PRODUCT DATA SHEET
1 to 6 Ton Vertical Wall Mount Air Conditioners
Models AVPA12-20-24-30-36-42-48-60-72 (Single Stage Compressor)
Models AVHA12-20-24-30-36-42-48-60 (Single Stage Compressor)
Models HVEA24-30-36-42-49-60 (Single Stage Compressor)
Models HVESA36-42-49-60 (2-Stage Compressor)
General Description
Used primarily to cool electronic and communication equipment shelters, Marvair®
ComPac® I and ComPac® II air conditioners are problem solvers for a wide range
of conditions and applications. Due to the high internal heat load, these shelters
require cooling even when outside temperatures drop below 60°F (15°C).
The ComPac I and ComPac II air conditioners have the necessary controls and
components for operation during these (less than 60°F [15°C]) temperatures. All
models use the non-ozone depleting R-410A refrigerant.
The primary difference between the ComPac I and the ComPac II units is that
the ComPac® II air conditioner has a factory installed economizer. When ambient
conditions are cool and dry, the economizer uses outside air to cool the shelter.
The economizer provides temperature control, energy cost savings, and increased
reliability by decreasing the operating hours of the compressor and the condenser
fan. To insure proper operation and optimum performance, all economizers are
non-removable, factory installed and tested. In addition, factory and field installed
accessories can be used to meet specific requirements.
➤ Standard Efficiency Models
AVPA: Marvair’s most popular model with an Energy Efficiency Ratio (EER) of 9.0
to 10.0. The ComPac AVPA is available in cooling capacities of 1, 1.5, 2, 2.5, 3, 3.5,
4, 5 and 6 tons (12,000 BTUH to 72,000 BTUH).
➤ High Efficiency Models
HVEA: Marvair’s most efficient wall mount air conditioners. Electronically commutated indoor fan motors combined with highly efficient scroll compressors result
in Energy Efficiency Ratios (EER’s) of up to 11.75.
AVHA: ComPac models with an EER of 10.0. The AVPA72 is also rated 10 EER.
➤ 2-Stage Compressor Models
HVESA: ComPac models 36-42-49-60 have a 2-stage compressor with first stage
cooling approximately 65% of the total cooling capacity. The 2-stage compressor
provides lower start-up amps which can be critical when operating with a
generator. The two stage compressor can also reduce energy costs and is able to
more precisely match the cooling capacity of the air conditioner with the heat
load in the shelter. Both ComPac I and ComPac II units are available with 2 stage
compressors.
1
AVPA36ACA-100C
Features and Benefits
Built-In Energy Savings
• Optional Factory Installed Economizer
• Three Model Lines to Meet Any Budget and
Efficiency Requirements
• Available EER of up to 11.75
• Available 2-Stage Compressor on HVESA Models
R-410A Refrigerant
• Efficient Heat Release
• Non-Ozone Depleting Refrigerant
• Synthetic Lubricant
• Reduced Compressor Wear
High Efficiency and Reliability
• High Efficiency Compressor and Lanced Coil Fins
• High/Low Pressure Switches with Lockout & Short
Cycle Protection
Ease of Installation and Service
• Side Access Panels for Power Connections
• Built-In Mounting Flanges and Iternal Disconnect
• Standard Access Valves and Filters, Status LEDs
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Safety Listed and Energy Certified
All ComPac air conditioners are built to UL standard 1995, 4th edition and CAN/CSA C22.2, No. 236-11. For energy
efficiency and performance, the units are tested and rated in accordance to the ANSI/ARI (Air-Conditioning and
Refrigeration Institute) Standard 390- 2003 (Single Package Vertical Units). All units meet or exceed the efficiency
requirements of ANSI/ASHRAE/IESNA 90.1.2010. The ComPac I and ComPac II air conditioners are commercial units and
are not intended for use in residential applications.
Standard Features
➤ Remote Alarm Capability
➤ Rugged Construction
➤ Designed for Operation in Low
Ambient Conditions
• Dry contacts can be used for
• Copper tube, aluminum fin
remote alarm or notification
evaporator & condenser coils.
• Low ambient control cycles
upon air conditioner lockout.
condenser fan to maintain proper
• Field or factory installed heaters
refrigerant pressures. Allows
➤ Ease of Service
on discharge side of evaporator
operation in mechanical cooling
coil (optional)
• Service access valves are
(compressor) of our standard
standard.
• Baked on neutral beige finish
air conditioners down to 20°F
over galvanneal steel for
• Standard 2” (50 mm) pleated
(-7°C). With the Extreme Duty
maximum cabinet life. (Other
filter
with
a
MERV
rating
of
8
option, the units will operate
finishes are available.)
changeable
from
outside.
down to 0°F (-18°C). Note: low
➤
Ease
of Installation
•
All
major
components
are
readily
temperature operation is affected
accessible.
•
Sloped
top with flashing
by ambient conditions, e.g. wind
eliminates
need of rainhood.
and humidity.
• Front Control Panel allows easy
access
and
complies
with
NEC
•
Built-in
mounting
flanges
• Three minute by-pass of the
clearance
codes
on
redundant
facilitate
installation
and
low pressure switch for start-up
side-by-side systems.
minimize chance of water leaks.
of compressor when outdoor
temperatures are below 55°F
• LEDs indicate operational status
• Supply and return openings
(13°C).
and fault conditions.
exactly match previous models.
• Factory built-in economizer.*
• Foil backed insulation on the
• Factory installed disconnect on
indoor air path.
all units.
➤ High Efficiency
• High efficiency compressor.
• A minimum position
• Single Point Power
potentiometer that can be
Entry complies with
• Lanced fins standard on all
adjusted to prevent the
latest edition of U.L.
evaporator and condenser coils.
economizer damper from closing
Standard 1995.
➤ Built-in Reliability
completely. This control ensures
• Side access panels
• High pressure switch and low
that whenever the evaporator
for easy access
pressure switch with lockout
fan is operating, fresh air is being
protects refrigerant circuit.
to electrical
introduced into the building.
connections.
• Adjustable .03 to ten minute
delay on make for short cycle
*ComPac® II air conditioner only
protection.
A Marvair® First – Factory Installed Economizer
Marvair’s ComPac® II air conditioner has been the industry standard since its introduction in 1986. Tens of thousands of
ComPac II air conditioners are in operation from the metropolitan areas of North America to the deserts of the Mid-East
to the Siberian tundra. Here’s how the economizer works:
On a signal from the wall mounted indoor thermostat that cooling is required, either mechanical cooling with the
compressor or free cooling with the economizer is provided. A factory installed enthalpy controller determines whether
the outside air is sufficiently cool and dry to be used for cooling. If suitable, the compressor is locked out and the
economizer damper opens to bring in outside air. Integral pressure relief allows the interior air to exit the shelter,
permitting outside air to enter the shelter. The temperature at which the economizer opens is adjustable from 63°F
(17°C) at 50% Relative Humidity to 73°F (23°C) at 50% Relative Humidity.
After the enthalpy control has activated and outside air is being brought into the building, the mixed air sensor measures
the temperature of the air entering the indoor blower and then modulates the economizer damper to mix the right
proportion of cool outside air with warm indoor air to maintain 50-63°F (10 - 17°C) air being delivered to the building.
This prevents shocking the electronic components with cold outside air. The compressor is not permitted to operate
when the economizer is functioning.
If the outside air becomes too hot or humid, the economizer damper closes completely, or to a field selectable minimum
open position, and mechanical cooling is activated.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.182
In all ComPac II air conditioners, the supply air flow in the economizer mode is the same or greater than the rated air
flow. (The rated air flow is the AHRI certified air flow when the unit is in mechanical cooling.) The “full flow” economizer
reduces electrical costs by maximizing the use of outside air for cooling.
100% Mechanical Cooling
100% Economizer Cooling
Savings with an Economizer
The following table shows the annual electrical cost of cooling a 10 ft. x 20 ft. x 9 ft. (3m x 6m x 2.7m) shelter in twelve
cities in the US. Costs are shown for an air conditioner without an economizer (ComPac I units), for an air conditioner
with an economizer (ComPac II units) and the savings. The savings do not include any demand charges. The savings are
based on the electrical usage of a five ton air conditioner and an electric rate of $.10 per kilowatt-hour, the approximate
average commercial rate in the US.
Atlanta, GA
Boston, MA
Chicago, IL
Dallas, TX
Denver, CO
Houston, TX
Annual Compressor & Condenser Motor Run Time without Economizer (Hrs.)
Hours of Operation
6,531
6,348
6,361
6,628
6,472
6,655
Annual Compressor & Condenser Motor Run Time with Economizer (Hrs.)
3,841
2,153
2,424
3,798
750
4,970
Run Time Savings with the Economimizer (Hrs.)
2,690
4,195
3,937
2,830
5,722
1,685
Annual Operating Cost 9.0 EER Unit without Economizer ($)
$4,100.00
$3,985.00
$4,792.00
$4,161.00
$3,657.00
$4,178.00
Annual Operating Cost 9.0 EER with Economizer
$2,685.00
$1,784.00
$2,315.00
$2,671.00
$940.00
$3,291.00
Annual Savings using 9.0 EER Unit with Economizer
$1,415.00
$2,201.00
$2,477.00
$1,490.00
$2,717.00
$887.00
Annual Costs Saving ($) of 9.0 EER unit with an Economizer (ComPac II)
Hours of Operation
Los Angeles, CA Miami, FL
Phoenix, AZ Pittsburgh, PA Seattle, WA St. Louis, MO
Annual Compressor & Condenser Motor Run Time without Economizer (Hrs.)
6,467
6,779
6,765
6,386
6,465
6,472
Annual Compressor & Condenser Motor Run Time with Economizer (Hrs.)
3,862
6,391
3,106
1,929
1,654
2,716
Run Time Savings with the Economimizer (Hrs.)
2,605
388
3,659
4,457
4,811
3,756
Annual Operating Cost 9.0 EER Unit without Economizer ($)
$4,060.00
$4,255.00
$4,247.00
$4,009.00
$3,653.00
$4,063.00
Annual Operating Cost 9.0 EER with Economizer
$2,686.00
$4,051.00
$2,315.00
$1,667.00
$1,368.00
$2,090.00
Annual Savings using 9.0 EER Unit with Economizer
$1,374.00
$204.00
$1,932.00
$2,342.00
$2,285.00
$1,973.00
Annual Costs Saving ($) of 9.0 EER unit with an Economizer (ComPac II)
Shelter Metrics:
•10’ x 20’ x 9’ building
•Internal heat gain (electronics load): 12,000 watts.
•Building surface area (excluding floor area): 740 ft²
•R-Value of walls and ceiling: R-12
•Internal shelter temperature (Thermostat set point): 75ºF
Air Conditioner Metrics:
•ComPac II Economizer setting: 57ºF (dry bulb or enthalpy sensor)
•A/C unit capacity: 60,000 BTUH (5 tons) with 1-stage compressor
•Nominal EER (unit efficiency): 9.0 (models AVPA)
•Cost of power: $.10 per KWH
3
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Operation of the 2-Stage Compressor Air Conditioners with a CommStat 4™ or CommStat 6 Lead/Lag Thermostat Controller
Marvair’s HVESA air conditioners have 2-stage compressors. These units can provide substantial energy savings and
better control of temperature and humidity by matching the cooling requirement with the performance of the air
conditioner. First stage is typically 65% of the total (2-stage) capacity of the air conditioner. When operated from power
supplied by a generator, starting the air conditioner in 1-stage means lower start-up amps.
• CommStat™ 4 Controller: When two, 2-stage air conditioners are controlled by a CommStat 4 lead/lag controller in a
redundant application, one of the air conditioners is the lead unit and the second is the lag unit. On a call for cooling,
the lead unit starts operation in the 1-stage (low capacity). If the temperature in the building continues to rise above
the set point temperature, the 1-stage (low capacity) of the lag unit will be initiated. When the temperature in the
building drops to the set point, the air conditioners will turn off. On a subsequent call for cooling the process will
repeat.
If the set point temperature is not reached with 1-stage capacity operation of both air conditioners, the lead air
conditioner will commence operation in 2-stage (full capacity). If the temperature in the building continues to
rise past the setpoint, the lag unit will switch to 2-stage cooling operation. At that time, both air conditioners are
operating in maximum capacity.
• CommStat™ 6 Controller: When two, 2-stage air conditioners are controlled by a CommStat 6 lead/lag controller
in a redundant application, one of the air conditioners is the lead unit and the second is the lag unit. On a call for
cooling, the lead unit starts operation in the 1st-stage (LOW capacity). If the temperature in the building continues
to rise above the set point temperature, the 2nd-stage (FULL capacity) of the LEAD unit will be initiated. When the
temperature in the building drops to the set point, the unit will turn off. On a subsequent call for cooling the process
will repeat.
If the set point temperature is not reached with 2nd-stage capacity operation of the LEAD air conditioner, the LAG
air conditioner will commence operation in 1st-stage (LOW capacity). If the temperature in the building continues
to rise past the setpoint, the lag unit will switch to 2-stage cooling operation. At that time, both air conditioners are
operating in maximum capacity
When the temperature in the building is satisfied with either controller, both units will turn off.
If the units have economizers (ComPac II air conditioners), the enthalpy sensor determines whether to use outside air or
use mechanical cooling. When the economizer is used, the compressors do not operate.
Marvair’s AVPA12 One Ton Air Conditioner
Ideal Replacement for Old Window Air Conditioners or New Construction
The electronic/communication shelter requires cooling virtually yearround because of the heat load generated by the internal electronic
equipment (i.e., switching and transmission gear). Residential
window room air conditioners are not designed to operate when
outside air temperatures are moderate to cold, i.e., below 65°F
(18°C). Typical problems are freezing of the coil, diminished capacity
and compressor damage which all contribute to high maintenance
and short operating life.
Combination Supply & Return Grille
Wall Sleeve Thru
Wall Opening
Built-In Sloped
Top Rain Hood
The Marvair® One Ton ComPac® I and ComPac® II air conditioners
are designed for the electronic/ communication shelter to provide
a commercial grade air conditioner for years of operation. The
Marvair One Ton is built to operate continuously and efficiently in
a variety of outside conditions. For existing shelters with window
air conditioners, upgrading to the commercial grade Marvair air
conditioners is made easy by the design of the One Ton ComPac
Built-In Mounting
II unit with the factory installed economizer. The back panel is
Flanges
designed for either a 19” x 19” (483 mm x 483 mm) or 28” x 19” (711
mm x 483 mm) opening, standard opening sizes for many window
units. The unit is shipped from the factory for mounting on a 19” x 19” (483 mm x 483 mm) opening, but can be easily
changed at site to fit in a 28” x 19” (711 mm x 483 mm) opening. With the built-in mounting flanges, the air conditioner
mounts quickly and simply to the exterior of the building. The single piece supply and return grille attaches easily to the
wall sleeve to complete the installation. The ComPac I (non-economizer) unit has separate supply and return grilles. (See
the Accessories section for the part numbers of the grilles and wall sleeves). Factory installed electric heat is available in
the Marvair One Ton Air Conditioner thus eliminating baseboard heat and a second power source.
C
PA
M
CO
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.184
II
Controllers and Thermostats
➤ Controllers
CommStat 6 2/4 Telecom HVAC Controller NEW!............................................................................................................................P/N 70705
CommStat 6 4/8 Telecom HVAC Controller NEW!................................................................................................................. P/N S/12087-04
CommStat 6 6/12 Telecom HVAC Controller NEW!.............................................................................................................. P/N S/12087-06
The CommStat 6 is an HVAC controller, is available in three configurations, and is designed
specifically for controlling up to six redundant air conditioners with two stage compressors
in a telecommunications shelter or enclosure. The CommStat 6 2/4 controls up to two
single or 2-stage air conditioners (4 Stages max.), the CommStat 6 4/8 controls up to four
single or 2-stage air conditioners (8 Stages max.) and the CommStat 6 6/12 controls up to
six single or 2-stage air conditioners (12 Stages max.)
In addition to the control of the air conditioners, the CommStat 6 has multiple configurable outputs for remote alarms
or notification. The CommStat 6 is factory programmed with standard industry set points, but can be configured on
site. Settings are retained indefinitely in the event of a power loss.
CommStat 4 Telecom HVAC Controller...............................................................................................................................................P/N S/7846
The CommStat 4 HVAC controller is designed specifically for controlling two redundant air
conditioners, heat pumps or air conditioners with 2-stage compressors. The CommStat 4 has seven
outputs for remote alarms or notification. Status LED’s indicate HEAT, COOL, POWER and the LEAD
unit. When a fault is detected, an alarm LED flashes and the LCD screen displays the fault.
The CommStat 4 uses RS-485 communications via a RJ11 jack. It can be daisy chained with a
second CommStat 4 controllers for controlling up to four air conditioners in one shelter. When two
CommStat 4 controllers are daisy chained together, one is the MASTER and the other controller
is the SLAVE. Any settings to the MASTER unit immediately take effect on the SLAVE unit. See the
CommStat 4 Product Data Sheet for complete details.
CommStat3™ Lead/Lag Microprocessor Controller.................................................................................................................. P/N S/04581
Solid state controller designed to operate a fully or partially redundant air conditioning system. Ensures
equal wear on both air conditioners while allowing the lag unit to assist upon demand. Lead/ lag
changeover is factory set at 7 days, but is field programmable in 1/2 day increments from 1/2 to 7 days.
The CommStat 3™ Controller has LED’s to indicate status & function, digital display of temperature, a
comfort override button for energy savings, five alarm relays, a built in temperature sensor and is fully
programmable. See CommStat 3™ Controller Product Data Sheet for details on operation & installation.
➤ Thermostats & Thermostat Guards
Note: All air conditioners with 2-stage compressors (models HVESA) require a 2-stage cooling thermostat.
Thermostat ....................................................................................................................................................................................................P/N 50123
Digital thermostat. 1-stage heat, 1-stage cooling. 7 day programmable. Fan switch: Auto & On. Auto-change over.
Keypad lockout. Non-volatile program memory.
Thermostat ....................................................................................................................................................................................................P/N 50107
Digital thermostat. 2-stage heat, 2-stage cooling. 7 day programmable. Fan switch: Auto & On. Auto-change over.
Status LED’s. Backlit display. Programmable fan. Non-volatile program memory.
Thermostat Guard..........................................................................................................................................................................................P/N 50092
Thermostat guard for use with the 50123 and 50107 thermostats.
Thermostat.......................................................................................................................................................................................................P/N 50218
Digital, non-programmable thermostat. 1-stage cooling and 1-stage heat. Auto-changeover.
Digital Humidistat.........................................................................................................................................................................................P/N 50254
To be used with units with hot gas or electric reheat. Programmable dehumidistat and ventilation controller.
Permanent memory retention of set points.Humidity sensor can be field calibrated. High & low dehumidification set
points. Outdoor temperature and humidity sensor included. °F or °C selectable.
Thermostat.......................................................................................................................................................................................................P/N 50252
Non-programmable digital thermostat with backlit display. 2 stage heat and 2-stage cooling. Auto changeover.
5
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Accessories
➤ Supply Grilles
For AVPA20/24...............................................................................................................................................................................................P/N 80674
20” x 8” (508 mm x 203 mm)
For AVPA/AVHA30,36 and HVEA24..........................................................................................................................................................P/N 80675
28” x 8” (711 mm x 203 mm)
For AVPA/AVHA42,48,60, AVPA72 and HVEA30, 36, 42, 49, 60.....................................................................................................P/N 80676
30” x 10” (762 mm x 254 mm)
➤ Return Grilles
For AVPA20/24...............................................................................................................................................................................................P/N 80677
20” x 12” (508 mm x 305 mm)
For AVPA/AVHA30,36 and HVEA24..........................................................................................................................................................P/N 80678
28” x 14” (711 mm x 356 mm)
For AVPA/AVHA42,48,60, AVPA72 and HVEA30, 36, 42, 49, 60.....................................................................................................P/N 80679
30” x 16” (762 mm x 406 mm)
➤ Return Filter Grilles
Used when filter must be changed from the interior. Not recommended for ComPac® II air conditioner.
Note: Filter used in Return Filter Grille is 1” (25 mm) thick.
For AVPA20/24...............................................................................................................................................................................................P/N 80671
20” x 12” (508 mm x 305 mm)
For AVPA/AVHA30,36 and HVEA24..........................................................................................................................................................P/N 80672
28” x 14” (711 mm x 356 mm)
For AVPA/AVHA42,48,60, AVPA72 and HVEA30, 36, 42, 49, 60.....................................................................................................P/N 80673
30” x 16” (762 mm x 406 mm)
➤ AVPA12 Grilles and Wall Sleeves
For AVPA12 ComPac I (non-economizer)...............................................................................................................................................P/N 80682
Supply Grille 17” x 5” ( 432 mm x 127 mm)
Return Air Grilles For AVPA12 (non-economizer unit).......................................................................................................................P/N 92352
17” x 10” (432 mm x 25)
For AVPA12 ComPac I (non-economizer) unit Return Air Filter Grille..........................................................................................P/N 80683
17” x 10” (432 mm x 25)
➤ For AVPA12 ComPac II with Factory Installed Economizer
Combination Supply and Return Air Grille and Wall Sleeve for 19” x 19” Opening
Wall Sleeve for 19” x 19” (483 mm x 483 mm) opening.............................................................................................................P/N S/09392
Combination Supply and Return Air Grille for 19” x 19” (483 mm x 483 mm) opening........................................................P/N 92379
Note: Grille is 17” x 17” (432 mm x 432 mm)
Combination Supply and Return Air Grille and Wall Sleeve for 28” x 19” Opening
Wall Sleeve for 28” x 19” (711 mm x 483 mm) opening............................................................................................................ P/N S/01784
Combination Supply and Return Air Grille for 28” x 19” (711 mm x 483 mm) opening....................................................... P/N 80681
Note: Grille is 26” x 17” (660 mm x 432 mm)
Options
The ComPac® I and ComPac® II air conditioners were designed and are built to stringent requirements of the
communications/electronic shelter. Applications occur that have special requirements. Numerous options are available
for the ComPac I and ComPac II air conditioners that meet these special needs.
➤ Hard Start Kit
Used on single phase equipment to give the compressor higher starting torque under low voltage conditions. (Field
installed only) (Note: Not recommended for use on scroll compressors.)
➤ Dehumidification
ComPac® I and ComPac® II A/C – Allows the electric heat to operate simultaneously with cooling. See
Dehumidification Application Bulletin for details. Note: The electrical characteristics and requirements of air
conditioners with the dehumidification option are different from standard air conditioners. Refer to the appropriate
Summary Rating Charts for the electrical characteristics of units with Electric Reheat. Available on all units except the
AVPA12. Units with reheat require a thermostat and a dehumidistat for proper operation.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.186
➤ Protective Coating Packages
Typically, only the ComPac I is used in corrosive environments, but the ComPac II air conditioner is also available
with corrosion protection. Two corrosion protection packages are offered - one for the condenser section (Coastal
Environmental Package) and the other for the entire unit (Coat-All Package).
The Coastal Environmental Package includes:
• Corrosion resistant fasteners
• Sealed or partially sealed condenser fan motor
• Protective coating applied to all exposed internal copper and metal in the condenser section
• Protective coating on the condenser coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment)
technology.
The Coat all Package includes all of the above, plus:
• Protective coating on the evaporator coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment)
technology
• Protective coating on exterior and interior components and sheet metal. (Note: the internal sheet metal which is
insulated and the internal control box are not coated)
Note: The AVPA12 is available with the protective coatings and corrosion resistant fasteners, but does not have a
sealed condenser fan motor.
➤ Protective Coil Coatings
The Condenser Coil or the Evaporator Coil or Both can be coated. Coating the Evaporator Coil in not common. For
harsh conditions, e.g., power plants, paper mills or sites where the unit will be exposed to salt water, the coils should
be protected by a protective coating.
Note: Cooling capacity may be reduced by up to 5% on units with coated coils.
➤ External Low Noise Blower (ELNB)
ComPac® I and ComPac® II A/C – A field installed kit that consists of a condenser air hood, centrifugal blowers,
controls and a compressor jacket to reduce the sound level by up to 6 dbA of Marvair ComPac air conditioners.
Available for models AVPA30-60. See External Low Noise Blower Product Data Sheet for details.
➤ ComPac® II Air Conditioner Transition Curb
ComPac II A/C only – A sheet metal curb that enables AVPA42/48/60 ComPac II air conditioner to replace an
AVPA30/36 ComPac II unit. Curb transitions supply and return openings of the 3-1/2, 4 and 5 ton units to the smaller
openings.
➤ Hot Gas By-Pass
ComPac® I A/C Only – Used in specialty applications; i.e., Magnetic Resonance Imaging (MRI) buildings, to prevent
magnetic voltage disturbance caused by compressor cycling. Hot gas by-pass option packages are available to
allow operation to 20°F (-7°C). Please refer to Hot Gas By-pass Application Bulletin for details. Not available on the
AVPA12, 20 & 24.
➤ High Filtration
Selected units are built with larger blowers/motors for use with higher efficiency filters with MERV ratings of 11, 13
and 14 when tested to ASHRAE 52.2. Units with economizers have a prefilter on the outside air. Not available on the
AVPA12. Contact your Marvair representative for specific models.
➤ Color
ComPac® I and ComPac® II air conditioners are available in five different cabinet colors -the standard Marvair® beige,
white, gray, brown and dark bronze. The standard cabinet’s sides, top and front panels are constructed of 20 gauge
painted steel. As an option, these panels can be built of 16 gauge steel in beige & gray or .050 stucco aluminum.
When the 16 gauge painted steel or the aluminum is used, only the side, top and front panels are 16 gauge or
aluminum. Contact your Marvair representative for color chips. The cabinet can also be constructed of type 316
stainless steel. Two stainless steel cabinet constructions are available- the complete cabinet, including most internal
sheet metal or only the exterior sheet metal.
➤ Extended Warranty
A first-year labor (Silver), and a two-year labor (Gold) are available. See www.marvair.com for optional warranty details.
➤ Dirty Filter Indicator
A factory installed option that measures the difference in pressure across the internal filter and
illuminates a LED when the pressure exceeds the desired difference. Not available on the AVPA12.
7
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
➤ Phase Monitor
Continuously measures the voltage of each of the three phases. The monitor separately senses low and high voltage,
voltage unbalance including phase loss and phase reversal. A red LED glows to indicate a fault. When all voltages are
acceptable, a green LED glows. Automatically resets when voltages and phases are within operating tolerances.
Note: Not required on 1ø units.
➤ Thermal Expansion Valve
Available on all ComPac air conditioners. Improves performance in hot ambient temperatures.
➤ Sealed Condenser Fan Motors
Recommended on units to be installed in corrosive sites, e.g., near the ocean and in deserts with blowing sand.
Available on all units except the AVPA12.
➤ Compressor Sound Jacket
To reduce sound of compressor. Available on all units except the AVPA12
➤ Extreme Duty Package (Not Available on AVPA12)
Allows Marvair® air conditioners to operate in extremely cold and hot
ambient conditions. The Extreme Duty Kit is always factory installed and
is available on all air conditioners. ComPac I units without an economizer
will operate from 0°F to 130°F (-18° to 54°C). ComPac II units with an
economizer will operate from -40°F to 130°F (-40° to 54°C).
The Extreme Duty Package includes a suction line accumulator, thermal
expansion valve (TXV), crankcase heater, hard start kit, an auto reset high
pressure switch and an outdoor thermostat and fan cycle switch. The fan
cycle control is standard on all ComPac air conditioners and operates
based upon the liquid line pressure. The outside thermostat opens
whenever the outside temperature is below 50°F (10°C) and closes when
the outside temperature is 50°F (10°C) or higher. When the temperature
is below 50°F (10°C), the fan cycle switch is in the circuit; when
temperatures are 50°F (10°C) or higher, the fan cycle switch is not in the
circuit. The outdoor thermostat is used with a TXV to prevent excessive
cycling or “hunting” of the TXV.
➤ Lockable Disconnect Access Cover Plate
The access plate to the service disconnect switch can be equipped with a lockable cover.
➤ Desert Duty Package (Not available on the AVPA12)
Our standard air conditioners will operate in outside ambient temperatures up to 120°F (48.9°C) The Desert Duty
package is a factory installed package of components and cabinet modifications to allow operation in ambient
temperatures up 130°F (54°C). Standard features of the Desert Duty package include a thermal expansion valve
and a sealed condenser fan motor. Cabinet modifications include a slotted panel in the base pan that improves
condenser air flow and also provides access to the compressor and condenser fan motor. To prevent sand and dust
infiltration, the electrical control box is sealed. A closed loop design on the ComPac I unit insures that no outside air
is introduced into the shelter. Note: the ComPac II unit with the economizer may be ordered with the Desert Duty
Package. If the ComPac II air conditioner is required with the Desert Duty Package, sand intrusion into the shelter
should be considered.
➤ Washable Filter
Spun aluminum construction allows cleaning of filters with water.
➤ Hot Gas Reheat (HGR)
A Hot Gas Reheat coil and controls allow the indoor humidity of the controlled environment to be maintained at or
below a certain humidity set point. These units do not have the ability to add humidity to the room. Dehumidification
is achieved by operating mechanical cooling in conjunction with a hot gas reheat coil.
➤ Right & Left Side Compressor Location
The air conditioners can be built with the compressor on the opposite side to facilitate service access when two units
are installed side by side. In the AVPA20-24-30-36 & AVHA30/36, the standard location for the compressor is on the
right hand side. In the AVPA12 and the AVPA42-48-60 & AVHA42-48-60, the standard location for the compressor is
on the left hand side. In the 72, the compressor is accessed from the front of the unit and an opposing configuration
is not required.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.188
➤ Marvair Coil Cop® Theft Deterrent System
The Marvair Coil Cop® is a factory installed, multi-layered theft deterrent system designed for use in
Marvair wall mounted air conditioners and heat pumps. It provides visual and audio warnings and remote
notification in the event of an attempted theft or vandalism of the unit. It is especially useful for air
conditioners located in remote or unsupervised locations, e.g., many cell sites, and can eliminate bulky and
expensive cages. For a complete description of the components and operation of the Coil Cop system, please
see the Coil Cop brochure (available for download at www.marvair.com).
Two variations of the Coil Cop theft deterrent system are available:
• Coil Cop Variation T1 is the complete Coil Cop Package. Includes stainless steel channels to secure both
the condenser and evaporator coils, warning labels, a speaker, tamper resistant fasteners, loss of charge
switch, tri-axis accelerometer and operator panel with status lights.
• Coil Cop Variation T2 includes stainless steel channels to secure the condenser coil, warning labels, a
speaker, tamper resistant fasteners, loss of charge switch, tri-axis accelerometer and operator panel with
status lights. Variation T2 does not include stainless steel channel on the evaporator coil.
Remote Access Data Points
Through the Ethernet connection, the network operations
center can monitor and change various data points in the
HVAC system and the shelter.
Data Points which can be monitored and changed:
• First Stage Cooling Set Point Temperature
• Second Stage Cooling Set Point Differential
• Dew point - Current
• Inside Temperature - Average Last Hour
• Outside Temperature - Average Last Hour
• Outside Humidity - Average Last Hour
• Dew point - Average Last Hour
• Unit 1 & Unit 2 Mechanical Cooling Time - Last Hour
• Unit 1 & Unit 2 Mechanical Cooling Requests - Last
Hour
• Unit 1 & Unit 2 Free Air Cooling Time - Last Hour
• Unit 1 & Unit 2 Free Air Cooling Requests - Last
Hour
• Unit 1 & Unit 2 Heating Time - Last Hour
• Unit 1 & Unit 2 Heating Requests - Last Hour
Temperature
• First Stage Heating Set Point Temperature
• Second Stage Heating Set Point Differential
Temperature
Data points which can only be monitored:
• Inside Temperature - Current
• Outside Temperature - Current
• Outside Humidity - Current
Dry Contacts Alarm Outputs
A dry contact is provided for each HVAC unit to indicate HVAC unit failure to the shelter alarm block. Unit failure
is defined as 1) a high pressure lockout or 2) a low pressure lockout or 3) a loss of landline power. This dry
contact is a normally open contact.
9
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Back Panel Adapters for AVPA60 & AVHA60 Air Conditioners
These back panel adapters are factory installed on the AVPA60 & AVHA60 ComPac I air conditioners and to match the
supply and return air openings on Marvair 2 and 3 ton air conditioners. This allows the AVPA60 & AVHA60 to be quickly
and easily installed. No cutting or sawing of the shelter is required. The back panel, K/04317 has supply and return openings that match the openings of AVP24 & AVPA24 wall mounted air conditioners. The back panel, K/04315, has supply
and return openings that match the openings of Marvair’s AVP36 & AVPA36 air conditioners. In addition to matching the
openings of Marvair units, the back panels will also match the openings of other brands.
When the K/04317 back panel adapter is used, a return filter grille, p/n 80671, must be used. When the K/04315 back
panel adapter is used, a return filter grille, p/n 80672, must be used.
Control Box
The internal control board in the ComPac® air conditioners simplifies wiring, consolidates several of the
electrical functions onto one device and improves the reliability of the air conditioner. In addition, the control board has
LED’s that indicate operational status and fault conditions.
➤ LED Indicator Lights
COLOR
TYPE
STATUS
DESCRIPTION
Green
Power
Constant On
24 VAC power has been applied
Constant On
Normal operation
1 Blink
High pressure switch has opened twice
2 Blinks
Low pressure switch has opened twice
3 Blinks
Freeze stat (optional) - indoor coil temperature is below 35°F (1°C)
Red
Status
➤ Modes of Operation
Normal Start-up: On a call for cooling, and the with the high pressure switch closed, the cooling system (compressor,
indoor blower motor and outdoor fan motor) will be energized. (Note: See the Delay on Make feature). The cooling
system will remain energized during the three minute low pressure switch bypass cycle. If the low pressure is closed,
the cooling system will continue to operate after the three-minute bypass. If the low pressure switch is open after the
three-minute bypass, the cooling system will be de-energized.
Lockout Mode: If either the high or low pressure switch opens twice on the same call for cooling, the control board
enters into and indicates the lockout mode. In the lockout mode, the compressor is turned off, the alarm output is
energized and the status LED’s will blink to indicate which fault has occurred. If there is a call for air flow, the indoor
blower will remain energized. When the lockout condition has cleared, the unit will reset if the demand of the thermostat is removed or when power is reset. The lockout circuit is factory wired for normally open contacts. The user
can select either normally closed or normally open remote alarm dry contacts.
Delay on Make: On initial power up or on resumption of power, the air conditioner will wait .03 to 10 minutes from a
call for cooling before allowing the contactor to energize.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1810
Model Identification
••• S A
••AC
Refrigerant
A = R410A
2-Stage
Compressor
AVP
AVH
HVE
•
System Type
Air Conditioner
Nominal Cooling
12 = 11,000 BTUH
20 = 20,000 BTUH
24 = 24,000 BTUH
30 = 30,000 BTUH
36 = 36,000 BTUH
42 = 42,000 BTUH
48/49 = 48,000 BTUH
60 = 60,000 BTUH
72 = 72,000 BTUH
•••
• •
Electric Heat – kW
000 = No Heat 080 =
022 = 2.2 kW 090 =
036 = 3.6 kW 100 =
040 = 4 kW
120 =
050 = 5 kW
150 =
060 = 6 kW
Power Supply
A =208/230V,1ø,60Hz
C = 208/230V,3ø,60Hz
D = 460V,3ø,60Hz (3 wire)
Z = 575V,3ø,60Hz
A5
Special Option Code
R = Electric Reheat
U = Scroll Compressor
X = Hot Gas Bypass
O = Opposite side compressor
E = Extreme Duty D = Desert Duty
G = Hot Gas Reheat
8 kW
9 kW
10 kW
12 kW
15 kW
Configuration
N = ComPac® I A/C
C =ComPac® II A/C
•••
Cabinet Color
100=Beige
200=Gray
400=White
500 = Stainless Steel
(Exterior Only)
SS-500 = Stainless Steel
700=Aluminum
Stucco
A5 = Built in
compliance with
UL 1995, 4th edition
ComPac I & ComPac II Ambient Temperature Operating Ranges
Basic Model
ComPac I
Special Option
AVPA
AVHA/HVEA/HVESA
Standard Unit (N)
20ºF - 120ºF (7ºC - 48.9ºC)
20ºF - 120ºF (7ºC - 48.9ºC)
Desert Duty (ND)
20ºF - 130ºF (7ºC - 54ºC)
20ºF - 130ºF (7ºC - 54ºC)
Extreme Duty Kit (NE)
ComPac II
0ºF - 130ºF (18ºC - 54ºC)
0ºF - 130ºF (18ºC - 54ºC)
Standard Unit (C)
-40ºF - 120ºF (-40ºC - 48.9ºC)
-40ºF - 120ºF (-29ºC - 48.9ºC)
Desert Duty (CD)
-40ºF - 130ºF (-40ºF - 54ºC)
-40ºF - 130ºF (-29ºC - 54ºC)
Extreme Duty Kit (CE)
-40ºF - 130ºF (-40ºF - 54ºC)
-40ºF - 130ºF (-29ºC - 54ºC)
EER Comparison by Model
Nominal Cooling Capacity (BTUH)
12,000
20,000
24,000
30,000
36,000
Basic Model
EER
Nominal Cooling Capacity (BTUH)
Basic Model
EER
AVPA12
9.00
AVPA42
9.25
AVHA12
10.00
AVHA42
10.00
AVPA20
9.00
HVEA42
10.50
AVHA20
10.00
HVESA42
10.50
AVPA24
9.25
AVPA48
9.50
AVHA24
10.00
HVEA24
10.75
AVPA30
9.25
42,000
48,000
AVHA48
10.00
HVEA49
11.50
HVESA49
11.50
AVHA30
10.00
AVPA60
9.25
HVEA30
11.75
AVHA60
10.00
AVPA36
9.25
AVHA36
10.00
HVEA36
11.25
HVESA36
11.25
60,000
72,000
HVEA60
10.50
HVESA60
10.50
AVPA72
10.00
Note: HVESA models have 2-stage compressors.
11 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
ComPac®AVPA Standard Efficiency Air Conditioners
Certified Efficiency and Capacity Ratings at
ANSI/AHRI Standard 390 - AVPA/AVHA Air Conditioners
AVPA12
AVPA20
ACA
ACA
10,800
19,600
24,000
EER2
9.00
9.00
9.25
9.25
9.25
9.25
Rated Air Flow (CFM3)
400
755
840
1,000
1,100
1,575
AVHA12
AVHA20
ACA
ACA
Cooling BTUH1
10,800
19,600
24,000
29,000
33,000
42,000
46,000
54,000
EER2
10.00
10.00
10.00
10.00
10.00
10.00
10.00
10.00
400
755
840
1,000
1,100
1,575
1,725
1,850
Model Number
Cooling BTUH1
Model Number
Rated Air Flow (CFM3)
AVPA24
ACA
ACC
ACD
AVPA30
ACA
ACC
AVPA36
ACD
ACA
29,000
AVHA24
ACA
ACC
ACD
ACC
ACD
AVPA42
ACA
35,000
AVHA30
ACA
ACC
ACA
ACC
ACD
AVPA48
ACA
42,000
AVHA36
ACD
ACC
ACD
ACC
ACD
AVPA60
ACA
46,000
AVHA42
ACA
ACC
ACD
AVPA72
ACD
ACA
ACC
ACD ACZ
54,500
62,000
70,000
9.50
9.25
10.00
10.00
1,725
1,850
1,925
1,925
AVHA48
ACA
ACC
ACC
ACD
AVHA60
ACA
ACC
ACD
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air. 2EER=Energy Efficiency Ratio 3CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect performance and air flow.
1
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb AVPA/AVHA Air Conditioners
Model Number
Total Capacity
AVPA12
AVPA20
ACA
ACA
10,800
19,600
AVPA24
ACA
ACC
ACD
AVPA30
ACA
24,000
ACC
AVPA36
ACD
ACA
29,000
ACC
ACD
AVPA42
ACA
35,000
ACC
ACD
AVPA48
ACA
42,000
ACC
ACD
AVPA60
ACA
46,000
ACC
AVPA72
ACD
54,500
ACA
62,000
ACC
ACD ACZ
70,000
Sensible Heat Ratio
0.74
0.76
0.75
0.75
0.69
0.76
0.76
0.73
0.71
0.67
Sensible Capacity
8,000
14,800
18,000
21,740
24,155
31,900
34,940
39,800
43,815
46,800
400
755
840
1,000
1,100
1,575
1,725
1,850
1,925
1,925
AVHA12
AVHA20
ACA
ACA
10,800
19,600
Rated Air Flow (CFM1)
Model Number
Total Capacity
AVHA24
ACA
ACC
ACD
24,000
AVHA30
ACA
ACC
AVHA36
ACD
ACA
29,000
ACC
ACD
AVHA42
ACA
33,000
ACC
ACD
42,000
AVHA48
ACA
ACC
46,000
ACD
AVHA60
ACA
ACC
Sensible Heat Ratio
0.74
0.76
0.75
0.75
0.74
0.74
0.76
0.72
Sensible Capacity
8,000
14,800
18,000
21,700
24,500
31,000
35,000
39,000
400
755
840
1,000
1,100
1,575
1,725
1,850
Rated Air Flow (CFM1)
1
ACD
54,000
CFM=Cubic Feet per Minute. Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
Cooling Performance (BTUH) at Various Outdoor Temperatures AVPA/AVHA Air Conditioners
Model Number
Outdoor Temperature
75ºF / 24ºC
80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC
95ºF / 35ºC
100ºF / 38ºC 105ºF / 40.5ºC 110ºF / 43.3ºC 115ºF / 46ºC 120ºF / 48.9ºC 125ºF / 51.7ºC 130ºF / 54.4ºC
AVPA12AC
12,525
12,095
11,660
11,230
10,800
10,365
9,9935
9,500
9,285
8,640
8,205
7,775
AVPA20AC
22,735
21,950
21,165
20,380
19,600
18,815
18,030
17,245
16,855
15,680
14,895
14,110
AVPA24AC
27,840
26,880
25,920
24,960
24,000
23,040
22,080
21,120
20,640
19,200
18,240
17,280
AVPA30AC
33,640
32,480
31,320
30,160
29,000
27,840
26,680
25,520
24,940
23,200
22,040
20,880
AVPA36AC
40,600
39,200
37,800
36,400
35,000
33,600
32,200
30,800
30,100
28,000
26,600
25,200
AVPA42AC
48,720
47,040
45,360
43,680
42,000
40,320
38,640
36,960
36,120
33,600
31,920
30,240
AVPA48AC
53,360
51,520
49,680
47,840
46,000
44,160
42,320
40,480
39,560
36,800
34,960
33,120
AVPA60AC
63,220
61,040
58,860
56,680
54,500
52,320
50,140
47,960
46,870
43,600
41,420
39,240
AVPA72ACA
71,920
69,440
66,960
64,480
62,000
59,520
57,040
54,560
53,320
49,600
47,120
44,640
AVPA72ACC, ACD, ACZ
81,200
78,400
75,600
72,800
70,000
67,200
64,400
61,600
60,200
56,000
53,200
50,400
AVHA12AC
12,525
12,095
11,660
11,230
10,800
10,365
9,9935
9,500
9,285
8,640
8,205
7,775
AVHA20AC
22,735
21,950
21,165
20,380
19,600
18,815
18,030
17,245
16,855
15,680
14,895
14,110
AVHA24AC
27,840
26,880
25,920
24,960
24,000
23,040
22,080
21,120
20,640
19,200
18,240
17,280
AVHA30AC
33,640
32,480
31,320
30,160
29,000
27,840
26,680
25,520
24,940
23,200
22,040
20,880
AVHA36AC
38,280
36,960
35,640
34,320
33,000
31,680
30,360
29,040
28,380
26,400
25,080
23,760
AVHA42AC
48,720
47,040
45,360
43,680
42,000
40,320
38,640
36,960
36,120
33,600
31,920
30,240
AVHA48AC
53,360
51,520
49,680
47,840
46,000
44,160
42,320
40,480
39,560
36,800
34,960
33,120
AVHA60AC
63,220
61,040
58,860
56,680
54,500
52,320
50,140
47,960
46,870
43,600
41,420
39,240
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Note: Operation of units above 120°F (48.9°C) requires the Desert Duty package.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1812
Electrical Characteristics - Compressor, Fan & Blower Motors AVPA/AVHA Air Conditioner
BASIC
MODEL
AVPA/AVHA12ACA
OUTDOOR FAN &
INDOOR BLOWER MOTORS
COMPRESSOR
OUTDOOR
FAN MOTOR
INDOOR
BLOWER MOTOR
TYPE
VOLTS / HZ
/ PH
RLA1
LRA2
VOLTS / HZ / PH
RPM3
FLA4
HP5
RPM3
FLA4
HP5
ROTARY
208/230-60-1
4.7
25.0
208/230-60-1
1630
0.65
1/6
1650
0.85
1/5
AVPA/AVHA20ACA
208/230-60-1
8.3
43.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
AVPA/AVHA24ACA
208/230-60-1
10.6
54.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
AVPA30ACA
208/230-60-1
13.1
74.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
AVPA36ACA
208/230-60-1
14.7
84.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
AVPA42ACA
208/230-60-1
15.7
84.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA48ACA
208/230-60-1
18.6
102.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA60ACA
208/230-60-1
23.0
130.0
208/230-60-1
825
2.8
1/3
1075
5.2
3/4
AVPA/AVHA24ACA
208/230-60-1
12.8
64.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
AVPA/AVHA30ACA
208/230-60-1
14.1
77.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
AVPA/AVHA36ACA
208/230-60-1
17.9
112.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
208/230-60-1
19.8
109.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA/AVHA48ACA
208/230-60-1
21.8
117.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA/AVHA60ACA
208/230-60-1
26.2
134.0
208/230-60-1
825
2.8
1/3
1075
5.2
3/4
AVPA72ACA
208/230-60-1
30.1
158.0
208/230-60-1
825
2.9
1/2
1075
5.2
3/4
AVPA/AVHA24ACC
208/230-60-3
8.3
61.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
AVPA/AVHA30ACC
208/230-60-3
9.0
71.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
208/230-60-3
13.2
88.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
208/230-60-3
13.6
83.1
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA/AVHA48ACC
208/230-60-3
13.7
83.1
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA/AVHA60ACC
208/230-60-3
15.6
111.0
208/230-60-1
825
2.8
1/3
1075
5.2
3/4
AVPA72ACC
208/230-60-3
22.4
149.0
208/230-60-1
825
2.9
1/2
1075
5.2
3/4
AVPA/AVHA24ACD
460-60-3
5.1
28.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
AVPA/AVHA30ACD
460-60-3
5.6
38.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
AVPA/AVHA36ACD
460-60-3
6.0
44.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
AVPA/AVHA42ACA
RECIPROCATING
SCROLL
AVPA/AVHA36ACC
AVPA/AVHA42ACC
AVPA/AVHA42ACD
SCROLL
SCROLL
460-60-3
6.1
41.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA/AVHA48ACD
460-60-3
6.2
41.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA/AVHA60ACD
460-60-3
7.7
52.0
208/230-60-1
825
2.8
1/3
1075
5.2
3/4
AVPA72ACD
460-60-3
10.6
75.0
208/230-60-1
825
2.9
1/2
1075
5.2
3/4
AVPA24ACZ
575-60-3
3.3
23.7
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
AVPA30ACZ
575-60-3
3.8
36.5
208/230-60-1
1075
1.5
1/5
1075
1.5
1/4
AVPA36ACZ
575-60-3
4.2
30.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
575-60-3
4.2
33.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/2
AVPA48ACZ
575-60-3
4.8
33.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
AVPA60ACZ
575-60-3
5.8
38.9
208/230-60-1
825
2.8
1/3
1075
3.1
3/4
AVPA72ACZ
575-60-3
7.7
54.0
825
2.8
1/3
1075
5.2
3/4
AVPA42ACZ
SCROLL
2
3
RLA = Rated Load Amps
LRA = Locked Rotor Amps
RPM = Revolutions per Minute
The 460 volt (ACD) units will have a step down transformer for the 230 volt motors.
1
208/230-60-1
4
FLA = Full Load Amps
5
HP = Horsepower
13 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Summary Electrical Ratings (Wire and Circuit Breaker Sizing) AVPA/AVHA Air Conditioners with Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”),
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT
BASIC
MODEL
000 = None 022 = 2.2 kw036 = 3.6 kw 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw
SPPE
SPPE
SPPE
SPPE
SPPE
SPPE
SPPE
SPPE
SPPE
SPPE
SPPE
VOLTAGE
PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
3
3
3
3
3
3
3
3
3
3
3
AVPA/AVHA12ACA
208/230-1-60 7.4
15
26.9
30
AVPA/AVHA20ACA
208/230-1-60 13.4
20
22.4
25
27.5
30
32.8
35
43.1
45
53.6
60
AVPA/AVHA24ACA
208/230-1-60 19.0
30
22.4
30
27.5
30
32.8
35
43.1
45
53.6
60
AVPA/AVHA30ACA
208/230-1-60 21.9
35
23.4
35
28.5
35
33.8
35
44.1
45
54.6
60
65.0
70
80.6
90
AVPA/AVHA36ACA
208/230-1-60 26.7
40
26.7
40
28.5
40
33.8
40
44.1
45
54.6
60
65.0
70
80.6
90
12.4
15
19.7
20
AVPA/AVHA42ACA
208/230-1-60 30.7
50
30.7
50
55.2
60
65.6
70
81.2
90
AVPA/AVHA48ACA
208/230-1-60 33.2
50
33.2
50
55.2
60
65.6
70
81.2
90
AVPA/AVHA60ACA
208/230-1-60 40.8
60
40.8
60
57.3
60
67.7
70
83.3
90
45.6
60
57.3
60
83.3
90
47.6
50
AVPA72ACA
208/230-1-60 45.6
60
67.7
70
AVPA/AVHA24ACC
208/230-3-60 13.4
20
19.5
20
28.6
30
37.6
40
AVPA/AVHA30ACC
208/230-3-60 15.6
20
20.5
25
29.6
30
38.6
40
AVPA/AVHA36ACC
208/230-3-60 20.8
30
20.8
30
29.6
30
38.6
40
47.6
50
AVPA/AVHA42ACC
208/230-3-60 22.9
35
22.9
35
30.2
35
39.1
40
48.1
50
AVPA/AVHA48ACC
208/230-3-60 23.0
35
23.0
35
30.2
35
39.1
40
48.1
50
AVPA/AVHA60ACC
208/230-3-60 27.5
40
27.5
40
32.3
40
41.3
45
50.2
60
AVPA72ACC
208/230-3-60 36.1
50
36.1
50
36.1
50
41.3
50
50.2
60
AVPA/AVHA24ACD
460-3-60
7.9
15
9.8
15
14.3
15
18.8
20
23.3
25
AVPA/AVHA30ACD
460-3-60
9.2
15
10.3
15
14.8
15
19.3
20
23.8
25
AVPA/AVHA36ACD
460-3-60
9.7
15
10.3
15
14.8
15
19.3
20
23.8
25
AVPA/AVHA42ACD
460-3-60
10.6
15
10.9
15
15.1
20
19.6
20
24.1
25
AVPA/AVHA48ACD
460-3-60
10.7
15
10.9
15
15.1
20
19.6
20
24.1
25
AVPA/AVHA60ACD
460-3-60
13.6
20
13.6
20
16.1
20
20.6
25
25.1
30
AVPA72ACD
460-3-60
17.3
25
17.3
25
17.3
25
20.6
25
25.1
30
AVPA24ACZ
575-3-60
5.3
15
7.9
15
11.5
15
15.0
16
AVPA30ACZ
575-3-60
6.5
15
8.3
15
11.9
15
15.4
20
19.0
20
AVPA36ACZ
575-3-60
7.0
15
8.3
15
11.9
15
15.4
20
19.0
20
AVPA42ACZ
575-3-60
7.6
15
8.5
15
12.1
15
16.6
20
19.2
20
AVPA48ACZ
575-3-60
8.4
15
8.5
15
12.1
15
16.6
20
19.2
20
AVPA60ACZ
575-3-60
10.5
15
10.5
15
13.0
15
16.5
20
20.1
25
AVPA72ACZ
575-3-60
12.8
20
12.8
20
13.0
20
16.5
20
20.1
25
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
1
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1814
Summary Electrical Ratings (Wire and Circuit Breaker Sizing) AVPA/AVHA Air Conditioners with Elec. Reheat (“R”) and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”),
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT
BASIC
MODEL
VOLTAGE
PHASE / HZ
000 = None 022 = 2.2 kw 036 = 3.6 kw 040 = 4 kw
SPPE3
MCA
SPPE3
SPPE3
SPPE3
MFS
MCA
1
AVPA/AVHA12ACA 208/230-1-60 7.4
15
18.9
AVPA/AVHA20ACA 208/230-1-60 13.4
20
34.3
AVPA/AVHA24ACA 208/230-1-60 19.0
30
39.9
MFS
20
26.2
30
1
MFS
33.4
35
35
39.4
40
45
AVPA/AVHA30ACA 208/230-1-60 21.9
35
42.8
45
AVPA/AVHA36ACA 208/230-1-60 26.7
40
AVPA/AVHA42ACA 208/230-1-60 30.7
50
47.6
50
AVPA/AVHA48ACA 208/230-1-60 33.2
1
MFS
MCA1
MFS2
45
65.5
70
60
71.1
80
50
53.2
60
74
80
84.8
90
100
100
52.7
60
56.7
60
58
60
78.8
80
89.2
90
82.8
90
93.2 100 108.8 110
50
59.2
60
85.3
90
95.7 100 111.3 120
AVPA/AVHA60ACA 208/230-1-60 40.8
60
AVPA72ACA
208/230-1-60 45.6
60
66.8
70
92.9 100 103.3 110 118.9 120
71.6
80
97.7 100 108.1 110 123.7 130
AVPA/AVHA24ACC 208/230-3-60 13.4
20
31.4
35
40.5
45
49.5
50
58.5
60
AVPA/AVHA30ACC 208/230-3-60 15.6
20
33.6
35
42.7
45
51.7
60
60.7
70
AVPA/AVHA36ACC 208/230-3-60 20.8
30
38.8
40
47.9
50
56.9
60
65.9
70
AVPA/AVHA42ACC 208/230-3-60 22.9
35
40.9
45
50.0
50
59.0
60
68.0
70
AVPA/AVHA48ACC 208/230-3-60 23.0
35
41.0
45
50.1
60
59.1
60
68.1
70
AVPA/AVHA60ACC 208/230-3-60 27.5
40
45.5
50
54.6
60
63.6
70
72.6
80
AVPA72ACC
50
54.1
60
63.2
70
72.2
80
81.2
90
1
2
MCA
1
MFS
2
MCA
2
MCA
SPPE3
MFS
2
MFS
150 = 15 kw
1
2
MCA
SPPE3
47.9
2
MCA
SPPE3
50.3
1
MCA
100 = 10 kw 120 = 12 kw
44.7
2
MFS
SPPE3
45
2
MCA
090 = 9 kw
SPPE3
40
208/230-3-60 36.1
MCA
080 = 8 kw
SPPE3
MFS
2
MFS
060 = 6 kw
SPPE3
1
1
1
050 = 5 kw
2
104.8 110
AVPA/AVHA24ACD
460-3-60
7.9
15
16.9
20
21.4
25
25.9
30
30.4
35
AVPA/AVHA30ACD
460-3-60
9.2
15
18.2
20
22.7
25
27.2
30
31.7
35
AVPA/AVHA36ACD
460-3-60
9.7
15
18.7
20
23.2
25
27.7
30
32.2
35
AVPA/AVHA42ACD
460-3-60
10.6
15
19.6
20
24.1
25
28.6
30
33.1
35
AVPA/AVHA48ACD
460-3-60
10.7
15
19.7
20
24.2
25
28.7
30
33.2
35
AVPA/AVHA60ACD
460-3-60
13.6
20
22.6
25
27.1
30
31.6
35
36.1
40
AVPA72ACD
460-3-60
17.3
25
26.3
30
30.8
35
35.3
40
39.8
40
AVPA24ACZ
575-3-60
5.3
15
12.6
15
16.2
20
19.7
20
AVPA30ACZ
575-3-60
6.5
15
13.7
15
17.3
20
20.8
25
24.5
25
AVPA36ACZ
575-3-60
7.0
15
14.2
15
17.8
20
21.3
25
25.0
25
AVPA42ACZ
575-3-60
7.6
15
14.9
16
18.5
20
22.0
25
25.6
30
AVPA48ACZ
575-3-60
8.4
15
15.6
20
19.2
20
22.7
25
26.4
30
AVPA60ACZ
575-3-60
10.5
15
17.7
20
21.3
25
24.8
25
28.5
30
AVPA72ACZ
575-3-60
12.8
20
20.1
25
23.7
25
27.2
30
30.8
35
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
2MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
1
15 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Unit Load Amps - AVPA/AVHA Air Conditioners with Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
BASIC
MODEL
NUMBER
VOLTAGE
PHASE
/ HZ
CURRENT
AMPS
AC1 IBM2
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS)
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE
CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE
LOCATED ON AN ELECTRICAL CIRCUIT THAT
DOES NOT HAVE HEATERS
2.2 kW 3.6 kW 04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 2.2 kW 3.6 kW 04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW
AVPA/AVHA12ACA
208/230-1-60
AVPA/AVHA20ACA
208/230-1-60 11.3 1.5
16.7 20.8 25.0 33.3
41.7
18.2 22.3 26.5 34.8
43.2
AVPA/AVHA24ACA
208/230-1-60 15.8 1.5
16.7 20.8 25.0 33.3
41.7
18.2 22.3 26.5 34.8
43.2
AVPA/AVHA30ACA
208/230-1-60 18.4 2.5
16.7 20.8 25.0 33.3
41.7 50.0 62.5
19.2 23.3 27.5 35.8
44.2 52.5 65.0
AVPA/AVHA36ACA
208/230-1-60 22.2 2.5
16.7 20.8 25.0 33.3
41.7 50.0 62.5
19.2 23.3 27.5 35.8
44.2 52.5 65.0
AVPA/AVHA42ACA
208/230-1-60 25.7 3.1
20.8
41.7 50.0 62.5
23.9
44.8 53.1 65.6
AVPA/AVHA48ACA
208/230-1-60 27.7 3.1
20.8
41.7 50.0 62.5
23.9
44.8 53.1 65.6
AVPA/AVHA60ACA
208/230-1-60 34.2 5.2
20.8
41.7 50.0 62.5
26.0
46.9 55.2 67.7
AVPA72ACA
208/230-1-60 38.2 5.2
20.8
41.7 50.0 62.5
26.0
46.9 55.2 67.7
6.1 0.85 9.2
15.0
20.8
10.1 15.0
21.7
AVPA/AVHA24ACC
208/230-3-60 11.2 1.5
14.4
21.7
28.9 36.1
15.9
23.2
30.4 37.6
AVPA/AVHA30ACC
208/230-3-60 13.3 2.5
14.4
21.7
28.9 36.1
16.9
24.2
31.4 38.6
AVPA/AVHA36ACC
208/230-3-60 17.5 2.5
14.4
21.7
28.9 36.1
16.9
24.2
31.4 38.6
AVPA/AVHA42ACC
208/230-3-60 19.5 3.1
14.4
21.7
28.9 36.1
17.5
24.8
32.0 39.2
AVPA/AVHA48ACC
208/230-3-60 19.6 3.1
14.4
21.7
28.9 36.1
17.5
24.8
32.0 39.2
AVPA/AVHA60ACC
208/230-3-60 23.6 5.2
14.4
21.7
28.9 36.1
19.6
26.9
34.1 41.3
AVPA72ACC
208/230-3-60 30.5 5.2
14.4
21.7
28.9 36.1
19.6
26.9
34.1 41.3
AVPA/AVHA24ACD
460-3-60
6.6
0.8
7.2
10.8
14.4 18.0
8.0
11.6
15.2 18.8
AVPA/AVHA30ACD
460-3-60
7.8
1.3
7.2
10.8
14.4 18.0
8.5
12.1
15.7 19.3
AVPA/AVHA36ACD
460-3-60
8.2
1.3
7.2
10.8
14.4 18.0
8.5
12.1
15.7 19.3
AVPA/AVHA42ACD
460-3-60
9.1
1.6
7.2
10.8
14.4 18.0
8.8
12.4
16.0 19.6
AVPA/AVHA48ACD
460-3-60
9.2
1.6
7.2
10.8
14.4 18.0
8.8
12.4
16.0 19.6
AVPA/AVHA60ACD
460-3-60
11.7 2.6
7.2
10.8
14.4 18.0
9.8
13.4
17.0 20.6
AVPA72ACD
460-3-60
14.7 2.6
7.2
10.8
14.4 18.0
9.8
13.4
17.0 20.6
AVPA24ACZ
575-3-60
4.5
0.6
5.8
8.7
11.5
6.4
9.3
12.1
AVPA30ACZ
575-3-60
5.5
1.0
5.8
8.7
11.5 14.4
6.8
9.7
12.5 15.4
AVPA36ACZ
575-3-60
5.9
1.0
5.8
8.7
11.5 14.4
6.8
9.7
12.5 15.4
AVPA42ACZ
575-3-60
6.6
1.2
5.8
8.7
11.5 14.4
7.0
9.9
12.7 15.6
AVPA48ACZ
575-3-60
7.2
1.2
5.8
8.7
11.5 14.4
7.0
9.9
12.7 15.6
AVPA60ACZ
575-3-60
9.0
2.1
5.8
8.7
11.5 14.4
7.9
10.8
13.6 16.5
AVPA72ACZ
575-3-60
10.9 2.1
5.8
8.7
11.5 14.4
7.9
10.8
13.6 16.5
2
AC = Air Conditioner Unit Amps
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models. Total heating and
cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are maximum phase loads.
1
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1816
ComPac®HVEA High Efficiency Air Conditioners
Certified Efficiency and Capacity Ratings at ANSI/AHRI Standard 390
for HVEA Air Conditioners with Single Stage Compressor
HVEA24
Model Number
ACA
ACC
HVEA30
ACD
ACA
ACC
HVEA36
ACD
ACA
ACC
HVEA42
ACD
ACA
HVEA49
ACC
ACD
ACA
ACC
HVEA60
ACD
ACA
ACC
Cooling BTUH1
23,600
29,000
35,600
40,000
49,000
58,000
EER2
10.75
11.75
11.25
10.50
11.50
10.50
800
1,000
1,300
1,400
1,750
1,900
Rated Air Flow (CFM3)
ACD
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air
EER=Energy Efficiency Ratio
CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect
performance and air flow.
1
2
3
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb HVEA Air Conditioners with Single Stage Compressor
HVEA24
Model Number
ACA
Total Capacity
Sensible Heat Ratio
Sensible Capacity
Rated Air Flow (CFM1)
ACC
HVEA30
ACD
ACA
ACC
HVEA36
ACD
ACA
ACC
HVEA42
ACD
ACA
ACC
HVEA49
ACD
ACA
ACC
HVEA60
ACD
ACA
ACC
23,600
29,000
35,600
40,000
49,000
58,000
0.74
0.76
0.76
0.73
0.74
0.73
17,435
22,020
26,945
29,270
36,175
42,505
800
1,000
1,300
1,400
1,750
1,900
ACD
CFM=Cubic Feet per Minute
Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
1
Cooling Performance (BTUH) at Various Outdoor Temperatures
for HVEA Air Conditioners with Single Stage Compressor
Model
Number
Outdoor Temperature
75ºF / 24ºC 80ºF / 26.5ºC
85ºF / 29ºC
90ºF / 32ºC
95ºF / 35ºC
100ºF / 38ºC 105ºF / 40.5ºC
HVEA24AC
27,375
26,430
25,490
24,545
23,600
22,655
110ºF / 43.3ºC
115ºF / 46.1ºC
120ºF / 48.9ºC
125ºF / 51.7ºC
130ºF / 54.4ºC
21,710
20,770
20,295
19,870
19,445
19,020
23,375
HVEA30AC
33,640
32,480
31,320
30,160
29,000
27,840
26,680
25,520
24,940
24,420
23,895
HVEA36AC
41,295
39,870
38,450
37,025
35,600
34,175
32,750
31,320
30,615
29,975
29,335
28,695
HVEA42AC
46,400
44,800
43,200
41,600
40,000
38,400
36,800
35,200
34,400
33,680
32,960
32,240
HVEA49AC
56,840
54,880
52,920
50,960
49,000
47,040
45,080
43,120
42,140
41,260
40,375
39,495
HVEA60AC
67,280
64,960
62,640
60,320
58,000
55,680
53,360
51,040
49,880
48,835
47,790
46,745
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
17 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Electrical Characteristics - Compressor, Fan & Blower Motors HVEA Air Conditioner with Single Stage Compressor
BASIC
MODEL
COMPRESSOR
OUTDOOR FAN MOTOR
INDOOR FAN MOTOR (ECM)
VOLTS-HZ-PH
RLA1
LRA2
VOLTS-HZ-PH
RPM3
FLA4
HP5
VOLTS-HZ-PH
RPM3
FLA4
HP5
HVEA24ACA
208/230-60-1
12.8
58.3
208/230-60-1
1075
1.8
1/4
208/230-60-1
1500
2.8
1/3
HVEA30ACA
208/230-60-1
12.8
64.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
208/230-60-1
16.6
79.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
208/230-60-1
19.8
109.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
HVEA49ACA
208/230-60-1
21.8
117.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVEA60ACA
208/230-60-1
26.4
134.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVEA24ACC
208/230-60-3
7.7
55.4
208/230-60-1
1075
1.8
1/4
208/230-60-1
1500
2.8
1/3
HVEA30ACC
208/230-60-3
8.3
61.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
HVEA36ACC
208/230-60-3
10.4
88.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
208/230-60-3
13.6
83.1
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
HVEA49ACC
208/230-60-3
13.7
83.1
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVEA60ACC
208/230-60-3
15.9
111.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVEA24ACD
460-60-3
4.0
28.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1500
2.8
1/3
HVEA30ACD
460-60-3
5.1
28.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
HVEA36ACD
460-60-3
5.8
38.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
HVEA36ACA
HVEA42ACA
HVEA42ACC
HVEA42ACD
Type
SCROLL
SCROLL
SCROLL
460-60-3
6.1
41.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
HVEA49ACD
460-60-3
6.2
41.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVEA60ACD
460-60-3
7.7
52.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
2
3
RLA = Rated Load Amps
LRA = Locked Rotor Amps
RPM = Revolutions per Minute
The 460 volt units will have a step down transformer for the 230 volt motors.
1
4
FLA = Full Load Amps
5
HP = Horsepower
Summary Electrical Ratings (Wire and Circuit Breaker Sizing) HVEA Air Conditioners with Single stage Compressors & Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
100 = 10 kw 120 = 12 kw 150 = 15 kw
SPPE3
BASIC
MODEL
VOLTAGE
PHASE / HZ
HVEA24ACA
208/230-1-60
20.6
30
23.1
30
28.8
30
34.1
35
44.4
45
54.9
60
HVEA30ACA
208/230-1-60
21.6
30
23.1
30
28.8
30
34.1
35
44.4
45
54.9
60
26.4
40
28.8
40
34.1
35
44.4
45
30.4
50
SPPE3
SPPE3
MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
HVEA36ACA
208/230-1-60
26.4
40
HVEA42ACA
208/230-1-60
30.4
50
65.3
70
80.9
90
54.9
60
65.3
70
80.9
90
54.9
60
65.3
70
80.9
90
HVEA49ACA
208/230-1-60
34.4
50
34.4
50
56.4
60
66.8
70
82.4
90
HVEA60ACA
208/230-1-60
40.1
60
40.1
60
56.4
60
66.8
70
82.4
90
HVEA24ACC
208/230-3-60
14.2
20
38.9
40
20.8
25
29.9
30
HVEA30ACC
208/230-3-60
16.0
20
20.8
25
29.9
30
38.9
40
47.9
50
HVEA36ACC
208/230-3-60
18.6
25
20.8
25
29.9
30
38.9
40
47.9
50
HVEA42ACC
208/230-3-60
22.6
35
22.6
35
29.9
35
38.9
40
47.9
50
HVEA49ACC
208/230-3-60
24.2
35
24.2
35
31.4
35
40.4
50
49.4
50
HVEA60ACC
208/230-3-60
27.0
40
27.0
40
31.4
40
40.4
50
49.4
50
HVEA24ACD
460-3-60
7.3
15
10.4
15
14.9
15
19.4
20
23.9
25
HVEA30ACD
460-3-60
9.2
15
10.4
15
14.9
15
19.4
20
23.9
25
HVEA36ACD
460-3-60
10.1
15
10.4
15
14.9
15
19.4
20
23.9
25
HVEA42ACD
460-3-60
10.4
15
10.4
15
14.9
15
19.4
20
23.9
25
HVEA49ACD
460-3-60
11.3
15
11.3
15
15.7
20
20.2
25
24.7
25
HVEA60ACD
460-3-60
13.2
20
13.2
20
15.7
20
20.2
25
24.7
25
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. he 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
1
2
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1818
3
Summary Electrical Ratings (Wire and Circuit Breaker Sizing) HVEA Air Conditioners with Electric Reheat (“R”) with Single stage Compressors and
Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT
000 = None
040 = 4 kw
3
050 = 5 kw
3
SPPE
060 = 6 kw
3
SPPE
080 = 8 kw
3
SPPE
3
SPPE
SPPE
090 = 9 kw
100 = 10 kw
3
3
SPPE
SPPE
120 = 12 kw
3
SPPE
150 = 15 kw
SPPE3
BASIC
MODEL
VOLTAGE
PHASE / HZ
HVEA24ACA
208/230-1-60
20.6
30
41.5
45
46.6
50
51.9
60
72.7
80
HVEA30ACA
208/230-1-60
21.6
30
42.5
45
47.6
50
52.9
60
73.7
80
84.1
90
99.7
100
HVEA36ACA
208/230-1-60
26.4
40
47.3
50
52.4
60
57.7
60
78.5
80
88.9
90
104.5
110
HVEA42ACA
208/230-1-60
30.4
50
56.4
60
82.5
90
92.9
100
108.5
110
HVEA49ACA
208/230-1-60
34.4
50
60.4
70
86.5
90
96.9
100
112.5
120
HVEA60ACA
208/230-1-60
40.1
60
66.1
70
92.2
100
102.6
110
118.2
120
HVEA24ACC
208/230-3-60
14.2
20
32.2
35
41.3
45
50.3
60
59.3
60
HVEA30ACC
208/230-3-60
16.0
20
34.0
35
43.1
45
52.1
60
61.1
70
HVEA36ACC
208/230-3-60
18.6
25
36.6
40
45.7
50
54.7
60
63.7
70
HVEA42ACC
208/230-3-60
22.6
35
40.6
45
49.7
50
58.7
60
67.7
70
HVEA49ACC
208/230-3-60
24.2
35
42.2
45
51.3
60
60.3
70
69.3
70
HVEA60ACC
208/230-3-60
27.0
40
45.0
45
54.1
60
63.1
70
72.1
80
HVEA24ACD
460-3-60
7.3
15
16.3
20
20.8
25
25.3
30
29.8
30
HVEA30ACD
460-3-60
9.2
15
18.2
20
22.7
25
27.2
30
31.7
35
HVEA36ACD
460-3-60
10.1
15
19.1
20
23.6
25
28.1
30
32.6
35
HVEA42ACD
460-3-60
10.4
15
19.4
20
23.9
25
28.4
30
32.9
35
HVEA49ACD
460-3-60
11.3
15
20.3
25
24.8
25
29.3
30
33.8
35
HVEA60ACD
460-3-60
13.2
20
22.2
25
26.7
30
31.2
35
35.7
40
MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
2MFS = Maximum Fuse or HACR Breaker Size
3SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
1
Unit Load Amps HVEA Air Conditioners with with Single stage Compressors and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
BASIC
MODEL
NUMBER
VOLTAGE
PHASE / HZ
HVEA24ACA
HVEA30ACA
CURRENT
AMPS
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS)
TOTAL MAXIMUM HEATING AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON
AN ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
AC1
IBM2
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
208/230-1-60
17.4
2.8
16.7
20.8
25.0
33.3
41.7
19.5
23.6
27.8
36.1
44.5
208/230-1-60
18.4
2.8
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.5
23.6
27.8
36.1
44.5
52.8
65.3
HVEA36ACA
208/230-1-60
22.2
2.8
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.5
23.6
27.8
36.1
44.5
52.8
65.3
HVEA42ACA
208/230-1-60
25.4
2.8
20.8
41.7
50.0
62.5
23.6
44.5
52.8
65.3
HVEA49ACA
208/230-1-60
28.9
4.3
20.8
41.7
50.0
62.5
25.1
46.0
54.3
66.8
HVEA60ACA
208/230-1-60
33.5
4.3
20.8
41.7
50.0
62.5
25.1
46.0
54.3
66.8
HVEA24ACC
208/230-3-60
12.3
2.8
14.4
21.7
28.9
36.1
17.2
24.5
31.7
38.9
HVEA30ACC
208/230-3-60
13.9
2.8
14.4
21.7
28.9
36.1
17.2
24.5
31.7
38.9
HVEA36ACC
208/230-3-60
16.0
2.8
14.4
21.7
28.9
36.1
17.2
24.5
31.7
38.9
HVEA42ACC
208/230-3-60
19.2
2.8
14.4
21.7
28.9
36.1
17.2
24.5
31.7
38.9
HVEA49ACC
208/230-3-60
20.8
4.3
14.4
21.7
28.9
36.1
18.7
26.0
33.2
40.4
HVEA60ACC
208/230-3-60
23.0
4.3
14.4
21.7
28.9
36.1
18.7
26.0
33.2
40.4
HVEA24ACD
460-3-60
6.3
1.4
7.2
10.8
14.4
18.0
8.6
12.2
15.8
19.4
HVEA30ACD
460-3-60
7.9
1.4
7.2
10.8
14.4
18.0
8.6
12.2
15.8
19.4
HVEA36ACD
460-3-60
8.6
1.4
7.2
10.8
14.4
18.0
8.6
12.2
15.8
19.4
HVEA42ACD
460-3-60
8.9
1.4
7.2
10.8
14.4
18.0
8.6
12.2
15.8
19.4
HVEA49ACD
460-3-60
9.8
2.2
7.2
10.8
14.4
18.0
9.4
13.0
16.6
20.2
HVEA60ACD
460-3-60
11.3
2.2
7.2
10.8
14.4
18.0
9.4
13.0
16.6
20.2
2
AC = Air Conditioner Unit Amps
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models.
Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are maximum phase loads.
1
19 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
ComPac®HVESA Air Conditioners with 2-Stage Compressor
Certified Efficiency and Capacity Ratings at ANSI/AHRI Standard 390
for HVESA Air Conditioners with 2-Stage Compressors
Model Number
HVESA36
ACA
ACC
HVESA42
ACD
ACA
ACC
HVESA49
ACD
ACA
ACC
HVESA60
ACD
ACA
ACC
Cooling BTUH1 - 2nd Stage
35,000
39,000
47,000
56,000
10.50
EER2 - 2nd Stage
11.00
10.50
11.75
Integrated Part Load Value3
16.0
14.1
16.0
14.8
Rated Air Flow (CFM4)
1,300
1,400
1,750
1,900
ACD
2
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
EER=Energy Efficiency Ratio
4
Integrated Part Load Value is an integrated efficiency measure from 1st and 2nd stage capacity modulation.
CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect performance and air flow.
1
3
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb HVESA Air Conditioners with 2-Stage Compressors
Model Number
Total Capacity
HVESA36
ACA
ACC
HVESA42
ACD
ACA
ACC
HVESA49
ACD
ACA
ACC
HVESA60
ACD
ACA
ACC
35,000
39,000
47,000
0.70
0.71
0.79
0.77
Sensible Capacity
24,445
27,590
36,920
43,235
Rated Air Flow (CFM1)
1,300
1,400
1,750
1,900
Sensible Heat Ratio
ACD
56,000
CFM=Cubic Feet per Minute
Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
1
Stage 2 Cooling Performance (BTUH) at Various Outdoor Temperatures
Model Number
Outdoor Temperature
75ºF / 24ºC
80ºF / 26.5ºC
85ºF / 29ºC
90ºF / 32ºC
95ºF / 35ºC
HVESA36AC
40,600
39,200
37,800
36,400
35,000
HVESA42AC
45,240
43,680
42,120
40,560
39,000
HVESA49AC
54,520
52,640
50,760
48,880
47,000
HVESA60AC
64,960
62,720
60,480
58,240
56,000
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Stage 1 Cooling Performance (BTUH) at Various Outdoor Temperatures
Model Number
Outdoor Temperature
75ºF / 24ºC
80ºF / 26.5ºC
85ºF / 29ºC
90ºF / 32ºC
95ºF / 35ºC
HVESA36AC
30,856
29,792
28,728
27,664
26,600
HVESA42AC
34,336
33,152
31,968
30,784
29,600
HVESA49AC
44,080
42,560
41,040
39,520
38,000
HVESA60AC
51,040
49,280
47,520
45,760
44,000
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1820
Electrical Characteristics - Compressor, Fan & Blower Motors HVESA Air Conditioner with 2-Stage Compressor
BASIC
MODEL
Type
COMPRESSOR
OUTDOOR FAN MOTOR
INDOOR FAN MOTOR (ECM6)
VOLTS-HZ-PH
RLA1
LRA2
VOLTS-HZ-PH
RPM3
FLA4
HP5
VOLTS-HZ-PH
RPM3
FLA4
HP5
HVESA36ACA
208/230-60-1
16.6
82.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
HVESA42ACA
208/230-60-1
16.6
96.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
208/230-60-1
21.1
96.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVESA60ACA
208/230-60-1
25.6
118.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVESA36ACC
208/230-60-3
11.1
58.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
208/230-60-3
13.4
88.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
208/230-60-3
13.4
88.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVESA60ACC
208/230-60-3
17.6
123.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVESA36ACD
460-60-3
4.5
29.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
460-60-3
6.1
44.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1500
2.8
1/2
460-60-3
6.4
41.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
460-60-3
9.0
62.0
208/230-60-1
825
2.8
1/2
208/230-60-1
1500
4.3
3/4
HVESA49ACA
HVESA42ACC
HVESA49ACC
HVESA42ACD
HVESA49ACD
SCROLL
SCROLL
SCROLL
HVESA60ACD
RLA = Rated Load Amps 2LRA = Locked Rotor Amps 3RPM = Revolutions per Minute
The 460 volt units have a step down transformer for the 230 volt motors.
1
4
FLA = Full Load Amps
5
HP = Horsepower
6
ECM = Electronically Commutated Motor
Summary Electrical Ratings (Wire and Circuit Breaker Sizing) HVESA Air Conditioners with Two Stage Compressor and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT
BASIC
MODEL
000 = None
3
MCA
HVESA36ACA
208/230-1-60
HVESA42ACA
208/230-1-60
HVESA49ACA
HVESA60ACA
HVESA36ACC
050 = 5 kw
3
SPPE
VOLTAGE
PHASE / HZ
040 = 4 kw
060 = 6 kw
3
SPPE
SPPE
35
SPPE
MFS
MCA
28.8
35
34.1
28.8
45
50
33.5
60
41.0
SPPE
35
24.6
28.0
45
208/230-1-60
33.5
208/230-1-60
41.0
208/230-3-60
20.1
30
20.8
25
29.9
2
1
35
44.4
60
60
50
56.4
60
56.4
2
1
MFS
MFS
MCA1
MFS2
65.3
70
80.9
90
65.3
70
80.9
90
60
66.8
70
82.4
90
60
66.8
70
82.4
90
30
38.9
40
47.9
50
2
45
MCA
150 = 15 kw
SPPE3
SPPE
54.9
1
MCA
SPPE
54.9
2
MFS
3
MCA
1
MCA
120 = 12 kw
MFS
2
MFS
3
SPPE
24.6
1
100 = 10 kw
3
MCA
2
MCA
090 = 9 kw
3
MFS
1
MFS
080 = 8 kw
3
1
2
1
2
HVESA42ACC
208/230-3-60
23.2
35
23.2
35
29.9
35
38.9
40
47.9
50
HVESA49ACC
208/230-3-60
24.6
35
24.6
35
31.4
35
40.4
50
49.4
50
HVESA60ACC
208/230-3-60
27.7
40
27.7
40
31.4
40
40.4
50
49.4
50
HVESA36ACD
460-3-60
9.9
15
10.4
15
14.9
15
19.4
20
23.9
25
HVESA42ACD
460-3-60
10.6
15
10.6
15
14.9
15
19.4
20
23.9
25
HVESA49ACD
460-3-60
11.6
15
11.6
15
15.7
20
20.2
25
24.7
25
HVESA60ACD
460-3-60
12.6
15
12.6
20
15.7
20
20.2
25
24.7
25
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
2MFS = Maximum Fuse or HACR Breaker Size
3SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for estimating
conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
1
2
3
21 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Summary Electrical Ratings (Wire and Circuit Breaker Sizing) HVESA Air Conditioners with Two Stage Compressor,
Electric Reheat (“R”) and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer, Outside Air with Pressure Relief (“C”)
ELECTRIC HEAT
BASIC
MODEL
VOLTAGE
PHASE / HZ
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
150 = 15 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
HVESA36ACA
208/230-1-60
24.6
35
45.5
50
50.6
60
55.9
60
76.7
80
87.1
90
102.7
110
HVESA42ACA
208/230-1-60
28.0
45
54.0
60
80.1
90
90.5
100
106.1
110
HVESA49ACA
208/230-1-60
33.5
50
59.5
60
85.6
90
96.0
100
111.6
120
HVESA60ACA
208/230-1-60
41.0
60
67.0
70
93.1
100
103.5
110
119.1
120
HVESA36ACC
208/230-3-60
20.1
30
38.1
40
47.2
50
56.2
60
65.2
70
HVESA42ACC
208/230-3-60
23.2
35
41.2
45
50.3
60
59.3
60
68.3
70
HVESA49ACC
208/230-3-60
24.6
35
42.6
45
51.7
60
60.7
70
69.7
70
HVESA60ACC
208/230-3-60
27.7
40
45.7
50
54.8
60
63.8
70
72.8
80
HVESA36ACD
460-3-60
9.9
15
18.9
20
23.4
25
27.9
30
32.4
35
HVESA42ACD
460-3-60
10.6
15
19.6
20
24.1
25
28.6
30
33.1
35
HVESA49ACD
460-3-60
11.6
15
20.6
25
25.1
30
29.6
30
34.1
35
HVESA60ACD
460-3-60
12.6
15
21.6
25
26.1
30
30.6
35
35.1
40
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
2MFS = Maximum Fuse or HACR Breaker Size
3SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the ACA & ACC models. The 460 volts ACD models are calculated at 460 volts. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
1
Unit Load Amps HVESA Air Conditioners with Two Stage Compressor and Ventilation Configurations:
Manual Damper, up to 15% Outside Air (“N”)
Economizer,Outside Air with Pressure Relief (“C”)
BASIC
MODEL
NUMBER
VOLTAGE
PHASE / HZ
CURRENT
AMPS
AC1
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY
(AMPS)
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON
AN ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
IBM2 04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
HVESA36ACA
208/230-1-60
20.8
2.8
41.7
50.0
62.5
44.5
52.8
65.3
HVESA42ACA
208/230-1-60
23.5
2.8
20.8
41.7
50.0
62.5
23.6
44.5
52.8
65.3
HVESA49ACA
208/230-1-60
28.2
4.3
20.8
41.7
50.0
62.5
25.1
46.0
54.3
66.8
HVESA60ACA
208/230-1-60
34.2
4.3
20.8
41.7
50.0
62.5
25.1
46.0
54.3
66.8
HVESA36ACC
208/230-3-60
17.2
2.8
14.4
21.7
28.9
36.1
17.2
24.5
31.7
38.9
HVESA42ACC
208/230-3-60
19.7
2.8
14.4
21.7
28.9
36.1
17.2
24.5
31.7
38.9
HVESA49ACC
208/230-3-60
21.1
4.3
14.4
21.7
28.9
36.1
18.7
26.0
33.2
40.4
16.7
20.8
25.0
33.3
19.5
23.6
27.8
36.1
HVESA60ACC
208/230-3-60
23.6
4.3
14.4
21.7
28.9
36.1
18.7
26.0
33.2
40.4
HVESA36ACD
460-3-60
8.5
1.4
7.2
10.8
14.4
18.0
8.6
12.2
15.8
19.4
HVESA42ACD
460-3-60
9.0
1.4
7.2
10.8
14.4
18.0
8.6
12.2
15.8
19.4
HVESA49ACD
460-3-60
9.2
2.2
7.2
10.8
14.4
18.0
9.4
13.0
16.6
20.2
HVESA60ACD
460-3-60
10.0
2.2
7.2
10.8
14.4
18.0
9.4
13.0
16.6
20.2
2
AC = Air Conditioner Unit Amps
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the ACA & ACC models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the ACD models.
Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads. Loads are not equally balanced on each phase and values shown are
maximum phase loads.
1
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1822
INCHES
10” x 20” x 2”
RETURN AIR FILTER
185/84
LBS/KGS
AVPA12
Filter Size
COMPAC I
AVPA12
254 x 508 x 52
MILLIMETERS
91974
PART NUMBER
Shipping Weight (pounds/kilograms)
1
FILTERS PER UNIT
7
MERV RATING
Dimensional Data - AVPA12 ComPac® I Air Conditioners
23 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1824
INCHES
6¼” x 22¼” x 2”
AVPA12
194/88
LBS/KGS
RETURN AIR FILTER
Filter Size
COMPAC II
AVPA12
159 x 565 x 52
MILLIMETERS
80172
PART NUMBER
Shipping Weight (pounds/kilograms)
1
FILTERS PER UNIT
7
MERV RATING
Dimensional Data - AVPA12 ComPac® II Air Conditioners
INCHES
10” x 20” x 2”
AVHA12
185/84
LBS/KGS
RETURN AIR FILTER
Filter Size
COMPAC I
AVHA12
254 x 508 x 52
MILLIMETERS
91974
PART NUMBER
Shipping Weight (pounds/kilograms)
1
FILTERS PER UNIT
7
MERV RATING
Dimensional Data - AVHA12 ComPac® I Air Conditioners
25 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1826
350/159
375/170.5
COMPAC II
INCHES
25” x 16” x 2”
AVPA/AVHA20/24
RETURN AIR FILTER
Filter Size
LBS/KGS
AVPA/AVHA20/24
COMPAC I
635 x 406 x 51
MILLIMETERS
80137
PART NUMBER
Shipping Weight (pounds/kilograms)
1
FILTERS PER UNIT
7
MERV RATING
Dimensional Data - AVPA/AVHA20/24 ComPac® I & II Air Conditioners
AVPA/AVHA30/36 & HVEA24
RETURN AIR FILTER
30 x 16 x 2
INCHES
762 x 406 x 51
MILLIMETERS
445/202.5
COMPAC II
Filter Size
420/191
LBS/KGS
COMPAC I
AVPA/AVHA30/36 & HVEA24
Shipping Weight (pounds/kilograms)
80138
PART NUMBER
1
FILTERS PER UNIT
7
MERV RATING
Dimensional Data - AVPA/AVHA30/36, and HVEA24 ComPac® I & II Air Conditioners
27 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1828
RETURN AIR FILTER
AVPA/AVHA42/48/60,
HVEA30/36/42, &
HVESA30/36/42
36½ x 22 x 2
INCHES
927 x 559 x 51
MILLIMETERS
80162
PART NUMBER
1
FILTERS PER UNIT
565/257
COMPAC II
Filter Size
LBS/KGS
540/245.5
AVPA/AVHA42/48/60 and HVEA30/36/42, HVESA30/36/42
COMPAC I
Shipping Weight (pounds/kilograms)
8
MERV RATING
Dimensional Data - AVPA/AVHA42/48/60, and HVEA30/36/42, HVESA30/36/42
ComPac® I & II Air Conditioners
RETURN AIR FILTER
AVPA/AVHA72, HVEA49/60
& HVESA49/60
18 x 24 x 2
INCHES
457 x 610 x 51
MILLIMETERS
81257
PART NUMBER
680/309
705/320.5
COMPAC II
Filter Size
LBS/KGS
AVPA/AVHA72, and HVEA49/60, HVESA49/60
COMPAC I
Shipping Weight (pounds/kilograms)
2
FILTERS PER UNIT
7
MERV RATING
Dimensional Data - AVPA72, and HVEA49/60, HVESA49/60
ComPac® I & ComPac® II Air Conditioners
29 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18
Dimensional Data - AVPA60/AVHA60 with K/04315 Back Panel - ComPac I Only
For matching existing AVP36 wall opening with new AVPA60/AVHA60
For ComPac I Only. For ComPac II use transition curb in Options section.
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1830
Dimensional Data - AVPA60 with K/04317 Back Panel - ComPac I Only
For matching existing AVP24 wall opening with new AVPA60/AVHA60
For ComPac I Only. For ComPac II use transition curb in Options section.
NOTES:
UNIT IS SHIPPED FROM THE FACTORY WITH SUPPLY AND RETURN LINES CENTERED LEFT TO RIGHT
ON BACK PANEL. RETURN AND SUPPLY OPENINGS MAY BE SHIFTED 2-9/16” LEFT OR RIGHT TO
ALLOW FOR A BETTER FIT. A SLOTTED HOLE PATTERN IS PROVIDED TO ASSIST WITH CUT OUT OF
OPENINGS AND COVER PLATES ARE ALSO PROVIDED TO COVER EXCESSIVE HOLES LEFT IN BACK
PANEL AFTER MAKING CUT OUTS.
Please consult the Marvair® website at www.marvair.com for the latest product literature. Detailed dimensional data is available upon
request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website or by contacting
Marvair at 229-273-3636. As part of the Marvair continuous improvement program, specifications are subject to change without notice.
P.O. Box 400 • Cordele, GA 31010
156 Seedling Drive • Cordele, GA 31015
Ph: 229-273-3636 • Fax: 229-273-5154
Email: marvair@airxcel.com • Internet: www.marvair.com
Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.1831
31 Marvair ComPac AVPA/AVHA/HVEA/HVESA PDS 03/2017 Rev.18