Fire and Gas Detection Systems Product Catalogue - Morley-IAS

Fire and Gas Detection Systems Product Catalogue - Morley-IAS
Fire and Gas
Detection Systems
Product
Catalogue
Introduction
Welcome to the new Morley-IAS by Honeywell Fire and Gas Detection Catalogue.
Morley-IAS is one of the world’s leading designers and manufacturers of fire alarm control panels and associated equipment
for professional fire alarm installers. Our vision is to deliver unsurpassed value through technical innovation and talented,
professional people. We listen to our customers to ensure that we understand not only their product requirements, but also their
expectations for customer and technical support.
Continuous investment in research and development drives the delivery of modern high technology products, which puts the
Morley-IAS brand in a leading position in the fire industry. By choosing Morley-IAS, you are assured of working with a company
that has a well established reputation for quality products with first-class support. The wide range of products from Morley-IAS
allows you the freedom to design the system that best suits your needs with the option to create, add and enhance, whenever
and however you wish.
The ethos of Morley-IAS is to supply products approved to meet local legislation. In the Benelux, all our fire detection and alarm
control panels are designed to meet EN54 Part 2 and Part 4 standards and approved by BOSEC, LPCB or VDS to ensure
compliance. The carefully planned evolution of our products over many years ensures that we can provide a panel to maintain
or extend existing Morley-IAS fire systems and a system purchased today meets not only your existing needs but can easily
grow to satisfy the requirements of tomorrow.
We supply our products to professional and qualified fire alarm installers who will design and install a complete system for a
building as well as providing commissioning and maintenance. Our extensive network of trained installers and maintenance
operatives gives end users the freedom to choose the service provider that best meets their requirements. We supply our
products to professional and qualified fire alarm installers who will design and install a complete system for a building as well
as providing commissioning and maintenance.
Our global parent is Honeywell International Inc., a diversified technology and manufacturing company. Honeywell is traded on
the New York Stock Exchange as well as the Chicago, Pacific and London Stock Exchanges. It is one of the 30 stocks that make
up the Dow Jones Industrial Average, and is listed on the Standard & Poors Index.
We are looking forward to continued success in working together.
Your Morley-IAS team
Legend:
Special product information.
Information regarding the delivery (packing units, special charges, etc.).
Please complete the partnumber with the correct information.
Lead time information
Special information regarding trainings.
This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use
of the information therein.
Design features may be changed or amended without prior notice.
3
Notes
4
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Table of Contents
1. Intelligent Systems
7
Example of system overview of ZXSe
8
Intelligent panels11
Intelligent detectors 21
Intelligent InnovairFLEXTM duct detectors
30
Intelligent beam detectors
32
Intelligent manual call points
34
Intelligent modules40
Intelligent audio & visual range 47
Spare parts51
2. Conventional Systems
53
Conventional panels55
Conventional detectors57
Conventional InnovairFLEXTM duct detectors
62
Conventional beam detectors
64
Conventional manual call points & switches
76
Conventional audio & visual range
85
Spare parts89
3. Extinguishing Systems
91
Extinguishing panels93
Manual control units
95
Emergency fire signalling panels
97
Spare parts99
4. Special Equipment
101
Aspirating Systems103
Sampling pipes & fittings
113
Smoke & heat evacuation systems
121
Wireless systems127
Linear heat detection
133
Industrial heat detectors
136
Industrial audio & visual devices
140
Intrinsically safe devices
142
Explosion proof devices
147
Flame detectors150
Spare parts156
5. Gas Detection Systems
157
Unipoint Controllers159
Gas Detectors160
Sensitron gas control panels
166
Sensitron gas detectors
170
Gas detector accessories
176
Spare parts178
6. Accessories
179
Power supplies181
Batteries184
Electro magnetic door holders
188
Fire resistant cables
191
Surge protection modules
192
Manual call point accessories
192
Protective accessories193
Detector test equipment
198
Spare parts213
7. Residential Smoke and Gas Detection X-Series Fire Alarms 8. Index
215
217
221
5
Notes
6
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent
Systems
Intelligent Systems
Intelligent system overview
Example of system overview of ZXSe
OR
Hi-RS485
MORL-OPTO-ESPA
Hi-485
Ring
RS-485
Straight
LAN
8 way input module
4 way sounder card
Hi-RS485
PC Windows
Configuration tool
OR
4 way input module
Connection possibility
Same as above
Internal printer
(only ZX5Se)
OR
D
RS-485
RS-485
40 way mimic
RS-485
ZXr-P
Passive repeater
ZXr-A
Active repeater
C
Morley-IAS
Loop card
20 zones indication
MS5/R/R
Y05D
MS2
20 zones indication
MI-HTSE-S2
MI-FHSE-S2
MI-PTSE-S2
MI-PSE-S2
MI-RHSE-S2
MI-LZR
FAAST-LT
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
8
Honeywell | Fire Safety
RS-232
ZXSe
Conventional AV ENscape range
MS1/R
B
A
SND
Y08D
OR
Benelux region
Catalogue version 2.1
MI-LPB2-S2I
DNRE
8100E
ISOX-8
Intelligent Systems
Intelligent system overview
RS-485
ZXSe Slave
Wireless
1
2
RS-485
ZXSe Master
3
4
Serial printer
PAVA
40/40
5
VFC
6
IRK-E-SI
MI-MM3E-S2
MI-DMM2I
MI-DMMI
MI-DISO
MI-D21CMO
MI-DCMO
7
8
MI-D240CMO
MI-MCP
Conv. devices
MI-CZ-6, MI-SC-6
MCX-55MH
MCPxx
CMX-10RMH
MMX-10MH
ITAC
VSN-RP1r+
WCPxx
ForMI-BSO-PP-I
spare parts, please referMI-WSO-PR-I
to § Spare Parts at theMI-WSS-PC-I
end of this chapter (01. Intelligent
Systems)
MI-BSS-PC-I
MI-WST-PC-I
MI-WSS-PC-I
9
Intelligent Systems
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
10
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Panels
DXc Series
• Optional 40 or 80 zone alarm LEDs
• Easy 4 key-press set-up
• Large blue LCD display
• Supports USB upload/download
• Mobile phone style keypad and navigation keys
• Option to upload a company logo
714-001-113
The Morley-IAS DX Connexion panel is ideally suited for use in the protection of
small to medium sized buildings. All in all, a compact, high performance, feature
rich, economical fire alarm control panel designed to help for both the installer and
the end user.
The DX Connexion is an enhancement of the Morley-IAS Dimension panel range,
connecting the traditional Morley-IAS qualities of reliability, flexibility and value with
advanced features and intuitive functionality.
The DX Connexion range of fire alarm control panels has been developed to be the
most time efficient fire panel on the market to install. Simply fix the control panel to
the wall, connect the field wiring, and in as few as four button presses later you can
have a compliant, working fire alarm system.
The panel’s large graphical display provides a clear menu structure making the
whole initial set-up process quick, clear and intuitive.
Programming the control panel couldn’t be easier. Text can be quickly inserted from
the panel’s mobile phone style keypad to identify the exact location of each field
device. All panel features and system cause and effect can be programmed via
either the panels large LCD display or by using the Windows configuration tool.
1
2
3
DXc1 - One loop fire alarm control panel
Specifications
•
•
•
•
•
•
4
Dimensions (HxWxD): 260 mm x 390 mm x 147 mm
Weight:4kg
Colour:
RAL 9002 - Grey white
Operating voltage: 230V AC (+15%,-15%) 50-60 Hz
Power supply: 24VDC/2A
Battery space:
2 x 7Ah/12V
5
6
CPD number: 0832-CPD-1511
714-001-213
7
DXc1-M One loop fire alarm control panel, with space for 17Ah batteries (availability will be announced)
8
As 714-001-113, but with a housing allowing 2 x 17Ah stand-by batteries.
Specifications
•
•
•
•
714-001-223
Dimensions (HxWxD): 391.5 mm x 390 mm x 147 mm
Weight:4.5kg
Power supply: 24VDC/4A
Battery space:
2 x 7Ah/12V
DXc2 - Two loop fire alarm control panel
Specifications
•
•
•
•
•
Dimensions (HxWxD): 391.5 mm x 390 mm x 147 mm
Weight:4.5kg
Operating voltage: 230 VAC (+15%,-15%) 50-60 Hz
Power supply: 24VDC/4A
Battery space:
2 x 17Ah/12V
CPD number: 0832-CPD-1512
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
11
Intelligent Systems
714-001-243
Intelligent Panels
DXc4 - Four loop fire alarm control panel
Specifications
•
•
•
•
•
•
Dimensions (HxWxD): 391.5 mm x 390 mm x 147 mm
Weight:4.5kg
Colour:
RAL 9002 - Grey white
Operating voltage: 230 VAC (+15%,-15%) 50-60 Hz
Power supply: 24VDC/4A
Battery space:
2 x 17Ah/12V
CPD-number: 0832-CPD-1513
DXc Series accessories
020-891
USB Interface lead cable for DX, DXc and ZXSe panels
795-099
DXc Network card
795-122
DXc RS232 card
795-102
DXc 40 Zone LED card
795-124
DXc 80 Zone LED card
795-111
DXc 2 Loop expansion card
795-101
DXc Cover blank
795-121
DXc Extension backbox
020-909
Kit Compact mimic 160 zone main PCB
020-910
Kit Compact mimic expansion PCB
Please note that the below items are available on request only. Please check the last price list for lead time information.
795-116
DXc Cover custom keyplate
795-112
DXc Bezel 1 loop
795-113
DXc Bezel 2-4 loop
795-114
DXc Bezel 1 loop + ext.
795-115
DXc Bezel 2-4 loop + ext.
795-118
DXc Keyswitch
795-119
DXc Rack mount 1 loop
795-120
DXc Rack mount 2 loop
795-130
DXC Loop splitter enclosure (availability will be announced)
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
12
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Panels
795-131
Loop splitter card (availability will be announced)
795-132
System I/O card (availability will be announced)
NEW
797-090
DXc extension EN54-4 PSU backbox
Increases the enclosure size of a Dxc2, or Dxc4 control panel to accommodate an
additional pair of 17Ah batteries to provide increased system battery standby of upto
34Ah at 24V(depending of the batteries fitted in the panel) . This unit is supplied with
the backbox, two cover blanks and an aditional power supply unit (PSU).
1
Specifications
• Dimensions (HxWxD): • Approved to:
263 mm x 390 mm x 147 mm
EN54-4
2
3
ZXSe Series
722-001-302 4
ZX1Se single loop intelligent panel (incl. UK, FR and NL language)
The ZX1Se is an intelligent intelligent fire alarm control panel. It has been designed
and constructed around proven and reliable microprocessor technology. This
simple approach has produced a modular, scalable fire alarm platform suitable for
protecting all types of premises.
Includes English, Dutch and French languages.
5
6
Specifications
•
•
•
•
•
Multi-protocol
Modular concept
Simple, robust design to EN54
Intuitive to use
Easy to maintain, to expand, to network, to install, to configure
• Dimensions (HxWxD): • Operating voltage: • Weight: • Construction: • Loop Capacity: • Max. PSU rating:
• Standby batteries:
• Operating temperature:
• Relative humidity:
7
400 mm x 400 mm x 135 mm
230V 50Hz AC
10 kg without batteries
Sheet steel painted, sealed to IP30
1 loop max. 460mA
2.5A total, comprising battery charger: 0.5A
max. 2 x 12Ah/12V
0°C to +40°C
max. 85% (non-condensing)
8
Bosec numbers: TCC2-909, TCC2-910, TCC2-911, TCC2-912, TCC2-913; CPD
number: 0786-CPD-20917
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
13
Intelligent Systems
720-001-302 Modular & Peripheral Devices
ZX2Se 1 or 2 loop intelligent panel (incl. UK, FR and NL language)
The ZX2Se is an intelligent fire alarm control panel. It has been designed and
constructed around proven and reliable microprocessor technology. This simple
approach has produced a modular, scalable fire alarm platform suitable for protecting
all types of premises.
Includes English, Dutch and French languages.
Specifications
• Dimensions (HxWxD): • Operating voltage: • Weight: • Construction: • Loop capacity: • Max. PSU rating:
• Standby batteries:
• Operating temperature: • Relative humidity:
400 mm x 400 mm x 135 mm
230V 50Hz AC
10 kg without batteries
Sheet steel painted, sealed to IP30
1 or 2 loops max. 460mA
2.5A total, comprising battery charger: 0.5A
max. 2 x 12Ah/12V
0°C to +40°C
max. 85% (non-condensing)
Bosec numbers: TCC2-909, TCC2-910, TCC2-911, TCC2-912, TCC2-913; CPD
number: 0786-CPD-20917
721-001-302 ZX5Se 1 to 5 Loop intelligent panel (incl. UK, FR and NL language)
Includes English, Dutch and French languages.
Specifications
• Dimensions (HxWxD): • Operating voltage: • Weight: • Construction: • Loop capacity: • Max. PSU rating:
• Standby batteries:
• Operating temperature: • Relative humidity:
500 mm x 500 mm x 195 mm
230V 50Hz AC
20 kg without batteries
Sheet steel painted, sealed to IP32
1 to 5 loops expandable, 460mA per loop maximum
see inst. manual for power distribution
max. 2 x 22Ah/12V
0°C to +40°C
max. 85% (non-condensing)
Bosec numbers: TCC2-909, TCC2-910, TCC2-911, TCC2-912, TCC2-913; CPD
number: 0786-CPD-20917
Modular & Peripheral Devices
795-072 Loop driver card Morley-IAS protocol - 250mA
Compatible with Zxe and ZXSe panels.
795-072-100 Loop driver card Morley-IAS protocol 460mA
Only compatible with ZXSe panels.
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
14
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Modular & Peripheral Devices
795-077-020 Please note that the below devices are available on request only. Please check the last price list for lead time information.
20-zones indication expansion module; only for ZX5Se
Expansion zone 21 till 40 (zone 1 till 20 is included in panel).
795-077-060 60-zones indication expansion module; only for ZX5Se
Expansion zone 21 till 80 (zone 1 till 20 is included in panel).
1
2
797-061 ZX1Se/ZX2Se Bezel kit.
3
Semi flush mounting kit for ZX1Se or ZX2Se control panel.
Bezel size 450 x 450mm.
4
5
6
797-062 ZX5Se Bezel kit.
7
Semi flush mounting kit for ZX5Se control panel.
Bezel size 550 x 550mm.
8
797-063 ZX1Se/ZX2Se Glass door kit
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
15
Intelligent Systems
Modular & Peripheral Devices
Please note that the below devices are available on request only. Please check the last price list for lead time information.
797-064 ZX5Se Glass door kit
797-076
”L” shaped mounting bracket to fit peripheral pub’s into ZXSe serie
795-063
PSU/Charger in box, 24VDC/5 Amp.
Space for 2x 12V/24 Ah batteries.
Specifications
• Dimensions (HxWxD): 500 mm x 500 mm x 180 mm
795-064 PSU/Charger without enclosure, 24VDC/5 Amp.
797-077
ZX1/2Se Battery box or mounting enclosure
Specifications
• Dimensions (HxWxD): For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
16
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
400 mm x 400 mm x 135 mm
Intelligent Systems
797-078 Modular & Peripheral Devices
ZX5Se Battery box or mounting enclosure
Specifications
• Dimensions (HxWxD): 500 mm x 500 mm x 185 mm
020-891
USB interface lead cable for DX, DXc and ZXSe panels
795-004-001 RS-485 Communication module
The module provides optical (galvanic) isolation for the serial input/output channel. It
translates the signal levels of this channel to the RS485 Communications Interface
Standard levels. Up to 31 peripheral units can be connected to the panel using this
module.
795-005
1
2
The below modules are available on request only. Please check the last price list for lead time information.
RS-232 Communication module
3
The RS232 Interface module provides a communication interface for BMS. The
module is compatible with the ZX5Se Fire Alarm Control Panels.
4
5
795-038-001 HI-485 communication module
6
The HI485 interface is typically used to form a closed loop. This ensures that data is
communicated to every device connected to the loop, even if a fault exists, and each
interface acts as a node access point onto the loop.
Requires an RS485 card to be fitted in the control panel.
7
Specifications
• Supply voltage:
• Supply current:
• Volt free contact rating:
• Communications:
709-601-001 8
18-28VDC
40mA @ 24VDC (typical)
Max. 100mA in fault condition
1A @ 24VDC
3 RS485 balanced transmission ports
Active repeater panel
Silence, Reset, Mute, Accept, Evacuate and Test Controls.
Requires an RS485 card fitted in control panel.
Specifications
•
•
•
•
•
•
Dimensions (HxWxD): 165 mm x 254 mm x 50 mm
Weight:1.7kg
Operating temperature:
+5°C to +45°C
Relative humidity:
10% to 93% (non-condensing)
Supply voltage:
18-28VDC
Current rate:
90 to 120mA
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
17
Intelligent Systems
709-701-001 Modular & Peripheral Devices
Passive repeater panel
Requires an RS485 card fitted in control panel.
Specifications
•
•
•
•
•
•
Dimensions (HxWxD): 165 mm x 254 mm x 50 mm
Weight:1.7kg
Operating temperature:
+5°C to +45°C
Relative humidity range:
max. 10-93% (non-condensing)
Supply voltage:
18-28VDC
Current rate:
90 to 120mA
Item available on request only. Please check the last price list for lead time information.
020-600-002 Bezel kit for repeater panels
Semi flush mounting kit.
795-014 4 way, programmable relay module, pcb
Requires an RS485 card fitted in the control panel.
Specifications
• Supply voltage:
• Current rate:
• Relay contact rating:
795-015 24-28VDC
80 to 160mA
5A, 240VAC
4 way, programmable sounder module, pcb
Requires an RS485 card fitted in the control panel.
Specifications
•
•
•
•
795-029 Supply voltage:
Current rate:
Max. current output per sounder circuit:
Max. total current:
24 to 28VDC
120 to 220mA
1A
3A (spread over all 4 outputs)
8 way, programmable input module, pcb
Requires an RS485 card fitted in the control panel.
Specifications
• Supply voltage:
• Current rate:
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
18
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
22 to 28VDC
65 to 97mA
Intelligent Systems
795-065 Modular & Peripheral Devices
40 way, programmable mimic interface, pcb
The card can be configured to display either zone or event information.
Requires an RS485 card fitted in the control panel.
Specifications
• Supply voltage:
• Current rate:
795-060-002
+/- 24VDC
+/- 300mA
External printer for ZXSE panels
1
2
795-057 Modbus interface module
3
The modbus interface unit connects to the RS485 peripheral bus of a fire control
panel and allows panel interrogation by a modbus (RTU) control system. Requires
an RS485 card fitted in control panel.
4
Specifications
•
•
•
•
Dimensions (enclosure):
Supply voltage:
Current rate:
Modbus functions:
5
250 mm x 175 mm x 75 mm
18-28VDC
120mA @ 24VDC
01, 02, 04, 07
6
ITS-BOX
RS232 - TCP/IP device server
7
ISOX-8
8-way loop splitter board
8
Transforms 1 intelligent loop into 4 closed and isolated sub-loops 3 types of
configurations possible. Requires external 24VDC. Compatible with all intelligent
Morley-IAS panels. Must be installed into the panel.
Specifications
• Dimensions (W x H x D): 155 mm x 115 mm x 70 mm
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
19
Intelligent Systems
Modular & Peripheral Devices
Espa Interfaces
MORL-OPTO-ESPA
Mini PC fire panel - Espa converter
• Used to connect a DXc or ZXSe fire panel on a pager system using a serial communication
• Uses the standard ESPA 4.4.4 “Third Party Protocol”
• Windows Configuration Tool
• Freely programming on site using the LAN
ports or the serial port COM3
• Onboard Intel Atom E620 microprocessor
• Includes 3 serial RS232 communication ports
• Includes 3 2.0 USB ports for the backup and download of the configuration
• LAN ports with dynamic and static IP address
• Allows the connection of a control display
• Filtering per group of event
• Event filtering per zone
• Tone and priority per event
• The message sent can include: panel number, loop number, device address, zone number
HLS-OPTO-RS232
The MORL-OPTO-ESPA 4.4.4 is a universal interface which is connected on the
DXc to the isolated RS232 port in a “stand alone” or network configuration. It uses
the “Third Party Protocol” to send out informations coming from the fire detection
panel to a pager or Dect system. The protocol used to communicate with the paging
system is the standard Espa4.4.4.
This interface is also compatible with the ZXSe fire panel (requires an RS232/
RS485 converter) and is connected to the RS485 bus (requires a 795-004-001
RS485 communication module).
The interface is delivered with an easy to use configuration tool, to set on site the
configuration data and messages to display on the pagers.
The communication software allows to visualize in real time the communication
which takes place on the incoming and outgoing serial ports and to send out a
standard test message to the pager interface. The programming is done using a
remote access with VNC Viewer.
The MORL-OPTO-ESPA includes:
Mini PC Fire panel
HLS-OPTO-RS232 (RS232 Optical Isolation Transceiver)
Specifications
• Operating voltage range: • Power consumption: • RS232 serial ports:
• Dimensions (H x W x L): • Operating temperature:
• Relative humidity:
12VDC to 24VDC
420 mA
3 (COM 1 Analog fire detection panel,
DXc & ZXSe range; COM 2 Pager system ESPA 4.4.4; COM 3 Activation
new configuration
140 mm x 59 mm x 167 mm
-5°C to +55°C
10% to 93% (non-condensing)
RS232 optical isolation transceiver
Required when connection the MORL-OPTO-ESPA to a DXc panel.
Item available on request only. Please check the last price list for lead time information.
HLS-OPTO-RS485
RS232/485 converter
Required when connection the MORL-OPTO-ESPA to a ZXSe panel.
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
20
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Detectors
MI200-S2 Series Intelligent detectors with Advanced protocol
• New mechanical platform with revolutionary chamber offering 3 doors:
- improved false alarm immunity
- improved detection across multiple fire types
- improved resilience to false alarms • Includes the Advanced protocol
• Available with standard short circuit isolator with status control using the Advanced protocol
• Tri colour LED offering red, green and amber colour
• Rotary decade address switches 0 - 159
• Pure white colour to complement modern buildings
• 100% mechanical and electrical backwards compatibility
• New base design to complement the detector
The MI200-S2 detectors have two integral tri-colour LEDs that provide 360°
local visual indication of the device status. The LEDs are programmable with
static or blinking red, amber and green status indications available. All MI200-S2
detectors are environmentally friendly and meet the WEEE and RoHS legislative
requirements, minimising end of life disposal costs, and are mechanically and
electrically backwards compatible with existing devices.
The MI200-S2 detectors include the standard protocol as well as the new Advanced
protocol for enhanced communication with future Morley-IAS panels, offering more
features.
Specifications
•
•
•
•
•
•
•
•
•
Max. wire gauge for terminals: Colour:
Material: Operating voltage range: Isolation current: Maximum continuous current: Temperature range: Relative humidity: Approved to:
2.5mm²
Pure white
PC/ABS
15 to 28.5VDC
15mA at 24VDC
1A (Switch closed)
-30°C to +70°C
10% to 93% (non-condensing)
EN54 (LPCB & CPD)
1
2
3
4
Pure white
MI-PSE-S2 5
Digital optical detector
6
The MI-PSE-S2 photoelectric smoke detector has a completely new detection
chamber design, the result of many years of research and development. This
delivers improved responsiveness, reduced sensitivity changes caused by settling
dust and reduced false alarms resulting from insect ingress and other debris. The
plug-in unit uses sophisticated processing circuitry that incorporates smoothing
filters to help eliminate transient environmental noise conditions that can be the
cause of unwanted alarms. The devices are managed by embedded software
running complex algorithms that further improve resilience to false alarms and
improve detection speed.
7
8
Specifications
• Weight: • Dimensions (Ø x h): • Approved to:
97g (base inc)
102 mm x 43 mm in base B501AP
EN54-7
CPD number: 0786-CPD-20745
MI-PSE-S2I Digital optical detector with isolator
CPD number: 0786-CPD-20739
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
21
Intelligent Systems
MI-FHSE-S2 Intelligent Detectors
Digital 58°C thermal detector
The MI-FHSE-S2 is fixed temperature intelligent sensors employing low mass
thermistors and microprocessor technology for fast response and linear temperature
sensing. Their linear response allows these sensors to be used to signal temperatures
over the range of 58°C (Class A1S).
Specifications
• Weight: • Dimensions (Ø x h): • Approved to: 88g (without base)
102 mm x 61 mm in base B501AP
EN54-5. Class A1S
CPD number: 0786-CPD-20746
MI-FHSE-S2I
Digital 58°C thermal detector with isolator
CPD number: 0786-CPD-20740
MI-HTSE-S2
Digital 78°C thermal detector
The MI-HTSE-S2 is fixed temperature intelligent sensors employing low mass
thermistors and microprocessor technology for fast response and linear temperature
sensing. Their linear response allows these sensors to be used to signal temperatures
over the range of 78°C (Class BS).
Specifications
• Weight: • Dimensions (Ø x h): • Approved to:
88g (without base)
102 mm x 61 mm in base B501AP
EN54-5. Class BS
CPD number: 0786-CPD-20747
MI-HTSE-S2I Digital 78°C thermal detector with isolator
CPD number: 0786-CPD-20741
MI-RHSE-S2 Digital R.O.R. thermal detector
The MI-RHSE-S2 uses the same thermistor and microprocessor technology to
provide an alarm when the rate of rise in temperature exceeds 10°C/minute (typical)
or if the temperature exceeds a threshold of 58°C (Response Class A1R).
Specifications
• Weight: • Dimensions (Ø x h): • Approved to: CPD number: 0786-CPD-20748
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
22
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
88g (without base)
102 mm x 61 mm in base B501AP
EN54-5. Class A1R
Intelligent Systems
MI-RHSE-S2I Intelligent Detectors
Digital R.O.R. thermal detector with isolator
CPD number: 0786-CPD-20742
MI-PTSE-S2 Digital multi (O/T) detector
The multi-criteria sensor MI-PTSE-S2 Photo Thermal detector uses thermal
assistance to the core photoelectric smoke detector to give enhanced false
alarm immunity and faster response to a wide range of incipient fires. The plugin unit combines two separate sensing elements that are managed by embedded
software to act as a single unit. The detector conforms to EN54-5, a 58°C fixed
temperature and rate of rise thermal assistance conforming to EN54-7. The thermal
detection function combines thermistor technology with a software corrected linear
temperature response.
1
Specifications
• Weight: • Dimensions (Ø x h): • Approved to:
2
97g (base inc)
102 mm x 43 mm in base B501AP
EN54-7, EN54-5
3
CPD number: 0786-CPD-20744
4
MI-PTSE-S2I
Digital multi (O/T) detector with isolator
5
CPD number: 0786-CPD-20738
6
MI-PTIR-S2 Digital multi (O/T/IR) detector
7
The MI-PTIR-S2 multi-criteria, multi-sensor Photo Thermal Infra Red detector is
the environmentally friendly alternative to the ionisation detector, a technology that
is now over sixty years old. The MI-PTIR-S2 offers comparable speed of response
to the ionisation technology for a fast flaming fire and is less susceptible to false
alarms. It can be deployed with confidence in locations where the main risk is
from fast-developing flaming fires. MI-PTIR-S2 moves the goalposts in the fight
against false alarms in the core detector space by delivering enhanced false alarm
immunity. In addition to being an effective alternative to ionisation units, MI-PTIR-S2
offers better performance over the alternative technologies of dual angle or dual
wavelength optical detectors and photo-thermal detectors.
8
Specifications
• Weight: • Dimensions (Ø x h): • Approved to:
102g (base inc)
102 mm x 63 mm in base B501AP
EN54-7, EN54-5
CPD number: 0786-CPD-20743
MI-PTIR-S2I Digital multi (O/T/IR) detector with isolator
CPD number: 0786-CPD-20737
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
23
Intelligent Systems
Intelligent Detectors
Detector Series for Retrofit & Black ceilings
• New mechanical platform with revolutionary chamber offering 3 doors:
- improved false alarm immunity
- improved detection across multiple fire types
- improved resilience to false alarms • Includes the Advanced Protocol
• Available with standard short circuit isolator with status control using the Advanced Protocol
• Tri colour LED offering red, green and amber colour
• Rotary decade address switches 0 - 159
• Ivory colour to complement with retrofit installations using ivory bases and detectors.
• 100% mechanical and electrical backwards compatibility
The MI200-S2 detectors have two integral tri-colour LEDs that provide 360°
local visual indication of the device status. The LEDs are programmable with
static or blinking red, amber and green status indications available. All MI200-S2
detectors are environmentally friendly and meet the WEEE and RoHS legislative
requirements, minimising end of life disposal costs, and are mechanically and
electrically backwards compatible with existing devices.
Specifications
•
•
•
•
•
•
•
•
Max Wire Gauge for Terminals: Material: Operating voltage range: Isolation Current: Maximum continuous current: Temperature range: Relative humidity: Approved to:
2.5mm²
PC/ABS
15 to 28.5VDC
15mA at 24VDC
1A (Switch closed)
-30°C to +70°C
10% to 93% (non-condensing)
EN54 (LPCB & CPD)
Ivory
Please note that the ivory sensors are available on request only. Please check the last price list for lead time information.
MI-PSE-S2-IV
Digital optical detector, ivory
MI-PSE-S2I-IV
Digital optical detector with isolator, ivory
MI-FHSE-S2-IV
Digital 58°C thermal detector, ivory
MI-FHSE-S2I-IV
Digital 58°C thermal detector with isolator, ivory
MI-HTSE-S2-IV
Digital 78°C thermal detector, ivory
MI-HTSE-S2I-IV
Digital 78°C thermal detector with isolator, ivory
MI-RHSE-S2-IV
Digital R.O.R. thermal detector, ivory
MI-RHSE-S2I-IV
Digital R.O.R. thermal detector with isolator, ivory
MI-PTSE-S2-IV
Digital multi (O/T) detector, ivory
MI-PTSE-S2I-IV
Digital multi (O/T) detector with isolator, ivory
MI-PTIR-S2-IV
Digital multi (O/T/IR) detector, ivory
MI-PTIR-S2I-IV
Digital multi (O/T/IR) detector with isolator, ivory
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
24
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Detectors
Black
In order to obtain a black detector, you have to order the standard detector and change the cover with the black cover indicated below.
Attention: The covers are specific per type of detector.
Please note that the black covers for intelligent detectors are available on request only. Please check the last price list for lead time information.
BCK-200EAP
Black detector cover for Optical MI200-S2 detector
BCK-200TEAP
Black detector cover for Optical/Thermal MI200-S2 detector
BCK-200TEMAP
Black detector cover for PTIR MI200-S2 detector
BCK-200REAP
Black detector cover for Thermal MI200-S2 detector
1
2
Intelligent Laser Detector
MI-LZR
• Extremely high sensitivity laser based smoke sensor
• Superior early warning performance
• Effective response to both fast flaming and slow smouldering fires
• Stable communication with high noise immunity
• 9 sensitivity levels (0.07 - 6.56%/m)
• Twin LEDs for 360° visibility
• Built-in test
3
Analogue high sensivity laser detector ivory
4
The MI-LZR high sensitivity laser based intelligent smoke sensor provides an
extremely high sensitivity to fire conditions, by detecting the earliest particles of
combustion. This is achieved by combining a patented optical chamber, the latest
in laser diode and precision optical technology. This combination enhances the
sensitivity of the device. Sophisticated processing circuitry and smoothing filters
help eliminate the effects of transient environmental noise, which can be the cause
of unwanted alarms.
The result is a very sensitive and stable sensor able to achieve sensitivities of 0.07
% to 6.56% per metre obscuration - up to 100 times more sensitive than a standard
photoelectric smoke sensor.
Historically, photoelectric smoke sensors have shown a quick response to slow
smouldering fires, whilst ionisation smoke sensors have responded quicker to
fast flaming fires. The MI-LZR provides a good response to both types of fire by
improving the signal to noise ratio. The use of a laser enables detection of small
particles (usually associated with fast flaming fires), that are not as easily detected
by a standard photoelectric smoke sensor.
A quick response and pin point accuracy makes the MI-LZR especially suitable
for environmental applications where there is substantial cost for down time or a
significant investment in installed equipment has been made. Typical installations
are electronics manufacturers clean rooms, telecommunication rooms and computer
rooms.
5
6
7
8
Specifications
• Dimensions (Ø x h): 102 mm x 42 mm
• Color:Ivory
• Material:
Bayblend FR110
• Terminal wire guage:
2.5mm² max.
• Operating temperature:
-10°C to +55°C
• Relative humidity:
10% to 93%(non condensing)
• Voltage:
+15 to +32 VDC
• Standby current:
No comm.: 230μA @ 24VDC max.
• One comm. every 5 seconds,
LED blink: 330μA @ 24VDC max.
Alarm current: 6.5mA @ 24VDC max.
• Sensitivity modes:
0.07 - 6.56%/m
• Approved to:
EN54-7
CPD number: 0832-CPD-0195
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
25
Intelligent Systems
Intelligent Detector Accessories
Intelligent Detector Accessories
Pure white
B501AP
Standard mounting base
Standard mounting base for intelligent MI200-S2 Series detectors. Contains adress
tag.
Specifications
•
•
•
•
•
•
•
•
•
•
Dimensions (Ø x h): Operating temperature range: Relative humidity: Operating voltage: 102 mm x 22.5 mm
-10°C to +60°C
10% to 93% (non-condensing)
15 to 32 VDC
Rugged industrial construction
Electronic free base allowing cabling to be tested for continuity prior to the installation of the sensors
Compact stylish design
Easy plug in the head of base
Tamper proof feature
SEMS screws for easy wiring
B524HTR-WH
Heated base
Standard base with heater, compatible with the MI200-S2 series. Rises the
temperature of the detector to avoid condensation in the detection room.
Specifications
•
•
•
•
•
•
B524IEFT-1W
Dimensions (Ø x h): Operating temperature range: Relative humidity: Operating voltage: Standby Current: Maximum cable size: Requires 24VDC power supply.
Mounting base with FET isolator, pure white
CPD-number: 0832-CPD-0925
Ivory
B501AP-IV
Standard mounting base, ivory
B524IEFT-1
Mounting base with FET isolator, ivory
B524HTR
Heated base, ivory
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
26
Honeywell | Fire Safety
102 mm x 26 mm
-10°C to +60°C
10% to 93% (non-condensing)
15 to 28.5 VDC
Max 100µA
2.5mm²
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Detector Accessories
Black
The black accessories for intelligent detectors are available on request only. Please check the last price list for lead time information.
B501AP-BK
Standard mounting base
B524IEFT-1B
Mounting base with FET isolator
Accessories
RMK400AP
1
Recess mounting kit
For suspended and drywall ceilings. For use with B501AP base.
2
Specifications
• Weight: • Diameter: • Material: 3
100g
internal 103 mm; ext. 143,5 mm
PC/ABS Pure white
4
SMK400EAP
Surface mounting kit
5
Provides for entry of surface wiring conduit. For use with standard B501AP base.
6
Specifications
• Weight: • Dimensions (Ø x h): • Material: 55g
102 mm x 34 mm
PC/ABS Pure white
7
8
WB-1AP
Wet base shroud
Adapter base enclosure for humid environments. For use with standard B501AP
base. Three mounting options are possible: surface mounting, cable mounting and
pendant mounting.
Specifications
• Weight: • Dimensions (Ø x h):
• Material: 200g
110 mm x 69 mm
PC/ABS Pure white
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
27
Intelligent Systems
IBS-LIDW
Intelligent Detector Accessories
Base cover for B501AP & ABS base sounders (pack of 10)
BA1AP
Pack of 10 pieces.
AP base conduit adapter, white
Item available on request only. Please check the last price list for lead time information.
SFT2000
Installation adaptor for suspended ceiling (pack of 10)
The mounting adapter is used for the quick and secure attachment of bases of
the MI200-S2 and ECO detector series to suspended ceiling systems. It saves the
usage of special hollow cavity fasteners, since the mounting screws of the bases
are screwed directly into the slots of the mounting adapter. The mounting adapter
offers additional advantages in the fixing of the cables, rigid/flexible cable inlays and
threaded cable connections.
Pack of 10 pieces.
Specifications
• Material:ABS
Application examples for the fixing of the cables:
Dimensions in mm:
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
28
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Detector Accessories
Ivory
RMK400AP-IV
Recess mounting kit
SMK400EAP-IV
Surface mounting kit
WB-1AP-IV
Wet base shroud
IBS-LIDDW
Base cover for B501AP-IV, B401 & ABS base sounders (pack of 10)
BA1AP-IV
Pack of 10 pieces.
1
AP base conduit adapter, ivory
Item available on request only. Please check the last price list for lead time information.
2
3
Remote indicators
IRK-2E
LED remote indicator, white
4
The remote indicator lamp has been designed for direct connection to all MorleyIAS fire detectors. It provides a visual alarm indication of the room in which the
detector is installed.
5
6
Specifications
Typical applications:
• All rooms permanently locked (boiler rooms, computer rooms, cupboards,…)
• Health buildings
• Find faster alarm location.
IRK-E-SI
•
•
•
•
•
•
•
•
•
Dimensions (H x W x D ): IP rating: Terminals: Maximum wire section: Operating temperature: Voltage range: Maximum current: Weight: Maximum cable size: 80 mm x 80 mm x 25 mm
IP40
Screw
1.5mm²
-10°C to +70°C
2,5 to 30 VDC
15mA
40g
2.5mm²
7
8
Note: Supply voltage must not exceed 3,5 VDC without limiting resistor. Above this, a serial resistor must be provided with no less than 40 Ohm per Volt (usually inside the detector).
LED remote indicator, ivory
Surface mounted on the supplied mounting plate.
Led's will not blink in normal mode on intelligent systems.
Specifications
•
•
•
•
•
•
Dimensions (H x W x D): IP rating: Operating temperature: Voltage range: Maximum current: Maximum cable size: 86 mm x 86 mm x 36 mm
IP40
-10°C to +70°C
2,5 to 30 VDC
25mA
1.5mm²
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
29
Intelligent Systems
IRK-W-1224
Intelligent Duct Detectors
Waterproof remote indicator
Led based technology. Surface mounted.
LED will blink in normal mode on intelligent systems.
Specifications
• IP rating:
• Voltage range:
IP55
12-24VDC
InnovairFLEXTM
DNRE
Duct detector housing
The DNRE Air Duct Smoke Detector uses photoelectric technology for the detection
of smoke. This detection method, when combined with an efficient housing design,
samples air passing through the duct and allows detection of a developing hazardous
condition.
The DNRE provides a remote alarm output for use with auxiliary devices, such as
the RA100Z remote LED annunciator, as well as remote test capability with the
RTS151 or RTS151KEY Remote Test Stations.
Compatible with MI200-S2 Series detectors.
To be ordered separately: Detector & DST-xx Inlet Sampling Tube.
Specifications
•
•
•
•
•
•
•
Voltage supply:
Air velocity rating:
Dimensions (W x H x D): Weight: Operating temperature: Relative humidity: IP rating:
24VDC
from 1.5m/s to 20.3m/s
370 mm x 127 mm x 63.5 mm
820g
-20°C to +70°C
0% to 95% (non-condensing)
IP40
Air Inlet Tubes for InnovairFLEXTM
DNRE requires an inlet sampling tube as listed below.
Specifications
• Diameter: • Length:
DST-1
Inlet sampling tube (30 cm)
DST-1.5
Inlet sampling tube (45.7 cm)
DST-3
Inlet sampling tube (91.6 cm)
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
30
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
18 mm
DST-1: 30 cm
DST-1.5: 45.7 cm
DST-3: 91.6 cm DST-5: 152 cm
DST-10: 325.5 cm
Intelligent Systems
Intelligent Duct Detectors
DST-5
Inlet sampling tube (152 cm)
DST-10
Inlet sampling tube (325.5 cm)
Accessories for InnovairFLEXTM
RTS151
Remote test station
Proof remote station for DNRE and D2E.
24VDC external power supply is required, according to EN54-4.
1
2
3
4
RTS151KEY
Remote test station with key
5
Proof remote station for DNRE and D2E with key.
6
24VDC external power supply is required, according to EN54-4.
7
8
RA100Z
Remote annunciator
Remote indicator with LED for DNRE and D2E.
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
31
Intelligent Systems
Intelligent Beam Detectors
Intelligent Beam Detectors
MI-LPB2-S2I
Intelligent optical smoke beam detector
The MI-LPB2-S2I is an intelligent reflector type linear optical beam smoke detector
designed to operate as a component of an intelligent fire alarm system. It operates
primarily on the principle of light obscuration utilising infra-red beam. Optical beam
smoke detectors are particularly appropriate for protecting buildings with large open
spaces such as warehouses, atriums etc.
The MI-LPB2-S2I detector is a combined transmitter/receiver unit which can be
directly connected to an intelligent loop. The Infra-Red transmitter generates a
beam of light towards a high efficiency reflector. The reflector returns the beam to
the receiver where an analysis of the received signal is made. The change in the
strength of the received signal is used to determine the alarm condition.
Specifications
• Combined transmitter and receiver unit
• Connects directly to the intelligent loop
• Range 5-100 metres
• 4 fixed sensitivity/threshold adjustment
• 2 automatic variable sensitivity modes
• Operates in the Infra-Red light spectrum
• Numerical indicators to aid beam alignment
• Standby, fault and alarm LED indicators visible from the front and bottom
• ± 10° horizontal & vertical beam alignment
• Automatic drift compensation
• Approved to EN54-12
• Uses the Advanced protocol
• Loop powered
• Contains a short-circuit isolator
• Weight: • Detector dimensions (W x H x D): • Reflector dimensions (W x H):
• Current consumption: • Operating voltage range: • Operating Tempurature Range: • IP Rating:
• Relative humidity: • Approved to:
1.77kg
190 mm x 254 mm x 84 mm
200 mm x 230 mm
- Typical standby: 2mA @ 24 VDC (No communications, LED off)
- Max. Alarm current (LED on): 8.5mA
15 to 32 VDC (24VDC nominal) 15 to 29 VDC if using built-in isolators
-30°C to +55°C
IP54
0% to 95% (non condensing)
EN54-12, EN54-17
CPD-number: 0832-CPD-0329
Includes: Beam detector and short range reflector (5-70m).
Intelligent Beam Detector Accessories
BEAM-LRK
Long-range reflector (70m-100m)
The BEAM-LRK kit contains 3 reflectors (200mm x 230mm).
In combination with the short range reflector supplied with the beam, the 4 reflectors
mounted in square form one big reflector surface which extends the beam range
over 70m, up to a maximum distance of 100m.
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
32
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
BEAM-SMK
Intelligent Beam Detector Accessories
Surface mounting box
Absolutely needed when using the mounting bracket kit.
1
BEAM-MMK
Mounting bracket - swivel type
2
Used for wall mount and ceiling mount applications.
3
Must be used together with surface mounting box BEAM-SMK.
(Beam not included.)
4
5
BEAM-HK
Heater kit for beam detector
6
Avoid condensation problems in non heated rooms.
7
Specifications
• Voltage: • Current:
• Power consumption:
BEAM-HKR
8
15 to 32V
92mA max at 32V
- nominal: 1.6W at 24V
- maximum: 3W at 32V
Heater kit for reflector
Avoid condensation problems in non heated rooms.
Specifications
• Voltage: • Current:
• Power consumption:
15 to 32V
450mA max at 32V
- nominal: 7.7W at 24V
- maximum: 15W at 32V
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
33
Intelligent Systems
Intelligent Manual Call Points
Intelligent Manual Call Points
Indoor (IP24)
•
•
•
•
•
•
•
•
•
Unique ‘Plug & Play’ installation concept
Resettable operating element option
Intelligent communications
Semi-flush or surface mounting
Fully compliant with EN54, Part 11
Backward compatibility
Enhanced aesthetics
Integral LED
Integral loop isolation option
MI-MCP is designed to provide a manual alarm interface to Morley-IAS fire alarm
control panel. Installation efficiency, flexibility and compliance with the latest
standards are at the heart of the call point range.
The unique ‘plug and play’ concept is designed specifically to reduce installation time
by using a terminal block which can be wired during the initial installation cabling
with a link (P102) to provide continuity for testing. During the commissioning phase,
the links are removed and the terminal block is simply inserted into the connector at
the back of the unit. No re-termination is required.
Both break glass, supplied, and resettable operating elements (PS230) can be used
in the standard unit. Operation of the resettable element, as well as being indicated
by the units LED, is also indicated by a yellow strip on the element which becomes
visible when activated. With the addition of a hinged transparent cover (PS200) the
element may be protected against accidental operation and may be further protected
by using a cover seal (PS056) which requires breaking in order to operate the unit.
The call point uses one of 99 possible addresses which is simply ‘dialled in’ using
the two rotary decade switches on the rear of the unit. A specialist test key may be
inserted into the bottom of the unit to lower the glass and release the micro-switch
and thus a full functional test is achieved.
Specifications
• Weight: • Dimensions (W x H x D): • Operating temperature: • Relative humidity: • IP Rating: Flush: 110g / Surface: 160g
- Semi-flush mounting: 89 mm x 93 mm x 27.5 mm
- Surface mounting: 89 mm x 93 mm x 59.5 mm
-10°C to +55°C
0% to 95% (non-condensing)
IP24
CPD number: 0832-CPD-0676 (version without isolator); 0832-CPD-0703
(version with isolator)
Red colour
MI-MCP-GLASS Manual call point with break glass
Including EN54 break glass, without back box. Compatible with standard electric
embedded box with screws.
MI-MCP-GLASS-I Manual call point with isolator & break glass
Including EN54 break glass & isolator, without back box. Compatible with standard
electric embedded box with screws.
MI-MCP-FLEX Manual call point with flexible
Including EN54 flexible element, without back box. Compatible with standard electric
embedded box with screws.
MI-MCP-FLEX-I Manual call point with isolator & flexible
Including EN54 flexible element & isolator, without back box. Compatible with
box with screws.
standard
electric
embedded
For spare parts, please refer to § Spare Parts at the end of this chapter
(01. Intelligent
Systems)
34
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Manual Call Points
Other colours
The MI-MCP call points in other colors contain:
- Operating Element label: EN54-11 'dot & arrows'
- Function label: Plain color
For other labels, please order the specific foil separately (See §. Foil with labels for Call Points & Switches)
Please replace “x” in the part n° by the code for the needed color:
Y = yellow; G = green; B = blue; W = white
Items available on request only. Please check the last price list for lead time information.
1
MI-MCP-GLASS-x Manual call point with break glass
2
Including EN54 break glass, without back box. Compatible with standard electric
embedded box with screws.
3
MI-MCP-GLASS-I-x Manual call point with isolator & break glass
4
Including EN54 break glass, without back box. Compatible with standard electric
embedded box with screws.
MI-MCP-FLEX-x
5
Manual call point with flexible
Including EN54 flexible element, without back box. Compatible with standard electric
embedded box with screws.
MI-MCP-FLEX-I-x 6
7
Manual call point with isolator & flexible
Including EN54 flexible element & isolator, without back box. Compatible with
standard electric embedded box with screws.
8
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
35
Intelligent Systems
Intelligent Manual Call Points
Water resistant (IP67)
Specifications
•
•
•
•
Weight:270g
Dimensions (WxHxD):
97.5 mm x 93 mm x 65.5 mm
Operating temperature: -30°C to +70°C
Color:RAL3001
CPD-number: 0832-CPD-0891 (version without isolator); 0832-CPD-0893
(version with isolator)
Red colour
The red call MI-WCP call points contain:
- Operating element label: EN54-11 “Dot & Arrows”
- Function label: Burning House
For other labels, please order the specific foil separately (See §. Foil with labels for Call Points & Switches)
Items available on request only. Please check the last price list for lead time information.
MI-WCP-R/SG MCP surface with break glass element
Including back box and break glass.
MI-WCP-R/SF MCP surface with flexible element
Including back box and flexible operating element.
MI-WCP-R/I/SG MCP surface with break glass element & isolator
Including back box, break glass and short circuit isolator.
MI-WCP-R/I/SF MCP surface with flexible element & isolator
Including back box, flexible operating element & short circuit isolator.
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
36
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Manual Call Points
Other colours
The MI-WCP call points in other colors contain:
- Operating Element label: EN54-11 'dot & arrows'
- Function label: Plain color
For other labels, please order the specific foil separately (See §. Foil with labels for Call Points & Switches)
Please replace “x” in the part n° by the code for the needed color:
Y = yellow; G = green; B = blue; W = white
Items available on request only. Please check the last price list for lead time information.
1
MI-WCP-x/SG
MI-WCP-x/SF
MCP surface with break glass element
Including back box and break glass.
2
MCP surface with flexible element
3
Including back box and flexible operating element.
MI-WCP-x/I/SF 4
MCP surface with flexible element & isolator
5
Including back box, break glass and short circuit isolator.
6
MI-WCP-x/I/SG
MCP surface with break glass element & isolator
7
Including back box, flexible operating element & short circuit isolator.
8
Intelligent Manual Call Point Accessories
Surface mounting boxes
Please replace “x” in the part n° by the code for the needed color:
Y = yellow; G = green; B = blue; W = white
SR1T
Surface mounting box red
Sx1T
Surface mounting box other color
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
37
Intelligent Systems
Intelligent Manual Call Points
Accessories
PS200
Transparent protective hinged cover
SC071
Please note that the below items are available on request only. Please check the last price list for lead time information.
Terminal blocks (pack of 20)
KL1 X 5
Pack of 20 pieces.
Earth continuity links (pack of 5)
BZR2
Pack of 5 pieces.
Red bezel for flush installation
Foil with labels for Call Points & Switches
Please see the images of the labels on the next page.
Each foil contains 48 labels.
The below items are available on request only. Please check the last price list for lead time information.
MCP-LABEL F 028
Foil with 48 ‘ALARME INCENDIE’ labels (black on red)
MCP-LABEL F 048
Foil with 48 ‘KOEPEL COUPOLE’ labels (white on red)
MCP-LABEL F 056
Foil with 48 ‘BRAND FEU’ labels (black on yellow)
MCP-LABEL F 071
Foil with 48 ‘EMERGENCY STOP’ labels (black on yellow)
MCP-LABEL F 078
Foil with 48 ‘EVACUATION’ labels (black on red)
MCP-LABEL F 081
Foil with 48 ‘FEU’ labels (black on yellow)
MCP-LABEL F 082
Foil with 48 ‘BLUSKNOP’ labels (black on yellow)
MCP-LABEL F 138
Foil with 48 ‘ALERTE INCENDIE’ labels (black on red)
MCP-LABEL F 217
Foil with 48 ‘EXTINCTION’ labels (black on yellow)
MCP-LABEL F 218
Foil with 48 ‘RUNNING MAN’ labels (white on green)
MCP-LABEL F 220
Foil with 48 ‘BIJ NOOD DEUR OPEN’ labels (white on blue)
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
38
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Manual Call Points
MCP-LABEL F 222
Foil with 48 ‘EN54 BURNING HOUSE’ labels (white on red)
MCP-LABEL F 228
Foil with 48 ‘DEUR ONGRENDELING’ labels (white on blue)
MCP-LABEL F 235
Foil with 48 ‘ALERTE WAARSCHUWING’ labels (black on red)
MCP-LABEL F 244
Foil with 48 ‘UITSTEL BLUSSING’ labels (white on blue)
F 028F 048F 056F 071F 078
F 081F 082F 138F 217F 218
1
F 220F 222F 228F 235F 244
2
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
39
Intelligent Systems
Intelligent Modules
Intelligent Modules
The new family of input/output modules are available in single and multi-way models
within the same mechanical package, reducing both the cost of installation and the
mounting space required.
Their unique mechanical design allows each module to be mounted in either a wall
box, on a DIN rail or within any type of enclosure. Irrespective of the mounting
method chosen, the address switch is both visible and accessible for selection.
Each module has built-in short circuit protection for the communications loop;
however, to increase application flexibility, the isolators can be selected/deselected
on an individual module basis.
To help engineers in the maintenance and fault-finding process, both the LEDs
and the switches can be viewed without having to remove the cover of the surface
mounting box. The LEDs, being multi-colour, provide diagnostic information
regarding the status of each individual input/output.
For ease of installation, testing and maintenance, the field wiring terminals are of
plug-in design.
MI-MM3E-S2
Intelligent mini monitor module
Intelligent mini monitor module with 1 monitored input circuit, to supervise alarm
initiating devices or technical signals that have voltage free contact. It connects
directly to the intelligent communication loop.
Compatible with CLIP (99 + 99) protocol.
Specifications
• Weight: • Dimensions (W x H x D): • Approved to:
57g
71 mm x 33 mm x 15 mm
EN54-18
CPD number: 0359-CPD-0176; VDS number: G214118
MI-MM3E/KAC
Intelligent remote indicator driver (LED output)
Intelligent LED output module to be used for driving a remote indicator. It connects
directly to the intelligent communication loop.
Specifications
• Dimensions (W x H x D): MI-DMMI
80 mm x 65 mm x 20mm
Single supervised input module
The MI-DMMI module monitors a single input device circuit of normally open dry
contact alarm activation devices.
Specifications
• Dimensions (W x H x D): • Weight: • Operating voltage: • Operating temperature:
• Relative humidity: • Current consumption: • Approved to:
94 mm x 93 mm x 23 mm
90g
15 to 30VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 310 μA @ 24 VDC (no comm.);
- 510 μA @ 24 VDC (one comm. every 5 sec with LED blink enabled)
EN54-17 & EN54-18
CPD-number: 0786-CPD-20342; VdS number: G202145
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
40
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
MI-DMM2I
Intelligent Modules
Double supervised input module
The MI-DMM2I dual monitor module provides two supervised input device circuits
of normally open dry contact alarm activation devices.
Specifications
• Dimensions (W x H x D): • Weight: • Operating voltage: • Operating temperature: • Relative humidity: • Current consumption: • Approved to:
94 mm x 93 mm x 23 mm
90g
15 to 30 VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 340 μA @ 24 VDC (no comm.),
- 600 μA @ 24 VDC (one comm. every 5 sec with LED blink enabled)
EN54-17 & EN54-18
1
CPD-number: 0786-CPD-20342; VdS number: G202145
2
MI-DCMO
Single supervised output module
3
The MI-DCMO control module provides a monitored single output circuit for use with
polarised loads (sounder circuit) which requires a suitable power source (7VDC 30VDC) for the connected load. Alternatively the same device may be placed in to
an unsupervised mode which can then be used to control any switched load up to
2A @ 30VDC.
4
5
Specifications
• Dimensions (W x H x D): • Weight: • Operating voltage: • Operating temperature: • Relative humidity: • Current consumption: • Approved to:
94 mm x 93 mm x 23 mm
102g
15 to 30 VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 310 μA @ 24 VDC (no comm.)
- 510 μA @ 24 VDC (one comm. every 5 sec with LED blink enabled)
EN54-17 & EN54-18
6
7
8
CPD-number: 0786-CPD-20341; VdS number: G202146
MI-D21CMO
Double supervised input + single relay output
In addition the MI-D21CMO dual input, single relay output module, as well as
providing two supervised inputs also provides a single change over relay output
rated at 2A @30VDC.
The MI-D21CMO uses three addresses of 99 available module addresses on a loop
and responds to regular polls from the control panel reporting its type and the status
(open/normal/ short) of their supervised device circuits.
Specifications
• Dimensions (W x H x D): • Weight: • Operating voltage: • Operating temperature: • Relative humidity: • Current consumption: • Approved to:
94 mm x 93 mm x 23 mm
102g
5 to 30 VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 340 μA @ 24 VDC (no comm.)
- 660 μA @ 24 VDC (one comm. every 5 sec with LED blink enabled)
EN54-17 & EN54-18
CPD-number: 0786-CPD-20343; VdS number: G202144
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
41
Intelligent Systems
MI-D240CMO
Intelligent Modules
Single 240VAC/5A relay module
The MI-D240CMO provides two (1 x N.O. 1 x N.C.) 250Vac (nominal 230Vac), 5Amp
contact outputs. It is provided complete with a surface mounting back box.
Specifications
• Dimensions (W x H x D): • Weight: • Operating voltage: • Operating temperature: • Relative humidity:
• Current consumption: • Approved to:
94 mm x 93 mm x 23 mm
200g
15 to 30VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 275 μA @ 24 VDC (no comm.) - 445 μA @ 24 VDC (one comm. every 5 sec with LED blink enabled)
EN54-17 & EN54-18
CPD-number: 0786-CPD-20341; VdS number: G202146
MI-D240CMO-KO
Single 240VAC/5A relay module (knock outs)
Wall mount with knockouts and rubber grommets, direct decade address entry and
tri-colour LED's complete with built-in isolator.
Specifications
• Dimensions (W x H x D):
• Weight: • Operating voltage: • Operating temperature: • Relative humidity: • Current consumption: • Approved to:
94 mm x 93 mm x 23 mm
200g
15 to 30VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 275 μA @ 24 VDC (no comm.)
- 445 μA @ 24 VDC (one comm. every 5 sec with LED blink enabled)
EN54-17 & EN54-18
VdS number: G202146
MI-D240CMO-DIN
Single 240VAC/5A relay module (DIN rail mount)
The MI-D240CMO-DIN provides two (1 x N.O. 1 x N.C.) 250Vac (nominal 230Vac),
5Amp contact outputs. Complete with DIN mounting enclosure, direct decade
address entry and tri-colour LED’s complete with built-in isolator.
Specifications
• Dimensions (W x H x D): • Weight: • Operating voltage: • Operating temperature: • Relative humidity: • Current consumption: • Approved to:
94 mm x 93 mm x 23 mm
195g
15 to 30VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 275 μA @ 24 VDC (no comm.)
- 445 μA @ 24 VDC (one comm. every 5 sec with LED blink enabled)
EN54-17 & EN54-18
CPD number: 0786-CPD-20341; VdS number: G202146
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
42
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
MI-DISO
Intelligent Modules
Single isolator module
Complete with plug-in screw connections and tri-colour LED.
Specifications
•
•
•
•
•
•
•
Dimensions (W x H x D): Weight: Operating voltage: Operating temperature: Relative humidity:
Current consumption: Approved to:
94 mm x 93 mm x 23 mm
62g
15 to 30 VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
200 μA @ 24 VDC
EN54-17 & EN54-18
CPD-number: 0786-CPD-20340; VdS number: G202142
1
MI-DCZRM
Conventional zone input module
2
Complete with end of line resistors, plug-in screw connections, direct decade
address entry and tri-colour LED's complete with built-in isolator.
3
Specifications
• Dimensions (W x H x D): • Weight: • Operating voltage: • Operating temperature: • Relative humidity: • Current consumption: • Approved to:
4
94 mm x 93 mm x 23 mm
90g
15 to 30 VDC peak
-20°C to +60°C
0% to 95% (non-condensing)
- 310 μA @ 24 VDC (no comm.);
- 510 μA @ 24 VDC (one comm. every 5 sec. with LED blink enabled).
EN54-17 & EN54-18
5
6
CPD number: 0832-CPD-1392; VdS number: G213074
ISO524-1
7
Micro isolator module
8
To build inside SR3T back box of intelligent call point.
Specifications
• Approved to:
EN54-17
CPD number: 0832-CPD-0926
M200-SMB
Surface mount box
To be used with MI series modules.
Specifications
• Dimensions (W x H x D): • IP rating:
139 mm x 134 mm x 40 mm
IP50
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
43
Intelligent Systems
M200-SMB KO
Intelligent Modules
Surface mount box with knockouts
Complete with rubber grommets.
M200-PMB
Panel mounting bracket
With 2 holes for fixing.
To be used with MI series modules.
M200-DIN
DIN-rail bracket
To be used with MI series modules.
MMX-10MH
10 way intelligent input monitor card
Complete with end of line resistors, individual input disable switches, plug in screw
connections and on board LED's with the facility for external LED's (unboxed). Max.
4 connections on an intelligent loop.
Specifications
• Dimensions (W x H x D): • Approved to:
233 mm x 70 mm x 13 mm
EN54-18
CPD number: 0051-CPD-0283
CMX-10RMH
10 way intelligent relay control card
Complete with individual output disable switches, plug in screw connections and on
board LED's with the facility for external LED's (unboxed). Max. 4 connections on
an intelligent loop.
Specifications
• Dimensions (W x H x D): • Contact rating:
• Approved to:
CPD number: 0051-CPD-0284
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
44
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
233 mm x 70 mm x 13 mm
30VDC - 1A
EN54-18
Intelligent Systems
MCX-55MH
Intelligent Modules
5 way intelligent input monitor & 5 way intelligent relay
Complete with end of line resistors and relays (30VDC - 1A) on board LED's with
the facility for external LED's (unboxed). Max. 4 connections on an intelligent loop.
Specifications
• Dimensions (W x H x D): • Approved to:
233 mm x 70 mm x 13 mm
EN54-18
CPD number: 0051-CPD-0285
MI-CZ-6
6 way zone interface multimodule
1
The MI-CZ-6 way zone interface module is intended for use in an intelligent alarm
system. Each module provides an interface between the intelligent alarm system
and a conventional alarm system loop. A common SLC input is used for all modules,
and the initiating device loops share a common supervisory supply and ground.
Otherwise, each monitor operates independently from the others. Requires a
separate reset.
2
3
Specifications
•
•
•
•
•
•
•
Weight: Dimensions (W x H x D): Normal operating voltage:
Stand-By Current: Temperature range: Relative humidity: Approved to:
4
360g
147 mm x 185 mm x 25 mm
15-32 VDC
2 mA
0°C to 49°C
10% to 85% (non-condensing)
EN54-18
5
6
CPD number: 0832-CPD-0929
7
MI-SC-6
6 way supervised sounders outputs
8
The MI-SC-6 six way supervised sounder output module is intended for use in
an intelligent alarm system. Each module is intended for switching applications
involving DC which require wiring supervision. A common SLC input is used for all
modules. Each module has its own address. A pair of rotary code switches is used
to set the address of the first module from 01 to 94. The remaining modules are
automatically assigned to the next five higher addresses.
Provisions are included for disabling a maximum of three unused modules to release
the addresses to be used elsewhere. Each module also has panel controlled green
LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
Specifications
•
•
•
•
•
•
Weight: Dimensions (W x H x D): Normal operating voltage: Stand-By Current: Temperature range: Approved to:
460g
147 mm x 185 mm x 25 mm
15-32 VDC
2.25 mA
-10°C to 55°C
EN54-18
CPD number: 0832-CPD-0930
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
45
Intelligent Systems
SMB6-V0
Intelligent Modules
Multi-mount ABS antistatic box
VO Flame retardant box in grey colour.
Can hold up to 6 MI modules (DIN accessory is not required).
Compatible with MMX-10MH, CMX-10RMH & MCX-55MH.
Specifications
• Weight: • Dimensions (W x H x D): SMBW-VO
700g
245 mm x 180 mm x 50 mm
ABS antistatic box for MI-xx-6
VO Flame retardant box, color cream.
Can hold 1 multimodule (CMX-10RMH, MMX-10MH, MCX-55MH, MI-CZ-6 and MISC-6).
Specifications
• Weight: • Dimensions (W x H x D): BB-2
720g
245 mm x 100 mm x 50 mm
Multi-mount steel cabinet
Up to 2 modules (MI-xx-6 series).
Red coated enclosure.
Specifications
• Dimensions (W x H x D): BB-6
227 mm x 305 mm x 93 mm
Multi-mount cabinet
Up to 6 modules (MI-xx-6 series) can be mounted using the BB-6 mount chassis.
Red coated enclosure.
Specifications
• Dimensions (W x H x D): CH-6
319 mm x 610 mm x 164 mm
Mount chassis for BB-6
The CH-6 chassis is mounted in the BB-6 cabinet.
It is shipped with two self-threading screws, which are used to fasten the chassis to
the back wall of the cabinet.
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
46
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Audio & Visual Devices
Intelligent Audio Visual range (IAV)
B501AP base allows the Intelligent AV range and the MI200-S2 Advanced range to
share a common installation base, giving reduced inventory costs.
• Greater flexibility of installation. Decisions regarding the positioning of AV and smoke
detection can be delayed until the commissioning stage.
• Maintain electrical and mechanical compatibility with the Morley-IAS detector range.
• The visual products meet the requirements of the latest EN54-23.
• The audible products meet the requirements of EN54-03.
• Loop powered with low current draw.
• Sounders and strobes will be fully controllable from the panel, enabling tone selection and
output levels to be set from the panel according to the status of the alarm; all sounders and
strobes on each loop will automatically be synchronised.
• Flush, surface and waterproof mounting base options.
• Loop address set using the familiar rotary switches.
1
The range consists of sounders, strobes and sounder-strobes in both wall-mounted
and detector base configurations. A major feature of the new family is that both the
wall-mounted and detector base devices will use the new Series 200 Advanced
B501AP base, thereby reducing the number of separate parts that have to be
stocked and managed. The new devices are not backwards compatible with the
AVAX base.
2
3
Specifications
• Supply voltage:
• Standby current:
• Temperature range:
• Relative humidity:
• IP rating:
• Wire gauge for terminals:
• Approved to:
15 to 28 VDC
225µA
-25°C to +70°C
Max. 95% (non-condensing)
IP24 with low profile base
(B501AP)IP44 with deep bases (BRR, BPW, BDD) IP65 for MI-BSO-PP-x with sealed deep base (WRR)
1.5 - 2.5mm² max.
EN54-3, EN54-17 and EN54-23
4
5
6
7
IAV Wall Mount Sounder
8
Specifications
• Dimensions (Ø x h):
121 mm x 64 mm
• Weight:168g
• Body color:
Red or Pure white
• Number of tones:
32
• Volume settings:
High, Medium & Low
• Max. current consumption:
11.4mA (High volume tone 21 @ 24V)
• Max. sound output:
97dB(A) ±3dB @ 1m (High volume, tone 8 @ 24V - tone dependent)
CPD number: 0832-CPD-1827 (version without isolator); 0832-CPD-1831
(version with isolator)
MI-WSO-PP-N
Wall mount sounder, no isolator, pure white
MI-WSO-PR-N
Wall mount sounder, no isolator, red
MI-WSO-PR-I
Wall mount sounder, with isolator, red
MI-WSO-PP-I
Wall mount sounder, with isolator, pure white
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
47
Intelligent Systems
Intelligent Audio & Visual Devices
IAV Wall Mount Sounder Strobe
Specifications
• Dimensions (Ø x h):
121 mm x 64 mm
• Weight:238g
• Lens color:
Clear
• Light color:
Red
• Number of tones:
32
• Beacon flash rate:
1Hz
• Volume settings:
High, Medium & Low
• Max. current consumption:
14.7mA (High volume tone 21 @ 24V)
• Max. sound output:
97dB(A) ±3dB @ 1m (High volume, tone 8 @ 24V - tone dependent)
• Approved to:
EN54-3, EN54-17 and EN54-23
CPR number: 0832-CPR-F0274 (version without isolator); 0832-CPR-F0276
(version with isolator)
MI-WSS-PC-N
Wall mount sounder strobe, no isolator, clear, clear lens
MI-WSS-PC-I
Wall mount sounder strobe, with isolator, clear, clear lens
IAV Wall Mount Strobe
Specifications
•
•
•
•
•
•
•
Dimensions (Ø x h):
121 mm x 51 mm
Weight:238g
Lens color:
Transparant or Amber
Light color:
Red or Amber
Beacon flash rate:
1Hz
Max. current consumption:
3.5mA
Approved to:
EN54-17 and EN54-23
CPR number: 0832-CPR-F0272 (version without isolator); 0832-CPR-F0269
(version with isolator)
MI-WST-PC-N
Wall mount strobe, no isolator, clear lens
MI-WST-PC-I
Wall mount strobe, with isolator, clear lens
MI-WST-PA-I
Wall mount strobe, with isolator, amber lens
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
48
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Intelligent Audio & Visual Devices
IAV Integrated Detector Base Sounder
Specifications
• Dimensions (Ø x h):
121 mm x 64 mm
• Weight:200g
• Body color:
Pure white (P) or Ivory (D)
• Number of tones:
32
• Volume settings:
High, Medium & Low
• Max. current consumption:
11.4mA (High volume tone 21 @ 24V)
• Max. sound output:
97dB(A) ±3dB @ 1m (High volume, tone 8 @ 24V - tone dependent)
• Approved to:
EN54-3, EN54-17
CPD number: 0832-CPD-1829 (version without isolator); 0832-CPD-1833
(version with isolator)
MI-BSO-PP-N
Int. detector base sounder, no isolator, pure white
MI-BSO-DD-N
Int. detector base sounder, no isolator, ivory
MI-BSO-PP-I
Int. detector base sounder, with isolator, pure white
MI-BSO-DD-I
Int. detector base sounder, with isolator, ivory
1
2
3
4
IAV Integrated Detector Base Sounder Strobe
5
Specifications
6
• Dimensions (Ø x h):
121 mm x 64 mm
• Weight:202g
• Lens color:
Clear
• Light color:
Red
• Number of tones:
32
• Beacon flash rate:
1Hz
• Volume settings:
High, Medium & Low
• Max. current consumption:
14.7mA (High volume tone 21 @ 24V)
• Max. sound output:
97dB(A) ±3dB @ 1m (High volume, tone 8 @ 24V - tone dependent)
• Approved to:
EN54-3, EN54-17
7
8
CPD number: 0832-CPD-1830 (version without isolator); 0832-CPD-1834
(version with isolator)
MI-BSS-PC-N
Int. detector base sounder strobe, no isolator, clear, clear lens, pure white housing
MI-BSS-PC-I
Int. detector base sounder strobe, with isolator, clear, clear lens, pure white housing
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
49
Intelligent Systems
Intelligent Audio & Visual Devices
IAV Mounting Bases
B501AP
Low profile base - pure white
B501AP-IV
Low profile base - ivory
BRR
Deep profile base - red (includes B501AP)
BDD
Deep profile base - ivory (includes B501AP)
BPW
Deep profile base - pure white (includes B501AP)
WRR
Deep waterproof base - red (includes B501AP)
WDD
Deep waterproof base - ivory (includes B501AP)
WPW
Deep waterproof base - pure white (includes B501AP)
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
50
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Intelligent Systems
Spare parts
Spare parts
Part number
Description
Spare part for:
002-439
Multi mount enclosure
Intelligent modules
020-820
Replacement paper roll for printer
ZXSe
020-836
Spare key for DXc & ZXr
ZXSe & DXc
020-891
Interface lead(cable) for ZX & DX Morley panels to PC (RS232)
ZXSe & DXc
124-196
230VAC mains input filter for all ZX models
Zxe
795-045
RS485 to RS232 convertor
ZXSe
795-051-001
Internal Printer Module for ZX5Se
ZXSe
795-072
Loop driver card Morley protocol for Zxe series panels
ZXSe
795-083
Keyswitch kit. Keyswitch and 2 keys for DX control panels
DX
795-084
Spare Key for all DX control panels (PACK OF 5)
DX
795-085
Internal Printer Module for DX 40 zone Control panels
DX
795-104
DXc Spare door
DXc
795-106
Kit DXc Spare PSU 1 loop
DXc
795-107
DXc spare PSU 2-4 loop
DXc
795-108-003
DXc Spare language pack region 3
DXc
795-109-003
Kit DXc Spare base card 1 loop region 3
DXc
795-109-004
Kit DXc Spare base card 1 loop region 2 version 2
DXc
795-110-003
Kit DXc Spare base card 2 loop region 3
DXc
796-045
Microprocessor board for Zxe series panels Without software (pcb 124-206)
ZXSe
796-150
Single loop motherboard for DX1e (pcb 124-336)
DX
796-151
2 loop motherboard for DX2e/4e (pcb 124-344)
DX
796-152
2 loop PLUG IN card for DX4e (pcb 124-351)
DX
796-153
Display card for all DX panels (pcb 124-335)
DX
796-157
2-Loop Base Mainboard for ZX2e (pcb 124-209-002)
ZXe
796-158
Display 2x40 characters. LCD display (pcb 124-327)
ZXSE
796-161
Power supply for ZX5e 3-Amp.(pcb 124-205-002)
ZXe
796-162
5-Loop Base Mainboard for ZX5Se (pcb 124-354)
ZXSe
796-163
1-Loop Base Mainboard for ZX1e (pcb 124-209-003)
ZXe
796-164-000
Set of EPROMS for ZXe series panels. Eproms programmed with the latest software.
ZXe
796-170
Spare ZX2Se Baseboard
ZXSe
796-171
Spare ZX1Se Baseboard
ZXSe
796-175
Reprofit PSU kit; Panels manufactured before January 2010
ZXSe
796-176
Retrofit PSU Kit for ZX5Se, Panels manufactured before Jan. 2010
ZXSe
796-177
Power supply for ZX1e/ZX2e 2-Amp.(pcb 124-207-003); Panels manufactured since
January 2010
ZXe
796-178
Power supply for ZX5e 2-Amp.; Panels manufactured since January 2010
ZXe
796-180
ZX5Se Retrofit PSU & PCB kit, Panels manufactured before Jan. 2010
ZXSe
796-181
Retrofit 4 lines display plate assembly complete with display and board; Panels
manufactured before January 2010 (ZX5Se)
ZXe
796-182
ZX1Se Retrofit PSU&PCB kit; Panels manufactured before January 2010
ZXSe
796-183
Retrofit 4 lines display plate assembly complete with display and board; Panels
manufactured before January 2010 (ZX1/2Se)
ZXe
796-184
ZX2Se Retrofit PSU&PCB kit; Panels manufactured before January 2010
ZXSe
796-855-M200
Set of Eproms with M200 850 software for Zxse
ZXSe
797-021
Spare Key for all ZX control panels (quantity 1)
ZXe
ESPA4.4.4-TEST_PROG
ZX-ESPA4.4.4 Test software
ZX-ESPA
KEYLCK-DRK220
Lock and Key for all ZX control panels
ZXe
MUS 156
EN54 break glass for MI call points (pack of 10; old code: KG1x10)
Call points
PS230
EN54 flexible op. elements for MI call points (pack of 10)
Call points
SC011
Screws for all MCP call points (pack of 100)
Call points
1
2
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
51
Intelligent Systems
Spare parts
SC070
Spare test keys (pack of 10)
Call points
SC071
Pack of 20 terminal blocks for MCP
Call points
For spare parts, please refer to § Spare Parts at the end of this chapter (01. Intelligent Systems)
52
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional
Systems
Conventional Systems
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
54
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
Conventional Panels
HRZ Series
Developed with efficiency in mind, HRZ2-8 zone non-intelligent fire alarm panels
offer both installers and end users a technically advanced range of functions while
remaining easy to install, program and operate. A full range of non-intelligent
detectors, advanced non-intelligent detectors, beam detectors, manual call points,
duct mounting applications, audible and visible alarm devices are available for use
with the panels.
HRZ2-8 series fire alarm panels are ideally suited for facilities including offices,
shop units, public houses, B & B, clubs, small industrial units, nursing homes and
schools, offering a wide range of benefits to installers and end-users.
•
•
•
•
•
•
•
•
•
•
•
Zones configurable for delay, coincidence, short-circuit alarm, capacitor or resistive end of line
Fire and fault outputs - volt-free relay or monitored (optional)
Auxiliary power output for ancillary equipment
2 configurable inputs for ancillary equipment (e.g. class change, alert, etc.)
Space for two option modules
Optional 8-way relay module, common or zonal switching
Optional 1.5A 4-way sounder module, common or zonal switching
Simple to install
Robust fire resistant ABS moulded
enclosure
Battery space for up to 72 hours stand-by
2, 4 or 8 zone versions available
Specifications
•
•
•
•
•
•
•
•
•
•
•
•
1
Dimensions (W x H x D): 356 mm x 318 mm x 96 mm
Weight: 2kg (without batteries)
Supply rating: 230V~(AC) ± 15%, 50 / 60Hz, 1.6A
Auxiliary output voltage: 18.0-28.5VDC
Auxiliary output current: 0.5A maximum
Sounder circuit: 0.5A maximum per circuit
Sounder circuit total: 1.0A maximum
Operating temperature: -5°C to +45°C
Relative humidity:
5% to 95% (non-condensing)
IP rating: IP30
Optional sounder module may be used with an external power supply to give an additional 1.5A per module
Approved to:
EN54-2 & EN54-4
2
3
4
CPD number: 0786-CPD-20798; BOSEC number: B-9057-FD-892-b
5
The EN54-13 Bosec System certificate (B-9057-FD-892-b) contains the
following items:
• Conventional fire panel
HRZ2-8
• Beam detectors
6500R(S)
• ECO1000 Detectors & Bases:
ECO1002
ECO1003
ECO1005
ECO1005T
ECO1004T
ECO1000B(R)
ECO1000DB(R)
• Manual Call Points
MCP1A-xxxxxx-01
WCP1A-xxxxxx-01
MCP2A-xxxxxx-01
MCP3A-xxxxxx-01
WCP3A-xxxxxx-01
MCP4A-xxxxxx-01
6
7
8
• Sounders
CWSO-RR-S1
CWSO-WW-S1
• Sounders with visual alarm
CWSS-RR-S5
CWSS-WW-S5
• Others
IRK-2E
IRK-E-SI
HRZ2
Two zone conventional fire alarm panel
HRZ4
Four zone conventional fire alarm panel
HRZ8
Eight zone conventional fire alarm panel
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
55
Conventional Systems
Conventional Panels
HRZ Accessories
020-713
FS02 A/F Fire and fault relay expansion card
Fire and fault relay outputs for the HRZ series panels.
Specifications
•
•
•
•
020-747
Weight: Dimensions (L x W x H):
Connection:
Relay contacts:
65g
65 mm x 37 mm x 12 mm
connects directly to the panel using the SK2
Rated 30VDC/1A
8-Way relay board
8 relay outputs which are configurable as N/O or N/C by jumper links (1A @ 30VDC).
Link setting allows 4 function presets to be configured for all 8 relays.
Specifications
•
•
•
020-772
Weight: Max Current (per PCB):
Relay contacts:
210g
- Quiescent 0.1mA - Alarm /all active 80.1mA
Rated at 30VDC, 1A.
Max 2 x 020-747 per panel.
4-Way sounder / monitored output board
Provides 4 monitored circuits with provision for external PSU and 2 digital inputs.
Specifications
•
•
•
•
•
•
•
Sounder PCB outputs: If DIP switch 6 is set to >250mA: If DIP switch 6 is set to <250mA: Digital Inputs: Sounder PCB input: Compliancy: Max Current (per PCB):
Honeywell | Fire Safety
Benelux region
26 - 28.5VDC
4 x 1A (maximum of 1.5A in total for 2 or more outputs)
4 x 250mA
2 x 5-32VDC
20-30VDC, 5A
EN54 Part 4 with power status volt-
free contact (NC when there are no faults present)
- Quiescent: 47mA - Alarm/all active: 1547mA
This board is required to comply with EN54-13.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
56
Catalogue version 2.1
Conventional Systems
Conventional Detectors
ECO1000 Series
•
•
•
•
•
•
•
•
Low profile design
Low current draw
Remote alarm test feature
Easy maintenance
Remote LED option
Certified to EN54-5 and EN54-7
Pan European approvals (CPD, MED and EN regions)
White color
The ECO1000 series is the Morley-IAS range of conventional detectors. These
detectors have been produced using the latest in manufacturing technology and
supplied with an array of advanced features, making them “better by design”.
A laser-based hand held Remote Test Unit can be used in conjunction with the
range of ECO1000 detectors for alarm test purposes. The unit transmits a coded
message, preventing spurious alarms being generated by other laser based devices.
With a range of several meters, the hand held test unit provides an effortless way
of remotely testing the ECO1000 range of detectors and removes the need for any
direct physical access to the detector by the user.
The ECO1000 detectors also have an internal LED, which illuminate to provide a
local alarm signal. This latches on, and remains illuminated until the detector is reset
by a momentary power interruption. An optional remote LED annunciator may be
used to repeat any alarm signal. The detector base is fitted with a shorting spring to
permit circuit testing prior to fitting the detector and has a tamper resistant feature,
which when activated prevents removal of the detector without the use of a tool.
1
2
Specifications
•
•
•
•
•
Operating temperature range: Operating voltage range: Storage temperature range: Relative humidity: Material: -30°C to +70°C
14-28VDC (Nominal 24VDC)
-40°C to +85°C
5% to 95% (non-condensing)
ABS
3
4
ECO1003
Optical conventional detector
5
The ECO1003 photoelectric smoke detector uses a state of the art optical chamber
combined with an application specific integrated circuit (ASIC) to provide quick and
accurate detection of fires. A combination of the unique chamber design and other
technically advanced features will significantly extend the service intervals before
the cleaning of the detector becomes necessary.
6
7
Specifications
• Dimensions (Ø x h): • Weight: 102 mm x 32.5 mm (without base)
75g (+45g for standard base)
8
CPD number: 0832-CPD-0064; Vds number: G201060
ECO1005
Rate of rise thermal conventional detector
The ECO1005 class A1R thermal detector uses a state of the art thermal element
combined with an application specific integrated circuit (ASIC) to provide quick and
accurate detection of fires.
The detector incorporates a static element and is suitable where ambient conditions
normally exhibit high temperatures.
Specifications
• Dimensions (Ø x h): • Weight: 102 mm x 40.5 mm (without base)
70g (+45g for standard base)
CPD number: 0832-CPD-0066; Vds number: G201016
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
57
Conventional Systems
ECO1005T
Conventional Detectors
Fixed thermal conventional detector (58°C)
The ECO1005T class A2S thermal detector uses a state of the art thermal element
combined with an application specific integrated circuit (ASIC) to provide quick and
accurate detection of fires.
The detection incorporates a static element and is suitable where ambient conditions
normally exhibit high temperatures.
Specifications
• Dimensions (Ø x h): • Weight: 102 mm x 40.5 mm (without base)
70g (+45g for standard base)
CPD number: 0832-CPD-0067; Vds number: G201073
ECO1004T
Fixed thermal conventional detector (78°C)
The ECO1004T detector uses a state of the art class BS and A1R thermal element
combined with a microprocessor, running sophisticated algorithms to provide quick
and accurate detection of fires. The detection incorporates a static element and is
suitable where ambient conditions normally inhibit rapid changes in temperature,
eg kitchens.
Specifications
• Dimensions (Ø x h):
• Weight: 102 mm x 40.5 mm (without base)
70g (+45g for standard base)
CPD number: 0832-CPD-0068; VDS number: G204042
ECO1002
Optical/thermal detector
The ECO1002 multi-criteria detector uses a state of the art optical chamber and a
class A1R thermal element combined with a microprocessor, running sophisticated
algorithms to provide quick and accurate detection of fires.
The combination of photoelectric and thermal characteristics provides a faster
response to ‘real fire’ situations, while at the same time reducing the risk of unwanted
environmentally generated alarms.
Specifications
• Dimensions (Ø x h): • Weight:
102 mm x 40.5 mm (no base)
78g (+45g for standard base)
CPD number: 0832-CPD-0065; Vds number: G201067
ECO1000B
Standard mounting base
Specifications
• Dimensions (Ø x h): For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
58
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
102 mm x 21 mm
Conventional Systems
Conventional Detectors
ECO1000BR
Base with 470R resistor
ECO1000DB
Deep base
Specifications
• Dimensions (Ø x h): ECO1000DBR
Deep base with 470R resistor
ECO1000BREL12NL
12V Relay base non latching
102 mm x 33 mm
Interface for 12V systems that do not provide a reset facility.
Resets automatically the ECO detector when the fire alarm condition no longer
exists.
1
2
3
4
ECO1000BREL12L
12V Relay base latching
5
Interface for 12V systems that latches the detector into alarm. The detector can only
be reset by removing its supply voltage. The base can be used with 4 wire security
systems that have a reset facility.
6
7
8
ECO1000BREL24L
24V Relay base latching
Interface for 24V system that requires an external contact. The detector stays in
alarm until the removing of its supply voltage. A break-off tab allows the base to
be connected to fire control panels. This tab should be broken when there is little
current flow or no current limiting resistor such as when used as a 24V stand-alone
system.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
59
Conventional Systems
Conventional Detectors Accessories
Conventional Detectors Accessories
IRK-2E
LED remote indicator, white
The LED remote indicator has been designed for direct connection to all Morley-IAS
fire detectors. It provides a visual alarm indication of the room in which the detector
is installed.
Specifications
Typical applications:
• All rooms permanently locked (boiler rooms, computer rooms, cupboards,…).
• Health buildings.
• Find fast the alarm location.
IRK-2E-B
•
•
•
•
•
•
•
•
•
Dimensions (H x W x D): IP rating: Terminals: Maximum wire section: Operating temperature: Voltage range: Maximum current: Weight: Maximum cable size: 80 mm x 80 mm x 25 mm
IP40
Screw
1.5mm²
-10°C to +70°C
2,5 to 30 VDC
15mA
40g
2.5mm²
Note: Supply voltage must not exceed 3,5 VDC without limiting resistor. Above this, a serial resistor must be provided with no less than 40 Ohm per Volt (usually inside the detector).
LED remote indicator with booster
The IRK-2E-B includes an amplifier which allows the connexion of several LED
remote indicators to a single detector.
Surface mounted on the supplied mounting plate.
IRK-E-SI
LED remote indicator, ivory
Surface mounted with the supplied mounting plate.
Led's will not blink in normal mode on intelligent systems!
Specifications
•
•
•
•
•
•
Dimensions (H x W x D): IP rating: Operating temperature: Voltage range: Maximum current: Maximum cable size: For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
60
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
86 mm x 86 mm x 36 mm
IP40
-10°C to +70°C
2,5 to 30 VDC
25mA
1.5mm²
Conventional Systems
IRK-W-624
Conventional Detector accessories
LED technology remote indicator
Surface mounted. LED blinks in normal mode on intelligent systems.
Specifications
• IP rating: • Voltage range:
SFT2000
IP55
6-24 VDC
Installation adaptor for suspended ceiling (pack of 10)
1
The mounting adapter is used for the quick and secure attachment of bases of the
MI-200-S2 and ECO detector series to suspended ceiling systems. It saves the
usage of special hollow cavity fasteners, since the mounting screws of the bases
are screwed directly into the slots of the mounting adapter. The mounting adapter
offers additional advantages in the fixing of the cables, rigid/flexible cable inlays and
threaded cable connections.
2
3
Pack of 10 pieces.
4
Specifications
• Material:
ABS
5
Dimensions in mm:
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
61
Conventional Systems
Conventional Duct Detectors
InnovairFLEXTM
D2E
Duct detector housing
The duct detector samples air passing through a duct and gives dependable
performance for shutdown of fans, blowers or airco systems, so preventing the
spread of toxic smoke and fire gases through the protected area.
The D2E housing is modular and can be mounted in square or rectangular
configuration. The D2E contains a LED remote indicator output and a B401 base to
be used with the 2351E conventional detector. The conventional smoke detector and
the air inlet sampling tube must be ordered separately. (No Relay output available.)
Specifications
•
•
•
•
•
•
•
2351E
Power supply:
Operating range:
Dimensions (W x H x D): Weight: Operating temperature: Relative humidity: IP rating:
12/24VDC
8.5 to 35VDC
370 mm x 127 mm x 63.5 mm
820g
-20°C to +70°C
0% to 95% (non-condensing)
IP40
Conventional Smoke Detector for D2E
Specifications
•
•
•
•
Dimensions (Ø x h): Weight: Operating temperature: Relative humidity: 102 mm x 47 mm (in B401)
165g (in B401)
-30°C to +70°C
0% to 95% (non-condensing)
Air Inlet Tubes for InnovairFLEXTM
D2E requires an inlet sampling tube as listed below.
Specifications
•
•
Diameter: Length:
DST-1
Inlet sampling tube (30 cm)
DST-1.5
Inlet sampling tube (45.7 cm)
DST-3
Inlet sampling tube (91.6 cm)
DST-5
Inlet sampling tube (152 cm)
DST-10
Inlet sampling tube (325.5 cm)
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
62
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
18 mm
DST-1: 30 cm
DST-1.5: 45.7 cm
DST-3: 91.6 cm DST-5: 152 cm
DST-10: 325.5 cm
Conventional Systems
Conventional Duct Detectors
Accessories for InnovairFLEXTM
RTS151
Remote test station
Proof remote station for DNRE and D2E.
24VDC external power supply is required, according to EN54-4.
1
2
RTS151KEY
3
Remote test station with key
Proof remote station for DNRE and D2E with key.
4
24VDC external power supply is required, according to EN54-4.
5
6
7
8
RA100Z
Remote annunciator
Remote indicator with LED for DNRE and D2E.
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
63
Conventional Systems
Conventional Beam Detectors
Conventional Beam Detectors
6500R(S)
The 6500R and 6500RS are conventional reflector type linear optical beam smoke
detectors designed to operate as a component of a conventional fire alarm system.
It operates primarily on the principle of light obscuration utilising infra-red light.
Optical beam smoke detectors are particularly appropriate for protecting buildings
with large open spaces such as warehouses, atriums etc.
The 6500R and 6500RS detectors are combined transmitter/receiver units, which
can be directly connected to a conventional zone and require a resetable 24VDC
power supply. The Infra-Red transmitter generates a beam of light towards a high
efficiency reflector. The reflector returns the beam to the receiver where an analysis
of the received signal is made. The change in the strength of the received signal is
used to determine the alarm condition.
Specifications
•
•
•
•
•
•
•
•
•
•
•
Combined transmitter and receiver unit
Suitable for connection to a conventional zone
Range 10-100 metres
4 fixed sensitivity/threshold adjustment
2 automatic variable sensitivity modes
Numerical indicators to aid beam alignment
Fault and alarm LED indicators
Integral horizontal and vertical beam alignment
Drift compensation
Approved to EN54-12
Unique servo operated test filter (6500RS)
6500R
•
•
•
•
•
•
Detector dimensions (W x H x D): Reflector dimensions (W x H):
Weight:
Operating temperature range: IP rating: Relative humidity:
254 mm x 84 mm x 90 mm
200 mm x 230 mm
1.77kg
-30°C to +55°C
IP54
0% to 95% (non-condensing)
CPD number: 0832-CPD-0323; VDS number: G205034
For protective cages, see Protective Accessories, Part 6.
100M conv. reflective IR beam detector
Includes: Beam detector and short range reflector (5-70m).
Specifications
• Operating voltage range: • Standby current:
• Alarm current:
6500RS
10.2 to 32VDC (24VDC Nominal)
17mA
38.5mA
100M conv. reflective IR beam detector with self test tool
Same as 6500R with servo motor test tool.
Requires 15V supply to operate Asuretest (remote test capability).
Specifications
• Operating voltage range: • Standby current:
• Alarm current:
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
64
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
15 to 32VDC (24VDC Nominal)
17mA (in Test Mode: 500mA peak)
38.5mA
Conventional Systems
Conventional Beam Detectors
Beam Detector Accessories
BEAM-LRK
Long-range reflector kit (70m-100m)
The BEAM-LRK kit contains 3 reflectors (200mm x 230mm).
In combination with the short range reflector supplied with the beam, the 4 reflectors
mounted in square form one big reflector surface which extends the beam range
over 70m, up to a maximum distance of 100m.
1
BEAM-SMK
Surface mounting box
2
Absolutely needed when using the mounting bracket kit.
3
4
5
6
BEAM-MMK
Mounting bracket - swivel type
7
Used for wall mount and ceiling mount applications.
BEAM-HK
8
Must be used together with surface mounting box BEAM-SMK.
(Beam not included.)
Heater kit for beam detector
Avoid condensation problems in non heated rooms.
Specifications
•
•
•
Voltage: Current:
Power consumption:
15 to 32V
92mA max at 32V
- nominal: 1.6W at 24V
- maximum: 3W at 32V
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
65
Conventional Systems
BEAM-HKR
Conventional Beam Detectors
Heater kit for reflector
Avoid condensation problems in non heated rooms.
Specifications
•
•
•
Voltage: Current:
Power consumption:
15 to 32V
450mA max at 32V
- nominal: 7.7W at 24V
- maximum: 15W at 32V
FireRay ® 50/100R Beam detectors
The FIRERAY® 50/100R series conventional infrared optical beam smoke detectors
provide economical and effective protection of large, open plan spaces with high
ceilings, particularly if access to 'point type' smoke detectors presents practical
difficulties.
Optical beam smoke detectors are ideally suited for protecting warehouses,
factories, atria, shopping malls, leisure centres, churches, museums, power stations
and industrial plants.
The FIRERAY® 50/100R optical beam smoke detectors can be connected to a zone
of a conventional fire alarm control panel, or interfaced to an intelligent system via
an intelligent input module or a zone monitored module.
Specifications
•
•
•
•
•
•
•
•
Combined transmitter and receiver unit in one discrete unit
Range 5-50 Metres (FIRERAY® 50R), 50-100 Metres (FIRERAY® 100R)
Low current consumption
Automatic self check drift compensation
Selectable sensitivity/threshold levels
Selectable latching / non latching fire alarm
LED indicators to aid the alignment process
World-Wide approvals including EN54-12
FR-0206.09
•
•
•
•
•
•
•
•
Operating range F50R: Operating range F100R:
Operating voltage range: Standby current:
Weight: IP rating: Relative humidity: Approvals / Certification: For protective cages, see Protective Accessories, Part 6.
FIRERAY 50R
FR-0206.10
Reflective infrared beam smoke detector, comprising transmitter / receiver unit and reflective prism. 50m range. Including test filter and 1x reflective prism.
FIRERAY 100R
Reflective infrared beam smoke detector, comprising transmitter / receiver unit and reflective prism. 100m range. Including test filter and 4x reflective prisms.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
Honeywell | Fire Safety
5 to 50 Metres
50 to 100 Metres
10.2VDC to 30VDC
17mA
0.67 kg
IP50
0% to 93% (non-condensing)
Designed, manufactured and certified to EN54-12: 2002
CPD number: 0786-CPD-20045; VDS number: G203070
66
Benelux region
Catalogue version 2.1
Conventional Systems
Conventional Beam Detectors
FireRay ® 3000 End-to-End infrared optical beam smoke detector
•
•
•
•
•
•
•
•
•
•
•
•
•
Separate transmitter and receiver heads
Range 5 to 120 metres, configurable per set of detectors
Integral laser alignment in receiver
2-wire Interface between controller and receiver
Single and twin detector options
Separate fire and fault relays per detector
Low level controller with LCD display
Programmable sensitivity and fire threshold
Automatic gain control (AGC) for drift compensation
First fix concept for transmitter, receiver and controller
Multiple cable gland knockouts for ease of wiring
Optional transmitter powering from controller
CPD approved
The FIRERAY 3000 End to End infrared optical beam smoke detector has been
designed using the latest optical technology, incorporating modern industrial
electronics and software technology. This detector offers cost effective protection
for large, open area spaces with high ceilings. It is also very suited to applications
where access to ceiling mounted smoke detectors presents practical difficulties.
The FIRERAY 3000 is ideal for applications where line of sight for the IR (infra-red)
detection path is narrow and where the building structure uses reflective surfaces.
It has also been designed to be aesthetically pleasing and thus can equally suit
modern architectural buildings as well as heritage sites, particularly where ornate
ceilings exist.
The system comprises a modern looking transmitter head, which emits a narrow
beam of infra-red light to an associated Receiver head, with a compact low level
controller. Once smoke crosses through and thus obscures the IR beam path, the
signal strength at the receiver drops below a preset level which in turn results in an
alarm condition.
Both the detector heads, transmitter and receiver, have integrated alignment
thumbwheels for ease of alignment. Using these thumbwheels provides a smooth
and repeatable alignment process. The detector heads have up to 10° of adjustment
in both planes. For further adjustment, a bespoke adjustment bracket is available,
which offers up to 180° movement in both planes, as well as a full 360° rotation.
The FIRERAY 3000 has been designed so that it can be installed by one operator,
with its laser assisted alignment method combined with easy to use alignment
LED’s offering a visual feedback. Integrated laser alignment aid can be activated at
the controller or at the receiver head.
An optional feature is to power the transmitter from the controller by wiring directly,
thus reducing the number of power supplies required.
The low level controller incorporates a LCD display, which offers a full icon-based,
easy-to-use interface unit. This controller enables ease of commissioning, testing
and maintenance of the beam detection system. During commissioning the detector
sensitivity and fire thresholds can be selected, along with the user variable time to
fire and time to fault settings.
The system is fully compliant with the requirements of RoHS and WEEE.
1
2
3
4
5
6
Specifications
•
•
•
•
•
•
•
•
•
•
•
•
•
Operating voltage range: Operating temperature:
Relative humidity:
IP rating:
Dimensions (W x H x D):
Weight:
Operating controller current:
Operating Transmitter current:
Power down reset time:
Fire and Fault relay contacts:
Optical wavelength:
Housing material:
Approved to:
7
12 to 36 VDC
-10°C to +55°C
93% (non-condensing)
IP54
Control unit: 203 mm x 124 mm x 71.5 mm Transmitter & receiver: 78 mm x 77 mm x 161 mm
Control unit: 606g Transmitter & receiver: 207g
14mA (constant) (with 1 or 2 receivers)
8mA (per transmitter)
>10 seconds
VFCO 2A @ 30VDC resistive
850nm
UL94 V2 PC
EN54-12
8
CPD number: 078-CPD-21162; VDS number: G212034
FR-3000-101
Fireray 3000 System
Kit containing: 1 transmitter (clear lens), 1 receiver (dark lens), 1 control unit, 1 test filter
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
67
Conventional Systems
FR-3000-015
Conventional Beam Detectors
Fireray 3000 detector pack
Kit containing: 1 transmitter (clear lens), 1 receiver (dark lens)
Item available on request only. Please check the last price list for lead time information.
FireRay ® 5000 Motorised infrared optical beam smoke detector
The FIRERAY® 5000 motorised reflective, auto aligning infrared optical beam
smoke detector can be installed with up to two detector heads per system, thus
saving on installation time and costs. In addition, each system controller houses
two pairs of fire and fault relays, one per detector. This innovative system has been
designed from the ground up to include pioneering technology that fully addresses
the needs of the installer and user, both now and in the future.
•
•
•
•
•
•
•
•
•
Up to 2 detectors per system controller
Each detector configurable from 8m to 100m
Integral LASER
Auto-align fast automatic beam alignment
Auto-optimise building movement and contamination compensation
Low level system controller
20mm cable gland knockouts on system controller
2-wire interface from system controller to detector
Worldwide approvals including EN54-12
With its industry leading optics, the FIRERAY® 5000 is ideally suited for the
protection of large areas where the use of traditional detection technologies would
prove to be too difficult and/or costly to install. The FIRERAY® 5000 combines an
infrared transmitter and receiver in the same discrete unit and operates by projecting
a well-defined beam to a reflective prism, which returns the beam to the receiver
for analysis. Smoke in the beam path causes a drop in power, which, if below a predetermined level, results in an alarm signal.
Specifications
•
•
•
•
•
•
•
•
Operating voltage range: Operating temperature:
Storage temperature:
Relative humidity:
IP rating:
System controller dimensions (W x H x D):
Operating current:
Approved to:
14 to 28 VDC
-10°C to +55°C
-40°C to +85°C
93% (non-condensing)
IP54
202 mm x 230 mm x 81 mm
37mA max (2 detectors)
EN54-12
CPR number 0832-CPR-F0390; VDS number: G208017
FR-5000-101
For protective cages, see Protective Accessories, Part 6.
FIRERAY 5000 System (50m)
Kit containing: 1 x detector head, 1 x system controller and 1 x reflective prism.
Suitable for operation up to 50m.
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
68
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
FR-5000-102
Conventional Beam Detectors
FIRERAY 5000 System (100m)
Kit containing: 1 x detector head, 1 x system controller and 4 x reflective prisms.
Suitable for operation up to 100m.
Item available on request only. Please check the last price list for lead time information.
FR-5000-002
FIRERAY 5000 single detector
FIRERAY 5000 detector plus 1 x prism for use with the FIRERAY 5000 50m system.
1
Item available on request only. Please check the last price list for lead time information.
2
3
FR-5000-039
FIRERAY 5000 single detector
4
FIRERAY 5000 detector plus 4 x reflective prisms for use with the FIRERAY 5000 100m system.
5
Item available on request only. Please check the last price list for lead time information.
6
7
FR-5000-004
FIRERAY 5000 long range kit
8
Long range kit, comprising 3 x reflective prisms, for use with FIRERAY 5000 system to give 100m capability. Can mount to either the 5000-006 or 5000-007 prism plate.
Specifications
• Dimensions (W x D):
• Weight:
205 mm x 205 mm
255g
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
69
Conventional Systems
Conventional Beam Detectors
FireRay accessories
FR-5000-005
Please note that the FireRay accessories are available on request only. Please check the last price list for lead time information.
Universal bracket
Universal mounting bracket comes pre-drilled to mount the FIRERAY 5000 detector
head as well as the 5000-007 four and 5000-008 single prism mounting plates.
Specifications
• Dimensions (W x H x D):
• Weight:
FR-5000-007
134 mm x 71.5 mm x 134 mm
283g
Four prism plate
Prism plate for 4 prisms (not included) for use with 5000-005 universal bracket (not
included). For beam range from 50m to 100m.
Specifications
• Dimensions (W x H x D):
• Weight:
FR-5000-008
205 mm x 205 mm x 105 mm
255g
Single prism plate
Prism plate for 1 prism (not included) for use with 5000-005 universal bracket (not
included). For beam range from 5 to 50m.
Specifications
• Dimensions (W x H x D):
• Weight:
FR-5000-006
134 mm x 134 mm x 105 mm
142g
Prism mount plate
Surface mount plate for prisms. Hole pattern for 1 or 4 prisms.
Specifications
• Dimensions (W x H x D):
• Weight:
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
70
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
284 mm x 211 mm x 12.7 mm
567g
Conventional Systems
Conventional Beam Detectors
FR-23901.01
Reflective prism
FR-5000-014
Universal ceiling mount
Ceiling pendant mount for use with F5000, F50/100, prism and 5000-005 universal
bracket. Includes universal mounting plate. Does not include universal mounting
brackets or 5000 detectors. Ceiling pendant mount comes with a 1” x 12” long
threaded nipple. Contractor shall provide other nipple lengths as required.
1
2
Specifications
• Dimensions (W x D):
• Weight:
3
216 mm x 216 mm
3.4kg
4
FR-0209
Obscuration filter
5
Only compatible with F50/100
6
FR-0608
F50/100 Back box
7
Surface mount back box for use with FIRERAY 50/100 reflective beam detectors.
8
Specifications
• Dimensions (W x H x D):
• Weight:
FR-0893
190 mm x 248 mm x 49 mm
1.58kg
F50/100 Surface mount alignment bracket
Surface mount alignment bracket for use with FIRERAY 50/100 reflective beam
detectors and prism.
Specifications
• Tilt angle:
• Dimensions (W x H x D):
• Weight:
45°
190 mm x 130 mm x 30 mm
1.02kg
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
71
Conventional Systems
FR-1000-007
Conventional Beam Detectors
Laser pointer
Pointer with red laser, output <5mW, for assisting beam alignment during installation.
FR-3000-201
Fireray 3000 adjustement bracket
The 3000-201 surface mount universal mounting bracket comes pre-drilled to mount
the FIRERAY 3000 detector heads allowing 360° x 180° adjustment. Can also be
used with 5000-007 four and 5000-008 single prism mounting plates.
Specifications
• Dimensions (Ø x H):
• Weight:
FR-3000-202
85 mm x 99.5 mm
283g
Fireray 3000 flush mount plate
The 3000-202 flush mounting plate comes pre-drilled to mount the FIRERAY 3000
detector heads to any flat cable.
Specifications
• Dimensions (Ø x H):
FR-5000-201
99.5 mm x 13.6 mm
Fireray 5000 adjustement bracket
The 5000-201 surface mount universal mounting bracket comes pre-drilled to mount
the FIRERAY 5000 detector heads allowing 360° x 140° adjustment.
Specifications
• Dimensions (Ø x H):
• Weight:
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
72
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
99.5 mm x 98 mm
283g
Conventional Systems
FR-5100-204
Conventional Beam Detectors
Anti-condensation heater for F50/100 beam detector
Heater to prevent condensation on lenses. Only compatible with F50 and F100, with
or without alignment bracket.
The design of the FR-5100-204 utilises forced air, which results in a circulating current
of warm air maintaining the detector lens at an incrementally higher temperature
than the surrounding air. The heater will reduce the likelihood of condensation
forming on the lens which, in turn, reduces the potential for false alarms.
Specifications
•
•
•
•
•
•
•
•
•
FR-3000-204
Operating voltage:
Power consumption at 24V:
Max. in-rush current:
Steady-state current at 24V:
Operating temperature:
Recommended fuse rating:
Connections:
Average temp. increase of lens above ambient:
Dimensions (W x H x D):
24VAC/DC
20W
3A
0.8A (typical)
-10°C to +45°C
T2A
4 leads (2 for heater & 2 for fan)
10°C
126 mm x 210 mm x 181 mm
1
2
Anti-condensation heater for FR-3000 beam detector
3
Heater to prevent condensation on lenses. Only compatible with FR-3000
(transmitter, receiver, universal bracket).
The design of the FR-3000-204 utilises forced air, which results in a circulating current
of warm air maintaining the detector lens at an incrementally higher temperature
than the surrounding air. The heater will reduce the likelihood of condensation
forming on the lens which, in turn, reduces the potential for false alarms.
4
5
Specifications
•
•
•
•
•
•
•
•
•
FR-5000-204
Operating voltage:
Power consumption at 24V:
Max. in-rush current:
Steady-state current at 24V:
Operating temperature:
Recommended fuse rating:
Connections:
Average temp. increase of lens above ambient:
Dimensions (W x H x D):
6
24VAC/DC
20W
3A
0.8A (typical)
-10°C to +45°C
T2A
4 leads (2 for heater & 2 for fan)
10°C
86 mm x 126 mm x 198 mm
7
8
Anti-condensation heater for FR-5000 beam detector
Heater to prevent condensation on lenses. Only compatible with FR-5000 (receiver,
universal bracket).
The design of the FR-5000-204 utilises forced air, which results in a circulating current
of warm air maintaining the detector lens at an incrementally higher temperature
than the surrounding air. The heater will reduce the likelihood of condensation
forming on the lens which, in turn, reduces the potential for false alarms.
Specifications
•
•
•
•
•
•
•
•
•
Operating voltage:
Power consumption at 24V:
Max. in-rush current:
Steady-state current at 24V:
Operating temperature:
Recommended fuse rating:
Connections:
Average temp. increase of lens above ambient:
Dimensions (W x H x D):
24VAC/DC
20W
3A
0.8A (typical)
-10°C to +45°C
T2A
4 leads (2 for heater & 2 for fan)
10°C
128 mm x 146 mm x 189 mm
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
73
Conventional Systems
FR-5000-205
Conventional Beam Detectors
Anti-condensation prism heater
The heater pad is an efficient, ultra slim heating pad which is fixed behind the
mounting plate.
The FR-5000-205 increases the temperature of the prism through the mounting
plate thus maintaining the reflector at a higher temperature than the surrounding
air. This reduces the likelihood of condensation forming on the lens which, in turn,
reduces the potential for false alarms.
Does not include the prisms.
Specifications
•
•
•
•
•
•
•
•
•
Operating voltage:
Power consumption at 24V:
Steady-state current at 24V:
Operating temperature:
Recommended fuse rating:
Connections:
Time taken to reach peak temperature: Average temp. increase of lens above ambient:
Dimensions (W x H x D):
24VAC/DC
20W
0.8A (typical)
-10°C to +35°C
2A
2 x 500 mm PTFE flying leads
30 min.
10°C
284 mm x 38 mm x 284 mm
OSID beam smoke detector
The OSID system measures the level of smoke entering beams of light projected
over an area of protection. A single OSID imager can detect up to 7 emitters to
provide a wide coverage area. Two innovations in smoke detection technology have
been developped for the revolutionary OSID smoke detector. By using advanced
dual wavelength projected beams and optical imaging technology for early warning
smoke detection, OSID provides a low-cost, reliable and easy-to-install solution
that overcomes typical beam detection issues such as false alarm incidents and
alignment difficulties.
•
•
•
•
•
•
Superior smoke detection and nuisance alarm rejection
Simple and fast installation, easy to align
High tolerance to vibration and structural movement
High immunity to dust, steam, birds and insects
High resistance to reflections and sunlight
Minimal free spacing required (20 x 20 cm)
This range is available on request only. Please check the last price list for lead time information.
Specifications
•
•
•
•
Supply voltage:
Imager current consumption:
Emitter current consumption:
Dimensions (Emitter / Imager):
20 to 30VDC (24VDC nominal)
Nominal @ 24VDC: 8mA (1 emitter); 10mA (7 emitters) Peak @ 24VDC (during training mode): 31mA
Wired version @ 24VDC: 350uA (Standard power); 800uA (High power)
198 mm x 130 mm x 96 mm
CPD number: 0333-CPD-075387
OSI-10
OSID Imager, 7° coverage, 24VDC
OSI-45
OSID Imager, 38° coverage, 24VDC
OSI-90
OSID Imager, 80° coverage, 24VDC
OSE-SP-01
OSID Emitter, Standard power, battery version
OSE-SPW
OSID Emitter, Standard power, wired at 24VDC
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
74
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
OSE-HPW
Conventional Beam Detectors
OSID Emitter, High power, wired at 24VDC
OSID beam detector accessories
OSID-INST
Installation kit for OSID beam detectors
Kit containing:
- Laser alignment tool (OSP-002)
- Test filter
- PC cable
- Cleaning cloth
- Manual
OSP-001
FTDI cable 1.5m for OSID beam detectors
OSP-002
Laser alignment tool for OSID beam detectors
OSI-EHI
Environmental housing (IP66) for OSID Imager
OSI-EHE
Environmental housing (IP66) for OSID Emitter
1
2
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
75
Conventional Systems
Manual Call Points & Switches
Conventional manual call points & switches
Indoor (IP24) red colour MCP
The MCP1A range are Manual Call Points (MCP), both with a 470 Ohm resistor and
normally open contact, complete with glass. The MCP1A-R470Fx-01 is designed for
flush mounting. The call points are designed to provide a manual alarm interface to
conventional fire alarm control panels. Both are supplied in the standard red colour.
The red conventional call points contain:
- Operating element label: EN54-11 “Dot & Arrows”
- Function label: Burning House
For other labels, please order the specific foil separately (See §. Foil with labels for Call Points & Switches)
•
•
•
•
•
•
•
Unique ‘Plug & Play’ installation concept
Re-settable operating element option
Resistive and clean contact connections
Semi-flush or surface mounting
Approved to EN54-11
Backward compatibility
Enhanced aesthetics
Specifications
•
•
•
•
Dimensions (W x H x D): Weight: Operating Temperature Range: Operating tension: - Semi-flush mounting: 89 mm x 93 mm x 27.5 mm - Surface mounting: 89 mm x 93 mm x 59.5 mm - Semi-flush: 110g - Surface: 160g
- 10°C to +55°C
24VDC Nominal
The series red MCP is LPCB approved EN54-11
MCP1A-R470FG-01
MCP flush with break glass element
2 outputs: Normally open (max. 30VDC/2A) + monitoring resistor 470R.
CPD number: 0832-CPD-0642
MCP1A-R470FF-01
MCP flush with flexible element
As MCP1A-R470FG-01, but with flexible element.
MCP2A-R470FG-01
MCP flush with break glass element & LED
2 outputs: normally open (max. 30VDC/2A) + monitoring resistor 470R.
CPD number: 0832-CPD-0644
MCP2A-R470FF-01
MCP flush with flexible element & LED
As MCP2A-R470FG-01, but with flexible element.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
76
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
MCP3A-R000FG-01
Manual Call Points & Switches
MCP flush with break glass element with changeover contacts
With changeover contacts (max. 30VDC/2A).
CPD number: 0832-CPD-0648
MCP3A-R000FF-01
MCP flush with flexible element with changeover contacts
As MCP3A-R000FG-01, but with flexible element.
MCP4A-R000FG-01
MCP flush with break glass element
1
With double pole changeover contacts (max. 30VDC/2A).
2
CPD number: 0832-CPD-0649
MCP4A-R000FF-01
3
MCP flush with flexible element
As MCP4A-R000FG-01, but with flexible element.
4
Indoor (IP24) MCP Other colours
The conventional call points in other colors contain: - Operating element label: EN54-11 'dot & arrows'
- Function label: Plain color
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
Please replace “x” in the part n° by the code for
the needed color: Y = yellow (RAL1006); G = green (RAL6016); B = blue (RAL5002); W = white (9010)
Items available on request only. Please check the last price
list for lead time information.
MCP3A-x000FG-11
5
6
7
8
MCP flush with break glass element
With changeover contacts (max. 30VDC).
MCP3A-x000FF-11
MCP flush with flexible element
As MCP3A-x000FG-11 but with flexible element.
MCP4A-x000FG-11
MCP flush with break glass element
With double pole changeover contacts (max. 30VDC).
MCP4A-x000FF-11
MCP flush with flexible element
As MCP4A-x000FG-11 but with flexible element.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
77
Conventional Systems
MCP4A-G000SG-12
Manual Call Points & Switches
MCP surface, green, EDR marking, with break glass
Security range, triple pole MCP
M8A-G000SF
M8 Triple pole call point, green, surface mount with plexi
Includes three change-over outputs to switch three separate circuits.
Specifications:
•
•
•
•
•
•
•
Maximum operating voltage: Maximum current:
IP rating:
Operating temperature:
Weight:
Dimensions (W x H x D):
Colour:
30VDC
2A
IP24D
-30°C to +70°C
180g
89 mm x 93 mm x 59.5 mm
Green, RAL6016
Contains:
Item available on request only. Please check the last price
list for lead time information.
- Triple pole call point, including back box
- 2 Function markings:
- Installation pack
Water resistant (IP67), red coloured MCP
Specifications:
• Operating Temperature Range: • Weight:
• Dimensions (W x H x D):
WCP3A-R000SG-01
-30°C to +70°C
270g
97.5 mm x 93 mm x 65.5 mm
The red call M700WCP call points contain:
- Operating element label: EN54-11 “Dot & Arrows”
- Function label: Burning House
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
IP67 MCP surface with break glass element
With single pole changeover (max. 30VDC/2A). Includes surface mounting box.
CPD number: 0832-CPD-0659
WCP3A-R000SF-01
IP67 MCP surface with flexible element
As WCP3A-R000SG-11, but with flexible element.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
78
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
WCP1A-R470SG-01
Manual Call Points & Switches
IP67 MCP surface with break glass element
2 outputs: normally open (max. 30VDC/2A) + monitoring resistor 470R. Includes
surface mounting box.
CPD number: 0832-CPD-0654
WCP1A-R470SF-01
IP67 MCP surface with flexible element
As WCP1A-R000SG-11, but with flexible element.
1
Water resistant (IP67), MCP other colours
The conventional call points in other colors contain: - Operating element label: EN54-11 'dot & arrows'
- Function label: Plain color
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
Please replace “x” in the part n° by the code for
the needed color: Y = yellow (RAL1006); G = green (RAL6016); B = blue (RAL5002); W = white (9010)
Items available on request only. Please check the last price
list for lead time information.
WCP3A-x000SG-11
2
3
4
5
IP67 MCP surface with break glass element
6
With single pole changeover (max. 30VDC/2A). Includes surface mounting box.
7
WCP3A-x000SF-11
IP67 MCP surface with flexible element
8
As WCP3A-x000SG-11 but with flexible element.
WCP1A-x470SG-11
MCP surface with break glass element
2 outputs: normally open (max. 30VDC/2A) + monitoring resistor 470R. Includes
surface mounting box.
WCP1A-x470SF-11
MCP surface with flexible element
As WCP1A-x470SG-11 but with flexible element.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
79
Conventional Systems
Manual Call Points & Switches
MCP Accessories
PS200
Transparent protective hinged cover
Specifications
• Weight: SC071
37g
Please note that the below items are available on request only. Please check the last price list for lead time information.
Terminal blocks (pack of 20)
KL1 X 5
Pack of 20 pieces.
Earth continuity links (pack of 5)
Pack of 5 pieces.
BZR2
Red bezel for flush installation
PTR
Semi flush tray for MCP
Key switches single pole (K**SxS range)
The keyswitches contain function label: Plain color
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
All the keyswitches (K**xS range) are surface mount. They replace the Wx9100 series.
Please replace “x” in the part n° by the code for the needed color: R = red; Y = yellow; G = green; B = blue; W = white
Specifications:
•
•
•
•
•
•
•
Maximum voltage range:
Current rating:
Operating Temperature Range: Dimensions (W x H x D):
IP rating:
Colour:
Material:
Honeywell | Fire Safety
Benelux region
250VAC @ 50Hz
2A @ 250VAC
-20°C to +55°C
87 mm x 87 mm x 52 mm
IP24
Red, Yellow, Green, Blue or White
ABS
Items available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
80
Catalogue version 2.1
Conventional Systems
K20SxS-01
Manual Call Points & Switches
Key switch, single pole, 2 positions (key removable in both positions)
Replacement for Wx9101 and Wx904.
K21SxS-01
Key switch, single pole, 2 positions (key captive in one position)
Replacement for Wx9102.
K30SxS-01
Key switch, single pole, 3 positions (key removable in all positions)
Replacement for Wx9103.
1
Rocker switches
2
The rocker switches contain: - Function label: Plain color
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
All the rocker switches (Wx920x range) are flush mount.
Please replace “x” in the part n° by the code for the
needed color: R = red; Y = yellow; G = green; B = blue; W = white
3
4
Specifications:
•
•
•
•
•
•
•
Wx9201
Maximum voltage range:
Current rating:
Operating Temperature Range: Relative humidity:
IP rating:
Colour:
Material:
5
240VAC or 24VDC
2A @ 240VAC; 6A @ 24VDC
-20°C to +70°C
0% to 95% (non-condensing)
IP24D
Red, Yellow, Green, Blue or White
ABS
6
7
Items available on request only. Please check the last price
list for lead time information.
8
Rocker switch 2 positions
Double pole changeover contact.
Wx9202
Rocker switch double pole ON/OFF
With 220VAC red neon indicator.
Wx9203
Rocker switch 3 positions
With two sets of three contacts.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
81
Conventional Systems
Manual Call Points & Switches
Miniature push switches
The miniature push switches contain: - Function label: Plain color
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
All the miniature push switches (Wx930x range) are Flush mount.
Please replace “x” in the part n° by the code for the
needed color: R = red; Y = yellow; G = green; B = blue; W = white
Specifications:
•
•
•
•
•
•
•
Maximum voltage range:
Current rating:
Operating Temperature Range: Relative humidity:
IP rating:
Colour:
Material:
240VAC or 24VDC
0.5A @ 240VAC; 1A @ 24VDC
-25°C to +55°C
0% to 95% (non-condensing)
IP24D
Red, Yellow, Green, Blue or White
ABS
Items available on request only. Please check the last price list for lead time information.
Wx9301
Miniature switch momentary action, non terminated
Wx9302
Miniature switch momentary action, terminated
Wx9303
Miniature switch latching, non terminated
Wx9304
Miniature switch latching, terminated
Push switches
The push switches contain: - Function label: Plain color
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
All the push switches (Wx940x range) are Flush mount.
Please replace “x” in the part n° by the code for the
needed color: R = red; Y = yellow; G = green; B = blue; W = white
Specifications:
•
•
•
•
•
•
•
Maximum voltage range:
Current rating:
Operating Temperature Range: Relative humidity:
IP rating:
Colour:
Material:
Wx9403-11
Switch single pole, momentary action
Wx9402
Switch 2 positions
Honeywell | Fire Safety
Benelux region
240VAC or 24VDC
6A @ 240VAC / 24VDC
-25°C to +55°C
0% to 95% (non-condensing)
IP24D
Red, Yellow, Green, Blue or White
ABS
Items available on request only. Please check the last price
list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
82
Catalogue version 2.1
Conventional Systems
Manual Call Points & Switches
Conventional Manual Call Point & Switches Accessories
Surface Mounting boxes
Please replace "x" in the part n° by the code for the needed colour:
Y = yellow; G = green; B = blue; W = white
Specifications:
• Dimensions (W x H x D):
87 mm x 87 mm x 32 mm
1
2
SR0T
Surface mounting box red
Sx0T
Surface mounting box other color
3
4
Foil with labels for Call Points & Switches
Please see the images of the labels on the next page.
Each foil contains 48 labels.
6
The below items are available on request only. Please check the last price list for lead time information.
7
MCP-LABEL F 028
Foil with 48 ‘ALARME INCENDIE’ labels (black on red)
MCP-LABEL F 048
Foil with 48 ‘KOEPEL COUPOLE’ labels (white on red)
MCP-LABEL F 056
Foil with 48 ‘BRAND FEU’ labels (black on yellow)
MCP-LABEL F 071
Foil with 48 ‘EMERGENCY STOP’ labels (black on yellow)
MCP-LABEL F 078
Foil with 48 ‘EVACUATION’ labels (black on red)
MCP-LABEL F 081
Foil with 48 ‘FEU’ labels (black on yellow)
MCP-LABEL F 082
Foil with 48 ‘BLUSKNOP’ labels (black on yellow)
MCP-LABEL F 138
Foil with 48 ‘ALERTE INCENDIE’ labels (black on red)
MCP-LABEL F 217
Foil with 48 ‘EXTINCTION’ labels (black on yellow)
MCP-LABEL F 218
Foil with 48 ‘RUNNING MAN’ labels (white on green)
MCP-LABEL F 220
Foil with 48 ‘BIJ NOOD DEUR OPEN’ labels (white on blue)
MCP-LABEL F 222
Foil with 48 ‘EN54 BURNING HOUSE’ labels (white on red)
5
8
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
83
Conventional Systems
Manual Call Points & Switches
MCP-LABEL F 228
Foil with 48 ‘DEUR ONGRENDELING’ labels (white on blue)
MCP-LABEL F 235
Foil with 48 ‘ALERTE WAARSCHUWING’ labels (black on red)
MCP-LABEL F 244
Foil with 48 ‘UITSTEL BLUSSING’ labels (white on blue)
F 028
F 048
F 056
F 071
F 078
F 081
F 082
F 138
F 217
F 218
F 220
F 222
F 228
F 235
F 244
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
84
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
Audio & Visual Devices
Conventional Audio & Visual Devices - ENscape series
Sounders
The conventional ENscape sounder is a high quality device designed to alert building
occupants of an emergency. The product features a new folded horn design which
provides outstanding sound output at low current draw. With its modern design,
global tone set and extensive installer-friendly features, the ENscape sounder is the
logical choice for specifiers, installers and distributors.
•
•
•
•
•
•
Simple, fast & flexible installation
Suitable for wall and ceiling mount
32 tones, including a bell tone
Two stage sounders enable alert and alarm sequences to be set for phased evacuation
Synchronised sounder output
Approved to EN54-3
Includes (low profile or deep) base, see product description.
1
Specifications
•
•
•
•
•
•
•
Dimensions (Ø x H): Weight: Operating Voltage Range: Current: Max. sound output: Number of tones: Approved to: 100 mm x 77 mm (low profile base)
100 mm x 102 mm (deep base)
190g (low profile base); 197g (deep
base)
9-29VDC
31mA at 29 VDC (Tone 8)
107dB (A) @ 1m (Tone 23)
32, including a bell tone
EN54-3
2
3
4
CPR number: 0832-CPR-F0254; VDS number: G215015
5
CWSO-RR-S1 EN Sounder, red, 32 tones, max. 107dB, incl. low profile base
CWSO-WW-S1 EN Sounder, white, 32 tones, max. 107dB, incl. low profile base
CWSO-RR-W1 EN Sounder, red, 32 tones, max. 107dB, incl. deep base (IP65)
CWSO-WW-W1 EN Sounder, white, 32 tones, max. 107dB, incl. deep base (IP65)
6
7
8
Strobes
The conventional beacons feature high output LEDs, advanced optics and an
innovative lens design, providing outstanding Omni-directional light coverage at
low current draw. Specifically designed for, and approved to meet EN54-23, the
ENscape beacon delivers outstanding quality, reliability and long operational life.
Includes (low profile or deep) base, see product description.
Specifications
•
•
•
•
•
•
Dimensions (Ø x H): Weight: Operating Voltage Range: Current: Flashing frequency:
Approved to: 100 mm x 72 mm (low profile base)
100 mm x 97 mm (deep base)
164g (low profile base); 171g (deep
base)
9-29VDC
26mA at 29 VDC
0.5Hz
EN54-23 C & W categories
CPR number: 0832-CPR-F0257; VDS number: G215016
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
85
Conventional Systems
Audio & Visible Devices
CWST-RW-S5 EN Strobe with red low profile base & white LED, EN54-23 C, W class
CWST-WW-S5 EN Strobe with white low profile base & white LED, EN54-23 C, W class
CWST-RR-S5 EN Strobe with red low profile base & red LED, EN54-23 C, W class
CWST-WR-S5 EN Strobe with white low profile base & red LED, EN54-23 C, W class
CWST-RW-W5 EN Strobe with red deep base & white LED, EN54-23 C, W class (IP65)
CWST-WW-W5 EN Strobe with white deep base & white LED, EN54-23 C, W class (IP65)
CWST-RR-W5 EN Strobe with red deep base & red LED, EN54-23 C, W class (IP65)
CWST-WR-W5 EN Strobe with white deep base & red LED, EN54-23 C, W class (IP65)
Sounder-strobes
The conventional sounder beacon is ideal for applications where a dual purpose
audible and visual alarm device is required. The product features a new folded horn
design, high output LEDs, advanced optics and an innovative lens design, providing
outstanding sound output and omnidirectional light coverage at low current draw.
Specifically designed and approved to meet both EN54-3 and EN54-23, the
ENscape sounder beacon delivers outstanding quality, reliability and extended
operational life.
•
•
•
•
•
•
Simple, fast & flexible installation
Suitable for wall and ceiling mount
32 tones, including a bell tone
Advanced optics ensure superior light coverage
Synchronised flash exceeds EN54-23 standard
Approved to EN54-3 (sounder) and EN54-23, C & W categories (strobe)
Includes (low profile or deep) base, see product description.
Specifications
•
•
•
•
•
•
•
•
Dimensions (Ø x H): Weight: Operating Voltage Range: Current: Max. sound output: Number of tones: Flashing frequency:
Approved to: 100 mm x 98 mm (low profile base)
100 mm x 122 mm (deep base)
low profile base: 248g (W class) or 236g (O class); deep base: 255g (W class) or 242g (O class)
12-29VDC
49mA at 29 VDC (class W) tone 7
22mA at 29VDC (class O) tone 7
107dB (A) @ 1m (Tone 23)
32, including a bell tone
0.5Hz
EN54-23 C, W & O categories
EN54-3
EN54-23 C, W Class
CPR number: 0832-CPR-F0262; VDS number: G215013
CWSS-RW-S5 EN Sounder/Strobe with red low profile base & white LED
CWSS-WW-S5 EN Sounder/Strobe with white low profile base & white LED
CWSS-RR-S5 EN Sounder/Strobe with red low profile base & red LED
CWSS-WR-S5 EN Sounder/Strobe with white low profile base & red LED
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
86
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
Audio & Visual Devices
CWSS-RW-W5 EN Sounder/Strobe with red deep base & white LED (IP65)
CWSS-WW-W5 EN Sounder/Strobe with white deep base & white LED (IP65)
CWSS-RR-W5 EN Sounder/Strobe with red deep base & red LED (IP65)
CWSS-WR-W5 EN Sounder/Strobe with white deep base & red LED (IP65)
EN54-23 Open Class
CPR number: 0832-CPR-F0259; VDS number: G215014
CWSS-RR-S3 EN Sounder/Strobe with red low profile base & red LED
CWSS-WR-S3 EN Sounder/Strobe with white low profile base & red LED
CWSS-RR-W3 EN Sounder/Strobe with red deep base & red LED (IP65)
CWSS-WR-W3 EN Sounder/Strobe with white deep base & red LED (IP65)
1
2
3
4
ENscape accessories
5
The below items are shipped per 5 pieces
CSR Low profile base, red, pack of 5
CSW Low profile base, white, pack of 5
CWR Deep IP65 base, red, pack of 5
CWW Deep IP65 base, white, pack of 5
PS188 Deep base O-ring, pack of 5
PS189 Deep base gasket, pack of 5
SC076 Earther strap, pack of 5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
87
Conventional Systems
Audio & Visible Devices
Base Sounder
Item available on request only. Please check the last price list for Lead time information.
NBS4
Standard base sounder (4 TONES)
Specifications
•
•
•
•
•
•
•
Dimensions (Ø x h): Weight:
Operating temperature range:
Operating voltage:
Current:
Cable section:
Compatible with:
117 mm x 30 mm
180g
-30°C to +70°C
9-33VDC
12mA at 24VDC (800Hz continuous, high volume)
2.5mm²
ECO series
VdS number: G211048; CPD number: 0832-CPD-0393
NBSLID/W
DBS white front LID-Pack of 10
NBSLID/R
Pack of 10 pieces.
DBS white front LID-Pack of 10
Pack of 10 pieces.
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
88
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Conventional Systems
Spare parts
Spare parts
Part number
Description
020-745-008
Spare installation kit, includes 8 capacitive end of lines, battery leads, allen key, panel HRZ2-8
controls key and sounder end of line resistors
Spare part for:
020-817
Spare text insert labels R1, Dutch, French, English, German, Swedish and Danish slide HRZ2-8
in labels
020-823
Spare allen key 4 mm right angle
HRZ2-8
020-849
Two zone replacement PCB
HRZ2-8
020-850
Four zone replacement PCB
HRZ2-8
020-851
Eight zone replacement PCB
HRZ2-8
020-852
Replacement power supply baseboard for HRZ panel range
HRZ2-8
020-865
Pack of 10 spare red keys
HRZ2-8
C 690
Spare key for key switches 2 positions rainproof unit
Switches
MUS 156
Spare EN54 breakglass for all KAC call points (pack of 10)
Conventional call points
OSE-RBA
Spare alkanine battery for emitter OSE-SP-01
OSID
PS230
Spare EN54 flexible operating elements for MCP call points (pack of 10)
Conventional call points
SC011
Screws for MCP call points (pack of 100)
Conventional call points
SC070
Pack of 10 spare test keys
Conventional call points
SC071
Pack of 20 terminal blocks
Conventional call points
SC080
Spare key for key switches 3 positions (pack of 6, replacement for C 273)
Switches
SC086
Spare key for keyswitch 2 positions, K2xD range (pack of 6; replacement for C 787)
Switches
SC087
Spare key for keyswitch 3 positions, K2xD range (pack of 6; replacement for C 788)
Switches
1
2
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
89
Conventional Systems
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (02. Conventional Systems)
90
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Extinguishing
Systems
Extinguishing Systems
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
92
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Extinguishing Systems
VSN-RP1R+
• Compact extinguishing panel controlled by 32 bits microprocessor from the last generation.
• Easy configuration by means of keyboard.
• 2 conventional zones for detectors and a third one configurable for detectors or call points.
• Manual abort switch and hold manual call point.
• Sounder delay configurable from 30 to 300 sec. and verification time from 1 to 10 min
• Delays disabled from keyboard (optional).
• Input circuit for flow and low pressure and open door monitoring.
• Two release circuits. The second one can be used independently for preactivation.
• Countdown timer display which indicates the seconds left for release.
• 40 leds to quickly identify events.
• Relays for General fault, Extinguishing release activated, Preactivation, Extinguishing release in progress, Extinguishing release cancelled, Manual mode, Automatic mode
• Operating mode: Automatic, Manual and Disabled.
• Digital input for remote actions configurable as: system reset, evacuation, silence or delay on/off.
• Plug-in terminals for all connections.
• Designed to comply with EN54-2/4 and EN12094/1:2003.
• CE marking.
Extinguishing Panels
Extinguishing control panel
The VSN-RP1r+ control panel has been designed to efficiently manage the
automatic release sequence of any extinguishing system of gas, CO2 (according
EN12094:1/2003 requirements), foam, dust, aerosol or sprinklers.
The VSN-RP1r+ compact control panel includes: a switched 65W power supply
with battery charger; three input zones to connect directly to two-wire conventional
detectors and external release call point; two release monitored and electronically
protected output circuits and two sounder outputs with different frequencies to
identify each of the extinguishing stages (preactivated mode, activated mode, hold/
abort and release). The front panel includes system status leds, a 2-digit countdown
timer, a GAS sign and a keyswitch for access level 2.
There are inputs circuits for low and flow pressure monitoring, open door control;
hold and release abort call points and status relays (general fault, extinguishing
release activated, preactivation, extinguishing release in progress, extinguishing
release cancelled, manual mode, automatic mode).
VSN-RP1r+ also includes two RS232 interfaces, an USB interface and an I2C which
allows a visualization of the history log using one of the optional communication
interfaces.
1
2
Specifications
• Power supply: • Quiescent current:
• Total max. current: • Batteries: • Load max. current: • Battery fuse: • Outputs:
• 2 monitored sounder outputs: • 2 aux. power supply outputs: • 2 release circuits: • Operating temperature: • Relative humidity: • IP rating: • Dimensions (W x H x D): • Weight:
110 - 230VAC; 50/60Hz.
125mA max.
2.4A
2 x 7Ah
300mA
F4L 250V (4A)
3
4
2 x 250mA
2 x 250mA (resettable and non-
resettable)
1A max. each circuit
from -5ºC to +40ºC
Max. 95% (non-condensing)
IP30
381 mm x 353 mm x 123 mm
4 kg (without batteries)
5
6
7
CPR certification: 1134-CPR-045
8
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
93
Extinguishing Systems
VSN-232
Extinguishing Panels
RS 232 serial interface
Specifications
• Weight:113g
ITAC
Interface module VSN-RP1r+
Communication card to transmit the information of the extinguishing control panel to
the intelligent DXc or ZXSe.
Specifications
•
•
•
•
•
•
• Dimensions (H x Wx D):
ITAC should be installed inside VSN-
RP1r+ box from which it is powered by means of the 4 supplied cables.
Relay included, 1A. NO/NC/C general fault.
16 leds to inform about 16 events max.
Shortcircuit isolator option.
2 rotary switches provided to select the start module addresses (01-99) in the loop.
2 plug-in connectors with 3 terminals each one (+,- and shield).
VSN-4REL
50 mm x 125 mm x 40 mm
4 Relay board
Required to comply with EN12094:1/2003 (Option 4.26).
Specifications
•
•
•
•
•
RACK-SUPRA
Weight:200g
Dimensions (H x Wx D):
357 mm x 382 mm x 94 mm
Operating temperature: -5°C to +45°C
Relative humidity: 5% to 95% (non-condensing)
Contact:2A/30VDC
19’’ Rack mounting kit for VSN-RP1r+
For rack mounting of VSN-RP1r+. Made in black lake iron of 8U height.
Specifications
• Dimensions (H x Wx D):
TFT-SUPRA
Spare TFT 4.3” Touchscreen display for VSN-RP1r+
Optional 4.3” TFT touchscreen for VSN-RP1r+
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
94
Honeywell | Fire Safety
355 mm x 480 mm x 125 mm
Benelux region
Catalogue version 2.1
Extinguishing Systems
Manual Control Units
Manual Control Units
ECP-804900
Manual release call point - class B
Includes: yellow housing, key for reset and enclosure opening.
EN12094-3 compliant.
Labels in Dutch, French, English and German.
Specifications
•
•
•
•
•
•
•
Operating voltage: Connection terminal:
Operating temperature: IP rating:
Housing:
Weight: Dimensions (H x W x D):
8-30VDC
max. 2.5mm²
-10°C to 50°C
IP44
PC ASA plastic
approx. 236g (with housing)
133 mm x 133 mm x 36 mm
1
2
CPD number: 0786-CPD-20194
ECP-804902
3
Electric stop push button - class B
Includes: blue housing, key for reset and enclosure opening.
EN12094-3 compliant.
Labels in Dutch, French, English and German.
4
5
Specifications
•
•
•
•
•
•
•
Operating voltage: Connection terminal:
Operating temperature: IP rating:
Housing:
Weight: Dimensions:
8-30VDC
max. 2.5mm²
-10°C to 50°C
IP44
PC ASA plastic
approx. 236g (with housing)
133 mm x 133 mm x 36 mm
6
7
CPD number: 0786-CPD-20195
8
ESS-704917
IP55 kit for ECP call points
Pack of 10 pieces
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
95
Extinguishing Systems
PUL-D/EXT
Manual Control Units
Manual release call point
Yellow, resettable, manual release call point with included protective cover. For
surface mount. For indoor use only. Includes surface mounting box, protective cover
and key for reset. Labels included in Dutch, French, English and Spanish.
Item available on request only. Please check the last price list for lead time information.
Specifications
•
•
•
•
•
Supply voltage: Operating temperature: Storage temperature: Relative humidity: Dimensions:
24VDC
-10°C to 50°C
-10°C to 50°C
max. 95% (non-condensing)
89 x 89 x 52 mm
CPD number: 1035-CPD-ES044861-2
PUL-P/EXT
Manual stop push button
Blue, resettable, manual stop push button with included protective cover. For surface
mount. For indoor use only. Includes surface mounting box, protective cover and key
for reset. Labels included in Dutch, French, English and Spanish.
Item available on request only. Please check the last price list for lead time information.
Specifications
•
•
•
•
•
Supply voltage: Operating temperature: Storage temperature: Relative humidity: Dimensions:
CPD number: 1035-CPD-ES044861-2
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
96
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
24VDC
-10°C to 50°C
-10°C to 50°C
max. 95% (non-condensing)
89 x 89 x 52 mm
Extinguishing Systems
Emergency Fire Signalling Panels
Emergency Fire Signalling Panels
Optical and acoustic signalling panels suitable for any risk situation such as fire,
flooding, gas extinguishing, etc.
Panels are delivered without labels that have to be ordered separately.
The housing material is a self-extinguishing thermoplastic, white color and the
diffuser is a clear self-extinguishing polycarbonate.
A5055 SS
Order labels separately.
LED’s light signalling panel
1
Specifications
•
•
•
•
Weight: Dimensions (W x H x D):
Rated current:
IP rating: 700g
365 mm x 180 mm x 50 mm
58 mA @ 24VDC
IP30
2
3
A5555 SS
LED’s light signalling panel IP65
4
Specifications
•
•
•
•
•
Weight: Dimensions (W x H x D): Operating temperature: Rated current:
IP rating: 5
900g
325 mm x 130 mm x 80 mm
from -10ºC to +50ºC
58 mA @ 24VDC
IP65
6
7
Text labels
8
Text labels for A5053 SS and A5055 SS Signalling Panels
The below items are available on request only. Please check the last price list for lead time information.
A08670N“BRANDALARM”
A08671N“ONTRUIMINGSALARM”
A08672N
“VERBODEN TOEGANG - GASALARM”
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
97
Extinguishing Systems
A08666
Text labels
“EXTINGUISHING IN PROGRESS”
A08667“ALARM”
A08668
“FIRE ALARM”
A08669
“DO NOT ENTER”
A08670
“ALARME INCENDIE”
A08671
“EVACUATION IMMEDIATE”
A08672
“ENTREE INTERDITE”
A08673
“EINTRITT VERBOTEN”
A08674“FEUERALARM”
A08675
“TIEFGARAGE SOFORT VERLASSEN”
A08676
“BETRETEN VERBOTEN - GASALARM”
A08660
“ALLARME INCENDIO”
A08664
“ABBANDONARE IL LOCALE”
A08658
“VIETATO ENTRARE SPEGNIMENTO AUTOMATICO IMMINENTE”
Other labels can be custom made (min. 100 pcs)
Text labels for A5553 SS and A5555 SS IP65 Signalling Panels
A08670N-W
“BRANDALARM” IP65
A08671N-W
“ONTRUIMINGSALARM” IP65
A08672N-W
“VERBODEN TOEGANG - GASALARM” IP65
A08666-W
“EXTINGUISHING IN PROGRESS” IP65
A08667-W
“ALARM” IP65
A08668-W
“FIRE ALARM” IP65
A08671-W
“EVACUATION IMMEDIATE” IP65
A08672-W
“ENTREE INTERDITE” IP65
A08660-W
“ALLARME INCENDIO” IP65
A08664-W
“ABBANDONARE IL LOCALE” IP65
Other labels can be custom made (min. 100 pcs)
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
98
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Extinguishing Systems
Spare parts
Spare parts
Part number
Description
Spare part for:
ECP-25566A
Foil of 24 Dutch labels for ECP-804900
ECP-804900
ECP-25566A-W
Foil of 12 Dutch and 12 French labels for ECP-804902
ECP-804902
ESS-704901
Blue housing for electric stop push button, includes plastic key
ECP-804902
ESS-704902
Yellow housing for electronic control unit, includes plastic key
ECP-804900
ESS-704910
Break glass for ECP-804900 and ECP-84902
ECP call points
ESS-704911
Front label foil for electronic stop push button, includes Dutch, French, English, German &
Italian labels (Pack of 10; Replacement for ECP-LABELS B)
ECP-804902
ESS-704912
Front label foil for manual control unit, includes Dutch, French, English, German & Italian labels
(Pack of 10; Replacement for ECP-LABELS Y)
ECP-804900
ESS-769910
Plastic key for Class B MCP
ECP call points
PUL-TAP
Spare cover for PUL-VSN/EXT (Pack of 5)
PUL-VSN/EXT
RP1r-CLL
Spare lock & key (1 key only)
VSN-RP1R
RP1r-FA
VSN-RP1R+ spare power supply unit
VSN-RP1R
RP1r-PCB
VSN-RP1R+ base PCA assembly kit
VSN-RP1R
RP1R-SUPRA-KEY
Spare keylock & key for VSN-RP1R+
VSN-RP1R+
RP1R-SUPRA-PCB
VSN-RP1r+ PCB panel
VSN-RP1R+
TFT-SUPRA
Spare TFT 4,3” Touchscreen display for VSN-RP1r+
VSN-RP1R+
VSN-LL
Key switch for level 2 access (only for VSN-RP1r)
VSN-RP1R
1
2
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
99
Extinguishing Systems
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (03. Extinguishing Systems)
100
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special
Equipment
Special Equipment
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
102
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Aspirating Systems
Aspirating Systems
NEW
FAAST XT (Availability will be announced)
The FAAST XT aspirating smoke detector combines advanced particle separation
with unique dual source optical smoke detection technology to provide highly
sensitive Very Early Warning Fire Detection while providing enhanced immunity to
false alarms. This technology enables FAAST XT to accurately detect incipient fire
conditions as early as 60 minutes before a fire actually starts when set for Early
Warning and Very Early Warning Fire Detection in applications ranging from mission
critical to harsh and extreme environments.
An installed FAAST XT device can protect up to 2.676 m² in standard coverage
type applications and can be monitored in several different ways, including: Serial
or TCP Modbus, Ethernet over a LAN or a direct connection, or via FAAST XT’s
onboard USB. When connected to a LAN, FAAST XT’s email server can provide
email event notification to appropriate personnel. FAAST XT also communicates
alarm and notifications via form C relays.
• Provides Very Early Warning Fire Detection, as precise as 0.0015%/m obscuration
• Five alarm levels and three sensitivity modes provide application flexibility
• User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption
• Ultrasonic flow sensing for each pipe inlet and chamber airflow monitoring for precise system health information
• A single device covers up to 2.676 m²
• Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions
• Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life
of the field-replacable filter
• TCP and Serial modbus for easy integration with building management systems
• Easy configuration via USB interface, no external power needed
• Onboard Ethernet interface enables remote monitoring, configuration, web server and e-mail notifications
• Multilingual LCD user interface
• Configurable air flow fault thresholds and verification period
9400X
2
3
Specifications
• Dimensions (H x W x D):
• External supply voltage: • Operating current:
• Operating current:
• Relay contact rating:
• Operating temperature: • Sampling air temperature:
• Relative humidity: • Sensitivity range:
• IP rating: • Coverage area: • Maximum single pipe length:
• Total pipe length:
• Event log:
• Communication network:
• Webserver:
1
338 mm x 333 mm x 191 mm
18-30 VDC
Fan high: 465mA, 11.2W; Fan med.: 340mA, 8.2W; Fan low: 220mA,5.3W
Fan high: 493mA, 11.85W; Fan med.: 368mA, 8.85W; Fan low: 248mA, 6W
3A @ 30VD; 0.5A @ 125VAC
8 form C; 3A, programmable latching or non-latching
0°C to 38°C
-20°C to +60°C
10% to 95% (non-condensing)
0.0015% Obs/m to 20.5% Obs/m
IP30
up to 2676 m²
123m (other three pipes disabled)
320m (all designs must be verified within PipeIQ software)
18.000 events stored
Ethernet monitoring, 6 email address alerts, TCP and serial modbus
Read configuration, live view, logs
4
5
6
7
8
CPD number: pending
FAAST high sensitive aspiration system
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
103
Special Equipment
Aspirating Systems
FAASTTM
• Detection as precise as 0.0015 %/m obscuration
• Five alarm levels and two sensitivity modes provide application flexibility
• Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement
• A single device protects up to 2000 m²
• Advanced detection algorithms reject common nuisance conditions
• Patented particle separator and field-
replaceable filter remove contaminants from the system
• PipeIQ™ software provides intuitive system layout, configuration, and monitoring all in one package
• Integral Ethernet interface enables remote monitoring and e-mail status updates
• Fault indicators provide a broad spectrum of events
• Unique air flow pendulum graph verifies pipe network functionality
• Particulate graph displays subtle environmental changes for early problem indications
• 5 programmable alarm levels for latching or non-latching as well as a 0 to 60 second delay to best accommodate local codes or environments
• At startup FAAST self-adapts to its environment in just 24 hours, not weeks. The exclusive Acclimate mode automatically adjusts within your specified parameters to reduce nuisance alarms and adjust to current conditions.
8100E-BNL
The FAASTTM 8100 aspirating smoke detector combines dual source (blue LED and
infra-red laser) optical smoke detection with advanced algorithms to detect a wide
range of fires while maintaining enhanced immunity to nuisance particulates. This
enables FAASTTM to accurately detect incipient fire conditions as early as 30 to 60
minutes before a fire actually starts for Early Warning Fire Detection and Very Early
Warning Fire Detection.
For initial system creation, the PipeIQ software guides users through pipe layout.
The software also provides intuitive control over system configuration and ongoing
system monitoring.
An installed device can be monitored through its integral display, from a computer
connected to the device, or remotely through a computer browser or mobile device
when the detector is connected to the Internet via its Ethernet port.
When Internet-connected, FAAST can also e-mail status updates to appropriate
personnel. The detector can communicate alarm levels, urgent and minor faults, and
isolate inputs via eight form C relays.
To enable a full detection strategy, FAAST combines its advanced communications
capabilities with an extensive range of customizable settings. The detector provides
five alarm levels that can be programmed for latching or non-latching relays.
To accommodate specific codes or environments, alarm delays can be set
anywhere between 0 to 60 seconds. FAAST also supports two sensitivity modes: In
Acclimate™ mode, the detector automatically adjusts itself to current environmental
conditions to reduce nuisance alarms.
Day/Night/Weekend mode enables technicians to preset alarm thresholds based on
routine changes in the environment.
Specifications
• Dimensions (H x W x D):
• External supply voltage: • Remote reset time: • Power reset: • Avg. operating current: • Operating temperature: • Relative humidity: • IP rating: • Coverage area: CPD number: 0786-CPD-21130; VDS number: G212002
FAAST high sensitive aspiration system, stand alone version
Including English language and a multi language pack (ref. F-A-LC-A) with Dutch, French, German and Italian.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
104
Honeywell | Fire Safety
337 mm x 330 mm x 127 mm
18-30 VDC
external monitor must be pulled low for a minimum of 100 ms
1 sec.
500mA @ 24VDC
0°C to 38°C
10% to 95% (non-condensing)
IP30
up to 2000 m²
Benelux region
Catalogue version 2.1
Special Equipment
Aspirating Systems
FAAST LT Loop version
• Multiple event logging up to 2240 events
• Ultrasonic airflow sensing
• PipeIQ™LT software provides intuitive system layout and configuration all in one package
• User friendly air flow pendulum graph for verification of pipe network functionality
• Protected electronics from air flow and accidental damage during installation or maintenance
• Easily replaceable and reusable filter without affecting the rest of the device
• Designed for efficient wiring and
installation: cable gland holes, easy access to the wiring area and no special tools required.
• Easy access to parts requiring routine maintenance: filter(s) or sensors(s).
• Single & Dual channel versions with independent channels including fan, sensor and flow monitoring
• IP65 enclosure
MI–FL2011EI
The FAAST LT Aspirating Smoke Detector is designed with the installer and end
user in mind. It serves the wide variety of Class C applications where maintenance
is difficult, other smoke detection methods are inappropriate or prone to fail due to
harsh environments or areas where aesthetics matters. It is also suitable for smaller
mission critical applications where very early warning - Class A or B detection is
required.
FAAST LT combines proven aspiration detection technologies to deliver reliable
smoke detection and efficient installation and maintenance. The device includes
high sensitivity laser fire detection, ultrasonic flow sensors, and internal design
features to protect vulnerable components from environmental and human threats.
The device is fast to install and easy to commission thanks to PIPE IQ LT pipe
design and configuration software which is included as standard.
FAAST LT loop based devices are available as single channel and dual channel
devices, offering flexibility for different detection strategies. A range of customisable
settings are geared towards maximizing device performance and meeting different
application needs.
Loop capability allows standard device integration, maintenance and support
consistent with other 200 series devices.
The detector provides alarm and fault relays with auxiliary events relay as an option.
These can be set as latched or non-latched. To accommodate local installation
standards or environments, flow and general fault delays can also be set.
Specifications
•
•
•
•
•
•
•
•
•
•
•
Dimensions (H x W x D):
403 mm x 356 mm x 135 mm
Weight:6.5kg
External supply voltage: 18.5-31.5VDC
Remote reset time: 1 sec.
Power reset: 0.5 sec.
Avg. operating current: 200mA @ 24VDC (excl. sounders)
Max. avg. operating current:
500mA @ 24VDC (excl. sounders)
Operating remperature: -10°C to 55°C
Relative humidity: 10% to 93% (non-condensing)
IP rating: IP65
Sensitivity range:
0.06% - 6% obs/m
FAAST-LT Loop based - 1 channel with 1 laser detector
1
2
3
4
5
6
7
8
CPD number: 0832-CPD-2169
MI–FL2012EI
FAAST-LT Loop based - 1 channel with 2 laser detectors (common chamber) for double knock functionality
CPD number: 0832-CPD-2170
MI–FL2022EI
FAAST-LT Loop based - 2 channels with 2 laser detectors (separated chambers)
CPD number: 0832-CPD-2171
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
105
Special Equipment
Aspirating Systems
FAAST LT Stand alone version
• Configurable sensitivity - 9 levels from 0.06% to 6% obs/m
• Multiple event logging up to 2240 events
• Programmable alarm thresholds
• Ultrasonic airflow sensing
• A single device covers up to 2000m² (2 channel detector with 2x80m pipes with 9 holes per pipe per channel in Class C)
• Particulate graph displays subtle environmental changes for early problem indication
• PipeIQ™LT software provides intuitive system layout and configuration all in one package
• User friendly air flow pendulum graph for verification of pipe network functionality
• Protected electronics from air flow and accidental damage during installation or maintenance
• Easily replaceable and reusable filter without affecting the rest of the device
• Designed for efficient wiring and installation: cable gland holes, easy access to the wiring area and no special tools required.
• Easy access to parts requiring routine maintenance: filter(s) or sensor(s).
• Single & Dual channel versions with independent channels including fan, sensor and flow monitoring
• IP65 enclosure
FL0111E
The FAAST LT Aspirating Smoke Detector is designed with the installer and end
user in mind. It serves the wide variety of Class C applications where maintenance
is difficult, other smoke detection methods are inappropriate or prone to fail due to
harsh environments or areas where aesthetics matters. It is also suitable for smaller
mission critical applications where very early warning - Class A or B detection is
required.
FAAST LT combines proven aspiration detection technologies to deliver reliable
smoke detection and efficient installation and maintenance. The device includes
high sensitivity laser fire detection, ultrasonic flow sensors, and internal design
features to protect vulnerable components from environmental and human threats.
The device is fast to install and easy to commission thanks to PIPE IQ LT pipe
design and configuration software which is included as standard.
FAAST LT stand alone devices are available as single channel and dual channel
devices, offering flexibility for different detection strategies. A range of customisable
settings are geared towards maximizing device performance and meeting different
application needs.
The detector provides alarm, pre-alarm and fault relays with auxiliary events relay
as an option. These can be set as latched or non-latched. To accommodate local
installation standards or environments, flow and general fault delays can also be set.
Day/Night/Weekend mode enables technicians to pre-set alarm thresholds based
on routine changes in the environment’s usage.
Specifications
•
•
•
•
•
•
•
•
•
•
•
•
Dimensions (H x W x D):
403 mm x 356 mm x 135 mm
Weight:6.5kg
External supply voltage: 18.5-31.5VDC
Remote reset time: 1 sec.
Power reset: 0.5 sec.
Avg. operating current: 200mA @ 24VDC (excl. sounders)
Max. avg. operating current:
500mA @ 24VDC (excl. sounders)
Operating temperature: -10°C to 55°C
Relative humidity: 10% to 93% (non-condensing)
IP rating: IP65
Sensitivity range:
0.06% - 6% obs/m
Coverage area:
up to 2000m²
FAAST-LT Stand Alone - 1 channel with 1 laser detector
CPD number: 0832-CPD-1990
FL0112E
FAAST-LT Stand Alone - 1 channel with 2 laser detectors (common chamber)
CPD number: 0832-CPD-1991
FL0122E
FAAST-LT Stand Alone - 2 channels with 2 laser detectors (separated chambers)
CPD number: 0832-CPD-1992
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
106
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Aspirating Systems
NEW
FAAST XS (Availability will be announced)
• Provides Very Early Warning Fire Detection, as precise as 0.00095%/m obscuration
• Three alarm levels and three sensitivity modes provide application flexibility
• User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption
• Ultrasonic flow sensing and chamber airflow monitoring for precise system health information
• A single device covers up to 464 m²
• Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions
• Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life
of the field-replacable filter
• TCP and Serial modbus for easy integration with building management systems
• Easy configuration via USB interface, no external power needed
• Onboard Ethernet interface enables remote monitoring, configuration, web server and e-mail notifications
• Multilingual LCD user interface
• Configurable air flow fault thresholds and verification period
7100X
The FAAST XS aspirating smoke detector combines advanced particle separation
with unique dual source optical smoke detection technology to provide highly
sensitive Very Early Warning Fire Detection while providing enhanced immunity to
false alarms.
This technology enables FAAST XS to accurately detect incipient fire conditions as
early as 60 minutes before a fire actually starts when set for Early Warning and Very
Early Warning Fire Detection in applications ranging from mission critical to harsh
and extreme environments.
An installed FAAST XS device can protect up to 464 m² in standard coverage type
applications and can be monitored in several different ways, including: Serial or TCP
Modbus, Ethernet over a LAN or a direct connection, or via FAAST XS’s onboard
USB. When connected to a LAN, FAAST XS’s email server can provide email event
notification to appropriate personnel. FAAST XS also communicates alarm and
notifications via form C relays.
1
2
Specifications
• Dimensions (H x W x D):
• External supply voltage: • Operating current:
• Operating current:
• Relay contact rating:
• Operating temperature: • Sampling air temperature:
• Relative humidity: • Sensitivity range:
• IP rating: • Coverage area: • Maximum single pipe length:
• Total pipe length:
• Event log:
• Communication network:
• Webserver:
279 mm x 229 mm x 159 mm
18-30 VDC
Fan high: 200mA, 4.8W; Fan med.: 151mA, 3.7W; Fan low: 120mA, 2.1W
Fan high: 230mA, 5.6W; Fan med.: 172mA, 4.2W; Fan low: 142mA, 3.5W
3A @ 30VD; 0.5A @ 125VAC
5 form C; 3A, programmable latching or non-latching
0°C to 38°C
-20°C to +60°C
10% to 95% (non-condensing)
0.00095% Obs/m to 20.5% Obs/m
IP30
up to 464 m²
54.9m (all designs must be verified within PipeIQ software)
91.5m (all designs must be verified within PipeIQ software)
18.000 events stored
Ethernet monitoring, 6 email address alerts, TCP and serial modbus
Read configuration, live view, logs
3
4
5
6
7
8
CPD number: pending
FAAST high sensitive aspiration system
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
107
Special Equipment
Aspirating Systems
FAASTTM and FAAST LT accessories
F-LT-EB
Earth bar for FAAST LT
Item available on request only. Please check the last price list for lead time information.
LaserFocus
VLF-250
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
LaserFocus is available on request only. Please check the last price list for lead time information.
Air sampling smoke detector
Swift-Start™ Operation
SonicFlow™ (Ultrasonic Airflow Sensing)
Laser-based absolute smoke detection
Pre-engineered pipe network designs
Programmable alarm thresholds
Clean air barrier optics protection
Instant recognition display
Instant fault finder™
AutoLearn™ smoke
AutoLearn™ flow
Field service access door
Multiple event logging in separate logs
Event log – up to 18,000 events
Offline/online configuration capability
Up to 250 m² coverage
The VLF-250 Air Sampling Smoke Detector provides very early warning smoke
detection performance for the protection of small, business critical environments of
250m2 or less.
The air sampling detection concept works by continually drawing ambient air through
sampling holes in a pipe network. Upon entering the unit the sampled air is filtered
and passed into the detection chamber where light scattering technology detects
the presence of very small amounts of smoke.
As the amount of detected smoke increases the revolutionary circular Smoke Dial™
provides the user with an instant understanding of a smoke event, even from a
significant distance. Detector status information is communicated externally via
relays or optional interface cards.
Specifications
• Voltage: • Current @ 24 VDC: • Dimensions (W x H x D): • Weight: • IP rating: • Detector ambient: • Sampled air: • Relative humidity: • Maximum pipe lengths: 24VDC Nominal (18-30VDC)
220mA nominal, 295mA in alarm
245 mm x 175 mm x 90 mm
Approx. 2 kg
IP30
0 °C to 40 °C
0 °C to 40 °C
5% to 95% (non-condensing)
1 x 25m (3-6 sampling holes pre-
engineered) / 2 x 15 m per branch (2-4 sampling holes per branch pre-
engineered)
CPD number: 0832-CPD-0771
VLF-500
Early warning smoke detector
As VLF-250, but up to 500m² coverage.
Specifications
• Current @ 24 VDC:
• Maximum pipe lengths:
CPD number: 0832-CPD-0771
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
108
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
410mA nominal, 490mA in alarm
1 x 50m (5-8 sampling holes pre-
engineered) / 2 x 30 m per branch (3-6 sampling holes per branch pre-engineered)
Special Equipment
Aspirating Systems
LaserCompact (VLC)
VLC-500RO
LaserCompact is available on request only. Please check the last price list for lead time information.
VLC detector – relays only
The VLC detector has been specifically designed to provide all the benefits of
aspirating smoke detection, including very early warning, in single environment
small areas and where space is a premium. The VLC combines the well-proven VLP
detection technology with a modified aspirator design, and incorporates them into a
compact enclosure with a simplified display.
The VLC-500RO is capable of monitoring up to 800m². Alarm and pre alarm is
adjustable from 0,005% to 20% obs./m. The LaserCompact detector is fitted with 3
relays (Fire, Pre-alarm and Fault) and a RS232 connection. The RS232 connection
makes commissioning of the unit simple especially with the VSC software.
2
Specifications
• Absolute smoke detection
• Wide sensitivity range
• Single pipe inlet
• Five (5) status LEDs
• Referencing
• VESDAnet communication (VN)
• Clean air barrier optics protection
• Three (3) Alarm Levels
• Three (3) Programmable Relays
• Air flow monitoring
• Optional remote display and relay capability
• Simple mounting design
• AutoLearn™
• Supply voltage: • Power consumption: • Current consumption: • Fuse rating: • Dimensions (W x H x D): • Weight: • Operating conditions: • Recommended detector ambient: • Sampled air: • Relative humidity: • Sampling network: • Maximum pipe lengths: • Computer design tool: • Pipe diameter: • Relays: • IP rating: • Cable access: • Cable termination: • Alarm sensitivity range: 1
18 to 30VDC
5.4 W quiescent, 5.9 W in alarm
225mA quiescent, 245mA in alarm
1.6 A
225 mm x 225 mm x 85 mm
1.9 kg
Tested to -10°C to 55°C
-10°C to 39°C
-20°C to 60°C
10% to 95% (non-condensing)
Maximum area of coverage 800m²
1 x 80 m, 2 x 50 m
ASPIRE2™
internal: 15 – 21 mm; external: 25 mm
3 Relays rated 2A @ 30VDC / Fire (NO) / Pre-Alarm (NO) / Alert/Fault
(Maintenance & Isolate) (NC/NO) / Configurable as latching & non latching
IP30
4 x 25mm cable entries
Screw terminal blocks 0.2–2.5 mm²
0.005% to 20% obs/m
3
4
5
6
7
8
CPD number: 0832-CPD-0770
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
109
Special Equipment
Aspirating Systems
LaserPlus detector
LaserPlus is available on request only. Please check the last price list for lead time information.
VLP-400
LaserPlus detector
LaserPlus is capable of monitoring up to 2000m². Alarm and pre alarm adjustable
from 0,005% to 20% obs./m. The detector is particularly well suited for controlling
various fire extinguishing systems e.g. sprinklers and gasextinguishing installations.
The detector standard comes with 7 software programmable relays. The DualStage
filter ensures that the laserchamber is provided with clean air, to prevent that
the optical parts being polluted by dust. Comes with 3 blank plates, one with two
signalling LED's (Fire 1, Alarm and OK), enclosure IP30.
Specifications
•
•
•
•
Maximum total pipe length: 200m
Maximum individual pipe length:
100m
Power consumption (no programmeror display): 460mA @ 4200rpm
Voltage:24VDC
CPD number: 0832-CPD-0768
VLP-002
LaserPlus with display
As VLP-400, but with a standard display module for reading the actual status of the
detector including alarm levels and system faults. The display is equipped with 4
push buttons for Mode, Mute, Reset and Isolate.
Specifications
• Power consumption (detector and display):
520mA @ 4200rpm
CPD number: 0832-CPD-0768
VLP-012
LaserPlus display programmer
As VLP-002, but with a standard programmer module for configuring and servicing
the detector. With the push buttons and integrated display all values can be entered
and read.
Specifications
• Power consumption (detector with display and programmer): 580mA
CPD number: 0832-CPD-0768
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
110
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Aspirating Systems
Laser Scanner
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Individual pipe identification
Adaptive scan threshold
Wide sensitivity range
Laser based smoke detection
VESDAnet™ communication
4 alarm levels per sector
High efficiency aspirator
Clean air barrier optics protection
Easy to replace air filter
7 or 12 programmable relays option
AutoLearn™
Referencing
Event log
Recessed mounting
VLS-600
LaserScanner is available on request only. Please check the last price list for lead time information.
LaserScanner is similar to the LaserPlus, but includes a valve mechanism in the
inlet manifold and software to control the airflow from the four sectors (pipes). This
configuration enables a single VESDA zone to be divided into 4 separate sectors,
for example, distinguishing between separate voids within a room.
Specifications
• Dimensions (W x H x D):
• Weight: • Supply voltage: • IP rating: • Maximum total pipe length: • Maximum individual pipe length: 350 mm x 225 mm x125 mm
4kg (incl. Display & Programmer
modules)
18–30VDC
IP30
200m
100m
LaserScanner detector
LaserScanner detector is capable of monitoring up to 2000m². Alarm and pre-alarm
adjustable from 0,005% to 20% obs./m.
The LaserScanner detector is able to secure and monitor up to four different zones.
In normal operation the detector draws air from all zones.
When the smokelevel reaches the Adaptive Scan Threshold, the Scanner will
retrace the source of the smoke and scan each pipe individually.
Comes with three blank plates, one with signalling LED's.
1
2
3
4
5
6
Specifications
• Power consumption (without programmer
or display): 400mA @ 4200rpm
7
CPD number: 0832-CPD-0769
8
VLS-700
LaserScanner three blank plates/leds 12 relays
As VLS-600 but with 12 software programmable relays.
CPD number: 0832-CPD-0769
VLS-204
LaserScanner detector standard display
As VLS-600, but with a standard display module for reading the actual status of the
detector including alarm levels and system faults. The display is equipped with 4
push buttons for Mode, Mute, Reset and Isolate.
Specifications
•
•
•
Power consumption (detector with display):
460mA @ 4200rpm
Voltage: 24VDC
Power consumption (without programmer or display):
400mA @ 4200rpm
CPD number: 0832-CPD-0769
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
111
Special Equipment
VLS-304
Aspirating Systems
LaserScanner with display 12 relays
As VLS-204 but with 12 software programmable relays.
CPD number: 0832-CPD-0769
VLS-214
LaserScanner with display and programmer 7 relays
As VLS-204, but with a standard programmer module for configuring and servicing
the detector. With the push buttons and integrated display all values can be entered
and read.
Specifications
• Power consumption (detector with display and programmer): 580mA
CPD number: 0832-CPD-0769
VLS-314
LaserScanner with display and programmer 12 relays
As VLS-214 but with 12 software programmable relays.
CPD number: 0832-CPD-0769
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
112
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Sampling pipes & fittings
Sampling pipes & fittings
Red
ABS 008/25
The red sampling pipes & fittings are packed per 10 units.
Pipe (ABS), red, diameter 25 mm - 3 metres long, pack of 10
3 metres long pipe with external diameter of 25mm and interior diameter of 21mm
with ABS material. Red color.
1
Specifications
• Weight: 5kg (30 meters)
2
ABS 001/25
90° (ABS) bend for 25mm pipe, red, pack of 10
3
Specifications
• Weight: 146g (for 10 units)
4
5
ABS 002/25
45° (ABS) elbow for 25mm pipe, red, pack of 10
6
Specifications
• Weight: ABS 030/25
260g (for 10 units)
Flexible pipe, diameter 25mm, transparent
7
8
Specifications
• Pipe length:
30 cm
ABS 003/25
Socket union (ABS) for 25mm pipe, red, pack of 10
ABS 004
Mounting clips for 25mm pipe, red, pack of 10
Specifications
• Weight: 76g (for 10 units)
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
113
Special Equipment
ABS 005/25
Sampling Pipes & Fittings
Socket to socket sleeve (ABS) for 25mm pipe, red, pack of 10
Jointing socket between two externals 25mm diameters pipes.
Specifications
• Weight: 120g (10 units)
ABS 005-1
Socket to socket sleeve (ABS) for 27 to 25mm pipe, red, pack of 10
ABS 006/25
T-piece (ABS) for 25mm pipe, red, pack of 10
Specifications
• Weight: ABS 007/25
266g (10 units)
End cap (ABS) for 25mm pipe, red, pack of 10
Specifications
• Weight: 66g (10 units)
White
The white sampling pipes & fittings are packed per 10 units.
The white sampling pipes & fittings are available on request only. Please check the last price list for lead time information.
ABS 008/25-WH
Pipe (ABS), white, diameter 25 mm - 3 metres long, pack of 10
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
114
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Sampling Pipes & Fittings
ABS 001/25-WH
90° (ABS) bend for 25mm pipe, white, pack of 10
ABS 002/25-WH
45° (ABS) elbow for 25mm pipe, white, pack of 10
1
ABS 003/25-WH
Socket union (ABS) for 25mm pipe, white, pack of 10
2
3
4
ABS 004-WH
Mounting clips for 25mm pipe, white, pack of 10
5
6
7
ABS 005/25-WH
Socket to socket sleeve (ABS) for 25mm pipe, white, pack of 10
ABS 005-1-WH
Socket to socket sleeve (ABS) for 27 to 25mm pipe, white, pack of 10
ABS 006/25-WH
T-piece (ABS) for 25mm pipe, white, pack of 10
8
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
115
Special Equipment
ABS 007/25-WH
Sampling Pipes & Fittings
End cap (ABS) for 25mm pipe, white, pack of 10
Remote sampling point assemblies
ABS 010
Warning labels for capillary sampling point, roll of 100 pieces
For the marking of the intake points of the PVC/ABS pipe(s).
Roll of 100 labels.
Specifications
• Weight: ABS 011
50g
Cement 250ml
Remote sampling point assemblies
Red
ABS 019C/25
Capillary conical sample point kit for 25mm pipes, red
To connect on an ABS 008/25 pipe. For flexible installation or suspended ceilings.
Kit containing: ABS 019F/25
- T-piece
- 2 meter capilary tube
- Sampling point (conical head)
Capillary flush sample point kit for 25mm pipes, red
To connect on an ABS 008/25 pipe. For flexible installation or suspended ceilings.
Kit containing: For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
116
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
- T-piece
- 2 meter capilary tube
- Sampling point (flush disc head)
Special Equipment
Sampling Pipes & Fittings
ABS 020/25
The below items are available on request only. Please check the last price list for lead time information.
Capillary discrete sample point kit for 25mm pipes, red
To connect on an ABS 008/25 pipe. For flexible installation or suspended ceilings.
Kit containing: ABS 019C/25EC
- T-piece
- 2 meter capilary tube
- Sampling point (discrete head)
Capillary conical sample point kit for 25mm pipes (end cap), red
To connect on an ABS 008/25 pipe. For flexible installation or suspended ceilings.
1
Kit containing: 2
- End cap
- 2 meter capilary tube
- Sampling point (conical head)
3
ABS 019F/25EC
Capillary flush sample point kit for 25mm pipes (end cap), red
To connect on an ABS 008/25 pipe. For flexible installation or suspended ceilings.
Kit containing: - End cap
- 2 meter capilary tube
- Sampling point (flush disc head)
4
5
6
ABS 020/25EC
Capillary discrete sample point kit for 25mm pipes (end cap), red
7
Point 8mm to connect on an ABS 008/25 pipe. For flexible installation or suspended
ceilings.
8
Kit containing: 510-KIT
- End cap
- 2 meter capilary tube
- Sampling point (discrete head)
Capillary flush sample point kit for 25mm pipes (T-piece), red
Ideal for mounting in false ceilings.
Kit containing capillary sampling point, a 1 meter tube made of flexible nylon (10mm outer diameter and 8mm inner diameter), ceiling mount and T-piece for connection to the aspiration pipe network and a kit of 8 white sampling points, with diameters of 2, 2.5, 3, 3.5, 4, 4.5, 5 and 6 mm.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
117
Special Equipment
Sampling Pipes & Fittings
510-FIN
The below items are available on request only. Please check the last price list for lead time information.
Capillary flush sample point kit for 25mm pipes (end cap), red
Ideal for mounting in false ceilings.
520-MTS-80R
Kit containing capillary sampling point, a 1 meter tube made of flexible nylon (10mm outer diameter and 8mm inner diameter), ceiling mount
and end cap for connection to the aspiration pipe network and a kit of 8 white sampling points, with diameters of 2, 2.5, 3, 3.5, 4, 4.5, 5 and 6 mm.
Pack of 5 sampling point kits, red (for 510-KIT only)
Kit of 8 sampling points, with diameters of 2, 2.5, 3, 3.5, 4, 4.5, 5 and 6 mm. In red
ABS material. Only for use with 510-KIT and 510-FIN.
White
The below items are available on request only. Please check the last price list for lead time information.
ABS 019C/25-WH
Capillary conical sample point kit for 25mm pipes, white
ABS 019F/25-WH
Capillary flush sample point kit for 25mm pipes, white
ABS 020/25-WH
Capillary discrete sample point kit for 25mm pipes, white
ABS 019C/25EC-WH
Capillary conical sample point kit for 25mm pipes (end cap), white
ABS 019F/25EC-WH
Capillary flush sample point kit for 25mm pipes (end cap), white
ABS 020/25EC-WH
Capillary discrete sample point kit for 25mm pipes (end cap), white
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
118
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Sampling Pipes & Fittings
Components
Red
ABS CAP-RED
The below items are available on request only. Please check the last price list for lead time information.
10mm nylon flexible - red (per metre)
1
2
3
ABS 021/25
Capillary end cap for ABS 008/25 pipe
4
Reduces 25 m pipe to 10mm pipe.
5
ABS 022/25
Capillary T piece for ABS 008/25 pipe
6
Reduces 25 mm pipe to 10mm pipe.
7
8
White
The below items are available on request only. Please check the last price list for lead time information.
ABS CAP-WHITE
10mm Nylon tube - opaque (per metre)
ABS 021/25-WH
Capillary end cap for ABS 008/25-WH pipe
ABS 022/25-WH
Capillary T piece for ABS 008/25-WH pipe
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
119
Special Equipment
Sampling pipes & fittings
Accessories
02-WT-01
The below items are available on request only. Please check the last price list for lead time information.
External water trap kit
Traps the water condensation.
PIP-025
25mm x 12” Condensation valve trap with ball valve
PIP-033
25mm Sight glass with condensation drain
F-PC
Pipe cutter, for pipes up to 27mm
Aspiration reducing films
F-BS
The Aspiration reducing films & banderole are packed per 10 units.
The below items are available on request only. Please check the last price list for lead time information.
Banderole, pack of 10
For securing the aspiration reducing film sheet on the PVC/ABS pipe(s).
F-AF-2.0
Aspiration reducing film sheet 2.0mm, pack of 10
F-AF-2.5
Aspiration reducing film sheet 2.5mm, pack of 10
F-AF-3.0
Aspiration reducing film sheet 3.0mm, pack of 10
F-AF-3.6
Aspiration reducing film sheet 3.6mm, pack of 10
F-AF-4.0
Aspiration reducing film sheet 4.0mm, pack of 10
F-AF-4.6
Aspiration reducing film sheet 4.6mm, pack of 10
F-AF-5.0
Aspiration reducing film sheet 5.0mm, pack of 10
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
120
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Smoke & Heat Evacuation Systems
F-AF-5.6
Aspiration reducing film sheet 5.6mm, pack of 10
F-AF-6.0
Aspiration reducing film sheet 6.0mm, pack of 10
Smoke & heat evacuation systems
1
SAHEP series
• 8A motor output, 24V
• EN12101-10 approval pending
• Two batteries of 2.1Ah included
• 6 led indications on front of panel
• Integrated priority control for fire brigade
• Possibility to connect MI-SAHEP-4-EFS slave panels
• Possibility to connect standard 470 ohms call points
• Easy installation: two wire polarity independant
The multilingual MI-SAHEP-4 panel is a smoke and heat evacuation panel built in a
compact and curved attractive housing.
The MI-SAHEP-4 is the smallest panel on the market delivering 8A and with full built
in control. Because of their size these panels are commonly installed directly in the
entrance halls of apartments without the need of installing extra priority controls, call
points, ventilation buttons.
The following functions are available on the control panel without the need of any
addition: call point function, ventilation opening and priority control for the fire
brigade.
The NBN S 21-208 demands a priority control for the fire brigade. The opening of
a smoke vent can be done automatically by a smoke detector but it is up to the fire
brigade to decide if the smoke vent must be closed when it brings to much oxygen
in the building. This open and close control must have a higher priority than fire
detectors or comfort controls. This priority control must be on a second access level
and it must be possible to put the smoke vent in the ‘close’ position even before a Fire
Switch is activated! The Sahep panels are a Belgian product and are manufactured
specially to fulfil this Belgian requirement. On the Sahep panels these buttons are
hidden behind a break out Plexiglas. There is also the possibility to add a second
external priority control on the Sahep panel: SAHEP-PRIOR.
The Sahep panels are specially designed for easy installation.
The standard conventional call points with 470 ohms resistor can be used as Fire
Switch on the Sahep panel.
2
3
4
5
6
7
8
Specifications
• Dimensions (W x H x D):
• Operation temperature:
• Colour: • Battery backup: • Autonomy:
• Max. total load, motor output:
• Fire brigade priority control:
• Fire brigade priority control input: • Fire group: • Comfort group: • Smoke-/heat detectors: • Wind-and rain sensor: • Master Slave connection: • Visual indicators:
• Designed to meet:
• Approval:
20 cm x 20 cm x 7 cm
-5°C to +60°C
White
Batteries included
72 h with 2.1 Ah batteries
24V, 8A
NBN S 21-208, Can be put in ‘close’ position before activation of a Fire Switch and is on a second access level behind a break out Plexiglas.
Two wire, polarity independent input, supervised by end of line open and close
Unlimited number of call points
Unlimited number of switches
1 line with line monitoring – max 30 detectors
Input for closing
Up to 20 slave control panels of each 8A can be connected to the master panel
LED
PR EN12101-9
EN12101-10 (pending)
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
121
Special Equipment
SAHEP-MI-SAHEP-4
Smoke & Heat Evacuation Systems
Smoke and heat evacuation panel for 4 motors, 8A
The functions Fire switch, Comfort switch and priority control for the fire brigade are
available on this panel.
Standard conventional call points with 470 ohms resistor are used as additional Fire
Switches.
If needed any type and an unlimited quantity of external comfort switches can be
added.
SAHEP-MI-SAHEP-4-EFS
2 X 2,1Ah-12V batteries included.
Smoke and heat evacuation panel 8A, slave version
This slave panel can be connected to the MI-SAHEP-4 and provides 8A with battery
backup. This slave panel can be installed close to the smoke vent which leads to
short high current wiring for the motors. On this slave panel a 70°C temperature
sensor can be added providing a failsafe opening system. Even when the connection
with the master panel fails, the slave panel will open the smoke vent at 70°C.
SAHEP-EFS-SENSOR
Temperature sensor 70°C for MI-SAHEP-4-EFS
This sensor can be connected to the MI-SAHEP-4-EFS to make a failsafe opening
system.
SAHEP-PRIOR
Additional external fire brigade priority control
Key switch as external priority control with open, close and neutral position. The
key switch contains electronics to connect this three position switch with only two,
polarity independent wires, to the Sahep panel. The connection is supervised with a
built in end of line resistor. Maximum one SAHEP-PRIOR can be added on a Sahep
panel.
Specifications
• Dimensions (W x H x D):
SAHEP-WRD1
87 mm x 87 mm x 52 mm
Wind & rain detector control unit
On this control unit a RD rain detector or WD wind detector can be added. The
control unit can be connected to the Sahep control panel to provide automated
closing of the vent in case of wind or rain. This automated closing will be overruled
by a fire detection or an activation of the fire brigade priority control. Includes surface
mounting box.
Specifications
•
•
•
•
•
Power supply: Load contact: Setting of the wind speed: Delay to avoid unwanted opening – closing: Dimensions (W x H x D):
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
122
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
230VAC
2.5A, 24V
5km/h to 35km/h
2 min
120 mm x 110 mm x 145 mm
Special Equipment
SAHEP-RD
Smoke & Heat Evacuation Systems
Rain detector
The SAHEP-RD rain detector functions with a capacitive sensor. So rain is detected
in a capacitive way. In a capacitive rain sensor no external PCB traces are visible.
These traces are sensitive for oxidation. This rain detector is compatible with the
WRD1. A mounting bracket in included.
Specifications
• Dimensions (W x H x D):
SAHEP-WD
120 mm x 110 mm x 145 mm
Wind detector
This wind detector is compatible with the WRD1.
A mounting bracket is included.
1
2
3
Spindle motors
4
Specifications
• Weight of smoke evacuation window that the motor can lift:
DS24VDC350/550/750: 65kg
DS24VDC950: 20kg
SAHEP-DS24VDC350
5
6
Motor 24VDC 650N 35 cm IP65
Item available on request only. Please check the last price list for lead time information.
7
8
SAHEP-DS24VDC550
Motor 24VDC 650N 55 cm IP65
SAHEP-DS24VDC750
Motor 24VDC 650N 75 cm IP65
SAHEP-DS24VDC950
Motor 24VDC 200N 95 cm IP65
Item available on request only. Please check the last price list for lead time information.
SAHEP-PROFIL U
‘U’ profile for DS24VDCxxx
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
123
Special Equipment
Smoke & Heat Evacuation Systems
Spindle motors for dual arms
The below items are available on request only. Please check the last price list for lead time information.
SAHEP-DUO24VDC550
Motor 24VDC 600N 55 cm IP65 for dual arms
SAHEP-DUO24VDC750
Motor 24VDC 600N 75 cm IP65 for dual arms
SAHEP-DUODR550
Slave arm for DUO 55cm
SAHEP-DUODR750
Requires assembling kit SAHEP-TT130
Slave arm for DUO 75cm
Requires assembling kit SAHEP-TT160
SAHEP-TT130
Assembling kit for DUO 55cm
SAHEP-TT160
Assembling kit for DUO 75cm
NEW
Apricolor chain motor
SAHEP-APRICOLOR
Chain motor, 24VDC, 300N, 150N
The Apricolor motor is a chain motor. The chain is rolled up in the motor inside a
nylon case. The chain is protected by a Dacromet coating.
Chain actuator for opening and closing gable windows and roof windows.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
124
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Smoke & Heat Evacuation Systems
Actulux series
SVM series control panels
SVM “Mini” control panels are constructed to provide and control the operation of
the opening systems for comfort and fire ventilation with 24VDC electrical opening
units.
The SVM control panel has a compact and elegant design and is equipped with
100% double supply as standard according to EN12101-10 (motor output from
internal supply or battery). 72 hours battery back-up is included.
The SVM control panel is equipped with connection terminals for external signals,
detectors and contacts. Possibility for built-in fire and comfort switches in the front.
The below items are available on request only. Please check the last price list for lead time information.
2
Specifications
• Compact and elegant design
• 24V - 5A or 8A
• LED indication in front panel for “OK”, “AC”, Fault”, “Cable error”, “Low battery”, “Comfort open”
• Meet the demands according to EU Standard EN12101-9 and EN12101-10 (double supply)
• Possibility for integrated fire switch, comfort switch and special “fire close” function
• Possibility for external connection of fire switch, smoke- and heat detectors, comfort switch and weather sensor
• Potential free relay output for “alarm”, “fault” and “comfort open”
• Possibility to connect more controls via bus communication
• Easy to install and set-up
• Service indication
• Power supply: • Operating temperature: • IP rating: • Dimensions (H x W x D): • Colour:
• Battery back-up: • Max. total load, motor output:
• Motor output: • Fire group: • Comfort group: • Smoke-/heat detectors: • Wind- and rain sensor: • Serial connection of controls:
• Visual indication (LED) in front panel: 1
230VAC - max. 250VA
-5°C - +60°C
IP50
286 mm x 238 mm x 113 mm
White RAL 9003
Incl. (72h)
24V - 5A / 8A
1 pc. (terminals 6mm²) - 1, 2, 3 or 4
lines with line monitoring
1 pc. with line monitoring - max. 20 pcs. external fire switches
1 pc. - unlimited no. of switches
1 line with line monitoring - max. 20
pcs. detectors
Input for close all
Bus connection integrates most functions - from 2-10 controls in same
bus connection
OK, AC fault, DC fault, Line fault, Alarm
ACT-SVM24V-5A-BASIC
Control panel SVM 24V-5A Basic
ACT-SVM24V-5A-CS
Control panel SVM 24V-5A incl. Comfort switch
ACT-SVM24V-5A-FS
Control panel SVM 24V-5A incl. Fire switch
ACT-SVM24V-5A-F-CS
Control panel SVM 24V-5A incl. Fire and comfort switch
ACT-SVM24V-8A-BASIC
Control panel SVM 24V-8A Basic
ACT-SVM24V-8A-CS
Control panel SVM 24V-8A incl. Comfort switch
ACT-SVM24V-8A-FS
Control panel SVM 24V-8A incl. Fire switch
ACT-SVM24V-8A-F-CS
Control panel SVM 24V-8A incl. Fire and comfort switch
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
125
Special Equipment
Smoke & Heat Evacuation Systems
Accessories for SVM Series control panels
ACT-VR-1
The below items are available on request only. Please check the last price list for lead time information.
Wind and rain detector for SVM panel
The wind/rain sensor consists of a wind wheel and a rain sensor surface. It is
developed for an automatic control of the smoke and comfort ventilation system.
The wind/rain sensor is protected with a potential free SPDT switch with a contact
rating of max. 60V/2A.
In case of wind and/or rain the SPDT switch is activated. The settings for the wind
trigger threshold (the wind force makes the sensor report a too high wind force), the
actuation delay, the drop out delay and the release in case of main power failure are
made by a 6 pole DIP switch in the sensor.
Specifications
• Power supply:
• Output contact:
• Load contact:
• Dimensions (WxHxD):
• Weight:
• IP rating:
• Setting of the wind mode:
• Setting of the wind-/rain drop out delay:
• Setting of the wind actuation delay:
• Setting of the monitoring:
• CE-marking:
ACT-WSK
18 to 26VAC or 20 to 32VDC
1 x potential free SPDT switch
60V / 2A
80 mm x 160 mm x 55 mm (without wind wheel)
Approx. 0,7 kgs
IP65
Approx. 3 to 14 m/s (+ / -20%)
10 min. / 20 min.
2 sec. / 5 sec.
Off / On
in accordance with the EMC-directive and low voltage directive.
Fire switch for SVM panel
Specifications
• Function: • LED indication: • Dimensions (W x H x D): • Colour: • IP rating: ACT-OPUS
Alarm (open), reset and off sound indicator
’’ok”; “fault’”(yellow); ’’alarm activated” (red)
125 mm x 125 mm x 36 mm
Grey
IP40
Comfort switch for SVM Panel
Up/down switch for manual control of comfort ventilation, e.g. in connection with 24V
fire and smoke ventilation systems.
The up/down switch is delivered with housing for wall mounting.
Specifications
• Dimensions (W x H x D): For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
126
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
65 mm x 65 mm x 45 mm
Special Equipment
Wireless Systems
Sagittarius Series
SAGITTARIUS is a highly advanced wire to wireless system providing a solution
for fire detection applications where traditional installations may be unacceptable
or uneconomic.
The system is based on a proven protocol and wireless technology derived from the
European security industry.
The translator provides for full sensor intelligent values on the European Frequency
of 868 Mhz, fire and fault information and type ID's to be transmitted to the fire
control panel.
All devices are delivered with batteries.
LPCB approved to EN54-25.
SG-PU
Display module with keypad
1
2
Wireless communication with receiver.
Only for conventional application.
3
4
5
6
SGCWE100
Sagittarius conventional system - expander module
The Sagittarius conventional system expander is a module device permitting to add
a wireless sub-system to a conventional fire security installation.
This device is connected directly to the conventional control panel’s zone line and is
actually part of it. This device allows wireless sounders silencing by being controlled
by the control panel’s sounder output line.
7
8
Item available on request only. Please check the last price list for lead time information.
Specifications
• Bi-directional communication.
• 868.15 MHz—869.85MHz.
• Multi-channel (up to 7 channels).
• Automatic management of power transmission.
• Double orthogonal antenna provides reliable and secure communication.
• Immediate transmission of alarm, fault and tamper signals from field devices.
• Flexible on site device adjustment.
• Communication range between expander and wireless devices: 200m (in open space)
• Operating frequency channels: 7
• Radiated power: 5 dBm (3 mW)
• Power supply voltage range: - 9-27VDC
- 12VDC typical
• Power supply lower fault threshold: 9VDC
• Conventional zone line applied voltage: Same as device’s power supply
applied voltage
• Sounder’s line maximum voltage: 27VDC
• Expander maximum current consumption: 60mA at 12VDC (alarm)
• Operating temperature range: -30 °C to +50 °C
• Dimensions (without antennas): 120 mm x 160 mm x 51 mm
• Weight: 330 g
• IP rating:
IP 51C
CPD number: 0832-CPD-1689
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
127
Special Equipment
SGWE
Wireless Systems
Wireless expander
Provides an extended signal coverage area up to 6 boosters per interface locally
powered (12-24 Vdc) up to 32 wireless devices.
Bi-directional dialogue protocol.
Specifications
•
•
•
•
•
Voltage range:
Expander current consumption:
Operating temperature range:
Dimensions (with antennas):
IP rating:
9-27VDC
15mA @ 24VDC
-30°C to +50°C
190 mm x 230 mm x 50 mm
IP51C
CPD number: 0832-CPD-1690
SG100
Wireless optical smoke detector
Includes 360° bicolor LED & base.
Specifications
•
•
•
•
•
•
•
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 200m (in open space)
Main battery:
CR-123 A (approx. life time 5 years)
Secondary battery:
CR-2032 A (approx. life time 2 months)
Weight: 150g
Dimensions:
110 mm x 54 mm
Approved to:
EN54-7 & EN54-25
CPD number: 0832-CPD-1069
SG200
Wireless multi-tech optic / heat detector
Includes 360° bicolor LED & base.
Specifications
•
•
•
•
•
•
•
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 200m (in open space)
Main battery:
CR-123 A (approx. life time 5 years)
Secondary battery:
CR-2032 A (approx. life time 2 months)
Weight: 150g
Dimensions:
110 mm x 54 mm
Approved to:
EN54-5 & EN54-7 & EN54-25
CPD number: 0832-CPD-1070
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
128
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
SG350
Wireless Systems
Wireless heat detector
Includes 360° bicolor LED & base.
Specifications
• Operating frequency chanels:
7
• Radiated power:
5dBm (3mW)
• Communication range with the receiver module:max. 200m (in open space)
• Main battery:
CR-123 A (approx. life time 5 years)
• Secondary battery:
CR-2032 A (approx. life time 2 months)
• Alarm treshold:
Programmable from 58°C to 78°C with translator
• Approved to:
EN54-5 & EN54-25
CPD number: 0832-CPD-1068
SG/SC
Decorline supplement for special coated detector
1
2
Available colors on request.
Minimum order quantity of 50 pcs.
Item available on request only. Please check the last price list for lead time information.
3
4
5
SGCP100
Wireless manual call point
6
Complies EN54-11.
Includes surface mounting box & break glass.
7
Specifications
•
•
•
•
•
Dimensions (H x W x D):
86 mm x 86 mm x 59 mm
Weight:186g
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 200m (in open space)
Approved to:
EN54-11 & EN54-25
8
CPD number: 0832-CPD-1683
SGWCP100
Wireless manual call point, weatherproof
Specifications
•
•
•
•
•
Dimensions (H x W x D):
120 mm x 130 mm x 55 mm
Operating temperature:
-30°C to +55°C
IP rating:
IP67
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 200m (in open space)
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
129
Special Equipment
SGMI200
Wireless Systems
Wireless monitored input module
The wireless monitored input module allows the switched on/off status of an external
device to be transmitted to the control panel through translator / expander devices.
Specifications
•
•
•
•
•
•
Main battery type:
CR123 A
Backup battery type:
CR2032 A
IP rating:
IP65
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 200m (in open space)
Approved to:
EN54-18 & EN54-25
CPD number: 0832-CPR-F0691
SGMC200
Wireless control module
With relay (requires external power supply).
Specifications
• Operating Voltage:
12-27VDC
• Current consumption:
50mA
• Dimensions:
109 mm x 37 mm
• Weight:52g
• IP rating:
IP65
• Relay:
Max. switched voltage: 30VDC
Max. switched current: 2A
• Radiated power:
5dBm (3mW)
• Communication range with the receiver module:max. 200m (in open space)
• Approved to:
EN54-18 & EN54-25
CPD number: 0832-CPR-F0691
SGMCB200
Wireless control module
With relay output (works on batteries).
Specifications
• Dimensions:
87 mm x 87 mm x 40 mm
• Weight:150g
• Main battery type:
CR123 A
• Backup battery type:
CR123 A
• IP rating:
IP65
• Relay:
Max. switched voltage: 30VDC
Max. switched current: 2A
• Radiated power:
5dBm (3mW)
• Communication range with the receiver module:max. 200m (in open space)
• Approved to:
EN54-18 & EN54-25
CPD number: 0832-CPR-F0691
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
130
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
SG-CWS100-KIT
Wireless Systems
Wireless wall mounted sounder, red
Replacement for SGRS100-H.
The CWS100 conventional red wall sounder with 32 tones (incl.Slow whoop tone)
and volume settings is weatherproof at standard.
When the SGWS-MOD is fitted into the CWS100 it becomes fully compatible with
the wireless translator and expander modules.
+
When ordering the SG-CWS100-KIT, you’ll receive:
1 x CWS100 conventional red sounder
1 x SGWS-MOD wireless module for CWS100(-AV)
1
Specifications
•
•
•
•
•
•
•
SGRBS100
Max. acoustic output:
100dB(A) @ 1m
IP rating:
IP65
Operating temperature:
-25°C to +70°C
Max. relative humidity:
95% (non-condensing)
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 150m (in open space)
Approved to:
EN54-3 (CWS100)
EN54-18 & EN54-25 (SGWS-MOD)
2
3
CPD number: pending
4
Wireless sounder base
5
The SGRBS100 wireless sounder base is an acoustic output device that is activated
in case of fire or emergency situations. Meets EN54 part 3.
6
Item available on request only. Please check the last price list for lead time information.
7
Specifications
•
•
•
•
•
•
Usable operating frequency channels:
Main battery type:
Operating temperature range:
IP rating:
Maximum volume range @ 1m :
Tones:
7
CR123A (3 V & 1.2 Ah)
From –10 °C to +55 °C
IP 21C
From 89 dBa to 91 dBa
32, incl. Slow Whoop tone (NL)
8
CPD number: 0832-CPD-1684
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
131
Special Equipment
SG-CWS100-AV-KIT
Wireless Systems
Wireless wall mounted sounder/beacon, red
The CWS100-AV conventional red wall sounder beacon with 32 tones (incl.Slow
Whoop tone) and volume settings is weatherproof as standard.
When the SGWS-MOD is fitted into the CWS100-AV it becomes fully compatible
with the wireless translator and expander modules.
+
When ordering the SG-CWS100-AV-KIT, you’ll receive:
1 x CWS100-AV conventional red sounder/beacon
1 x SGWS-MOD wireless module for CWS100(-AV)
Specifications
•
•
•
•
•
•
•
•
•
Max. acoustic output:
100dB(A) @ 1m
Visual alarm device frequency: 0.5Hz or 1Hz
EN54-23 Classification: W-2.4-9.5
IP rating:
IP65
Operating temperature:
-25°C to +70°C
Max. relative humidity:
95% (non-condensing)
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 150m (in open space)
Approved to:
EN54-3 & EN54-23 (CWS100-AV)
EN54-18 & EN54-25 (SGWS-MOD)
CPD number: pending
SGRBS100-AV
Wireless audiovisual sounder base
The SGRBS100-AV wireless audiovisual sounder base is an output device that
combines together acoustic and visual signaling features performed in case of fire
or emergency situations. SGRBS100-AV’s incorporated beacon’s flash rate and
light intensity are fixed. Meet EN 54 part 25.
Item available on request only. Please check the last price list for lead time information.
Specifications
•
•
•
•
•
•
•
•
•
Operating temperature range:
From –10 °C to +55 °C
Maximum volume range @ 1m :
From 70 dBa to 95 dBa (selectable)
Tones:32
Radiated power:
5dBm (3mW)
Communication range with the receiver module:max. 200m (in open space)
Max. relative humidity:
95% (non-condensing)
IP rating:
IP21C (type A for indoor using only)
Dimensions:
145 mm x 66 mm
Approved to:
EN54-3 & EN54-25
CPD number: 0832-CPD-1685
SGFI200-S
Remote led indicator
The SGFI200-S wireless remote indicator lamp is an output device which, activated
by the control panel, switches on in the event of alarms, faults or emergency
conditions.
Specifications
•
•
•
•
Operating temperature range:
From –10 °C to +55 °C
Dimensions:
87 mm x 87 mm x 68 mm
Weight:180g
Communication range with the receiver module:max. 200m (in open space)
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
132
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Linear Heat Detection
Accessories for Sagittarius series
The below items are available on request only. Please check the last price list for lead time information.
SG/CI
Plexi protection cap for SGCP100
SG-LBS100
Lid for SGRBS100
Linear Heat Detection
Linear Heat Detection (LHD) cable-based systems provide economical temperature
monitoring at the precise point of risk. The system is reliable, flexible and has the
ability to detect abnormal temperature variance before fire breaks out. The LHD
product allows a vast range of commercial and industrial fire and overheat risks to
be protected, in ambient temperature of -65 to +238°C.
Classic applications: cable tunnels, floating roof tanks, conveyors bulk storage, rail
locomatives, rolling stock, vehicle engine bays, etc..
LHD-LWM1
The below items are available on request only. Please check the last price list for lead time information.
1
2
3
4
Electronic interface module
The LWM-1 linear heat detection system allows early detection of fire or overheating.
It is especially suited for confined areas or harsh environments where adverse
ambient conditions cause other detection devices to be unreliable or difficult to use.
The system consists of two components: the sensor cable and the Alarmline control
unit LWM-1.
5
6
7
Specifications
•
•
•
•
Sensor length up to 300m
Resistant to mechanical and chemical influences, corrosion, humidity and dust
Easy to install, economic, low maintenance, simple commissioning
Suitable for use in EX classified areas
•
•
•
•
•
•
•
•
•
•
•
•
Housing material Dimensions (WxHxD): Weight approx.: IP rating: Color: Temperature range: Length of sensor per control unit: Voltage: Quiescent current consumption: Current consumption on: Current consumption on fault max.: In-rush current (on power up): ABS
200 mm x 120 mm x 80 mm
550 g
IP65
Grey similar to RAL 7035
-20 °C to 50 °C
Max. 300 m, min. 10 m
10-30VDC
Max. 25 mA / 24VDC
Max. 25 mA / 24VDC
15 mA / 24VDC
< 100 mA / 24VDC
8
Approved to EN54 Part 5; VdS number: G205066
LHD-BLUE
Standard high resistance intelligent cable
For environments ranging from clean and dry to moderate dust and moisture.
Available reel lengths are: 100m; 200m; 500m; 1000m.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
133
Special Equipment
LHD-BLACK
Linear Heat Detection
Nylon coated high resistance int. cable
For use in wet, oily or corrosive environments or outdoors. Use in freezer warehouse.
LHD-BRONZE
Available reel lengths are: 100m; 200m; 500m; 1000m.
Bronze braided high resistance int. cable
For applications requiring superior abrasion protection or increased tensile strength.
LHD-STAINLESS
Available reel lengths are: 100m; 200m; 500m; 1000m.
Nylon stainless steel braided high resistance intelligent cable
Recommended for extreme environments.
LHD-EC2.3
Available reel lengths are: 100m; 200m; 500m; 1000m.
Edge clip, 2-3mm WEB
LHD-EC3.8
Requires neoprene sleeves & ties.
Edge clip, 3-8mm WEB
LHD-EC8.18
Requires neoprene sleeves & ties.
Edge clip, 8-14mm WEB
LHD-EC14.2
Requires neoprene sleeves & ties.
Edge clip, 14-20mm WEB
Requires neoprene sleeves & ties.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
134
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
LHD-DP
Linear Heat Detection
200mm distance piece for edge clip
LHD-TC
Requires neoprene sleeves & ties.
Order edge clips & neoprobene sleeving separately.
T clip
Requires neoprene sleeves & ties.
Order edge clips & neoprobene sleeving separately.
1
LHD-PC
Pipe clip
Requires neoprene sleeves & ties.
Order edge clips & neoprobene sleeving separately.
2
3
4
LHD-VC
V clip (incl. rubber)
Requires neoprene sleeves & ties.
Order edge clips & neoprobene sleeving separately.
5
6
7
LHD-CT
Cable ties (100/set)
LHD-NS
Neoprene sleeving
LHD-ELTK
End line termination kit
8
Pack of 10.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
135
Special Equipment
LHD-ILJK
Industrial Heat Detectors
In line jointing kit
MTL7761AC
Pack of 10.
Intrinsically safe zener barrière
Industrial Heat Detectors
Thermal rate of rise detectors of the TMP2 series detectors guarantee high measure
precision for long periods and high immunity from EMI interference. TMP2 detectors
have an integrated alarm LED for alarm indication. Both peculiarities confer to TMP2
high performance, reducing probability of false alarms.
Sensors are compatible with all Morley-IAS control panels using them like normal
smoke detectors. Direct wiring for conventional panels and connection through MIDCZRM module, for intelligent panels.
The TMP2 series includes an electronic circuit for signal conditioning generated
by the transducer. The electronic card is reduced to the minimum size using SMC
technology and placed directly into the unit probe.
The industrial heat detectors & accessories are available on request only. Please check the last price list for lead time information.
Specifications
• Supply voltage:
• Supply current:
• Temperature range:
• Code of Protection:
• IP rating:
• Approved to: CPR number: 0068-CPR-009/2014
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
136
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
10-30VDC
approx. 20/30uA in normal conditions
>20mA in alarm condition
-20°C to +110°C
ATEX II 2G Ex d IIC T6
IP66 (Probe IP67)
EN54 Part 5
Special Equipment
Industrial Heat Detectors
Dust type
Specifications
•
•
•
•
•
•
•
Overal dimensions (h x l x d):
Weight:
IP rating:
Cable holder:
203 mm x 95 mm x 60 mm
400 g
IP66
M20
Introduced double cable holder
New auto-locking terminal block for quicker and easier installation
Diagnostic LED showing connections errors as loop inversions
TMP2-D-A257R1A
Rate of Rise dust thermal detector - 57°C
TMP2-D-C90R1A
Rate of Rise dust thermal detector - 90°C
TMP2-D-D110R1A
Rate of Rise dust thermal detector - 110°C
TMP2-D-A257S1A
Fixed temp. dust thermal detector - 57°C
TMP2-D-C90S1A
Fixed temp. dust thermal detector - 90°C
TMP2-D-D110S1A
Fixed temp. dust thermal detector - 110°C
1
2
3
4
5
Dust type Probes only
Housing not included.
6
TMP2-P-A257R1A
Rate of Rise dust thermal detector probe - 57°C
TMP2-P-C90R1A
Rate of Rise dust thermal detector probe - 90°C
TMP2-P-D110R1A
Rate of Rise dust thermal detector probe - 110°C
TMP2-P-A257S1A
Fixed temp. dust thermal detector probe - 57°C
TMP2-P-C90S1A
Fixed temp. dust thermal detector probe - 90°C
TMP2-P-D110S1A
Fixed temp. dust thermal detector probe - 110°C
7
8
ATEX Type
Specifications
• Overal dimensions (h x l x d):
• Weight:
160 mm x 85 mm x 75 mm
410 g
TMP2-TO-A257R1A
Rate of Rise Eexd thermal detector - 57°C
TMP2-TO-C90R1A
Rate of Rise Eexd thermal detector - 90°C
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
137
Special Equipment
Industrial Heat Detectors
TMP2-TO-D110R1A
Rate of Rise Eexd thermal detector - 110°C
TMP2-TO-A257S1A
Fixed temp. Eexd thermal detector - 57°C
TMP2-TO-C90S1A
Fixed temp. Eexd thermal detector - 90°C
TMP2-TO-D110S1A
Fixed temp.Eexd thermal detector - 110°C
Accessories
TMP2-ST14
EEx-d junction box for end-of-line resistor
GDA-M/B-KF4A
Mounting brackets
Mounting Brackets for heat detectors ATEX type TMP2.
GDA-CH12-NA
ATEX cable gland
Size 1/2" for ATEX type TMP2, for non armoured cables.
GDA-CH12
ATEX cable gland
Size 1/2" for ATEX type TMP2, complete of rubber parts, for armoured cables.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
138
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
TMP_Configurator
Industrial Heat Detectors
Software for TMP2 maintenance & configuration
Special software for TMP2 heat detectors maintenance and configuration. Data Log
capability, Trends, Calibration report, Stand-Alone calibration station. Complete of
USB/RS485 connection cable.
1
HD Series
Thermal detectors of HD series guarantee high measure precision for long period
and high immunity from EMI interference. Both peculiarities confer to HD high
performance, reducing the probability of false alarms.
HD Sensors are compatible with all Morley-IAS control panels using them like normal
smoke detectors. Direct wiring for conventional panels and connection through MIDCZRM module, for intelligent panels.
The sensing element is a heat pick-up shield and a bi-metal switch.
2
3
4
Mounting box & cable gland included.
5
Specifications
• Dimensions (Ø x h) :
• Weight: • IP rating:
95 mm x 42 mm
82g
IP67
6
7
HD6295
IP67 sensor. T°: 60°C
CPD number: 0845-CPD-232.1192; ATEX compliance: II 3 G Ex ic IIC T5 Gc
X & II 3 D Ex ic IIIC T100˚C Dc X
HD6296
8
IP67 sensor. T°: 80°C
CPD number: 0845-CPD-232.1193; ATEX compliance: II 3 G Ex ic IIC T5 Gc
X & II 3 D Ex ic IIIC T100˚C Dc X
HD6297
IP67 sensor. T°: 100°C
CPD number: 0845-CPD-232.1194
HD6298
IP67 sensor. T°: 120°C
CPD number: 0845-CPD-232.1195
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
139
Special Equipment
Industrial Audio&Visual Devices
Industrial sounders
MS1/R
Industrial sounder max. 106dB
Specifications
•
•
•
•
•
Dimensions (W x H x D): Voltage:
Current consumption:
IP rating:
Approved to:
90 mm x 90 mm x 81 mm
24 VDC
20 - 110mA
IP54
EN54-3
VdS number: G28702
Y05D
Industrial sounder 24V 110dB
Specifications
•
•
•
•
•
•
•
•
Dimensions (W x H x D):
Operation temperature:
Storage temperature:
Current consumption:
Voltage:
Weight:
IP rating:
Approved to:
169 mm x 134 mm x 128 mm
-25°C to 55°C
-40°C to 70°C
min. 20mA
24 VDC
0.55kg (DC)
IP54
EN54-3
VdS number: G28702
Y08D
Industrial sounder 24V 116dB
Specifications
•
•
•
•
•
•
•
Dimensions (W x H x D): 269 mm x 216 mm x 153 mm
Operation temperature:
-25°C to 55°C
Storage temperature:
-40°C to 70°C
Weight:2.5kg
Current consumption:
min. 300mA
Voltage:
24 VDC
Approved to:
EN54-3
CPD number: 0086-CPD-96705
Y08/SD_YA80/D/RF/SU
Industrial super sounder 24V 120dB
Item available on request only. Please check the last price list for lead time information.
Specifications
•
•
•
•
•
•
•
Dimensions (W x H x D): 269 mm x 216 mm x 153 mm
Operation temperature:
-25°C to 55°C
Storage temperature:
-40°C to 70°C
Weight:3kg
Current consumption:
Min. 300mA
Voltage:
24 VDC
Approved to:
EN54-3
CPD number: 0086-CPD-96705
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
140
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Industrial Audio&Visual Devices
Industrial strobes & Combined sounders
MS2/R/R
Xenon strobe - 24VDC - 5W - red
Specifications
•
•
•
•
•
•
•
Dimensions (W x H x D): Weight: Voltage:
Current consumption:
Operating temperature: IP rating:
Approved to:
90 mm x 90 mm x 81 mm
240g
24 VDC
3-65mA
-40°C to +70°C
IP54
EN54-23
Vds number: G28714
MS5/R/R
1
Industrial strobe and sounder 5 W - 106dB - 32 tones
3
Specifications
•
•
•
•
•
•
•
Dimensions (W x H x D):
Weight: Voltage:
Current consumption:
Operating temperature: IP rating:
Approved to:
2
90 mm x 179 mm x 81 mm
450g
24 VDC
Flash: 300mA; Sounder: 35mA
-40°C to +70°C
IP54
EN54-3
4
5
CPD number: 0086-CPD-96705
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
141
Special Equipment
Intrinsically Safe Devices
Intrinsically safe devices
Conventional manual call points
Manual break glass fire alarm call points for use with galvanic isolator in hazardous areas.
MTL5561
CONVENTIONAL
ZONE
MCP IS +
SERIAL R470
MCP IS +
SERIAL R470
MCP IS +
SERIAL R470
EOL
Maximum 10 MCP per zone
The below items are available on request only. Please check the last price list for lead time information.
The red conventional call points contain:
- Operating element label: EN54-11 “Dot & Arrows”
- Function label: Burning House
For other labels, please order the specific foil separately (See §. Foil with labels for Call Points & Switches)
Red
MCP1A-R470FG-01IS
IS MCP with break glass element 470R
Includes break glass element & monitoring resistor R470.
Specifications
•
•
•
•
•
•
•
•
•
•
Dimensions (W x H x D): Weight: Ambient temperature range: Operating voltage range: Storage temperature range: Relative humidity: Material: IP rating:
Color:
ATEX compliance:
89 mm x 93 mm x 59,5 mm
130g (flush); 180g (surface)
-10°C to +55°C
14-28VDC (nominal 24VDC)
-40°C to +85°C
93 +/-3% (non-condensing)
PC/ABS
IP24D
Red, RAL3001
II 1G EX ia IIC T4 Ga
ATEX number: SIRA-04ATEX2350X_ISS4
MCP1A-R470FF-01IS
Please order surface mounting box separately.
Cable glands are not included.
IS MCP with flexible element 470R
As MCP1A-R470FG-01IS but with flexible element.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
142
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
MCP3A-R000FG-01IS
Intrinsically Safe Devices
IS MCP with break glass element
Includes break glass element & a changeover contact (max. 30VDC).
Specifications
•
•
•
•
•
•
•
•
•
Dimensions (W x H x D): Weight: Ambient temperature range: Relative humidity: Maximum voltage:
IP rating:
Material: Color:
ATEX compliance:
89 mm x 93 mm x 59,5 mm
130g (flush); 180g (surface)
-10°C to +55°C
93 +/-3% (non-condensing)
30VDC
IP24D
PC/ABS
Red, RAL3001
II 1G EX ia IIC T4 Ga
1
ATEX number: SIRA-04ATEX2350X_ISS4
MCP3A-R000FF-01IS
Please order surface mounting box separately.
Cable glands are not included.
3
4
IS MCP with flexible element
As MCP3A-R000FG-01IS but with flexible element.
WCP1A-R470SG-01IS
2
Waterproof IS MCP with break glass element
Includes break glass element, surface mounting box, a normally open contact (max.
30VDC) and 470R monitoring resistor.
5
6
7
Specifications
• Dimensions (W x H x D): • Weight: • Operating temperature range: • Relative humidity: • IP rating:
• Material: • Color:
• ATEX compliance:
97.5 mm x 93 mm x 71 mm
350g
-25°C to +70°C
0-93 +/-3% (non-condensing)
IP67
PC/ABS
Red, RAL3001
II 1GD Ex ia IIC T4 Ga; Ex ia IIIC T135°C Da
8
ATEX number: SIRA06ATEX2131X ISSUE 5
WCP1A-R470SF-01IS
Cable glands are included.
Waterproof IS MCP with flexible element
As WCP1A-R470SG-01IS but with flexible element.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
143
Special Equipment
WCP3A-R000SG-01IS
Intrinsically Safe Devices
Waterproof IS MCP with break glass element
Includes break glass element, surface mounting box & a changeover contact (max.
30VDC).
Specifications
• Dimensions (W x H x D): • Weight: • Operating temperature range: • Relative humidity: • IP rating:
• Material: • Color:
• ATEX compliance:
97.5 mm x 93 mm x 71 mm
240g
-30°C to +70°C
0% to 95% (non-condensing)
IP67
PC/ABS
Red, RAL3001
II 1GD Ex ia IIC T4 Ga; Ex ia IIIC T135°C Da
ATEX number: SIRA06ATEX2131X ISSUE 5
WCP3A-R000SF-01IS
Cable glands are included.
Waterproof IS MCP with flexible element
As WCP3A-R000SG-01IS but with flexible element.
Other colours
The conventional call points in other colors contain:
- Operating element label: EN54-11 'dot & arrows'
- Function label: plain color
For other labels, please order the specific foil separately
(See §. Foil with labels for Call Points & Switches)
- Surface mounting box.
Please replace “x” in the part n° by the code for
the needed color: Y = yellow; G = green; B = blue; W = white
Items available on request only. Please check the last price
list for lead time information.
WCP1A-x470SG-01IS
Waterproof IS MCP with break glass element
WCP3A-x000SG-01IS
Waterproof IS MCP with break glass element
WCP1A-x470SF-01IS
Waterproof IS MCP with flexible element
WCP3A-x000SF-01IS
Waterproof IS MCP with flexible element
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
144
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Intrinsically Safe Devices
Accessories
MTL5561
2 channel galvanic isolator for IS conv. det
Specifications
• Weight: • Number of channels:
• Current range:
• Integral input polarity protection:
• Hazardous-area output:
• Loop supply voltage:
130g
2
1 to 40mA, nominal
Input circuit protected against reverse polarity
M ax. output voltage 28VDC from 300Ω
6 to 35VDC
For connection from conventional zone to intelligent panel
1
2
MI-DCZRM
Conventional zone input module
Complete with end of line resistors, plug in screw connections, direct decade
address entry and tri-colour LED's complete with built-in isolator.
4
Specifications
•
•
•
•
•
•
•
3
External supply voltage conv. zone:
12 to 28.5 VDC
Max. conventional zone current limit:
60mA
Operating Temperature:
-20°C to 60°C
Relative humidity :
5% to 95% (non-condensing)
Dimensions (W x H x D): 93 mm x 83 mm x 23 mm
Weight:110g
Approved to:
EN54-17 & EN54-18
5
6
CPD number: 0832-CPD-1392; VDS number: G213074
7
M200-SMB
Surface mount box
8
To be used with MI series modules.
Specifications
• Dimensions (W x H x D):
• IP rating:
139 mm x 134 mm x 40 mm
IP50
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
145
Special Equipment
Intrinsically Safe Devices
Audio & Visual devices
For use with galvanic isolator in hazardous areas.
I.S. SOUNDER
MTL5525
PANEL
SOUNDER
OUTPUT
EOL
Max. 1 sounder per isolator.
MS1/R/IS
The below items are available on request only. Please check the last price list for lead time information.
Cable glands are not included.
IS sounder 100dB, IP55, 32 selectable tones, incl. Slow whoop tone
Specifications
• Dimensions (W x H x D):
• Current: • Operating temperature: • Relative humidity: • Weight: • IP rating: • Intrinsic safety Rating: • Supply voltage:
90 mm x 180 mm x 81 mm
25 mA
-25°C to +40°C
95% at 40°C
0,490Kg
IP55
II 1 G Ex ia IIC T4 Ga & II 1 D Ex ia IIIC T190°C Da
24VDC
ATEX number: EECS-BAS02ATEX1190X; Baseefa 08 Atex 0194x
DA5-24VDC
IS sounder 100dB, IP65, 26 selectable tones incl. Slow whoop tone
Specifications
•
•
•
•
•
•
Dimensions (Ø x h): Supply voltage: Current:
IP rating: Intrinsic safety Rating: Supply voltage:
ATEX number: BAS00ATEX1259
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
146
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
93 mm x 103 mm
24VDC
14 mA
IP65
Group II, Category 1G, EEX ia T4
24VDC
Special Equipment
Y05/R/IS
Explosion Proof Devices
IS sounder 105dB, IP65, 32 selectable tones incl. Slow whoop tone
Specifications
• Dimensions (W x H x D) : • Intrinsic safety Rating : • Current: • Operating temperature: • Relative humidity: • Weight: • IP rating: • Operating voltage:
169 mm x 134 mm x 128 mm
II 1 G Ex ia IIC T4 Ga; II 1 D Ex ia IIIC
T190°C Da
28 mA
-25°C to +40°C
95% at 40°C
0,810Kg
IP56
24VDC, 48VDC (BT)
ATEX number: EECS-BAS02ATEX1190X; Baseefa 08 Atex 0194x
1
MTL5525
Galvanic isolator for IS sounders
2
Specifications
• Minimum output voltage:
• Maximum output voltage:
• Current limit:
• Maximum current consumption:
• Safety description:
7V at 48mA
24V from 300Ω
48mA
100mA at 24VDC
V0=25VDC, I0=83.3mA, P0=0.52W, Um=253V RMS or DC
3
4
5
Explosion Proof Devices
6
Audible and visual alarm devices
7
8
PANEL
SOUNDER
OUTPUT
• Omni directional sounder output
• 2 stage alarm
• Independently selectable 2nd stage
• All units share a common explosion proof housing
• Reduced installation costs
• Meets UL, ATEX and IECEx Approvals
• ATEX approved for Gas & Dust
• Low current consumption
• Dual cable entry, cable in – cable out
• Aluminium enclosure
• Stainless steel fasteners
• Polycarbonate dome
• Lens guard provided as standard
• Weather proof flame retardant ABS horn
• Red Lens in flame retardant polycarbonate
• 32 selectable tones meeting international regulations
EOL
The below items are available on request only. Please check the last price list for lead time information.
Cable glands are not included.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
147
Special Equipment
Y06/R/24V
Explosion Proof Devices
EEX sounder 110dB 32 tones - IP66 - red
Specifications
•
•
•
•
•
Dimensions (Ø x h): 145 mm x 288 mm
Voltage:24VDC
Current consumption:
350mA
Weight:5.4kg
Intrinsic safety Rating : II 2G D EEx dIIB+H2 T135°C
ATEX number: Baseefa 02ATEX0222X
YL6/R/24V
EEX Sounder-strobe 110dB 32 tones - IP66
Specifications
•
•
•
•
•
Dimensions (Ø x h): 145 mm x 420 mm
Current consumption:
570mA
Voltage:24VDC
Weight:6kg
Intrinsic safety Rating: II 2G D EEx dIIB+H2 T135°C
ATEX number: Baseefa 02ATEX0222X
V6/R/24V
EEX Proof strobe - IP66 - Red
Specifications
•
•
•
•
•
Dimensions (Ø x h): 145 mm x 276 mm
Voltage:24VDC
Current consumption:
220mA (5J)
Weight:5.08kg
Intrinsic safety Rating: II 2G D EEx dIIB+H2 T135°C
ATEX number: Baseefa 02ATEX0222X
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
148
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Explosion Proof Devices
V6/B/24V
EEX Proof strobe - IP66 - Blue lens
V6/G/24V
EEX Proof strobe - IP66 - Green lens
V6/Y/24V
EEX Proof strobe - IP66 - Yellow lens
V6/C/24V
EEX Proof strobe - IP66 - Clear lens
Flame Detector
FR-24006-01
The below items are available on request only. Please check the last price list for lead time information.
1
FIRERAY 2000 EExd
Explosion proof infrared beam smoke detector. End to end type, comprising control
unit, explosion proof transmitter and receiver. Including test filter and 1x surface
mount wall bracket (23835.00). ATEX approved.
2
3
Specifications
•
•
•
•
•
Separate transmitter and receiver units
Range 10 to 100 metres
Automatic drift compensation
3 selectable sensivity threshold levels
Approved to EN54:12
FR-23835.00
• Operating voltage range:
• Transmitter current:
• Fire relay contacts:
• Fault relay contacts:
• Intrinsic safety Rating: 11.5 to 28VDC
1.6 to 5.6mA
Normally open, VFCO [email protected] 30VDC, resistive
Normally closed [email protected], resistive
II 2 G D IP 6x; EEx d IIB T6
CPD number: 0786-CPD-20196; ATEX number: Sira 03ATEX1504 issue3
EExd wall bracket
4
5
6
7
Surface mount wall bracket for use with FIRERAY 2000 EExd. Detector not included.
8
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
149
Special Equipment
Flame Detectors
Flame detectors
40/40 series
• Protection against hydrocarbon based fuel and gas fires, hydroxyl and hydrogen fires, as well as metal and inorganic fires
• Highest performance, cost effective
• 5 year warranty
• Compliant with IEC 61508 Safety Integrity requirements (SIL2)
• CPD and LPCB certified, according to EN54-10
The SharpEye 40/40 Series Flame Detectors provide the most comprehensive
protection against hydrocarbon based fuel and gas fires, hydroxyl and hydrogen
fires, as well as metal and inorganic fires. The detectors provide early warning of
fires at long distances with high immunity to false alarms.
The 40/40 series designs are the highest performance, cost effective flame detectors
currently on the market. The flame detectors include a stainless steel housing with
a heated window, to eliminate condensation and icing; HART capabilities for digital
communications; lower power requirements; and a compact, lightweight but highly
durable and weather resistant design.
The 40/40 flame detector series is highly reliable, with a newly extended 5-years
warranty period and compliance with the IEC 61508 safety integrity requirements
of SIL2.
Standard delivered with a special weather cover.
Test equipment for flame detectors is included in Part 6 of this catalogue.
The below items are available on request only. Please check the last price list for lead time information.
Specifications
• Dimensions (W x H x D): • Weight: • Ex Approved for Zone 1: • Operating voltage: • Power consumption: 90 mm x114 mm x 156 mm
- Detector (St.St.) 2.5 kg
- Detector, aluminum 1.2 kg
ATEX and IECEx
24 VDC nominal (18-32 VDC)
- Standby: max 100mA
- Alarm: max 150mA (add 50mA for heated window)
Approved: LPCB EN54-10, TÜV SIL2, ATEX/IECEX & CPD
40/40-U
UV detector
Detector detects hydrocarbon based fuel and gas fires, invisible hydrogen flames
and fires from hydrides, ammonia, silane and other organic materials with its unique
UV solar blind sensor.
CPD approved: 0832-CPD-0979
40/40-UB
UV detector with built in test kit
CPD approved: 0832-CPD-0980
40/40-L
UV/IR dual detector
A dual UV and IR detector, comprising an IR sensor that operates at a wavelength
of 2.5-3.0 μm and a UV solar blind sensor, the 40/40L detects hydrocarbon based
fuel and gas fires, hydroxyl and hydrogen fires, as well as metal and inorganic fires.
CPD approved: 0832-CPD-0973
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
150
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
40/40-LB
Flame Detectors
UV/IR dual detector with built in test kit
CPD approved: 0832-CPD-0976
40/40-L4
UV/IR (4,5µm) dual detector
A dual UV and IR detector, comprising an IR sensor that operates at a wavelength
of 4.5 μm and a solar blind UV sensor, the 40/40L detects only hydrocarbon based
fuel and gas fires.
CPD approved: 0832-CPD-0974
1
40/40-L4B
UV/IR (4,5µm) dual detector with built in test kit
2
CPD approved: 0832-CPD-0975
3
40/40-I
Triple IR detector
Detects hydrocarbon fuel and gas fires at long distances and provides the highest
immunity to false alarms with its triple spectrum design.
The IR3 can detect a 0.1m² gasoline pan fire at 65m in less than 5 seconds.
4
5
CPD approved: 0832-CPD-0972
6
40/40-M
Multi sensor detector
Detects hydrocarbon and hydrogen flames at long distances and provides the
highest immunity to false alarms with its multi spectrum design. The 40/40M can
detect a gasoline pan fire at 65m, or a hydrogen flame at 30m in less then 5 seconds.
7
8
CPD approved: 0832-CPD-0977
40/40-R
Single IR detector
Detects hydrocarbon based fuel and gas fires, comprising an IR sensor working at
4.5 μm wavelength for maximum sensitivity and provides immunity to false alarms
from IR sources such as sunlight and IR projectors.
CPD approved: 0832-CPD-0978
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
151
Special Equipment
Flame Detectors
RIV Series
Item available on request only. Please check the last price list for lead time information.
RIV-601P/F
IP66 waterproof IR flame detector
The IR flame detector model RIV-601P/F is an electronic optical fire detecting device
which responds immediately to the thermal infrared radiation emitted by fire and is
turned to the flickering frequency of the flame to ignore sun and lamp light.
Specifications
• Dimensions (W x H x D): • Weight: • Current consumption:
• Operating voltage:
• IP rating:
• Cable entry fitting:
• Operating temperature:
• Relay output: • Approved to:
180 mm x 85 mm x 65 mm
700g
13mA stand-by, 50mA in alarm
24VDC
IP66 (Cast aluminium watertight case)
M25, internal diameter 13-18mm
-20°C to +60°C
One changeover relay contact rated 1A/30VDC
EN54-10 Class 1
CPD number: 0786-CPD-21103; VdS number: G211093
RIV-601P/FA
RIV-601P/F IR flame detector with eex-proof enclosure
The RIV-601P/FA is the same IR flame detector as the RIV-601P/F, but in an
explosion proof enclosure.
Specifications
•
•
•
•
Protection rating:
Max. case temperature:
Dimensions:
Weight:
II 2 GD Ex d IIC T6 Ex tD IP66
85°C max
225 mm x 255 mm x 170 mm
11.5 kg
Atex number: BVI 07 ATEX 0023
SOR-873P
Variable direction stand for RIV-601P/F
SOA-875
Variable direction stand for RIV-601P/FA
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
152
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
Flame Detectors
Mini 20/20MI Series
The SharpEye Mini-IR3 Flame Detector (20/20MI) is a high performance and high
reliability compact, selfcontained triple spectrum infrared flame detector which offers
the highest immunity to false alarms for applications in a wide range of industrial
and commercial facilities, where the threat of accidental fire involves hydrocarbon
fuels such as gasoline, kerosene, diesel fuel, aviation jet fuels like JP-4, JP-5, JP8, hydraulic fluids, paints and solvents, monomers and polymers like ethylene and
polyethylene, natural gas (LNG), town gas and liquefied petroleum gas (LPG),
hydrocarbon gases like methane, ethane, propane, butane, acetylene, propylene,
etc.
•
•
•
•
•
Available in Non Eex version.
Multiple detection levels
90°/90° cone of vision
Adjustable time delay
Stainless steel 316
The below items are available on request only. Please check the last price list for lead time information.
1
Specifications
• Spectral response: • Field of View: • Sensitivity range: • Power supply: • Power consumption: • Relays: • Dimensions: • Weight: • Relative humidity: • Operating temperature range: • IP rating: • Approved to: Three IR bands
100° horizontal, 100° vertical
20/20MI-1: 10m to 40m; 20/20MI-3 2,5m to 10m
18-32VDC
Max.50 mA in Alarm
Alarm (NO) & fault (NC) volt free contact rated at 2A/30VDC
100 mm x 100 mm x 62 mm
1,2Kg
Max. 95%
-40°C to +70°C
IP66
EN54-10
CPD number: 0786-CPD-20916; Vds number: G207073
20/20MI-1-1-F
Triple IR Detector low powered - 10-40m - non ATEX
20/20MI-3-1-F
Triple IR detector low powered - 2,5-10m - non ATEX
2
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
153
Special Equipment
Flame Detectors
Mini 20/20MPI-R
20/20MPI-R
Triple IR detector flame detector, relay outputs
The 20/20 MPI-R is a high performance, compact triple IR (IR3) flame detector in a
lightweight polycarbonate housing. It retains all the benefits if IR3 technology - long
distance detection (up to 43 m) along with the highest immunity to false alarm. The
IR3 detector is especially suited to indoor applications, such as airport terminals,
train stations, storage areas, public buildings,...
This item is available on request only. Please check the last price list for lead time information.
Specifications
• Spectral response: • Field of View: • Power supply: • Power consumption: • Relays: • Dimensions: • Weight: • Humidity: • Operating temperature range: • IP rating: • Approved to: Three IR bands
100° horizontal, 90° vertical
18-32VDC
Max.25 mA in Alarm
Alarm (NO) & fault (NC) volt free contact rated at 2A/30VDC
119 mm x 74 mm
300gr
Max. 95%
-40°C to +70°C
IP55
EN54-10
VdS number: 0786-CPR-21344
Flame detectors accessories
The below items are available on request only. Please check the last price list for lead time information.
20/20-005
Swivel mount stainless steel for 20/20-M series
20/20-787
Air shield for mini series
20/20-794079-3
Commissioning tools kit for mini series
Used for change default delay and default sensitivity.
40/40-ADD-ST
Supplement for a stainless steel housing
40/40-ADD-85
Supplement for a calibration to 85°C
40/40-001
Tilt mount for 40/40 flame detectors
The tilt mount is an adjustable mounting bracket to allow the detector to be oriented
towards the intended fire detection area to maximise coverage.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
154
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Special Equipment
40/40-777650
Flame Detectors
Air shield stainless steel
The air shield enables the connection of a compressed air line to provide an ‘air
curtain’ that helps avoid accumulation of dirt on the detector window thereby
reducing maintenance need and frequency in polluted or dirty environments.
40/40-777163
Stainless steel weather cover
The weather protector is designed to protect the detector from rain and snow and
direct extreme temperatures from the sun (remember our detectors can operate in
ambients up to 85ºC without protection).
1
2
3
4
40/40-777166
Laser pointer
The laser detection area coverage pointer enables designers and installers to
assess and optimise, on site, the actual location and area coverage (cone of vision)
of our flame detectors.
40/40-789260-2
Pole mount (U-BOLT) - 2”
40/40-789260-1
Pole mount (U-BOLT) - 3”
40/40-777910
Window protector (dust cap) for 40/40 flame detectors
40/40-A0000231
TCC-80 RS-232 to RS-485 convertor
5
6
7
8
Serial port powered RS-232 to TS-485 convertor with 15 KV ESD Surge.
40/40-794079-5
USB connection kit for PC
Includes USB to RS232 convertor, RS232 to RS485 convertor, cable and software.
40/40-777820
Handheld pocket pc diagnostics kit
Mini PC kit containing all configuration software for 20/20 and 40/40 series flame
detectors.
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
155
Special Equipment
Spare parts
Spare parts
Part number
Description
Spare part for:
02-FL53
Replacement filter for A300 Series 20PPI (Pack of 10)
A300 series aspiration
02-FL56
Replacement filter for A300 Series 45PPI (Pack of 10)
A300 series aspiration
20-LA00015-03
Replacement key to open an A300 housing
A300 series aspiration
BATV-23
Spare battery for FKAC 2100R
FKAC
CR-123
Main lithium battery for wireless devices
Wireless
CR-2032
Back up lithium battery for wireless devices
Wireless
CR-4148
Battery pack for FDKM 2100 R
FDKM
F-A3384-000
Integral filter for FAAST 8100E
FAAST
F-AF-2.0
Aspiration Reducing Film Sheet 2.0mm
Aspirating systems
F-AF-2.5
Aspiration Reducing Film Sheet 2.5mm
Aspirating systems
F-AF-3.0
Aspiration Reducing Film Sheet 3.0mm
Aspirating systems
F-AF-3.6
Aspiration Reducing Film Sheet 3.6mm
Aspirating systems
F-AF-4.0
Aspiration Reducing Film Sheet 4.0mm
Aspirating systems
F-AF-4.6
Aspiration Reducing Film Sheet 4.6mm
Aspirating systems
F-AF-5.0
Aspiration Reducing Film Sheet 5.0mm
Aspirating systems
F-AF-5.6
Aspiration Reducing Film Sheet 5.6mm
Aspirating systems
F-AF-6.0
Aspiration Reducing Film Sheet 6.0mm
Aspirating systems
F-A-LC-A
Language Card Faast 8100e
FAAST
F-BS
Banderole for Suction- Reducing Foil
Aspirating systems
FL-IF-6
FAAST LT integral filters (pack of 6)
FAAST LT
F-LT-EB
Earth bar for FAAST-LT
FAAST LT
F-PC
Pipe cutter, for pipes up to 27mm
Aspirating systems
MSD/A
Dome for MS2/ Amber
MS2
MSD/B
Dome for MS2/ Blue
MS2
MSD/R
Dome for MS2/ Red
MS2
NAS-2 FIL
NAS2 Main internal filter cartridge
NAS aspiration
NAS-2 FIL-INT
NAS-2 Second internal filter cartridge
NAS aspiration
NAS-2 KEYPAD
Replacement keypad for NAS-2
NAS aspiration
RF-FTX
Replacement filter for HPX-751E
HPX-751E
SAHEP-KEY
Spare key for MI-SAHEP-4
SAHEP
SAHEP-PCB
Replacement PCB for MI-SAHEP-4
SAHEP
SAHEP-PLEXI/M-IAS
Plexi breakglass for MI-SAHEP-4 (with Morley-IAS logo)
SAHEP
SG-M210
Spare test key for SGCP100
Wireless
VSP-005
Filter cartridge for Vesda
Vesda aspiration
VSP-850-G
External filter for very harsh environment
Aspirating systems
VSP-850-R
Inline filter red for tube 25mm & 3/4”
Aspirating systems
VSP-855-20
Replacement filter element for VSP-850-G (pack of 20)
Aspirating systems
VSP-855-4
Replacement filter element for VSP-850-G (pack of 4)
Aspirating systems
For spare parts, please refer to § Spare Parts at the end of this chapter (04. Special Equipment)
156
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection
Systems
Gas Detection Systems
Notes
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
158
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Gas Detection Panels
Unipoint Controllers
The Unipoint controllers are available on request only. Please check the last price list for lead time information.
The Unipoint is a simple DIN rail mounted controller offering integrators a flexible
and low cost solution to incorporate flammable, toxic or oxygen gas detection into
their control systems.
Unipoint can be easily installed into any plastic or metal enclosure for use indoor or
outdoor and even in potentially explosive atmospheres. With the addition of one of
the range of flammable, toxic or oxygen detectors, systems may be configured to
monitor gases in a wide range of applications from car parks and boiler houses to
analyzer shelters or crane cabs in offshore facilities.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Small and medium integrated systems
Custom control cabinets and panels
Unmanned equipment rooms
Boiler houses
HVAC systems
Analyser houses
Car parks
Crane cabs
Laboratories
Ultra-clear backlit display
System status codes
Built-in audiovisual alarms
Intuitive menu system
Simple push button operation
Remote accept, reset and inhibit inputs
Each controller is supplied with all necessary removable terminals, DIN rail socket
and power connector.
Each controller contains a buzzer and 3 (NO-NC) alarm relays and 1 (NO-NC) fault
relay. Alarm levels are configurable per controller. Inputs for remote reset and inhibit
functionality are available on each controller.
Password protection for configuration menu is possible.
1
3
Please note that a specific training is required for the installation of this item.
4
Specifications
• IP rating:
• Weight: • Operating temperature range: • Relative humidity: • Operating pressure range: • Storage: Indoor, IP3x, to BS EN 60529:1992
(controller to be installed in suitable enclosure)
225g (controller only)
-10°C to +40°C
10% to 90% (non-condensing)
90-110kPa
-25°C to +60°C, 20 to 80%RH (non condensing)
Approvals:
EMC/RFI EN50270; Electrical Safety EN61010, UL61010b
Performance ATEX measuring function EN60079-29-1; Other CE, TUV
Z-2306B2000
2
5
6
7
8
Unipoint controller mV input version
Compatible with combustible gas detectors.
Z-2306B1000
Unipoint controller mA input version
Compatible with toxic gas detectors (4-20mA).
Z-ZDINPSUX1
DIN rail mounted power supply 24Vdc - 1A
Up to 4 Unipoint controller modules can be connected.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
159
Gas Detection Systems
Gas Detectors
Gas Detectors
Signalpoint Range
The Signalpoint range of flammable, toxic and oxygen gas detectors offer users a
low cost solution to their indoor gas monitoring needs. Supplied with an integral prewired junction box, the detector can be installed using conduit or cable and glands
depending on individual site standards.
Two basic arrangements are provided. Flammable detectors offer mV bridge output
for use with dedicated gas control systems (such as Unipoint) and are certified under
ATEX for use in potentially explosive atmospheres. Toxic and Oxygen detectors
are designed for use in non explosive atmospheres. They are 2 wire 4-20mA loop
powered and can be used with PLC or dedicated gas control systems.
• Flammable, toxic and oxygen versions available
• IP54 as standard
• Suitable for indoor use
• Surecell™ electrochemical sensors
• Poison resistant catalytic bead
• Fast and reliable
• ATEX hazardous area approval
• Performance to EN50054
• Typical 5 years operational life
Z-2106B1100
Signalpoint 0-100% LEL comb. detector (mV output)
The Signalpoint range is available on request only. Please check the last price list for lead time information.
Specifications
• Material: • IP rating:
• Operating humidity range:
• Operating pressure:
• Storage conditions:
• Weight:
• Certification:
• Standards:
Sensor Polyphenylene Sulphide (PPS) Integral Junction Box: Impact resistant Nylon.
IP54 in accordance with EN60529:1992
Continuous: 20-90% RH (non condensing), Intermittent: 10-99% RH (non condensing)
90-110kPa
0°C to +25°C
Flammable (0-100%LEL): 465g
Toxic & Oxygen: 495g
Flammable (0-100%LEL): Ex II 2G EEx e d IIC T4; BAS98ATEX2085X
Toxic & Oxygen: Safe area use only
Toxic & Oxygen: MC to BS EN50081 part 1; BS EN50082 part 2; Performance to EN45544
IP54; ATEX II2G Ex dc IIC T4 (T°amb. = -30°C to +40°C); BAS98ATEX2085X.
Average life time: 5 years.
Signalpoint Toxic
Z-2106B1305
Signalpoint CO 0-100 ppm toxic detector (mA output)
IP54 - Only to be used in safe zones. Average life time is 48 months.
Z-2106B1306
Signalpoint CO 0-200 ppm toxic detector (mA output)
IP54 - Only to be used in safe zones. Average life time is 48 months.
Z-2106B1307
Signalpoint CO 0-500 ppm toxic detector (mA output)
IP54 - Only to be used in safe zones. Average life time is 48 months.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
160
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Z-2106B1300
Gas Detectors
Signalpoint H2S 0-20 ppm toxic detector (mA output)
IP54 - Only to be used in safe zones. Average life time is 48 months.
Z-2106B1301
Signalpoint H2S 0-50 ppm toxic detector (mA output)
IP54 - Only to be used in safe zones. Average life time is 48 months.
Z-2106B1302
Signalpoint H2S 0-100 ppm toxic detector (mA output)
IP54 - Only to be used in safe zones. Average life time is 48 months.
1
Z-2106B1316
Z-2106B1310
Signalpoint O2 0-25%VOL toxic detector (mA output)
IP54 - Only to be used in safe zones. Average life time is 12 months.
2
Signalpoint Cl2 0-5 ppm toxic detector (mA output)
3
IP54 - Only to be used in safe zones. Average life time is 18 months.
4
Z-2106B1311
Signalpoint Cl2 0-15 ppm toxic detector (mA output)
5
IP54 - Only to be used in safe zones. Average life time is 18 months.
Z-2106B1313
Z-2106B1314
Signalpoint NH3 0-50 ppm toxic detector (mA output)
6
IP54 - Only to be used in safe zones. Average life time is 18 months.
7
Signalpoint NH3 0-1000 ppm toxic detector (mA output)
8
IP54 - Only to be used in safe zones. Average life time is 18 months.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
161
Gas Detection Systems
Gas Detectors
Sensepoint range
The Sensepoint range of flammable, toxic and oxygen gas detectors offer users
a low cost solution to their gas monitoring needs, in or out of doors and even in
potentially explosive atmospheres. Supplied with a pre-wired junction box, a
detector can be installed using conduit or armored cable and glands depending on
individual site standards.
Sensepoint flammable and toxic gas detectors are designed for use in potentially
explosive atmospheres and allow for hands free, unhindered access, to terminals
via the hinged lid of the junction box. Installation should follow national guidelines
using suitably approved armored cable and glands or conduit.
• Flammable, toxic and oxygen versions available
• Suitable for indoor or outdoor use
• IP65 as standard
• SurecellTM electrochemical sensors
• Poison resistant catalytic bead
• Fast and reliable
• Typical 2 to 5 years operational life
The Sensepoint range is available on request only. Please check the last price list for lead time information.
Specifications
• IP rating: • Operating temperature:
• Relative humidity:
• Operating pressure: • Storage conditions instrument: IP65 standard, IP66 with weather protection in accordance with EN60529:1992
Dependent upon gas type and certification
Continuous: 20-90% (non-condensing)
Intermittent: 10-99% (non-condensing)
90-110kPa
-40°C to +50°C
Gas Detectors
EMC to EN540270, Flammable to EN60079-29-1, Toxic to EN445544 (only
H2S)
Z-SPSTAXF1
0-100% LEL methane detector (mV output)
IP65; ATEX II2GD EEx d IIC T6 (T°amb.= -55°C to +55°C). Average life time: 5 years.
Z-SPSTAXC2
0-500 ppm carbon monoxide (CO) detector (mA output)
IP65; ATEX II2GD EEx d IIC T4 (T°amb. = -20°C to +65°C). Average life time: 48
months.
Z-SPSTAXO1
0-25% VOL oxygen (O2) detector (mA output)
IP65: ATEX II2GD EEx d IIC T4 (T°amb. = -20°C to +65°C). Average life time: 12
months.
Z-SPSTAXA1
0-50 ppm ammonia (NH3) detector (mA output)
IP65; ATEX II2GD EEx d IIC T4 (T°amb. = -20°C to +65°C). Average life time: 18
months.
Z-SPSTAXA2
0-1000 ppm ammonia (NH3) detector (mA output)
IP65; ATEX II2GD EEx d IIC T4 (T°amb. = -20°C to +65°C). Average life time: 18
months.
Other types of gas detectors are available on demand.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
162
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Gas Detectors
Z-02000-A-1635
Weatherproof CAP for Flammable detector
Z-02000-A-1640
Weatherproof CAP for Toxic/Oxygen detector
Z-02000-A-1642
Collecting cone for Flammable detector
Z-00780-A-0160
Right angle mounting bracket for ceiling mounting
Only compatible with Sensepoint series detectors.
Sensepoint XCD range
The standard XCD detector is supplied including one of three types of plug-in
stainless steel sensor. These sensors simply plug into the socket at the bottom of
the transmitter and the transmitter recognizes the sensor type and automatically
configures itself accordingly.
The Catalytic sensor is used to detect flammable gases in the range 0-100%LEL.
The Infrared (IR) sensors are used for detecting Hydrocarbon gases in the range
of 0-100%LEL and 0-100%V/V, as well as Carbon Dioxide (CO2) in the range 02.00%V/V
The Electrochemical Cell (ECC) sensor is used to detect Oxygen and toxic gases;
Carbon Monoxide (CO), Hydrogen Sulphide (H2S) and Hydrogen (H2).
The Sensepoint XCD range is available on request only. Please check the last price list for lead time information.
1
2
3
4
5
• Flammable, toxic and oxygen versions available
• Suitable for indoor or outdoor use
• IP65 as standard Proven Sensor Technology
• SurecellTM electrochemical sensors
• Poison resistant catalytic bead
• Fast and reliable
• Typical operational life:
- 5 years (Catalytic)
- 2 years (Electrochemical cells)
Specifications
Global Certifications
• North American and European
• Compliant with UL and ATEX standards
• Includes hazardous area and performance approval
ATEX: II2 GD Exd IIc GB T6 (Tamb. -40°C to +65°C); II2 GD Exd IIc GB T5
(Tamb. -40°C to +75°C); Ex td IIIc T85°C Db IP66 T100°C (Tamb. -40°C to
+75°C)
EMC: EN50270:2006; EN6100-6-4: 2007
• Weight: • IP rating: • Relative humidity: • Operating pressure: • Storage conditions instrument: • Operating temperature:
Stainless Steel SS316: 5 kg
Alu LM25: 2 kg
IP66 as standard in accordance with EN60529:1992
Continuous: 20-90% (non-condensing) Intermittent: 10-99% (non-condensing)
90-110kPa
-25°C to +65°C
Depends on gas type and certification
6
7
8
Sensepoint XCD - Stainless Steel SS316
Z-SPXCDASMFX
SENSEPOINT XCD flammable CAT 0-100% LEL
ATEX/IECEX & AP approved. (20 to 100%LEL, 10%LEL) with 316SS, M20 entry.
Z-SPXCDASMRX
SP XCD CH4 (methane) IR 0-100% LEL
ATEX/IECEX & AP approved. (20 to 100%LEL, 10%LEL) with 316SS, M20 entry.
Z-SPXCDASMO1
SP XCD oxygen 25.0% /Vol
ATEX/IECEX & AP approved. With 316SS, M20 entry.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
163
Gas Detection Systems
Z-SPXCDASMHX
Gas Detectors
SP XCD hydrogen sulfide 0-50 ppm
ATEX/IECEX & AP approved. (10.0 to 100.0ppm, 1ppm) with 316SS, M20 entry.
Z-SPXCDASMCX
SP XCD carbon monoxide 0-500 ppm
ATEX/IECEX & AP approved. (100 to 1000ppm, 100ppm) with 316SS, M20 Entry.
Z-SPXCDASMG1
SP XCD hydrogen 0-1000 ppm
ATEX/IECEX & AP approved. With 316SS, M20 Entry.
Z-SPXCDASMB1
ATEX/IECEX & AP approved SP XCD carbon dioxide IR 0-2.00 %VO
ATEX/IECEX & AP approved. With 316SS, M20 Entry.
Sensepoint XCD - Alu LM25
Z-SPXCDALMFX
Sensepoint XCD flammable CAT 0-100% LEL
ATEX/IECEX & AP approved. (20 to 100%LEL, 10%LEL) with LM25, M20 entry.
Z-SPXCDALMRX
SP XCD CH4 (methane) IR 0-100% LEL
ATEX/IECEX & AP approved. (20 to 100%LEL, 10%LEL) with LM25, M20 entry.
Z-SPXCDALMO1
SP XCD oxygen 25.0% / Vol
ATEX/IECEX & AP approved. With LM25, M20 entry.
Z-SPXCDALMHX
SP XCD hydrogen sulfide 0-50 ppm
ATEX/IECEX & AP approved. (10.0 to 100.0ppm, 1ppm) with LM25, M20 entry.
Z-SPXCDALMCX
SP XCD carbon monoxide 0-500 ppm
ATEX/IECEX & AP approved. (100 to 1000ppm, 100ppm) with LM25, M20 Entry.
Z-SPXCDALMG1
SP XCD hydrogen 0-1000 ppm
ATEX/IECEX & AP approved. With LM25, M20 Entry.
Z-SPXCDALMB1
ATEX/IECEX & AP approved SP XCD carbon dioxide IR 0-2.00%VOL
ATEX/IECEX & AP approved. With LM25, M20 Entry.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
164
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Gas Detectors
Accessories for Sensepoint XCD
The below items are available on request only. Please check the last price list for lead time information.
Z-S3KCAL
Calibration cup
Z-SPXCDCC
Collecting cone for use with lighter than air gases
Z-SPXCDDMK
Duct mounting kit
Z-SPXCD MTBR
Mounting bracket (inc. bolts, nuts, brackets)
Z-SPXCDSDP
Sunshade / Deluge protection
Z-00780-A-0100
ATEX approved junction box (Explosion proof)
1
2
3
4
5
6
7
8
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
165
Gas Detection Systems
Sensitron Gas Detection Panels
MULTISCAN++ S1
•
•
•
•
•
•
•
ATEX and SIL 1 certified (EN50402)
Up to 4 open RS485 (EIA-485) galvanic isolated loops
Up to 256 inputs (both 4-20 mA or intelligent loop daisy-chained)
Up to 256 O/C or relay outputs via remote modules and 8 pre-configured relays onboard the control unit.
Event log accessible from the front display or to be PC downloaded.
RS232 serial port for PC connection for programming or supervising the system via a specific software
Parallel port for printer connection.
The MULTISCAN++S1 is a gas detection control unit designed to meet the widest
range of flexibility required by the market.
The control panel is based on a powerful microprocessor which provides a wide
range of self-diagnostic procedures to detect and locate possible faults.
Extremely flexible and reliable, it can manage up to 64 or 128 or 256 gas detectors
(according to the different 4 versions). The detectors can be either of addressable
type, directly connected on buses, or 4-20mA analogical types connected via 8-input
STG/IN8-S remote modules.
System architecture also includes 8 on-board machine relays and the potential to
expand outputs up to 256 using remote STG/OUT16-S modules and 8-relay boards.
Up to 4 serial buses can be connected to the unit.
The unit allows for three alarm thresholds to be set for each detector. The alarm
threshold activation mode changes according to the type of gas detection profile
and connected detector.
The unit is inserted in a plastic box complete with 27 Vdc 4 A power supply.
The Multiscan++S1 range is available on request only. Please check the last price list for lead time information.
Specifications
• Housing: • Dimensions (L x H x D):
• Inputs:
• Outputs:
• Serial ports: • Power consumption: • Display: • Visual indications LED: • Operating temperature:
• Storage: • Relative humidity: • Storage: plastic box, IP65 or 19” 6U (HE) rack for 256 version)
470 mm x 426 mm x 148 mm
max. 256 RS485 comm. gas detectors bus connected (IDI version) or 4-20mA through STG/IN8.S modules.
8 relays on the unit + 128 or 256 open collector outputs on STG/OUT16-S modules (optional STG/8REL relay board)
4 RS485 ports (2 for 65 version) 1 RS232 for PC connection
Max 10 VA
Graphic Liquid Crystal Display (LCD)
Double 9 LED raw
0-55°C -20 / +60 C°
15% to 85% (non-condensing)
5% to 85% (non condensing)
Certification: IMG12ATEX002X; C-IS-213297-01
Block diagram for MULTISCAN++ S1
(1
16 O/C
(3
LOOP
(5
(2
(4
LOOP
(4
(1
LOOP
(OPTIONAL)
LOOP
CONTROL PANEL
(MULTISCAN ++ S1)
(1) 4-20 mA analog gas detectors
(2) Analog 8 input module ST.G/IN8N or S
(3) 2 Twisted wires for the RS485 bus + 2 wires for the power
supply (12-24Vdc)
(4) Gas detectors with RS485 output
(5) 16 O/C output module ST.G/OUT16N or S
(6) 8 relay ST.G/8REL module
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
166
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
(6
Gas Detection Systems
ST.MTS/S1
Sensitron Gas Detection Panels
MULTISCAN++ S1 gas control panel, rack version; 256 gas detectors
4 x RS485 type open bus lines or 2 closed loops. 256 Analog 4-20 mA gas detectors
connected through remote 8-input modules or intelligent gas detectors daisy chained
to the RS485 control panel’s loops and 8 4-20mA input boards. 8 relay output and up
to 256 O/C or relay outputs via remote modules.
The panels comes complete with 1 parallel printer port and 1 RS232 serial port for
PC connection.
Housed on a 19” 3 U rack (24 VDC power supply is required).
ST.MTS/S1-256B
MULTISCAN++ S1 gas control panel, ABS box; 256 gas detectors
As above but in IP65 ABS box. 230 VAC power supply.
1
ST.MTS/S1-128B
ST.MTS/S1-64B
ST.G/IN8-S
MULTISCAN++ S1 gas control panel, ABS box; 128 gas detectors
As above but in IP65 ABS box. 230 VAC power supply.
2
MULTISCAN++ S1 gas control panel, ABS box; 64 gas detectors
3
As above but in IP65 ABS box. 230 VAC power supply.
2 RS485 type open bus lines or 1 closed loop.
4
8-input remote max 16 modules
5
High safety 8-input remote module with improved performance for MULTISCAN++S1.
Max 16 modules per line for a total of 256 detectors connectable to the system.
ST.G/OUT16-S
16-output remote 8 modules
High safety 16-output remote module (Open collector type) with improved
performance for MULTISCAN++S1. Max 8 modules per line.
ST.G/8REL
6
7
8
Plug and play relay board
Plug and play relay board to be connected to STG/OUT16 to provide 8 relay outputs.
ST.G/SER++
Additional Serial board
Additional Serial board to implement serial lines in Multiscan++S1.
VMB/267V40
Power supply 24 Vdc/4A
Metal Cabinet with enclosed power supply to house one of the above remote cards.
24 VDC 4A.
ST.G/BOX
IP55 Plastic box
IP55 Plastic box to house one ST.G/IN8-S or ST.G/OUT16-S card.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
167
Gas Detection Systems
Sensitron Gas Detection Panels
Sentox IDI+ Gas Control Panel
SENTOX IDI+ has been designed for light industrial applications and can be
connected to max. 32 intelligent gas detectors daisy chained on the RS 485 bus line.
A high brightness display provides an ongoing reading of the concentration being
measured and, in case of an alarm, the alarm threshold attained and the respective
channel. Each threshold or function is visualised by a double LEDs raw.
SENTOX IDI+ provides 4 relays output: three associated to the alarm thresholds
and one to fault.
The panel also features the implementation of further 32 optional outputs via 2
ST.G/OUT16-N remote cards.
The unit comes into a metal cabinet, complete with 24VDC/5A power supply and
offers the possibility to allocate 2 back-up batteries (max. 12V/7Ah).
SENTOX IDI+ is SIL1 and ATEX certified according to EN60079-29-1
Specifications
•
•
•
•
•
•
•
Housing:
Dimensions (L x H x D):
Relay contact rating:
Power consumption:
Backup battery:
Operating temperature:
Relative humidity:
ABS IP65 rated box
486 mm x 288 mm x 148 mm
1A/24VDC /60Va
Max. 6VA
2 x 12V/7Ah max.
0°C to +55°C
15% to 85% (non-condensing)
ATEX number: IMG09ATEX027x
Block diagram for Sentox IDI+
Control panel
2 wires for Rs485 communication (Belden 9841 cable)
+ 2 wires for the power supply
2 OUTPUT MODULES
ST.G/OUT
16N (S)
RELAY
ST.G/OUT
16N (S)
RELAY
UP T O 30 SMART3 IDI OR LCR 3 PK IDI GAS DETECTORS
16 OPEN COLLECT
OR
OUTPUTS or 8 + 8
RELA Y by ST .G/8REL
CARDS (OPTIONAL)
I/F Rs485 /
USB or Rs232
(OPTIONAL)
5 RELAY OUTPUTS
PC FOR CONTROL PANEL SET-UP
ST.SX/IDI+
Microprocessor based control panel
Microprocessor based control panel to manage up to 32 "IDI" gas detectors.
4 output upgradeable to 36 by connecting two remote 16-output cards.
Housed in IP65 rated ABS box with enclosed 24 VDC/5A power supply.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
168
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Sensitron Gas Detection Panels
STPL4+ Gas Control Panel
•
•
•
•
•
Real time reading of flammable, toxic and oxygen contents
4-8 input 4-20mA
5 relay outputs
Ideal for small plants
ATEX and SIL1 certified
The STPL4+ gas control unit represents the best technology for the detection of
flammable, toxic or oxigen compounds in small systems.
The STPL4+ has 4 intelligent 4-20mA inputs that can be extended to 8 by using the
4-input expansion board (ST.PL4/ESP), easy to plug in the control unit.
The panel is housed in a IP65 ABS box with a 12vdc 1.5A power supply integrated.
Mode status LEDs for alarms and fault warning along with the backlit LCD display
provide real time gas concentration reading.
An internal buzzer provides an audible alarm that will activate according to the
programmed alarm thresholds.
Alarms are user selectable and for each input it is possible to set the type of detector,
its full scale range and the alarm thresholds.
The panel can be easily programmed via the 3 position key-switch for Set, Unset
and Program along with the Reset and Acknowledge push buttons.
The panel comes complete with 5 output relays: one for each threshold (AL1, AL2,
AL3), 1 for fault (FLT) and 1 auxiliary and freely programmable.
By using the on 4-input expansion board, the panel can benefit of further 16 Opencollector outputs linked to the second and third alarm thresholds (AL2 - AL3) of each
detector being connected.
The STPL4+ box can fit a 12Vdc 7Ah back-up battery to ensure the system correct
working when the main power supply fails.
1
2
3
Specifications
• Housing:
• Dimensions (L x H x D):
• Microprocessor:
• Inputs:
• Outputs:
• Display:
• LED indications:
• Power supply:
• Power consumption (@ 12Vdc):
• Operating temperature:
• Relative humidity:
ABS IP65 rated box
486 mm x 288 mm x 148 mm
8 BIT
4 intelligent inputs 4-20mA expandable to 8 by adding the ST.PL4/ESP board
5 relays on board the panel. 16 O/C outputs available on the ST.PL4/ESP board
Backlit LCD; 16 caracters on 2 rows
Main power supply; AL1; AL2; AL3; Fault; Battery operated
230Vac +/- 10%
80mA normally; 160mA in alarm; 240mA with ST.PL4/ESP
0°C to +50°C
15% to 85% (non-condensing)
4
5
6
7
8
Block diagram for STPL4+
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
169
Gas Detection Systems
STPL4+
Sensitron Gas Detectors
Microprocessor based control panel
Gas control panel to manage up to 4 "IDI" gas detectors. Extendable to 8 by using
the 4-input expansion board ST.PL4/ESP.
ST.PL4/ESP
4 Channel extension card for STPL4+
Sensitron gas detectors
SMART3 NC Series
Gas detectors series SMART3 NC have been designed to offer cost effective
products with Hi-Tech professional features for car parks and non-classified areas.
Available only for Methane, LPG, Petrol Vapours, CO, NO2 and CO2, these
detectors employ a professional catalytic sensor for flammable gas detection, an
electrochemical cell for CO and an infrared sensor for the CO2 detection.
The SMART3 NC provide an analog 4-20 mA output signal and can be implemented
with additional features to allow the instrument to have an RS485 communication
or three-relay outputs.
SMART3 NC gas detectors are IP55 rated. Estimated sensor lifetime is 4 years
SMART3 NCPK - For car parks
S1450CO
CARBON MONOXIDE (CO) detector
Range value interface: 0-300 ppm, 4-20 mA.
S2396VB
The below SMART3 NCPK gas detectors are available on request only. Please check the last price list for lead time information.
PETROL VAPOURS detector
Range value interface: 4-20mA.
S1451ND
NO2 detector
Range value interface: 4-20mA.
SMART3 NC - Flammable gas detectors for non classified areas
S2396ME
METHANE detector
0-100% LEL. Range value interface: 4-20mA.
S2396GP
LPG detector
0-100% LEL. Range value interface: 4-20mA.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
170
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
S2401CO2
Sensitron Gas Detectors
CARBON DIOXIDE (CO2) detector
Range value interface: 0-5000 ppm, 4-20 mA.
Item available on request only. Please check the last price list for lead time information.
SMART3G-D2
Designed to meet with tough industrial requirements, the SMART3G-D2 allows
monitoring toxic and flammable contents in harsh environments and classified areas.
They offer a 4-digit back-lit display and 5 status mode LED for the gas concentration
reading.
Ideal in harsh environments, the SMART3G-D2 feature non intrusive calibration
for an accurate and easy adjustment via Hall-effect switches, without opening the
instrument and declassifying the area.
They can reliably monitor flammable compounds (%LEL), toxic compounds in ppm,
Oxygen and CO2 contents in % by Vol.
SMART3G-D2 features:
•
•
•
•
•
•
•
•
•
•
•
Non-intrusive one man calibration via Hall effect switches
4-digit display and 5 mode status LEDs
Standard 4-20 mA 3 wires output
Optional 3 relays output
Optional RS485 interface for Modbus communication to make the detectors communicate to MULTISCAN++ and SENTOX IDI+ control panels.
Zero tracking to maintain the zero point steady from possible drifts
Ongoing system self diagnosis
ATEX II2G (GD with optional adapter) and SIL 1 certified (EN50402)
Wide range of sensors and detectable gases
Wide range of accessories for installation and maintenance
Easy sensor replacement
SMART3G-D2 Flammable Gas (with Catalytic sensor)
The below items are available on request only. Please check the last price list for lead time information.
Range value interface: 4-20 mA, 0-100%LEL.
S2157ME
METHANE detector
S2157GP
LPG detector
S2157PR
PROPANE detector
S2157BU
BUTANE detector
S2157VB
PETROL VAPOURS detector
1
2
3
4
5
6
7
8
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
171
Gas Detection Systems
Sensitron Gas Detectors
SMART3G-D2 IRL - Flammable Gas (with infrared sensor)
The below items are available on request only. Please check the last price list for lead time information.
Range value interface: 4-20 mA, 0-100%LEL.
S2602ME
METHANE detector
S2602PR
PROPANE detector
S2602BU
BUTANE detector
SMART3G-C2 - Gas detectors for Zone 1 Category 2 areas
Designed to meet with tough industrial requirements, the SMART3G-C2 allows
monitoring toxic and flammable contents in industrial environments and classified
areas.
The SMART3G-C2 detectors can reliably monitor flammable compounds (%LEL),
toxic compounds in ppm, Oxygen and CO2 contents in % by vol.
SMART3G-C2 features:
•
•
•
•
•
•
•
•
•
Standard 4-20 mA 3 wires output
Optional 3 relay output
Optional RS485 interface for Modbus communication to make the detectors communicate to MULTISCAN++ and SENTOX IDI+ control panels.
Zero tracking to maintain the zero point steady from possible drifts
Ongoing system self diagnosis
ATEX II2G (GD with optional adapter) and SIL 1 certified (EN50402)
Wide range of sensors and detectable gases
Wide range of accessories for installation and maintenance
Easy sensor replacement
The below items are available on request only. Please check the last price list for lead time information.
Range value interface: 4-20 mA, 0-100%LEL.
S2097ME
METHANE detector
S2097GP
LPG detector
S2097BU
BUTANE detector
S2097PR
PROPANE detector
S2097VB
PETROL VAPOURS detector
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
172
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Sensitron Gas Detectors
SMART3G-C2 IR - Flammable Gas (with infrared sensor)
The below items are available on request only. Please check the last price list for lead time information.
Range value interface: 4-20 mA, 0-100%LEL.
S2654ME
METHANE detector
S2654PR
PROPANE detector
S2654BU
BUTANE detector
1
2
SMART3G-C2 - Toxic Gases (with Electrochemical cell)
S2641O2
S2131CO
The below items are available on request only. Please check the last price list for lead time information.
OXYGEN (O2) detector
3
4
Range value interface: 0-25% Vol., 4-20mA
5
CARBON MONOXIDE (CO) detector
6
Range value interface: 0-500 ppm, 4-20mA
7
S2133AM
AMMONIA (NH3) detector
Range value interface: 0-200 ppm, 4-20mA
S2135AM
8
AMMONIA (NH3) detector
Range value interface: 0-1000 ppm, 4-20mA
S2137HS
HYDROGEN SULPHIDE (H2S) detector
Range value interface: 0-50 ppm, 4-20mA
S2145NO
NITRIC OXIDE (NO) detector
Range value interface: 0-100 ppm, 4-20mA
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
173
Gas Detection Systems
Sensitron Gas Detectors
SMART3G-D3 - Gas detectors with display, for zone 2 category 3 areas
Designed to meet with industrial requirements, the SMART3G-D3 allow monitoring
toxic and flammable contents in areas classified as zone 3.
They offer a 4-digits back-lit display and 5 mode status LEDs for the gas concentration
reading and feature non intrusive calibration for an accurate and easy adjustment
via Hall-effect switches, without opening the instrument and declassifying the area.
The SMART3G-D3 detectors can reliably monitor flammable compounds (%LEL),
toxic compounds in ppm, Oxygen and CO2 in % by vol.
SMART3G-D3 features:
•
•
•
•
•
•
•
•
•
•
•
Non-intrusive one man calibration via Hall effect switches
4-digit display and 5 mode status LEDs
Standard 4-20 mA 3 wires output
Optional 3 relays output
Optional RS485 interface for Modbus communication to make the detectors communicate to MULTISCAN++ and SENTOX IDI+ control panels.
Zero tracking to maintain the zero point steady from possible drifts
Ongoing system self diagnosis
ATEX II3G (GD with optional adapter) and SIL 1 certified (EN50402)
Wide range of sensors and detectable gases
Wide range of accessories for installation and maintenance
Easy sensor replacement
The below items are available on request only. Please check the last price list for lead time information.
Range value interface: 4-20 mA, 0-100%LEL.
S2156ME
METHANE detector
S2156GP
LPG detector
S2156PR
PROPANE detector
S2156BU
BUTANE detector
S2156VB
PETROL VAPOURS detector
SMART3G-D3 IR - Flammable Gas (with Infrared sensor)
The below items are available on request only. Please check the last price list for lead time information.
Range value interface: 4-20 mA, 0-100%LEL.
S2601ME
METHANE detector
S2601PR
PROPANE detector
S2601BU
BUTANE detector
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
174
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Sensitron Gas Detectors
SMART3G-D3 - Toxic Gas (with Electrochemical cell)
S2642O2
The below items are available on request only. Please check the last price list for lead time information.
OXYGEN (O2) detector
Range value interface: 0-25% Vol., 4-20 mA.
S2162CO
CARBON MONOXIDE (CO) detector
Range value interface: 0-500 ppm, 4-20 mA.
SMART3G-C3 - Gas detectors for zone 2, category 3 areas
Designed to meet with light industrial requirements, the SMART3 GC-2 gas detectors
allow monitoring toxic and flammable contents in areas classified as zone 3.
The SMART3 GC-3 can reliably monitor flammable compounds (%LEL), toxic
compounds in ppm, Oxygen and CO2 contents in % by vol.
1
2
3
4
SMART3 GC-3 features:
•
•
•
•
•
•
•
•
Standard 4-20 mA 3 wires output
Optional 3 relays output
Optional RS485 interface for Modbus communication to make the detectors communicate to MULTISCAN++ and SENTOX IDI+ control panels.
Ongoing system self diagnostic
ATEX II3G (GD with optional adapter) and SIL 1 certified (EN50402)
Wide range of sensors and detectable gases
Wide range of accessories for installation and maintenance
Easy sensor replacement
5
6
7
The below items are available on request only. Please check the last price list for lead time information.
8
Range value interface: 4-20 mA, 0-100%LEL.
S2096ME
METHANE detector
S2096GP
LPG detector
S2096PR
PROPANE detector
S2096BU
BUTANE detector
S2096VB
PETROL VAPOURS detector
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
175
Gas Detection Systems
Sensitron Gas Detectors
SMART3G-C3 IR - Flammable gases (with Infrared sensor)
The below items are available on request only. Please check the last price list for lead time information.
Range value interface: 4-20 mA, 0-100%LEL.
S2653ME
METHANE detector
S2653PR
PROPANE detector
S2653BU
BUTANE detector
SMART3G-C3 - Toxic gases (with Electrochemical cell)
S2640O2
The below items are available on request only. Please check the last price list for lead time information.
OXYGEN (O2) detector
Range value interface: 0-25% Vol., 4-20 mA.
S2130CO
CARBON MONOXIDE (CO) detector
Range value interface: 0-500 ppm, 4-20 mA.
Gas detector accessories
ST.S/IDI
Plug-in RS485 interface
Plug-in RS485 interface, to make SMART3 series gas detectors communicate with
SENTOX IDI+ and MULTISCAN++ control panels.
ST.S/CKD
Handheld calibration keypad
Handheld calibration keypad to be connected to the detector to adjust the Zero,
Span and 4-20mA values.
ST.S3REL
3-Relay card with short flat cable
3-Relay card for SMART3GC series gas detectors. Relay at 12÷24V. Includes short
flatcable.
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
176
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Gas Detection Systems
Gas Detectors Accessories
STGD/AD3
The below items are available on request only. Please check the last price list for lead time information.
Adapter for type 3 sensor heads
Adapter for type 3 sensor heads to upgrade the protection from G to GD.
STGD/AD2
Adapter for type 2 sensor heads
Adapter for type 2 sensor heads to upgrade the protection from G to GD.
Detector type
GD2GD3GG1GC2GC3
STS/CSW XXXXX
ST.S/IDI XXXXX
ST.S/CKD ----XXX
ST.S3REL----XXX
ZM/TEST/2
Water protection/test adapter for sensor head type 2
Permanent water protection/test adapter suitable for sensor head type 2 (like S2096
and S2097).
ZM/TEST/3
Water protection/test adapter for sensor head type 3
1
2
3
4
5
Permanent water protection/test adapter suitable for sensor head type 3.
6
SL517
Stainless steel collector for sensor head type 3
Stainless steel collector and weather protection cone for Explosion proof gas
detector (suitable for sensor head type 3).
7
8
SL523
Stainless steel collector for sensor head type 2
Stainless steel collector and weather protection cone for Explosion proof gas
detector suitable for sensor head type 2 (like S2096 and S2097).
SL647
Stainless steel weather protection roof, wall mount type
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
177
Gas Detection Systems
Spare parts
Spare parts
Part number
Description
Spare part for:
Z-2106B1130
Signalpoint 0-100% LEL flam. replacement lid
Signalpoint
Z-2106B1545
Signalpoint O2 electrochemical cell
Signalpoint
Z-2106B1548
Signalpoint CO electrochemical cell
Signalpoint
Z-2106B1549
Signalpoint H2S electrochemical cell
Signalpoint
Z-2106B1596
Signalpoint 0-50PPM NH3 electrochemical cell
Signalpoint
Z-2306B3010
Unipoint terminal block (2x)
Unipoint
Z-2306B3020
Unipoint DIN rail socket
Unipoint
Z-2306B3030
Unipoint power connector
Unipoint
Z-SPPPMTS
Touchpoint TP1 or TP4 terminal screw and ‘U’ clamp (bag of 20)
Touchpoint
Z-SPSTAXO1SS
Sensepoint O2 electrochemical cell
Sensepoint
Z-SPSTAXA1SS
Sensepoint NH3 0-50PPM electrochemical cell
Sensepoint
Z-SPSTAXA2SS
Sensepoint NH3 0-1000PPM electrochemical cell
Sensepoint
Z-SPSTAXC2SS
Sensepoint CO electrochemical cell
Sensepoint
Z-SPSTAXF1SS
Sensepoint 0-100% LEL flam. replacement lid
Sensepoint
Z-TP1IDC
Touchpoint TP1 IDC lead (display to input module)
Touchpoint
Z-TP1MADM
Touchpoint TP1 replacement mA display module
Touchpoint
Z-TP1MAIM
Touchpoint TP1 replacement mA input module
Touchpoint
Z-TP1MVDM
Touchpoint TP1 replacement mV display module
Touchpoint
Z-TP1MVIM
Touchpoint TP1 replacement mV input module
Touchpoint
Z-TP1WMB
TP1 wall mounting bracket
Touchpoint
Z-TP4CMDM
Touchpoint TP4 replacement display module for common module
Touchpoint
Z-TP4CMIM
Touchpoint TP4 replacement input module for common module
Touchpoint
Z-TP4IDC
Touchpoint TP4 IDC lead (display to input module)
Touchpoint
Z-TP4INT
Touchpoint TP4 interconnect cable (input module to input module)
Touchpoint
Z-TP4MADM
Touchpoint TP4 replacement mA display module
Touchpoint
Z-TP4MAIM
Touchpoint TP4 replacement mA input module
Touchpoint
Z-TP4MVDM
Touchpoint TP4 replacement mV display module
Touchpoint
Z-TP4MVIM
Touchpoint TP4 replacement mV input module
Touchpoint
Z-TP4WMB
Touchpoint TP4 wall mounting bracket
Touchpoint
Test and calibrating equipment for gas detectors is included in Part 6 of this catalogue.
For spare parts, please refer to § Spare Parts at the end of this chapter (05. Gas Detection Systems)
178
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Accessories
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
180
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Power Supplies
Power Supplies
HLSPS25
Power supply unit 24VDC - 3A (2 x 1,1A)
Earth monitoring and fault relay input to disable the battery charger when the fire
panel is in alarm (providing 300mA extra current).
Specifications
• Weight: • Dimensions (W x H x D): • For battery type:
5.5kg
377 mm x 408 mm x 92 mm
2 x 7.2Ah/12V
CPR certified (1134-CPR-085)
1
HLSPS50
Power supply unit 24 VDC - 5A (2 x 2,2A)
Earth monitoring and fault relay input to disable the battery charger when the fire
panel is in alarm (providing 600mA extra current).
Specifications
• Weight: • Dimensions (W x H x D): • For battery type:
2
3
4
5.7kg
377 mm x 408 mm x 92 mm
2 x 17Ah/12V
5
CPR certified (1134-CPR-085)
6
The below items are available on request only. Please check the last price list for lead time information.
7
8
BF362-1
PSU24V-1,5A with charger
Power supply with battery charger for batteries up to 17Ah.
Housing inclusive power supply with space for 2 x 12V / 17Ah batteries.
Specifications
•
•
•
•
•
•
Input voltage: Output voltage: Operating temperature: Dimensions (W x H x D): Weight: For battery type:
230 V AC - 50/60 Hz
24 VDC - 1,5 A
5°C to +40°C
404 mm x 404 mm x 110 mm
approx. 5 kg
2 x 17Ah/12V
CPD number: 0786-CPD-20891; VDS number: G 209196
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
181
Accessories
Power Supplies
BF362-5
PSU24V-5A with charger
Power supply with battery charger for batteries up to 17Ah.
Housing inclusive power supply with space for 2 x 12V / 17Ah batteries.
Specifications
•
•
•
•
•
Output voltage: Operating temperature: Dimensions (W x H x D): Weight: For battery type:
24 VDC – 5A
5°C to +40°C
404 mm x 404 mm x 110 mm
approx. 5 kg
2 x 17A/12V
CPD number: 0786-CPD-20892; VDS number: G 209197
AES Series
The AES series is designed to supply electrical power for fire detection systems
approved to EN54-4/A8. The AES series is protected against lightning strikes and
short circuits.
A dynamic regulation stabilizes the output voltage and keeps it within the preset
tolerance range.
Elaborate filters eliminate all interferences and reduce the residual ripple from the
230 VAC mains.The status of the power device is locally displayed by leds and
remotely by means of dry contacts.
To preserve the capacity of batteries, their discharge is limited in conjunction with
automatic disconnection of the user circuit.
These units are both CPD and VDS approved.
NF Approved EN54-4/A8
The indicated power includes the battery charger consumption. Therefore, the total available power is 5% less (Exc. AES 28V 8A C85 SB).
C24 Box
AES 24V 3A C24 SB G
Power supply unit 24V - 3A
Specifications
• Dimensions (W x H x D): • Can hold up to 2 batteries: 322 mm x 248 mm x 126 mm
12Ah / 12V
CPR number: 0333-CPR-075230; VDS number: G209209
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
182
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Power Supplies
C38 Box
AES 24V 3A C38 SB G
Power supply unit 24V - 3A
Specifications
• Dimensions (W x H x D): • Can hold up to 2 batteries: 289 mm x 350 mm x 189 mm
24Ah / 12V
CPR number: 0333-CPR-075373; VDS number: G209209
1
AES 24V 4A C38 SB G
2
Power supply unit 24V - 4A
CPR number: 0333-CPR-075189; VDS number: G209026
AES 24V 6A C38 SB G
4
Power supply unit 24V - 6A
CPR number: 0333-CPR-075180; VDS number: G209036
5
6
C85 Box
AES 24V 8A C85 SB G
3
Power supply unit 24V - 8A
7
Specifications
• Dimensions (W x H x D): • Can hold up to 2 batteries:
8
408 mm x 408 mm x 224 mm
38Ah / 12V
CPR number: 0333-CPR-075220; VDS number: G210080
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
183
Accessories
Batteries
Batteries
VABO batteries
RB012AHB
1,2 Ah / 12V sealed lead acid battery
Specifications
• Dimensions (W x H x D): • Weight:
97 mm x 48 mm x 54 mm
570g
VDS number: G111062
RB022AHB
2,2 Ah / 12V sealed lead acid battery
Specifications
• Dimensions (W x H x D): • Weight:
178 mm x 34 mm x 60 mm
1.05kg
VDS number: G111063
RB040AHB
4.5 Ah / 12V sealed lead acid battery
Item available on request only. Please check the last price list for lead time information.
Specifications
• Dimensions (W x H x D): • Weight:
RB070AHB
90 mm x 70 mm x 102 mm
1.7kg
7.2 Ah / 12V sealed lead acid battery
Specifications
• Dimensions (W x H x D): • Weight:
VDS number: G114067
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
184
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
151 mm x 65 mm x 94 mm
2.650kg
Accessories
RB120AHB
Batteries
12 Ah / 12V sealed lead acid battery
Specifications
• Dimensions (W x H x D): • Weight:
151 mm x 98 mm x 98 mm
3.8kg
VDS number: G114068
RB180AHB
18 Ah / 12V sealed lead acid battery
Specifications
• Dimensions (W x H x D): • Weight:
1
181 mm x 76 mm x 167 mm
6.3kg
2
VDS number: G114069
3
4
RB260AHB
26 Ah / 12V sealed lead acid battery
5
Specifications
• Dimensions (W x H x D): • Weight:
166 mm x 175 mm x 125 mm
9.3kg
6
VDS number: G111066
7
8
RB450AHB
45 Ah / 12V sealed lead acid battery
Specifications
• Dimensions (W x H x D): • Weight:
198 mm x 166 mm x 171 mm
14.5kg
VDS number: G111067
RB650AHB
65 Ah / 12V sealed lead acid battery
Specifications
• Dimensions (W x H x D): • Weight:
350 mm x 166 mm x 174 mm
22.5kg
VDS number: G111104
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
185
Accessories
Batteries
YUASA batteries
NP2.3-12
2,3Ah / 12V valve regulated lead acid battery
Specifications
•
•
•
•
•
Dimensions (L x W x H ):
Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C:
178 mm x 34 mm x 64 mm
0.95kg
12V
2.3 Ah
2.1 Ah
VDS number: G101139
NP7-12
7Ah / 12V valve regulated lead acid battery
Specifications
•
•
•
•
•
Dimensions (L x W x H ): Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C:
151 mm x 65 mm x 97.5 mm
2.65kg
12V
7Ah
6.4 Ah
VDS number: G189099
NP12-6
12Ah / 6V valve regulated lead acid battery
Item available on request only. Please check the last price list for lead time information.
Specifications
•
•
•
•
•
Dimensions (L x W x H ): Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C:
151 mm x 50 mm x 97.5 mm
2.05kg
6V
12 Ah
11.1 Ah
VDS number: G194006
NP12-12
12Ah / 12V valve regulated lead acid battery
Specifications
•
•
•
•
•
Dimensions (L x W x H ): Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C: VDS number: G189170
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
186
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
151 mm x 98 mm x 97.5 mm
4.05kg
12V
12 Ah
11.1 Ah
Accessories
NP17-12
Batteries
17Ah / 12V valve regulated lead acid battery
Specifications
•
•
•
•
•
Dimensions (L x W x H ): Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C: 181 mm x 76 mm x 167 mm
6.1kg
12V
17 Ah
15.7 Ah
VDS number: G197022
NP24-12
24Ah / 12V valve regulated lead acid battery
1
Specifications
•
•
•
•
•
Dimensions (L x W x H ): Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C: 2
166 mm x 175 mm x 125 mm
9kg
12V
24 Ah
22.3 Ah
3
VDS number: G182026
NP38-12
4
38Ah / 12V valve regulated lead acid battery
5
Specifications
•
•
•
•
•
Dimensions (L x W x H ): Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C: 6
197 mm x 165 mm x 170 mm
14.2kg
12V
38 Ah
35.3 Ah
7
VDS number: G182024
NP65-12
8
65Ah / 12V valve regulated lead acid battery
Item available on request only. Please check the last price list for lead time information.
Specifications
•
•
•
•
•
Dimensions (L x W x H ): Weight:
Nominal voltage:
20-hr rate Capacity to 1.75VPC at 20°C:
10-hr rate Capacity to 1.75VPC at 20°C: 350 mm x 166 mm x 174 mm
23kg
12V
65 Ah
60.5 Ah
VDS number: G183008
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
187
Accessories
Electro Magnetic Door Holders
Electro Magnetic Door Holders
1330NEML-D
Electro magnetic lock - retaining strength 50kg
Equipped with cushioned counter plates. With protection diode against current
spikes. Nickel plated steel body; base in ABS; connection by wires.
Specifications
• IP rating: • Weight: • Power consumption: 1340NEML-D
IP40
480g
24 VDC/60mA
Electro magnetic lock - retaining strength 100kg
Equipped with cushioned counter plates. With protection diode against current
spikes. Nickel plated steel body; base in ABS; Wire terminals.
Specifications
• Weight: • IP rating: • Power consumption: 1335NEML
770g
IP40
24 VDC/100mA
Electro magnetic lock - retaining strength 50kg
Equipped with cushioned counter plates. With release button, Nickel plated steel
body & base in ABS. Connection to terminals - Unlock button.
Specifications
• Weight: • IP rating: • Power consumption: 1345NEML
550g
IP40
24 VDC/65mA
Electro magnetic lock- retaining strength 100kg
Equipped with cushioned counter plates. With release button and protection diode
against current spikes. Nickel plated steel body; base in ABS. Connection to
terminals - Unlock button.
Specifications
• Weight: • IP rating: • Power consumption: For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
188
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
760g
IP40
24 VDC/100mA
Accessories
1350NEML
Electro Magnetic Door Holders
Electro magnetic lock - retaining strength 25-50kg
Equipped with cushioned counter plates. Aluminium container - Nickel plated steel
body. Connection to terminals. Internal electronic circuit allows halving the retaining
strength. Unlock button. Protection diode against current spikes. Release button on
the container side.
Specifications
•
•
•
•
1360NEML
Weight: IP rating: Power consumption: Dimensions (W x H x D): 800g
IP40
24 VDC/60mA
95 mm x 95 mm x 40 mm
Electro magnetic lock - retaining strength 50-100kg
1
Equipped with cushioned counter plates Aluminium container, Nickel plated steel
body. Connection to terminals. Internal electronic circuit allows halving the retaining
strength. Protection diode against current spikes. Release button on the container
side.
2
3
Specifications
•
•
•
•
Weight: IP rating: Power consumption: Dimensions (H x W x D): 800g
IP40
24 VDC/60mA
95 mm x 95 mm x 40 mm
4
5
1369NEML
Electro magnetic lock - floor fitting - retaining strength 50kg
Equipped with cushioned counter plates. Supplied with release push-button.
7
Specifications
• Weight: • IP rating: • Power consumption: 1315NEML
6
800g
IP40
24 VDC/60mA
8
Electro magnetic lock - retaining strength 50kg
Original and aesthetically innovative design. Supplied with easily unlocking pushbutton. Equipped with cushioned counter-plates. Black thermoplastic material body.
Cable input on four sides. Nickel plated steel core. With protection diode against
current spikes.
Specifications
• Weight: • IP rating: • Power consumption: 800g
IP40
24 VDC/40mA
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
189
Accessories
Electro Magnetic Door Holders
1370/15D
Magnetic door release unit - retaining strength 50kg
The fixing bracket allows installation on floor, ceiling and wall. Nickel plated steel
coil; steel bracket; allodium support. Equipped with cushioned counter-plates. Wire
terminals; release button; 15 cm bracket. With protection diode against current
spikes.
Specifications
• Weight: • IP rating: 1370/30D
1.2kg
IP40
Magnetic door release unit
Same as item 1370/15 D but with a 30cm bracket.
1380/15D
Magnetic door release unit
Same as item 1370/15 D but with a retaining strength of 100kg and 100mA power
consumption.
1380/30D
Magnetic door release unit
Same as item 1380/15 D but with a 30cm bracket.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
190
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Fire Resistant Cables
Fire Resistant Cables
Halogen free sheated & shielded cable
Polyester/aluminium shield and 0,5mm² tinned copper drain.
Recommended for Morley-IAS intelligent loop installation. Flame non spreader, halogen free, low level of smoke emission and aggressively.
Reels of 500 meters.
2x1,5-LH-500
Twisted-shielded cable 2 wires 1,5mm²
2x2,5-LH-500
Twisted-shielded cable 2 wires 2,5mm²
Item available on request only. Please check the last price list for lead time information.
1
2
3
4
Halogen free sheathed & shielded fire resistant cable
Reels of 500 meters.
5
6
7
2x1,5-LHR-500
Twisted-shielded cable 2 wires 1,5mm² fire resistant
2x2,5-LHR-500
Twisted-shielded cable 2 wires 2,5mm² fire resistant
Item available on request only. Please check the last price list for lead time information.
8
Special communication cable
CSR485-100
Twisted-shielded cable 2 wires 1mm² - 100m
CSR485-500
The below items are available on request only. Please check the last price list for lead time information.
Reel of 100 meters.
Twisted-shielded cable 2 wires 1mm² - 500m
Reel of 100 meters.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
191
Accessories
Surge Protection Modules
Surge Protection Modules
All modules are modular and easy to fit on standard DIN rails. These kind of modules can avoid big damage to the fire panel and auxiliary
equipment in case of a lightning strike.
ZB24544
Surge protection module for 24V loop (use 1 loop, 2 channels)
ZB24518
Surge protection module for RS485 interface
ZB24578
Surge protection module for sounder output
Item available on request only. Please check the last price list for lead time information.
The below items are available on request only. Please check the last price list for lead time information.
MA05/D/2
Surge protection module 220V - up to 5A
MA10/D/2
Surge protection module 220V - up to 10A
MA15/D/2/SI
Surge protection module 220V - up to 15A
Manual Call Point Accessories
SC083
The below items are available on request only. Please check the last price list for lead time information.
Breakable cover seal for MCP (50 pcs)
CG2
Sold per pack of 50 pieces.
Nylon cable gland for IP55 AND IP67 call point
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
192
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Protective Accessories
Protective Accessories
Steel protective covers for detectors
Steel web stoppers are for areas were abuse to smoke detectors, emergency lighting
and so on, is severe. Constructed from plastic coated galvanised steel rod the
cages can cope with the severest of abuse from vandalism or accidental damage.
Installation and service is very easy with models for flush and surface mounting.
215 mm
210 mm
75 mm
108 mm
70 mm
150 mm
175 mm
155 mm
STI 9601
180 mm
STI 9604
215 mm
175 mm
95 mm
115 mm
110 mm
STI 9606
100 mm
STI 9605
1
125 mm
STI 9602
2
124 mm
78 mm
STI 9609
214 mm
3
4
145 mm
5
85 mm
STI 9610
6
STI 9601
Low profile, flush mounting 70 (h) x 210 ( ) mm
STI 9602
Low profile, surface mounting 108 (h) x 215 (Ø) mm
STI 9604
Low profile, flush mounting 75 (h) x 175 (Ø) mm
STI 9605
Low profile, surface mounting 115 (h) x 180 (Ø) mm
STI 9606
Low profile, flush mounting 95 (h) x 175 (Ø) mm
STI 9609
High profile, flush mounting 124 (h) x 215 (Ø) mm
STI 9610
High profile, surface mounting 145 (h) x 214 (Ø) mm
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
193
Accessories
Protective Accessories
Protective covers for beam detectors
325 mm
140 mm
225 mm
195
mm
244
mm
120
mm
TOP VIEW SIDE VIEW
STI 9625
83 mm
TOP VIEW FRONT VIEW
STI 9624
140
mm
120
mm
237 mm
244 mm
275 mm
262 mm
280 mm
50 mm
262 mm
102 mm
FRONT VIEW SIDE VIEW STI 9706 STI 9706
FRONT VIEW STI 9707
SIDE VIEW
STI 9707
170 mm
100
mm
146 mm
91 mm
293
mm
56 mm
256 mm
84
mm
168 mm
130 mm
TOP & SIDE VIEW TOP VIEW
STI 9841
STI 9624
37 mm
75 mm
TOP VIEW
STI 9840
The below items are available on request only. Please check the last price list for lead time information.
Detector guard 225 (h) x 140 (w) x 120 (d) mm
This guard is, for instance compatible with FireRay 50/100 beam detectors.
STI 9625
Beam detector guard 260 (h) x 195 (w) x 325 (d) mm
STI 9706
Beam detector guard 275 (h) x 237 (w) x 120 (d) mm
This guard is, for instance compatible with 6500, MI-LPB2(-S2I) beam detectors.
STI 9707
Surface mount beam detector guard 280 (h) x 244 (w) x 140 (d) mm
This guard is, for instance compatible with 6500, MI-LPB2(-S2I) beam detectors in
surface mount.
STI 9841
Beam detector guard 293 (h) x 256 (w) x 91 (d) mm
This guard is, for instance compatible with the FIRERAY 5000 System Controller.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
194
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
STI 9840
Protective Accessories
Beam detector guard 168 (h) x 168 (w) x 146 (d) mm
This guard is, for instance compatible with the FIRERAY 5000 motorised detector.
OSID-WG
Wire guard for OSID Imager and Emitter
Protective guard for OSID imager and emitter. The guard is plastic coated for
durability and use in harsh environments. It protects the emitter and imager against
vandalism or accidental damage.
Specifications
• Dimensions:
104 mm x 167 mm x 234 mm
1
Steel Protective Covers for MCP
Protective cover to help stop malicious or accidental false fire alarms.
This unique device has been helping stop false fire alarms around the world for
decades, without restricting legitimate operation of devices such as fire alarm break
glass call points. It is ideal for schools, colleges, hospitals, nursing homes, hotels
and all public buildings where there is a threat of false fire alarms.
The Stopper consists of a clear, tamper-proof, tough polycarbonate cover and frame
that fits over the break glass call point. When lifted to gain access to the break glass,
its optional battery powered integral sounder emits a piercing 120 dB. Immediate
attention is drawn to the area and a prankster will either run or be caught.
•
•
•
•
•
•
•
•
Constructed from tough clear polycarbonate.
Protects equipment from accidental operation, vandalism, product misuse, dust and weather.
Available with or without integral sounder.
Integral sounder powered by a 9V PP3 battery (included).
Available for flush or surface mounted products.
Lock or break seal options for added security.
Weather proofing available with a choice of gaskets.
Optional depth spacers to accommodate a wider variety of products.
Please replace “n” in the part n° by the code for the needed language:
N = Dutch; F = French; E = Englisch; D = German; I = Italian
The below items are available on request only. Please check the last price list for Lead time information.
2
3
4
5
6
7
8
STI 6530/n
Stopper flush mounted without sounder
STI 6531/n
Stopper surface mounted without sounder
STI 6532/n
Stopper flush mounted with sounder
STI 6533/n
Stopper surface mounted with sounder
STI 6534/n
Weather stopper flush mounted without sounder
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
195
Accessories
Protective Accessories
STI 6535/n
Weather stopper surface mounted without sounder
Cover to protect against the ingress of dust or water. The Weather Stopper is a
protective cover that is ideal for extending the life and reliability of weather exposed
devices, such as manual call points. It offers protection against harsh environments
and conditions both outside and inside, as well as preventing tampering, vandalism
and damage from accidental operation.
Easy to install, the Weather Stopper consists of a clear, tamper-proof, tough polycarbonate cover, frame and weather gasket that fits over the manual call point. The
weather gasket seals the unit, preventing dust, grime and water from getting to the
device. In the event of an emergency, simply lift the cover to gain access to the
protected device.
•
•
•
•
•
•
•
•
Strong, durable cover to take even the severest of knocks.
Protects equipment against damage, dust and grime as well as water ingress.
A variety of cable entry gaskets are available.
Ideal in saline atmospheres.
Optional depth spacers to accommodate a wider variety of products.
Available for flush or surface mounted products.
Available in red, yellow, green and blue.
Lock or break seal options for added security.
For Green, Blue or Yellow add /G, /B, /Y
Options : extra cost
/BS
Security break seal (to be ordered along with the stopper)
CKS002
Break seal conversion kit
STI/BS
This kit contains: 1 retainer, 2 break seals, instructions.
Breakable seals
/L
Pack of 10 pieces.
Frangible lock
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
196
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Protective Accessories
Steel protective covers for Audio & Visual Devices
108 mm
125 mm
171 mm
FRONT VIEW
STI 9617
STI 9617
150 mm
BOTTOM VIEW
STI 9617
146
mm
SIDE VIEW END VIEW
STI 9621 STI 9621
The below items are available on request only. Please check the last price list for lead time information.
1
Protective cover 150 (Ø) x 125 (h) mm
This guard is, for instance compatible with the intelligent audio & visual devices.
2
STI 9621
Protective cover 171 (h) x 146 (w) x 108 (h) mm
This guard is, for instance compatible with the old (NX/NS) audio & visual devices.
3
4
Steel protective covers for signalling panels
372 mm
100 mm
65 mm
270 mm
273 mm
6
340 mm
TOP VIEW SIDE VIEW
STI 9640 STI 9640
TOP VIEW SIDE VIEW
STI 9641 STI 9641
7
550 mm
245 mm
150 mm
350 mm
245 mm
570
mm
5
STI 9649
8
TOP VIEW SIDE VIEW
STI 9645 STI 9645
The below items are available on request only. Please check the last price list for lead time information.
STI 9640
Exit light guard 270 (h) x 340 (w) x 65 (d) mm
STI 9641
Exit light guard 273 (h) x 372 (w) x 100 (d) mm
STI 9645
Exit light guard 350 (h) x 550 (w) x 150 (h) mm
STI 9649
Exit light guard 245 (h) x 570 (w) x 245 (h) mm
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
197
Accessories
Detector Test Equipment
Detector Test Equipment
25E smoke detector tester
HSI-25E
Smoke detector tester
Compatible with HSI-1490-1 delivery tube.
150ml - Flammable canister.
AITA Rules for Air Freight: UN 1950 Class 2.1 No subsidiary risk.
Box of 12 cans.
Please note that next to the standard freight charge a special ADR cost will be charged following the transportation safety regulations for flammable or dangerous products.
25E smoke detector tester accessories
HSI-1490-1
18” Fiberglass Delivery Tube for 25E
Compatible with HSI-25E
Length of 45cm
SDT series smoke detector testers
SDT150-12
Smoke detector testers
Handheld unit for functional testing of smoke detectors.
150 ml - Non flammable canister.
SDT250-12
Box of 12 cans.
Smoke detector testers
For use with Solo 330 smoke dispenser.
Not suitable for handheld use.
250ml - Non flammable canister.
Box of 12 cans.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
198
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
SOLO A7
Detector Test Equipment
Detector duster
For cleaning smoke detectors.
250ml - non flammable canister.
SDT150-S-12
Box of 12 cans.
Smoke Sabre
1
Smoke detector tester for handheld use.
Telescopic smoke dispenser included per can.
150 ml - UL listed - Flammable canister.
2
Box of 12 cans.
Please note that next to the standard freight charge a special ADR cost will be charged following the transportation safety regulations for flammable or dangerous products. 3
4
5
SDT series smoke detector tester accessories
6
SOLO 810
Smoke detector test starter pack 2,5 m
Includes:
1 x Solo 101 fibreglass extension pole - 1,13m
1 x Solo 330 aerosol smoke dispenser
7
8
SOLO 808
Smoke detector test starter pack 4 m
SOLO 809
Includes:
1 x Solo 108 fibreglass extension pole - 2,5m
1 x Solo 330 aerosol smoke dispenser
Smoke detector test starter pack 6 m
Includes:
1 x Solo 100 fibreglass telescopic extension pole - 4,5m
1 x Solo 330 aerosol smoke dispenser
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
199
Accessories
Detector Test Equipment
SOLO 811
Smoke detector test & removal set 6 m
Includes:
1 x Solo 100 fibreglass telescopic extension pole - 4,5m
1 x Solo 200 universal removal tool
1 x Solo 330 aerosol smoke dispenser
1 x Solo 610 protective carrying/storage bag
Item available on request only. Please check the last price list for lead time information.
SOLO 814
Smoke & mains heat detector test set 6 m
Includes:
1 x Solo 100 fibreglass telescopic extension pole - 4,5m
1 x Solo 200 universal removal tool
1 x Solo 330 aerosol smoke dispenser
1 x Solo 424 240V heat detector tester
1 x Solo 610 protective carrying/storage bag
Item available on request only. Please check the last price list for lead time information.
SOLO 822
Smoke & cordless heat detector test set 6 m
Includes:
1 x Solo 100 fibreglass telescopic extension pole - 4,5m
1 x Solo 200 universal removal tool
1 x Solo 330 aerosol smoke dispenser
1 x Solo 461 cordless heat detector test set
1 x Solo 610 protective carrying/storage bag
SOLO 610
Protective carrying storage bags
SOLO 101
Fiberglass extension pole - 1,13m
Reach of 2,5 m including height of man.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
200
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
SOLO 108
Detector Test Equipment
Fiberglass 2 section telescopic pole - 2,5m
Reach of 4 m including height of man.
SOLO 100
Fiberglass 4 section telescopic pole - 4,5m
Reach of 6 m including height of man.
SOLO 713-001
Adapter tool 713
Adapter for connection of ECO1000DRT.
Compatible with Solo poles. Incl. magnet tester.
1
2
3
SOLO 200
Universal detector removal tool
Detector removal tool which is compatible with most types of fire detectors.
4
5
6
SOLO 330
Aerosol smoke dispenser
7
Economic and easy for testing smoke detectors.
For use with SOLO 100 poles.
8
SOLO 424
Heat detector tester 220V-240V
Complete with 5m cable.
SOLO 461
Cordless heat detector tester set
Includes :
1 x Solo 460-001 cordless heat unit
2 x Solo 760-001 NIMH battery baton
1 x Solo 725-001 fast charger
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
201
Accessories
Detector Test Equipment
Testifire units
TESTIFIRE 1001-001
Testifire 1001-001 smoke/heat kit
TESTIFIRE 6001-001
Includes:
1 x Testifire 1000-001 head unit
1 x TS3-001 smoke capsule
2 x Solo 760 NIMH battery baton
1 x Solo 725-001 fast charger
Testifire 6001-001 smoke/heat kit 6 m
TESTIFIRE 9001-001
Includes:
1 x Testifire 1000-001 head unit
1 x TS3-001 smoke capsule
2 x Solo 760-001 NIMH battery baton
1 x Solo 725-001 fast charger
1 x Solo 100-001 fibreglass telescopic access pole 4.5 m
1 x Solo 200-001 universal detector removal tool
1 x Solo 610-001 protective carrying / storage bag
Testifire 9001-001 smoke/heat kit 9 m
Includes:
1 x Testifire 1000-001 head unit
1 x TS3-001 smoke capsule
2 x Solo 760-001 NIMH battery baton
1 x Solo 725-001 fast charger
1 x Solo 100-001 fibreglass telescopic access pole 4.5 m
3 x Solo 101-001 fibreglass extension pole 1.13m
1 x Solo 200-001 universal detector removal tool
1 x Solo 610-001 protective carrying / storage bag
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
202
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
TESTIFIRE 2001-001
Detector Test Equipment
Testifire 2001-001 smoke/heat/CO kit
Includes:
1 x Testifire 2000-001 head unit
1 x TS3-001 smoke capsule
1 x TC3-001 CO capsule
2 x Solo 760-001 NIMH battery baton
1 x Solo 725-001 fast charger
1
2
TESTIFIRE 6201-001
Testifire 6201-001 smoke/heat/CO kit 6 m
Includes:
1 x Testifire 2000-001 head unit
1 x TS3-001 smoke capsule
1 x TC3-001 CO capsule
2 x Solo 760-001 NIMH battery baton
1 x Solo 725-001 fast charger
1 x Solo 100-001 fibreglass telescopic access pole 4.5 m
1 x Solo 200-001 universal detector removal tool
1 x Solo 610-001 protective carrying / storage bag
3
4
5
6
TESTIFIRE 9201-001
Testifire 9201-001 smoke/heat/CO kit 9 m
Includes:
1 x Testifire 2000-001 head unit
1 x TS3-001 smoke capsule
1 x TC3-001 CO capsule
2 x Solo 760-001 NIMH battery baton
1 x Solo 725-001 fast charger
1 x Solo 100-001 fibreglass telescopic access pole 4.5 m
3 x Solo 101-001 fibreglass extension pole 1.13m
1 x Solo 200-001 universal detector removal tool
1 x Solo 610-001 protective carrying / storage bag
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
203
Accessories
Detector Test Equipment
Testifire replacement capsules
TS3-3PACK-001
Replacement smoke capsule
Up to 900 tests per capsule!
TS3-001
Pack of 3 capsules
Replacement smoke capsule
Up to 900 tests per capsule!
TC3-3PACK-001
Pack of 6 capsules
Replacement CO capsule
Up to 900 tests per capsule!
Pack of 3 capsules
Testifire accessories
TESTIFIRE 25
IR controller for Testifire
The remote control for Testifire is required for situations where the IR test beam of
Testifire that triggers or stops a test is not broken by a physical presence. Typical
situations are the sampling ports of aspirating detection systems or detectors with
‘virtual chambers’. The Testifire 25 is then used to initiate the test procedure.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
204
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Detector Test Equipment
System Sensor test equipment Series
ECO1000 DRT
Detector removal tool for ECO1000 detectors
Compatible with SOLO 100 pole series by SOLO 713-001 adapter.
Item available on request only. Please check the last price list for lead time information.
1
ECO1000 RTU
2
Remote laser test unit
The unit transmits a coded message, preventing spurious alarms being generated
by other laser-based devices. With a range of several metres, the handheld test
unit provides an effortless way of remotely alarm testing the range of ECO1000
detectors and removes the need for any direct physical access to the detector by
the user.
3
4
5
M02-04-00
Test magnet
6
For all Series Detectors except ECO series. Activates internal reed switch to give
alarm.
Item available on request only. Please check the last price list for lead time information.
7
8
POL-100 Portable Loop Polling Tool
Compatible with Morley-IAS loop protocol.
The POL-100 is designed to help the technician for the intelligent loop commissioning.
The POL-100 is equipped with a blue backlit display and removable terminals. It is
powered via batteries.
The POL-100 displays :
- Resistance between loop wires & wires and earth
- Voltage on the loop
- Identification of devices (auto-learn)
- Eventually, the double or missed address
- PW value of each detector
It is also able to register informations of a device for later diagnostic.
POL-100
Polling tool
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
205
Accessories
Detector Test Equipment
Scorpion® Tester for Aspirating systems & Point detectors
Scorpion ® ASD is a unique, functional remote smoke detector test system for
Aspirating Smoke Detection (ASD) Systems, and offers an approved, benign
and effectively non-contaminating test particulate delivered in a controlled and
repeatable manner.
Specifications
• ASD particle lifetime:
• Testing capacity:
•
•
•
•
Suitable for 120sec / 100m pipe runs
Up to 240 tests of 15 seconds of smoke per Scorpion
Improved access benefits
Time and cost saving benefits
Up to 8 Scorpion heads (ASD or Point) connected to a single Control panel
Battery powered
SCORP 8000-001
Scorpion control panel (Incl. mounting box)
SCORP 2001-001
Scorpion ASD head unit kit
SCORP 1001-001
Scorpion point detector head unit kit
SCORP 7000-001
Item available on request only. Please check the last price list for lead time information.
Scorpion portable controller
Includes SCORP 60 battery cable for SOLO 760 and SPARE 1054 control cable to
access point.
SCORP 25-001
Item available on request only. Please check the last price list for lead time information.
Scorpion access point
For use with SCORP 7000 portable controller (one required per head unit).
Item available on request only. Please check the last price list for lead time information.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
206
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Detector Test Equipment
Scorpion® Tester accessories
SCORP 50-001
Scorpion battery pack, NiMH rechargeable nominal 7.2V/2.2Ah
SCORP 60-001
Item available on request only. Please check the last price list for lead time information.
Scorpion battery cable, for connecting SOLO 760 battery batton to Scorpion Control Panel
1
Item available on request only. Please check the last price list for lead time information.
2
3
SOLO 726-101
4
Solo battery batton, NiMH rechargeable nominal 7.2V/2.2Ah
Item available on request only. Please check the last price list for lead time information.
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
207
Accessories
Detector Test Equipment
Test Equipment for Sagitarius wireless system
SGSK100
Item available on request only. Please check the last price list for Lead time information.
Test kit for Sagittarius wireless system
Wireless keypad
Test device
Radio interface
module
Programming lead
Carriage case
For SAGITTARIUS series wireless detectors.
Compatible with SOLO 100 pole series using SOLO 713-001 adapter.
Complies to EN 54-25.
The SGSK100 is composed of the following elements:
1. A carrying case.
2. A pair of carrying case’s keys.
3. A test device.
4. A test device’s adaptor base.
5. A battery for the test device: CR123A (3 V & 1.2 Ah).
6. A holding pole for the test device.
7. A radio interface module.
8. A power supply transformer unit for the radio interface.
9. A wireless keypad.
10. An ER9V battery for the wireless keypad (9 V & 1.2 Ah).
11. A programming lead for wireless keypad and radio interface connection.
12. A CD containing the wireless system configuration program (Wirelex) for the PC.
SG-DRT
Detector head removal tools
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
208
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Detector Test Equipment
Flame detector testers
Specially designed to use with the 20/20 series.
Based on a emitting of electromagnetic radiation recognized by the specific flame
detectors.
Allows to test detectors under real conditions without the associated risks of an
open flame.
The simulators use NiCd batteries as a rechargeable power source.
Possibility to add a collimator to extend the range of application.
Item available on request only. Please check the last price list for lead time information.
Did you know that Honeywell Fire Safety also offers to possibility to rent some of these fire simulators. Please consult the latest version of the price list for more information.
1
2
20/20-310
Fire simulator for triple IR flame detectors
Can be used to test 20/20I, 20/20XI, 20/20SI, 20/20MI, 20/20FI, 20/20CTIN and
CTIP.
20/20-311
Fire simulator for UV/IR flame detectors
Can be used to test 20/20L-LB, 20/20ML, 20/20F, 20/20U-UB and 20/20MU.
20/20-312
Fire simulator for single IR flame detectors (20/20R and 20/20MR).
20/20-313
Fire simulator for hydrogen flame detectors
Can be used to test 20/20H, 20/20SH and 20/20MH.
20/20-190
Collimator for 20/20 simulators
3
4
5
6
7
8
NEW
FS-1100
Tester for flame detectors
The FS-1100 FLAME SIMULATOR is the essential complimentary tool to the selftesting capabilities of your Sharpeye™ IR3 Flame Detectors. It brings fire prevention
safety to a higher level by giving you the ability to fully test the operational readiness
of your entire fire detection system.
The robust and reliable FS-1100 Flame Simulator allows remote testing of flame
detectors, which are often located in difficult to access and/or classified hazardous
areas (Zone 1, Zone 21).
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
209
Accessories
Detector Test Equipment
Tester for RIV flame detectors
PTL611
Portable test lamp for RIV IR flame detector
The PTL-611 portable test lamp is a plastic explosion-proof shock-proof and antistatic torch lamp with high intensity light which is modulated at a frequency of
23Hz so as to be used for external testing of RIV-601/F IR flame detectors, as an
alternative to the internal test feature built-in inside these detectors.
The working distance is over 10 meters, normally adequate for most common
applications.
The portable test lamp is powered by 2 non rechargeable alkaline batteries size D
(LR20) with an autonomy of more than 20 hours.
The lamp is turned on by a slide switch on the side.
The light beam aperture is about 3 degrees.
Specifications
•
•
•
•
•
•
•
•
•
•
Krypton bulb lamp: Light beam aperture: Modulation:
Operating distance from detector: Type of batteries:
IP rating:
Explosion-proof: Operating temperature: Dimensions: Weight: For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
210
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
2.4V – 0.5A
About 3 degrees
By 50% pulses (50% on, 50% off) with 23Hz frequency
Over 10 meters
2 non rechargeable alkaline batteries size D (LR20), autonomy of more than 20 hours, included.
IP67
Ex II 2GD T80°C EEx eib IIC T4
(ATEX zone 1 and zone 2 gas, zone 21 and zone 22 dust)
-20°C +55°C
200 mm x 85 mm x 60 mm
600 grams with batteries and case (net without batteries 240 grams).
Accessories
Gas Detector Test Equipment
Gas Detector Test Equipment
Z-CAL-COM
The below items are available on request only. Please check the last price list for lead time information.
Gas detector calibration kit - combustible detectors
The test kit includes the following items:
1 x Z-02000-A1645 calibration gas flow housing Signalpoint & Sensepoint
1 x Z-REG-0.30 pre-set flow regulator
1 x Z-SPPPTUB tygon tube
1 x Z-GasCH4-22-AIR-34 2,2%VOL methane in cylindre
1 x Z-2302D0765 Case for storing the above products
1
Z-CAL-CO
Gas detector calibration kit - CO gas detectors
The test kit includes the following items:
1 x Z-02000-A1645 calibration gas flow housing Signalpoint & Sensepoint
1 x Z-REG-0.30 pre-set flow regulator
1 x Z-SPPPTUB tygon tube
1 x Z-GasCO-250-AIR-34 250ppm carbon monoxide in cylinder
1 x Z-2302D0765 case for storing the above products
2
3
4
Z-02000-A1645
Calibration gas flow housing for Signalpoint & Sensepoint
Z-SPPPCAL
Calibration cup for Sensepoint Pro & Plus
Z-REG-0.30
Pre-set 0,3l/m flow regulator
Z-SPPPTUB
1m tygon tubing (suitable for all gases)
Z-2302D0765
Case for up to 2x2 alu. gas cylinders, regulator, tubing
Z-GasCH4-22-AIR-34
2,2%Vol. Methane in air (EU=50% LEL, US=44% LEL)
Z-GasO2-209-N2-34
20,9%Vol Oxygen in N2 (compressed air)
Z-GasCO-250-AIR-34
250 ppm Carbon monoxide in air
Z-GasNH3-25-AIR-34
25 ppm Ammonia in air
Z-GASNH3-300-AIR-34
300 ppm Ammonia in air
Z-GASCO-100-AIR-34
100 ppm Carbon monoxide in air
Z-GASH2S-10-AIR-34
10 ppm H2S in air
Single gas cylinder (34 L) - Approximately 30 Calibrations.
Please note that next to the standard freight charge a special ADR cost will be charged following the transportation safety regulations for flammable or dangerous products. This means a fix amount per shipment will be invoiced whenever a flammable smoke detector tester class 2.1 UN1950 will be shipped.
Till 20 box, this amount will be 10 euro per shipment.
For more than 20 boxes, 35 euro will be invoiced.
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
211
Accessories
Gas Detector Test Equipment
Calibration & Installation Tools
All SENSITRON gas detectors are factory calibrated prior to despatch. In order
to fulfil the EN60079–17:2003, detectors have to undergo periodical operational
testing, each three to six months according to the plant’s risk assessment. Test
results are to be recorded into a suitable book to be shown to the Authority in case
of inspection.
In environments where polluting elements might alter the original sensor
performances, periodical testing should be carried out at shorter time intervals.
All tests should be carried out by employing a specific gas mixture, according to the
manufacturer's advice.
The calibration carrying case has place for 2 sample gas bottles and comprises
one flow indicator, hose and adaptors. On request, this calibration gas kit can be
equipped with portable gas detectors available for different gases and ranges.
VTX+XA
The below items are available on request only. Please check the last price list for lead time information.
Calibration gas case
SI.B/XXX
Calibration gas case including one flow indicator, hose and adaptor.
(Calibration gas cylinders not included).
Disposable gas cylinders; 50% LEL
Disposable gas cylinders filled with either flammable or toxic non reactive gas
mixtures.
Dangerous goods: ADR/RID UN 2037, Class 2, Packing instructions 203.
SG.B/XXX
At the order please specify the gas type.
Disposable gas cylinders, 50% LEL
Disposable gas cylinders filled with reactive gas mixtures.
Dangerous goods: ADR/RID UN 1956, Class 2.
PC.VALVOLA
At the order please specify the gas type.
Flow-meter valve
Flow-meter valve to be mounted on the gas cylinder to set the gas flow.
ZMCAP/123Adapter
Adapter for all of Sensitron gas detectors.
Made anodized alloy, it allows the right quantity of gas inlet to flow to the detector.
It comes complete with adapters to fit on the detectors' heads.
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
212
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Accessories
Spare Parts
Spare parts
Part number
Description
Spare part for:
MOD45R
Replacement cord for MOD400R
MOD400R
SOLO 460-001
Cordless heat detector head unit only
Test Equipment
SOLO 726-101
220/240V Mains & car charger
Test Equipment
SOLO 760-001
Nimh battery baton
Test Equipment
SPARE 1002
Pair of transparent grips for Solo 200
Test Equipment
SPARE 1005
Silicone membrane for Solo300
Test Equipment
SPARE 1049
Membrane ring for testifire
Test Equipment
SPARE 1028
Aerosol retaining cup
Test Equipment
1
2
3
4
5
6
7
8
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
213
Accessories
Notes
For spare parts, please refer to § Spare Parts at the end of this chapter (06. Accessories)
214
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Residential Smoke
and Gas Detection
Domestic Fire Detection
Notes
216
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Domestic Fire Detection
X-Series Alarms
NEW
X-Series Fire Alarms (Availability will be announced)
Battery powered Fire Alarms
The Honeywell range of smoke and heat alarms has been engineered for ultimate
performance and reliability. Featuring a ten year lifespan and warranty; low profile
design; and easy installation, they are ideal for professionals dealing with residential
fire detection.
All X-Series alarms can be interconnected wirelessly for increased safety by using
the wireless plug-in module XW100. Honeywell’s - X-Series alarms are available as
a complete range of fire and Carbon Monoxide solutions.
1
• High reliability
• Sealed housing to protect from adverse environmental conditions
• Automatic self-test every month
• Dirt compensation
• Tamper-proof
• Designed for residential environments
• Low total cost of ownership, 10 year warranty
• Easy to operate and use by end-user
• Easy to install
• Interconnectivity with snap-in wireless module (optional)
Specifications
• Operating temperature:
• Relative humidity:
• IP rating:
• Power supply:
• Visual indicators (LED):
• Audible indicator:
• Button:
• Dimensions (Ø x H):
• Weight:
0°C - +40°C
25-93% (non condensing)
IPX2D
Long-life lithium battery, 3V, sealed-in
Power: green; Alarm: red (big surface); Fault: yellow
>85dB @ 3m, Distinct “Fire” alarm sound
Test with reduced sound level; Alarm hush; Fault hush (24h)
125 mm x 41 mm
185 g
2
3
4
5
Approvals:
VdS Q-label
6
XH100
Heat Alarm
XS100
Optical Smoke Alarm
XS100T
Optical Thermal Smoke Alarm
7
8
Accessories
XW100
Wireless Module
217
Domestic Fire Detection
X-Series Alarms
Mains powered fire alarms
The Honeywell range of smoke and heat alarms has been engineered for ultimate
performance and reliability. Featuring a ten year lifespan and warranty; low profile
design; and easy installation, they are ideal for professionals dealing with residential
fire detection.
All X-Series alarms can be interconnected wirelessly for increased safety by using
the wireless plug-in module XW100.
Specifications
• High reliability
• Sealed housing to protect from adverse environmental conditions
• Automatic self-test every month
• Dirt compensation
• Tamper-proof
• Designed for residential environments
• Low total cost of ownership, 10 year warranty
• Easy to operate and use by end-user
• Easy to install
• Equipped with a terminal and a back-up battery
• Interconnectivity with snap-in wireless module (optional)
• Operating temperature:
• Relative humidity:
• IP rating:
• Power supply:
• Visual indicators (LED):
• Audible indicator:
• Button:
• Dimensions (Ø x H):
• Weight:
Approvals:
VdS Q-label
XHM100
Heat Alarm
XSM100
Optical Alarm
XS100T
Optical Thermal Smoke Alarm
Accessories
XW100
218
Honeywell | Fire Safety
Wireless Module
Benelux region
Catalogue version 2.1
0°C - +40°C
25-93% (non condensing)
IPX2D
240VAC
Power: green; Alarm: red (big surface); Fault: yellow
>85dB @ 3m, Distinct “Fire” alarm sound
Test with reduced sound level; Alarm hush; Fault hush (24h)
125 mm x 41 mm
185 g
Domestic Fire Detection
X-Series Alarms
NEW
X-series Carbon Monoxide Alarms
Battery powered Carbon Monoxide Alarms
The Honeywell range of smoke and heat alarms has been engineered for ultimate
performance and reliability. Featuring a ten year lifespan and warranty; low profile
design; and easy installation, they are ideal for professionals dealing with residential
fire detection.
All X-Series alarms can be interconnected wirelessly for increased safety by using
the wireless plug-in module XW100. Honeywell’s - X-Series alarms are available as
a complete range of fire and Carbon Monoxide solutions.
1
Specifications
•
•
•
•
•
•
Reliable fast detection with sealed tamper proof unit
Fast simple installation with snap fit base
and auto activation
Excellent lifetime value
Minimum maintenance with no need for battery replacement
Discrete appearance and hidden LEDs
Interconnectivity with snap in wireless module (optional)
• Operating temperature:
• Relative humidity:
• IP rating:
• Power supply:
• Visual indicators (LED):
• Audible indicator:
• Button:
• Dimensions (Ø x H):
• Weight:
0°C - +40°C
25-93% (non condensing)
IPX2D
Long-life lithium battery, 3V, sealed-in
Power: green; Alarm: red (big surface); Fault: yellow
>85dB @ 3m, Distinct “Fire” alarm sound
Test with reduced sound level; Alarm hush; Fault hush (24h)
125 mm x 41 mm
185 g
2
3
4
5
Approvals:
VdS Q-label
6
XC70
CO Alarm - 7 year life and warranty
XC100
CO Alarm with alarm message - 10 year life and warranty
XC100D
CO Alarm with alarm message and multifunction CO level display - 10 year life and warranty
7
8
Accessories
XW100
Wireless Module
219
Domestic Fire Detection
X-Series Alarms
Mains powered Carbon Monoxide Alarms
The Honeywell range of smoke and heat alarms has been engineered for ultimate
performance and reliability. Featuring a ten year lifespan and warranty; low profile
design; and easy installation, they are ideal for professionals dealing with residential
fire detection.
All X-Series alarms can be interconnected wirelessly for increased safety by using
the wireless plug-in module XW100. Honeywell’s - X-Series alarms are available as
a complete range of fire and Carbon Monoxide solutions.
Specifications
•
•
•
•
•
•
• Operating temperature:
• Relative humidity:
• IP rating:
• Power supply:
• Visual indicators (LED):
• Audible indicator:
• Button:
• Dimensions (Ø x H):
• Weight:
Reliable fast detection with sealed tamper proof unit
Fast simple installation with snap fit base
and auto activation
Excellent lifetime value with 10 year life and warranty
Minimum maintenance with no need for battery replacement
Discrete appearance and hidden LEDs
Interconnectivity with snap in wireless module (optional)
0°C - +40°C
25-93% (non condensing)
IPX2D
240VAC
Power: green; Alarm: red (big surface); Fault: yellow
>85dB @ 3m, Distinct “Fire” alarm sound
Test with reduced sound level; Alarm hush; Fault hush (24h)
125 mm x 41 mm
185 g
Approvals:
VdS Q-label
XCM100
CO Alarm with alarm message
XCM100D
CO Alarm with alarm message and multifunctions CO level display
Wireless plug-in module XW100
XW100
Wireless plug-in module for X-series
All X-Series alarms can be interconnected wirelessly for increased safety by using
the wireless plug-in module XW100.
220
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Index
Index
Notes
222
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Index
Reference
Page
Symbols
/BS196
/L196
002-43951
020-600-002 18
020-71356
020-74756
020-77256
020-82051
020-83651
020-891
12, 17, 51
020-90912
020-91012
02-FL53156
02-FL56156
02-WT-01120
124-19651
1315NEML189
1330NEML-D188
1335NEML188
1340NEML-D188
1345NEML188
1350NEML189
1360NEML189
1369NEML189
1370/15D190
1370/30D190
1380/15D190
1380/30D190
20/20-005154
20/20-190209
20/20-310209
20/20-311209
20/20-312209
20/20-313209
20/20-787154
20/20-794079-3154
20/20MI-1-1-F153
20/20MI-3-1-F153
20/20MPI-R154
20-LA00015-03156
2351E62
2x1,5-LH-500191
2x1,5-LHR-500191
2x2,5-LH-500191
2x2,5-LHR-500191
40/40-001154
40/40-777163155
40/40-777166155
40/40-777650155
40/40-777820155
40/40-777910155
40/40-789260-1155
40/40-789260-2155
40/40-794079-5155
40/40-A0000231155
40/40-ADD-85154
40/40-ADD-ST154
40/40-I151
40/40-L150
40/40-L4151
40/40-L4B151
40/40-LB151
40/40-M151
40/40-R151
40/40-U150
40/40-UB150
510-FIN118
510-KIT117
520-MTS-80R118
6500R64
6500RS64
709-601-001 17
709-701-001 18
Reference
Page
7100X107
714-001-11311
714-001-21311
714-001-22311
714-001-24312
720-001-302 14
721-001-302 14
722-001-302 13
795-004-001 17
795-00517
795-014 18
795-015 18
795-029 18
795-038-001 17
795-04551
795-051-00151
795-057 19
795-060-00219
795-06316
795-064 16
795-065 19
795-07251
795-072 14
795-072-100 14
795-077-020 15
795-077-060 15
795-08351
795-08451
795-08551
795-09912
795-10112
795-10212
795-10451
795-10651
795-10751
795-108-00351
795-109-00351
795-109-00451
795-110-00351
795-11112
795-11212
795-11312
795-11412
795-11512
795-11612
795-11812
795-11912
795-12012
795-12112
795-12212
795-12412
795-13012
795-13113
795-13213
796-04551
796-15051
796-15151
796-15251
796-15351
796-15751
796-15851
796-16151
796-16251
796-16351
796-164-00051
796-17051
796-17151
796-17551
796-17651
796-17751
796-17851
796-18051
796-18151
796-18251
Reference
Page
796-18351
796-18451
796-855-M20051
797-02151
797-061 15
797-062 15
797-063 15
797-064 16
797-07616
797-07716
797-078 17
797-09013
8100E-BNL104
9400X103
A
A0865898
A0866098
A08660-W98
A0866498
A08664-W98
A0866698
A08666-W98
A0866798
A08667-W98
A0866898
A08668-W98
A0866998
A0867098
A08670N97
A08670N-W98
A0867198
A08671N97
A08671N-W98
A08671-W98
A0867298
A08672N97
A08672N-W98
A08672-W98
A0867398
A0867498
A0867598
A0867698
A5055 SS
97
A5555 SS
97
ABS 001/25
113
ABS 001/25-WH
115
ABS 002/25
113
ABS 002/25-WH
115
ABS 003/25
113
ABS 003/25-WH
115
ABS 004
113
ABS 004-WH
115
ABS 005/25
114
ABS 005/25-WH
115
ABS 005-1
114
ABS 005-1-WH
115
ABS 006/25
114
ABS 006/25-WH
115
ABS 007/25
114
ABS 007/25-WH
116
ABS 008/25
113
ABS 008/25-WH
114
ABS 010
116
ABS 011
116
ABS 019C/25
116
ABS 019C/25EC
117
ABS 019C/25EC-WH
118
ABS 019C/25-WH
118
ABS 019F/25
116
ABS 019F/25EC
117
ABS 019F/25EC-WH
118
ABS 019F/25-WH
118
1
2
3
4
5
6
7
8
223
Index
Reference
Page
ABS 020/25
117
ABS 020/25EC
117
ABS 020/25EC-WH
118
ABS 020/25-WH
118
ABS 021/25
119
ABS 021/25-WH
119
ABS 022/25
119
ABS 022/25-WH
119
ABS 030/25
113
ABS CAP-RED
119
ABS CAP-WHITE
119
ACT-OPUS126
ACT-SVM24V-5A-BASIC125
ACT-SVM24V-5A-CS125
ACT-SVM24V-5A-F-CS125
ACT-SVM24V-5A-FS125
ACT-SVM24V-8A-BASIC125
ACT-SVM24V-8A-CS125
ACT-SVM24V-8A-F-CS125
ACT-SVM24V-8A-FS125
ACT-VR-1126
ACT-WSK126
AES 24V 3A C24 SB G
182
AES 24V 3A C38 SB G
183
AES 24V 4A C38 SB G
183
AES 24V 6A C38 SB G
183
AES 24V 8A C85 SB G
183
B
B501AP
26, 50
B501AP-BK27
B501AP-IV
26, 50
B524HTR26
B524HTR-WH26
B524IEFT-126
B524IEFT-1B27
B524IEFT-1W26
BA1AP28
BA1AP-IV29
BATV-23156
BB-246
BB-646
BCK-200EAP25
BCK-200REAP25
BCK-200TEAP25
BCK-200TEMAP25
BDD50
BEAM-HK
33, 65
BEAM-HKR
33, 66
BEAM-LRK
32, 65
BEAM-MMK
33, 65
BEAM-SMK
33, 65
BF362-1181
BF362-5182
BPW50
BRR50
BZR2
38, 80
C
CG2192
CH-646
CKS002196
CMX-10RMH44
CR-123156
CR-2032156
CR-4148156
CSR 87
CSR485-100191
CSR485-500191
CSW 87
CWR 87
CWSO-RR-S1 85
224
Honeywell | Fire Safety
Reference
CWSO-RR-W1 CWSO-WW-S1 CWSO-WW-W1 CWSS-RR-S3 CWSS-RR-S5 CWSS-RR-W3 CWSS-RR-W5 CWSS-RW-S5 CWSS-RW-W5 CWSS-WR-S3 CWSS-WR-S5 CWSS-WR-W3 CWSS-WR-W5 CWSS-WW-S5 CWSS-WW-W5 CWST-RR-S5 CWST-RR-W5 CWST-RW-S5 CWST-RW-W5 CWST-WR-S5 CWST-WR-W5 CWST-WW-S5 CWST-WW-W5 CWW Page
85
85
85
87
86
87
87
86
87
87
86
87
87
86
87
86
86
86
86
86
86
86
86
87
D
D2E62
DA5-24VDC146
DNRE30
DST-1
30, 62
DST-1.5
30, 62
DST-10
31, 62
DST-3
30, 62
DST-5
31, 62
E
ECO1000 DRT
205
ECO1000 RTU
205
ECO1000B58
ECO1000BR59
ECO1000BREL12L59
ECO1000BREL12NL59
ECO1000BREL24L59
ECO1000DB59
ECO1000DBR59
ECO100258
ECO100357
ECO1004T58
ECO100557
ECO1005T58
ECP-25566A99
ECP-25566A-W99
ECP-80490095
ECP-80490295
ESS-70490199
ESS-70490299
ESS-70491099
ESS-70491199
ESS-70491299
ESS-70491795
ESS-76991099
Reference
Page
F-AF-5.0
120, 156
F-AF-5.6
121, 156
F-AF-6.0
121, 156
F-A-LC-A156
F-BS
120, 156
FL0111E106
FL0112E106
FL0122E106
FL-IF-6156
F-LT-EB
108, 156
F-PC
120, 156
FR-0206.0966
FR-0206.1066
FR-020971
FR-060871
FR-089371
FR-1000-00772
FR-23835.00149
FR-23901.0171
FR-24006-01149
FR-3000-01568
FR-3000-10167
FR-3000-20172
FR-3000-20272
FR-3000-20473
FR-5000-00269
FR-5000-00469
FR-5000-00570
FR-5000-00670
FR-5000-00770
FR-5000-00870
FR-5000-01471
FR-5000-03969
FR-5000-10168
FR-5000-10269
FR-5000-20172
FR-5000-20473
FR-5000-20574
FR-5100-20473
FS-1100209
G
GDA-CH12138
GDA-CH12-NA138
GDA-M/B-KF4A138
H
HD6295139
HD6296139
HD6297139
HD6298139
HLS-OPTO-RS23220
HLS-OPTO-RS48520
HLSPS25181
HLSPS50181
HRZ255
HRZ455
HRZ855
HSI-1490-1198
HSI-25E198
I
F
F-A3384-000156
F-AF-2.0
120, 156
F-AF-2.5
120, 156
F-AF-3.0
120, 156
F-AF-3.6
120, 156
F-AF-4.0
120, 156
F-AF-4.6
120, 156
Benelux region
Catalogue version 2.1
IBS-LIDDW29
IBS-LIDW28
IRK-2E
29, 60
IRK-2E-B60
IRK-E-SI
29, 60
IRK-W-122430
IRK-W-62461
ISO524-143
Index
Reference
Page
ISOX-819
ITAC94
ITS-BOX19
K
K20SxS-0181
K21SxS-0181
K30SxS-0181
KEYLCK-DRK22051
KL1 X 5
38, 80
L
LHD-BLACK134
LHD-BLUE133
LHD-BRONZE134
LHD-CT135
LHD-DP135
LHD-EC14.2134
LHD-EC2.3134
LHD-EC3.8134
LHD-EC8.18134
LHD-ELTK135
LHD-ILJK136
LHD-LWM1133
LHD-NS135
LHD-PC135
LHD-STAINLESS134
LHD-TC135
LHD-VC135
M
M02-04-00205
M200-DIN44
M200-PMB44
M200-SMB
43, 145
M200-SMB KO
44
M8A-G000SF78
MA05/D/2192
MA10/D/2192
MA15/D/2/SI192
MCP1A-R470FF-0176
MCP1A-R470FF-01IS142
MCP1A-R470FG-0176
MCP1A-R470FG-01IS142
MCP2A-R470FF-0176
MCP2A-R470FG-0176
MCP3A-R000FF-0177
MCP3A-R000FF-01IS143
MCP3A-R000FG-0177
MCP3A-R000FG-01IS143
MCP3A-x000FF-1177
MCP3A-x000FG-1177
MCP4A-G000SG-1278
MCP4A-R000FF-0177
MCP4A-R000FG-0177
MCP4A-x000FF-1177
MCP4A-x000FG-1177
MCP-LABEL F 028
38, 83
MCP-LABEL F 048
38, 83
MCP-LABEL F 056
38, 83
MCP-LABEL F 071
38, 83
MCP-LABEL F 078
38, 83
MCP-LABEL F 081
38, 83
MCP-LABEL F 082
38, 83
MCP-LABEL F 138
38, 83
MCP-LABEL F 217
38, 83
MCP-LABEL F 218
38, 83
MCP-LABEL F 220
38, 83
MCP-LABEL F 222
39, 83
MCP-LABEL F 228
39, 84
Reference
Page
MCP-LABEL F 235
39, 84
MCP-LABEL F 244
39, 84
MCX-55MH45
MI-BSO-DD-I49
MI-BSO-DD-N49
MI-BSO-PP-I49
MI-BSO-PP-N49
MI-BSS-PC-I49
MI-BSS-PC-N49
MI-CZ-645
MI-D21CMO41
MI-D240CMO42
MI-D240CMO-DIN42
MI-D240CMO-KO42
MI-DCMO41
MI-DCZRM
43, 145
MI-DISO43
MI-DMM2I41
MI-DMMI40
MI-FHSE-S2 22
MI-FHSE-S2I22
MI-FHSE-S2I-IV24
MI-FHSE-S2-IV24
MI–FL2011EI105
MI–FL2012EI105
MI–FL2022EI105
MI-HTSE-S222
MI-HTSE-S2I 22
MI-HTSE-S2I-IV24
MI-HTSE-S2-IV24
MI-LPB2-S2I32
MI-LZR25
MI-MCP-FLEX 34
MI-MCP-FLEX-I 34
MI-MCP-FLEX-I-x 35
MI-MCP-FLEX-x35
MI-MCP-GLASS 34
MI-MCP-GLASS-I 34
MI-MCP-GLASS-I-x 35
MI-MCP-GLASS-x 35
MI-MM3E/KAC40
MI-MM3E-S240
MI-PSE-S2 21
MI-PSE-S2I 21
MI-PSE-S2I-IV24
MI-PSE-S2-IV24
MI-PTIR-S2 23
MI-PTIR-S2I 23
MI-PTIR-S2I-IV24
MI-PTIR-S2-IV24
MI-PTSE-S2 23
MI-PTSE-S2I23
MI-PTSE-S2I-IV24
MI-PTSE-S2-IV24
MI-RHSE-S2 22
MI-RHSE-S2I 23
MI-RHSE-S2I-IV24
MI-RHSE-S2-IV24
MI-SC-645
MI-WCP-R/I/SF 36
MI-WCP-R/I/SG 36
MI-WCP-R/SF 36
MI-WCP-R/SG 36
MI-WCP-x/I/SF 37
MI-WCP-x/I/SG37
MI-WCP-x/SF37
MI-WCP-x/SG37
MI-WSO-PP-I47
MI-WSO-PP-N47
MI-WSO-PR-I47
MI-WSO-PR-N47
MI-WSS-PC-I48
MI-WSS-PC-N48
MI-WST-PA-I48
Reference
Page
MI-WST-PC-I48
MI-WST-PC-N48
MMX-10MH44
MOD45R213
MORL-OPTO-ESPA20
MS1/R140
MS1/R/IS146
MS2/R/R141
MS5/R/R141
MSD/A156
MSD/B156
MSD/R156
MTL5525147
MTL5561145
MTL7761AC136
MUS 156
51
1
N
NAS-2 FIL
156
NAS-2 FIL-INT
156
NAS-2 KEYPAD
156
NBS488
NBSLID/R88
NBSLID/W88
NP12-12186
NP12-6186
NP17-12187
NP2.3-12186
NP24-12187
NP38-12187
NP65-12187
NP7-12186
O
OSE-HPW75
OSE-SP-0174
OSE-SPW74
OSI-1074
OSI-4574
OSI-9074
OSID-INST75
OSID-WG195
OSI-EHE75
OSI-EHI75
OSP-00175
OSP-00275
2
3
4
5
6
7
8
P
PC.VALVOLA212
PIP-025120
PIP-033120
POL-100205
PS188 87
PS189 87
PS200
38, 80
PS23051
PTL611210
PTR80
PUL-D/EXT96
PUL-P/EXT96
PUL-TAP99
R
RA100Z
31, 63
RACK-SUPRA94
RB012AHB184
RB022AHB184
RB040AHB184
RB070AHB184
225
Index
Reference
page
RB120AHB185
RB180AHB185
RB260AHB185
RB450AHB185
RB650AHB185
RF-FTX156
RIV-601P/F152
RIV-601P/FA152
RMK400AP27
RMK400AP-IV29
RP1r-CLL99
RP1r-FA99
RP1r-PCB99
RP1R-SUPRA-KEY99
RP1R-SUPRA-PCB99
RTS151
31, 63
RTS151KEY
31, 63
S
S1450CO170
S1451ND170
S2096BU175
S2096GP175
S2096ME175
S2096PR175
S2096VB175
S2097BU172
S2097GP172
S2097ME172
S2097PR172
S2097VB172
S2130CO176
S2131CO173
S2133AM173
S2135AM173
S2137HS173
S2145NO173
S2156BU174
S2156GP174
S2156ME174
S2156PR174
S2156VB174
S2157BU171
S2157GP171
S2157ME171
S2157PR171
S2157VB171
S2162CO175
S2396GP170
S2396ME170
S2396VB170
S2401CO2171
S2601BU174
S2601ME174
S2601PR174
S2602BU172
S2602ME172
S2602PR172
S2640O2176
S2641O2173
S2642O2175
S2653BU176
S2653ME176
S2653PR176
S2654BU173
S2654ME173
S2654PR173
SAHEP-APRICOLOR124
SAHEP-DS24VDC350123
SAHEP-DS24VDC550123
SAHEP-DS24VDC750123
SAHEP-DS24VDC950123
SAHEP-DUO24VDC550124
226
Honeywell | Fire Safety
Reference
page
SAHEP-DUO24VDC750124
SAHEP-DUODR550124
SAHEP-DUODR750124
SAHEP-EFS-SENSOR122
SAHEP-KEY156
SAHEP-MI-SAHEP-4122
SAHEP-MI-SAHEP-4-EFS122
SAHEP-PCB156
SAHEP-PLEXI/M-IAS156
SAHEP-PRIOR122
SAHEP-PROFIL U
123
SAHEP-RD123
SAHEP-TT130124
SAHEP-TT160124
SAHEP-WD123
SAHEP-WRD1122
SC01151
SC07052
SC071
38, 52, 80
SC076 87
SC083192
SCORP 1001-001
206
SCORP 2001-001
206
SCORP 25-001
206
SCORP 50-001
207
SCORP 60-001
207
SCORP 7000-001
206
SCORP 8000-001
206
SDT150-12198
SDT150-S-12199
SDT250-12198
SFT2000
28, 61
SG.B/XXX212
SG/CI133
SG/SC129
SG100128
SG200128
SG350129
SGCP100129
SGCWE100127
SG-CWS100-AV-KIT132
SG-CWS100-KIT131
SG-DRT208
SGFI200-S132
SG-LBS100133
SG-M210156
SGMC200130
SGMCB200130
SGMI200130
SG-PU127
SGRBS100131
SGRBS100-AV132
SGSK100208
SGWCP100129
SGWE128
SI.B/XXX212
SL517177
SL523177
SL647177
SMB6-V046
SMBW-VO46
SMK400EAP27
SMK400EAP-IV29
SOA-875152
SOLO 100
201
SOLO 101
200
SOLO 108
201
SOLO 200
201
SOLO 330
201
SOLO 424
201
Benelux region
Catalogue version 2.1
Reference
page
SOLO 460-001
213
SOLO 461
201
SOLO 610
200
SOLO 713-001
201
SOLO 726-101
207, 213
SOLO 760-001
213
SOLO 808
199
SOLO 809
199
SOLO 810
199
SOLO 811
200
SOLO 814
200
SOLO 822
200
SOLO A7
199
SOR-873P152
SPARE 1002
213
SPARE 1005
213
SPARE 1028
213
SPARE 1049
213
SR0T83
SR1T37
ST.G/8REL167
ST.G/BOX167
ST.G/IN8-S167
ST.G/OUT16-S167
ST.G/SER++167
ST.MTS/S1167
ST.MTS/S1-128B167
ST.MTS/S1-256B167
ST.MTS/S1-64B167
ST.PL4/ESP170
ST.S/CKD176
ST.S/IDI176
ST.S3REL176
ST.SX/IDI+168
STGD/AD2177
STGD/AD3177
STI 6530/n
195
STI 6531/n
195
STI 6532/n
195
STI 6533/n
195
STI 6534/n
195
STI 6535/n
196
STI 9601
193
STI 9602
193
STI 9604
193
STI 9605
193
STI 9606
193
STI 9609
193
STI 9610
193
STI 9617
197
STI 9621
197
STI 9624
194
STI 9625
194
STI 9640
197
STI 9641
197
STI 9645
197
STI 9649
197
STI 9706
194
STI 9707
194
STI 9840
195
STI 9841
194
STI/BS196
STPL4+170
Sx0T83
Sx1T37
T
TC3-3PACK-001204
TESTIFIRE 1001-001
202
TESTIFIRE 2001-001
203
TESTIFIRE 25
204
TESTIFIRE 6001-001
202
TESTIFIRE 6201-001
203
Index
Reference
Page
TESTIFIRE 9001-001
202
TESTIFIRE 9201-001
203
TFT-SUPRA
94, 99
TMP_Configurator139
TMP2-D-A257R1A137
TMP2-D-A257S1A137
TMP2-D-C90R1A137
TMP2-D-C90S1A137
TMP2-D-D110R1A137
TMP2-D-D110S1A137
TMP2-P-A257R1A137
TMP2-P-A257S1A137
TMP2-P-C90R1A137
TMP2-P-C90S1A137
TMP2-P-D110R1A137
TMP2-P-D110S1A137
TMP2-ST14138
TMP2-TO-A257R1A137
TMP2-TO-A257S1A138
TMP2-TO-C90R1A137
TMP2-TO-C90S1A138
TMP2-TO-D110R1A138
TMP2-TO-D110S1A138
TS3-001204
TS3-3PACK-001204
V
V6/B/24V149
V6/C/24V149
V6/G/24V149
V6/R/24V148
V6/Y/24V149
VLC-500RO109
VLF-250108
VLF-500108
VLP-002110
VLP-012110
VLP-400110
VLS-204111
VLS-214112
VLS-304112
VLS-314112
VLS-600111
VLS-700111
VMB/267V40167
VSN-23294
VSN-4REL94
VSN-LL99
VSN-RP1R+93
VSP-005156
VSP-850-G156
VSP-850-R156
VSP-855-20156
VSP-855-4156
VTX+XA212
W
WB-1AP27
WB-1AP-IV29
WCP1A-R470SF-0179
WCP1A-R470SF-01IS143
WCP1A-R470SG-0179
WCP1A-R470SG-01IS143
WCP1A-x470SF-01IS144
WCP1A-x470SF-1179
WCP1A-x470SG-01IS144
WCP1A-x470SG-1179
WCP3A-R000SF-0178
WCP3A-R000SF-01IS144
WCP3A-R000SG-0178
WCP3A-R000SG-01IS144
WCP3A-x000SF-01IS144
Reference
Page
WCP3A-x000SF-1179
WCP3A-x000SG-01IS144
WCP3A-x000SG-1179
WDD50
WPW50
WRR50
Wx920181
Wx920281
Wx920381
Wx930182
Wx930282
Wx930382
Wx930482
Wx940282
Wx9403-1182
X
XC100219
XC100D219
XC70219
XCM100220
XCM100D220
XH100217
XHM100218
XS100217
XS100T
217, 218
XSM100218
XW100
217, 218, 219, 220
Y
Y05/R/IS147
Y05D140
Y06/R/24V148
Y08/SD_YA80/D/RF/SU140
Y08D140
YL6/R/24V148
Z
Z-00780-A-0100165
Z-00780-A-0160163
Z-02000-A-1635163
Z-02000-A-1640163
Z-02000-A-1642163
Z-02000-A1645211
Z-2106B1100160
Z-2106B1130178
Z-2106B1300161
Z-2106B1301161
Z-2106B1302161
Z-2106B1305160
Z-2106B1306160
Z-2106B1307160
Z-2106B1310161
Z-2106B1311161
Z-2106B1313161
Z-2106B1314161
Z-2106B1316161
Z-2106B1545178
Z-2106B1548178
Z-2106B1549178
Z-2106B1596178
Z-2302D0765211
Z-2306B1000159
Z-2306B2000159
Z-2306B3010178
Z-2306B3020178
Z-2306B3030178
ZB24518192
ZB24544192
ZB24578192
Reference
Page
Z-CAL-CO211
Z-CAL-COM211
Z-GasCH4-22-AIR-34211
Z-GASCO-100-AIR-34211
Z-GasCO-250-AIR-34211
Z-GASH2S-10-AIR-34211
Z-GasNH3-25-AIR-34211
Z-GASNH3-300-AIR-34211
Z-GasO2-209-N2-34211
ZM/TEST/2177
ZM/TEST/3177
ZMCAP/123212
Z-REG-0.30211
Z-S3KCAL165
Z-SPPPCAL211
Z-SPPPMTS178
Z-SPPPTUB211
Z-SPSTAXA1162
Z-SPSTAXA1SS178
Z-SPSTAXA2162
Z-SPSTAXA2SS178
Z-SPSTAXC2162
Z-SPSTAXC2SS178
Z-SPSTAXF1162
Z-SPSTAXF1SS178
Z-SPSTAXO1162
Z-SPSTAXO1SS178
Z-SPXCD MTBR
165
Z-SPXCDALMB1164
Z-SPXCDALMCX164
Z-SPXCDALMFX164
Z-SPXCDALMG1164
Z-SPXCDALMHX164
Z-SPXCDALMO1164
Z-SPXCDALMRX164
Z-SPXCDASMB1164
Z-SPXCDASMCX164
Z-SPXCDASMFX163
Z-SPXCDASMG1164
Z-SPXCDASMHX164
Z-SPXCDASMO1163
Z-SPXCDASMRX163
Z-SPXCDCC165
Z-SPXCDDMK165
Z-SPXCDSDP165
Z-TP1IDC178
Z-TP1MADM178
Z-TP1MAIM178
Z-TP1MVDM178
Z-TP1MVIM178
Z-TP1WMB178
Z-TP4CMDM178
Z-TP4CMIM178
Z-TP4IDC178
Z-TP4INT178
Z-TP4MADM178
Z-TP4MAIM178
Z-TP4MVDM178
Z-TP4MVIM178
Z-TP4WMB178
Z-ZDINPSUX1159
1
2
3
4
5
6
7
8
227
Index
Notes
228
Honeywell | Fire Safety
Benelux region
Catalogue version 2.1
Honeywell Life Safety Benelux
Honeywell Life Safety Belgium
Liège Airport Business Park
Building 50
4460 Grâce-Hollogne
T: (+32) 4 2470300 F: (+32) 4 2470220
Email: [email protected]
www.morley-ias.be
Honeywell Life Safety Netherlands
Burgemeester Burgerslaan 40
5245 NH Rosmalen (‘s Hertogenbosch)
T: (+31) 736273295 F: (+31) 736273298
Email: [email protected]
www.morley-ias.nl
Morley-IAS Product Catalogue, version 2.1
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement