countis e63 - GHV Trading

countis e63 - GHV Trading
COUNTIS E63
count_201_a_1_cat
Active energy meter and concentrator
site_502_a
 Applications
3 x 1 phase - Direct 100 A
 Function
The COUNTIS E63 is a communicating
active energy Energy meter, with
breakdown of consumption per phase. It
provides metering of the consumption of
single phase loads on a single- phase or
three-phase network. It is connected online up to 100 A.
COUNTIS E63 are protected against
phase/neutral inversion and detect wiring
errors.
 Applications
The COUNTIS E63 is an active energy
meter and concentrator that provides a
direct reading of the power consumed per
phase as well as the total consumed by the
3 phases. It has a JBUS/MODBUS RTU
communication output on RS485. A partial
meter with reset allows you to meter the
energy over a specific period for each of
the phases or for the total of all 3 phases.
The COUNTIS E63 is unidirectional : it
only meters the positive active energy
(generator mode).
2
E 63
COUNTIS E63
count_205_a_1_x_cat
CO
UN
TIS
Due to the integration of 3 single phase meters in the
same case (7 modules wide), the COUNTIS E63 provides a
significant space-saving feature.
In addition, it is designed to provide metering of single
phase loads up to 100 A.
Its communication output port provides access to
advanced multi-measurement functions :
• Instantaneous currents: I1, I2, I3
• Instantaneous voltages: U1, U2, U3
• Instantaneous power: 3P, 3S
• Instantaneous power factors: 3PF
• Load curves for each of the 3 phases : reproduction
of average positive active power energy consumption
demand for a programmable period.
 Conformity to
standards
• IEC 62053-21 class 1
General Catalogue 2011-2012 SOCOMEC
Active energy meter and concentrator
COUNTIS E63
ÂÂ Front panel
count_201x_a_1_cat
1. LCD display
2. Navigation key
3. Reset key
4. Metrological LED
2
3
4
1
ÂÂ Electrical characteristics
Current measurement
Output (pulsed)
Type
Input consumption
Startup current (Ist)
Minimum current (Imin)
Transition current (Itr)
Reference current (Iref)
Permanent overload (Imax)
Short-time over-current
Number
Type of optocoupler
Fixed weight of impulses
Impulse duration
100 A direct
0.5 VA max. per phase
80 mA
0,5 A
2A
20 A
100 A
3000 A max for 10 ms
Operating conditions
Operating temperature
Storage temperature
Relative humidity
Voltage measurement
Range of measurement
Consumption on inrush (VA)
Permanent overload
230 ... 400 V +/- 20 %
2
280 V phase-neutral / 480 V phase-phase
Energy accuracy
Active (according to IEC 62053-21)
1
IEC 62053-31 Class A (20 ... 30 VDC)
100 Wh
100 ms
-10 to 55 °C
-20 to 70 °C
95 %
Communication
Link
Type
Protocol
JBUS/MODBUS® speed
RS485
2 … 3 half duplex wires
JBUS/MODBUS® in RTU mode
3800 … 38400 bauds
Class 1
Supply
Self supplied
Frequency
Yes
50 / 60 Hz
ÂÂ Case
62.5
45
126
Type
Number of modules
Dimensions W x H x D
Case protection index
Front protection rating
Display type
Rigid cable connection section
Flexible cable connection section
Weight
COUNTIS E60
45
Partial
90
count_203_a_1_x_cat
Error
RESET / PROG
3X230(400)VAC 50/60Hz 0.5-20(100)A
C=2Wh / imp
3 x phases 100A
Modular
7
126 x 90 x 62.5 mm
IP20
IP51
Backlit LCD display
2.5 to 35 mm2
2.5 to 35 mm2
490 g
ÂÂ Terminals and connections
N
Line 1’
Line 2’
Line 3’
count_206_a_1_gb_cat
Line 1
Line 2
Line 3
+ 2
15 17 13
N
COUNTIS E63
1 3 5 7 9 11
L - 1 - L’
L - 2 - L’
L - 3 - L’
ÂÂ References
Type
3x 100 A direct with JBUS/MODBUS communication via RS485 - MID(1)
COUNTIS E63
Reference
4850 3016
(1) 4 tariffs via RS485 communication.
SOCOMEC General Catalogue 2011-2012
3