MMG100D - Generac Mobile Products

MMG100D - Generac Mobile Products
MMG100D
MOBILE DIESEL GENERATOR
SPECIFICATIONS
ENGINE
• John Deere® PE4045HFG92 - turbocharged, diesel engine
o Prime - 121 hp @ 1800 rpm
o Standby - 133 hp @ 1800 rpm
o 4 cylinder
o 4.5 L displacement
o Interim Tier IV approved
• Steel, single wall fuel tank
o 165 gal. (625 L) capacity
o 24 hr. run time – full load
o Fuel tank built into skid of generator set
• Fuel consumption at prime:
o 100% - 6.2 gph (23.5 Lph)
o 75% - 4.7 gph (17.8 Lph)
o 50% - 3.1 gph (11.7 Lph)
• Cooling system capable of operating at 120°F (49°C) ambient
• Radiator and oil drains plumbed to exterior
• Rubber vibration dampers isolate engine/generator from frame
• Disposable air filter - paper element
• 60 Hz engine/generator
• Electronic isochronous governing
GENERATOR
•
Marathon Electric®
o Brushless
o 4 pole
o Class H insulation
•
Voltage regulation +/- 0.5% with Magnum PM600 Voltage Regulator
SYSTEM OUTPUTS
•
•
•
•
•
3 position selector switch
o Single phase – 120 / 240V Zig Zag
o Three phase – 120 / 208V Low Wye
o Three phase – 277 / 480V High Wye
75 kW / 75 kVA – standby, single phase
71 kW / 71 kVA – prime, single phase
86 kW / 107 kVA – standby, three phase
78 kW / 98 kVA – prime, three phase
Generac Mobile Products LLC l 800-926-9768 l 920-361-4442 l www.generacmobileproducts.com
Page 1 of 4
MMG100D
MOBILE DIESEL GENERATOR
SPECIFICATIONS
SYSTEM CONTROLS
•
•
Power Zone® controller and display
o Backlit, 800 x 480 pixel resolution color display
o -40°F to 185°F (-40°C to 85°C) operating temperature range
o Automatic coarse voltage adjustment
o Integrated fine voltage adjustment
o PLC functionality
Push buttons for easy operation
o Manual or Auto Start
o Engine Start
o Engine Stop/Reset
o Alarm Mute
o Operator Screens
 Home
 Engine
 Generator
 Voltage Adjust
o Scrolling Arrows for Diagnostic Information
 Engine diagnostic display
• Oil pressure
• Engine temperature
• Fuel level
• Battery
• After treatment inlet/outlet temperature
• Ash/soot levels
 Generator diagnostic display
• System kW output display
• Line output & frequency display
 Alarms
• Warning
• Shutdown
• Electrical Trip
• Engine
 Alarm list – warnings / shutdowns; 250 event history log – date/time stamp
• Fuel level: warning – 15%; shutdown – 5%
• Over speed protection: shutdown – 115%
• Oil pressure: warning – 25 psi; shutdown – 20 psi
• Coolant temperature: warning – 220°F (104°C); shutdown – 230°F (110°C)
• Battery voltage: over – 15VDC; under – 11VDC
• Generator over voltage: warning – 110%; electrical trip – 111%
• Generator under voltage: warning – 87%; electrical trip – 86%
• Generator over frequency: warning – 105%; electrical trip – 110%
• Generator under frequency: warning – 95%; electrical trip – 90%
Generac Mobile Products LLC l 800-926-9768 l 920-361-4442 l www.generacmobileproducts.com
Page 2 of 4
MMG100D
MOBILE DIESEL GENERATOR
SPECIFICATIONS
SYSTEM CONTROLS (continued)
•
 Inputs/Outputs
 Auto Schedule
 Status
Configuration of controller, firmware and connections
ELECTRICAL CONTROLS
•
•
•
•
•
•
•
•
Remote start / stop contacts located in lug box
Lockable control box door with diagnostics window
Lockable lug box with safety switch
o Trips main breaker when door is opened
o Disables voltage regulator
Output ground connection lug inside lug box
400A main breaker with shunt trip
Convenience receptacles with individual breakers (restricted use in high wye mode)
o (2) 120V 20 Amp GFCI duplex outlets – (NEMA 5-20R type)
o (3) 125 / 250V 50 Amp, 3 pole, 4 wire Twistlock (Non-NEMA 6369)
Voltage adjustment integrated into Power Zone controller, +/- 10%
720CCA wet cell battery
ENCLOSURE
•
•
•
•
•
•
Aluminum, sound attenuated enclosure
o UV & fade resistant, high temperature cured, white polyester powder paint
o Insulated and baffled
o 68 dB(A) @ 23 ft. (7 m) – prime power
Fully lockable enclosure including doors and fuel fill
Emergency stop switch located on outside of enclosure
Central lifting point
Multi-lingual operating/safety decals
Document holder with operating manual including AC/DC wiring diagrams
TRAILER
•
•
•
•
•
•
•
DOT approved tail, side, brake, and directional lights; recessed rear lights
Transportation tie downs
Safety chains with spring loaded safety hooks
3 in. (76.2 mm) lunette ring hitch
6000 lb. (2722 kg) axle with surge brakes
3000 lb. (1361 kg) tongue jack with footplate
ST225/75R15 tubeless tires – 8 ply
Generac Mobile Products LLC l 800-926-9768 l 920-361-4442 l www.generacmobileproducts.com
Page 3 of 4
MMG100D
MOBILE DIESEL GENERATOR
SPECIFICATIONS
WEIGHT & DIMENSIONS
•
•
Skid mounted
o Dry weight: 3780 lbs. (1714 kg)
o Operating weight: 4740 lbs. (2150 kg)
o 119 x 40 x 62 in. (3.02 x 1.02 x 1.57 m)
Trailer mounted
• Dry weight: 4480 lbs. (2032 kg)
• Operating weight: 5440 lbs. (2467 kg)
170 x 69 x 80 in. (4.32 x 1.75 x 2.03 m)
WARRANTY
2 Years / 2000 Hours
CERTIFICATIONS
CSA Certified
Generac Mobile Products LLC l 800-926-9768 l 920-361-4442 l www.generacmobileproducts.com