Features
• Plug-in detector line – mounting base included.
• Large wire-entry port.
• In-line terminals with SEMS screws.
• Mounts to octagonal and single-gang backboxes, 4 in.
(102 mm) square backboxes, or directly to ceiling.
• Stop-Drop ‘N Lock™ attachment to base.
• Removable detector cover and chamber for easy cleaning.
• Built-in remote maintenance signaling.
• Drift compensation and smoothing algorithms.
• Simplified sensitivity measurement.
008037
• Wide-angle, dual-color LED indication.
Physical Specifications
• Loop testing via “EZ Walk” feature.
Operating Temperature Range: For models 2W-B and 4WB:
32 °F to 120 °F (0 °C to 49 °C); for thermal models 2WT-B and
4WT-B: 32 °F to 100 °F (0 °C to 38 °C).
• Built-in test switch.
Description
New Series photoelectric and photoelectric/ thermal smoke
detectors represent a significant advancement in conventional
detection, incorporating three key features: installation ease,
intelligence, and instant inspection.
Installation ease: The New Series redefines installation ease
with its plug-in design. This allows an installer to pre-wire the
bases included with the heads. The large wire-entry port and
in-line terminals provide ample room for neatly routing the
wiring inside the base. The base accommodates a variety of
backbox mounting methods, as well as direct mounting with
drywall anchors. To complete the installation, New Series
heads plug into the base with a simple Stop-Drop ’N Lock
action.
Intelligence: New Series detectors offer a number of intelligent features to simplify testing and maintenance. Drift
compensation and smoothing algorithms, to minimize
nuisance alarms, are standard in the New Series. When
connected to an AUTOPULSE 542R/542D Control Panel,
two-wire New Series detectors are capable of generating a
remote maintenance signal when they need cleaning. This
signal is indicated by LEDs located at the AUTOPULSE
542R/542D Control Panel.
Storage Temperature Range: –4 °F to +158 °F (–20 °C to
+70 °C).
Operating Humidity Range: 10% – 95% RH, non-condensing.
Thermal Sensor: 135 °F (57 °C) fixed (models 2WT-B,
4WT-B).
Freeze Trouble: 41 °F (5 °C) (models 2WT-B and 4WT-B).
Sensitivity: 2.5%/ft (0.762%/meter) nominal.
Input Terminals: Utilize 14 to 22 AWG wire.
Dimensions (including base): 5.3 in. (135 mm) diameter,
2.0 in. (51 mm) high.
Weight: 6.3 oz (178.6 grams).
Mounting Options: 3.5 in. (89 mm) octagonal backbox; 4 in.
(102 mm) octagonal backbox; single-gang backbox; 4 in.
(102 mm) square backbox with a plaster ring; or direct mount
to ceiling.
Instant inspection: The New Series provides wide-angle red
and green LED indicators for instant inspection of detector
condition. The LEDs indicate: normal standby, out-of-sensitivity, alarm, or freeze trouble conditions. The “EZ Walk” loop test
feature is available on two-wire New Series detectors when
connected to an AUTOPULSE 542R/542D Control Panel. The
“EZ Walk” feature verifies the initiating loop wiring by providing LED status indication at each detector.
3-54
Electrical Specifications
LED Modes
Green LED
Red LED
Power Up
Blink every
10 seconds
Blink every
10 seconds
Normal (Standby)
Blink every
5 seconds
OFF
Out of Sensitivity
OFF
Blink every
5 seconds
Freeze Trouble
OFF
Blink every
10 seconds
Maximum Initial Start-Up Time: For two-wire models: 45
seconds; for four-wire models: 15 seconds.
Alarm
OFF
Solid ON
Maximum Alarm Current: For two-wire models: 130 mA
limited by control panel; For four-wire models: 20 mA @ 12 V,
23 mA @ 24 V.
Condition
Duration
Initial LED
Status Indication
80 Seconds
Initial LED
Status Indication (if
excessive electrical
noise is present)
4 Minutes
Operating Voltage: 12/24 V non-polarized nominal; 8.5 V
minimum; 35 V maximum.
Maximum Ripple Voltage: 30% of nominal (peak to peak).
Standby Current: 50 μA maximum average. Peak standby
current: for two-wire models: 100 μA; not applicable for fourwire models.
Maximum Start-Up Capacitance: For two-wire models:
0.1 μF; not applicable for four-wire models.
Latching Alarm: Reset by momentary power interruption.
Alarm Contact Ratings: For four-wire models: 0.5 A @ 30
VAC/VDC; not applicable for two-wire models.
Alarm Reset Voltage: 2.5 V.
Alarm Reset Time: 0.3 seconds.
Wiring Diagrams
Power Up Sequence for LED Indication
Agency Listings and Approvals
UL Listed . . . . . . . . . . . . . . . . . . . . . . . . S911
FM . . . . . . . . . . . . . . . . . . . . . . . . . Approved
CSFM . . . . . . . . . . . . . . . . . . . . 7272-1653:152
MEA . . . . . . . . . . . . . . . . . . . . . . . . 290-01-E
Maryland State Fire Marshal . . . . . . . . Permit No. 2093
ETL . . . . . . . . . . . . . . . . . . . . . . . . Approved
USCG. . . . . . . . . . . . . . . . . . . . . 161.002/A42/1
ANN-BUS
Ordering Information
AUX or
SMOKE +
POWER –
Part
No.
_______
435893
Description
_________
2W-B: Two-Wire
Photoelectric Smoke Detector
435894
2WT-B: Two-Wire
Photoelectric Smoke Detector
with 135 °F (57 °C)
Fixed Thermal Sensor
1.5
(0.7)
435895
4W-B: Four-Wire
Photoelectric Smoke Detector
1.5
(0.7)
435896
4WT-B: Four-Wire
Photoelectric Smoke Detector
with 135 °F (57 °C)
Fixed Thermal Sensor
1.5
(0.7)
EOL RELAY
EOLR-1
IDC +
–
EOL
RESISTOR
(5) COM
(4) NO
(3) – IN/OUT
(2) + OUT
(1) + IN
(5) COM
(4) NO
(3) – IN/OUT
(2) + OUT
(1) + IN
4-WIRE
CONTROL
PANEL
4W-B or 4WT-B
DETECTOR
008038
Shipping
Weight
lb
(kg)
_________
1.5 (0.7)
Stop-Drop ‘N Lock™ is a trademark of Honeywell International Inc.
TYCO FIRE PROTECTION PRODUCTS
ONE STANTON STREET
MARINETTE, WI 54143-2542
715-735-7411
Copyright © 2011 Tyco Fire Protection Products
All rights reserved.
Form No. T-2008081-3
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising