Ballast Compatible LED T8 A2 Series

Ballast Compatible LED T8 A2 Series
Ballast Compatible LED T8 A2 Series
WARNING
RISK OF ELECTRICAL SHOCK
FASTFIT™ T8 Linear Tube
INSTALLATION INSTRUCTIONS
INSTRUCTIONS D’INSTALLATIO
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
This lamp is UL listed for installation in existing luminaires as UL Type A/B
using G13 Bi-pin sockets. To ensure safety
and rated lifespan, this product must be installed according
to these instructions.
Do not use this equipment for other than the intended use.
E478349
TYPE A/B
For installation of E-Tech LED A2 Series FASTFIT
T8 models:
1. Disconnect electrical power to luminaire (fixture).
2. Remove existing lamps and dispose of properly.
3. Inspect existing sockets to ensure that sockets are G13
bi-pin, and that they are intact and undamaged.
4. If this tube is being used with existing ballast proceed
to step 8.
5. If this tube is being installed with the existing ballast
removed and line voltage connected directly to tube
proceed with step 6.
6. Remove existing ballast and dispose of properly.
7. Wire 100-277VAC line voltage circuit as shown in
Wiring Diagram 1 below.
8. Confirm that existing ballast is included on the list
“Tested Ballast Type” included with these installation
instructions.
9. Insert FASTFIT tube into G13 sockets and rotate to
secure.
10. Reconnect electrical power to luminaire.
Line Voltage Wiring
Line Voltage / Neutral wire combinations:
Non Shurnted Sockets:
Pin 1 / Pin 2
Pin 3 / Pin 4
Pin 1 / Pin 3
Pin 2 / Pin 4
Pin 2 / Pin 3
Pin 1 / Pin 4
DANGER - Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc - Couper l’alimentation avant
l’installation.
WARNING- Risk of fire. Use only in place of T8 fluorescent
lamps.
AVERTISSEMENT - Risque de feu. Utilisez uniquement à la
place de lampes fluorescentes T8.
CAUTION - If the lamp or luminaire operates improperly
(buzzing, flickering, etc.), turn off power, remove lamp from
luminaire and contact qualified electrican.
ATTENTION - Si la lampe ou un luminaire fonctionne mal
(bourdonnement, scintillement, etc.), mettre hors tension,
retirez lampe luminaire et contact electricien.
WARNING - This lamp is for use in indoor / damp locations
only. Not suitable for wet location.
ATTENTION - Ces lampes sont a utiliser dans un endroit
humide a l’interieru seulemnt.
WARNING - This lamp is not intended for use with
emergency exists.
ATTENTION - Ne convient pas aux sorties de secours.
WARNING - This lamp is not to be used with light dimming
systems.
ATTENTION - Cette lampe ne doit ne pas être utilisé avec les
systèmes de gradation de lumière.
Wiring Diagram 1
Pin 1
Pin 2
Pin 3
FF-T82/4-A2-XX-XX
Pin 4
*Please refer to product data sheet for part number detail.
Shunted Sockets:
Pins 1-2 / Pins 3-4
eTech LED, LLC
2559 Badger Ave
Oshkosh WI 54904
920 - 267 6109
www.etechled.com
© Copyright 2016 eTech LED FASTFIT A2 Install Guide V 2.4
Ballast Compatible / Ballast Bypass
LED T8 A2 Series Wiring Diagrams
UL Type B (ballast bypass) wiring diagram for installation of all ETech
LED A2 Series FASTFIT T8 linear and Ubend models using
NON SHUNTED G13 Bi-PIN SOCKETS.
UL Type A (ballast compatible) wiring diagram for installation
of all ETech LED A2 Series FASTFIT T8 models using INSTANT START AC
ELECTRONIC BALLASTS and FULHAM Model FH11-UNV-750L
Emergency Power Supply & Battery Pack.
Note: USE NONSHUNTED G13 Bi-PIN SOCKETS ONLY. Refer to Fulham
installation instructions for additional information, precautions and specifications.
100-277VAC
Neutral / Common
100-277VAC
Neutral / Common
100-277VAC
Neutral / Common
100-277VAC
Neutral / Common
100-277VAC
Neutral / Common
100-277VAC
Neutral / Common
UL Type A (ballast compatible) wiring diagram for installation
of all ETech LED A2 Series FASTFIT T8 models using RAPID START AC
ELECTRONIC BALLASTS and FULHAM Model FH11-UNV-750L
Emergency Power Supply & Battery Pack.
Note: USE NONSHUNTED G13 Bi-PIN SOCKETS ONLY. Refer to Fulham
installation instructions for additional information, precautions and specifications.
UL Type B (ballast bypass) wiring diagram for installation of all ETech
LED A2 Series FASTFIT T8 linear and Ubend models using
SHUNTED G13 Bi-PIN SOCKETS.
100-277VAC
Neutral / Common
UL Type A (ballast compatible) wiring diagram for installation of all
ETech LED A2 Series FASTFIT T8 linear and Ubend models using
NON SHUNTED G13 Bi-PIN SOCKETS.
Electronic
Ballast
Approved
Electronic
Ballast
Output 1
UL Type A (ballast compatible) wiring diagram for installation
of all ETech LED A2 Series FASTFIT T8 models using INSTANT START AC
ELECTRONIC BALLASTS and BODINE Model B50
Emergency Power Supply & Battery Pack.
Note: USE NONSHUNTED G13 Bi-PIN SOCKETS ONLY. Refer to Bodine
installation instructions for additional information, precautions and specifications.
Output 2
UL Type B (ballast bypass) wiring diagram for installation of all ETech
LED A2 Series FASTFIT BIAX 2G11 models using 2G11 SOCKETS.
100-277VAC
Neutral / Common
UL Type A (ballast compatible) wiring diagram for installation of all
ETech LED A2 Series FASTFIT BIAX 2G11 models using 2G11 SOCKETS.
Output 1
Approved Electronic Ballast
Output 2
UL Type A (ballast compatible) wiring diagram for installation
of all ETech LED A2 Series FASTFIT T8 models using RAPID START AC
ELECTRONIC BALLASTS and BODINE Model B50
Emergency Power Supply & Battery Pack.
Note: USE NONSHUNTED G13 Bi-PIN SOCKETS ONLY. Refer to Bodine
installation instructions for additional information, precautions and specifications.