Thermozone® AR 200 A/E/W

Thermozone® AR 200 A/E/W
Thermozone AR 200 A/E/W
Ambient, no heat
Electrical heat 3–18 kW
Lengths: 1, 1,5 and 2 metres
R
Water heat
Thermozone® AR 200 A/E/W
Recessed air curtains for installation heights up to 2,5 metres
Application
AR200 is especially suited for environments with high
demands in respect of design. It is recessed in ceilings
above entry doors and other small doors where the
height is no greater than 2,5 metres. A low height
makes it possible to install AR200 where ceiling space
is limited. The recessed installation and low sound level
makes AR200 very discreet.
Comfort
AR200 creates an air barrier, which prevents cold
draughts and ensures comfortable heating inside the
door. An adjustable air blower grille makes it possible to
direct the air for an optimal air curtain effect. AR200,
with heat, can also contribute to the heating of the
room when the door is closed.
Operation and economy
Thanks to Thermozone Technology AR200 saves
energy. The air barrier reduces energy losses through
the door opening and the energy consumption of the air
curtain is also low. With an air curtain as a heat source
it produces heat in the area where it is most needed,
and as a result the rest of the premises can be covered
with less output. Easy installation and maintenance
minimizes the cost and the risk of errors.
Product specifications
• Just one model per length, but electrical units
are convertible between several outputs and
230V~/400V3N~ making it simple and flexible to
adapt the output to current need.
• Optimized airflow with Thermozone Technology.
• Low unit height (200 mm).
• Bottom plate in white lacquered aluminium.
Colour: RAL 9016, NCS 0500. The bottom plate can
easily be removed and painted in an optional colour.
Non visible parts made of hot zinc plated steel panels.
Air velocity profile
E
Design
AR200 is designed for recessed installation and the
visible bottom plate may be painted to make it blend
even better with the premises.
0,1 m
8,2 m/s
6,0 m/s
0,5 m
6,2 m/s
´4,8 m/s
1,0 m
4,2 m/s
3,6 m/s
1,5 m
3,3 m/s
3,0 m/s
2,0 m
2,8 m/s
2,6 m/s
2,5 m
2,4 m/s
2,3 m/s
2011-03-09
*
*¹)) Peak values
*2) Mean values. Measurements made according to AMCA 220
*²)
"Test methods for Air Curtain Units"
1
Thermozone AR 200 A/E/W
Technical specifications | Thermozone AR 200 A without heat  1
Type
Output
[kW]
[m3/h]
[dB(A)]
AR210A
0
650/1200
34/50
AR215A
0
950/1750
34/50
AR220A
0
1300/2400
40/54
Sound level*¹
Airflow
Technical specifications | Voltage
Amperage
Length
Weight
[V]
[A]
[mm]
[kg]
230V~
0,5
1042
18
230V~
0,6
1552
25
230V~
1,0
2042
36
Thermozone AR 200 E electrically heated  3
∆t*2
Type
Output
steps
400V3N~
[kW]
Output
steps
230V~
[kW]
Airflow
[m3/h]
[dB(A)]
[°C]
[V]
[A]
[A]
[mm]
[kg]
AR210E09
0/3
-
650/1200
34/50
13/7
400V3N~
4,3
-
1042
23
AR215E11
AR220E18
Voltage
Amperage Amperage Length
400V3N~ 230V~
Weight
0/6/9
-
650/1200
34/50
41/22
400V3N~
13
-
1042
23
-
0/3
650/1200
34/50
13/7
230V~
-
13
1042
23
-
3/5
650/1200
34/50
23/12
230V~
-
22
1042
23
0/4,5
-
950/1750
34/50
14/8
400V3N~
6,5
-
1552
32
0/6,8/11,3
-
950/1750
34/50
35/20
400V3N~
16
-
1552
32
-
0/4,5
950/1750
34/50
14/8
230V~
-
20
1552
32
34/50
-
0/4,5/6,8
950/1750
0/6
-
1300/2400 40/54
21/12
230V~
-
30
1552
32
13/7
400V3N~
8,7
-
2042
44
0/12/18
-
1300/2400 40/54
41/22
400V3N~
26
-
2042
44
-
0/6
1300/2400 40/54
13/7
230V~
-
26
2042
44
-
0/6/10
1300/2400 40/54
23/12
230V~
-
43
2042
44
Technical specifications | Type
Sound
level*¹
Thermozone AR 200 W water heated   2
Output*³
Airflow
Sound level*1 ∆t*2,3
Watervolume
Voltage
Amperage
Length
Weight
[kW]
[m3/h]
[dB(A)]
[°C]
[l]
[V]
[A]
[mm]
[kg]
AR210W
5.5/7
700/1000
41/49
24/21
0.5
230V~
0.4
1042
21
AR215W
8/11
1000/1600
37/50
24/20
0.9
230V~
0.6
1552
30
AR220W
11/14
1400/2000
44/53
23/20
1.1
230V~
1.0
2042
42
*¹) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m².
*²) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*3) Applicable at water temperature 80/60 °C, air temperature, in +15 °C.
AR200E is delivered as 9 kW, 11 kW and 18 kW (400V3N~) models, but they are convertible to 230V~ and different
outputs as shown in above table.
Protection class AR200A/E/W: normal design (IP20).
CE compliant.
Design and specifications are subject to change without notice.
Thermozone AR 200 A/E/W
Dimensions
445
1002 / 1512 / 2002
392
198
AR210: 940 / AR215: 1450
432
1042 / 1552
Front
Side
K-O ø29
Top view
AR220A/E: 1000 / AR220W: 960
AR220A/E: 940 / AR220W: 980
2240
Front
Thermozone AR 200 A/E/W
Mounting and connection
Mounting
AR200 unit is installed horizontally with the supply air
grille facing downwards as close to the door as possible,
concealed in the false ceiling. The only visible part of
the unit is the underside that is level with the ceiling.
For the protection of wider doorways, several units
can be mounted next to each other. Ensure that the
bottom plate is accessible and can be fully opened.
Minimum distance from outlet to floor for electrically
heated units is 1800 mm, see Fig. 1.
Connection AR 200 A 3
The connection to the unit's side or top is made with
2x1.5 mm² + earth. See Wiring Diagram.
Connection AR 200 E 3
Connection is made on the top or on the side of the unit
with a five-wired cable with earth. The supply terminal
block is intended for a cable of maximum 16 mm2. See
wiring diagrams. The units are convertible between
different output and 230V~/400V3N~.
Connection AR 200 W 2
The control cable is connected via knock outs to the
unit's side or top, with 2x1.5 mm² + earth. Connections
(DN15 (1/2”), inside thread) to the water heating coil
are located on the top of the unit to the right (seen from
inside the building). For AR220W the water connection
is located in the middle of the top side of the unit. See
wiring diagrams and dimension drawings.
Min 1,8 m
Fig. 1: Minimum distance to floor for electrically heated units.
Thermozone AR 200 A/E/W
Control kits
Ambient 1
Water 2
Level 1
Airflow is controlled manually
Control kit:
Level 1
Airflow is controlled manually. Room thermostat
controls the heat output via actuator/valve on/off.
Control kit CK01W:
- CB30N, control box , controls the airflow in 3 steps.
- CB30N, control box , controls the airflow in 3 steps.
Electrical 3
Level 1
Airflow is regulated manually. Room thermostat controls
the heat output in 2 steps.
Control kit CK01E:
- CB32N, control box, controls the airflow in 3 steps
and heat output in 2 steps
- RTI2, 2-step room thermostat (option KRT2800)
Level 2
Airflow and heat output are controlled automatically
based on the opening of the door and the room
temperature. When the door is open the fan runs on
high speed, when the door closes the fan will continue
to run on high speed for the desired time (2s–10 min.)
set on MDC. When the door is closed the fan runs on
low speed if there is a need for heating, if not the fan is
switched off.
The room thermostat controls the heat output.
E.g. the thermostat is set on 23 °C and the difference
between the stages 4 °C. The thermostat will activate
below 19 °C when the door is closed. When the door
opens, the thermostat will activate below 23 °C and
normally the heat is switched on.
Control kit CK02E:
- CB32N, control box, controls the airflow in 3 steps
and heat output in 2 steps
- MDC, door contact with time delay
- RTI2, 2-step room thermostat (option KRT2800)
- T10, room thermostat IP30.
Note! A set of valves VR20 or VR25 or actuator+valve
SD20+TVV20 or TVV25 should be added for a complete
control kit.
Level 2
Airflow and heat output are controlled automatically
based on the opening of the door and the room
temperature. When the door is open the fan runs on
high speed, when the door closes the fan will continue
to run for the desired time (2s–10 min.) set on the MDC.
When the door is closed the fan runs on low speed if
there is a need for heating, if not the fan is switched off.
The room thermostat controls the heat output on/off.
E.g. the thermostat is set on 23 °C and the difference
between the stages 4 °C. The thermostat will activate
below 19 °C when the door is closed. When the door
opens, the thermostat will activate below 23 °C and
normally the heat is switched on.
Control kit CK02W:
- CB30N, control box, controls the airflow in 3 steps.
- MDC, magnetic door contact with time delay.
- RTI2, 2-step room thermostat.
Note! A set of valves VR20 or VR25 or actuator+valve
SD20+TVV20 or TVV25 should be added for a complete
control kit.
Thermozone AR 200 A/E/W
Output charts water
Incoming / outgoing water temperature 90/70 °C
Type
Fan
position
Airflow
[m³/s]
AR210W
max
1000
min
700
AR215W
AR220W
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Output
Water flow Pressure
drop
[l/s]
[kPa]
Output
[kW]
Air temp.
out
[°C]
8,5
40
0,1
24,9
7,5
43
0,09
21,6
6,5
43
0,08
16,8
6
46
0,08
14,6
[kW]
Air temp.
out
[°C]
Water flow Pressure
drop
[l/s]
[kPa]
max
1600
13,5
40
0,16
13,4
12,5
43
0,15
11,5
min
1000
10
45
0,10
7,9
9
47
0,11
6,8
max
2000
16,6
40
0,2
22,8
15,5
43
0,19
19,7
min
1400
13,5
43
0,16
15,3
12,5
46
0,15
15,3
Incoming / outgoing water temperature 80/60 °C
Type
Fan
position
Airflow
[m³/s]
AR210W
max
1000
min
700
AR215W
AR220W
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Output
Water flow Pressure
drop
[l/s]
[kPa]
Output
[kW]
Air temp.
out
[°C]
7
36
0,08
18,2
6,5
39
0,08
15,3
5,5
39
0,07
12,4
5
41
0,06
10,4
[kW]
Air temp.
out
[°C]
Water flow Pressure
drop
[l/s]
[kPa]
max
1600
11
35
0,13
9,7
10
38
0,12
8,1
min
1000
8,5
39
0,10
5,8
7,5
42
0,09
4,8
max
2000
14
35
0,17
16,6
12,5
38
0,15
13,9
min
1400
11
38
0,14
11,2
10
41
0,12
9,4
Incoming / outgoing water temperature 60/50 °C
Type
Fan
position
Airflow
[m³/s]
AR210W
max
1000
min
700
AR215W
AR220W
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Output
Water flow Pressure
drop
[l/s]
[kPa]
Output
[kW]
Air temp.
out
[°C]
5
30
0,12
38,6
4,5
33
0,11
30,2
4
32
0,10
26,1
3,5
35
0,09
20,4
[kW]
Air temp.
out
[°C]
Water flow Pressure
drop
[l/s]
[kPa]
max
1600
8
30
0,20
20,7
7
33
0,17
16,1
min
1000
6
33
0,15
12,3
5,5
35
0,13
9,6
max
2000
9,5
28
0,23
26,3
8
32
0,20
20,4
min
1400
7,5
31
0,18
17,9
6,5
33
0,16
14
Incoming / outgoing water temperature 60/40 °C
Type
Fan
position
Airflow
[m³/s]
AR210W
max
1000
min
700
AR215W
AR220W
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Output
Water flow Pressure
drop
[l/s]
[kPa]
Output
[kW]
Air temp.
out
[°C]
4
27
0,05
7,5
3,5
30
0,04
5,4
3,5
29
0,04
5,1
3
32
0,03
3,7
[kW]
Air temp.
out
[°C]
Water flow Pressure
drop
[l/s]
[kPa]
max
1600
6,5
27
0,08
3,9
5,5
30
0,06
2,8
min
1000
5
29
0,06
2,3
4
32
0,05
1,7
max
2000
8
27
0,10
6,8
7
30
0,08
4,9
min
1400
6,5
29
0,08
4,6
5,5
31
0,07
3,3
Frico AB
031 336 86 00
www.frico.se
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising