FireNET® Series - ANALOG ADDRESSABLE
FireNET® Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL
STANDARD FEATURES
 UL 864 9th Edition Listed
 Seismic certified
 Analog design using Hochiki’s advanced DCP
protocol for fast and robust communication
 Up to 127 sensors & modules, plus 127 analog
sounder bases, for a total of 254 points possible per
loop
 Uses standard wire, no shielded or twisted pair
required on SLC loops
 Supports Class B (style 4) and Class A (style 6 or 7)
SLC loops
 4 on board Class B (style Y) NAC circuits rated at 2.5
Amps each
DESCRIPTION
The FireNET® 4127 control panel is an analog addressable fire alarm panel containing 2 or 4 SLC loops with
each loop supporting 127 devices of any combination
(sensors or modules), and 127 analog sounder bases,
for a possible total of 254 points. Communication between devices is transferred through standard cable
(shielded or twisted pair is not required). Each panel
includes a 5.25 amp power supply and has 4 on board
NAC circuits. An RS-485 bus provides communication
to the panel network, while the RS-232 interface allows
the convenience of programming via a PC.
 Programmable sensitivity levels per device &
automatic day/night sensitivity modes
The system will support a variety of Hochiki devices
such as photo, ion and heat sensors, which contain a
unique, patented sensor design incorporating automatic
drift compensation and day/night sensitivity mode. Additional devices include contact monitors, relay controllers, supervised auxiliary output and short circuit isolator modules. In addition, interfaces to conventional detection systems can be established by using a conventional zone-monitoring module.
 5 on board programmable Form C relays rated at
1 amp at 30VDC (Fire1, Fire2, trouble, supervisory,
aux.)
®
The Loop Explorer Windows Software interface provides the installer with fingertip access to installation
programming and diagnostic tools. An Auto-learn feature offers the convenience for quick start applications.
Add to this Hochiki's reputation for high quality and dedicated service, and you have an exceptional product
with performance and value.
Specifications subject to change without notice.
 Automatic daily calibration & drift compensation
routine
 Large 8-line x 40-character LCD (320 char.)
 2 loop (FN-2127 Series) or 4 loop (FN-4127 Series)
versions (800 addresses/sub-addr. max.)
 Dual RS-485 bus for panel network
 2 built-in RS-232 interfaces for programming via a
PC and serial printer interface
 500mA of auxiliary power available rated at 24 VDC
 Loop Explorer Windows® configuration utility
 500 network wide software zones
 Network capability of up to 64 panels
 RS485 slave bus for expansion - up to 32
FN-4127-IO boards or up to 15 FN-LCD-S serial
annunciators and up to 17 FN-4127-IO boards
 Auto-learn feature
 Fire Drill test function
 Walk test function
 Alarm verification feature
 FireNET® is UL listed for Central Station Service,
Remote Station Service and Proprietary Service
 Operates on 120VAC or 240VAC input voltage
PRODUCT LISTINGS
S6468
UL 864, Local Signaling Unit.
Types: Automatic, manual,
waterflow, sprinkler supervisory,
Remote Station and Central
Station Service (DACT)
Non-coded signaling.
NFPA 70, 72 &13 Compliant
California State
Fire Marshal
3033817
 Powerful & versatile Cause & Effect programming
(up to 500 maximum, network wide) including:
*Cause & Effect action
*Disable function configuration
*Test mode configuration
7165-0410:159
Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax: 714-522-2268
Technical Support: 800-845-6692 or technicalsupport@hochiki.com
Find latest revision at www.hochiki.com
F0068 02/2017
FireNET® Series - ANALOG ADDRESSABLE
FIRE ALARM CONTROL PANEL
SPECIFICATIONS
Primary AC
Output DC
Power Supply
Charger Current
Dimensions
Weight
Color
Material
Display
Network
Zones
SLC loops
Devices per loop
Addresses per panel
NAC Outputs
Relay Outputs
Voltage Outputs
Aux. Power
Aux. Inputs
PC Port / Printer
Operating Temp.
Relative Humidity
120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 50hz
24VDC @ 5.25 Amps (4 Amps available for system power)
5.25 Amps integrated
1.5 Amps max.
14.5" W x 24" H x 5" D
31 lbs. (without batteries)
Red (optional gray)
ABS/steel enclosure
8 line x 40 character LCD (320 characters total)
Dual RS485 ports (64 panels max.)
500 network wide software zones per system
2 or 4 (class A, "style 6 or 7" or class B, "style 4")
127 sensors & modules, plus 127 analog sounder bases, 254 total
(800 addresses+sub-addresses max. per panel)
(4) 2.5 Amps @ 24VDC (class B)
(5) Form C 1 Amp @ 30VDC
(3) 500mA @ 24VDC
500mA @ 24VDC
(8) digital pull downs
RS232
32°F (0°C) 120°F (49°C)
85% RH Non-Condensing
FIRENET® ORDERING MODELS
MODEL
DESCRIPTION
FN2127US0ERS120
2015 Ed. FireNET® FACP, 2 Loop, Red, 120V
FN4127US0ERS120
2015 Ed. FireNET® FACP, 4 Loop, Red, 120V
FN2127US1ERS120
2015 Ed. FireNET® FACP, 2 Loop, W/Network Card, Red, 120V
FN4127US1ERS120
2015 Ed. FireNET® FACP, 4 Loop, W/Network Card, Red, 120V
FN-2127US0ERS-220
2015 Ed. FireNET® FACP, 2 Loop, Red, 220V
FN-4127US0ERS-220
2015 Ed. FireNET® FACP, 4 Loop, Red, 220V
FN-2127US1ERS-220
2015 Ed. FireNET® FACP, 2 Loop, W/Network Card, Red, 220V
FN-4127US1ERS-220
2015 Ed. FireNET® FACP, 4 Loop, W/Network Card, Red, 220V
SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES
CONTROL PANEL EXPANDERS
FN-4127-SLC
FN-4127-NIC
FN-4127-IO 16
FN-DAC
FN-CTM
Dual SLC Loop Expansion Card
Network Interface Card
16 Channel Input/Output Board
Digital Alarm Communicator
City-Tie Module (Local Energy Type)
ANNUNCIATOR
FN-LCD-N
FN-LCD-S
Network LCD Annunciator
Serial LCD Annunciator
SLC LOOP DEVICES
ALG-V, ALK-V, ALN-V
AIE-EA
ATG-EA, ATJ-EA
ACA-V, ACC-V
NSA-4 & NSA-6
SCI-B4 & SCI-B6
ASB
ASBL
DH-98A, DH-98AR, DH-99A, DH-99AR
MS-RA, MS-RA/R, MS-KA/R
DCP-FRCME-M
DCP-FRCME-P
DCP-FRCME-4
DCP-FRCMA, DCP-FRCMA-I
DCP-DIMM
DCP-CZM
DCP-R2M
DCP-R2ML/H Series
DCP-SOM
DCP-SOM-A, DCP-SOM-AI
DCP-SOM-R
DCP-SCI
DCP-AMS Series
Analog Addressable Photoelectric Sensor
Analog Addressable Ionization Sensor
Analog Addressable Heat Sensor
Multi-criteria Sensor
Four Inch Sensor Base and Six Inch Sensor Base
Four Inch Short Circuit Isolator Analog Sensor Base & Six Inch Circuit Isolator Analog Sensor Base
Analog Sounder Base
Analog Low Frequency Sounder Base
Analog Addressable Duct Detector Unit (DH-98AR and DH-99AR have relays built-in)
Remote Test Station for DH-98AR & DH-99AR
Contact Monitoring Module (mini w/terminal blocks)
Contact Monitoring Module (mini w/pigtail leads)
Contact Monitoring Module (with faceplate/indicating LED)
Class A Contact Monitoring Module (FRCMA-I has built-in SCI)
Dual Input Monitor Module (with faceplate/indicating LED)
Conventional Zone Module
Dual Relay Module
Dual Relay Module (R2ML-I & R2MH-I has built-in SCI)
Supervised Output Module
Class A Supervised Output Module (SOM-AI has built-in SCI)
Supervised Output Module for Releasing Pre-action System
Short Circuit Isolator Module
Addressable Manual Pull Station
ACCESSORIES
TCH-B100
FN-ACC
FNP-ETR
Hand Held Programmer (portable device addresser)
Battery/Accessory Enclosure (houses up to 33AH size batteries)
Enclosure Trim Ring for panel flush mount
Hochiki America Corporation FireNET ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL
Specifications subject to change without notice.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising