PC2001142 FCM-1 Module
DETECTION AND CONTROL EQUIPMENT
DATA SHEET
®
One Stanton Street
Marinette, WI 54143
FCM-1 CONTROL MODULE
either manually or through panel programming, on a
select (zone or area of coverage) basis.
FlashScan (patent pending) is a new communication protocol that greatly enhances the speed of communication
between analog intelligent devices. Intelligent devices
communicate in a grouped fashion. If one of the devices
within the group has new information, the panel CPU
stops the group poll and concentrates on single points.
The net effect is response speed greater than five times
that of other designs.
Part No. 428101
CB500
004749
Features
• Built-in type identification automatically identifies these
devices to the control unit
• Internal circuitry and relay powered directly by two-wire
SLC loop; requires power (for horns, strobes, etc.),
audio (for speakers), or a telephone riser (for handsets)
• Integral LED blinks green each time a communication
is received from the control unit and turns on in steady
red when activated
• LED blink may be deselected globally (affects all
devices)
• High noise immunity (EMF/RFI)
• Switch between 24-volt NAC power, audio (up to 70.7
VRMS) or telephone
• Wide viewing angle of LED
• SEMS screws with clamping plates for wiring ease
• Direct-dial entry of address (01-159)*
• Speaker, audible/visual, and telephone applications
may be wired for Class B or A (Style Y or Z)
• Face plate is made of off-white Noryl®
• Configured for a single Class B (Style Y) or Class A
(Style Z) Notification Appliance Circuit
• FlashScan™ (patent pending) communication protocol
Applications
The FCM-1 Addressable Control Module provides the
PCR-400 control unit a circuit for Notification Appliances
(horns, strobes, speakers, etc.) or monitors a telephone
circuit. Addressability allows the FCM-1 to be activated,
Description
Each FCM-1 Control Module uses one of 159* possible
module addresses on a SLC loop. It responds to regular
polls from the control unit and reports its type and status,
including the open/normal/short status of its Notification
Appliance Circuit (NAC). The LED blinks with each poll
received. On command, it activates its internal relay. The
FCM-1 supervises Class B (Style Y) or Class A (Style Z)
notification or control circuits. The FCM-1 can be used to
replace the CMX-2 module, Part No. 417479, in existing
systems.
Upon code command from the unit, the FCM-1 will disconnect the supervision and connect the external power
supply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication to the panel that the control relay actually turned
ON. The external power supply is always relay isolated
from the communication loop so that a trouble condition
on the external power supply will never interfere with the
rest of the system.
Rotary switches set a unique address for each module.
The address may be set before or after mounting. The
built-in TYPE CODE (not settable) will identify the module to the control panel, so as to differentiate between a
module and a sensor address.
The FCM-1 is used to switch 24 VDC audible/visual
power, high-level audio (speakers), or control telephone
devices.
Technical Information
Normal Operating Voltage: . . . . . . . . . . . 15 to 32 VDC
Maximum Current Draw: . . . . . . . . . . 5.1 mA (LED on)
Average Operating Current: . . . . 390 µA (LED flashing)
External Supply Voltage . . . max 80 volts (RMS or DC)
between T3 and T4:
Drain on External. 2 µA max. (using internal EOL relay)
Supply:
EOL Resistance: . . . . . . . . . . . . . . . . . . . . . 47 K ohms
Temperature Range: . . 32 °F to 120 °F ( 0 °C to 49 °C)
Humidity Range: . . . . . . . 10% to 93% non-condensing
NAC RATINGS
Load
Description
Resistive
Resistive
Resistive
Resistive
Inductive )
(L/R = 5 ms
Inductive
(L/R = 2 ms)
Inductive
(PF = 0.35 )
Listings and Approvals*
UL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S3705
ULC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CS669
Factory Mutual Research Corporation . . . . . . Approved
(FMRC)
California State Fire Marshal (CSFM) . . 7300-0028:202
MEA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457-99-E
Maryland State Fire Marshal . . . . . . . . . Permit # 2020
Application
Non-Coded
Coded
Non-Coded
Non-Coded
Coded
Maximum
Voltage
30 VDC
30 VDC
110 VDC
125 VAC
30 VDC
Current
Rating
3.0 A
2.0 A
0.9 A
0.9 A
0.5 A
Coded
30 VDC
1.0 A
Ordering Information
0.5 A
Part
No.
Non-Coded
125 VAC
NOTE: The CB500 barrier is required by U.L. for separating power-limited and non-power limited wiring in the
same junction box.
* Listings and Approvals are under NOTIFIER Division of Pittway Corporation
Shipping
Weight
lb.
(kg)
Description
428101 FCM-1 Intelligent
Control Module
1
(0.45)
FlashScan is a trademark of Notifier.
Noryl is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
* 01-99 with PCR-400
TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Y
•
•
•
•
CONNECT MODULES TO CONTROL UNITS
ALL WIRING SHOWN IS SUPERVISED
WIRES MUST BE SUPERVISED PER NFPA
MODULE POLARITIES ARE SHOWN IN ALARM
TO NEXT
DEVICE
COMMUNICATION LINE – 32
VDC MAXIMUM. TWISTED-PAIR
RECOMMENDED
FROM CONTROL
UNIT OR
PREVIOUS DEVICE
AUDIO BRANCH CIRCUIT – DO NOT
LOOP WIRE ON TERMINALS 3 & 4.
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
47K EOL
RESISTOR
ELR-47K
AUDIO AMPLIFIER 70.7
VRMS MAX.
Use only models AA-30,
AA-100, or AA-120. Amplifier
must provide wiring
Supervision per NFPA.
SPEAKER SWITCHING CIRCUIT: NFPA STYLE W SPEAKERS
MUST BE LISTED FOR FIRE PROTECTION. REFER TO THE
RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.
TO NEXT CONTROL MODULE –
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
004750a
SUPERVISION
TYPICAL FAULT-TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Z
•
•
•
•
CONNECT MODULES TO CONTROL UNITS
ALL WIRING SHOWN IS SUPERVISED
WIRES MUST BE SUPERVISED PER NFPA
MODULE POLARITIES ARE SHOWN IN ALARM
TO NEXT
DEVICE
COMMUNICATION LINE – 32
VDC MAXIMUM. TWISTED-PAIR
RECOMMENDED
FROM CONTROL
UNIT OR PREVIOUS
DEVICE
EOL RESISTOR IS INTERNAL AT TERMINALS
8 & 9. BYPASS CAPACITORS: A2143-20, 100
µF, 16 V, NON-POLARIZED, < 10 µA LEAKAGE.
AUDIO BRANCH CIRCUIT – DO NOT
LOOP WIRE ON TERMINALS 3 & 4.
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
AUDIO AMPLIFIER 70.7
VRMS MAX.
Use only models AA-30,
AA-100, or AA-120. Amplifier
must provide wiring
Supervision per NFPA.
SPEAKER SWITCHING CIRCUIT: NFPA STYLE X SPEAKERS
MUST BE LISTED FOR FIRE PROTECTION. REFER TO THE
RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.
TO NEXT CONTROL MODULE –
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
004750b
SUPERVISION
NOTES: 1. Audio circuit wiring must be twisted-pair as a minimum. See Pyro-Chem installation manual for detailed information.
2. When a 70.7 V audio amplifier is used, terminals 1 and 2 are power limited, while terminals 3 through 9 are non-power limited. In this case, the CB500
barrier is required. Otherwise, all terminal wiring is power limited. The CB500 includes a label indicating which terminals are non-power limited.
This label MUST BE PLACED adjacent to the nameplate label, which is on the module housing.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising