E5EF for pdf

E5EF for pdf
Fuzzy Temperature Controllers
E5EF
1/8 DIN Controllers Combine Fuzzy and PID Control
For Fast Response to Process Disturbances
■ Advanced PID control for optimal response
during start-up and steady-state operation
■ Fuzzy and PID control work together to
correct a process upset quickly, with minimal
overshoot
■ Fuzzy parameters can be changed to adjust
fuzzy control's impact on the process
■ Accuracy to ±0.3% of set value
■ Field-selectable temperature ranges, °F/°C
scaling, and sensor input types
■ Plug-in outputs for field interchangeability
■ Communications function, heater burnout
alarm and 8-bank models available
■ 3-year warranty
Ordering Information
■ TEMPERATURE CONTROLLERS
Order one control output separately below. For example, E5EF-A02TC-F with E53-S SSR output unit. For heater burnout models, be
sure to order a current transformer. To order models marked for degrees Celsius, omit the "F" at the end of the part number.
Controller type
Input type
No communications
RS-422 communications
RS-485 communications
8-bank program memory
Part number
Standard
Thermocouple (10 types)
E5EF-ATC-F
E5EF-A02TC-F
E5EF-A03TC-F
E5EF-BATC-F
Platinum RTD
E5EF-AP-F
E5EF-A02P-F
E5EF-A03P-F
E5EF-BAP-F
Heater burnout type*
Thermocouple (10 types)
E5EF-AHTC-F
E5EF-AH02TC-F
E5EF-AH03TC-F
E5EF-BAHTC-F
Platinum RTD
E5EF-AHP-F
E5EF-AH02P-F
E5EF-AH03P-F
E5EF-BAHP-F
* Current Output E53-C may not be used with heater burnout type controllers.
Temperature Ranges
Sensor input type
Temperature
range
Unit of measure
Sensor input type
Temperature
range
Unit of measure
°C
°F
°C
°F
Thermocouple
Type K
Type J/L
-200 to 1,300
-100 to 850
-300 to 2,300
-100 to 1,500
1° C or F, main setting and alarm
Type T/U
-200 to 400
-300 to 700
Type E
0 to 600
0 to 1,100
Type R/S
0 to 1,700
0 to 3,000
Type B
100 to 1,800
300 to 3,200
Type N
0 to 1,300
0 to 2,300
Platinum RTD (Pt100 or JPt100)
-99.9 to 450.0
-99.9 to 800.0
0.1° C or F, main setting and alarm
■ CONTROL OUTPUT UNITS
Output type
Part number
Relay
output*
E53-R
SSR
output
E53-S
Voltage output (for driving SSR)
12 VDC (NPN)
24 VDC (NPN)
E53-Q
E53-Q3
24 VDC (PNP)
E53-Q4
Current
output
E53-C
E5EF
E5EF
Advanced PID Control Improved with Fuzzy Control
Omron's E5EF temperature controllers combine advanced PID
control with Fuzzy Logic control to improve responsiveness to
external process disturbances, events that cause a clear offset
between the process and set temperatures.
Omron's advanced PID control and Fuzzy Logic control operate
in parallel. The PID control operates during normal conditions,
while the Fuzzy Logic control operates only when there has
been an external disturbance to the process. The start-up and
stable state operation is identical to Omron's conventional PID
controllers. The output of the E5EF is the sum total of the
output of the PID and fuzzy control functions. Both PID and
fuzzy scale parameters can be set automatically by autotuning, or may be manually set.
There are three fuzzy parameters users can set, and the
illustrations show the impact of each one:
■ FUZZY INTENSITY
Fuzzy intensity (FU1) determines the impact of the Fuzzy
Logic section of the control algorithm, on the final control output
percentage. This parameter is the nominal value which can be
set from 0 to 99%. Default setting is 50%. When set to 0%,
fuzzy control will have no influence, and the unit will function as
a PID controller (like Omron's E5EX). As this value is
increased, the corrective actions taken by the controller will
become larger. The FU1 value should be increased in
applications where quicker neutralization of a process
disturbance is required, and/or overshoot on the recovery from
the disturbance needs to be further minimized.
Small
Fuzzy
intensity
Large
FUS1
Small
■ FUZZY SCALE 1
Fuzzy Scale 1 (FUS1) controls the magnitude of error
"membership function". This value corresponds to what the
controller should consider to be a "large" error and can be set
in a range of 0.2° to 999.9° (C or F). Default setting is 40°. For
every sample the controller compares the present error to
FUS1 value in order to make a subjective decision about the
size of the error. Decreasing this value makes the controller
more sensitive to error, and will decrease the response time for
returning the process back to set value.
Large
■ FUZZY SCALE 2
Large
FUS2
Small
Fuzzy Scale 2 (FUS2) controls the rate-of-change "membership function". This value corresponds to what the controller
should consider a "large" rate of change, and can be set in a
range from 0.20° to 99.9° (C or F) per second. For every
sample the controller compares the present rate-of-change to
the FUS2 value in order to make a subjective decision about
the size of the change. Decreasing this value will make the
controller more sensitive to change. Because small changes in
this value can cause a large increase in oscillations, best
results can usually be achieved by manually setting FU1 and
FUS1 and leaving FUS2 at the auto-tuned value.
■ COMBINED EFFECTS OF FUZZY ADJUSTMENTS
Correcting large overshoot
without hunting with an increase
in Fuzzy Intensity
2
Eliminating small overshoot and
lengthening stabilization time by
decreasing Fuzzy Scale 1
Eliminating large overshoot and
shortening hunting time by
increasing Fuzzy Intensity and
Fuzzy Scale 1
E5EF
E5EF
Specifications
Supply voltage
Operating voltage
Power consumption
Control
Number
output
Type
100 to 240 VAC, 50/60 Hz
85 to 110% of rated supply voltage
Approx. 10 VA at 100 VAC to 15 VA at 240 VAC
One output unit, ordered separately; mounts in internal socket of Standard E5EF-A and heater
burnout E5EF-AH types
Relay*
SPDT, 5 A, 250 VAC (resistive load) using E53-R output unit
SSR
SPST-NO, 1 A, 75 to 250 VAC using E53-S output unit
Voltage 40 mA, 12 VDC, NPN, using E53-Q output unit with short-circuit protection
20 mA, 24 VDC, NPN, using E53-Q3 output unit with short-circuit protection
20 mA, 24 VDC, PNP, using E53-Q4 output unit with short-circuit protection
Current 4 to 20 mA DC, 600 Ω max. load, 8-bit resolution using E53-C output unit.
Current output unit cannot be used with heater burnout type E5EF-AH.
Isolation
All output units are optically isolated from the internal circuits
Hysteresis
0.0 to 999.9 °C/°F in units of 0.1 (during ON/OFF control action)
Update
Output
500 ms for pulse output
time
Display 500 ms
Service life
100,000 electrical operations minimum for relay output unit E53-R
10 million mechanical operations minimum for relay output unit E53-R
Alarm
Number
Two SPST-NO relays, 3 A, 250 VAC for E5EF-A; one SPST-NO relay for E5EF-AH
output
Setting range
Thermocouple: -999 to 9,999 °C/°F
Platinum RTD: -99.9 to 999.9 °C/°F
Heater burnout
Type
SPST-NO relay, 1 A, 250 VAC
output E5EF-H
Setting range
0.1 to 49.9 A in units of 0.1 A
only
0.0 setting disables the output
50.0 setting turns output ON continuously
Minimum detectable 200 ms; heater current is not measured when the control output is ON less than 200 ms
ON time
Indication
General
±0.3% of set value or ±1°, whichever is greater, ±1 digit maximum
accuracy
Exceptions
Accuracy of types T and U thermocouples is ±2°C (3.6°F) from -150° to 400°C (-240 to 700°F),
±1 digit. Accuracy is not guaranteed below -150°C (-240°F).
Accuracy of types R and S thermocouples is ±3°C (±5.4°F) from 0° to 200°C (32° to 400°F),
±1 digit.
Accuracy of type B thermocouples is not guaranteed at or below 400°C (750°F).
Heater burnout
±5% of full scale, ±1 digit maximum of heater current
Display Range
-9999 to 9999 (limited by input type)
Setting accuracy
Set value coincides with the indicated value, since no relative error exists between both values
Control
Type
ON/OFF or auto-tuning PID and fuzzy control to prevent overshoot
modes
Proportional band
P = 0.0 to 999.9 °C/°F in units of 0.1°
Reset time
I = 0 to 3,999 seconds in units of 1 second
Rate time
D = 0 to 3,999 seconds in units of 1 second
Control period
Pulse output: 1 to 99 seconds in units of 1 second
Sampling period
500 ms
Fuzzy intensity
FU = 0 to 99% in units of 1%; factory set to 50% for general-purpose control applications
Fuzzy scale 1
FUS1 = 0.2 to 999.9 °C or °F in units of 0.1°; factory set to 40.0°C
Fuzzy scale 2
FUS2 = 0.20 to 99.99 °C or °F/sec2 in units of 0.01 °F or °C/sec2; factory set to 0.47°C/sec2
Memory protection
Non-volatile memory (EEPROM)
Other
Shift set input
Sets a second set point. Requires no-voltage contact signal with input impedance of
functions
E5EF-A only
100 Ω max.
Thermocouple range: -999 to 9,999 °C/°F
Platinum RTD range: -99.9 to 999.9 °C/°F
Input shift,
Offsets input value and display value to accommodate a sensor input that deviates
all models
by a known value.
Thermocouple range: -999 to 9,999 °C/°F
Platinum RTD range: -99.9 to 999.9 °C/°F
Miscellaneous
Upper and lower set value limits, setting key disable, °C/°F selectable internally, input shift,
shift set (not on heater burnout models) Normal and Reverse output selection, Watchdog
function to detect CPU failure and restore CPU to normal operation.
*Note: If control period is less than 5 seconds, use solid state relay or voltage relay.
3
E5EF
E5EF
SPECIFICATIONS (continued)
Indicators
Materials
Mounting
Connections
Weight
Enclosure
ratings
Approvals
Front panel
Rear panel
Terminals
UL
CSA
Operating
Storage
Ambient
temperature
Humidity
Insulation resistance
Dielectric strength
Vibration Mechanical durability
Malfunction durability
Shock
Mechanical durability
Malfunction durability
Present Value (green LED), 11 mm H (0.43 in); Set Value (red LED), 8 mm H (0.32 in);
Bank Number (orange LED), 8 mm H (0.32 in); LED indicators for all functions
Plastic case
Fits 1/8 DIN panel cutouts; includes two panel mounting brackets
Plated steel screw terminals mounted on rear of unit
Approx. 310 g (10.9 oz.), with communications 360 g (12.7 oz.)
IEC IP50, NEMA 4 with optional cover Y92A-49N
IEC IP20
IEC IP00
Recognized, File Number E68481 (all models)
Certified, File Number LR59623 (all models)
-10° to 55°C (14° to 131°F)
-25° to 65°C (-13° to 149°F)
35 to 85% RH
20 MΩ minimum at 500 VDC, measured with an output unit installed
2,000 VAC, 50/60 Hz for 1 minute between terminals of different polarity, measured with an
output unit installed
10 to 55 Hz, 0.75 mm (0.03 in) in X, Y, and Z directions for 2 hours each
2 to 5 Hz, 2 G, in X, Y, and Z directions for 10 minutes each
300 m/s2 in 6 directions, 3 times each
200 m/s2 in 6 directions, 3 times each
■ COMMUNICATIONS FEATURES
Output type
Transmission method
Maximum cable length
Synchronization method
Transmission rate
Transmission code
Write to controller
functions
Read from controller
functions
System limits
RS-422
RS-485
4-wire half duplex 2-wire half-duplex
500 m (1,640 ft)
Start-stop
150/300/600/1,200/2,400/4,800/9,600 bps
ASCII (7 bits)
Set temperature, alarm value, proportional band, integral time, rate time, auto-tuning start/stop, fuzzy
intensity, fuzzy scales 1 and 2, heater burnout alarm set value (E5EF-H)
Set temperature, alarm value, proportional band, reset time, rate time, output variable, process value,
fuzzy intensity, fuzzy scales 1 and 2, heater burnout current and current transformer
input value (E5EF-H)
A maximum of 32 temperature controllers can be
connected to one host computer in serial communication
■ CURRENT TRANSFORMERS (for E5EF-H)
Heater current
Weight
Dielectric strength
Vibration
Maximum 50 A continuous service, single-phase
Approx. 11.5 g (0.41 oz.) for E54-CT1; approx. 50 g (1.8 oz.) for E54-CT3
1,000 VAC
50 Hz (approx. 10 G)
■ CURRENT TRANSFORMERS FOR HEATER-BURNOUT CONTROLLERS
Hole diameter
Part number
5.8 mm (0.23 in)
E54-CT1
*Note: If control period is less than 5 seconds, use solid state relay or voltage relay.
4
12.0 mm (0.47 in)
E54-CT3
E5EF
E5EF
Dimensions
Unit: mm (inch)
■ TEMPERATURE CONTROLLERS
48
(1.89)
112
(4.41)
89
(3.5)
12
6-15
11
96
(3.78)
Mounting
screw
Panel cutout
45+0.6
-0
(1.77)
Side-by-side mounting of
several controllers
L
92+0.8
-0
(3.62)
92+0.8
-0
(3.62)
120 min
(4.72)
L = (48N-3)+1
-0
For side-by-side mounting:
L = 48 mm x Number of units - 3 mm
= (1.89 in x Number of units - 0.12 in)
■ CURRENT TRANSFORMERS (for E5EF-H)
E54-CT1
E54-CT3
15
(0.59)
7.5
(0.3)
2.8
(0.11)
2.36
(0.09)
dia.
30
(1.2)
25
(0.98)
5.8
(0.23)
dia.
10.5
(0.41)
9 (0.35)
3
(0.12)
40
(1.6)
12 (0.47) dia.
10
(0.39)
21
(0.83)
30
(1.2)
40
(1.6)
Two, 3.5
(0.14) dia.
holes
5
(0.2)
30
(1.2)
5
(0.2)
15
(0.59)
40
(1.6)
5
E5EF
E5EF
Nomenclature
■ E5EF-A STANDARD CONTROLLERS
12. Auto-tuning
(AT) indicator
1. Process value
(PV) indicator
Key
1.
2.
3. Alarm (ALM1)
indicator
2. Set value
(SV) indicator
3.
4.
5.
6.
4. Alarm (ALM2)
indicator
11. Output (OUT)
indicator
7.
5. Up key
10. Mode key
8.
9.
10.
6. Auto-tuning
(AT) key
9. Level key
8. Front cover
11.
12.
Indicator lights when alarm 1 output is ON.
Indicator lights when alarm 2 output is ON.
Up key increases the value of any parameter
when pressed.
Automatic tuning of parameters is executed when
the AT key is pressed for 1 second or more. To
stop auto-tuning press the key for 1 second or more.
Down key decreases the value of any parameter
when pressed.
Front cover shows setting symbols.
Level key, pressed for 2 seconds or more,
selects the next of three parameter setting levels.
Mode key changes the items to be set, such as
alarm value, etc.
Output indicator lights when control output is ON.
Automatic tuning indicator flashes at 1-second
intervals while tuning is executed, then stops
when completed.
7. Down key
■ E5EF-AH STANDARD HEATER BURNOUT TYPE
13. Heater burnout
(HB) indicator
1. Process value
(PV) indicator
2. Set value
(SV) indicator
12. Auto-tuning
(AT) indicator
Key
1.
2.
Description
Process value indicator displays the process
temperature and indicates the parameter being
displayed on the SV (Set Value) display and error
messages.
Set value indicator.
3.
4.
Lights when sensor error is detected.
Indicator lights when alarm output is ON.
5.
Up key increases the value of any parameter when
pressed.
6.
Automatic tuning of parameters is executed when
the AT key is pressed for 1 second or more. To
stop auto-tuning press the key for 1 second or more.
Down key decreases the value of any parameter
when pressed.
Front cover shows setting symbols.
Level key, pressed for 2 seconds or more,
selects the next of three parameter setting levels.
Mode key changes the items to be set, such as
alarm value, etc.
Output indicator lights when control output is ON.
Automatic tuning indicator flashes at 1-second
intervals while tuning is executed, then stops
when completed.
Lights when a heater burnout is detected and stays
lit until reset.
3. Sensor error
indicator
11. Output (OUT)
indicator
10. Mode key
4. Alarm
indicator
7.
5. Up key
8.
9.
6. Auto-tuning
(AT) key
9. Level key
10.
7. Down key
11.
12.
13.
8. Front cover
6
Description
Process value indicator displays the process
temperature and indicates the parameter being
displayed on the SV (Set Value) display and error
messages.
Set value indicator.
E5EF
E5EF
■ E5EF-BA 8- BANK TYPE
■ E5EF-BAH HEATER BURNOUT TYPE
WITH 8- BANK MEMORY
Note:
Models with 8-bank program memory
have the same indicators and keys as
standard models. The bank number (BK)
display is to the left of the set value (SV)
display.
Bank number
indicator shows
the currently
selected
memory bank.
■ E5EF-A02/-A03 SERIAL
COMMUNICATIONS TYPE
■ E5EF-AH02/-AH03 HEATER BURNOUT TYPE
WITH SERIAL COMMUNICATIONS
Key
Description
1.
The Remote (RMT) key initiates
and breaks on-line communications.
Remote mode indicator stays lit
during on-line communications.
Automatic tuning of parameters is
executed when the Mode and Level
keys are pressed simultaneously
for 1 second or more. To stop autotuning press both keys for 1
second or more.
2.
2. Remote
indicator
(RMT)
Note
1. Remote
key (RMT)
7
E5EF
E5EF
Connections
■ STANDARD CONTROLLERS (E5EF-A)
For current
output
9
For voltage
output
+
9
8
-
+
9
Control
output
12 VDC 40 mA
4 to 20 mA
8
For relay or
SSR output
8
-
9
FG
17
Ground FG terminal 17 to avoid noise interference.
8
16
to 240 VAC
~ 100
50/60 Hz
7
Alarm output 1
15
6
Alarm output 2
14
5
13
4
12
12
3
11
11
10
10
-
B
B
11
2
SP SHIFT
Note: Do not connect unused terminals.
10
+
1
Use these terminals
when connecting a
thermocouple.
A
Use these terminals when
connecting a platinum resistance thermometer.
■ HEATER BURNOUT TYPE STANDARD CONTROLLERS (E5EF-AH)
For voltage
output
9
For relay or
SSR output
+
9
Control
output
12 VDC 40 mA
8
8
-
9
FG
17
Ground FG terminal 17 to avoid noise interference.
8
16
to 240 VAC
~ 100
50/60 Hz
7
Alarm output
Heater burnout alarm output**
15
6
Current Transformer (CT)*
14
CT
5
13
4
12
12
3
11
11
10
10
-
B
B
11
2
1
SP SHIFT
Note: *The current transformer must be the E54-CT1 or
E54-CT3. Other current transformer cannot be
connected.
**The heater burnout alarm goes ON when the E5EF
detects a sensor failure or heater burnout.
10
+
Use these terminals
when connecting a
thermocouple.
A
Use these terminals when
connecting a platinum resistance thermometer.
■ 8-BANK TYPES (E5EF-BA-F)
For current
output
9
For voltage
output
+
9
4 to 20 mA
8
-
For relay or
SSR output
+
9
12 VDC 40 mA
8
-
8
Control
output
9
FG
17
Ground FG terminal 17 to avoid noise interference.
8
16
7
Alarm output 1
Alarm output 2
15
to 240 VAC
~ 100
50/60 Hz
6
14
5
13
BANK2
4
BANK1
3
BANK0
2
12
1
Note: Do not connect unused terminals.
8
12
11
11
10
10
+
Use these terminals
when connecting a
thermocouple.
B
B
11
10
A
Use these terminals when
connecting a platinum resistance thermometer.
E5EF
E5EF
■ 8-BANK TYPES WITH HEATER BURNOUT (E5EF-BAH-F)
For voltage
output
For relay or
SSR output
+
9
9
Control
output
12 VDC 40 mA
8
8
-
9
FG
17
Ground FG terminal 17 to avoid noise inte
8
16
to 240 VAC
~ 100
50/60 Hz
7
Alarm output
15
6
Heater burnout alarm output**
14
5
Current Transformer (CT)*
13
BANK2
4
CT
12
BANK1
3
BANK0
2
11
11
10
10
-
B
11
10
+
1
Note: *The current transformer must be the E54-CT1 or
E54-CT3. Other current transformer cannot be connected.
**The heater burnout alarm goes ON when the E5EF
detects a sensor failure or heater burnout.
B
12
Use these terminals
when connecting a
thermocouple.
A
Use these terminals when
connecting a platinum resistance thermometer.
■ RS-422 COMMUNICATIONS (E5EF-A02-F)
For current
output
9
For voltage
output
+
8
+
9
4 to 20 mA
9
Control
output
12 VDC 40 mA
8
-
For relay or
SSR output
8
-
9
FG
17
Ground FG terminal 17 to avoid noise interference.
8
16
to 240 VAC
~ 100
50/60 Hz
7
Alarm output 1
15
6
Alarm output 2
14
SDB
5
13
SDA
4
RDB
3
RDA
2
SG
1
12
Note: Do not connect unused terminals.
12
11
11
10
10
-
B
B
11
10
+
Use these terminals
when connecting a
thermocouple.
A
Use these terminals when
connecting a platinum resistance thermometer.
■ HEATER BURNOUT TYPES WITH RS-422 COMMUNICATIONS (E5EF-AH02-F)
For voltage
output
9
For relay or
SSR output
+
9
12 VDC 40 mA
8
-
8
Control
output
9
FG
17
Ground FG terminal 17 to avoid noise in
8
16
7
Alarm output
Heater burnout alarm output**
15
to 240 VAC
~ 100
50/60 Hz
6
14
5
13
SDA
4
RDB
3
RDA
2
SG
1
SDB
Current Transformer (CT)*
CT
12
Note: *The current transformer must be the E54-CT1 or
E54-CT3. Other current transformer cannot be connected.
**The heater burnout alarm goes ON when the E5EF
detects a sensor failure or heater burnout.
12
11
11
10
10
+
Use these terminals
when connecting a
thermocouple.
B
B
11
10
A
Use these terminals when
connecting a platinum resistance thermometer.
9
E5EF
E5EF
■ RS-485 COMMUNICATIONS (E5EF-A03-F)
For current
output
9
For voltage
output
+
8
+
9
4 to 20 mA
9
Control
output
12 VDC 40 mA
8
-
For relay or
SSR output
8
-
9
FG
17
Ground FG terminal 17 to avoid noise interference.
8
16
to 240 VAC
~ 100
50/60 Hz
7
Alarm output 1
15
6
Alarm output 2
SDB
14
5
13
B
4
A
3
SG
2
12
12
11
11
10
10
1
Note: Do not connect unused terminals.
-
B
B
11
10
+
Use these terminals
when connecting a
thermocouple.
A
Use these terminals when
connecting a platinum resistance thermometer.
■ HEATER BURNOUT TYPES WITH RS-485 COMMUNICATIONS (E5EF-AH03-F)
For voltage
output
9
For relay or
SSR output
+
9
Control
output
12 VDC 40 mA
8
8
-
9
FG
17
Ground FG terminal 17 to avoid noise interfere
8
16
7
Alarm output
Heater burnout alarm output**
15
6
14
5
13
B
to 240 VAC
~ 100
50/60 Hz
4
Current Transformer (CT)*
CT
12
A
SG
12
3
11
11
10
10
-
B
B
11
2
1
Note: *The current transformer must be the E54-CT1 or
E54-CT3. Other current transformer cannot be connected.
**The heater burnout alarm goes ON when the E5EF
detects a sensor failure or heater burnout.
+
Use these terminals
when connecting a
thermocouple.
10
A
Use these terminals when
connecting a platinum resistance thermometer.
■ E5EF-AH OVERALL SYSTEM CONNECTIONS
Heater burnout and
sensor failure alarm
Current Transformer
Connected to
temperature
controller
9
17
8
16
7
15
6
14
5
13
4
Connected to heater
12
3
11
-
2
10
1
+
Temperature Controller
10
Heater
*
200 VAC
This wiring must be passed through the
hole of the current transformer. The current
transformer can be connected to the
temperature controller in any polarity.
E5EF
E5EF
Omron
Europe
B.V. EMA-ISD,
tel:+31 23 5681390, fax:+31 23 5681397, http://www.eu.omron.com/ema
OMRON
ELECTRONICS,
INC.
OMRON CANADA, INC.
One East Commerce Drive
Schaumburg, IL 60173
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC TC12
1/99