The Square D ® Clipsal ® Ethernet Network Interface unit is a C-BusTM
system device designed to provide an isolated communications path
between an Ethernet 10Base-T Network and a C-Bus Network.
This allows high-speed control and monitoring of a Clipsal installation
via the TCP/IP protocols used in computer networks and by the Internet.
The Square D Clipsal Ethernet Network Interface unit provides a nearly
instantaneous connection to a C-Bus network allowing multiple systems
to be commanded together over a local or wide area network.
System integrators and installers will also benefit from having remote
access to the system. With the Square D Clipsal Ethernet Network
Interface unit, access to the network can be as close as the nearest
Ethernet connection.
View of the Clipsal DIN Rail Mounted
Ethernet Network Interface Unit
For ease of installation the Ethernet Network Interface unit is DIN rail
mounted. Power supply included, 120V IN; 12V OUT.
Features

Remote access to Clipsal systems

Bridge multiple C-Bus networks together over LAN or WAN

Fully supports all Clipsal commands

Small size, mounts in standard DIN enclosure (4M wide)

Includes 12V DC power supply
Specifications
Ethernet Network Interface
View of the Ethernet Network Interface unit
showing width, height and depth
C-BusTM Voltage
Requirements
15–36 V DC
Supply Current
300mA
Electrical Isolation
500Vrms continuous C-Bus/RS-232
Status Indicators
Ethernet LED/Comms LED
C-Bus System
Clock
Software selectable
C-Bus Network
Burden
Software selectable
C-Bus Connection
(2) pair of RJ-45 sockets for connection to
C-Bus networks
Ethernet
Connection
RJ-45 socket for connection to Ethernet
Dimensions
3.35 in. (H) x 2.84 in. (W) x 2.60 in. (D)
[85 mm (H) x 72 mm (W) x 66 mm (D)]
Mounting
DIN rail mounted (4M wide)
Weight
4.59 oz (130 g)
Operating
Environment
• Temp.: 32°F to 113°F (0°C to 45°C)
• RH: 95%, noncondensing
Standards
• UL: Listed 916 Energy Management
Equipment
• CSA C22.2 No. 205 Signal Equipment
• FCC: Part 15.101, Class B Digital Device
View of the Ethernet Network Interface unit’s
power supply
Order Information
Description
Catalog
Number
Ethernet Network
Interface Unit
SLC5500CN
Nominal Supply
Voltage
• 12VDC + /- 10%
Operating
Environment
• Temp.: 32°F to 104°F (0°C to 40°C)
• RH: 8% to 90%, noncondensing
Storage
Environment
• Temp.: -13°F to 185°F (-25°C to 85°C)
• RH: 5% to 95%, noncondensing
Weight
2.82 oz (80 g)
Standards
• UL: Listed 60950 Information
Technology Equipment - Safety: General
Requirements
• CSA 22.2 Spec 205 Signal Equipment
• FCC: Part 15.101, Class B Digital Device
Output Cable
5.9 ft. (1.8 m)
Schneider Electric North American Operating Division
Document Number 1250HO0702
295 Tech Park Drive
Square D, the
logo, Powerlink, Clipsal, and C-Bus are trademarks or registered
LaVergne, TN 37086
trademarks of Schneider Electric and/or its affiliates in the United States and/or other countries.
Tel: 1-888-Squared
www.squaredlightingcontrol.com
7/07
© 2007 Schneider Electric. All Rights Reserved.
Ethernet Network Interface Power Supply
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising