Avocent PM3000 User guide

Add to my manuals
117 Pages

advertisement

Avocent PM3000 User guide | Manualzz

AVOCENT PM PDU

Installer/User Guide

USA Notification

WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canadian Notification

This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.

Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la classe A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le Ministère des Communications du Canada.

Japanese Notification

Safety and EMC Approvals and Markings

UL, FCC, cUL, ICES-003, CE, GOST-R, C-Tick, CB

Avocent PM PDU

Installer/User Guide

Avocent, the Avocent logo, DSView, Cyclades and DSR are either trademarks or registered trademarks of Avocent Corporation or its affiliates in the U.S. and other countries.

© 2011 Avocent Corporation.

590-860-501H

Symbols Used

NOTE: The following symbols may appear within the documentation or on the appliance.

Instructions

This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.

Dangerous Voltage

This symbol is intended to alert the user to the presence of uninsulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.

Power On

This symbol indicates the principal on/off switch is in the on position.

Power Off

This symbol indicates the principal on/off switch is in the off position.

Protective Grounding Terminal

This symbol indicates a terminal which must be connected to earth ground prior to making any other connections to the equipment.

Functional Earthing Terminal

This symbol indicates a terminal which serves the purpose of establishing chassis ground equal potential.

T A B L E   O F   C O N T E N T S

Introduction

Features and Benefits

Alarms and monitoring

LED display

Power reset button

In-rush current control

Support for daisy chaining

Integration with Avocent management products

DSView 3 software plug-in

External sensors

Hardware Configuration Options

Standalone configuration

Daisy-chained configuration

Installation

Getting Started

Supplied with the PM PDU

Additional items needed

Rack Mounting the PM PDU

Mounting a horizontal PM PDU

Mounting a vertical PM PDU

Rack mount safety considerations

Safety Precautions

Accessing the PM PDU

Configuring the PM PDU

Default configuration parameters

Recovering the PM PDU password

Accessing a PM PDU via the Web Manager

Web Manager Overview for Administrators

Wizard Mode

Expert Mode

13

13

14

14

15

15

8

10

7

8

7

7

7

17

17

18

20

2

3

2

2

3

5

2

2

2

2

1

1

1

IV

V Avocent PM PDU Installer/User Guide

Access

System Tools

Power Management

PDUs

Settings

Outlet Groups

Data Logging

System

Security

Date and Time

Help and Language

Boot Configuration

Information

Usage

Network

Settings

Devices

IPv4 and IPv6 static routes

Hosts

Firewall

SNMP configuration

Authentication

Appliance authentication

Authentication servers

Users

Local accounts

Authorization

Event and Logs

Event List

Event Destinations

41

41

41

35

37

38

39

31

34

35

35

30

30

31

31

29

30

30

30

25

25

27

28

22

23

24

25

21

21

22

Data Buffering

Appliance Logging

Active Sessions

Monitoring

Change Password

Web Manager Overview for Regular Users

Accessing a PM PDU via the Command Line Interface

Access Options and How to Log Into the CLI

Configuration Tasks Performed With the CLI

CLI Navigation

Autocompletion

Parameters

Command Line Syntax

CLI Command Set help

add delete cd

pwd exit/quit ftp

scp set commit revert show/ls

cycle, on, off, lock and unlock passwd opiepasswd

CLI Equivalent Actions to Web Manager Checkbox Selection

Table of Contents VI

53

53

53

54

51

52

52

52

50

50

50

51

47

47

48

48

55

55

55

56

54

54

54

54

43

44

44

42

43

43

VII Avocent PM PDU Installer/User Guide

CLI Overview for Administrators

System

System/Security

System/Boot Configuration

System/Date and Time

System/Help and Language

System/Information

System/Usage

Network

Wiz command

Network/Settings

Network/IPv4 and IPv6 Static Routes

Network/Devices

Network/Hosts

Network/Firewall

Network/SNMP

Authentication

Users

Events_and_Logs

Power Management

Active Sessions Information

Appendix A: Accessing a PM PDU via SNMP

Appendix B: Specifications

Appendix C: Outlet Bank Assignment

Appendix D: Replacing the Fuses (For Service Personnel Only)

63

64

65

66

61

61

62

63

59

59

60

61

57

57

58

67

67

68

69

70

71

73

74

82

108

1

Introduction

This guide enables you to install, configure and maintain your Avocent Power Management

Power Distribution Unit (PM PDU).

All Avocent PM PDUs (PM 1000, PM 2000 and PM 3000 PDUs) have strip level metering capabilities. All attached units can also be managed through a web manager, Command Line

Interface (CLI), SNMP or serially in conjunction with several Avocent DSR™ KVM over IP switches, ACS 6000 advanced console servers or with DSView™ 3 management software.

The 2000 and 3000 models both provide outlet level metering capability, while the 3000 model also provides outlet level switching.

Metering capability on all Avocent PM units includes:

• Current - Present, Maximum, Minimum, Average

• Voltage - Present, Maximum, Minimum, Average

• Power - Present, Maximum, Minimum, Average

• Power Factor

• Cumulative Watt Hour

Features and Benefits

Alarms and monitoring

The Avocent PM PDU delivers accurate, real-time global current monitoring of all connected devices via the web manager, DSView 3 software or locally through an LED digital display.

Users can set a current alarm threshold that, once exceeded, will cause the PM PDU to sound an alarm or send a notification message, or both.

1

2  Avocent PM PDU Installer/User Guide

LED display

The PM PDU has an LED that displays aggregate current, phase/bank current, outlet current or temperature. You can use the Function 1 button to switch the type of display and use the

Function 2 button to cycle through different targets. Pressing and holding any function button for two seconds will reset the overcurrent protection.

Power reset button

The PM PDU has a power reset button that can be used to reset the PDU without affecting the power supply to equipment plugged into the PDU.

In-rush current control

The PM PDU incorporates an in-rush current control feature that prevents all power outlet receptacles from turning on at once, eliminating possible current surges that could render the equipment inoperable. Together with the global current monitoring, the in-rush current control feature lets users safely install more equipment on existing power circuits without the worry of current overloads.

Support for daisy chaining

PM PDUs can be daisy chained to increase capacity by connecting the control interfaces of several PM PDUs in a series.

Integration with Avocent management products

The PM PDU can be combined with an ACS 6000 console server or DSR KVM over IP switch to provide power management capabilities and faster problem solving by integrating system access and power control in a single interface. Please refer to the appropriate product documentation for more information on how to use the PM PDU with your specific

 implementation.

DSView 3 software plug-in

The DSView 3 software may be used with the PM PDU to allow IT administrators to remotely access, monitor and control target devices on multiple platforms through a single, web-based user interface. For more information, see the DSView 3 Installer/User Guide or the Avocent PM

PDU Technical Bulletin (DSView 3 Software Plug-in).

External sensors

The PM PDU supports external sensors which can monitor a variety of states depending on the model of the sensor. The PM PDU has two RJ-45 connectors which can be used to connect the

Chapter 1: Introduction 3 sensors. Contact your Avocent representative for more information about external sensors for the PM PDU.

Hardware Configuration Options

The PM PDU may be used in one of two hardware configurations:

• Standalone – Managed independently of any other hardware device.

• Daisy chained - Multiple PDUs connected to one another and managed by one main

Avocent PM PDU.

Standalone configuration

In a standalone configuration, the PM PDU operates independently of any other hardware. The following graphic displays a PM PDU with the console port connected to a computer running terminal emulation.

4  Avocent PM PDU Installer/User Guide

Figure 1.1: Standalone Configuration

Table 1.1: Standalone Configuration Descriptions

Number Description Number Description

1

2

3

RJ-45 to DB-9F Adaptor (Optional)

CAT 5 Cable

IN Port

4

5

Servers

Workstation

6

7

Ethernet Port

Ethernet Connection

Chapter 1: Introduction 5

NOTE: The installation shows the PM PDU being connected with the RJ-45 to DB-9F adaptor that is shipped with the product. If your unit does not have a DB-9M COM port, you may use a USB serial adaptor and connect to a USB port when possible.

Daisy-chained configuration

In a daisy-chained configuration, multiple PM PDUs are connected to one another and managed by a single main PM PDU. The PM PDUs are linked together with CAT 5 cables connected through the PM PDU’s IN and OUT ports. Avocent PM PDUs can be daisy chained with

Cyclades™ PDUs.

NOTE: You cannot daisy chain an Avocent PM PDU from a Cyclades PDU.

You may manage a maximum of five PDUs or a maximum of 128 outlets by connecting multiple PM PDUs to the main PM PDU. The following example shows two PM PDUs operating in a daisy chained environment.

6  Avocent PM PDU Installer/User Guide

Figure 1.2: Daisy Chained Avocent PM PDUs

To daisy chain a PM PDU:

1.

Connect one end of a CAT 5 cable to the OUT port of the main PM PDU, which is connected to a workstation or management appliance.

2.

Connect the other end of the CAT 5 cable to the IN port of the secondary PM PDU.

Repeat these steps until you have connected the desired number of PM PDUs.

2

Installation

Getting Started

Before installing your Avocent PM PDU, refer to the following list to ensure you have all items shipped with the PDU, as well as other items necessary for proper installation.

Supplied with the PM PDU

• PM PDU Quick Installation Guide (QIG)

• Security Warning Card

• Power Cord

• RJ-45 to RJ-45 straight-through CAT 5 cable

• RJ-45 to DB-9F straight-through adaptor

• RJ-45 adaptor

• Mounting brackets, screws and cord retention clips

• Keyhole mounting kit

NOTE: If your PM PDU model does not have a fixed power input cable, it may ship with a modular cable. Depending on your site’s location, the modular input power cables included in the box vary.

Additional items needed

If you are configuring the PM PDU in a standalone configuration, you will also need the following items:

• One or more RJ-45 to RJ-45 CAT 5 straight-through cables

• An RJ-45 to DB-9F straight-through adaptor

• A PC running a terminal emulation program

7

8  Avocent PM PDU Installer/User Guide

Rack Mounting the PM PDU

You may rack mount the PM PDU or place it on a desktop or other flat surface. A horizontal

PM PDU can be mounted in a 1U fashion using the included brackets. It can be mounted on either the front or back to display outlets and LEDs on either the front or rear of the rack. A vertical PM PDU can be mounted utilizing the side bars in the rack. When using the sidebars, the PM PDU can be mounted with the outlets on either the top end or the bottom end of the

PM PDU.

Mounting a horizontal PM PDU

Attach the supplied mounting brackets to the PM PDU using the four retaining screws provided for each bracket. Align the mounting holes of the brackets with the notched holes on the vertical rail of the rack and attach with the retaining screws. Attach the supplied retention clips

(single retention clip for 3-port PM PDU, dual retention clip for 6-port PM PDU) using the notches to the side of the outlets on the PM PDU. Use the provided retention clips or

VELCRO® strips to secure the power cords to the PM PDU.

NOTE: Ensure each bracket is attached to the correct side of the PM PDU so that neither bracket is covering any part of the air vents on the sides of the PDU.

1

2

3

Figure 2.1: Mounting a Horizontal PM PDU

Table 2.1: Descriptions for Mounting a Horizontal PM PDU

Number Description

Attaching mounting brackets to a horizontal PM PDU

Attaching retention clips to a 3-port horizontal PM PDU

Attaching retention clips to a 6-port horizontal PM PDU

Chapter 2: Installation 9

10  Avocent PM PDU Installer/User Guide

Figure 2.2: Attaching VELCRO ® Retention Strips for a Horizontal PM PDU

Mounting a vertical PM PDU

Rack mounting using the tool-less keyed mounting hardware

Locate the two pre-installed round plastic keys on the far ends of the back of the PM PDU.

Line up each key with the large end of the keyhole-shaped mounting socket on each end of the rack. Insert the keys and then pull down to lock the PM PDU in place. Use the provided retention clips or VELCRO strips to secure the power cords to the PM PDU.

Rack mounting using the universal mounting brackets

Locate the four pre-installed machine screws on the ends of the back of the PM PDU. Remove these four screws, leaving the the plastic keys installed. Using the same screws you just removed, attach the L-shaped universal mounting brackets to the PM PDU, making sure they are in the desired orientation. Using two screws (designed for your rack) for each bracket, attach the PM PDU to the rack. Leave enough space at either end for cable connections. Attach the supplied retention clips or VELCRO strips using the notches to the side of the outlets on the

PM PDU.

NOTE: Ensure the positioning of the bracket does not interfere with equipment in the rack or doors.

Figure 2.3: Rack Mounting a Vertical PM PDU

Table 2.2: Descriptions for Rack Mounting a Vertical PM PDU

Number Description

1 Rack mounting using the tool-less keyed mounting hardware.

2 Rack mounting using the universal mounting brackets.

Chapter 2: Installation 11

12  Avocent PM PDU Installer/User Guide

Figure 2.4: Attaching Retention Clips for a Vertical PM PDU

Figure 2.5: Attaching VELCRO Retention Strips for a Vertical PM PDU

Chapter 2: Installation 13

Rack mount safety considerations

• Elevated Operating Ambient Temperature: If the PM PDU is installed in a closed or multiunit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient temperature. Therefore, consideration should be given to installing the equipment in an environment compatible with the manufacturer’s maximum rated ambient temperature.

• Reduced Air Flow:. Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised.

• Mechanical Loading: Mounting of the equipment in the rack should be such that a hazardous condition is not created due to uneven mechanical loading.

• Circuit Overloading: Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.

• Reliable Grounding: Reliable grounding of rack mounted equipment should be maintained.

Particular attention should be given to supply connections other than direct connections to the branch circuit, such as power strips or extension cords.

NOTE: Install a PM PDU model in a location where there is an adjacent and accessible socket outlet.

Safety Precautions

Read all the following safety guidelines to protect yourself and your PDU.

WARNING: All outlets of the PDU output high voltage. Necessary precautions should be taken.

WARNING: Do not push any objects through the openings of the PDU. Doing so may cause fire or electric shock by shorting out interior components.

WARNING: There is a possibility of severe electrical shock from either the live or neutral side of any of the power outlets or their wiring, even if one of the circuit breakers is disabled.

WARNING: The PDU is intended for indoor use only.

WARNING: To help protect the PDU from electrical power fluctuations, use a surge suppressor, line conditioner or uninterruptible power supply.

WARNING: Be sure that nothing rests on the cables of the PDU and that it is not located where it may be stepped on or tripped over.

14  Avocent PM PDU Installer/User Guide

WARNING: Do not spill food or liquids on the PDU. If it gets wet, disconnect the power immediately and contact

Avocent.

WARNING: Keep the PDU away from heat sources.

WARNING: Disconnect power from the product by unplugging the power cord from either the electrical outlet or the PDU. The AC inlet is the main disconnect for removing power to the PDU. For PDUs that have more than one

AC inlet, to remove power completely, all AC line cords must be disconnected. The socket-outlet shall be installed near the equipment and shall be easily accessible.

WARNING: The PDU relies on protective devices in building installations. Please refer to Appendix A for Listed

Branch Circuit type protection.

Accessing the PM PDU

Users and administrators may access the PM PDU either by making a direct console connection to the PM PDU’s IN port or by connecting the PM PDU to an Avocent console server or KVM switch.

To connect the PM PDU to a computer:

1.

Connect a CAT 5 cable to the IN port on the PM PDU.

2.

Connect the CAT 5 cable to a computer with a terminal emulation program using the RJ-

45 to DB-9F straight-through adaptor or a USB serial adaptor.

3.

Using a terminal emulation program, connect to the PM PDU with the following settings:

ANSI emulation, 9600 bps, 8 bits, no parity, 1stop bit and no flow control.

When prompted, log in either as admin with the default password avocent or as root with the default password linux.

To connect a PM PDU to an Avocent DSR switch:

1.

Plug the male end of the included RJ-45 adaptor into the DSR switch’s SPC port.

2.

Plug one end of a straight-through CAT 5 cable into the female end of the adaptor and plug the other end of the CAT 5 cable into the PM PDU’s IN port.

To connect a PM PDU to an Avocent ACS 6000:

1.

Plug one end of a straight-through CAT 5 cable into one of the ACS 6000’s serial ports.

2.

Plug the other end of the CAT 5 cable into the PM PDU’s IN port.

Configuring the PM PDU

The PM PDU may be configured by either of two methods:

Chapter 2: Installation 15

• Command Prompt

• Browser or text based menu

For information about integrated use with an Avocent management device visit, www.avocent.com or refer to the appropriate product documentation.

Default configuration parameters

The PM PDU’s default configuration is as follows:

• User is admin

• Admin user’s password is pm8

NOTE: The pm8 password is valid only for the console and is used by the main PM PDU in a chain to log in to chained PM PDUs.

• All outlets are named. The default name is PDU id_<outlet number>

• All outlets are unassigned to user

• All outlets are turned on

• All outlets are unlocked

Recovering the PM PDU password

To recover the PM root password:

1.

Connect directly to the PM PDU’s console port.

2.

Press the power reset button or power cycle the PM PDU.

3.

Type Ctrl-C to access the uboot prompt.

4.

Type hw_boot single and press Enter .

5.

The PM PDU will boot into single-user mode. Type passwd and press Enter .

6.

Enter the new password and confirm.

7.

Type reboot and let the unit boot normally.

16  Avocent PM PDU Installer/User Guide

3

Accessing a PM PDU via the Web

Manager

17

Once you’ve connected your Avocent PM PDU to a network, you can access the PM PDU with the web manager. The web manager provides direct access to the PM PDU via a graphical user interface instead of a command-based interface.

NOTE: For instructions on accessing the PM PDU via the command line interface (CLI), SNMP or DSView 3

software, see Accessing a PM PDU via the Command Line Interface on page 47, Accessing a PM PDU via SNMP on page 73 or the DSView 3 Installer/User Guide.

Web Manager Overview for Administrators

NOTE: For an overview of the web manager for regular users, see Web Manager Overview for Regular Users on

page 44.

To log into the web manager:

1.

Open a web browser and enter the PM PDU’s IP address in the address field.

2.

Log in as either admin with the password avocent or as root with the password linux .

18  Avocent PM PDU Installer/User Guide

Figure 3.1: Administrator Web Manager Screen

Table 3.1: Web Manager Administrators Screen Functional Areas

Number Description

1

2

Top option bar. The name of the appliance and of the logged in user appear on the left side. Refresh, Print, Logout and Help buttons appear on the right.

Tab bar. Displays whether the admin is in Expert or Wizard mode.

3

4

Side Navigation Bar. Menu options for configuration, viewing of system information and access to devices. The options change based on user rights.

Content area. Contents change based on the options selected in the side navigation bar.

Wizard Mode

The Wizard mode is designed to simplify the setup and configuration process by guiding an administrator through the configuration steps. An administrator can configure the Security

Profile, Network and Users Settings using the Wizard.

Chapter 3: Accessing a PM PDU via the Web Manager 19

By default, the first time an administrator accesses the PM PDU through the web manager, the

Wizard will be displayed. Subsequent log-ins will open in Expert mode, and once the PM PDU has been configured, Expert mode becomes the default mode. An administrator can toggle between Expert and Wizard modes by clicking the tab bar on the web manager administrator screen.

Figure 3.2 shows a typical screen when an administrator is in Wizard mode.

Figure 3.2: Wizard screen

The following procedures describe how to configure the PM PDU from the Wizard.

To configure security parameters and select a Security Profile:

1.

Select the Security link in the content area.

2.

Select the desired Security Profile. If using a Custom Security Profile, click the checkboxes and enter values as needed to configure the services, SSH and HTTP and HTTPS options to conform with your site security policy.

3.

Under the Bootp Configuration Retrieval heading, uncheck the box(es) to disable Bootp configuration retrieval or live configuration retrieval.

4.

If you are not using DSView 3 software to manage the appliance, uncheck the Allow

Appliance to be Managed by DSView 3 box.

20  Avocent PM PDU Installer/User Guide

5.

Click Next to configure the Network or click the Network or Users link to open the appropriate screen.

To configure network parameters:

1.

Select the Network link in the content area.

2.

Enter the Hostname, Primary DNS and Domain in the appropriate fields.

3.

Select the IPv4 or IPv6 method for the ETH0 interface. If using Static, enter the Address,

Mask and Gateway in the appropriate fields.

4.

Click Next to configure Users or click on the Security or Users link to open the appropriate screen.

To configure users and change the default user passwords:

WARNING: For security reasons, it is recommended you change the default password for both root and admin users immediately.

1.

Select the Users ink in the content area.

2.

Click a username (admin or root) and enter the new password in the Password and Confirm

Password fields.

-or-

Click Add to add a user. Enter the new username and password in the appropriate fields.

3.

(Optional) To force the user to change the default password, select the User must change

password at the next in checkbox.

4.

Assign the user to one or more groups.

5.

(Optional) Configure account expiration and password expiration.

6.

Click Next.

7.

Repeat steps 3-6 as needed to configure new user accounts and assign them to default groups.

8.

Click Save, then click Finish.

Expert Mode

The following tabs are available in the Side Navigation Bar of the web manager when an administrator is in Expert mode.

Chapter 3: Accessing a PM PDU via the Web Manager 21

Access

Click Access to view all PM PDUs connected to the network. Click on a PM PDU’s name to display its outlets. Click on the arrow next to a PM PDU to display a list of PDUs in a daisychained configuration.

NOTE: For PM 3000 models, you can turn on, turn off or cycle individual outlets or all outlets in the PDU from the

Action column. You can also select multiple outlets or multiple PDUs by checking the box next to their names, then turn on, turn off, cycle, lock or unlock them all at the same time.

To view and connect to devices using the web manager:

1.

Select Access in the Side Navigation Bar. The content area displays the name of the PM

PDU and a list of names or aliases for all installed and configured devices the user is authorized to access.

2.

Select Appliance Viewer from the Action column. A Java applet viewer appears, which shows the following:

Welcome to PM1024 <PM1000-24-1024000004>.

Type help for more information.

--:- / cli->

3.

Log in if prompted.

Table 3.2: Java Applet Buttons for Connecting to the Console Server

Button Purpose

SendBreak

Disconnect

To send a break to the terminal

To disconnect from the Java applet

Select the left icon to reconnect to the server or device; or select the right icon to end the session and disconnect from the Java applet

System Tools

Click System Tools to display icons which can be clicked to reboot or shut down the PM PDU, upgrade its firmware, save or restore its configuration, restore it to factory default settings or open a terminal session with the PM PDU.

For details on upgrading the PM PDU’s firmware through a direct connection to the network, an advanced console server or the DSView 3 software, see the "Upgrading Firmware" Technical

Bulletin for the PM PDU.

22  Avocent PM PDU Installer/User Guide

Power Management

The following tabs are listed under Power Management in the Side Navigation Bar.

PDUs

To manage a PDU:

1.

Select Power Management - PDUs.

2.

Select the checkbox next to the PDU for which you want to manage power.

3.

Click On, Off, Cycle, Reboot PDU, Reset HW Overcurrent Protection for Factory Defaults if desired. A confirmation appears. Click OK.

NOTE: The power controls (On, Off and Cycle) will be applied to all outlets of the PDU.

4.

To change the PDU ID, click Rename and enter the name in the New PDU ID field.

5.

Click Save.

To view a PDU’s information:

1.

Select Power Management - PDUs.

2.

Click the name of the PDU you want to view or manage.

3.

The Outlet Table with power controls window appears and the Side Navigation Bar displays a list of options.

4.

To manage outlets of PDU: a.

Check the box(es) of the outlet number(s) you want to manage.

b.

Click On, Off, Cycle, Lock or Unlock to perform that function for the selected outlet(s).

5.

Click Information in the Side Navigation Bar to view a PDU’s information.

6.

Click Overview, Current, Voltage, Power Consumption, Cumulative Power or Environment in the Side Navigation Bar to view a table with appropriate information.

7.

To reset values, check the box next to the outlet you want to reset and click Reset Values to clear Max, Min and Average values.

To manage outlets on a PDU:

1.

Select Power Management - PDUs and click on the name of the PDU you want to manage.

2.

Click Settings to expand the Side Navigation Bar.

3.

Click Outlets.

Chapter 3: Accessing a PM PDU via the Web Manager 23

4.

Click on an outlet number to change its settings. You can change the Name, Post On

Delay, Post Off Delay, Current Critical Threshold, Current Warning Threshold and Current

Low Warning Threshold.Click Save, then click Close.

-or-

Check two or more boxes next to the outlets for which you want to change settings.

Click Edit. You can change the Prefix Name (the outlet name will be the Prefix Name with an underscore and the outlet number), Post On Delay, Post Off Delay, Current

Critical Threshold, Current Warning Threshold and Current Low Warning Threshold.

Click Save.

5.

Click PDU to see PDU settings. You can configure Cold Start Delay and Current

Threshold(s). Click Save when finished.

6.

Click Phases or Banks.

a.

Click on the name of a phase or bank to change its settings, or click one or more boxes next to the phase(s) or bank(s) you want to change. You can change the Current

Critical Threshold, Current Warning Threshold and Current Low Warning Threshold.

b.

Click Save to save the settings and click Close to return to the Phases or Banks screen.

7.

Click Environment.

a.

Click on the name of a sensor to change its settings. You can configure a sensor’s name and its thresholds. Click Save.

NOTE: The PDU model defines available parameters in the Settings window.

Settings

Select Power Management -Settings to view and configure power management settings.

To manage PDU settings:

1.

Select Power Management - Settings.

2.

In the Password field, enter the password an administrator can use to log in to the PDU from its console port. This password is saved in plain text format and it is not the secure password of an admin user, which by default is set as avocent. The password is also used by the PM PDU to connect to any daisy-chained PDUs.

3.

Enter the polling rate (in seconds) the PM PDU will use to retrieve data from daisy-chained

PDUs.

24  Avocent PM PDU Installer/User Guide

4.

Enter the power cycle interval (in seconds) and then use the drop-down menus to enable or disable syslog, buzzer and SW overcurrent protection. These settings will apply to all

PDUs in a daisy-chained configuration.

5.

To enable data logging, check the box next to Enable Data Logging.

6.

Click Save.

Outlet Groups

By selecting the Outlet Groups tab, you can view status, outlet and power consumption for outlet groups. You can also turn on, turn off or cycle selected outlet groups.

To add an outlet group:

1.

Select Power Management - Outlet Groups. The Outlet Groups window appears.

2.

Click Add. The Add Group window appears.

3.

Enter the name of the Outlet Group in the Group Name field.

4.

Click Save.

To manage outlet groups:

1.

Select Power Management - Outlet Groups. The Outlet Groups window appears.

2.

Check the box next to the name of the Outlet Group you want to manage.

3.

Click Delete to remove the outlet group. Click On, Off or Cycle as desired.

NOTE: If the command fails for one outlet, the entire command is rejected so no outlets in the group will change.

To configure an outlet group:

1.

Select Power Management - Outlet Groups. The Outlet Groups window appears.

2.

Click the name of the outlet group you want to configure. The Outlet Group Details window appears.

3.

Click Add. The Outlet Settings window appears.

4.

Click the radio button next to Select PDU to use a connected PDU. Enter the outlets to be part of the group in the outlets field.

-or-

Click the radio button next to Custom and enter the PDU ID and outlets in the appropriate fields.

5.

Click Save.

Chapter 3: Accessing a PM PDU via the Web Manager 25

To view and change outlet group information:

1.

Select Power Management - Outlet Groups. The Outlet Groups window appears.

2.

Click on the name of the outlet group for which you want to view information. The Outlet

Group Information window appears displaying outlet, status and power consumption information.

Data Logging

By selecting the Data Logging tab, you can clear or export data logging for PDU, phase, bank, outlet or environment.

To clear data logging:

1.

Select Power Management - Data Logging. The Data Logging window appears.

2.

Select the checkbox next to the type you want to clear.

3.

Click Clear Data Logging. A confirmation box opens. Click OK.

To export data logging:

1.

Select Power Management - Data Logging. The Data Logging window appears.

2.

Select the checkbox next to the type you want to export.

3.

Click Export Data Logging. The Export Data Logging window appears.

4.

Select to export data logging to either an FTP Site or to a Local File, then click Save.

System

Click System to display information about the PM PDU and allow an administrator to configure the PM PDU’s system parameters. The following tabs are listed under System in the Side

Navigation Bar.

Security

Security Profiles determine which network services are enabled on the PM PDU.

During initial configuration, the PM PDU administrator must configure security parameters to conform with the site security policy. The following security features can be configured either in the web manager, CLI or the DSView 3 software:

• Configure the session idle time-out

• Enable or disable RPC

• Enable outlet access control by authorized user groups.

26  Avocent PM PDU Installer/User Guide

• Select a Security Profile, which defines:

• Enabled services (FTP, ICMP, IPSec, SNMP and Telnet)

• SSH and HTTP/HTTPS access

The administrator can select either a preconfigured Security Profile or create a custom profile.

All the services and the SSH and HTTP/HTTPS configuration options that are enabled and disabled for each Security Profile are shown in the Wizard - Security and the System - Security

- Security Profile pages.

To configure the Security Profile:

1.

Select System - Security - Security Profile.

2.

In the Idle Timeout field, enter the number of seconds before the PM PDU times out open sessions.

NOTE: This value applies to any user session to the appliance via HTTP, HTTPS, SSH, Telnet or CONSOLE port.

The new idle time-out will be applied to new sessions only.

3.

Under the Enabled Services section, enable or disable the RCP checkbox.

4.

Under the Authorization heading, uncheck the box if you want to allow regular users to be able to control outlets.

5.

Under the Bootp Configuration Retrieval heading, uncheck the box(es) to disable Bootp configuration retrieval or live configuration retrieval.

6.

Select the checkbox for Custom, Moderate, Open or Secure under the Security Profile heading.

a.

If using a Custom security profile, to enable Telnet, FTP, SNMP or ICMP, check the appropriate box(es) in the Enabled Services field.

b.

Use the pull-down menu to set the version, check the box to allow root access and enter the TCP Port number in the SSH field.

c.

Enable HTTP and HTTPS by checking the appropriate boxes in the WEB field.

d.

Enter the numbers for the HTTP and HTTPS ports in the appropriate fields.

e.

Use the pull-down menu to set the HTTPS SSL Version.

f.

Check the box to redirect HTTP/HTTPS.

7.

Click Save.

Chapter 3: Accessing a PM PDU via the Web Manager 27

You can also configure DSView 3 software security settings. When the PM PDU is managed by the DSView 3 software, the DSView 3 server will supply the certificate to the PM PDU.

Under normal conditions, the DSView 3 software will manage the certificate to clear and replace it with a new certificate as needed. If communication with the DSView 3 software is lost, the DSView 3 server will be unable to clear the certificate and the PM PDU cannot be used. Click the Clear DSView 3 Certificate button to configure the PM PDU in Trust All mode.

To configure DSView 3 software security settings:

1.

Select System - Security - DSView 3.

2.

Click the Allow appliance to be managed by DSView 3 checkbox and click Save.

Bootp Configuration Retrieval

You can set your PM PDU to be reconfigured during boot or at IP renewal.

To reconfigure a PDU via bootp:

1.

Click System Tools-Save Configuration and save the configuration to either an FTP site or locally.

-or-

Use the list_configuration command to get the CLI template scripts, edit the configuration of the PDU and save it as a text file.

2.

Transfer the saved file to a DHCP server.

3.

Click System-Security-Security Profile. Under the Bootp Configuration Retrieval heading, ensure the box next to Enabled is checked.

4.

Uncheck the box next to Enable Live Configuration. The saved configuration will be retrieved and applied on the next reboot.

-or-

Ensure the box next to Enable Live Configuration is checked. The saved configuration will be retrieved and applied on the next IP renewal.

NOTE: You must configure your DHCP server in order to transfer the configuration file to your PM PDU.

Date and Time

The PM PDU provides two options for setting the date and time. It can retrieve the date and time from a network time protocol (NTP) server, or you can set the date and time manually so that the PM PDU’s internal clock is used to provide time and date information.

NOTE: The Current Time displayed in the Date & Time screen shows only the time when the screen was opened. It does not continue to update in real time.

28  Avocent PM PDU Installer/User Guide

To set the time and date using NTP:

1.

Click System - Date And Time.

2.

Select Enable network time protocol.

3.

Enter the NTP server site of your choice and click Save.

To set the time and date manually:

1.

Click System - Date And Time.

2.

Select Set manually.

3.

Using the drop-down menus, select the required date and time and click Save.

To set the time zone using a predefined time zone:

1.

Click System - Date And Time - Time Zone.

2.

Select Predefined.

3.

Select the required time zone from the drop-down menu and click Save.

To define custom time zone settings:

1.

Click System- Date And Time - Time Zone.

2.

Select Define Time Zone.

3.

Enter the Time Zone Name and Standard Time Acronym of your choice.

4.

Enter the GMT Offset.

5.

Select Enable daylight savings time if needed.

6.

Select or enter the required values for daylight savings time settings and click Save.

Help and Language

Click System - Help And Language and use the drop-down menu to select the PM PDU’s language. Enter the full URL of the online help, ending in /index.html, on the local web server in the Online Help URL field. Click Save.

Online help

When the online help feature is configured for your PM PDU, clicking the Help button from any form on the web manager opens a new window and redirects its content to the configured path for the online help product documentation.

NOTE: Using the online help feature from the Avocent/Cyclades server is not always possible due to firewall configurations, nor is it recommended. It is generally advisable for you to use the online help system provided with the product or download the online help .zip file and run it from a local server.

Chapter 3: Accessing a PM PDU via the Web Manager 29

The system administrator can download the online help from Avocent. For more information on downloading the online help, contact Technical Support.

Once the online help file is obtained (in zip format), the files must be extracted and put in to a user-selected directory under the web server’s root directory. The web server must be publicly accessible.

Boot Configuration

Boot configuration defines the location from which the PM PDU loads the operating system.

The PM PDU can boot from its internal firmware or from the network. By default, the PM PDU boots from Flash memory. Clicking System- Boot Configuration will display the Boot

Configuration screen.

If you need to boot from the network, make sure the following prerequisites are met:

• A TFTP or BootP server must be available on the network

• An upgraded PM PDU boot image file must be downloaded from Avocent and made available on the TFTP or BootP server

• The PM PDU must be configured with a fixed IP address

• The boot filename and the IP address of the TFTP or BootP server is known

To configure boot configuration:

1.

Click System - Boot Configuration.

2.

Under Boot Mode, select From Flash, and select Image 1 or Image 2.

-or-

Select From Network and enter the following information:

• Appliance IP Address: Enter the fixed IP address or a DHCP assigned IP address to the

PM PDU.

• TFTP Server IP: Enter the IP address of the TFTP boot server.

• Filename: Enter the filename of the boot firmware.

3.

Using the drop-down menu, select whether the Watchdog Timer is enabled. If the

Watchdog Timer is enabled, the PM PDU reboots if the software crashes.

4.

Using the drop-down menu, select one of the following speeds for Ethernet 0: 100BT full,

100BT half, 10BT full, 10BT half or Auto. Click Save.

NOTE: Ethernet Mode will be affected after saving. The rest of the configuration will be applied after rebooting.

30  Avocent PM PDU Installer/User Guide

Information

Click System-Information to view the PM PDU’s identity, versions and CPU information.

Usage

Click System-Usage to view memory and Flash usage.

Network

Click Network to view and configure the network options for Hostname, DNS, IPv6, IPv4 and

IPv6 static routes, Hosts, Firewall and SNMP.

Settings

Click Network - Settings to make changes to the configured network settings.

Devices

An administrator can select, enable and configure the IP addresses assigned to the network interface and view the MAC address. A PM PDU has a single eth port and cannot have any plugged in eth port.

To configure a network device:

1.

Select Network - Devices. The Devices screen appears with a list of network interfaces and their status (enabled or disabled).

2.

Click the name of the network device to configure.

3.

Select the status (either Enabled or Disabled) from the drop-down menu.

4.

Select one of the following IPv4 method options:

• Select DHCP to have the IPv4 IP address set by the DHCP server.

• Select Static to enter the IPv4 IP address and subnet mask manually.

• Select IPv4 address unconfigured to disable IPv4.

5.

Select one of the following IPv6 method options:

• Select Stateless if the link is restricted to the local IP address.

• Select DHCPv6 to have the IPv6 IP address set by the DHCP server.

• Select Static to enter the IPv6 IP address and prefix length manually.

• Select IPv6 address unconfigured to disable IPv6.

6.

Select the Ethernet Mode for the built-in interface (ETH0).

Chapter 3: Accessing a PM PDU via the Web Manager 31

NOTE: The MAC Address for the device will be displayed after this option.

IPv4 and IPv6 static routes

An administrator can select Network - IPv4 Static Routes or IPv6 Static Routes to configure static routes.

To add static routes:

1.

Select Network - IPv4 Static Routes or IPv6 Static Routes. Any existing static routes are listed with their Destination IP/Mask, Gateway, Interface and Metric values shown.

2.

Click Add.

3.

Select Default to configure the default route.

-or-

Select Host IP Or Network to enter custom settings for Destination IP/Mask.

Enter the required Destination IP/Mask Bits with the syntax <destination IP>/<CIDR> in the Destination IP/Mask Bits field.

4.

Enter the IP address of the gateway in the Gateway field.

5.

Enter the number of hops to the destination in the Metric field, then click Save

Hosts

An administrator can configure a table of host names, IP addresses and host aliases for the local network.

To add a host:

1.

Select Network - Hosts.

2.

Click Add to add a new host.

3.

Enter the IP address, hostname and alias of the host you want to add, then click Save.

To edit a host:

1.

Select Network - Hosts.

2.

Click on the IP address of the hostname you want to edit.

3.

Enter a new hostname and alias, as applicable, then click Save.

Firewall

Administrators can configure the PM PDU to act as a firewall. By default, three built-in chains accept all INPUT, FORWARD and OUTPUT packets. Select the Add, Delete or Change Policy

32  Avocent PM PDU Installer/User Guide buttons to add a user chain, delete user added chains and to change the built-in chains policy.

Default chains can have their policy changed (Change Policy) to accept or drop, but cannot be deleted. Clicking on the Chain Name allows you to configure rules for chains.

Firewall configuration is available by clicking Network - Firewall. Separate but identical configuration screens are available from either the IPv4 Filter Table or IPv6 Filter Table menu options.

Only the policy can be edited for a default chain; default chain policy options are ACCEPT and DROP.

When a chain is added, only a named entry for the chain is created. One or more rules must be configured for a chain after it is added.

Configuring the firewall

For each rule, an action (either ACCEPT, DROP, RETURN, LOG or REJECT ) must be selected from the Target pull-down menu. The selected action is performed on an IP packet that matches all the criteria specified in the rule.

If LOG is selected from the Target pull-down menu, an administrator can configure a Log

Level, a Log Prefix and whether the TCP sequence, TCP options and IP options are logged in the Log Options Section.

If REJECT is selected from the Target pull-down menu, an administrator can select an option from the Reject with pull-down menu; the packet is dropped and a reply packet of the selected type is sent.

Protocol options

Different fields are activated for each option in the Protocol pull-down menu.

• If Numeric is selected from the Protocol menu, enter a Protocol Number in the text field.

• If TCP is selected from the Protocol menu, a TCP Options Section is activated for entering source and destination ports and TCP flags.

• If UDP is selected from the Protocol menu, the UDP section is activated for entering source and destination ports.

Table 3.3: Firewall Configuration - TCP and UDP Options Fields

Field/Menu Option Definition

Source Port - or - Destination Port

A single IP address or a range of IP addresses.

Chapter 3: Accessing a PM PDU via the Web Manager 33

Field/Menu Option

TCP Flags

Definition

[TCP only] SYN (synchronize), ACK (acknowledge), FIN (finish), RST (reset),

URG (urgent) and PSH (push). The conditions in the pull-down menu for each flag are: Any, Set or Unset.

• If ICMP is selected from the Protocol menu, the ICMP Type pull-down menu is activated.

• If an administrator enters the Ethernet interface (eth0 or eth1) in the input or output interface fields and selects an option (2nd and further packets, All packets and fragments or Unfragmented packets and 1st packets) from the Fragments pull-down menu, the target action is performed on packets from or to the specified interface if they meet the criteria in the selected Fragments menu option.

To add a chain:

1.

Select Network - Firewall.

2.

Select either IPv4 Filter Table or IPv6 Filter Table as needed.

3.

Click Add.

4.

Enter the name of the chain to be added.

5.

Click Save.

NOTE: Spaces are not allowed in the chain name.

6.

Add one or more rules to complete the chain configuration.

To change the policy for a default chain:

NOTE: User-defined chains cannot be edited. To rename a user-added chain, delete it and create a new one.

1.

Select Network - Firewall.

2.

Select either IPv4 Filter Table or IPv6 Filter Table as needed.

3.

Select the checkbox next to the name of the chain you want to change (FORWARD,

INPUT, OUTPUT).

4.

Click Change Policy and select Accept or Drop from the drop-down menu.

5.

Click Save.

To add a rule:

1.

Select Network - Firewall.

2.

Select either IPv4 Filter Table or IPv6 Filter Table as needed.

3.

From the chain list, click the name of the chain you want to add a rule to.

34  Avocent PM PDU Installer/User Guide

4.

Click Add and configure the rule as needed, then click Save.

To edit a rule:

1.

Select Network - Firewall.

2.

Select either IPv4 Filter Table or IPv6 Filter Table as needed.

3.

From the chain list, click the name of the chain with the rule you want to edit.

4.

Select the rule you want to edit and click Edit.

5.

Modify the rule as needed and click Save.

SNMP configuration

An administrator can configure SNMP, which is needed if notifications are to be sent to an

SNMP management application.

To configure SNMP:

1.

Click Network - SNMP.

2.

Click the System button.

a.

Enter the SysContact information (email address of the PM PDU’s administrator, for example, [email protected]).

b.

Enter the SysLocation information (physical location of the PM PDU, for example,

Avocent_pmpdu), then click Save to go back to the SNMP screen.

3.

Click Add to add a new community or v3 user.

4.

Enter the community name for SNMP v1/v2 or the user name for SNMP v3 in the Name field and enter the OID.

5.

Select the desired permission from the pull-down menu. Choices are Read and Write or

Read Only.

6.

If the required SNMP version is v1 or v2, click the Version v1, v2 button, then enter the source (valid entry is the subnet address).

-or-

If the required SNMP version is v1 or v2 using an IPv6 network, click the Version

v1,v2 for IPv6 network button, then enter the source (valid entry is the subnet address).

-or-

If the required SNMP version is v3, click the Version v3 button, then select the

Authentication Type (MD5 or SHA), enter the authentication passphrase or password,

Chapter 3: Accessing a PM PDU via the Web Manager 35 enter the privacy passphrase for DES and select the Minimum Authentication Level

(NoAuthNoPriv, AuthNoPriv, AuthPriv).

7.

Click SaveSNMP Configuration.

Authentication

Authentication can be performed locally, with OTP, or on a remote Kerberos, LDAP, NIS,

Radius or TACACS+ authentication server. If the PM PDU is managed by a DSView 3 server,

DSView 3 authentication is also supported. The PM PDU also supports remote group authorizations for the LDAP, Radius and TACACS+ authentication methods.

Fallback mechanisms of the following types are available:

Local authentication can be tried first, followed by remote, if the local authentication fails

(Local/Remote_Method)

-or-

Remote authentication may be tried first, followed by local (Remote_Method/Local)

-or-

Local authentication may be tried only if a remote authentication server is down (Remote_

Method_Down_Local).

An administrator can configure authentication using the CLI utility and the web manager. The default authentication method for the PM PDU is Local. Any authentication method that is configured for the PM PDU is used for authentication of any user who attempts to log in through Telnet, SSH or the web manager.

Appliance authentication

Select Appliance Authentication to configure the authentication method used to log in to the

PM PDU with access to all allowed operations in the appliance, PDUs and outlets.

To set authentication for the PM PDU:

1.

Click Authentication - Appliance Authentication.

2.

Select the desired authentication server from the Authentication Type drop-down menu.

3.

Click Save.

Authentication servers

When using an authentication server, you must configure its IP address and in most cases other parameters before it can be used. The following authentication servers require configuration:

36  Avocent PM PDU Installer/User Guide

RADIUS, TACACS+, LDAP(S)|AD, Kerberos, NIS and DSView 3 servers.

To configure a RADIUS authentication server:

1.

Select Authentication - Authentication Servers - RADIUS.

2.

Enter the IP addresses of the First Authentication Server and First Accounting Server.

3.

If used, enter the IP addresses for the Second Authentication Server and Second Accounting

Server.

4.

Enter your secret word or passphrase in the Secret field (applies to both first and second authentication and accounting servers), then re-enter the secret word or passphrase in the

Confirm Secret field.

5.

Enter the desired number of seconds for server time-out in the Timeout field.

6.

Enter the desired number of retries in the Retries field.

7.

If you select the Enable Service-Type attribute to specify the authorization group checkbox, enter the authorization group name for each of the following Service Types:

Login, Framed, Callback Login, Callback Framed, Outbound and Administrative.

8.

Click Save.

To configure a TACACS+ authentication server:

1.

Select Authentication - Authentication Servers - TACACS+.

2.

Enter the IP addresses for the First Authentication Server and First Accounting Server.

3.

If used, enter the IP addresses of the Second Authentication Server and Second Accounting

Server.

4.

Select the desired service (PPP or raccess) from the Service drop-down menu.

5.

Enter your secret word or passphrase in the Secret field (applies to both first and second authentication and accounting servers), then re-enter the secret word or passphrase in the

Confirm Secret field.

6.

Enter the desired number of seconds for server time-out in the Timeout field.

7.

Enter the desired number of retries in the Retries field.

8.

If you select the Enable User-Level attribute of Shell and raccess services to specify the

authorization group checkbox, enter the authorization group name for up to 15 User-

Levels.

9.

Click Save.

Chapter 3: Accessing a PM PDU via the Web Manager 37

To configure an LDAP(S)|AD authentication server:

1.

Select Authentication - Authentication Servers - LDAP(S)|AD.

2.

Enter the IP address of the server.

3.

Enter the Base.

4.

At the Secure drop-down menu, select Off, On or Start_TLS.

5.

Enter the Database User Name.

6.

Enter your Database Password, then re-type the database password in the Confirm Password field.

7.

Enter your desired Login Attributes.

8.

Click Save.

To configure a Kerberos authentication server:

1.

Select Authentication - Authentication Servers - Kerberos.

2.

Enter the IP address (Realm) of the server.

3.

Enter the Realm Domain Name (example: avocent.com).

4.

Enter the Domain Name (example: avocent.com).

5.

Click Save.

To configure an NIS authentication server:

1.

Select Authentication - Authentication Servers - NIS.

2.

Enter the NIS Domain Name of the server (example: corp.avocent.com).

3.

Enter the NIS Server Address or broadcast (default is broadcast).

4.

Click Save.

To configure a DSView 3 authentication server:

1.

Select Authentication - Authentication Servers - DSView 3.

2.

Enter IP Address 1 - 4 for the DSView 3 servers in the relevant fields.

3.

Click Save.

Users

There are three standard local user account types supported on a PM PDU: admin, root and user.

38  Avocent PM PDU Installer/User Guide

Local accounts

The admin and root accounts are equivalent users but named differently to address users familiar with either Avocent or Cyclades equipment. Regular users can be granted permissions by administrators at any time. The PM PDU has three user account types:

• admin: Performs the initial network configuration. The factory default password for admin is avocent. The admin user is a member of the admin group and can configure the PM PDU as well as user and group authorizations.

• root: Has the same permissions as the admin user. The factory default password for root is

linux. In the PM PDU, the root user is a member of the admin group and shell-login-profile groups. When a root user logs in via the CONSOLE port, SSH or telnet, the session is predefined by the login profile to go directly to shell. The login profile can be customized so that it does not go directly to shell.

NOTE: Change the default passwords for root and admin before you put the PM PDU into operation.

• Administrator-added regular users: Have limited access to the web manager features based on the group(s) to which they are assigned. Users can change their own passwords.

To add new users:

1.

Click Users - Local Accounts - User Names. The User Names screen is displayed with a list of all users.

2.

Click Add The Local User Information screen is displayed.

3.

Enter the new username and enter a password, then confirm the password.

4.

Select or deselect User must change password at the next login checkbox.

5.

If you wish to add the user to an available user group, select the user group name in the box on the left and click Add (user is the default group). You can remove a user group from the box at right by selecting it and clicking Remove.

6.

Enter the desired parameters for Password Expiration.

• Min Days: Enter the minimum number of days allowed between password changes.

Password changes attempted sooner will be rejected. If not specified, -1 is the default which disables the restriction.

• Max Days: Enter the maximum number of days a password is valid. After this period, a password change will be forced. If not specified, -1 is the default which disables the restriction.

Chapter 3: Accessing a PM PDU via the Web Manager 39

• Warning Days: Enter the number of days that a warning is issued to the user prior to expiration. Entering 0 will cause the warning to be issued on the expiration day. A negative value or no value means that no warning will be issued.

7.

Enter the desired Account Expiration date (YYYY-MM-DD).

8.

Click Save.

To delete users:

1.

Click Users - Local Accounts - User Names. The User Names screen is displayed with a list of all users.

2.

Check the box next to the user to be deleted.

3.

Click Delete. A confirmation box appears. Click OK.

To configure password rules:

1.

Click Users - Local Accounts - Password Rules.

2.

If password complexity is desired (recommended), make sure Check Password Complexity is selected.

3.

If password complexity is enabled, enter the desired values for password complexity.

4.

Enter the desired values for Default Expiration.

5.

Click Save.

Authorization

There are three default user groups on a PM PDU:

• admin

• admin-appliance

• user

User groups are given access and authorizations either by default or as assigned by an administrator. Administrators can alter the permissions and access rights of users belonging to the appliance-admin or user groups or create additional groups with custom permissions and access rights. Administrators can add, delete or modify permissions and access rights for users from any group at any time.

admin group

Members of the admin group have full administrative privileges that cannot be changed.

Administrators can add users and manage outlets connected to the PM PDU.

NOTE: The only configuration allowed for the admin group is adding or deleting regular users.

40  Avocent PM PDU Installer/User Guide

To view admin Appliance Access Rights:

1.

Click Users - Authorization - Groups. The Group Names screen is displayed, showing the three default user groups along with any groups that have been created.

2.

Click on admin under the Group Name heading. The content area will display the

Members screen listing all members belonging to the admin group (default members are admin and root users).

NOTE: When any Group Name is selected, both the content area and Side Navigation Bar change. The Side

Navigation Bar will display specific menu options for Members and Access Rights (which include Power and

Appliance rights).

3.

In the Side Navigation Bar, click Poweror Applianceto access the screens displaying the fixed access rights and permissions for members of the admin group pertaining to power management and appliance management.

NOTE: The Power screen is read-only and cannot be changed.

4.

In the Side Navigation Bar, click on Access Rights - Appliance. The Appliance Access

Rights screen appears and lists all access rights available to a member belonging to the admin group. All appliance access rights are shown enabled (checked). Available appliance access rights are:

• View Appliance Information

• Disconnect Sessions and Reboot Appliance

• Appliance Flash Upgrade and Reboot Appliance

• Configure Appliance Settings

• Configure User Accounts

• Backup/Restore Configuration

• Shell Access

• Transfer Files

NOTE: The Appliance Access Rights screen for the admin and appliance-admin user groups is read-only and cannot be changed. Unchecking any box and clicking Save will result in an error message. The PM PDU will maintain all rights selected.

appliance-admin group

Members of the appliance-admin group have access restricted to tasks for managing only the appliance. Appliance-admin user group members have no access to power management options,

Chapter 3: Accessing a PM PDU via the Web Manager 41 and share all of the appliance access rights as admin except for Configure User Accounts and

Shell Access, which are permanently disabled for this group.

user group

Members of the user group have access to target devices unless they are restricted by an administrator but have no access rights for the PM PDU. Administrators can add appliance access rights and permissions, or can add users to custom user groups to add permissions and access rights as needed. By default, all selections on the Appliance Access Rights screen will be disabled.

NOTE: The Appliance Access Rights screen for the user group can be changed at any time by an administrator.

This will change the access rights for all members of the PM PDU’s user group.

Event and Logs

The PM PDU will generate notifications for a wide variety of events. You can configure it to direct or store those event notifications to various destinations for immediate use or for analysis later.

Event List

The Event List screen lists PM PDU events, each of which can be configured for SNMP Traps,

Syslog, DSView 3 software, Email and SMS.

To configure Events:

1.

Click Events and Logs - Events.

2.

Locate the events for which you want notification sent and select the checkbox(es) next to the event number(s).

3.

Click Edit.

4.

If you want an event notification sent for any configured event destination type, click its associated Send checkbox.

5.

Click Save. The Events page appears with an X in the column below the destination type if the Send box was checked on the Events Settings screen.

Event Destinations

To configure Event Destinations:

1.

Click on Event and Logs - Event Destinations.

2.

Under the Syslog heading, use the drop-down menu to select the Facility.

42  Avocent PM PDU Installer/User Guide

3.

Select Remote Server - IPv4 to enable syslog messages to be sent to one or more remote

IPv4 syslog servers, and enter the IPv4 Address or Hostname. Separate multiple server addresses by commas.

-or-

Select Remote Server - IPv6 to enable syslog messages to be sent to one or more remote IPv6 syslog servers, and enter the IPv6 Address or Hostname. Separate multiple server address by commas.

4.

Select Appliance Console to send messages to the PM PDU’s console.

5.

Select Root Session to send syslog messages to all sessions where you are logged in as root user.

6.

Under the SNMP Trap heading, enter the name of the community defined in one or more of the SNMP trap servers in the Community field then enter the IP addresses of up to five servers in the server fields.

7.

Under the SMS heading, enter the SMS Server, Port and Pager Number information in the appropriate fields.

8.

Under the Email heading, enter the Server, Port and Destination Email information in the appropriate fields.

9.

Under the DSView 3 heading, enter the IP address of the DSView 3 server where event notifications will be sent in the DSView 3 server field. Enter the syslog server port number for the DSView 3 server, the SSH information and the buffer warning information in the appropiate fields.

10. Click Save.

Data Buffering

To configure Data Buffering:

1.

Select Events and Logs - Data Buffering.

2.

Enter the segment size in kilobytes and spare segments in the Local Data Buffering

Settings section.

3.

In the NFS Data Buffering Settings section, enter the following information: NFS Server,

NFS Path, Segment Size (Kbytes) and Spare Segments.

NOTE: RPC service must be enabled in the Security Profile screen before configuring NFS Data Buffering

Settings. NFS does not support IPv6.

Chapter 3: Accessing a PM PDU via the Web Manager 43

4.

To configure data buffer storage on a syslog server in the Syslog Data Buffering Settings section; select a facility number from the drop-down menu: Log Local 0, Log Local 1, Log

Local 2, Log Local 3, Log Local 4 or Log Local 5.

5.

Click Save.

Appliance Logging

To configure Appliance Logging:

1.

Click Enable appliance session data logging.

a.

Select the destination for appliance session data logs from the pull-down menu.

Choices are Local, NFS, Syslog and DSView 3.

b.

Enable or disable timestamping the appliance session data logs.

2.

Click Enable appliance session data logging alerts.

3.

Enter the desired alert strings (up to ten) in the fields provided.

4.

Click Save.

Active Sessions

The PM PDU allows multiple users to log in and run sessions simultaneously. The Active

Sessions feature allows you to view all active sessions and to kill any unwanted sessions. Click

Active Sessions to view all open sessions on the PM PDU.

NOTE: If you start another session with the PM PDU while viewing this screen, it will not be visible until you click

Refresh at the top of the web manager window.

To kill an active session:

1.

Click Active Sessions. The Active Sessions screen appears and lists all open sessions to the

PM PDU by the user’s workstation IP.

2.

Select the checkbox next to the session you want to kill, then click the Kill button. After a few seconds, the Active Session screen will redisplay the open sessions, minus the one you killed.

Monitoring

When you click Monitoring, a variety of network and console port information is available for viewing. The screens are only for viewing and have no interactivity with the user. The following table shows the types of information available.

44  Avocent PM PDU Installer/User Guide

Table 3.4: Monitoring Screens

Screen Name Definition

Network - Devices

Shows Ethernet status (enabled/disabled), IPv4 Address, IPv4 Mask and IPv6

Address.

Network - IPv4 Routing Table Shows Destination, Gateway, Genmask, Flags, Metric, Ref, Use and lface.

Network - IPv6 Routing Table Shows Destination, NextHop, Flags, Metric, Ref, Use and lface.

Serial Ports

Shows Device Name, Profile, Settings, Signals, TX Bytes, RX Bytes, Frame

Error, Parity Error, Break and Overrun.

Change Password

An admin or user can change his or her own password from this screen.

To change your own password:

1.

Select Change Password.

2.

Enter the old password and new password in the appropriate fields.

3.

Confirm the new password, then click Save.

Web Manager Overview for Regular Users

The following figure shows features of the web manager for a regular user.

Chapter 3: Accessing a PM PDU via the Web Manager 45

Figure 3.3: Web Manager Regular User Screen

Table 3.5: Web Manager Regular Users Screen Functional Areas

Number Description

1

Top option bar. The name of the appliance and the name of the logged in user appears on the left side and Refresh, Print, Logout and Help buttons appear on the right.

2

3

Side Navigation Bar. Menu options appear that are available for regular users.

Content area. Contents change based on the options selected in the side navigation bar.

The following table provides an overview of the options for regular users.

Table 3.6: Web Manager Options for Regular Users

Menu Option Description

Access

Displays all the devices the user can access. Click Appliance Viewer in a device’s

Action column to launch a terminal session with that device.

46  Avocent PM PDU Installer/User Guide

Menu Option

Power Management

PDUs

Outlet Groups

Change Password

Description

Click PDUs to turn on, turn off, cycle, reboot, reset the HW overcurrent protection, return to factory defaults or rename PDUs connected to the PM PDU.

Click Outlet Groups to manage groups of outlets on connected PDUs.

Change your own password.

4

Accessing a PM PDU via the

Command Line Interface

Access Options and How to Log Into the CLI

The CLI utility can be accessed in the following ways:

• Through a local terminal or a computer that has a terminal emulation program connected to the console port of the console server with session settings of 9600, 8, N and 1, with no flow control.

• After the PM PDU is connected to the network and has an IP address, it can be accessed by one of the following methods:

• An SSH or Telnet client on a remote computer (if the SSH or Telnet protocol is enabled in the selected Security Profile).

• By selecting Web Manager - Overview - Appliance Session.

• With DSView 3 software.

Administrators have full access to the CLI and to connected devices. An administrator can authorize regular users to manage power, manage data buffer storage and use one or more PM

PDU administration tools. Users can always change their own passwords.

To start the CLI:

1.

Access the CLI through the console port, with Telnet or SSH or through the web manager.

2.

Type the username and password at the prompt. The cli-> prompt appears.

Welcome to Avocent PM PDU <host name>.

Type help for more information

--:- / cli->

NOTE: The default password for admin is avocent and for root is linux. The password for these users may have been changed during installation of the PM PDU. If not, change the default root and admin passwords to avoid potential security breaches.

47

48  Avocent PM PDU Installer/User Guide

To disable the shell prompt:

By default, logging in as root will display the shell prompt instead of the CLI prompt. To disable this, perform the following steps:

1.

Log into the CLI as admin .

2.

Type cd/users/local_accounts/user_names/root and press enter .

--:-/cli-> cd/users/local_accounts/user_names/root

3.

Type set user_group=admin and press enter .

--:-root cli-> set user_group=admin

4.

Type commit and press enter .

**:-root cli-> commit

Configuration Tasks Performed With the CLI

The navigation structure of the CLI mirrors that of the web manager. Options and parameters are also the same, except that spaces in web manager options and parameters are replaced with underscores (_), as in: system_tools. Examples that show how to select an option in the web manager use a dash surrounded by two spaces ( - ). In the CLI, two similar options in a path are separated by a forward slash (/).

For example, in the web manager, user configuration is done when an administrator selects

Users - Local Accounts - User Names to get to the User Names screen. To navigate to the equivalent configuration level in the CLI, an administrator would use the cd command followed by the path: cd /users/local_accounts/user_names.

Administrators should log into the CLI in one window and log into the web manager in another window to see how the menu options in the web manager map to the navigation options in the CLI.

CLI Navigation

The CLI navigation options are in a nested tree configuration.

NOTE: When a command line is shown in an example, and the step starts with “Enter,” or when a syntax example is given, the user should type the command as shown and then press Enter. The Enter key is not shown in command line examples unless needed for clarity.

When a user logs in the CLI, the prompt indicates the user is at the / level.

--:- / cli->

No parameters can be set at this level of the navigation tree.

Chapter 4: Accessing a PM PDU via the Command Line Interface 49

At any CLI prompt at any level, if you type cd and press Tab Tab, the navigation options

(path elements) for that level are listed. Different options appear for administrators and for authorized users.

• When an administrator types the cd command and then presses Tab Tab at the / prompt, the following navigation options (path elements) appear.

--:- / cli-> cd<Tab><Tab> access/ change_password/ network/ system_tools/ active_sessions/ events_and_logs/ power_management/ users/ authentication/ monitoring/ system/

• When a regular user types the cd command and then presses Tab Tab at the / prompt, the following navigation options appear.

--:- / cli-> cd<Tab><Tab> access/ power_management/ change_password/

Enter cd <one_or_more_path_elements> to move down one or more levels of the navigation tree.

--:- / cli-> cd system_tools

A prompt like the following appears at each level.

--:- system_tools cli->

NOTE: CLI commands are case sensitive.

At any level, you can press Tab Tab at the prompt to see the commands that can be entered at the current level.

---:- system_tools cli->< Tab><Tab> cd passwd shell commit pwd show exit quit shutdown ftp reboot upgrade_firmware help restore_configuration whoami hostname revert wiz ls save_configuration opiepasswd scp

If you know the path, you can enter multiple path elements in a single command separated with forward slashes (/).

--:- / cli-> cd network/devices/

50  Avocent PM PDU Installer/User Guide

--:- devices cli->

Enter cd.. to move up one level of the navigation tree. Enter cd ../..[/..] to move up multiple levels.

--:- devices cli-> cd ../..

--:- / cli->

Autocompletion

Autocompletion allows you to type the first few letters of a command or navigation option and then press Tab. The rest of the name is filled in automatically if the letters typed are unique to one command or to a navigation option at that level. If the letters match more than one of the commands or navigation options for that level, the matching options are listed.

For example, if you type cd acc and press Tab at the CLI prompt from the / level, the access option will be completed.

--:- / cli-> cd acc<Tab>

--:- / cli-> cd access

If you then press Enter, you are changed to the access level and the access level prompt appears.

--:- access cli->

The following example illustrates a case when more than one command matches the letters typed.

--:- / cli-> sh<Tab> shell show

Parameters

Some CLI commands take parameters. If you press Tab Tab after a command that requires a parameter, you are prompted to enter the parameter.

Command Line Syntax

NOTE: Square brackets ([ ]) denote an optional element. Each element is separated by a space. There are no spaces between sub-elements.

Command only (help, pwd):

--:- <current_level> cli-> <command>

Commands with paths only (cd, ls, add):

--:- <current_level> cli-> <command> [Path]

Chapter 4: Accessing a PM PDU via the Command Line Interface 51

Commands with targets (del):

--:- <current_level> cli-> <command> [Path] <Targets>

Commands that require parameters (set):

--:- <current_level> cli-> <command> [Path] <Params>

Commands with values only (sendmsg, ftp...):

--:- <current_level> cli-> <command> [Path] <Values> where:

Path := path_elem[/path_elem]* path_elem := . | .. | Section_Label | ^/

Targets := Row_Label(,Row_Label)

Params := Param_Names=PValues

Param_Names := Param_Label(:Param_Label)*

PValues := Value_text(,Value_text)*

Values := Value_text Value_text

Section_Label

Param_Label

Value_text := labels or data from the UIC.

Syntax used:

^ : beginning of the element

* : 0 - many

| : or

() : group

CLI Command Set

This section describes the general commands used when accessing the PM PDU via the command line interface.

NOTE: Most of the commands work from any location when the path to the command parameter is included.

NOTE: The word “node” refers to an entity such as a route, host or user, which can be added, configured or deleted.

help

Generate a help message about how to navigate the CLI.

Syntax:

--:- / cli-> help

- Thank you for using the cli -

52  Avocent PM PDU Installer/User Guide

This interface allows you to easily modify configurations to customize and define the functionality of your unit.

Press <tab> <tab> to see the list of available commands.

Please refer to the Reference Guide for a description of commands, special keys and additional information on how to use this interface.

Some basic and useful keys are: up/down arrow - navigates up/down in the command history tab (once/twice) - shows the next possible option(s)

Other hints:

Use backslash '\' to escape spaces, '\' and other control characters when assigning values to parameters.

add delete

Delete a node.

Syntax:

--:- / cli-> delete <Path> <parameter>

cd

Add a node.

Syntax:

--:- / cli-> add <Path>

Example:

--:- / cli-> add network/hosts

--:#- [hosts] cli->

Change directory (level).

Syntax:

--:- / cli-> cd <Path>

Example:

--:- / cli-> cd access

Chapter 4: Accessing a PM PDU via the Command Line Interface 53

Displays the following:

--:- access cli->

Example:

--:- access cli-> cd ..

-or-

--:- access cli-> cd ../

Moves up one directory level and displays the following:

--:- / cli->

Example:

--:- access cli-> cd /

Moves to the top level and displays the following:

--:- / cli->

Example:

--:- access cli-> cd /information

Displays the following:

--:- information cli->

pwd

Display the path to the current level (print working directory).

Syntax:

--:- / cli-> pwd

exit/quit

Exit the CLI and return to the login prompt.

Syntax:

--:- / cli-> exit

-or-

--:- / cli-> quit

ftp

Connect to a remote FTP server.

Syntax:

--:- / cli-> ftp [<server_IP_address>|<hostname>]

NOTE: You must log into the CLI as root to have full control over the local directory path. All normal FTP commands apply.

54  Avocent PM PDU Installer/User Guide

scp

Perform a secure shell copy.

Syntax:

--:- / cli-> scp [[user @]host1:]file1 [...] [[user@]host2:]file2

set

Set a parameter.

Syntax:

--:- / cli-> set <Path> <Parameter>=<Value>

After a parameter has been changed using the set command, a pair of asterisks appear at the beginning of the CLI prompt.

**:- / cli->

Save the change:

**:- / cli-> commit

-or-

Undo the change:

**:- / cli-> revert

NOTE: After a commit or revert command, the asterisks at the beginning of the CLI prompt are replaced by hyphens. Asterisks will not appear after the execution of the set command if using wizard mode, which can be recognized by a prompt that has a pound sign after the colon and the current directory in square brackets (example,

--:#- [hosts] cli->).

commit

Save settings.

Syntax:

**:- settings cli-> commit

revert

Undo a previous parameter setting.

Syntax:

**:- / cli-> revert

show/ls

Show the available directories, commands or parameters at the current location.

Chapter 4: Accessing a PM PDU via the Command Line Interface 55

Syntax:

--:- / cli-> show

-or-

--:- / cli-> ls

Example:

--:- / cli-> show user_profile user_profile change_password/

--:- / cli->

cycle, on, off, lock and unlock

Control power on outlets on a PDU.

NOTE: Enter commas (,) between multiple outlets or use a hyphen to specify a range (1-4).

--:- / cli-> cd power_management/pdus/<PDU_ID>/outlets

--:- outlets cli-> [cycle|on|off|lock|unlock] <outlet_number[,..,outlet_ number]>

Examples:

--:- / cli-> cd power_management/pdus/myPDU/outlets

--:- outlets cli-> off 1,2,5,8

Are you sure you want to turn off the outlet(s)? y/n : y

The cycle, on and off commands can be used from the access level, where they are enabled and configured with the Power Profile.

--:- / cli -> [cycle|on|off] access/<PDU_ID>

passwd

Configure the password for the current user. The terminal does not echo the password.

Syntax:

--:- / cli-> passwd

opiepasswd

Configure a one time password (OTP) for the local user. After you type the command, you will be asked for the pass phrase to use for the OTP.

Syntax:

--:- / cli-> opiepasswd

56  Avocent PM PDU Installer/User Guide

Example: opiepasswd -f -c teste

Adding teste:

Only use this method from the console; NEVER from remote. If you are using telnet, xterm, or a dial-in, type ^C now or exit with no password.

Then run opiepasswd without the -c parameter.

Using MD5 to compute responses.

Enter new secret pass phrase:

Again new secret pass phrase:

ID teste OTP key is 499 AC0241

FOOD HUGH SKI ALMA LURK BRAD

CLI Equivalent Actions to Web Manager Checkbox Selection

NOTE: The following example procedure, which configures IPv6, illustrates the actions to use in the CLI to enable or disable an option when a checkbox would be selected or deselected in the web manager.

To configure IPv6 (example of how to perform the equivalent of web manager checkbox selection/deselection):

1.

Log into the CLI and type cd network/settings .

--:- / cli-> cd network/settings

2.

Type show to view the status of IPv6 configuration.

--:- settings cli-> show hostname = PM1000-24-1024000004 primary_dns = 172.26.29.4

secondary_dns = domain = corp.avocent.com

enable_ipv6 = yes get_dns_from_dhcpv6 = no get_domain_from_dhcpv6 = no

NOTE: At this location, you can use '=' to change the value or '/' to select a parameter inside the section.

3.

Type set enable_ipv6= and press Tab to view the options for the parameter.

--:- ipv6 cli-> set enable_ipv6=<Tab> no yes

4.

Type set enable_ipv6 : and press Tab to view the child parameters.

--:- ipv6 cli-> set enable_ipv6 /<Tab> get_dns_from_dhcpv6= get_domain_from_dhcpv6=

Chapter 4: Accessing a PM PDU via the Command Line Interface 57

5.

Type set enable_ipv6=no to disable IPv6.

--:- ipv6 cli-> set enable_ipv6=no

-or-

Type set enable_ipv6=yes to enable IPv6.

--:- ipv6 cli-> set enable_ipv6=yes

6.

(Optional) Type either of the following commands to enable subparameters.

**:- ipv6 cli-> set enable_ipv6/ get_dns_from_dhcpv6=yes

**:- ipv6 cli-> set enable_ipv6/ get_domain_from_dhcpv6=yes

7.

Type show to verify the change.

**:- ipv6 cli-> show enable_ipv6 = yes get_dns_from_dhcpv6 = yes get_domain_from_dhcpv6 = yes enable_bonding = no

8.

Type commit .

CLI Overview for Administrators

This section describes using the Command Line Interface for administrators. Only administrators and authorized users can access the commands listed in this section. These procedures assume you have logged into the CLI as an administrator and are at the --:- / cli-> prompt.

NOTE: In the tables that show output from the show command, when an option that is followed by an equal sign (=) is left blank, that option is not assigned a value by default.

System

1.

Type cd system to navigate to the System level.

--:- / cli-> cd system

2.

Type show to view the available options.

--:- system cli-> ls security/ date_and_time/ help_and_language/ boot_configuration/ information/ usage/

58  Avocent PM PDU Installer/User Guide

3.

Type show followed by an option name to view information about each option.

--:- security cli-> show security_profile

System/Security

Type cd system/security to navigate to the security level.

--:- / cli-> cd system/security

Table 4.1: System/Security Options

System Navigation Tree security_profile idle_timeout= outlet_access_is_controlled_by_authorization_assigned_to_user_groups= rpc= security_profile= security_profile/ custom answer_icmp_message= enable_ftp_service= enable_http_session= enable_https_sessions= enable_snmp_service= enable_telnet_service= ssh_allow_root_access= ssh_tcp_port= ssh_version= enable_http_session

Chapter 4: Accessing a PM PDU via the Command Line Interface 59

System Navigation Tree http_port= enable_https_session= https_port= https_ssl_version= redirect_http|https= bootp_configuration_retrieval enabled= interface= enable_live_configuration_retrieval= dsview allow_appliance_to_be_managed_by_dsview=

System/Boot Configuration

Type cd system/boot_configuration to navigate to the boot_configuration level.

--:- / cli-> cd system/boot_configuration

Table 4.2: System/Boot Configuration Options

Boot Configuration Navigation Tree boot_mode= image= watchdog_timer= console_speed= eth0_mode=

System/Date and Time

Type cd system/date_and_time to navigate to the date_and_time level.

--:- / cli-> cd system/date_and_time

60  Avocent PM PDU Installer/User Guide

Table 4.3: Date and Time Options

Date and Time Navigation Tree date_and_time date_and_time settings manual day= hour= minute= month= second= year= time_zone predefined zone=set

System/Help and Language

Type cd system/help_and_language to navigate to the online_help level.

--:- / cli-> cd system/help_and_language

To set the online help URL:

Perform this procedure if you have downloaded the online help files to a web server that is accessible to the console server.

1.

Type the following command.

--:- / cli> cd system/help_and_language/

2.

Type the following command.

--:- help_and_language cli> set url=<online_help_location>

A line similar to the following appears.

**:- help_and_language cli>

3.

Save your settings.

Chapter 4: Accessing a PM PDU via the Command Line Interface 61

**:- help_and_language cli> commit .

Table 4.4: Help and Language Options

Help and Language Navigation Tree appliance_language= url=

System/Information

1.

Type cd system/information to navigate to the Information level.

--:- / cli> cd system/information/

2.

Type show to view the system information.

System/Usage

Type cd system/usage to navigate to the Usage level.

--:- / cli> cd system/usage/

Table 4.5: System/Usage Options

Usage Navigation Tree flash_usage memory

Network

IPv4 addresses are always enabled. An administrator can also enable IPv6 addresses at the

network/settings/ipv6 level. A procedure to enable IPv6 is used as an example in CLI

Equivalent Actions to Web Manager Checkbox Selection on page 56.

1.

Type cd network to navigate to the Network level

--:- / cli-> cd network/

2.

Type ls to view the list of available options.

settings/ devices/ ipv4_static_routes/

62  Avocent PM PDU Installer/User Guide ipv6_static_routes/ hosts/ firewall/ snmp/

Wiz command

The wiz command allows administrators to easily and quickly perform the initial network configuration of the eth0.

At the command prompt at the / level, enter wiz to view the current IP configuration. To change the IP configuration, press Tab to move through the parameters, and press Esc + Tab to edit the selected parameter. When you are finished, enter yes to confirm that all parameters are correct and to save the new parameters.

--:- / cli-> wiz current ipv4 address: 172.26.30.249

current ipv6 address: eth0: device_status = enabled ipv4_method = dhcp ipv4_address = 192.168.160.10

ipv4_mask = 255.255.255.0

ipv4_default_gateway = ipv6_method = ipv6_address_unconfigured ipv6_address = ipv6_prefix_length = ipv6_default_gateway = mac address: 00:e0:86:21:67:72 dns: primary_dns = 172.26.29.4

secondary_dns = domain = corp.avocent.com

hostname = PM3000-10-0011223344

Some basic and useful keys are:

- tab (once/twice) - shows the next possible commands/option(s)

- cntrl e - gets the current parameter value for editing

Other hints:

- Use backslash '\' to escape spaces, '\' and other control

Chapter 4: Accessing a PM PDU via the Command Line Interface 63 characters when assigning values to parameters.

current ipv4 address: 172.26.30.249

current ipv6 address: eth0: device_status (disabled, enabled) [enabled]:

Network/Settings

1.

Type cd network/settings to navigate to the Network settings level.

--:- / cli-> cd network/settings/

2.

Type show to view the list of available options.

Table 4.6: Network Options

Network Navigation Tree settings domain= enable_ipv6= hostname= primary_dns= secondary_dns= enable_ipv6 get_dns_from_dhcpv6= get_domain_from_dhcpv6=

Network/IPv4 and IPv6 Static Routes

The following table displays options for configuring IPv4 and IPv6 Static Routes.

Table 4.7: Network/IPv4 and IPv6 Static Routes Options

IPv4 and IPv6 Static Routes Navigation Tree ipv4_static_routes default_3

64  Avocent PM PDU Installer/User Guide

IPv4 and IPv6 Static Routes Navigation Tree gateway= interface= metric= ipv6_static_routes

Network/Devices

The procedure to configure a static IP address for the primary Ethernet interface is usually performed during installation so that administrators have a fixed IP address for access to the web manager and can finish configuration.

To configure a IPv4 or IPv6 static IP address:

NOTE: This procedure configures either an IPv4 or IPv6 static IP address for the ETH0 (eth0) port. You can configure an IPv6 static IP address only if IPv6 is enabled.

1.

Type cd network/devices/<eth0>/settings to navigate to the Settings level for the desired interface.

--:- / cli-> cd network/devices/eth0/

2.

Type set ipv<4|6>_method=static to set the method to static for IPv4 or IPv6.

**:- eth0 cli-> set ipv4_method=static

3.

Type set ipv<4|6>_method/static/ address=<IP_Address> mask=<netmask> to set the IP address and subnet mask then enter commit to save the change.

--:- eth0 cli-> set ipv4_method/static/ ipv4_address=172.26.31.10 ipv4_ mask=255.255.255.0

**:- eth0 cli-> commit

4.

Type show to view the changes.

--:- eth0 cli-> show

Table 4.8: Network/Devices Options

Devices Navigation Tree devices eth0

Chapter 4: Accessing a PM PDU via the Command Line Interface 65

Devices Navigation Tree ipv4_method= ipv6_method= mode= status=

Network/Hosts

The following procedure describes how to add a host to the hosts table.

To add a host to the host table:

1.

Type cd network/hosts to navigate to the Hosts level.

--:- / cli-> cd network/hosts

2.

Type show to view the current host settings.

--:- hosts cli-> show ip hostname alias

===== ======== =====

127.0.0.1 localhost

3.

Type add then press Enter .

--:- hosts cli-> add <Enter>

--:#- [hosts] cli-> show ip = hostname = alias =

--:#- [hosts] cli->

4.

Type set hostname=<hostname> ip=<IP_address> to add the name of a host and the IP address for the host.

NOTE: Each parameter that follows the add command is separated by a space.

--:#- [hosts] cli-> set hostname=sharedpmpdu ip=172.26.31.164

5.

Type save

--:#- [hosts] cli-> save

6.

Type show to verify the changes took place and to view the new host entry.

--:- hosts cli-> show

66  Avocent PM PDU Installer/User Guide ip hostname alias

===== ======== =====

127.0.0.1 localhost

127.26.31.164 sharedpmpdu

7.

Type cd <IP_address>/settings to navigate to the level where you can perform additional configuration of the host entry.

--:- hosts cli-> cd 172.26.31.164/settings

8.

Type show to view the additions to the host table and the Settings option.

ip hostname alias

===== ======== =====

127.26.31.164 sharedpmpdu

Table 4.9: Network/Hosts Options

Hosts Navigation Tree hosts

127.0.0.1

alias= hostname=

Network/Firewall

Type cd network/firewall to navigate to the firewall level.

--:- / cli-> cd network/firewall

NOTE: To set a rule, you must enable the interface, set the rule for the interface and physically connect the interface to the network.

Table 4.10: Network/Firewall Options

Firewall Navigation Tree firewall ipv4_filter_table

FORWARD

INPUT

Chapter 4: Accessing a PM PDU via the Command Line Interface 67

Firewall Navigation Tree

OUTPUT ipv6_filter_table

FORWARD

INPUT

OUTPUT

Network/SNMP

Type cd network/snmp to navigate to the snmp level.

--:- / cli-> cd network/snmp

Type add then press Enter to start configuring a new snmp community:

--:- snmp cli-> add <Enter>

--:#- [snmp] cli-> show name = oid = permission = version = version_v1|v2 source =

--:#- [snmp] cli-> set name=public

--:#- [snmp] cli-> save

--:- snmp cli-> show name version source oid permission

==== ===== ===== ====== ========== public v1/v2 default read and write

--:- snmp cli-> system

--:#- [snmp] cli-> show syscontact = Avocent_Corporation syslocation = Avocent_PM

Authentication

Type cd authentication to navigate to the authentication level.

68  Avocent PM PDU Installer/User Guide

--:- / cli-> cd authentication

NOTE: Kerberos does not work unless the administrator copies the /etc/krb5.keytab file from the Kerberos server and overwrites the /etc/krb5.keytab file in the PM PDU.

Table 4.11: Authentication Options

Authentication Navigation Tree appliance_authentication authentication_servers radius tacacs+ ldap(s)/ad kerberos nis dsview

Users

Type cd users to navigate to the users level.

--:- / cli-> cd users

Table 4.12: Users Options

Users Options local_accounts user_names root admin password_rules password enforcement default expiration authorization

Chapter 4: Accessing a PM PDU via the Command Line Interface 69

Users Options groups admin appliance-admin user

To add a user and password:

1.

Type cd users/local_accounts/user_names to navigate to the user_names level.

--:- / cli-> cd users/local_accounts/user_names

2.

Type add . Then type set with the parameters all on one line separated by spaces as shown.

--:- user_names cli-> add

--:#- [user_name] cli-> set user_name=fred password=smith123abc confirm_ password=smith123abc

--:#- [user_names] cli->

3.

Type save .

--:#- [user_names] cli-> save

4.

Type show to verify the new user has been added.

--:#- [user_names] cli-> show

Events_and_Logs

Type cd events_and_logs to navigate to the events_and_logs level.

--:- / cli-> cd events_and_logs

Table 4.13: Events_and_Logs Options

Events_and_Logs Navigation Tree event list event destinations syslog snmp trap

70  Avocent PM PDU Installer/User Guide

Events_and_Logs Navigation Tree sms email dsview data_buffering local_data_buffering_settings segment_size_(kbytes)= spare_segments= nfs_data_buffering_settings nfs_server= nfs_path= segment_size_(kbytes)= spare_segments= syslog_data_buffering_settings syslog_facility=

Power Management

Type cd power_management to navigate to the power_management level.

--:- / cli-> cd power_management

Table 4.14: Power Management Options Descriptions

Option Description pdus

Allows an authorized user to reboot, restore factory default settings or to rename PDU(s). Also allows the authorized user to view information about each PDU, monitor sensors, clear sensor values, set up syslogging of events related to the PDU, configure an alarm and the LED display mode, and to manage outlets on the PDU.

Chapter 4: Accessing a PM PDU via the Command Line Interface 71

Option settings outlet_ groups data_logging

Description

Allows an authorized user to set the password used to log in to the PDU and to connect to daisychained PDUs. Also allows an authorized user to set the polling rate to retrieve data from daisychained PDUs, set the power cycle interval, syslog, buzzer and SW overcurrent protection and enableor disable data logging.

Lists all configured outlet groups that the current user is authorized to manage (to manage outlet groups, the user must be in a user group that is authorized to manage all the outlets in the outlet group). An administrator can configure outlet groups.

Allows an authorized user to clear or export data logging for PDU, phase, bank, outlet or environment.

To rename a PDU:

1.

Log onto the CLI as an administrator and type cd power_management/pdus to navigate to the pdus level.

--:- / cli-> cd power_management/pdus

2.

Type rename and press Tab Tab to expand the parameters.

--:- settings cli-> rename <PDU_ID> <Tab><Tab>

3.

Type set newpdu_id=<new_PDU_ID>.

--:#- [settings] cli-> set new_pdu_id= mypdu

--:#- [settings] save

To manage power for a selected outlet:

See cycle, on, off, lock and unlock on page 55 for how to manage power at the power_

management level.

Active Sessions Information

The Active Session information fields are described in Active Sessions Information on page 71.

An authorized user can kill an active session with the Kill command.

Table 4.15: Active Sessions Field Descriptions

Field Description user client_ip

Logged in user

Source of the connection

72  Avocent PM PDU Installer/User Guide

Field creation_ time

Description

Time of the session creation session_ type target_ name

Type of session (console, http) connection_ type

Type of connection (cli, wmi - that is, web manager)

Target name or alias if session is an access session id parent id

Session ID

Parent ID if session is a subsession

To view and kill Active_Sessions:

1.

From the / level CLI prompt, type cd active_sessions .

--:- / cli-> cd active_sessions

--:- active_sessions cli->

2.

Type show . Information displays as shown about all active sessions.

--:- active_sessions cli-> show

37 user: admin client_ip: none creation_time: Tue Dec 18 03:31:01 2007 session_type: console connection_type: cli id: 37 parent_id:

--:- active_sessions cli->

3.

To kill a session (if authorized), type kill followed by the session number.

--:- active_sessions cli-> kill_session 122

73

A P P E N D I C E S

Appendix A: Accessing a PM PDU via SNMP

Using a machine with an SNMP-client application, an administrator can configure PDU power parameters using snmpset and snmpget commands. An administrator can, for example, change the PDU's name, change an outlet's name or change the current thresholds of an outlet. A complete list of configurable parameters can be found in the PDU's MIB file.

Configuration via SNMP will take effect upon completion of the command. To save the configuration across reboots, you must issue the save command.

To use SNMP, you must enable it and configure it on the PDU. To enable and configure SNMP

with the web manager, see Security on page 25 and SNMP configuration on page 34. To

enable and configure SNMP with the CLI, see System/Security on page 58 and Network/SNMP on page 67.

NOTE: When using snmpset commands, especially in a daisy-chained configuration, it is recommended you extend the time-out with no retries. The time-out should depend on the command and the length of the chain. For example, issuing a save command or power cycling outlets will need a longer time-out.

Example of an SNMP command to rename the PDU:

#snmpset -t 60 -r 0 -v 2c -c <community> <IP address>

 pmPowerMgmtPDUTablePDUTablePduId.1.1 s NewPDUname

Example of an SNMP command to rename an outlet:

#snmpset -t 60 -r 0 -v 2c -c <community> <IP address>

 pmPowerMgmtOutletsTableName.1.1.1 s NewOut1

Example of an SNMP command to change the high critical threshold on an outlet:

#snmpset -t 60 -r 0 -v 2c -c <community> <IP address>

 pmPowerMgmtOutletsTableCurrentHighCritical.1.1.1 i 100

Example of an SNMP command to save:

#snmpset -t 60 -r 0 -v 2c -c <community> <IP address> pmPowerMgmtSerialTableSave.1 i 2

NOTE: Some PDU models don't support the entire set of configurable parameters. In this instance, the snmpset command will fail and the snmpget command will return 0 for integer OIDs and N/A for strings.

74 Avocent PM PDU Installer/User Guide

Appendix B: Specifications

Table B.1: Avocent PM PDU Specifications

Unit CMN

Input Voltage

Input

Current

Output

Voltage

Outlet

Max

Current

Bank Max

Unbalanced

Current

Bank

Max

Balanced

Current

Listed

Branch

Circuit

Protection

PM1001V-

401

PM1002V-

401

PM1003V-

401

PM1004V-

401

PM1005V-

401

1075-

773

US single phase 200-240

VAC 2W + PE

50/60 Hz

NEMA L6-30P

24A

US three phase

1075-

755

100-120/200-

208 VAC

3W+N+PE,

50/60 Hz

NEMA L21-

30P

24A per phase

200-240

VAC

50/60

Hz

16A

(C19)

12A

(C13

200-208

VAC

50/60Hz

16A

(C19)

12A

(C13)

1075-

776

US three phase 200-240

VAC 3W + PE

50/60 Hz

CS8365C

40A per phase

200-240

VAC

50/60

Hz

16A

(C19)

12A

(C13)

1075-

775

US three phase 200-240

VAC 3W + PE

50/60 Hz

IEC309

460P9W

48A per phase

200-240

VAC

50/60

Hz

16A

(C19)

12A

(C13)

1075-

774

EU single phase 220-240

VAC 2W + PE

50/60 Hz

IEC309

332P6W

32A

220-240

VAC

50/60

Hz

16A

(C19)

10A

(C13)

16A (see note 2)

16A (see note 1)

32A (see note 4)

32A (see note 5)

16A (see note 3)

12A

13.85A

23A

27.71A

16A

30A

30A

50A

60A

40A

Appendices 75

Unit

PM1006V-

401

PM1007V-

401

PM1008V-

401

PM2002H-

401

PM3002H-

401

PM2002V-

401

PM3002V-

401

PM2004H-

401

PM3004H-

401

CMN

Input Voltage

Input

Current

Output

Voltage

Outlet

Max

Current

Bank Max

Unbalanced

Current

Bank

Max

Balanced

Current

Listed

Branch

Circuit

Protection

1075-

772

EU three phase 220-

240/381-415

VAC 3W + N +

PE 50/60 Hz

IEC309

516P6W

1075-

777

EU three phase 220-

240/381-415

VAC 3W + N +

PE 50/60 Hz

IEC309

532P6W

16A per phase

32A per phase

220-240

VAC

50/60

Hz

220-240

VAC

50/60

Hz

16A

(C19)

10A

(C13)

16A

(C19)

10A

(C13)

1075-

797

US three phase 200-240

VAC 3W+PE,

50/60 Hz

NEMA L15-30

24A per phase

200-240

VAC

50/60

Hz

16A

(C19)

12A

(C13)

1057-

211

US three phase 200-240

VAC 3W + PE

50/60Hz

NEMA L15-

30P

24A per phase

200-240

VAC

50/60

Hz

16A

1066-

200

US three phase 200-240

VAC 3W + PE

50/60Hz

NEMA L15-

30P

24A per phase

200-240

VAC

50/60

Hz

16A

(C19)

12A

(C13

1058

EU three phase 220-

240/381-415

VAC 3W + N +

PE 50/60Hz

IEC309

516P6W

16A per phase

220-240

VAC

50/60

Hz

16A

16A

32A

16A (see note 1)

16A (see note 1)

16A (see note 1)

16A

16A

32A

13.85A

13.85A

13.85A

16A

20A

40A

30A

30A

30A

20A

76 Avocent PM PDU Installer/User Guide

Unit

PM2004V-

401

PM3004V-

401

PM2006H-

401

PM3006H-

401

PM2001H-

401

PM3001H-

401

PM2001V-

401

PM3001V-

401

YAH3001V-

401

PM2003H-

401

PM3003H-

401

CMN

Input Voltage

Input

Current

Output

Voltage

Outlet

Max

Current

Bank Max

Unbalanced

Current

Bank

Max

Balanced

Current

Listed

Branch

Circuit

Protection

1068

EU three phase 220-

240/381-415

VAC 3W + N +

PE 50/60Hz

IEC309

516P6W

1057-

264

US three phase 100-

120/200-208

VAC 3W + N +

PE, 50/60 Hz

NEMA L21-

L30P

16A per phase

24A per phase

1059

US single phase 200-240

VAC 2W + PE

50/60 HZ

NEMA L6-30P

24A

220-240

VAC

50/60

Hz

16A

(C19)

10A

(C13)

200-208

VAC

50/60

Hz

16A

200-240

VAC

50/60

Hz

16A

1065

US single phase 200-240

VAC 2W + PE

50/60 HZ

NEMA L6-30P

24A

200-240

VAC

50/60

Hz

16A

(C19)

12A

(C13)

1065

US single phase 200-240

VAC 2W + PE

50/60 HZ

NEMA L6-30P

24A

1060

EU single phase 220-240

VAC 2W + PE

50/60 Hz

IEC309

332P6W

32A

200-240

VAC

50/60

Hz

220-240

VAC

50/60

Hz

12A

(C13)

16A

16A

16A (see note 1)

16A (see note 2)

16A (see note 2)

16A (see note 2)

16A (see note 3)

16A

13.85A

8A

8A

8A

10.66A

20A

30A

30A

30A

30A

40A

Appendices 77

Unit

PM2003V-

401

PM3003V-

401

PM2005H-

403

PM3005H-

403

PM2005V-

403

PM3005V-

403

PM2005H-

406

PM3005H-

406

PM2005V-

406

PM3005V-

406

PM2005H-

404

PM3005H-

404

CMN

Input Voltage

Input

Current

Output

Voltage

Outlet

Max

Current

Bank Max

Unbalanced

Current

Bank

Max

Balanced

Current

Listed

Branch

Circuit

Protection

1067

EU single phase 220-240

VAC 2W + PE

50/60 Hz

IEC309

332P6W

32A

1078-

185

US three phase 200-240

VAC 3W + PE

50/60 Hz

CS8365C

40A per phase

200-240

VAC

50/60

Hz

16A

1076-

185

US three phase 200-240

VAC 3W + PE

50/60 Hz

CS8365C

40A per phase

200-240

VAC

50/60

Hz

16A

(C19

12A

(C13)

1079

EU three phase 220-

240/381-415

VAC 3W + N +

PE 50/60 Hz

IEC309

532P6W

32A per phase

220-240

VAC

50/60

Hz

220-240

VAC

50/60

Hz

16A

(C19)

10A

(C13)

16A

1077

EU three phase 220-

240/381-415

VAC 3W + N +

PE 50/60 Hz

IEC309

532P6W

32A per phase

220-240

VAC

50/60

Hz

16A

(C19)

10A

(C13)

1078-

184

US three phase 200-240

VAC 3W + PE

50/60 Hz

IEC309

460P9W

48A per phase

200-240

VAC

50/60

Hz

16A

16A (see note 3)

32A (see note 4)

32A (see note 4)

32A

32A

32A (see note 5)

10.66A

23A

23A

32A

32A

27.71A

40A

50A

50A

40A

40A

60A

78 Avocent PM PDU Installer/User Guide

Unit

PM2005V-

404

PM3005V-

404

PM2006V-

401

PM3006V-

401

PM1012V-

401

PM1013V-

401

PM1014V

PM2010V-

401

PM3010V-

401

CMN

Input Voltage

Input

Current

Output

Voltage

Outlet

Max

Current

Bank Max

Unbalanced

Current

Bank

Max

Balanced

Current

Listed

Branch

Circuit

Protection

1076-

184

US three phase 200-240

VAC 3W + PE

50/60 Hz

IEC309

460P9W

48A per phase

200-240

VAC

50/60

Hz

16A

(C19)

12A

(C13)

1066-

267

US three phase 100-

120/200-208

VAC 3W + N +

PE, 50/60 Hz

NEMA L21-

30P

24A per phase

1084-

809

US single phase 200-240

VAC 2W + PE

50/60 Hz

NEMA L6-30P

24A

200-208

VAC

50/60

Hz

16A

(C19)

12A

(C13)

200-240

VAC

50/60

Hz

12A

1084-

810

EU single phase 220-240

VAC 2W + PE

50/60 Hz

IEC309

332P6W

32A

1084-

808

Single phase

100-240 VAC

2W + PE 50/60

Hz IEC320-

C20

16A

1083-

806

US single phase 200-240

VAC 2W + PE

50/60 Hz

NEMA L6-30P

24A

220-240

VAC

50/60

Hz

100-240

VAC

50/60

Hz

200-240

VAC

50/60

Hz

10A

10A

12A

32A (see note 5)

16A (see note 1)

16A (see note 2)

16A (see note 3)

N/A

16A (see note 2)

27.71A

13.85A

12A

16A

N/A

12A

60A

30A

30A

40A

20A

30A

Appendices 79

Unit

PM2011V-

401

PM3011V-

401

PM2012V

PM3012V

PM1009H-

401

PM1010H-

401

PM1011H

PM2007H-

401

PM3007H-

401

CMN

Input Voltage

Input

Current

Output

Voltage

Outlet

Max

Current

Bank Max

Unbalanced

Current

Bank

Max

Balanced

Current

Listed

Branch

Circuit

Protection

1083-

807

EU single phase 220-240

VAC 2W + PE

50/60 Hz

IEC309

332P6W

32A

1083-

805

Single phase

100-240 VAC

2W + PE 50/60

Hz IEC320-

C20

16A

1084-

799

US single phase 200-240

VAC 2W + PE

50/60 Hz

NEMA L6-30P

24A

1084-

800

EU single phase 220-240

VAC 2W + PE

50/60 Hz

IEC309

332P6W

32A

1084-

798

Single phase

100-240 VAC

2W + PE 50/60

Hz IEC320-

C20

16A

1083-

794

US single phase 200-240

VAC 2W + PE

50/60 Hz

NEMA L6-30P

24A

220-240

VAC

50/60

Hz

100-240

VAC

50/60

Hz

200-240

VAC

50/60

Hz

220-240

VAC

50/60

Hz

100-240

VAC

50/60

Hz

200-240

VAC

50/60

Hz

10A

10A

12A

10A

10A

12A

16A (see note 3)

N/A

16A (see note 2)

16A (see note 3)

N/A

16A (see note 2)

16A

N/A

12A

16A

N/A

12A

40A

20A

30A

40A

20A

30A

80 Avocent PM PDU Installer/User Guide

Unit CMN

Input Voltage

Input

Current

Output

Voltage

Outlet

Max

Current

Bank Max

Unbalanced

Current

Bank

Max

Balanced

Current

Listed

Branch

Circuit

Protection

PM2008H-

401

PM3008H-

401

PM2009H

PM3009H

1083-

796

EU single phase 220-240

VAC 2W + PE

50/60 Hz

IEC309

332P6W

32A

1083-

792

Single phase

100-240 VAC

2W + PE 50/60

Hz IEC320-

C20

16A

220-240

VAC

50/60

Hz

100-240

VAC

50/60

Hz

10A

10A

16A (see note 3)

N/A

16A

N/A

NOTE 1: When one bank is at a maximum 16A, the other banks shall not exceed 12A per bank.

NOTE 2: When one bank is at a maximum 16A, the other bank(s) shall not exceed 8A total.

NOTE 3: When one bank is at a maximum 16A, the other bank(s) shall not exceed 16A total.

NOTE 4: When one bank is at a maximum 32A, the other banks shall not exceed 13A per bank.

NOTE 5: When one bank is at a maximum 32A, the other banks shall not exceed 23A per bank.

40A

20A

Table B.2: Avocent PM PDU Information

Environmental

Operating Temperature

Storage Temperature

Relative Humidity

10ºC to 45ºC (50ºF to 113ºF)

-40ºC to 65ºC (-40ºF to 149ºF)

20% to 80% (non-condensing) across the operating temperature range; 5% to 95% (non-condensing) across the non-operating temperature range

Dimensions

Form Factor

Weight

0U, 1U rack mountable

7.3 lbs (horizontal high amperage models without power cord),

14.8 lbs (vertical high amperage models without power cord),

5.2 lbs (horizontal low amperage models without power cord),

11 lbs (vertical low amperage models without power cord)

Physical Dimensions (W x D x H)

Network Connection

Number

Type

Safety Markings and Approvals

Appendices 81

17 x 8.272 x 1.719 in (horizontal high amperage models), 2.2 x

66 x 3.15 in (vertical high amperage models), 1.7 x 17 x 5.5 in

(horizontal low amperage models), 2.2 x 3.2 x 52 in (vertical low amperage models)

1

10/100/1000 Ethernet

UL, FCC, cUL, CE, VCCI, C-Tick, CB Safety certifications and

EMC certifications for this product are obtained under one or more of the following designations: CMN (Certification Model

Number), MPN (Manufacturer’s Part Number) or Sales Level

Model designation. The designation that is referenced in the

EMC and/ or safety reports and certificates are printed on the label applied to this product.

82 Avocent PM PDU Installer/User Guide

Appendix C: Outlet Bank Assignment

Table C.3:  Outlet Bank Assignment

Unit Bank 1 Bank 2 Bank 3 Bank 4

PM1001V-

401 outlets 1, 9 and 17 FC22-

FC24 FC18-

FC20 outlets 2-8,

10-16 and

18-24 FC21-

FC23 FC17-

FC19

N/A N/A

PM1002V-

401

PM1008V-

401

PM2002V-

401

PM2006V-

401

PM3002V-

401

PM3006V-

401 outlets 1-8

FC22-FC24

FC18-FC20 outlets 9-16

FC14-FC16

FC10-FC12 outlets 17-24

FC6-FC8

FC2-FC4

N/A

PM1005V-

401 outlets 1, 9 and 17 FC22-

FC24 outlets 2-8,

10-16 and

18-24 FC21-

FC23

N/A N/A

PM2001H-

401

PM3001H-

401

PM2003H-

401

PM3003H-

401 outlet 1 FC5-

FC6 FC7-

FC8 outlet 1 FC5-

FC6 outlet 2

FC13-FC14

FC15-FC16 outlet 2

FC13-FC14 outlet 3

FC21-FC22

FC23-FC24 outlet 3

FC21-FC22

N/A

N/A

PM2002H-

401

PM3002H-

401

PM2006H-40

PM3006H-

401 outlets 1 and 2

FC5-FC6

FC7-FC8 outlets 3 and

4 FC13-

FC14 FC15-

FC16 outlets 5 and

6 FC21-

FC22 FC23-

FC24

N/A

Bank 5 Bank 6

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Appendices 83

PM2005H-

406

PM3005H-

406

PM2001V-

401

PM3001V-

401

YAH3001V-

401

PM2003V-

401

PM3003V-

401

PM1006V-

401

PM2004V-

401

PM3004V-

401

Unit

PM2004H-

401

PM3004H-

401

PM2005H-

404

PM3005H-

404

PM2005H-

403

PM3005H-

403

Bank 1 outlet 1 FC1-

FC2 FC3-

FC4 outlets 1-8

FC22-FC24

FC18-FC20 outlets 1-8

FC22-FC24 outlets 1-8

FC22-FC24

Bank 2 outlets 1 and 2

FC5-FC6 outlets 3 and

4 FC13-

FC14 outlet 2 FC5-

FC6 FC7-

FC8 outlets 9-16

FC14-FC16

FC10-FC12 outlets 9-16

FC14-FC16 outlets 9-16

FC14-FC16

Bank 3 Bank 4 outlets 5 and

6 FC21-

FC22

N/A outlet 3 FC9-

FC10 FC11-

FC12 outlet 4

FC13-FC14

FC15-FC16 outlets 17-24

FC6-FC8

FC2-FC4 outlets 17-24

FC6-FC8 outlets 17-24

FC6-FC8

N/A

N/A

N/A

Bank 5

N/A outlet 5

FC17-FC18

FC19-FC20 outlet 6

FC21-FC22

FC23-FC24 outlet 1 FC1-

FC2 outlet 2 FC5-

FC6 outlet 3 FC9-

FC10 outlet 4

FC13-FC14 outlet 5

FC17-FC18 outlet 6

FC21-FC22

N/A

N/A

N/A

Bank 6

N/A

N/A

N/A

N/A

84 Avocent PM PDU Installer/User Guide

Unit

PM1003V-

401

PM1004V-

401

PM2005V-

404

PM3005V-

404

PM2005V-

403

PM3005V-

403

PM1007V-

401

PM2005V-

406

PM3005V-

406

PM1009H-

401

PM2007H-

401

PM3007H-

401

PM1010H-

401

PM2008H-

401

PM3008H-

401

PM1012V-

401

PM2010V-

401

PM3010V-

401

PM1013V-

401

PM2011V-

401

PM3011V-

401

Bank 1 outlet 1 FC22-

FC24 FC18-

FC20 outlet 1 FC22-

FC24 outlets 1-5

FC1-FC5

FC4-FC8 outlets 1-5

FC4-FC8 outlets 1-10

FC1-FC5

FC4-FC8 outlets 1-10

FC4-FC8

Bank 2 outlets 2-8

FC21-FC23

FC17-FC19 outlets 2-8

FC21-FC23 outlets 6-10

FC2-FC6

FC3-FC7 outlets 6-10

FC3-FC7 outlets 11-20

FC2-FC6

FC3-FC7

Bank 3 outlet 9

FC14-FC16

FC10-FC12 outlet 9

FC14-FC16

N/A

N/A

N/A outlets 11-20

FC3-FC7

N/A

Bank 4 outlets 10-16

FC13-FC15

FC9-FC11

N/A

N/A

N/A

N/A

Bank 5 outlet 17

FC6-FC8

FC2-FC4 outlets 10-16

FC13-FC15 outlet 17

FC6-FC8

N/A

N/A

N/A

N/A

Bank 6 outlets 18-24

FC5-FC7

FC1-FC3 outlets 18-24

FC5-FC7

N/A

N/A

N/A

N/A

Appendices 85

Unit

PM1011H

PM2009H

PM3009H

PM1014V

PM2012V

PM3012V

Bank 1 Bank 2 Bank 3 outlets 1-5 (no fuses) outlets 6-10

(no fuses)

N/A outlets 1-10

(no fuses) outlets 11-20

(no fuses)

N/A

Bank 4

N/A

N/A

Bank 5

N/A

Bank 6

N/A

N/A N/A

Figure C.1: PM2003V-401/PM3003V-401, IEC-309 32A 1-Phase Power Cord

86 Avocent PM PDU Installer/User Guide

Figure C.2: PM1005V-401, IEC-309 32A 1-Phase Power Cord

Appendices 87

Figure C.3: PM2004-401/PM3004V-401/PM1006V-401, IEC-309 16A 3-Phase Power Cord

88 Avocent PM PDU Installer/User Guide

Figure C.4: PM2005V-406/PM3005V-406/PM1007V-401, IEC 309 32A 3-Phase Power Cord

Figure C.5: PM2001V-401/PM3001V-401, L6-30P 24A 1-Phase Power Cord

Appendices 89

90 Avocent PM PDU Installer/User Guide

Figure C.6: YAH3001V-401, L6-30P 24A 1-Phase Power Cord

Appendices 91

92 Avocent PM PDU Installer/User Guide

Figure C.7: PM1001V-401, L6-30P 24A 1-Phase Power Cord

Figure C.8: PM2002V-401/PM3002V-401/PM1008V-401, L15-L30P 3-Phase Power Cord PM2006V-

401/PM3006V-401/PM1002V-401, L21-30P 3-Phase 24A Power Cord

Appendices 93

Figure C.9: PM2005V-403/PM3005V-403/PM1003V-401, Hubbell CS8365C 40A 3-Phase Power Cord

94 Avocent PM PDU Installer/User Guide

Figure C.10: PM2005V-404/PM3005V-404/PM1004V-401, IEC-309 48A 3-Phase Power Cord

Figure C.11: PM2003H-401/PM3003H-401, IEC-309 32A 1-Phase Power Cord

Appendices 95

96 Avocent PM PDU Installer/User Guide

Figure C.12: PM2004H-401/PM3004H-401, IEC-309 16A 3-Phase Power Cord

Figure C.13: PM2005H-406/PM3005H-406, IEC309 32A 3-Phase Power Cord

Appendices 97

98 Avocent PM PDU Installer/User Guide

Figure C.14: PM2001H-401/PM3001H-401, L6-30P 24A 1-Phase Power Cord

Appendices 99

Figure C.15: PM2002H-401/PM3002H-401, L15-L30P 24A 3-Phase Power Cord PM2006H-401/PM3006H-

401, L21-L30P 24A 3-Phase Power Cord

100 Avocent PM PDU Installer/User Guide

Figure C.16: PM2005H-403/PM3005H-403, Hubbell CS8365C 40A 3-Phase Power Cord

Figure C.17: PM2005H-404/PM3005H-404, IEC-309 48A 3-Phase Power Cord

Appendices 101

102 Avocent PM PDU Installer/User Guide

Figure C.18: PM1009H-401/PM2007H-401/PM3007H-401, L6-30P 24A 1-Phase Power Cord

Appendices 103

Figure C.19: PM1001H-401/PM2008H-401/PM3008H-401, IEC309 32A 1-Phase Power Cord

104 Avocent PM PDU Installer/User Guide

Figure C.20: PM1011H/PM2009H/PM3009H, C20 16A 1-Phase Power Cord

Appendices 105

Figure C.21: PM1012V-401/PM2010V-401/PM3010V-401, L6-30P 24A 1-Phase Power Cord

106 Avocent PM PDU Installer/User Guide

Figure C.22: PM1013V-401/PM2011V-401/PM3011V-401, IEC 309 32A 1-Phase Power Cord

Appendices 107

Figure C.23: PM1014V/PM2012V/PM3012V, C20 16A 1-Phase Power Cord

NOTE: Hardware overcurrent protection is in place to protect fuses. All outlets in a bank, that are protected by a common fuse or dual fuses, will turn off together in case the total current in that bank exceeds the fuse limits. The web manager/CLI will show all outlets in that bank as tripped.

108 Avocent PM PDU Installer/User Guide

Appendix D: Replacing the Fuses (For Service Personnel Only)

This product contains replaceable fuses. To avoid serious injury and/or damage to your

Avocent PM PDU, make sure:

• The PDU is disconnected from a power source and all connected devices are turned off before replacing a fuse.

• Fuses are replaced with an Avocent approved branch circuit fuse class G time delay type with 20A 600 VAC rating.

CAUTION: Avocent recommends using the Avocent fuse replacement kit. Avocent is not responsible for any issues that may occur using any other vendor’s fuse replacement kit.

• Fuses are replaced by qualified personnel.

• Fuses are denoted with the following markings on the board: FC1-FC2, FC3-FC4, FC5-

FC6, FC7-FC8, FC9-FC10, FC11-FC12, FC13-FC14, FC15-FC16, FC17-FC18, FC19-FC20,

FC21-FC22, FC23-FC24, FC1-FC5, FC2-FC6, FC3-FC7, FC4-FC8 . Refer to Appendix B for fuse(s) to outlet(s) correlation.

WARNING: There is a risk of explosion if the lithium battery is replaced with an incorrect type. Dispose of used batteries according to the manufacturer’s instructions.

CAUTION: Double pole/neutral fusing.

For Technical Support: www.avocent.com/support

590-860-501H

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents