubleshooting purposes only.

For troubleshooting purposes only.

Siemens Industry, Inc. Application Note, App 14900

23

140-1231

2017-01-17

Application 14900 Point Database

Object Type 1

BinaryOutput 3

BinaryOutput 3

AnalogValue

Object

Instance

(Point

Number)

7

8

0

Object Name

(Descriptor)

AuxOutput2

AuxOutput3

HmdySp

AnalogValue 1 DeHmdySp

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

2 CO2Setpoint

10

11

12

13

7

8

9

14

15

3

4

5

6

ChgOvrDB

TmpOffset

ChgOvrDly

MinOnTimeHt

MinOffTimeHt

MinOffTimeCl

MinOnTimeCl

OccMinRun

StgDlyHt

StgDlyCl

HeatStg

AuxHeatStg

HrsOvrRide

16

17

18

19

20

21

22

23

UvLampSrvc

HmdfrSrvc

FilterSrvc

BackLight

TmpIn1Low

TmpIn1High

TmpIn2Low

TmpIn2High

5.0

5.0

3.0

30.0

5.0

5.0

2.0

0.0

2.0

5.0

0.0

10.0

3.0

DegF/DegC

DegF/DegC

Minutes

Minutes

Minutes

Minutes

Minutes

Minutes

Minutes

Minutes

Hours

0.0

0.0

0.0

15.0

0.0

120.0

0.0

120.0

Days

Days

Days

Seconds

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

Factory

Default

(SI Units) 2

Eng Units

(SI Units)

0

0

25.0 %RH

State Text

RelayOff/Relay On

RelayOff/Relay On

50.0 %RH

1000.0 Ppm

Enumerations/Notes

OUT2

OUT3

If AuxOut1-3 = 1, this is a runtime humidity setpoint.

If AuxOut1-3 = 2, this is a runtime dehumidification setpoint.

If AuxOut1-3 = 4 and Input1-

4 = 7, this is a runtime CO2 setpoint.

Present, but no impact on the control sequence.

24

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

Object Type 1

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

Object

Instance

(Point

Number)

24

25

26

Object Name

(Descriptor)

TmpIn3Low

TmpIn3High

TmpIn4Low

27

28

29

30

TmpIn4High

InstallPW

ExpertPW

HeatingSp

31 CoolingSp

40

41

42

36

37

38

39

43

44

32

33

34

35

ComfortClgSP

ComfortHtgSP

EconClgSP

EconHtgSP

CoolStg

PreOcpyPrg

MS/TP MAC

ProtClgSP

ProtHtgSP

UnitNumber

HEAT LIMIT

COOL LIMIT

APPLICATION

AnalogValue

AnalogValue

AnalogValue

AnalogValue

45 IndoorTmpRmt

46 CO2

47 SupplyTmp

48 ReturnTmp

Application 14900 Point Database

Enumerations/Notes Factory

Default

(SI Units) 2

Eng Units

(SI Units)

0.0

120.0

0.0

120.0

0000.0

9999.0

70.0

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

75.0 DegF/DegC

75.0

70.0

82.0

62.0

DegF/DegC

DegF/DegC

DegF/DegC

DegF/DegC

2

0.0

255

104.0

40.0

0.0

95.0

Hours

DegF/DegC

DegF/DegC

DegF/DegC

50.0

14900.0

DegF/DegC

State Text

0.0

0.0

0.0

0.0

DegF/DegC

Ppm

DegF/DegC

DegF/DegC

Effective runtime heating setpoint.

Effective runtime cooling setpoint.

Conventional = 14900

(Read Only, write to

SystemType).

If Input1-4 = 1, this is an intermediate value.

If Input1-4 = 7, this is a runtime value.

If Input1-4 = 3, this is a runtime value.

If Input1-4 = 4, this is a runtime value

Siemens Industry, Inc. Application Note, App 14900

25

140-1231

2017-01-17

AnalogValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

AnalogValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

Application 14900 Point Database

Object Type 1

AnalogValue

Object

Instance

(Point

Number)

49

Object Name

(Descriptor)

OutDoorTmp

AnalogValue

AnalogValue

50 IndoorTmpAvg

51 Humidity

52 IndoorTmpEff

DST

SpDispMode

OcupyInput

HmdyOn

DeHmdyOn

OcupyStatus

DCV

ExtFault

EcomzrOn

SrvcUvLamp

SrvcHmdy

FanRunTime

FanMode

RevValveMode

SemiContFan

FanOpr

Eco_MstEn

Eco_MstCtrl

HumidityIndp

Changeover

ClockFormat

AckService

Units

17

18

19

20

21

14

15

16

11

12

13

8

9

10

5

6

7

3

4

1

2

53

0

0.0

1

0

0

0

0

14

0

1

0

0

0

0

0

0

0

0

1

0.0

0

1

0

0

0

Factory

Default

(SI Units) 2

Eng Units

(SI Units)

0.0

0.0

0.0

DegF/DegC

DegF/DegC

%RH

State Text

DegF / DegC

Minutes

Auto/Manual

Cooling/Heating

No/Yes

Gas/Electric

Disabled/Enable

Disabled/Enabled

No/Yes

Manual/Automatic

12-hour/24-hour

NoAction/Clear

DegF/DegC

Disabled/Enabled

Absolute/Relative

Unocc/Occ

Off/On

Off/On

No/Yes

Off/On

Normal/Fault

Off/On

No Serv/Service

No Serv/Service

Enumerations/Notes

If Input1-4 = 5, this is runtime value.

If Input1-4 = 2, this is an intermediate value.

If Input1-4 = 6, this is a runtime value.

If Input1-4 = 1 or 2, this is a runtime value.

26

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Application 14900 Point Database

Object Type 1

BinaryValue

BinaryValue

Object

Instance

(Point

Number)

22

23

Object Name

(Descriptor)

SrvcFilter

HpCompLockOn

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

Siemens Industry, Inc.

24

28

29

0

25

26

27

1

2

3

4

5

6

7

8

9

HpAuxLockOn

OverCurrent

SchOcupy

HmiOcupy

VntlationEff

PrePurgeEn

Periods

TmpOvrRide

KeyLock

SystemType

AuxOut1

AuxOut2

AuxOut3

Input1

Input2

Input3

Factory

Default

(SI Units) 2

Eng Units

(SI Units)

State Text Enumerations/Notes

0

0

1

0

1

0

11

0

0

0

1

1

6

6

6

10

10

10

Application Note, App 14900

No Serv/Service

No Lock/Lock

No Lock/Locke

Off/On

No/Yes

No/Yes

Off/On

Off/On

6 Prds

1F/0.5C, 2F/1C,

3F/1.5C, 4F/2C,

5F/2.5C, 6F/3C,

7F/3.5C, 8F/4C,

9F/4.5C, 10F/5C,

No Limit

NONE, PARTIAL, FULL

CONVEN,HEAT P

Humid, Dehumid,

Occupied, AirQual,

EconEn, Not Used

Humid, Dehumid,

Occupied, AirQual,

EconEn, Not Used

Humid, Dehumid,

Occupied, AirQual,

EconEn, Not Used

InTemRem, InTemAvg,

Sup Temp, Ret Temp,

Out Temp, Hum 0-10,

CO2 0-10, Occ DI, Fault,

Not Used

InTemRem, InTemAvg,

Sup Temp, Ret Temp,

Out Temp, Hum 0-10,

CO2 0-10, Occ DI, Fault,

Not Used

InTemRem, InTemAvg,

Sup Temp, Ret Temp,

Out Temp, Hum 0-10,

CO2 0-10, Occ DI, Fault,

Not Used

Present, but no impact on the control sequence.

Present, but no impact on the control sequence.

27

140-1231

2017-01-17

Application 14900 Point Database

Object Type 1

MultistateValue

Object

Instance

(Point

Number)

10

Object Name

(Descriptor)

Input4

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

11

12

13

14

15

TmpIn1Type

TmpIn2Type

TmpIn3Type

TmpIn4Type

StgDifCl

16 CoolingDB

17 StgDifHt

18 HeatingDB

19 BaudRate

20 SchEditMode

21 HpCompLock

22 HpAuxLock

23 HeatCoolMode

24 SchedMode

25 ModeEff

Factory

Default

(SI Units) 2

Eng Units

(SI Units)

10

1

1

1

1

1

1

1

1

7

2

1

1

4

1

1

State Text Enumerations/Notes

InTemRem, InTemAvg,

Sup Temp, Ret Temp,

Out Temp, Hum 0-10,

CO2 0-10, Occ DI, Fault,

Not Used

Type2Th, 0-10V

Type2Th, 0-10V

Type2Th, 0-10V

Type2Th, 0-10V

1F/0.5C, 2F/1C,

3F/1.5C, 4F/2C,

5F/2.5C, 6F/3C,

7F/3.5C, 8F/4C,

9F/4.5C, 10F/5C

1F/0.5C, 2F/1C,

3F/1.5C, 4F/2C,

5F/2.5C

1F/0.5C, 2F/1C,

3F/1.5C, 4F/2C,

5F/2.5C

1F/0.5C, 2F/1C,

3F/1.5C, 4F/2C,

5F/2.5C

9600, 19200, 38400,

57600, 76800, 115200,

Auto

7 days, 5+2, 5+1+1,

Individ, disable

Off, 15F/9C,

20F/7C, 25F/4C,

30F/1C, 35F/2C,

40F/4C, 45F/7C

Off, 40F/4C,

45F/7C, 50F/10C,

55F/13C, 60F/16C

COOLING, HEATING,

AUTO, Off

Present, but no impact on the control sequence.

Present, but no impact on the control sequence.

Comfort, Economy,

Protect

The factory

Relinquish_Default value is

OFF. If AUTO or another default value is preferred, set it appropriately.

COOLING, HEATING,

Off

28

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Application 14900 Point Database

Object Type 1

MultistateValue

Schedule

Object

Instance

(Point

Number)

26

Object Name

(Descriptor)

RM OP MODE

0

Factory

Default

(SI Units) 2

Eng Units

(SI Units)

State Text Enumerations/Notes

1 Comfort, Economy,

Protect

Effective runtime room operating mode

WeeklySchedule_1

1) Object Types are: Analog Input (AI), Analog Value (AV), Binary Input (BI), Binary

Value (BV), Multistate Value (MV), and Binary Output (BO).

2) A single value in a column means that the value is the same in English units and in

SI units.

3) This object has an internal algorithm commanding at Priority 16. To issue a command to the object, use a higher priority.

NOTES:

1. The RDY2000BN commands its points at Priority 16.

2. To change between Heat Pump and Conventional Applications, write to the Point

System Type rather than the Application Point.

Table 4: Points that Can be Read and Written.

Object Type Object

Instance

(Point

Number)

Object Name

(Descriptor)

AnalogInput 1

AnalogInput 1

0

1

UI1.NTC10K

UI1.10V

AnalogInput 1

AnalogInput 1

AnalogInput 1

AnalogInput 1

AnalogInput 1

AnalogInput 1

AnalogInput 1

AnalogInput 1

BinaryInput 2

BinaryInput 2

BinaryInput 2

BinaryInput 2

BinaryOutput 2 , 3

2

3

0

0

1

8

9

5

6

7

2

3

4

UI2.NTC10K

UI2.10V

UI3.NTC10K

UI3.10V

UI4.NTC10K

UI4.10V

OnbrdTmp

OnbrdRH

DI1

DI2

DI3

DI4

O/B

R

R

R

R

R

R

R

Read (R)/

Write (W)

Present

Value

R

R

R

R

R

R

R

W

Write Values

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

(0) RelayOff; (1) Relay On

Read (R)/

Write (W)

Out of Service

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

Siemens Industry, Inc. Application Note, App 14900

29

140-1231

2017-01-17

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

BinaryOutput 2 , 3

BinaryOutput 2 , 3

BinaryOutput 2 , 3

BinaryOutput 2 , 3

BinaryOutput 2 , 3

BinaryOutput 2 , 3

BinaryOutput 2 , 3

BinaryOutput 2 , 3

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

Application 14900 Point Database

Object Type Object Name

(Descriptor)

15

16

17

11

12

13

14

18

19

20

8

9

10

5

6

7

3

4

1

2

7

8

0

Object

Instance

(Point

Number)

1

2

3

4

5

6

ChgOvrDly

MinOnTimeHt

MinOffTimeHt

MinOffTimeCl

MinOnTimeCl

OccMinRun

StgDlyHt

StgDlyCl

HeatStg

AuxHeatStg

HrsOvrRide

UvLampSrvc

HmdfrSrvc

FilterSrvc

BackLight

TmpIn1Low

FanCmd

Y1

Y2

W1

W2

AuxOutput1

AuxOutput2

AuxOutput3

HmdySp

DeHmdySp

CO2Setpoint

ChgOvrDB

TmpOffset

30

Siemens Industry, Inc. Application Note, App 14900

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

Read (R)/

Write (W)

Present

Value

W

W

W

W

W

W

Write Values

(0) RelayOff; (1) Relay On

(0) RelayOff; (1) Relay On

(0) RelayOff; (1) Relay On

(0) RelayOff; (1) Relay On

(0) RelayOff; (1) Relay On

(0) RelayOff; (1) Relay On

(0) RelayOff; (1) Relay On

(0) RelayOff; (1) Relay On

10 – 90%

10 – 90%

500 – 2000 ppm

3 – 9℉; 2 – 5℃

-5 – 5℉; -3 – 3℃

1 – 60 min

1 – 10 minutes

1 – 10 minutes

1 – 10 minutes

1 – 10 minutes

3 – 60 minutes

1 – 10 minutes

1 – 10 minutes

0 – 3 stages

0 – 2 stages

0 – 96 hours

0 – 365 days

0 – 365 days

0 – 365 days

0 – 99 seconds

-58 – 250℉; -50 – 120℃

Read (R)/

Write (W)

Out of Service

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

W

W

R

W

W

W

W

W

W

140-1231

2017-01-17

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

Object Type

Siemens Industry, Inc.

44

45

46

40

41

42

43

47

48

49

37

38

39

34

35

36

30

31

32

33

27

28

29

Object

Instance

(Point

Number)

21

22

23

24

25

26

Object Name

(Descriptor)

EconClgSP

EconHtgSP

CoolStg

PreOcpyPrg

MS/TP MAC

ProtClgSP

ProtHtgSP

UnitNumber

HEAT LIMIT

COOL LIMIT

APPLICATION

IndoorTmpRmt

CO2

SupplyTmp

ReturnTmp

OutDoorTmp

TmpIn1High

TmpIn2Low

TmpIn2High

TmpIn3Low

TmpIn3High

TmpIn4Low

TmpIn4High

InstallPW

ExpertPW

HeatingSp

CoolingSp

ComfortClgSP

ComfortHtgSP

Application 14900 Point Database

R

R

R

W

W

W

W

R

R

R

W

W

W

W

W

W

R

R

W

W

W

W

W

Read (R)/

Write (W)

Present

Value

W

W

W

W

W

W

Write Values

45 - 104℉; 8 – 40℃

40 – 104℉; 5 – 40℃

0 – 3 stages

0 – 3 hours

0 – 255

45 - 104℉; 8 – 40℃

40 – 104℉; 5 – 40℃

0 – 999

45 – 95℉; 7 – 35℃

50 – 95℉; 10 – 35℃

N/A

N/A

N/A

N/A

N/A

N/A

-58 – 250℉; -50 – 120℃

-58 – 250℉; -50 – 120℃

-58 – 250℉; -50 – 120℃

-58 – 25℉; -50 – 120℃

-58 – 25 ℉; -50 – 120℃

-58 – 250℉ ;-50 – 120℃

-58 – 250℉; -50 – 120℃

0000 – 4999

5000 – 9999

N/A

N/A

50 – 95℉; 5 – 3 ℃

45 – 95℉; 7 - 40℃

Read (R)/

Write (W)

Out of Service

R

W

W

R

R

R

R

W

W

W

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

Application Note, App 14900

31

140-1231

2017-01-17

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

BinaryValue 3

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

Application 14900 Point Database

Object Type Object Name

(Descriptor)

19

20

21

15

16

17

18

22

23

24

12

13

14

9

10

11

7

8

5

6

2

3

4

Object

Instance

(Point

Number)

50

51

52

53

0

1

AckService

Units

DST

SpDispMode

OcupyInput

HmdyOn

DeHmdyOn

OcupyStatus

DCV

ExtFault

EcomzrOn

SrvcUvLamp

SrvcHmdy

SrvcFilter

HpCompLockOn

HpAuxLockOn

IndoorTmpAvg

Humidity

IndoorTmpEff

FanRunTime

FanMode

RevValveMode

SemiContFan

FanOpr

Eco_MstEn

Eco_MstCtrl

HumidityIndp

Changeover

ClockFormat

32

Siemens Industry, Inc. Application Note, App 14900

R

R

R

R

R

R

R

R

R

R

W

R

R

W

W

W

W

W

W

W

W

W

W

Read (R)/

Write (W)

Present

Value

R

R

R

R

W

W

Write Values

N/A

N/A

N/A

N/A

(0) Auto; (1) Manual

(0) Cooling; (1) Heating

(0) No; (1) Yes

(0) Gas; (1) Electric

(0) Disabled; (1) Enabled

(0) Disabled; (1) Enabled

(0) No; (1) Yes

(0) Manual; (1) Auto

(0) 12-hour; (1) 24-hour

N/A

N/A

N/A

N/A

N/A

N/A

N/A

(0) NoAction; (1) Clear

(0) Deg F; (1) Deg C

(0) Disabled; (1) Enabled

(0) Absolute; (1) Relative

N/A

N/A

N/A

N/A

N/A

Read (R)/

Write (W)

Out of Service

W

W

W

W

W

W

W

W

W

W

R

W

W

R

R

R

R

R

R

R

R

R

R

W

W

R

W

W

W

140-1231

2017-01-17

Object Type

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

Siemens Industry, Inc.

Object

Instance

(Point

Number)

25

26

27

28

29

0

1

Object Name

(Descriptor)

OverCurrent

SchOcupy

HmiOcupy

VntlationEff

PrePurgeEn

Periods

TmpOvrRide

2

3

4

5

6

7

8

9

10

KeyLock

SystemType

AuxOut1

AuxOut2

AuxOut3

Input1

Input2

Input3

Input4

Application 14900 Point Database

Read (R)/

Write (W)

Present

Value

R

R

R

R

R

R

W

Write Values

W

W

W

W

W

W

W

W

W

N/A

N/A

N/A

N/A

N/A

N/A

(1) 1F/0.5C; (2) 2F/1C;

(3) 3F/1.5C; (4) 4F/2C;

(5) 5F/2.5C; (6) 6F/3C;

(7) 7F/3.5C; (8) 8F/4C;

(9) 9F/4.5C; (10) 10F/5C;

(11) No Limit

(1) NONE; (2) PARTIAL; (3) FULL

(1) CONVEN; (2) HEAT P

(1) Humid; (2) Dehumid;

(3) Occupied; (4) AirQual;

(5) EconEn; (6) Not Used

(1) Humid; (2) Dehumid;

(3) Occupied; (4) AirQual;

(5) EconEn; (6) Not Used

(1) Humid; (2) Dehumid;

(3) Occupied; (4) AirQual;

(5) EconEn; (6) Not Used

(1) InTemRem; (2) InTemAvg;

(3) Sup Temp; (4) Ret Temp;

(5) Out Temp; (6) Hum 0-10;

(7) CO2 0-10; (8) Occ DI;

(9) Fault; (10) Not Used

(1) InTemRem; (2) InTemAvg;

(3) Sup Temp; (4) Ret Temp;

(5) Out Temp; (6) Hum 0-10;

(7) CO2 0-10; (8) Occ DI;

(9) Fault; (10) Not Used

(1) InTemRem; (2) InTemAvg;

(3) Sup Temp; (4) Ret Temp;

(5) Out Temp; (6) Hum 0-10;

(7) CO2 0-10; (8) Occ DI;

(9) Fault; (10) Not Used

(1) InTemRem; (2) InTemAvg;

(3) Sup Temp; (4) Ret Temp;

(5) Out Temp; (6) Hum 0-10;

(7) CO2 0-10; (8) Occ DI;

(9) Fault; (10) Not Used

Read (R)/

Write (W)

Out of Service

W

W

R

W

W

W

R

R

R

R

R

R

R

R

R

R

Application Note, App 14900

33

140-1231

2017-01-17

Application 14900 Point Database

Object Type

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue 3

MultistateValue 3

MultistateValue

MultistateValue

Schedule 4

Object

Instance

(Point

Number)

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

Object Name

(Descriptor)

TmpIn1Type

TmpIn2Type

TmpIn3Type

TmpIn4Type

StgDifCl

CoolingDB

StgDifHt

HeatingDB

BaudRate

SchEditMode

HpCompLock

HpAuxLock

HeatCoolMode

SchedMode

ModeEff

RM OP MODE

Read (R)/

Write (W)

Present

Value

W

W

W

W

W

W

W

W

W

R

W

W

W

W

R

R

Write Values

(1) Type2Th; (2) 0-10V

(1) Type2Th; (2) 0-10V

(1) Type2Th; (2) 0-10V

(1) Type2Th; (2) 0-10V

(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;

(4) 4F/2C; (5) 5F/2.5C; (6) 6F/3C;

(7) 7F/3.5C; (8) 8F/4C; (9) 9F/4.5C;

(10) 10F/5C

(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;

(4) 4F/2C; (5) 5F/2.5C

(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;

(4) 4F/2C; (5) 5F/2.5C

(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;

(4) 4F/2C; (5) 5F/2.5C

(1) 9600; (2) 19200; (3) 38400;

(4) 57600; (5) 76800; (6) 115200;

(7) Auto

N/A

(1) Off; (2) 15F/-9C; (3) 20F/-7C;

(4) 25F/-4C; (5) 30F/1C;

(6) 35F/2C; (7) 40F/4C; (8) 45F/7C

(1) Off; (2) 40F/4C; (3) 45F/7C;

(4) 50F/10C; (5) 55F/13C; (6) 60F/16C

(1) COOLING; (2) HEATING;

(3) AUTO; (4) Off

(1) Comfort; (2) Economy; (3) Protect

N/A

N/A

Read (R)/

Write (W)

Out of Service

R

R

R

R

R

R

R

W

0 WeeklySchedule_1 R N/A

1) This point has a resolution of 0.10.

2) This point has a writable polarity property.

3) This point has a relinquish default that can be written.

4) See the

Scheduling

section for more information on configuring a schedule.

W

W

W

W

R

R

R

R

R

34

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Application 14900 Point Database

Table 5: Object Parameter Mapping.

Object Type Object Instance

(Point Number)

BinaryInput

BinaryOutput

BinaryOutput

BinaryOutput

BinaryOutput

BinaryOutput

BinaryOutput

BinaryOutput

BinaryOutput

BinaryOutput

AnalogValue

AnalogValue

AnalogValue

AnalogValue

Device

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

AnalogInput

BinaryInput

BinaryInput

BinaryInput

8

0

1

2

3

5

6

7

2

3

4

3

0

1

0

1

2

8

9

6

7

4194303

0

1

2

3

4

5

Object Name (Descriptor)

Y1

Y2

W1

DI4

O/B

FanCmd

W2

AuxOutput1

AuxOutput2

AuxOutput3

HmdySp

DeHmdySp

CO2Setpoint

ChgOvrDB

RDY

UI1.NTC10K

UI1.10V

UI2.NTC10K

UI2.10V

UI3.NTC10K

UI3.10V

DI1

DI2

DI3

UI4.NTC10K

UI4.10V

OnbrdTmp

OnbrdRH

Installer Menu

Parameter Name

CO2 SET PT

DEADBAND

Installer Menu

Parameter Number

P402

P111

Siemens Industry, Inc. Application Note, App 14900

35

140-1231

2017-01-17

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

Application 14900 Point Database

Object Type Object Name (Descriptor)

HmdfrSrvc

FilterSrvc

BackLight

TmpIn1Low

TmpIn1High

TmpIn2Low

TmpIn2High

TmpIn3Low

TmpIn3High

TmpIn4Low

TmpIn4High

InstallPW

ExpertPW

TmpOffset

ChgOvrDly

MinOnTimeHt

MinOffTimeHt

MinOffTimeCl

MinOnTimeCl

OccMinRun

StgDlyHt

StgDlyCl

HeatStg

AuxHeatStg

HrsOvrRide

UvLampSrvc

HeatingSp

CoolingSp

ComfortClgSP

ComfortHtgSP

26

27

28

29

23

24

25

20

21

22

17

18

19

14

15

16

10

11

12

13

Object Instance

(Point Number)

4

5

6

7

8

9

30

31

32

33

HMDFR SRVC

FLTR SRVC

LIGHT

TMP 1 LO

TMP 1 HI

TMP 2 LO

TMP 2 HI

TMP 3 LO

TMP 3 HI

TMP 4 LO

TMP 4 HI

INSTALL PW

XPRT PW

Installer Menu

Parameter Name

TMP OFFSET

C-O DLY

M R T HT

M O T HT

M O T CL

M R T CL

OCC MRT

STG DLY HT

STG DLY CL

HEAT STGS

AUX HTG STG

HRS OVR RD

UV LAMP

COMF CL SP

COMF HT SP

P308

P311

P312

P315

P316

P407

P911

P209

P210

P213

P303

P304

P307

P221

P220

P404

P507

P501

P103

P104

P204

P208

Installer Menu

Parameter Number

P203

P505

P510

P509

P503

P504

36

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Object Type

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

AnalogValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

Siemens Industry, Inc.

Application 14900 Point Database

Object Name (Descriptor)

SupplyTmp

ReturnTmp

OutDoorTmp

IndoorTmpAvg

Humidity

IndoorTmpEff

FanRunTime

FanMode

RevValveMode

SemiContFan

FanOpr

Eco_MstEn

Eco_MstCtrl

EconClgSP

EconHtgSP

CoolStg

PreOcpyPrg

MS/TP MAC

ProtClgSP

ProtHtgSP

UnitNumber

HEAT LIMIT

COOL LIMIT

APPLICATION

IndoorTmpRmt

CO2

HumidityIndp

Changeover

ClockFormat

AckService

4

5

2

3

53

0

1

50

51

52

47

48

49

44

45

46

40

41

42

43

Object Instance

(Point Number)

34

35

36

37

38

39

6

7

8

9

REV VALVE

CONT FAN

HTG FAN

Installer Menu

Parameter Name

ECO CL SP

ECO HT SP

COOL STGS

PRE OC PRG

MS/TP MAC

PROT HT SP

PROT CL SP

UNIT NMBR

HEAT LIMIT

COOL LIMIT

IND HMDTY

AUTO CHNGE

CLOCK

P106

P405

P105

P320

P110

P212

P224

P401

P201

P202

Installer Menu

Parameter Number

P223

P222

P102

P403

P601

P225

Application Note, App 14900

37

140-1231

2017-01-17

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

BinaryValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

Application 14900 Point Database

Object Type Object Name (Descriptor)

HpCompLockOn

HpAuxLockOn

OverCurrent

SchOcupy

HmiOcupy

VntlationEff

PrePurgeEn

Periods

TmpOvrRide

KeyLock

SystemType

AuxOut1

AuxOut2

Units

DST

SpDispMode

OcupyInput

HmdyOn

DeHmdyOn

OcupyStatus

DCV

ExtFault

EcomzrOn

SrvcUvLamp

SrvcHmdy

SrvcFilter

AuxOut3

Input1

Input2

Input3

4

5

2

3

29

0

1

26

27

28

23

24

25

20

21

22

16

17

18

19

Object Instance

(Point Number)

10

11

12

13

14

15

6

7

8

9

TMP OVR RD

KEY LOCK

SYS TYPE

AUX OUT 1

AUX OUT 2

Installer Menu

Parameter Name

UNITS

DAYLT SAVE

TMP SP DIS

AUX OUT 3

INPUT 1

INPUT 2

INPUT 3

P205

P211

P101

P317

P318

P319

P301

P305

P309

Installer Menu

Parameter Number

P109

P112

P113

38

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Object Type

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

MultistateValue

Schedule

Application 14900 Point Database

20

21

22

16

17

18

19

Object Instance

(Point Number)

10

11

12

13

14

15

23

24

25

26

0

Object Name (Descriptor)

Input4

TmpIn1Type

TmpIn2Type

TmpIn3Type

TmpIn4Type

StgDifCl

CoolingDB

StgDifHt

HeatingDB

BaudRate

SchEditMode

HpCompLock

HpAuxLock

HeatCoolMode

SchedMode

ModeEff

RM OP MODE

WeeklySchedule_1

P506

P508

P511

P602

P107

P206

P207

Installer Menu

Parameter Number

P313

P302

P306

P310

P314

P502

Installer Menu

Parameter Name

INPUT 4

TMP IN 1

TMP IN 2

TMP IN 3

TMP IN 4

STG DIF CL

CL DEADBND

STG DIF HT

HT DEADBND

BAUD RATE

SCHEDULER

HP COMP LO

HP AUX LO

Certain parameters may not appear in the Installer Menu depending upon how other parameters are configured.

Siemens Industry, Inc. Application Note, App 14900

39

140-1231

2017-01-17

Scheduling Examples

Scheduling Examples

Table 6: Daily Schedule Example

6 Periods per Day, Parameter 107 = 1.

Day Monday – Sunday (Each day is the same)

Event

Mode

1

COM

2

ECO

3

COM

4

ECO

5

COM

6

ECO

Time 6:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

Table 7: Work Week Schedule with Weekend Example

6 Periods per Day, Parameter 107 = 2.

Day Work Week (Monday-Friday)

Event 1 2 3 4 5 6

Mode

Time

COM ECO COM ECO COM ECO

6:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

Day

Event 1 2

Weekend (Saturday-Sunday)

3 4 5 6

Time

Day

Event

Mode

Time

Day

Event

Mode

Time

Mode COM ECO COM ECO COM ECO

Time 8:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

Table 8: Work Week Schedule with Separate Weekend Days Example

6 Periods per Day, Parameter 107 = 3.

Day Work Week (Monday-Friday)

Event

Mode

1

COM

2

ECO

3

COM

4

ECO

5

COM

6

ECO

6:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

1

COM

2

ECO

3

Saturday

COM

4

ECO

5

COM

6

ECO

8:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

Sunday

1

COM

2

ECO

3

COM

4

ECO

10:00 AM 12:00 PM 2:00 PM 3:00 PM

5

---

--:--

6

---

--:--

40

Siemens Industry, Inc. Application Note, App 14900 140-1231

2017-01-17

Scheduling Examples

Table 9: Individual Days (Monday – Sunday) Example

6 Periods per Day, Parameter 107 = 7.

Day Monday – Sunday (Each day can be unique)

Event

Mode

Time

1 2 3 4 5 6

Comfort Economy Comfort Economy Comfort Economy

6:00 AM 11:00 AM 1:00 PM 2:00 PM 3:00 PM 10:00 PM

NOTE:

The Scheduler default setting consists of two events:

Event 1 = ON (Comfort) at 7:00 AM,

Event 2 = ECO (Economy) at 7:00 PM.

Siemens Industry, Inc. Application Note, App 14900

41

140-1231

2017-01-17

Issued by

Siemens Industry, Inc.

Building Technologies Division

1000 Deerfield Pkwy

Buffalo Grove IL 60089

Tel. +1 847-215-1000

Document ID

Edition

140-1231

2017-01-17

© Siemens Industry, Inc., 2017

Technical specifications and availability subject to change without notice.

140-1231 (BA)

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement