Switching Power Supply S82K

Switching Power Supply S82K
Switching Power Supply
S82K
DIN-Rail Mount Power Supply with a
Wide Power Range of 3 to 240 W
Universal voltage range: 100 to
240 VAC
UL 508 listed on all models
Class 2 approved on all models below
240-W, except dual-output types
Undervoltage indicators on all.
90-W, 100-W and 240-W T-Models have
indicator and output
Meets EN61000-3-2 (limits for harmonic
current emissions) with PFC on 240-W
models
Parallel operation capability (90-W,
100-W and 240-W)
Finger-safe terminal block with cover
according to VDE0106/P100
uR
Approvals: UL, CSA, VDE, and CE
3-year warranty
Ordering Information
SWITCHING POWER SUPPLIES
Rated input voltage
Power ratings
Output voltage
Output current
Functional configuration
Part number
100 to 240 VAC
3W
5V
0.6 A
Single
g output
S82K-00305
12 V
0.25 A
S82K-00312
15 V
0.2 A
S82K-00315
24 V
0.13 A
S82K-00324
5V
1.5 A
S82K-00705
12 V
0.6 A
S82K-00712
15 V
0.5 A
S82K-00715
24 V
0.3 A
7.5 W
15 W
30 W
50 W
S82K-00724
Dual output
+12 V/–12 V
0.3 A/0.2 A
+15 V/–15 V
0.2 A/0.2 A
5V
2.5 A
12 V
1.2 A
S82K-01512
24 V
0.6 A
S82K-01524
5V
5.0 A
S82K-03005
12 V
2.5 A
S82K-03012
24 V
1.3 A
S82K-03024
24 V
2.1 A
S82K-05024
(This table continues on the next page.)
S82K-00727
S82K-00728
Single output
S82K-01505
S82K
S82K
Ordering Information Table – continued from previous page
Rated input voltage
Power ratings
Output voltage
Output current
Functional configuration
Part number
120/240 VAC
selectable
l t bl
90 W
24 V
3.75 A
Single
g output
S82K-09024
100 W
24 V
4.2 A
240 W
24 V
10 A
240 W
24 V
10 A
With undervoltage alarm
indicator/output
S82K-24024T
240 W
24 V
10 A
With PFC
S82K-P24024
100 to 240 VAC
S82K-10024
S82K-24024
MODEL NUMBER LEGEND
3- to 100-W Models
S82K 1
2
1. Power Ratings
003: 3 W
007: 7.5 W
015: 15 W
030: 30 W
050: 50 W
090: 90 W
100: 100 W
2. Output Voltage
05:
12:
15:
24:
27:
28:
5 VDC
12 VDC
15 VDC
24 VDC
Dual output +12/-12 VDC
Dual output +15/-15 VDC
240-W Models
S82K -
24024
1
2
1. Power Factor Correction
None: No
P: Yes
2. 2. Undervoltage alarm indicator/output
None: No
T: Yes
ACCESSORIES (SOLD SEPARATELY)
DIN Rail
Item
Length
Width
Part number
DIN-rail ((See Dimensions section for details.))
0.5 m (1.64 ft)
7.3 mm (0.29 in)
PFP-50N
1 m (3.28 ft)
7.3 mm (0.29 in)
PFP-100N
1 m (3.28 ft)
16 mm (0.63 in)
PFP-100N2
Noise Filter
Item
Applicable power supply
Part number
Noise filter
For 3- to 50-W models
S82Y-JF3-N
For 90-W and 100-W models
S82Y-JF6-N
2
S82K
S82K
Specifications
RATINGS/CHARACTERISTICS
Non–PFC models
Item
Efficiency (typical)
Input
Voltage
(see
note 1)
Single output
Dual
outputs
Single output
3W
7.5 W
15 W
7.5 W
30 W
AC
100 to 240 V (85 to 264 V)
90 W
100 W
DC
90 to 350 V (see note 2)
100 V (85 to
132 V)/
200 V (170 to
264 V) Selectable
240 W
240 W
100 V
(85 to
132 V)/
200 V
(170 to
253 V)
Selectable
100 to 230 V
(85 V to
253 V)
Not possible
50/60 Hz (47 to 450 Hz)
100-V
input
0.15 A
max.
0.25 A max.
200-V
input
50/60 Hz
(47 to
63 Hz)
0.45 A
max.
0.9 A
max.
1.3 A
max.
2.5 A max.
5.5 A
max.
4 A max.
0.25 A
max.
0.6 A
max.
0.8 A
max.
1.5 A max.
3.5 A
max.
2 A max.
Power factor
---
Leakage
current
(
(see
note 3)
100-V
input
0.5 mA max.
200-V
input
1 mA max.
Inrush
current
(
(see
note 3)
100-V
input
15 A max.
25 A max.
200-V
input
30 A max.
50 A max.
Noise filter
50 W
60% to 80% (Varies depending on specifications.)
Frequency
Current
(see
note 3)
PFC model
0.95 min.
Yes
Note: 1. Use with DC voltage input is beyond the conditions of approval or conformance to applicable safety standards.
2. Use the 7.5-W single-output models under the load of 90% max. if the voltage range is between 90 and 110 VDC.
3. Defined with a 100 % load and the rated input voltage (100 or 200 VAC).
3
S82K
S82K
Specifications Table – continued from previous page
Non–PFC models
Item
PFC model
Single output
Dual
outputs
Single output
3W
7.5 W
15 W
Not
possible
(see
note 3)
±10% (V.ADJ); –10% to 15% for S82K-03012/-03024/-05024
7.5 W
30 W
50 W
Output
(see
note 2)
Voltage adjustment range
±10% (V.ADJ)
Output
(see
note 2)
Ripple
(see note 1)
2% (p-p) max.
Input variation
influence
0.5 % max. (at 85 to 264 VAC input, 100% load)
Load variation
influence
1.5% max.
(0 to 100% load)
Temperature variation influence
(see note 1)
0.05%/°C max.
Rise time
100 ms max. (up to 90% of output voltage at rated input
and output)
Hold time
(see note 1)
20 ms min.
+V:
1.5%
max.
-V: 3 %
max.
(0 to
100%
load)
90 W
100 W
0.5 % max. (at 85
to 132 VAC/170
to 264 VAC input,
100% load)
1.5% max.
(0 to 100% load)
240 W
0.5 %
max.
(at 85
to 132
VAC/
170 to
253
VAC input,
100%
load)
240 W
0.5 % max.
(at 85 to
253 VAC input, 100 %
load)
1.5% max.
(10 to 100% load)
200 ms max.
300 ms
max.
1,000 ms
max.
(This table continues on the next page.)
Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC).
2. The output specification is defined at the power supply output terminals.
3. The settings for the output voltage must be within the following range:
+V: ±1% of the rated value
–V: ±5% of the rated value
4. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the protection function will
operate at a current of 95% to 160% of the rated load current.
5. When the ambient temperature exceeds 25°C, the overload protection function will operate at a current of 92% to 111% of the
rated load current.
6. Circuit-breaker type. To reset, turn the input power supply OFF, then after 1 min has elapsed, turn the input power supply ON
again.
4
S82K
S82K
Specifications Table – continued from previous page
Non–PFC models
Item
Additional
function
PFC model
Single output
Dual
outputs
Single output
3W
7.5 W
15 W
105%
to
250%
of rated
load
current,
automatic
reset
105% to 160% of rated load
current, automatic reset
7.5 W
30 W
50 W
90 W
100 W
101%
to
111%
of rated
load
current,
automatic
reset
(see
note 5)
105% to 160% of rated load current, automatic reset
240 W
240 W
Overload
protection
105% to 160%
of rated load
current, automatic reset
(see note 4)
Overvoltage
protection (see
note 6)
No
S82K24024T
model
only
No
Undervoltage
alarm indicator
(DC LOW indicator)
Yes (color: red)
S82K24024T
model
only
No
Undervoltage
alarm output (DC
LOW output)
No
Yes
S82K24024T
model
only
No
Parallel operation
Impossible
Possible (2 units max.)
(This table continues on the next page.)
Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC).
2. The output specification is defined at the power supply output terminals.
3. The settings for the output voltage must be within the following range:
+V: ±1% of the rated value
–V: ±5% of the rated value
4. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the protection function will
operate at a current of 95% to 160% of the rated load current.
5. When the ambient temperature exceeds 25°C, the overload protection function will operate at a current of 92% to 111% of the
rated load current.
6. Circuit-breaker type. To reset, turn the input power supply OFF, then after 1 min has elapsed, turn the input power supply ON
again.
5
S82K
S82K
Specifications Table – continued from previous page
Non–PFC models
Item
PFC model
Single output
Dual
outputs
Single output
3W
7.5 W
15 W
7.5 W
30 W
50 W
90 W
100 W
240 W
240 W
Other
Ambient
temperature
Operating: See the derating curve in the Engineering Data section
(no condensation or icing)
Storage:
–25°C to 65°C (no condensation or icing)
Other
Ambient humidity
Operating: 25% to 85%
Storage:
25% to 90%
Dielectric strength
3,000 VAC at 50/60 Hz for 1 min (between all inputs and outputs)
2,000 VAC at 50/60 Hz for 1 min (between all inputs and GR terminal)
1,000 VAC at 50/60 Hz for 1 min (between all outputs and GR terminal)
Alarm current: 10 mA (3- to 7.5-W models) 20 mA (15- to 100-W models) 25 mA (240-W models)
Insulation
resistance
100 MΩ min. at 500 VDC (between all outputs and all inputs/GR terminal)
Vibration
resistance
Malfunction: 10 to 55 Hz, 0.375-mm single amplitude for 2 hrs each in X, Y,
and Z directions
Shock resistance
Malfunction: 300 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Screw tightening
torque
0.74 N m max. (see note 2)
Output indicator
Yes (green)
Electromagnetic
interference
(see note 1)
Conforms to FCC class B
EMC
(see note 3, 4)
3 to 100-W Models
(EMI):
Emission Enclosure:
Emission AC Mains:
Emission Output Ports:
240-W Models
(EMI):
Emission Enclosure:
Emission AC Mains:
Harmonic Current:
Common to All Models
(EMS):
Immunity ESD:
Malfunction: 10 to
55 Hz, 0.15-mm single
amplitude for 2 hrs
each in X, Y, and
Z directions
Conforms to FCC class A
EN50081-1
EN55022 class B (equivalent to EN55011 class B)
EN55022 class B (equivalent to EN55011 class B)
EN55022 class A (with a recommended optional filter) (see note 3)
EN50081-2
EN55011 class A (see note 4)
EN55011 class A (see note 4)
EN61000-3-2 (only for S82K-P24024)
EN50082-2
EN61000-4-2:
Immunity Burst:
EN61000-4-4:
Immunity Surge:
EN61000-4-5:
4-kV contact discharge (level 2)
8-kV air discharge (level 3)
2-kV power-line (level 3)
2-kV output line (level 4)
between 2-kV lines (except for 240-W models)
between 4-kV line and FG (except for 240-W models)
Approved
standards
Class 2 (UL 1310)/Class 2 (CSA C22.2 No. 950) (see notes 5 and 6)
UL 508 (Listing)/1950
CSA C22.2 No.14/No.950, EN50178 (VDE0160), EN60950
Conforms to VDE0106/P100
UL 508 (Listing)/1012
CSA C22.2 No.14,
CSA E.B. 1402C,
EN50178 (VDE0160),
EN60950
Conforms to
VDE106/P100
Weight
150 g max.
1,800 g
max.
260 g
max.
380 g
max.
400 g
max.
600 g max.
2,200 g max.
Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC).
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
3. To ensure the emission ratings, a noise filter should be used on the output lines at the closest point.
(3- to 50-W models: S82Y-JF3-N, 90- and 100-W models: S82Y-JF6-N)
4. To ensure the Emission Enclosure rating, a ferrite ring core should be used on all cables (for S82K-P24024).
5. Models other than dual output models satisfy the Class-2 requirements.
6. To meet Class-2 requirements with the 100-W model, either a fuse or circuit breaker that is UL listed or CSA certified, and rated
at 4.2 A max. should be wired in series with the load to be connected to the power supply. Only then can the power supply output be considered as meeting Class 2.
6
S82K
S82K
REFERENCE VALUE
Item
Value
Definition
Reliability (MTBF)
135,000 hrs min.
MTBF stands for Mean Time Between Failures, which is calculated according to the
probability of accidental device failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
Life expectancy
8 yrs. min.
The life expectancy indicates average operating hours under the ambient
temperature of 40°C and a load rate of 50%. Normally this is determined by the life
expectancy of the built-in aluminum electrolytic capacitor.
Engineering Data
DERATING CURVE
3-/7.5-/15-/30-/50-/90-W/
100-W Models
240-W Model
Single-Unit Operation
Parallel-Unit Operation
Installation A
Installation A
Installation B
S82K-03005
Installation A
S82K-P24024:
100-VAC input
(see note)
Load (%)
200-VAC input
Load (%)
Load (%)
Installation A
S82K-P24024:
100-VAC input
Ambient temperature (°C)
Ambient temperature (°C)
Note: When using the 7.5-W single-output
models within the input voltage range
between 90 and 110 VDC, the load
rate will become 90% or less.
When using the 90-W model at an
ambient temperature exceeding
25°C, the load rate will become 90%
or less.
Ambient temperature (°C)
Note: 100-V input: 85 to 132 VAC
Mounting Position
The derating curve can be ensured for these two kinds of installations.
(A) Standard (Vertical) Installation
Top
(B) Horizontal Installation
Top
Note: Not permitted for 240-W models.
7
S82K
S82K
OVERLOAD PROTECTION
The Power Supply has an overload protection function that
protects the load and the power supply from possible damage by
overcurrent. When the output current rises above a set value
(105% of the rated output current of most models; 101% of the
rated output current for 90-W model), the protection function is
triggered, decreasing the output voltage. When the output current
falls within the rated range, the overload protection function is
automatically cleared.
OVERVOLTAGE PROTECTION
(S82K-24024T MODELS ONLY)
The Power Supply is provided with an overvoltage protection
function that protects the load and the Power Supply from
possible damage by overvoltage. When the output voltage rises
above a set value, the protection function is triggered, shutting off
the output voltage. If this occurs, reset the Power Supply by
turning it off for 1 minute min. and then turning it on again.
When using the 90-W model at an ambient temperature
exceeding 25°C, the protection function will operate at a current
of 92% of the rated load current.
Note: To avoid damage to the unit or deterioration of the internal
circuitry, do not short-circuit the output terminals of the
S82K or use the S82K with excessive output current for a
long time.
Output voltage (V)
3-/7.5-/15-/90-W/100-/240-W Models
Rated voltage
Output current (%)
Output voltage (V)
30-/50-W Models
Rated voltage
Intermittent
operation
0
50
100
Output current (%)
When Using ± Output Models
The +V output detects the total output power (+V output and
–V output) to trigger the short-circuit protection against
overcurrent. This protection varies depending on the -V output
state. The –V output independently triggers the short-circuit
protection.
8
Output voltage (V)
When using the 7.5-W single-output models within the input
voltage range between 90 and 110 VDC, the protection function
will operate at a current of 95% of the rated load current.
Overvoltage
protection
operating
10%
Rated output
voltage
–10%
Variable range
S82K
S82K
INRUSH CURRENT, RISE TIME, HOLD TIME
Input OFF
Input ON
AC input
voltage
Inrush current on input application
AC input
current
96.5%
90%
Output
voltage
Rise time: 100 to 1000 ms
max. depending on the
model.
Hold time
(20 ms min.)
Operation
UNDERVOLTAGE ALARM INDICATOR AND OUTPUT FUNCTION
(ALL MODELS EXCEPT S82K-24024/P24024)
If the output voltage at the output terminal drops to 75% to 90% of the rated voltage, the red indicator of the S82K (DC LOW indicator) will
be lit. In the case of the S82K-10024/24024T, a voltage drop alarm will be output via the relay available in the models (DC LOW output).
This function detects the voltage at the output terminal of the Power Supply. To check the precise output voltage, measure the voltage at
the terminal of the load.
Voltage
Indicator
Green:
DC ON
Red:
DC LOW
Green:
DC ON
If the voltage at the output terminal is more than 90%
of the rated voltage, the green indicator will be lit.
(see note 1)
Red:
DC LOW
Green:
DC ON
Red:
DC LOW
Operation of 09024/10024/24024T’s
output (DC LOW output)
(see note 2)
If the voltage at the output terminal is 75% to 90%,
the red indicator will be lit.
If the voltage at the output terminal is 0 V, both the
green and red indicators will not be lit.
Note: 1. The more the voltage at the output terminal drops, the darker both the green and red indicators will be.
2. The relay contacts have a capacity of 0.1 A at 24 VDC.
9
S82K
S82K
BLOCK DIAGRAMS
S82K-003 (3 W)
S82K-007 (7.5 W, Single Output)
Fuse (1 A)
+V
AC (L)
Noise filter
–V
AC (N)
Inrush current Rectifier
protection circuit
Rectifier
Undervoltage
alarm
indicator
Drive control
circuit
Overload
alarm
circuit
Detector
Photocoupler
S82K-007 (7.5 W, Dual Outputs)
Fuse (1 A)
–V
AC (L)
Noise filter
AC (N)
Inrush current Rectifier
protection circuit
Rectifier
3-terminal
REG
+V
Undervoltage
alarm
indicator
Drive control
circuit
Rectifier
Overload
alarm
circuit
Detector
Photocoupler
S82K-015 (15 W)
S82K-030 (30 W)
S82K-05024 (50 W)
Fuse (3 A)
+V
AC (L)
Noise filter
–V
AC (N)
Inrush current Rectifier
protection circuit
Rectifier
Undervoltage
alarm
indicator
Drive control
circuit
Overload
alarm
circuit
Detector
Photocoupler
10
S82K
S82K
S82K-09024 (90 W)
S82K-10024 (100 W)
Fuse (5 A)
Rectifier
+V
AC (L)
Noise filter
–V
AC (N)
Rectifier
Inrush current
protection circuit
100 or 200 V
Selectable
terminals
(See Note.)
DC LOW
Undervoltage
alarm
indicator/output
Drive control
circuit
Overload
alarm
circuit
Detector
Photocoupler
Note: Use the short bar to short-circuit terminals 7 and 8 to select 100 to 120 VAC and remove the short bar to select
200 to 240 VAC.
S82K-24024 (240 W)
Fuse (5 A)
AC (L)
INPUT
Noise filter
AC (N)
Inrush current
Rectifier
protection circuit
100 or 200 V
Selectable
terminals
(See Note 2.)
Rectifying and
smoothing circuit
Drive control
circuit
+V
DC
OUTPUT
–V
Detector
GR
DC LOW
Photocoupler
Overload alarm
circuit
Overvoltage
alarm circuit
Undervoltage
alarm
indicator/output
(See Note 3.)
Overvoltage protection circuitry (see note 1)
Note: 1. The overvoltage protection circuitry is available in the S82K-24024T only.
2. Use the short bar to short-circuit terminals 7 and 8 to select 100 to 120 VAC and remove the short bar to select
200 to 230 VAC.
3. The undervoltage alarm indicator is available in the S82K-24024T.
S82K-P24024 (240 W)
Fuse (8 A)
AC (L)
INPUT
+V
DC
OUTPUT
Noise filter
AC (N)
Inrush current
protection circuit
Rectifier
Harmonic current Smoothing
emission control
Rectifying and
smoothing circuit
–V
Drive control
circuit
Overload alarm
circuit
Detector
Photocoupler
GR
11
S82K
S82K
Dimensions
Unit: mm (inch)
S82K-003 (3 W)
S82K-007 (7.5 W)
37.5
(1.48)
9.8
8.3
Mounting Brackets
(Supplied with the Power Supply)
65 (2.56)
Used when not mounting the Power Supply
directly on the DIN rail.
75
(2.95)
45
Two,
4.5 dia.
35
58.1
25
35
4.6
(sliding
7 max.)
27
37.5
4
M3.5 with square washer
Mounting Holes
Attached
Mounting Bracket
M4 or 4.5-dia. hole
27
L
(See Note.)
Note: If more than one Power Supply is installed
in a row, keep a distance of 20 mm min.
(L = 20 mm min.) between each adjacent
Power Supply.
S82K-015 (15 W)
45
(1.77)
9.8 8.3
7.5
45
75 58.1
(2.95)
35
91 (3.58)
5
M3.5 with square
washer
4.6
(sliding
7 max.)
Mounting Holes
Two, M4 or 4.5-dia. mounting holes
60
(2.36)
L
(See Note.)
12
35
Note: If more than one Power Supply is installed in a row,
keep a distance of 20 mm min. (L = 20 mm min.)
between each adjacent Power Supply.
S82K
S82K
Unit: mm (inch)
S82K-030 (30 W)
S82K-05024 (50 W)
90 (3.54)
80
Four, 4.5 dia.
58.1
60
75
(2.95)
7.5
45
35.2
M3.5 with square washer
4
(sliding
7 max.)
91 (3.58)
5
Mounting Holes
Four, M4 or 4.5-dia. mounting holes
60
(2.36)
L
(See Note.)
Note: If more than one Power Supply is installed in a
row, keep a distance of 20 mm min. (L = 20 mm
min.) between each adjacent Power Supply.
80 (3.15)
S82K-09024 (90 W)
S82K-10024 (100 W)
145 (5.71)
Four, 4.5 dia.
135
9.8
8.3
7.5
75
58.1
(2.95)
60
45
35.2
91 (3.58)
4
(sliding
7 max.)
M3.5 with square washer
5
M3.5 terminal screw
Short bar
Mounting Holes
Four, M4 or 4.5-dia. mounting holes
60
(2.36)
L
(See
Note.)
Note: If more than one Power Supply is installed
in a row, keep a distance of 20 mm min. (L
= 20 mm min.) between each adjacent
Power Supply.
135 (5.31)