Fan Coil Unit 50Hz

Fan Coil Unit 50Hz
MCAC-2012-16
Fan Coil Unit 50Hz
2012
Commercial Air Conditioner Business Units
Midea Air Conditioning and Refrigeration Sector
Add: West region of Midea commercial air conditioner department, Industry Avenue,
Beijiao, Shunde, Foshan, Guangdong, P.R. China Postal code:528311
Tel:+86-757-22394101 Fax: +86-757-26338003
http://www.midea.com http://www.mideaaircon.com
Corporate
Introduction
Midea Group
From its humble beginnings in 1968, Midea has developed into a
large corporation, covering HVAC, appliances, lighting, industrial
components, logistics, and real estate. Its 40 years of relentless
growth has brought its global turnover to $14 billion USD in 2009.
Consequently, Midea has created over 150,000 jobs both within
China and all over the world. In addition to providing affordable
goods to consumers worldwide, Midea is a responsible corporate
citizen, and has contributed to several social causes.
Midea believes in creating value through rapid response to
market demands, cost-efficient operations and consumer
satisfaction. As a result, Midea wields vast production capacities
to meet these demands, a fully integrated manufacturing
process, and a comprehensive range of affordable, high-quality
products to serve its global customers.
Today, Midea is a home appliance leader in China. The company
continues to actively globalize its operation by opening plants in
Vietnam, Belarus and Egypt. Additionally, Midea has several
forthcoming plants in order to offer enhanced products and
services closer to the market.
Midea CAC (MCAC)
As a key part of Midea Group, the Midea Central Air Conditioner
(CAC) Business Unit is a professional CAC products supplier and
commercial products solution expert. Since 1999 Midea central
air-conditioner contributes to the commercial product R&D and
technology innovation. By cooperating with the international
enterprises plus the independent R&D, Midea CAC achieves big
success in the commercial air-conditioner market and has
established thousands of sample projects all over the world.
Right now Midea CAC is one of the most professional CAC products
supplier as well as the professional project solution provider in
marketing, sales, project design and after service etc.
MCAC Chongqing factory with 14 product lines concentrates on the
water cooled centrifugal / screw/ scroll chillers, Air cooled screw/
scroll chillers, AHU/FCU etc.
MCAC Shunde factory with 31 product lines concentrates on the
VRF (DC inverter product/ Digital scroll product), split product, heat
pump water heater, AHU/FCU etc.
03
Fan Coil Unit
Fan Coil Unit
Product Line Up
2-pipe Fan Coil Units
Floor-standing and Ceiling & Floor (150-900CFM)
Cassette (300–1500CFM)
Floor-standing
4-way Cassette
4-way Cassette (compact)
Floor-standing (new appearance)
1-way Cassette
Duct (200-2200CFM)
Ceiling & Floor
Standard Static Pressure Duct
High Static Pressure Duct
Concealed Type
District Cooling FCU
4-pipe Fan Coil Units
Cassette (300-1500CFM)
Duct (200-1200CFM)
Wall-mounted (250-600CFM)
Wall-mounted
4-way Cassette
4-way Cassette (compact)
duct
04
05
R410A DC Inverter VR4 Plus
Fan Coil Unit
Introduction
Dedicated to creat a comfortable,queit and
high quality life for you
The Midea Chilled Water Fan Coil Unit is designed and manufactured on the base
of advanced technology, and utilize qualified galvanized iron as structure material.
Due to its supper-thin design, it has such advantages: beautiful outlook, space
saving, easy installation, etc. And the most obvious advantage is that it can
decrease the outlet air temperature difference as low as possible to make room
more comfortable, as well as don’t decrease cooling capacity output. For the large
air flow volume design, it can increase room ventilation frequency, supply more
flesh air, and balance room temperature distribution. Benefiting from adoption of
advanced material and technology, it can effectively reduce the running noise and
keep running smoothly. With the advantages above, it can be widely applied in
Contents
07 Nomenclature
08 Features and specifications
52 Fan performance
55 Controllers
58 Accessories
market, hospital, office building, hotel airport, etc..
61 Application of network control & BMS control
The Midea Chilled Water Fan Coil Unit contains ceiling exposed type, ceiling
62 Selection software
concealed type, wall-mounted type and floor-standing type. The air volume varies
from 150CFM~2,200CFM (255m3/h~3740m3/h). The standard power supply is
220-240V/1phase/50Hz.
06
07
Fan Coil Unit
Fan Coil Unit
Nomenclature
M K T3 H
2200 E G100
Static Pressure
G12: 12Pa G30: 30Pa G50: 50Pa
G70: 70Pa G100: 100Pa
Function Code
R: Remote Control
RA: Remote Control with EAH
E: With EAH
F: 4-pipe 4-way Cassette
S: 4-pipe 4-way Cassette(compact)
N: Without PCB
NF: 4-pipe FCU without PCB
Nominal Air Volume (CFM)
Static Pressure Type
H: High Static Pressure
Omit: 12Pa
Type Code*(Refer to below table)
Chilled Water Fan Coil Unit
Midea
*Meaning of the code
Type Code
Meanings
A
4-way cassette
C
1-way cassette
D
4-way cassette (compact)
F1
Exposed floor-standing (air return from side)
F2
Exposed floor-standing (air return from bottom)
F3
Concealed floor-standing
F4
Exposed floor-standing (air return from side) of new appearance
F5
Exposed floor-standing (air return from bottom) of new appearance
G
Wall-mounted
H1
Exposed ceiling & floor (air return from side)
H2
Exposed ceiling & floor (air return from bottom)
H3
Concealed ceiling & floor
T2
2-row duct
T3
3-row duct
T4
4-row duct
T5
4-pipe duct
T3H***G***
Q
High static pressure duct
District cooling (High temp. difference)
Features and specifications
08
09
Fan Coil Unit
Fan Coil Unit
Features and specifications
Optional accessories
Specifications
Features
4-way cassette
Model MKA-
600R(A)
750R(A)
850R(A)
950R(A)
1200R(A)
1500R
m3/h
1,000
1,250
1,400
1,600
2,000
2,550
CFM
590
740
820
940
1,180
1,500
m3/h
850
1,060
1,190
1,360
1,700
2,170
CFM
500
620
700
800
1,000
1,280
m3/h
720
900
1,010
1,150
1,440
1,840
CFM
420
530
590
680
850
1,080
Cooling Capacity
W
5,700
7,000
7,270
8,220
10,390
12,900
Heating Capacity
W
9,660
11,550
12,420
13,850
17,580
17,600
Electrical Auxiliary Heater (EAH)
W
2,100
2,100
2,850
2,850
2,850
/
Power Input
W
125
130
150
155
190
190
Noise(Hi/Med/Lo)
dB(A)
45/41/36
46/42/37
47/43/38
48/44/39
49/45/40
50/46/41
Water Flow
l/min
16.4
20
20.8
23.6
29.8
36.9
Water Pressure Drop
kPa
23.8
25.2
27
31.2
44
40
2
3
High
Air Volume
Med
Low
Features
Capacity range: 600CFM to 1500CFM.
Four color panels for choose: White, Gray, Blue, Black.
4-way air supply panel is standard, 360°air supply panel is optional.
Unique design of the centrifugal fan ensures extra-quiet operation and high efficiency.
Wireless remote control with LED display, wired control is optional.
Safety grill for safety maintenance.
Built-in drain water pump with 750mm pumping head.
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Optional extended drainage pan for protecting your ceiling better.
2
Row
2
2
2
Coil
Four-speed motor with one reserved for more choice.
Fresh air provision makes life healthier and more comfortable.
Current Panel
Fresh air provision
High water pump head
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
950×45×950
kg
6
mm
840×230×840 840×230×840 840×300×840 840×300×840 840×300×840 840×300×840
Panel
Net Weight
Net Dimension (W×H×D)
Indoor Unit
750mm
Fresh air
360°panel
10
Four color panels
Safety grill
Net Weight (with EAH)
Pipe
Connection
kg
25(27)
25(27)
30.5(33)
30.5(33)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ32
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with A type unit.
30.5(33)
35
11
Fan Coil Unit
Fan Coil Unit
4-way
Featurescassette (without PCB)
Optional accessories
Specifications
Model MKA-
750N
950N
1200N
1500N
m3/h
1,250
1,600
1,920
1,900
CFM
740
940
1,130
1,120
m3/h
1,060
1,360
1,630
1,620
CFM
620
800
960
950
m3/h
900
1,150
1,380
CFM
530
680
810
800
Cooling Capacity
W
6,100
6,650
9,900
11,400
Heating Capacity
W
8,100
8,600
16,500
19,000
Power Input
W
130
190
180
228
Noise(Hi/Med/Lo)
dB(A)
46/42/37
48/44/39
49/45/40
50/46/41
Various thermostats can be chosen by customer’s need.
Water Flow
l/min
17.5
19.1
28.4
32.7
Flexible wiring connection for non-PCB.
Water Pressure Drop
kPa
25.2
31.2
44
40
High
Air Volume
Med
Low
Features
Capacity range: 750CFM to 1500CFM.
Four color panels for choose: White, Gray, Blue, Black.
4-way air supply panel is standard, 360°air supply panel is optional.
Unique design of the centrifugal fan ensures extra-quiet operation and high efficiency.
Fan Motor
Type
Low noise 3-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Safety grill for safety maintenance.
Built-in drain water pump with 750mm pumping head.
12
Row
2
2
160
1,370
16.0kW
2
3
Coil
Optional extended drainage pan for protecting your ceiling better.
Fresh air provision makes life healthier and more comfortable.
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
950×45×950
kg
6
Panel
Net Weight
Net Dimension (W×H×D)
mm
840×230×840
840×300×840
840×300×840
840×300×840
kg
29
35
35
35
Indoor Unit
Net Weight
Pipe
Connection
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ32
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
13
Fan Coil Unit
Fan Coil Unit
4-way
cassette (compact)
Features
Optional accessories
Specifications
Model MKD-
300
400
500
m3/h
510
680
850
CFM
300
400
500
m3/h
440
580
730
CFM
260
340
430
m3/h
360
480
600
CFM
210
280
350
Cooling Capacity
W
3,000
3,700
4,500
Heating Capacity
W
4,000
5,100
6,000
Power Input
W
50
70
95
Noise(Hi/Med/Lo)
dB(A)
36/33/28
42/39/32
45/42/34
Water Flow
l/min
8.7
10.7
12.9
Water Pressure Drop
kPa
14
15
16
High
Air Volume
Med
Low
Features
Capacity range: 300CFM to 500CFM.
Compact design, simple installation and easy maintenance.
Round blow air supply enables uniform air flow distribution.
Comfortable horizontal air discharge reduces draughts and ceiling soiling.
Wireless remote control with LED display, wired control is optional.
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Coil
Built-in drain water pump with 500mm pumping head.
Optional extended drainage pan for protecting your ceiling better.
MPa
1.6
Net Dimension (W×H×D)
mm
647×50×647
kg
3
mm
575×261×575
kg
17.5
Water-inlet pipe
Inch
G3/4"
Water-outlet pipe
Inch
G3/4"
Drain pipe
mm
ODΦ25
Panel
Four-speed motor with one reserved for more choice .
Net Weight
Fresh air provision makes life healthier and more comfortable.
Round blow panel
Working Pressure
Compact body
High water pump head
Indoor Unit
Net Weight
575mm
575mm
500mm
Net Dimension (W×H×D)
Pipe
Connection
261mm
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
14
15
Fan Coil Unit
Fan Coil Unit
4-way
cassette (compact) (without PCB)
Features
Optional accessories
Specifications
Model MKD-
High
Air Volume
300N
400N
500N
m3/h
510
680
850
CFM
300
400
500
m3/h
440
580
730
CFM
260
340
430
m3/h
360
480
600
Med
Low
Features
Capacity range: 300CFM to 500CFM.
Various thermostats can be chosen by customer’s need.
Flexible wiring connection for non-PCB.
Compact design, simple installation and easy maintenance.
16.0kW
CFM
210
280
350
Cooling Capacity
W
2,930
3,700
4,500
Heating Capacity
W
4,000
5,100
6,000
Power Input
W
50
70
87
Noise(Hi/Med/Lo)
dB(A)
36/33/28
42/39/32
45/42/34
Water Flow
l/min
8.7
10.7
12.9
Water Pressure Drop
kPa
14
15
16
Fan Motor
Type
Low noise 3-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Round blow air supply enables uniform air flow distribution.
Comfortable horizontal air discharge reduces draughts and ceiling soiling.
Built-in drain water pump with 500mm pumping head.
Optional extended drainage pan for protecting your ceiling better.
Coil
Fresh air provision makes life healthier and more comfortable.
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
647×50×647
kg
3
mm
575×261×575
kg
17.5
Water-inlet pipe
Inch
G3/4"
Water-outlet pipe
Inch
G3/4"
Drain pipe
mm
ODΦ25
Panel
Net Weight
Net Dimension (W×H×D)
Indoor Unit
Net Weight
Pipe
Connection
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
160
16
17
Fan Coil Unit
Fan Coil Unit
Features
1-way
cassette
Optional accessories
Specifications
Model MKC-
300R(A)
400R(A)
m3/h
500
630
CFM
300
370
m3/h
450
560
CFM
270
330
m3/h
400
500
CFM
240
300
Cooling Capacity
W
3,040
3,790
Heating Capacity
W
5,130
6,410
Electrical Auxiliary Heater (EAH)
W
1,000
1,000
Power Input
W
60
60
Noise(Hi/Med/Lo)
dB(A)
38/35/33
40/37/35
Water Flow
l/min
8.7
10.9
Water Pressure Drop
kPa
10.1
14.5
High
Air Volume
Med
Low
Features
Capacity range: 300CFM to 400CFM.
Smoother air flow with less turbulence.
One direction air flow guarantees quick cooling, flexible installation position.
Space saving, only 235mm in height.
Built-in drain water pump with 750mm pumping head.
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
Coil
Four-speed motor with one reserved for more choice .
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
1,050×18×470
kg
4
mm
850×235×400
kg
22.5(23)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ18
Panel
Net Weight
Space saving
One direction air flow
High water pump head
Single direction airflow,flexibly
installed in various corners
235mm
Net Dimension (W×H×D)
Indoor Unit
Net Weight (with EAH)
750mm
UItra Thin
Pipe
Connection
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with A type unit.
18
19
Fan Coil Unit
Fan Coil Unit
Duct
Features
Optional accessories
Specifications
(2-row)
Model MKT2(H)-
200(E)
300(E)
400(E)
500(E)
600(E)
m3/h
340
510
680
850
1,020
CFM
200
300
400
500
600
m3/h
285
420
580
700
840
CFM
170
250
340
410
495
m3/h
210
320
420
520
620
CFM
125
190
250
305
365
Cooling Capacity
W
2,000
2,700
3,600
4,500
5,400
Heating Capacity
W
3,200
4,300
5,400
6,800
8,100
Electrical Auxiliary Heater (EAH)
W
500
650
1,000
1,000
1,500
Standard External Static Pressure
Pa
High
Air Volume
Med
Low
12/30
12Pa
W
37
42.5
63.5
78
98
30Pa
W
43.4
61.2
78.6
89.3
112
12Pa
dB(A)
36/30/25
38/32/26
40/33/27
42/35/29
43/35/30
30Pa
dB(A)
39/32/27
41/33/28
43/35/30
44/35/31
45/36/32
Water Flow
l/min
5.7
7.7
10.3
12.9
15.5
Flexible control, no standard controller, remote controller and wired controller are optional.
Water Pressure Drop
kPa
9.8
11
21
12.7
17.5
Pipe connection from left or right can be selected (in factory).
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Features
Power Input
Capacity range: 200CFM to 2000CFM.
Two external static pressure (12Pa and 30Pa) settings for added flexibility.
Space saving, only 242mm (200CFM to 1200CFM models) or 342mm (1500CFM to 2000CFM models) in height.
Air return from the rear or below for increased installation flexibility.
Standard extended drainage pan for protecting your ceiling better.
Four-speed motor with one reserved for more choice .
2-Row Duct
Noise(Hi/Med/Lo)
Coil
12Pa ESP
MKT2-200
MKT2-300
MKT2-400
MKT2-500
MKT2-600
MKT2-800
MKT2-1000
MKT2-1200
MKT2-1400
30Pa ESP
MKT2H-200
MKT2H-300
MKT2H-400
MKT2H-500
MKT2H-600
MKT2H-800
MKT2H-1000
MKT2H-1200
MKT2H-1400
12Pa ESP with EAH
MKT2-200E
MKT2-300E
MKT2-400E
MKT2-500E
MKT2-600E
MKT2-800E
MKT2-1000E
MKT2-1200E
MKT2-1400E
30Pa ESP with EAH
MKT2H-200E
MKT2H-300E
MKT2H-400E
MKT2H-500E
MKT2H-600E
MKT2H-800E
MKT2H-1000E
MKT2H-1200E
MKT2H-1400E
Indoor Unit
(without EAH)
Indoor Unit
(with EAH)
3-Row Duct
12Pa ESP
MKT3-200
MKT3-300
MKT3-400
MKT3-500
MKT3-600
MKT3-800
MKT3-1000
MKT3-1200
30Pa ESP
MKT3H-200
MKT3H-300
MKT3H-400
MKT3H-500
MKT3H-600
MKT3H-800
MKT3H-1000
MKT3H-1200
4-Row Duct
30Pa ESP
30Pa ESP with EAH
50Pa ESP
20
Pipe Connection
Working Pressure
MPa
Net Dimension (W×H×D)
mm
770×242×490
827×242×490
927×242×490
Net Weight (12Pa/30Pa)
kg
16(15.5)
18.5(18)
15(20.5)
Net Dimension (W×H×D)
mm
770×242×534
827×242×534
927×242×534
Net Weight (12Pa/30Pa)
kg
18(18)
19(19)
25(25)
1.6
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
Note:
MKT4H-200
MKT4H-300
MKT4H-400
MKT4H-500
MKT4H-600
MKT4H-200E
MKT4H-300E
MKT4H-400E
MKT4H-500E
MKT4H-600E
MKT4H-800
MKT4H-1000
MKT4-1200
MKT4H-800E MKT4H-1000E MKT4-1200E
MKT4-1500
MKT4-2000
MKT4-1500E
MKT4-2000E
MKT4H-1500G50
MKT4H-2000EG50
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with E type unit.
1,140×242×490 1,140×242×490
19(24)
24(24.5)
1,140×242×534 1,140×242×534
28(28)
28(28)
21
Fan Coil Unit
Fan Coil Unit
Specifications (3-row)
Specifications (2-row)
Model MKT2(H)-
High
m3/h
800(E)
1000(E)
1200(E)
1400(E)
1,360
1,700
2,040
2,380
Model MKT3(H)-
High
200
300
400
500
m3/h
340
510
680
850
CFM
200
300
400
500
m3/h
255
385
510
640
CFM
150
225
300
375
m3/h
170
255
340
425
CFM
100
150
200
250
CFM
800
1,000
1,200
1,400
m3/h
1,150
1,400
1,650
2,000
CFM
680
820
970
1,175
m3/h
840
1,000
1,250
1,480
CFM
495
590
735
870
Cooling Capacity
W
7,200
9,000
11,000
13,000
Heating Capacity
W
11,000
13,500
16,500
19,500
Cooling Capacity
W
2,100
3,300
4,200
4,800
Electrical Auxiliary Heater (EAH)
W
2,000
2,000
3,000
3,000
Heating Capacity
W
3,500
5,300
6,800
7,900
Standard External Static Pressure
Pa
Standard External Static Pressure
Pa
Air Volume
Med
Low
12Pa
Power Input
W
12/30
143
206
178
W
156
197
234
262
12Pa
dB(A)
43/34/30
46/36/32
47/37/33
48/38/34
dB(A)
46/37/33
48/38/35
50/40/37
52/42/39
Water Flow
l/min
20.6
25.8
31.5
37.3
Water Pressure Drop
kPa
13.6
20
35
40
30Pa
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Coil
Indoor Unit
(without EAH)
Indoor Unit
(with EAH)
Pipe Connection
MPa
Net Dimension (W×H×D)
mm
1,440×242×490
1,546×242×490
1,835×242×490
1,835×242×490
Net Weight (12Pa/30Pa)
kg
27(32)
29(36)
33(33)
34(34)
Net Dimension (W×H×D)
Net Weight (12Pa/30Pa)
mm
1,440×242×534
1,546×242×534
1,835×242×534
1,835×242×534
kg
34(32.4)
37(37)
44(44)
44(44)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
12/30
12Pa
W
34
46
65
68
30Pa
W
40
60
80
110
12Pa
dB(A)
36/33/27
38/32/28
40/34/30
42/36/31
30Pa
dB(A)
39/34/28
40/35/29
43/35/28
45/38/30
Water Flow
l/min
6
9.5
12
13.8
Water Pressure Drop
kPa
9.8
11
20
12.7
Power Input
Noise(Hi/Med/Lo)
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
1.6
Working Pressure
Med
Low
240
30Pa
Noise(Hi/Med/Lo)
Air Volume
Coil
Indoor Unit
Pipe Connection
1.6
Working Pressure
MPa
Net Dimension (W×H×D)
mm
757×242×534
812×242×534
912×242×534
912×242×534
Net Weight (12Pa/30Pa)
kg
18(18)
19(19)
21.2(25)
21.5(25)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
Note:
Note:
1. The data is the performance in high speed with relevant external static pressure.
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with E type unit.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
22
23
Fan Coil Unit
Fan Coil Unit
Specifications (3-row)
Specifications (4-row)
Model MKT3(H)-
High
Air Volume
Med
m3/h
600
800
1000
1200
1,020
1,360
1,700
2,040
CFM
600
800
1,000
1,200
m3/h
765
1,020
1,275
1,530
CFM
450
600
750
900
m3/h
510
680
850
1,020
CFM
300
400
500
600
Cooling Capacity
W
5,800
7,900
9,100
11,500
Heating Capacity
W
10,000
13,600
16,000
20,300
12/30
Pa
12Pa
W
30Pa
100
140
170
220
W
110
155
210
230
12Pa
dB(A)
44/39/32
45/41/32
46/40/32
47/41/32
30Pa
dB(A)
46/39/30
48/40/31
49/41/32
50/42/32
Water Flow
l/min
16.6
22.7
26.1
33
Water Pressure Drop
kPa
17.5
14.4
20.5
35
Power Input
Noise(Hi/Med/Lo)
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
Coil
Pipe Connection
200(E)
300(E)
400(E)
500(E)
600(E)
800(E)
m3/h
340
510
680
850
1,020
1,360
CFM
200
300
400
500
600
800
m3/h
255
385
510
640
765
1,020
CFM
150
225
300
375
450
600
m3/h
170
255
340
425
510
680
CFM
100
150
200
250
300
400
Cooling Capacity
W
2,200
3,200
4,000
4,800
6,000
7,300
Heating Capacity
W
4,100
5,800
7,100
8,000
10,500
12,500
Electrical Auxiliary Heater (EAH)
W
500
650
1,000
1,000
1,500
2,000
Standard External Static Pressure
Pa
30
30
30
30
30
30
Power Input
W
47
65
85
90
110
180
Noise(Hi/Med/Lo)
dB(A)
40/35/29
42/36/30
43/36/31
48/38/33
48/39/33
50/40/34
Water Flow
l/min
6.3
9.2
11.5
13.8
17.2
21
Water Pressure Drop
kPa
3.3
6.3
13
13
24.5
14.5
Air Volume
Med
Low
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
4
Coil
1.6
Working Pressure
MPa
Net Dimension (W×H×D)
mm
1,125×242×534
1,425×242×534
1,530×242×534
1,820×242×534
Net Weight (12Pa/30Pa)
kg
25(28)
34(34)
37(37)
44(44)
Indoor Unit
Model MKT4(H)-
High
Low
Standard External Static Pressure
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
Working Pressure
MPa
Net Dimension (W×H×D)
mm
Net Weight (With EAH)
kg
Indoor Unit
Pipe Connection
1.6
757×242×534 812×242×534 912×242×534 912×242×534 1,125×242×534 1,425×242×534
19(20)
21(22)
24(25)
24(25)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
Note:
Note:
1. The data is the performance in high speed with relevant external static pressure.
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
24
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with E type unit.
30(32)
40(41)
25
Fan Coil Unit
Fan Coil Unit
26
New 2-row and 3-row duct
Specifications (4-row)
Model MKT4(H)-
1000(E)
1200(E)
1500(E)
1500G50
2000(E)
2000G50
m3/h
1,700
2,040
2,550
2,550
3,400
3,400
CFM
1,000
1,200
1,500
1,500
2,000
2,000
m3/h
1,275
1,530
2,100
2,100
2,550
2,550
CFM
750
900
1,240
1,240
1,500
1,500
m3/h
850
1,020
1,300
1,300
1,700
1,700
CFM
500
600
760
760
1,000
1,000
Cooling Capacity
W
9,200
10,800
13,500
13,500
18,000
18,000
Heating Capacity
W
15,000
16,000
17,500
17,500
23,400
23,400
Electrical Auxiliary Heater (EAH)
W
2,000
2,400
2,400
/
3,000
/
Standard External Static Pressure
Pa
30
30
30
50
30
50
Power Input
W
190
175
236
474
360
665
Noise(Hi/Med/Lo)
dB(A)
50/39/33
51/40/34
51/39/33
55/52/48
53/41/35
59/56/50
Water Flow
l/min
26.4
31
38.7
38.7
51.6
51.6
Water Pressure Drop
kPa
15
30
39
39
60
60
High
Air Volume
Med
Low
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
4
Features
Capacity range: 200~1400CFM.
Wider external static pressure supplying. Three external static pressure (12Pa/30Pa/50Pa) settings for added flexibility.
A patent design is able to prevent abnormal noise caused by blowing flins.
Higher efficient heat exchange for complete contranatant flow type.
Air inlet and air outlet both with flange.
Filter can be extracted in upward/downward/leftward/rightward way.
Accessary hook for extracting conveniently.
Standard extended drainage pan for protecting your celling better.
Filter be extracted in upward/downward/leftward/rightward way
Coil
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
1,530×242×534 1,369×342×612 1,369×342×612 1,369×342×612 1,500×342×612 1,500×342×612
Net Weight (With EAH)
kg
Indoor Unit
Pipe Connection
41(42)
45.5(49)
46
46(49)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
57(58)
53.7
New 2-Row Duct
12Pa ESP
MKT2-200G12
MKT2-300G12
MKT2-400G12
MKT2-500G12
MKT2-600G12
MKT2-800G12
MKT2-1000G12
MKT2-1200G12
MKT2-1400G12
30Pa ESP
MKT2-200G30
MKT2-300G30
MKT2-400G30
MKT2-500G30
MKT2-600G30
MKT2-800G30
MKT2-1000G30
MKT2-1200G30
MKT2-1400G30
Note:
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with E type unit.
New 3-Row Duct
12Pa ESP
MKT3-200G12
MKT3-300G12
MKT3-400G12
MKT3-500G12
MKT3-600G12
MKT3-800G12
MKT3-1000G12
MKT3-1200G12
MKT3-1400G12
30Pa ESP
MKT3-200G30
MKT3-300G30
MKT3-400G30
MKT3-500G30
MKT3-600G30
MKT3-800G30
MKT3-1000G30
MKT3-1200G30
MKT3-1400G30
50Pa ESP
MKT3-200G50
MKT3-300G50
MKT3-400G50
MKT3-500G50
MKT3-600G50
MKT3-800G50
MKT3-1000G50
MKT3-1200G50
MKT3-1400G50
27
Fan Coil Unit
Fan Coil Unit
Specifications
Specifications
200G12
200G30
300G12
300G30
400G12
400G30
500G12
500G30
600G12
600G30
m3/h
340
510
680
850
1020
CFM
200
300
400
500
600
m3/h
255
385
510
640
765
CFM
150
225
300
375
450
m3/h
170
255
340
425
510
CFM
100
150
200
250
300
Cooling Capacity
W
1,810
2,610
3,210
3,460
4,530
Heating Capacity
W
2,680
3,770
4,660
5,080
6,770
Standard External Static Pressure
Pa
Model MKT2-
High
Air Volume
Med
Low
12/30
12
W
31
50
60
80
97
30
W
45
45
67
108
110
12
dB(A)
36/34/29
38/33/29
38/35/31
39/36/32
40/36/33
dB(A)
41/37/31
41/37/32
42/39/33
45/41/34
46/41/35
Water Flow
l/min
5.2
7.5
9.2
9.9
13.0
Water Pressure Drop
kPa
5
11
19
22
14
Power Input
Noise(Hi/Med/Lo)
30
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Coil
Indoor Unit
Working Pressure
Net Dimension (W×H×D) mm
Net Weight(12Pa/30Pa)
Pipe Connection
kg
757×241×526
812×241×526
912×241×526
912×241×526
1135×241×526
18/17
21/19
23/23
23/23
27/27
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
1000G12
1000G30
1200G12
1200G30
1400G12
1400G30
m3/h
1360
1700
2040
2380
CFM
800
1000
1200
1400
m3/h
1020
1275
1530
1785
CFM
600
750
900
1050
m3/h
680
850
1020
1190
CFM
400
500
600
700
Cooling Capacity
W
6,250
7,510
9,590
10,320
Heating Capacity
W
9,080
10,880
13,420
14,280
Standard External Static Pressure
Pa
High
Air Volume
Med
Low
12/30
12
W
140
172
205
216
30
W
130
171
212
249
12
dB(A)
42/37/33
44/39/34
46/40/35
48/42/37
30
dB(A)
46/41/36
47/43/37
48/44/38
49/44/39
Water Flow
l/min
17.9
21.5
27.5
29.6
Water Pressure Drop
kPa
14
22
39
46
Power Input
Noise(Hi/Med/Lo)
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Coil
1.6
MPa
800G12
800G30
Model MKT2-
Indoor Unit
Working Pressure
Net Dimension (W×H×D) mm
Net Weight(12Pa/30Pa)
Pipe Connection
1.6
MPa
kg
1435×241×526
1540×241×526
1830×241×526
1992×241×526
36/36
41.5/38
47.5/44.2
49.5/49.5
Water-inlet pipe
Inch
RC3/4
Water-outlet pipe
Inch
RC3/4
Drain pipe
mm
ODΦ24
Note:
Note:
1. The data is the performance in high speed with relevant external static pressure.
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
28
29
Fan Coil Unit
Fan Coil Unit
Specifications
Specifications
200G12
200G30
200G50
300G12
300G30
300G50
400G12
400G30
400G50
500G12
500G30
500G50
600G12
600G30
600G50
m3/h
340
510
680
850
1,020
CFM
200
300
400
500
600
m3/h
255
385
510
640
765
CFM
150
225
300
375
450
m3/h
170
255
340
425
510
CFM
100
150
200
250
300
Cooling Capacity
W
2,200
3,100
4,000
4,600
5,800
Heating Capacity
W
3,500
5,300
6,800
7,900
9,800
Standard External Static Pressure
Pa
Model MKT3-
High
Air Volume
Med
Low
12/30/50
12
W
33
53
66
87
100
30
W
49
64
75
93
114
50
W
51
76
89
111
128
12
dB(A)
35/32/26
36/33/27
37/34/28
40/36/30
42/38/32
30
dB(A)
41/37/31
42/38/32
43/39/33
44/40/34
45/41/35
50
dB(A)
45/40/35
47/42/37
48/43/38
49/44/39
49/44/40
Water Flow
l/min
6.3
8.9
11.5
13.2
16.7
Water Pressure Drop
kPa
14
26
18
24
36
Power Input
Noise(Hi/Med/Lo)
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
Coil
Indoor Unit
Working Pressure
1200G12
1200G30
1200G50
1400G12
1400G30
1400G50
m3/h
1,360
1,700
2,040
2,380
CFM
800
1,000
1,200
1,400
m3/h
1,020
1,275
1,530
1,785
CFM
600
750
900
1,050
m3/h
680
850
1,020
1,190
CFM
400
500
600
700
Cooling Capacity
W
8,200
9,000
11,000
12,500
Heating Capacity
W
13,600
16,000
20,100
21,000
Standard External Static Pressure
Pa
High
Air Volume
757×241×526
812×241×526
912×241×526
Low
kg
17.5
21
23
Water-inlet pipe
Inch
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
W
145
180
210
222
30
W
154
180
220
278
50
W
174
225
271
335
12
dB(A)
43/39/33
45/41/35
46/42/36
48/44/38
30
dB(A)
46/42/36
47/43/37
48/44/38
49/45/39
50
dB(A)
49/45/40
50/45/40
51/46/41
51/46/42
Water Flow
l/min
23.5
25.8
31.6
35.9
Water Pressure Drop
kPa
39
32
39
45
Power Input
Noise(Hi/Med/Lo)
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
Indoor Unit
Pipe Connection
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
1.6
Working Pressure
MPa
Net Dimension (W×H×D)
mm
1,435x241x526
1,540x241x526
1,830x241x526
1,992x241x526
kg
36
41.5
47.5
49.5
27
RC3/4"
Note:
3. Noise level is tested in semi-anechoic room.
23
12/30/50
12
Coil
912×241×526 1,135×241×526
Med
Net Weight
Net Weight
Pipe Connection
1000G12
1000G30
1000G50
1.6
MPa
Net Dimension (W×H×D) mm
800G12
800G30
800G50
Model MKT3-
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
Note:
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
30
31
Fan Coil Unit
Fan Coil Unit
High
static pressure duct
Features
Specifications
Model MKT3H-
800(E)G70
1000(E)G70
1200(E)G70
m3/h
1,360
1,700
2,040
2,380
CFM
800
1,000
1,200
1,400
m3/h
1,220
1,530
1,880
2,120
CFM
720
900
1,105
1,250
m3/h
1,090
1,380
1,610
1,860
CFM
640
810
950
1,095
Cooling Capacity
W
6,600
8,800
10,000
12,000
Heating Capacity
W
9,700
13,200
15,000
17,900
Electrical Auxiliary Heater (EAH)
W
5,000
5,000
5,000
5,000
High air volume, high static pressure, high capacity.
Standard External Static Pressure
Pa
70
70
70
70
High-pressure centrifugal fans.
Power Input
W
350
350
350
350
Noise(Hi/Med/Lo)
dB(A)
60/56/50
61/57/51
61/57/51
62/59/52
Water Flow
l/min
18.5
25.2
28.5
34.2
Standard extended drainage pan for protecting your ceiling better.
Water Pressure Drop
kPa
8
24
24
36
Four-speed motor with one reserved for more choice .
Fan Motor
Type
Low noise 4-speed fan motor
Pipe connection from left or right can be selected (in factory).
Fan
Type
Centrifugal, forward-curved Blades
High
Air Volume
1400(E)G70
Med
Low
Features
Easy to clean and change the air filter.
Auxiliary electrical heater is optional.
Flexible control, no standard controller, remote controller and wired controller are optional.
High water pump head
2
Row
3
3
4
Coil
Indoor Unit
Working Pressure
MPa
1.6
Net Dimension (with EAH) (W×H×D)
mm
946×400×816 (946×400×876)
Net Weight (with EAH)
Pipe Connection
kg
50(53)
52(55)
52(55)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ32
Note:
1. The data is the performance in high speed with 70Pa external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with E type unit.
54(57)
32
33
Fan Coil Unit
Fan Coil Unit
Wall-mounted
Features
Optional accessories
Specifications
Model MKT3H-
1600(E)G100
1800(E)G100
2200(E)G100
m3/h
2,720
3,060
3,740
CFM
1,600
1,800
2,200
m3/h
2,450
2,750
3,360
CFM
1,440
1,620
1,980
m3/h
2,170
2,450
2,990
CFM
1,280
1,440
1,760
Cooling Capacity
W
14,100
15,800
19,900
Heating Capacity
W
21,200
23,800
30,000
Electrical Auxiliary Heater (EAH)
W
9,500
9,500
9,500
Standard External Static Pressure
Pa
100
100
100
Power Input
W
550
800
950
Noise(Hi/Med/Lo)
dB(A)
62/58/53
63/60/55
66/63/58
Water Flow
l/min
40.4
45.4
57.2
Water Pressure Drop
kPa
52
90
130
High
Air Volume
Med
Low
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
Features
Different color of panels for choose.
Cross flow fan creates quiet and comfortable environment.
Wireless remote control with LED display, wired control is optional.
Multi-connection outlet pipe method: left\right\rear, satisfy the need of different rooms.
Built-in the 3-way electromagnetic valve.
Easy maintenance has been realized as the front panel can be removed for easy access.
Four-speed motor with one reserved for more choice.
Coil
Indoor Unit
Working Pressure
MPa
1.6
Net Dimension (with EAH) (W×H×D)
mm
1,290×400×809 (1,290×400×874)
kg
76(82)
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ32
Net Weight (with EAH)
Pipe Connection
Note:
1. The data is the performance in high speed with 100Pa external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room.
4. The EAH capacity only available with E type unit.
Easy maintenance
Multi-connection outlet pipe
Compact body
High water pump head
34
35
Fan Coil Unit
Fan Coil Unit
Floor-standing and Ceiling & Floor
Optional accessories
Specifications
Model MKG-
250
300
400
500
600
m3/h
425
510
680
850
1,020
CFM
250
300
400
500
600
m3/h
360
430
580
720
870
CFM
210
250
340
420
510
m3/h
320
380
510
640
770
CFM
190
220
300
380
450
Cooling Capacity
W
2,200
2,640
3,080
4,070
4,450
Heating Capacity
W
3,020
3,690
4,340
5,690
6,300
Power Input
W
28
40
44
50
60
Noise(Hi/Med/Lo)
dB(A)
30/24/20
35/29/24
37/31/26
39/33/28
40/34/29
Water Flow
l/min
6.3
7.6
8.8
11.7
12.8
Water Pressure Drop
kPa
12
18
22
26
29
High
Air Volume
Features
MKF1(2)
MKF4(5) (New appearance)
MKH1(2)
MKF3/MKH3 (Concealed type)
Med
Low
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Cross flow fan
Row
2
Flexible for installation, designed for horizontal/vertical, concealed/cabinet application.
Ultra-thin body, streamlined appearance.
Air return from the side or below for increased choice flexibility.
Coil
Working Pressure
MPa
Net Dimension (with EAH) (W×H×D)
mm
915×210×290
915×210×290
kg
12
12
1.6
3-way electromagnetic valve can be built inside.
915×210×290 1,070×210×316 1,070×210×316
Indoor Unit
Net Weight (with EAH)
Pipe Connection
12
Water-inlet pipe
Inch
G3/4"
Water-outlet pipe
Inch
G3/4"
Drain pipe
mm
ODΦ20
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room
Features
15
15
Movable louver makes wide angle air flow.
Pipe connection from left or right can be selected (in factory).
Alternative air return type
Movable louver
36
37
Fan Coil Unit
Fan Coil Unit
Optional accessories
Specifications
Optional accessories
Specifications
Model MKF1(2,3,4,5)-
High
Air Volume
150
250
300
400
450
m3/h
255
425
510
680
765
CFM
150
250
300
400
450
m3/h
215
360
430
580
650
Med
CFM
125
210
250
340
380
m3/h
190
320
380
510
570
Model MKF1(2,3,4,5)-
High
Air Volume
Low
500
600
800
900
m3/h
850
1,020
1,360
1,530
CFM
500
600
800
900
m3/h
720
870
1,160
1,300
CFM
420
510
680
760
m3/h
640
765
1,020
1,150
CFM
375
450
600
675
Med
Low
CFM
110
190
220
300
335
Cooling Capacity
W
1,150
1,870
2,530
3,270
3,970
Cooling Capacity
W
4,850
5,640
6,520
7,850
Heating Capacity
W
2,540
4,170
5,640
7,220
8,850
Heating Capacity
W
10,280
12,240
15,350
18,200
Power Input
W
27
29
40
46
39
Power Input
W
49
63
88
137
Noise(Hi/Med/Lo)
dB(A)
32/29/26
35/32/30
37/34/32
39/36/34
41/38/36
Noise(Hi/Med/Lo)
dB(A)
43/40/38
44/41/39
46/43/40
48/45/42
Water Flow
l/min
3.3
5.4
7.3
9.4
11.4
Water Flow
l/min
13.9
16.2
18.7
22.5
Water Pressure Drop
kPa
18.3
10.1
14.2
9.5
10.3
Water Pressure Drop
kPa
24.6
11.4
9.5
12.1
Fan Motor
Type
Low noise 3-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Working Pressure
MPa
Coil
Indoor Unit
MKF1(2)
Indoor Unit
MKF3
Indoor Unit
MKF4(5)
Pipe Connection
Net Dimension (W×H×D)
Net Weight
Net Dimension (W×H×D)
Net Weight
Net Dimension (W×H×D)
Net Weight
Type
Low noise 3-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
1.6
3
Row
Fan Motor
2
3
Working Pressure
2
3
800×626×220 1,000×626×220 1,000×626×220 1,200×626×220
mm
800×626×220
kg
22.8(22.5)
22.6(24.5)
23.4(29)
26(26)
32.5(32.5)
mm
550×545×212
550×545×212
750×545×212
750×545×212
950×545×212
kg
17
17
20
20
25
mm
800×572×225
kg
22.5(22.5)
800×572×225 1,000×572×225 1,000×572×225 1,200×572×225
26(26)
22.5(22.5)
Water-inlet pipe
Inch
G3/4"
Water-outlet pipe
Inch
G3/4"
Drain pipe
mm
ODΦ16
26(26)
32.5(32.5)
MPa
Coil
3
2
2
2
mm
1,200×626×220
1,500×626×220
1,500×626×220
1,500×626×220
kg
32.5(31.5)
38(39)
38(39)
39(39)
mm
950×545×212
1,250×545×212
1,250×545×212
1,250×545×212
kg
25
32
32
32
mm
1,200×572×225
1,500×572×225
1,500×572×225
1,500×572×225
kg
32.5(35)
39(36.6)
39(39)
39(39)
Row
Indoor Unit
MKF1(2)
Indoor Unit
MKF3
Indoor Unit
MKF4(5)
Pipe Connection
Net Dimension (W×H×D)
Net Weight
Net Dimension (W×H×D)
Net Weight
Net Dimension (W×H×D)
Net Weight
1.6
Water-inlet pipe
Inch
G3/4"
Water-outlet pipe
Inch
G3/4"
Drain pipe
mm
ODΦ16
Note:
Note:
1. The data is the performance in high speed.
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room
38
39
Fan Coil Unit
Fan Coil Unit
Optional accessories
Specifications
Optional accessories
Specifications
Model MKH1(2,3)m3/h
150
250
300
400
450
255
425
510
680
765
High
Air Volume
CFM
150
250
300
400
450
m3/h
215
360
430
580
650
Med
Model MKH1(2,3)-
500
600
800
900
m3/h
850
1,020
1,360
1,530
CFM
500
600
800
900
m3/h
720
870
1,160
1,300
High
Air Volume
Med
CFM
125
210
250
340
380
CFM
420
510
680
760
m3/h
190
320
380
510
570
m3/h
640
765
1,020
1,150
CFM
375
450
600
675
Low
Low
CFM
110
190
220
300
335
Cooling Capacity
W
1,150
1,870
2,530
3,270
3,970
Cooling Capacity
W
4,850
5,640
6,520
7,850
Heating Capacity
W
1,520
2,530
3,490
4,580
5,640
Heating Capacity
W
6,980
8,230
9,580
11,690
Power Input
W
27
45
44
46
40
Power Input
W
49
77
118
137
Noise(Hi/Med/Lo)
dB(A)
32/29/26
35/32/30
37/34/32
39/36/34
41/38/36
Noise(Hi/Med/Lo)
dB(A)
43/40/38
44/41/39
46/43/40
48/45/42
Water Flow
l/min
3.3
5.4
7.3
9.4
11.4
Water Flow
l/min
13.9
16.2
18.7
22.5
Water Pressure Drop
kPa
18.3
10.1
14.2
9.5
10.3
Water Pressure Drop
kPa
24.6
11.4
9.5
12.1
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Coil
Working Pressure
Indoor Unit
MKH1(2)
Indoor Unit
MKH3
Pipe Connection
Net Dimension (W×H×D)
Net Weight
Net Dimension (W×H×D)
Net Weight
kg
mm
kg
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Coil
3
mm
Type
1.6
MPa
Row
Fan Motor
3
800×626×220 800×626×220
22.5
2
3
1,000×626×220 1,000×626×220 1,200×626×220
22.5
550×545×212 550×545×212
17
2
26
26
32.5
750×545×212
750×545×212
950×545×212
20
20
25
17
Water-inlet pipe
Inch
G3/4"
Water-outlet pipe
Inch
G3/4"
Drain pipe
mm
ODΦ16
Working Pressure
3
2
2
2
mm
1,200×626×220
1,500×626×220
1,500×626×220
1,500×626×220
kg
32.5
39
39
39
mm
950×545×212
1,250×545×212
1,250×545×212
1,250×545×212
kg
25
32
32
32
Row
Indoor Unit
MKH1(2)
Indoor Unit
MKH3
Pipe Connection
Net Dimension (W×H×D)
Net Weight
Net Dimension (W×H×D)
Net Weight
1.6
MPa
Water-inlet pipe
Inch
G3/4"
Water-outlet pipe
Inch
G3/4"
Drain pipe
mm
ODΦ16
Note:
Note:
1. The data is the performance in high speed.
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room
Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise level is tested in semi-anechoic room
40
41
Fan Coil Unit
Fan Coil Unit
42
District
Features cooling FCU
Specifications
Model MKQT3H-
200
300
400
500
600
m3/h
340
510
680
850
1,020
CFM
200
300
400
500
600
m3/h
290
430
580
720
870
CFM
170
250
340
420
510
m3/h
200
310
410
510
610
CFM
120
180
240
300
360
Cooling Capacity (1*/2*)
W
2,000/2,480
2,900/3,600
3,200/3,970
3,700/4,590
5,100/6,320
Sensible Cooling Capacity (1*/2*)
W
1,600/1,640
2,320/2,370
2,560/2,620
2,960/3,030
4,080/4,170
Standard External Static Pressure
Pa
30
30
30
30
30
Power Input
W
45
62
72
92
112
Noise(Hi/Med/Lo)
dB(A)
36/33/27
38/32/28
40/34/30
42/36/31
44/39/32
Water Flow (1*/2*)
l/min
3.2/6.4
4.7/9.2
5/10.2
5.9/11.8
8.2/16.2
Standard extended drainage pan for protecting your ceiling better.
Water Pressure Drop (1*/2*)
kPa
3.9/8
5.6/11.2
6.2/12.5
7.2/14.6
9.9/20.2
Air return from the rear or below for increased installation flexibility.
Fan Motor
Type
Low noise 4-speed fan motor
Pipe connection from left or right can be selected (in factory).
Fan
Type
Centrifugal, forward-curved Blades
Row
3
High
Air Volume
Med
Low
Features
Capacity range: 200CFM to 1200CFM.
Space saving, only 242mm in height.
30Pa external static pressure for standard.
Need less water, little power of water pumps, save power cost for the high temp difference.
Four-Speed motor with one reserved for more choice.
Coil
1.6
Working Pressure
MPa
Net Dimension (W×H×D)
mm
757×242×534
812×242×534
912×242×534
912×242×534
1,125×242×534
kg
17
19.5
21.5
21.5
25
Indoor Unit
Net Weight
Pipe
Connection
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
Note:
1. The data is the performance in high speed with 30Pa external static pressure.
2. Cooling Conditions: 1*-Entering Water 7.2°C, Temperature Rise 8.4°C, Entering Air Temperature 26.7°C DB, 19.4°C WB.
2*-Entering Water 7.2°C, Temperature Rise 5.6°C, Entering Air Temperature 26.7°C DB, 19.4°C WB.
3. Noise level is tested in semi-anechoic room.
43
Fan Coil Unit
Fan Coil Unit
44
4-pipe FCU
Features
Specifications
Model MKQT3H-
800
1000
1200
1500
2000
m3/h
1,360
1,700
2,040
2,550
3,400
CFM
800
1,000
1,200
1,500
2,000
m3/h
1160
1,440
1,730
2,170
2,890
CFM
680
850
1,020
1,280
1,700
m3/h
820
1020
1,220
1,530
2,040
CFM
480
600
720
900
1,200
Cooling Capacity (1*/2*)
W
7,100/8,800
7,500/9,300
9,600/11,900
11,250/13,950
15,000/18,600
Sensible Cooling Capacity (1*/2*)
W
5,680/5,810
6,000/6,140
7,680/7,860
9,000/9,210
12,000/12,280
Standard External Static Pressure
Pa
30
30
30
30
30
Power Input
W
145
170
220
280
350
Noise(Hi/Med/Lo)
dB(A)
45/41/32
46/40/32
47/41/32
49/43/34
52/46/37
Water Flow (1*/2*)
l/min
11.4/22.6
11.9/23.9
15.2/30.5
18.1/35.8
24.1/47.7
Water Pressure Drop (1*/2*)
kPa
13.8/27.5
14.6/29.2
18.7/37.6
23.5/47.1
28.7/57.2
High
Air Volume
4-way Cassette
4-way Cassette (compact)
Med
Low
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
duct
Features
High comfortable, cold and hot water can be supplied simultaneously.
Cooling and heating model can be exchanged conveniently.
High capacity of cooling and heating performance, high efficiency and energy-saving.
Coil
Optional extended drainage pan for protecting your ceiling better.
1.6
Working Pressure
MPa
Net Dimension (W×H×D)
mm
1,425×242×534
1,530×242×534
1,820×242×534
1,369×342×612
1,500×342×612
kg
34
39.5
44.5
46
57
Four-speed motor with one reserved for more choice .
Indoor Unit
Net Weight
Pipe
Connection
Water-inlet pipe
Inch
RC3/4"
Water-outlet pipe
Inch
RC3/4"
Drain pipe
mm
ODΦ24
Note:
1. The data is the performance in high speed with 30Pa external static pressure.
2. Cooling Conditions: 1*-Entering Water 7.2°C, Temperature Rise 8.4°C, Entering Air Temperature 26.7°C DB, 19.4°C WB.
2*-Entering Water 7.2°C, Temperature Rise 5.6°C, Entering Air Temperature 26.7°C DB, 19.4°C WB.
3. Noise level is tested in semi-anechoic room.
4-way cassette
Hot water
Cold water
4-way Cassette (compact)
Hot water
Cold water
Duct type
Hot water
Cold water
45
Fan Coil Unit
Fan Coil Unit
Specifications
Specifications
Model MKA-
600F
750F
850F
950F
1200F
1500F
m3/h
1,150
1,460
1,480
1,720
1,860
2,100
CFM
680
860
870
1,010
1,090
1,230
m3/h
800
1,020
1,040
1,200
1,300
1,470
CFM
470
600
610
700
760
860
m3/h
690
880
890
1,030
1,110
1,260
CFM
410
510
520
610
650
740
Cooling Capacity
W
5,100
5,930
6,170
6,700
9,280
10,580
Heating Capacity
W
6,670
7,870
8,060
8,670
11,650
12,620
Power Input
W
170
188
198
205
197
234
dB(A)
42/32/26
44/34/28
46/36/30
47/38/32
48/40/34
50/42/36
l/min
14.6
17
17.7
19.2
26.6
30.3
High
Air Volume
Med
Low
Noise(Hi/Med/Lo)
Cooling
Water Flow
Water Pressure Drop
l/min
9.6
11.3
11.6
12.4
16.7
18.1
Cooling
kPa
15
17
20
22
32
38
kPa
37
41
42
39
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
2
Row
2
2
2
57
3
61
MPa
1.6
Net Dimension (W×H×D)
mm
950×45×950
Net Dimension (W×H×D)
Indoor Unit
Net Weight
Pipe Connection
m3/h
510
680
850
CFM
300
400
500
m3/h
440
580
730
CFM
260
340
430
m3/h
360
480
600
CFM
210
280
350
Cooling Capacity
W
2,500
2,900
3,500
Heating Capacity
W
3,700
4,600
5,100
Power Input
W
50
70
95
dB(A)
36/33/28
42/39/32
45/42/34
Cooling
l/min
7.2
8.4
10
Heating
l/min
5.3
6.6
7.3
Cooling
kPa
22
16
24
Heating
kPa
17
23
27
Air Volume
6
mm
840×300×840
35
35
35
Med
Low
Noise(Hi/Med/Lo)
Water Flow
Water Pressure Drop
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Panel
kg
kg
500S
Coil
Working Pressure
Net Weight
400S
3
Coil
Panel
300S
High
Heating
Heating
Model MKD-
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
647×50×647
kg
3
mm
575×261×575
kg
17.5
Water-inlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Water-outlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Drain pipe
mm
ODΦ25
Net Weight
35
Water-inlet pipe
Inch
Cold water: RC3/4" Hot water: RC1/2"
Water-outlet pipe
Inch
Cold water: RC3/4" Hot water: RC1/2"
Drain pipe
mm
ODΦ32
38
38
Indoor Unit
Net Dimension (W×H×D)
Net Weight
Pipe Connection
Note:
Note:
1. The data is the performance in high speed.
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C
3. Noise level is tested in semi-anechoic room
Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C, enter air temperature 20°C
3. Noise level is tested in semi-anechoic room.
46
47
Fan Coil Unit
Fan Coil Unit
Specifications
Specifications
200
300
400
500
m3/h
340
510
680
850
CFM
200
300
400
500
m3/h
260
390
510
640
CFM
150
230
300
380
m3/h
170
260
340
430
CFM
100
150
200
250
Cooling Capacity
W
2,000
2,700
3,600
4,300
Heating Capacity
W
3,000
4,000
5,200
5,700
Standard External Static Pressure
Pa
Model MKT5(H)-
High
Air Volume
Med
Low
12Pa
Power Input
W
34
65
46
W
40
60
80
115
12Pa
dB(A)
36/33/28
38/35/30
40/37/32
42/39/34
30Pa
dB(A)
39/36/31
41/38/33
43/40/35
44/41/36
Cooling
l/min
5.7
7.7
10.3
12.3
Water Flow
l/min
4.3
5.7
7.5
8.2
Cooling
kPa
7.8
16
11
36
8.8
17
kPa
34
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
Working Pressure
MPa
Net Dimension (W×H×D)
mm
Indoor Unit
Net Weight
Pipe Connection
1200
m3/h
1,020
1,360
1,700
2,040
CFM
600
800
1,000
1,200
m3/h
770
1,020
1,280
1,530
CFM
450
600
750
900
m3/h
510
680
850
1,020
CFM
300
400
500
600
Cooling Capacity
W
5,000
6,800
7,800
10,200
Heating Capacity
W
7,200
9,600
10,800
13,500
Standard External Static Pressure
Pa
High
Air Volume
Med
Low
Power Input
kg
33
W
100
134
172
220
30Pa
W
115
160
220
240
12Pa
dB(A)
43/40/35
44/41/36
46/43/38
47/44/39
30Pa
dB(A)
45/42/37
46/43/38
48/45/40
50/47/42
Cooling
l/min
14.4
19.5
22.4
29.2
Heating
l/min
10.3
13.8
15.5
19.4
Cooling
kPa
22
20
47
57
Heating
kPa
60
26
45
53
757×240×490
14
812×240×490
Fan Motor
Type
Low noise 4-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
3
Coil
1.6
912×240×490
16.5
18
Water-inlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Water-outlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Drain pipe
mm
ODΦ24
912×240×490
18
12/30
12Pa
Noise(Hi/Med/Lo)
Water Pressure Drop
Fan Motor
Coil
1000
Water Flow
Heating
Heating
800
80
30Pa
Noise(Hi/Med/Lo)
Water Pressure Drop
12/30
600
Model MKT5(H)-
MPa
Net Dimension (W×H×D)
mm
1,125×240×490
1,425×240×490
1,530×240×490
1,820×240×490
kg
21
28
32
37
Indoor Unit
Net Weight
Pipe Connection
1.6
Working Pressure
Water-inlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Water-outlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Drain pipe
mm
ODΦ24
Note:
Note:
1. The data is the performance in high speed with relevant external static pressure.
1. The data is the performance in high speed with relevant external static pressure.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C
3. Noise level is tested in semi-anechoic room.
Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C
3. Noise level is tested in semi-anechoic room.
48
49
Fan Coil Unit
Fan Coil Unit
4 -pipe cassette FCU (without PCB)
4-way Cassette
Specifications
Model MKA-
750NF
950NF
1200NF
m3/h
1,460
1,720
1,860
2,050
CFM
860
1,010
1,090
1,210
m3/h
1,020
1,200
1,300
1,470
CFM
600
700
760
860
m3/h
880
1,030
1,110
CFM
520
610
650
740
Cooling Capacity
W
5,930
6,650
9,100
10,000
Heating Capacity
W
7,870
8,600
11,650
12,600
Power Input
W
188
190
197
234
dB(A)
44/34/28
47/38/32
48/40/34
50/42/36
Cooling
l/min
17
19.1
26.1
28.7
Heating
l/min
11.3
12.3
17
18.1
Cooling
kPa
17
22
32
38
Heating
kPa
41
42
57
61
4-way Cassette (compact)
High
Air Volume
Med
Low
Features
High comfortable, cold and hot water can supply simultaneously.
Noise(Hi/Med/Lo)
Water Flow
Cooling and heating model can exchange conveniently.
Various thermostats can be chosen by customer’s need.
Flexible wiring connection for non-PCB.
High capacity of cooling and heating performance, high efficiency and energy-saving.
Built-in control valve helps to switch the supply of cold or hot water by remote controller.
Optional extended drainage pan for protecting your ceiling better.
Fresh air provision makes life healthier and more comfortable.
50
Water
Pressure Drop
Fan Motor
Type
Low noise 3-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
2
Row
2
1500NF
160
1,260
16.0kW
3
3
38
38
Coil
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
950×45×950
kg
6
mm
840×300×840
Panel
Net Weight
Net Dimension (W×H×D)
Indoor Unit
Pipe
Connection
Net Weight
kg
35
35
Water-inlet pipe
Inch
Cold water: RC3/4" Hot water: RC1/2"
Water-outlet pipe
Inch
Cold water: RC3/4" Hot water: RC1/2"
Drain pipe
mm
ODΦ32
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C
3.Noise level is tested in semi-anechoic room
51
Fan Coil Unit
Fan Coil Unit
Specifications
Model MKD-
300NF
400NF
500NF
m3/h
510
680
850
CFM
300
400
500
m3/h
440
580
730
CFM
260
340
430
m3/h
360
480
600
CFM
210
280
350
Cooling Capacity
W
2,360
2,900
3,500
Heating Capacity
W
3,700
4,600
4,830
Power Input
W
50
70
87
dB(A)
36/33/28
42/39/32
45/42/34
Cooling
l/min
6.8
8.3
10
Heating
l/min
5.3
6.6
6.9
Cooling
kPa
22
16
24
Heating
kPa
17
23
27
High
Air Volume
Med
Low
Noise(Hi/Med/Lo)
Water Flow
Water
Pressure Drop
Fan Motor
Type
Low noise 3-speed fan motor
Fan
Type
Centrifugal, forward-curved Blades
Row
2
Coil
Working Pressure
MPa
1.6
Net Dimension (W×H×D)
mm
647×50×647
kg
3
mm
575×261×575
kg
17.5
Water-inlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Water-outlet pipe
Inch
Cold water: G3/4" Hot water: G1/2"
Drain pipe
mm
ODΦ25
Panel
Net Weight
Net Dimension (W×H×D)
Indoor Unit
Pipe
Connection
Net Weight
Note:
1. The data is the performance in high speed.
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB.
Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C
3.Noise level is tested in semi-anechoic room
Fan performance
160
16.0kW
52
53
Fan Coil Unit
Fan Coil Unit
Fan performance
30Pa
30Pa
MKT2-200~1400(E)
MKT2H-200~1400(E)
1200
1400
40
30
20
10
0
4
8
12
16
20
24
28
32
36
40
44
48
52
80
200 300 400 500 600 800 1000
1200
1400
70
60
50
40
30
20
10
0
90
90
4
8
12
16
Air Flow (m3 /min)
20
24
28
32
36
40
44
48
52
80
External Static Pressure (Pa)
50
MKT3-200~1400G50
MKT4H-1500~2000G50
MKT4H-200~2000(E)
90
External Static Pressure (Pa)
External Static Pressure (Pa)
60
200 300 400 500 600 800 1000
50Pa
200 300 400 500 600 8001000
1200
1500
External Static Pressure (Pa)
12Pa
2000
70
60
50
40
30
20
10
Air Flow (m3 /min)
0
5
10
15 20 25 30
35 40
45 50 55 60
65 70 75
MKT3H-200~1200
1200
40
30
20
10
0
4
8
12
16
20
24
28
32
36
40
44
48
80
200 300 400 500 600 800 1000
180
50
Air Flow (m3 /min)
MKT3-200~1400G30
80
External Static Pressure (Pa)
External Static Pressure (Pa)
80
1400
60
50
40
30
20
10
0
4
8
12
16
20
24
28
32
36
Air Flow (m3 /min)
40
44
48
52
1600
1800
2200
100
10
90
1200
1400
120
20
90
1000
1000 1200
140
30
52
70
800
160
40
MKT3-200~1400G12
800
MKT3H-800~1400G70
MKT3H-1600~2200G100
60
Air Flow (m3 /min)
200 300 400 500 600
1200
70
External Static Pressure (Pa)
External Static Pressure (Pa)
External Static Pressure (Pa)
50
200 300 400 500 600 800 1000
70/100Pa
90
80
60
40
20
0
200 300 400 500 600
800
1000
1200
6
12
18 24 30 36
42 48
54 60 66 72 78
84 90
3
Air Flow (m /min)
1400
70
60
The units using the wide wheel of latest design and
50
low speed forward-curved blades are most suitable
40
for the motor through dynamic balance test.
30
20
The motor adopts durable capacitance, superior
10
lubricant oil and rust-proof treatment for high
0
4
8
12
16
20
24
28
32
36
Air Flow (m3 /min)
40
44
48
52
reliability and low noise.
80
70
60
50
40
30
20
10
0
5
10
15 20 25 30
35 40
45 50 55 60
Air Flow (m /min)
Air Flow (m /min)
MKT3-200~1200
1200 1400 1500G50 2000G50
3
3
60
200 300 400 500 600 8001000
65 70 75
54
55
Fan Coil Unit
Fan Coil Unit
56
Controllers
For cassette and wall-mounted
Controllers
Standard wireless remote controllers for cassette and wall-mounted
Specification
R05/BGE
R51/E
Function
Working Rated Voltage: DC3V.
Applied Equipment: R05/BGE: cassette(standard), R51/E:
Min vlotage for sending signal of CPU: DC2.4V.
wall-mounted(standard).
Working Environment:Temperature: -5~60°C.
LCD display screen.
Effective receiving distance: 8~11m.
Mode setting: auto/cool/heat/dry/fan.
Temperature Controlling Range: 17~30°C.
Fan speed selection: auto/high/medium/low.
Temperature Controlling Precision: ±1°C.
Time setting/temp. setting/ swing setting.
Optional wired controller for cassette and wall-mounted
Specification
KJR-10B/DP(T)-E
KJR-12B(DP)
Function
Working Voltage: DC5V.
Applied Equipment: cassette and wall-mounted(optional).
Working Environment:
Big LCD display screen.
Temperature: -15~43°C
Mode setting: auto/cool/heat/dry/fan.
Relative Humidity: 40%~90%.
Fan speed selection: auto/high/medium/low.
Temperature Controlling Range: 17~30°C.
Economic operation mode/time setting/temp. setting.
Temperature Controlling Precision: ±1°C.
ON/OFF mode setting.
Optional central controller for cassette and wall-mounted
Specification
CCM03
Function
Working Voltage: AC220±10%, 50/60Hz.
Applied Equipment: cassette and wall-mounted(optional).
Working Environment:
Centralized control:
Temperature: -15~43°C
the max. quality of indoor units is up to 64 by one CCM03.
Relative Humidity: 40%~90%.
Big LCD display screen.
Temperature Controlling Range: 17~30°C.
Mode setting: cool/heat/ fan.
Temperature Controlling Precision: ±1°C.
Fan speed selection: auto/high/medium/low.
Time setting/temp. setting/ swing setting.
57
Fan Coil Unit
Fan Coil Unit
For floor-standing and ceiling & floor
Optional wired controller for floor-standing and ceiling & floor
Specification
KJR-15B/E(P)
Function
Working Voltage: AC220V~230V, 50/60Hz
Applied Equipment:
Working Environment:
floor standing and ceiling & floor standing (optional).
Temperature: -15~43°C
LCD display screen.
Relative Humidity: 40%~90%.
Mode setting: cool/heat/fan.
Temperature Controlling Range:17~30°C /62~86°F.
Fan speed selection: high/medium/low.
Temperature Controlling Precision: ±1°C.
Temperature display in °F or °C.
ON/OFF mode setting.
For Duct
Optional wired controller for duct units without EAH
Function
Specification
Working Voltage: AC220V±10%, 50/60Hz.
Applied Equipment: duct units without EAH(optional).
Working Environment:
Mode setting: cool/heat/off.
Temperature: 0~45°C
Fan speed selection: high/medium/low.
Relative Humidity: 5%~90%.
Temperature setting.
Temperature Controlling Range:10~30°C.
Temperature Controlling Precision: ±1°C.
External Dimension: 85×130×43mm (W×H×D).
Installation hole pitch: 60mm (standard).
KJR-18B
Model
Applied Equipment
Objects Controlled
KJB-18B-A
2-pipe duct
3-speed fan
KJB-18B-B
2-pipe duct
motorized valve and 3-speed fan
KJB-18B-C
2-pipe duct
motorized valve and 3-speed fan
KJB-18B-D
4-pipe duct
two motorized valve and 3-speed fan
Optional wired controller for duct units with EAH
Specification
KJR-21B/D
Function
Working Voltage: AC220V±10%, 50/60Hz.
Applied Equipment: duct units with EAH(optional).
Power Consumption: <2W.
Blue backlight.
Current Loae: <2A.
Clock display.
Temperature Controlling Range: 5~35°C.
Temp. setting.
Temperature Controlling Precision: ±1°C.
Mode setting: cool/heat/fan/electric heating on/off.
External Dimension: 86×86×13mm (W×H×D).
Fan speed selection: auto/high/medium/low.
Installation hole pitch: 60mm (standard).
Motorized valve control.
Electric heating control.
Remote control (optional).
Accessories
58
59
Fan Coil Unit
Fan Coil Unit
Accessories
Specification
Features
Working Voltage: AC230±10%, 50/60Hz(24V can be customized).
PC board control kit for FCU
Power Consumption: 4W(AC230V) 6W(AC24V).
Nominal Pressure: 1.6Mpa.
DDSTF-04
DDSTF-05
Applied Medium: Cold or hot water, 50% glycol water liquor.
Protection Grade: IP54.
Working Journey: 2.5~3mm.
Features
Medium Temperature: -20~70°C.
Suitable for 2-pipe and 4-pipe ductable FCU without electric auxiliary heater.
Environment Temperature: 0~50°C.
Installation flexible ,it can be installed attaching on the unit, mounting on the wall or hanging under the ceiling.
Security Class: Ⅱ(Double Insulation).
Maintenance convenient for its external installed.
Running Time: ≤5 Minutes(25°C).
Three speeds adjustment: high/medium/low.
Operating status can be displayed from lamp indicator.
Network Interface Module standard, compatible with the CCM control and PC based software control.
Optional accessories
Specifications
Model
FCUKZ-01
2-pipe ductable FCU
Applicable appliance
Power supply
Operation range
FCUKZ-02
4-pipe ductable FCU
220-240V-1Ph-50/60Hz
Room temperature
17°C-30°C
Inlet water temperature
3°C-75°C
Temperature controlling precision
±1°C
Dimension (W×H×D)
310×76×290
Packing Size (W×H×D)
384×174×359
Selection for compatibility
Remote /Wired /Central /PC based network software control
Valve kit
Specification
Working Voltage: AC230±10%, 50/60Hz(24V can be customized).
Power Consumption: 4W(Only when you open and close the valve).
Nominal Pressure: 1.6Mpa.
Applied Medium: Cold or hot water, 50% glycol water liquor.
Medium Temperature: 2~75°C.
Environment Temperature: -5~50°C.
DDSTF-01
Extended drainage pan
There is standard auxiliary drainage pan for ductable FCU with inlet
plenum box, and optional auxiliary drainage pan for cassette FCU
and ductable FCU without inlet plenum box.With extended drainage
pan to receive the condensate water dripping from the water piping
and valve connection.
60
61
Fan Coil Unit
Fan Coil Unit
Application of network
control & BMS control
Max.64
Optional wired controller
Indoor CCM03
Wall Mounted
4-way Cassette
KJR-90A-E
Compact 4-way Cassette
KJR-90A1-E
MAX. 16
Max.64
KJR-10B
FCUKZ-01
FCUKZ-02
Indoor CCM03
KJR-12B
All basic function as the same as KJR-10B.
Small size and Easy for installation.
Exquisite appearance and LCD display function.
Optional for all the indoor units.
Designed for hotel or other similar place.
1) Only can select ON/OFF, Temp, Swing, and Timer
2) Avoid mode conflict.
Other functions are the same with KJR-90A-E.
Optional for all the indoor units.
Mode selection: Auto, Cool, Dry, Heat, Fan only.
Temp. setting range: 17 ? to 30 ?
Daily Timer setting.
Fan speed control: H/M/L/Auto .
Louver swing.
Same function with KJR-10B.
Add the follow me function.
Optional central controller
2-pipe concealed Ductable
4-pipe concealed Ductable
KJR-90B/M-E
CCM03
UPS
RS485/RS232
Converter
KJR-180A
Softdog
CCM09
Network control
software
New design indoor unit central controller,
simple on/off function.
Max. 16 indoor units can be controlled.
Switch modes between cooling and heating .
Overall/mono-control the indoor units.
Indoor unit central controller.
Max. 64 indoor units can be controlled.
Automatically record all setting information
when lose power.
Clear & bright LCD display screen, background light,
more parameters display.
Emergency ON/OFF control with simple dry contact input.
New design indoor unit central controller, similar
function with CCM03.
Max. 16 indoor units can be controlled.
Easier for installation in the wall, complete cabinet
at the rear.
Indoor unit weekly timer central controller.
7 -days Weekly schedule setting (Maximum 128
weekly & daily schedules).
Max. 64 indoor units group control or individual setting.
Clear and bright screen with LCD backlight.
Wireless remote control restriction.
Sleep and Silent mode.
Mode lock.
Permanent schedule setting storage.
Network Control Software
BMS
CCM08
Bacnet/IP Network
TCP/IP Network
PC in LAN
Perfect system monitor/control function
It can dynamically monitor indoor /outdoor units operation condition.
Powerful schedule management, group management, uniform management.
Accurately electricity distribution function.
Adopt Microsoft Fire Bird Server database, It can output detailed data table.
BACnet Gateway - CCM08
BACnet/Ethernet optional.
Max. 4 Indoor/Outdoor CCMs (CCM02 or CCM03)
Each CCM can connect Max. 64 indoor units or 32 outdoor units.
No need to install the Network Control Software any more.
By inputting IP address of CCM08,PC in LAN could access
CCM08 to realize simple setting and controlling of A/C.
Selection software
62
63
Fan Coil Unit
Selection software
SELECTION SOFTWARE
Fan Coil Unit
Main interface
Menu
Project Operation Area
Selection Button
Product Operation Area
Features
Selection Resule (Equipment List)
Simple Report (Specifications)
Unit Settings
Selection interface
The products of this selection software contain Fan Coil Unit, standard Air Handling Unit
and Modular Air Handling Unit.
You can make selections under varies entering air conditions, entering water conditions
and different fan speed settings.
The interface is very visualized, which makes the operation easy.
Powerful project management function.
All copyrights reserved by Midea. It should be authorized through Midea technical
support engineer before using.
64
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project