INSTALLATION INSTRUCTIONS FOR M500ME MONITOR MODULE,
M500CHE CONTROL MODULE, AND M500XE FAULT ISOLATOR MODULES
This information is included with the modules as a quick reference installation guide. Refer to the control panel manufacturer’s installation manual for detailed system information. If the module will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing
the modules.
GENERAL DESCRIPTION
M500ME MONITOR MODULES provide a two-wire, or fault-tolerant, initiating circuit for normally open contact fire alarm and
supervisory devices, or either normally open or normally closed security devices.
The LED indicator can be latched on or returned to the normal mode by code
command from the panel. Convenient rotary decade switches are used to set the
address of each module.
M500CHE CONTROL MODULES allow a compatible control panel to switch
discrete contacts by code command. The control module offers a status LED that
can be latched on or returned to the normal mode by code command from the
panel. Convenient rotary decade switches are used to set the address of each
module.
The control module offers two modes of switching operation. As shipped, the
module is configured for switching an external power source to notification
appliances. The external power source can be a DC power supply or an audio
amplifier (up to 70.7 Vrms). In this mode, the module reports supervision status of
FIGURE 1.
the connected loads to the control panel. Load circuit status is reported as a
MONITOR AND CONTROL MODULE
NORMAL, OPEN, or SHORTED circuit. Two pairs of output termination points are
CONTROLS AND INDICATORS
available for fault-tolerant wiring. The second mode of switching operation allows
the panel to control one Form-C (SPDT) set of contacts. Circuits connections to the
contacts are not supervised by the module. This mode is enabled by breaking two
external tabs on the module.
M500XE FAULT ISOLATION MODULES enable part of the communications loop
to continue operating when a short circuit occurs on it. A LED indicator blinks in the
normal condition and turns on during a short circuit condition. The module will
automatically restore the entire communications loop to the normal condition when
the short circuit is removed.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed compatible
system control panels only.
MOUNTING M500ME, M500CHE AND M500XE DEVICES
M500ME, M500CHE, and M500XE modules mount directly to 4 inch square electrical boxes as shown in Figure 2. The box must have a minimum depth of 2-1/8
inches.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances and regulations.
1. Install module wiring in accordance with the job drawings and appropriate wiring
diagrams (Figures 3-10).
2. Set the address on the module per job drawings.
3. Secure the module to the electrical box (supplied by installer), as shown in
Figure 2.
4. Perform steps one, two, and three for all modules.
MAGNET TEST
The monitor and control modules can be tested with a test magnet available from
System Sensor (M02-04-00, see Figure 1). The magnet test checks the module
electronics and connections to the control panel. Interfaced initiating and indicating
devices must be tested independently.
Pittway Tecnologica S.p.A.,Via Caboto19, 34147 Trieste,Italy
D500-26-00
1
FIGURE 2.
EXPLODED VIEW OF TYPICAL
MODULE DETAILING MOUNTING
ARRANGEMENT
I56-0893-001
M500ME MONITOR MODULE WIRING DIAGRAMS
FROM PANEL OR
PREVIOUS DEVICE
TO NEXT
DEVICE
MONITOR
MODULE
M500ME
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY.
47K EOL
RESISTOR
A2143-00
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE A OR B
POWER LIMITED: 230 µA MAX @ 12 VDC MAX
IDC INSTALLATION WIRING SHALL NOT
EXCEED 40 OHMS OR 2500 FEET, 12-18 AWG.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
ALL WIRING SHOWN IS SUPERVISED.
P1444-D4
FIGURE 3. TYPYCAL 2- WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE A OR B
FROM PANEL OR
PREVIOUS DEVICE
TO NEXT
DEVICE
MONITOR
MODULE
M500ME
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY.
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9.
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED.
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE D
POWER LIMITED: 230 µA MAX @ 12 VDC MAX
IDC INSTALLATION WIRING SHALL NOT
EXCEED 40 OHMS OR 2500 FEET, 12-18 AWG.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
P1445-D4
FIGURE 4. TYPICAL FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA STYLE D
M500CHE CONTROL MODULE WIRING DIAGRAMS
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANEL ONLY.
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED.
FROM PANEL OR
PREVIOUS DEVICE
24 VDC BRANCH CIRCUIT
DO NOT LOOP WIRE ON TERMINALS
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
TO NEXT
DEVICE
CONTROL
MODULE
M500CHE
INITIATING APPLIANCE CIRCUIT (IAC) - NFPA STYLE W OR Y
USE UL LISTED INDICATING APPLIANCES
MAXIMUM LOAD: RESISTIVE: 2 A @ 30 VDC
INDUCTIVE:1 A @ 30 VDC (0.6 PF)
PILOT DUTY: 0.6 A @ 30 VDC (0.35 PF)
ISOLATED, REGULATED, 24VDC
POWER SUPPLY, LISTED FOR FIRE
PROTECTION WITH BATTERY
BACKUP (MONITOR LOSS OF
PRIMARY POWER)
47K EOL
RESISTOR
A2143-00
XXX - DO NOT
USE TERMINAL 5
MODULE POLARITIES ARE SHOWN IN ALARM
TO NEXT CONTROL MODULE OR END OF
LINE RELAY (EOLR); ONE EOLR REQUIRED
PER 24 VDC BRANCH CIRCUIT
UL LISTED EOL RELAY
SHOWN ENERGIZED
24 VDC COIL
A77-716-02
P1446-D4
FIGURE 5. TYPICAL INDICATING CIRCUIT CONFIGURATION, NFPA STYLE W OR Y
D500-26-00
2
I56-0893-001
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANEL ONLY.
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
FROM PANEL OR
PREVIOUS DEVICE
ALL WIRING SHOWN IS SUPERVISED.
TO NEXT
DEVICE
INITIATING APPLIANCE CIRCUIT (IAC) - NFPA STYLE X OR Z
CONTROL
MODULE
M500CHE
24 VDC BRANCH CIRCUIT
DO NOT LOOP WIRE ON TERMINALS
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
USE UL LISTED INDICATING APPLIANCES
MAXIMUM LOAD: RESISTIVE: 2 A @ 30 VDC
INDUCTIVE:1 A @ 30 VDC (0.6 PF)
PILOT DUTY: 0.6 A @ 30 VDC (0.35 PF)
ISOLATED, REGULATED, 24VDC
POWER SUPPLY, LISTED FOR FIRE
PROTECTION WITH BATTERY
BACKUP (MONITOR LOSS OF
PRIMARY POWER)
EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9
UL LISTED EOL RELAY
SHOWN ENERGIZED
24 VDC COIL
A77-716-02
XXX - DO NOT
USE TERMINAL 5
TO NEXT CONTROL MODULE OR END OF
LINE RELAY (EOLR); ONE EOLR REQUIRED
PER 24 VDC BRANCH CIRCUIT
MODULE POLARITIES ARE SHOWN IN ALARM
P1447-D4
FIGURE 6. TYPICAL FAULT TOLERANT INDICATING CIRCUIT CONFIGURATION, NFPA STYLE X OR Z
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANEL ONLY.
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED.
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
CONTROL
MODULE
M500CHE
AUDIO BRANCH CIRCUIT
DO NOT LOOP WIRE ON TERMINALS
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
SPEAKER SWITCHING CIRCUIT - NFPA STYLE W OR Y
SPEAKER MUST BE LISTED FOR FIRE PROTECTION
MAXIMUM LOAD: 43.75 WATTS MAX
UP TO 70.7 Vrms
(0.35 POWER FACTOR)
47K EOL
RESISTOR
A2143-00
AUDIO AMPLIFIER
UP TO 70.7 Vrms MAX
XXX - DO NOT
USE TERMINAL 5
TO NEXT CONTROL MODULE OR
AUDIO SUPERVISION CIRCUITS
MODULE POLARITIES ARE SHOWN IN ALARM
P1448-D4
FIGURE 7. TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE W OR Y
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANEL ONLY.
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED.
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
AUDIO BRANCH CIRCUIT
DO NOT LOOP WIRE ON TERMINALS
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
CONTROL
MODULE
M500CHE
SPEAKER SWITCHING CIRCUIT - NFPA STYLE X OR Z
SPEAKER MUST BE LISTED FOR FIRE PROTECTION
MAXIMUM LOAD: 43.75 WATTS MAX
UP TO 70.7 Vrms
(0.35 POWER FACTOR)
EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9
AUDIO AMPLIFIER
UP TO 70.7 Vrms MAX
XXX - DO NOT
USE TERMINAL 5
TO NEXT CONTROL MODULE OR
AUDIO SUPERVISION CIRCUITS
BYPASS CAPACITORS: 100 µF, 10V
NON-POLARIZED
< 10 µA LEAKAGE
P1449-D4
MODULE POLARITIES ARE SHOWN IN ALARM
FIGURE 8. TYPICAL FAULT TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE X OR Z
Pittway Tecnologica S.p.A.,Via Caboto19, 34147 Trieste,Italy
3
I56-0893-001
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANEL ONLY.
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
CONTROL
MODULE
M500CHE
RELAY CONTACT RATINGS:
RESISTIVE:
2 A 30 VDC
INDUCTIVE:
1 A 30 VDC (0.6 PF)
PILOT DUTY: 0.6 A 30 VDC (0.35 PF)
0.3 A 110 VDC (0.35 PF)
0.3 A 120 VAC (0.35 PF)
RELAY COMMON
NORMALLY CLOSED
NORMALLY OPEN
J1 & J2
FORM “C” RELAY OPERATION WHEN
BOTH TABS J1 AND J2 ARE BROKEN.
MODULE DOES NOT SUPERVISE CIRCUITS
CONTROLLED BY FORM C CONTACT.
P1450-D4
BREAK OFF TABS
J1 & J2 TO ENABLE
FORM C OPERATION
FIGURE 9. CONTROL MODULE IN RELAY OUTPUT MODE
WARNING
Control Module switch contacts are shipped in the standby state (open). Contacts may have transferred to the activated state
(closed) during shipping.
The module utilizes a mechanical latching-type relay that can change states due to shock or jarring. The control panel controls this
relay with “STANDBY” and “ALARM” control commands. To insure that the switch contacts are in the standby state, control modules
must be made to communicate with the panel before connecting circuits controlled by the module.
M500XE FAULT ISOLATOR MODULE WIRING DIAGRAM
FAULT ISOLATOR
MODULE
M500XE
UL LISTED COMPATIBLE
CONTROL PANEL
COMMUNICATION LINE
28 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED.
FAULT ISOLATOR
MODULE
M500XE
GROUPS OF DEVICES ARE SEPARATED BY FAULT ISOLATOR
MODULES. ANY COMBINATION OF COMPATIBLE, LISTED
DEVICES MAY BE MIXED WITHIN A GROUP.
A PAIR OF FAULT ISOLATOR MODULES WILL DISCONNECT A
GROUP OF DEVICES IF A SHORT CIRCUIT OCCURS ON THE
SIGNALING LINE CIRCUIT WITHIN THAT GROUP.
FAULT ISOLATOR
MODULE
M500XE
FAULT ISOLATOR
MODULE
M500XE
P1451-D3
FIGURE 10. FAULT ISOLATOR MODULE WIRING
D500-26-00
4
© System Sensor 2000
I56-0893-001