Digital indicator, model DI35-M

Digital indicator, model DI35-M
Operating instructions
Digital indicator, model DI35-M
Digital indicator for panel mounting
EN
Page
3 - 67
© 2016 WIKA Alexander Wiegand SE & Co. KG
All rights reserved.
WIKA® is a registered trademark in various countries.
Prior to starting any work, read the operating instructions!
Keep for later use!
2
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN Operating instructions model DI35-D
Contents
Contents
1. General information
6
2. Design and function
7
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . 8
3. Safety9
3.1 Explanation of symbols . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Improper use . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Personnel qualification .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
10
3.5 Labelling, safety marks . . . . . . . . . . . . . . . . . . . . . 11
4. Transport, packaging and storage
12
4.1 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2 Packaging and storage . . . . . . . . . . . . . . . . . . . . . 12
5. Commissioning13
5.1 Requirements for the installation location . . . . . . . . . . . . . . . 13
5.2 Mounting, version for panel mounting .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
13
5.3 Electrical connection . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 Notes on installation . . . . . . . . . . . . . . . . . . . . 14
5.3.2 Pin assignment .
5.4 Interface connector .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
15
16
5.5 Switching on the digital indicator . . . . . . . . . . . . . . . . . . 16
5.6 Connection examples . . . . . . . . . . . . . . . . . . . . . . 17
6. Operation21
6.1 Button functions . . . . . . . . . . . . . . . . . . . . . . . . 21
6.2 Accessing and exiting programming mode . . . . . . . . . . . . . . . 21
6.3 Navigating in the menu . . . . . . . . . . . . . . . . . . . . . 22
6.4 Changing numerical values . . . . . . . . . . . . . . . . . . . . 22
14053538.02 05/2017 EN
6.5 Accessing or clearing MIN/MAX values . . . . . . . . . . . . . . . . 22
WIKA operating instructions digital indicator, model DI35-M
3
EN
Contents
7. Description of program numbers
23
7.1 Setting the measuring input . . . . . . . . . . . . . . . . . . . . 23
7.1.1 Input signal . . . . . . . . . . . . . . . . . . . . . . . 23
7.1.2 Start and end value . . . . . . . . . . . . . . . . . . . . 25
7.1.3 Number of decimal places . . . . . . . . . . . . . . . . . . 26
EN
7.1.4 Offset adjustment .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
26
7.1.5 Comparative measurement table (only with thermocouples) . . . . . . 27
7.1.6 TARE function . . . . . . . . . . . . . . . . . . . . . . 27
7.2 General settings .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
28
7.2.2 Refresh rate .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
28
7.2.1 Running averaging . . . . . . . . . . . . . . . . . . . . 28
7.2.3 Measuring time . . . . . . . . . . . . . . . . . . . . . 29
7.2.4 Display mode . . . . . . . . . . . . . . . . . . . . . . 29
7.2.5 Trigger for MIN/MAX reset . . . . . . . . . . . . . . . . . . 30
7.2.6 Zero point suppression . . . . . . . . . . . . . . . . . . . 31
7.2.7 Display brightness . . . . . . . . . . . . . . . . . . . . 31
7.3 Setting the analogue output (option) . . . . . . . . . . . . . . . . . 31
7.3.1 Start and end value . . . . . . . . . . . . . . . . . . . . 31
7.3.2 Reference value . . . . . . . . . . . . . . . . . . . . . 32
7.3.3 Output signal . . . . . . . . . . . . . . . . . . . . . . 32
7.4 Setting the serial interface (option) . . . . . . . . . . . . . . . . . 33
7.5 Setting user authorisations . . . . . . . . . . . . . . . . . . . . 34
7.5.1 Authorisation levels . . . . . . . . . . . . . . . . . . . . 34
7.5.2 Cancelling the password protection .
7.6 Setting switching outputs .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
35
35
7.6.1 Flashing display on reaching the switch points . . . . . . . . . . . 35
7.6.2 Reference value . . . . . . . . . . . . . . . . . . . . . 36
7.6.3 Switch points . . . . . . . . . . . . . . . . . . . . . . 36
7.6.4 Switch behaviour . . . . . . . . . . . . . . . . . . . . . 37
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
42
44
7.8.1 Calculation . . . . . . . . . . . . . . . . . . . . . . . 44
7.8.2 Reset . . . . . . . . . . . . . . . . . . . . . . . . . 45
7.8.3 Display change to totaliser value .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
45
.
.
.
.
.
.
.
.
.
.
.
.
.
.
45
7.9 Reading the serial number . . . . . . . . . . . . . . . . . . . . 45
7.10 Restoring factory settings .
4
.
.
.
.
.
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
7.7 Linearising sensors .
7.8 Totaliser function .
Contents
8. Faults46
9. Maintenance and cleaning
48
9.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 48
9.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10.Dismounting, return and disposal
49
10.1 Dismounting, version for control panel . . . . . . . . . . . . . . . . 49
10.2 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.3 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . 49
11.Specifications50
Appendix 1: Overview of program numbers
56
14053538.02 05/2017 EN
Declarations of conformity can be found online at www.wika.com
WIKA operating instructions digital indicator, model DI35-M
5
EN
1. General information
1.General information
■■ The digital indicator described in these operating instructions has been designed and
■■ These operating instructions contain important information on handling the instru-
ment. Working safely requires that all safety instructions and work instructions are
observed.
■■ Observe the relevant local accident prevention regulations and general safety regula-
tions for the instrument's range of use.
■■ The operating instructions are part of the product and must be kept in the immediate
vicinity of the instrument and readily accessible to skilled personnel at any time. Pass
the operating instructions on to the next operator or owner of the instrument.
■■ Skilled personnel must have carefully read and understood the operating instructions
prior to beginning any work.
■■ The general terms and conditions contained in the sales documentation shall apply.
■■ Subject to technical modifications.
■■ Further information:
- Internet address:
- Relevant data sheet:
- Application consultant:
6
www.wika.de / www.wika.com
AC 80.03
Tel.: +49 9372 132-0
Fax: +49 9372 132-406
[email protected]
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
manufactured using state-of-the-art technology. All components are subject to stringent quality and environmental criteria during production. Our management systems
are certified to ISO 9001 and ISO 14001.
2. Design and function
2.Design and function
2.1 Overview



14053538.02 05/2017 EN
Designation

EN




Description

Button [☼]
Programming mode is accessed
Changes to a deeper parameter level

Button [▼]
MIN memory is accessed
Changes lower limit values
Changes between parameters
Changes parameter values

Button [▲]
MAX memory is accessed
Changes lower limit values
Changes between parameters
Changes parameter values

Button [○]
Multi-function button

Switch point display
Displays the status of the switching outputs

Mounting element with
clamping screw
Used for fixing

7-segment display
Displays measured values, program numbers or
parameters

Product label
Contains product information
WIKA operating instructions digital indicator, model DI35-M
7
2. Design and function
2.2 Description
The model DI35-M digital indicator is a multi-function and very accurate instrument for a
wide variety of measuring tasks.
In addition, both versions offer the possibility to calibrate sensors and linearise using
up to 30 points. This allows further adaptation of the display values to different sensor
signals and application requirements. The standard features are completed by a transmitter power supply, a HOLD function and a TARE function for the correction of offset
shifts and sensor drifts. The sampling rate and display time can be configured and the
display can be dimmed. Unauthorised alteration of the set instrument parameters can
be prevented via different user levels, in conjunction with a freely selectable access
code.
Optionally available are up to four freely configurable switch contacts, an analogue
output signal and a serial interface.
Functions
Analogue output
Retrieval of the MIN/MAX value
HOLD and TARE function
Linearisation of the measuring input
Semiconductor switching outputs (option)
Switch point display (option)
Adjustable switch points (option)
■■
■■
■■
■■
■■
■■
■■
2.3 Scope of delivery
■■
■■
■■
■■
■■
Digital indicator
Sealing
2 mounting elements
Operating instructions
Unit characters
Cross-check scope of delivery with delivery note.
8
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
The model DI35-M digital indicator has a multi-function input with 29 different calibrated
input configurations that can be selected via terminal connections and the input signal in
the instrument configuration. The display can permanently show the MIN or MAX value.
Moreover, a totaliser function is integrated.
3. Safety
3.Safety
3.1 Explanation of symbols
DANGER!
... identifies hazards caused by electrical power. Should the safety instructions not be observed, there is a risk of serious or fatal injury.
WARNING!
... indicates a potentially dangerous situation that can result in serious
injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light
injuries or damage to property or the environment, if not avoided.
Information
... points out useful tips, recommendations and information for efficient
and trouble-free operation.
3.2 Intended use
The DI35 digital indicator is designed for the evaluation and display of sensor signals.
With the switching outputs, it is possible to realise simple control functions.
The digital indicator is suitable only for indoor applications with pollution degree 2 and
overvoltage category II.
Only use the digital indicator in applications that lie within its technical performance
limits (e.g. max. ambient temperature).
→ For performance limits see chapter 11 “Specifications”.
14053538.02 05/2017 EN
This is class B equipment for emissions and is intended for use in industrial environments. In other environments, e.g. residential or commercial installations, it can interfere
with other equipment under certain conditions.
In such circumstances the operator is expected to take the appropriate measures.
The instrument has been designed and built solely for the intended use described here,
and may only be used accordingly.
The manufacturer shall not be liable for claims of any type based on operation contrary
to the intended use.
WIKA operating instructions digital indicator, model DI35-M
9
EN
3. Safety
3.3 Improper use
WARNING!
Injuries through improper use
Improper use of the instrument can lead to hazardous situations and
injuries.
▶▶ Refrain from unauthorised modifications to the instrument.
▶▶ Do not open the instrument.
▶▶ Do not use the instrument within hazardous areas.
EN
Any use beyond or different to the intended use is considered as improper use.
3.4 Personnel qualification
WARNING!
Risk of injury should qualification be insufficient
Improper handling can result in considerable injury and damage to
equipment.
▶▶ The activities described in these operating instructions may only be
carried out by personnel who have the qualifications described below.
10
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
Skilled electrical personnel
Skilled electrical personnel are understood to be personnel who, based on their technical training, know-how and experience as well as their knowledge of country-specific
regulations, current standards and directives, are capable of carrying out work on
electrical systems and independently recognising and avoiding potential hazards. The
skilled electrical personnel have been specifically trained for the work environment they
are working in and know the relevant standards and regulations. The skilled electrical
personnel must comply with current legal accident prevention regulations.
3. Safety
3.5 Labelling, safety marks
Product label

Power supply:
Input:
Product no:
Product code:

Serial no:
100...240V (max. 15VA)
Multi-function
67213892
DI35-M-2W5C32B-Z
EN
Serial No.
Alarm outputs
Interface
RS-232
(insulated)
V
mA
RxD
S2
S1

GND
(RS)
TxD
21 22 23 24 25 26 27 28 29 30 31 32 41 42 43
-
-
L/LMade in Germany
Power supply
230V
Digital input
0-5/10V
Transmitter supply
DC 24V, < 50mA
+
-
< 2,5V
Analogue output
DC 0/4...20mA
DC 0...10V
-
+
TC
+
+
0/4-20mA
3-wire
Input
+
N/L+
4-wire
+
+
1 2 3 4 5 6 7 8 9 10 11 12 13 14
 Pin assignment
 Serial number
 Specifications
14053538.02 05/2017 EN
Before mounting and commissioning the instrument, ensure you read the
operating instructions!
WIKA operating instructions digital indicator, model DI35-M
11
4. Transport, packaging and storage
4.Transport, packaging and storage
CAUTION!
Damage through improper transport
With improper transport, damage to property can occur.
▶▶ When unloading packed goods upon delivery as well as during internal
transport, proceed carefully and observe the symbols on the packaging.
▶▶ With internal transport, observe the instructions in chapter 4.2
“Packaging and storage”.
4.2 Packaging and storage
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change
in installation site, sending for repair).
Permissible conditions at the place of storage:
■■ Storage temperature: -20 ... +80 °C
■■ Humidity: 0 ... 75 % relative humidity (no condensation)
Avoid exposure to the following factors:
■■ Direct sunlight or proximity to hot objects
■■ Mechanical vibration, mechanical shock (putting it down hard)
■■ Soot, vapour, dust and corrosive gases
Store the digital indicator in its original packaging in a location that fulfils the conditions
listed above. If the original packaging is not available, pack and store the instrument as
described below:
1. Wrap the instrument in a plastic film.
2. Place the instrument, along with shock-absorbent material, in the packaging.
12
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
4.1 Transport
Check the digital indicator for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
5. Commissioning
5.Commissioning
If the instrument is transported from a cold into a warm environment, the formation of
condensation may result in instrument malfunction. Before putting it into operation, wait
for the instrument temperature and the room temperature to equalise.
5.1 Requirements for the installation location
■■ In the vicinity there should be no magnetic or electrical fields, e.g. from transformers,
radio-telephones or electrostatic discharges.
■■ In the vicinity there should be no strong heat sources. The permissible operating
■■
■■
■■
■■
temperature must not be exceeded (max. 50 °C).
The installation location must conform to pollution degree 2.
No direct sunlight or proximity to hot objects
No mechanical vibration, mechanical shock (putting it down hard)
No soot, vapour, dust and corrosive gases
5.2 Mounting, version for panel mounting
10
7,0
0,0
12
48,0
3,0

96
,0
9,0
13

Dimensions in mm
14053538.02 05/2017 EN
 Mounting element with clamping screw
 Sealing
Cutting out the control panel
■■ Control panel thickness max. 15 mm
■■ Panel cutout 92.0+0.6 x 45.0+0.3 mm
Recommended mounting grid: 120 mm horizontal, 96 mm vertical
WIKA operating instructions digital indicator, model DI35-M
13
EN
5. Commissioning
Installing the digital indicator
1. As required, slide the unit characters into the window provided via the lateral channel.
2. Remove the mounting elements.
4. Slide the digital indicator into the control panel from the front.
Check the seal is properly seated.
5. Lock the mounting elements into place and tighten the clamping screws (max. 0.1 Nm).
5.3 Electrical connection
5.3.1 Notes on installation
The supply must comply with overvoltage category II.
Protect the voltage supply with a slow fuse of max. 0.5 A.
For the panel-mounting version, a suitable isolation device must be provided.
Route the signal input lines and signal output lines separately.
Route outward and return lines side-by-side.
Galvanically isolated potentials must be connected to a suitable point (e.g. earth or
plant ground).
■■ For high-accuracy requirements and small measuring signals, the sensor wires
must be shielded and twisted. The shield should be connected at one end only to a
suitable equipotential bonding (e.g. measurement ground).
■■ Avoid electrostatic discharges in the area of the terminals.
■■
■■
■■
■■
■■
■■
14
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
3. Slide the seal over the digital indicator.
5. Commissioning
5.3.2 Pin assignment
Terminal assignment (upper terminal block)
Switching outputs
Serial interface
EN
GND
(RS)
TxD
RxD
RS 232
GND
(RS)
Data B (+)
Data A (-)
S4
S3
S2
S1
21 22 23 24 25 26 27 28 29 30 31 32 41 42 43
RS 485
For further information see chapter 11 “Specifications”
Terminal assignment (lower terminal block)
1 2 3 4 5 6 7 8 9 10 11 12 1314
+
L
N
Voltage supply
l
Digital input
+
Transmitter power supply
l
Analogue output
Measuring inputs
+
14053538.02 05/2017 EN
→ For further information see chapter 11 “Specifications”
WIKA operating instructions digital indicator, model DI35-M
15
5. Commissioning
5.4 Interface connector
RS-232
The RS-232 interface cables must be connected 1:1 (TxD to TxD and RxD to RxD).
EN
PC or
PLC
DI35
RS-485
The RS-485 interface is connected via a shielded data cable with twisted pairs. At
each end of the bus segment, a termination of the bus lines must be connected. This is
needed in order to ensure safe data transfer over the bus. For this, a resistor (120 Ω) is
inserted between data B (+) and data A (-).
PC or PLC
DATA B (+)
DI35
DATA A (―)
5.5 Switching on the digital indicator
▶▶ Connect the power supply.
⇒⇒Segment test is carried out. Check the correct operation of all LEDs
⇒⇒Software type and software version are displayed.
⇒⇒Digital indicator is ready for operation.
16
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
Where interfaces are not galvanically isolated, the potential reference
between the interface and the measuring input can lead to a compensating current. This compensating current can influence the measuring
signals.
5. Commissioning
5.6 Connection examples
Input
Analogue
output
Transmitter
power
supply
digital input
Measurement of a current signal (4 ... 20 mA), 2-wire transmitter, supply AC 100 ... 240 V
EN
Power
supply
AC 100 ... 240 V
Input
Analogue
output
Transmitter
power
supply
Digital input
Measurement of a voltage signal (DC 5 V or DC 10 V), 3-wire transmitter, supply DC 10 ... 40 V
Power
supply
14053538.02 05/2017 EN
DC 10 ... 40 V
WIKA operating instructions digital indicator, model DI35-M
17
5. Commissioning
EN
Input
Analogue
output
Transmitter
power
supply
Digital input
Measurement of a current signal (≤ DC 2.5 V) with transmitter power supply, 3-wire
transmitter, supply AC 100 ... 240 V
Power
supply
AC 100 ... 240 V
Input
Analogue
output
Transmitter
power
supply
Digital input
Measurement of a resistance (e.g. resistance thermometer Pt100) , 2-wire, supply
AC 100 ... 240 V
Power
supply
18
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
AC 100 ... 240 V
5. Commissioning
Input
Analogue
output
Transmitter
power
supply
Digital input
Measurement of a resistance (e.g. resistance thermometer Pt100) , 2-wire, supply
AC 100 ... 240 V
EN
Power
supply
AC 100 ... 240 V
Input
Analogue
output
Transmitter
power
supply
Digital input
Measurement of a resistance (e.g. resistance thermometer Pt100) , 3-wire, supply
DC 10 ... 24 V
Power
supply
14053538.02 05/2017 EN
DC 10 ... 24 V
WIKA operating instructions digital indicator, model DI35-M
19
5. Commissioning
EN
Input
Analogue
output
Transmitter
power
supply
Digital input
Measurement of a resistance (e.g. resistance thermometer Pt100) , 4-wire, supply
AC 100 ... 240 V
Power
supply
AC 100 ... 240 V
Input
Analogue
output
Transmitter
power
supply
Digital input
Measurement of a thermocouple and digital input, supply AC 100 ... 240 V
Power
supply
20
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
AC 100 ... 240 V
6. Operation
6.Operation
6.1 Button functions
Button
Function
Button [☼]
Programming mode is accessed
Pressing < 1 s: Changes the cursor position
Pressing > 1 s: Saves all parameters
Button [☼] + [▼] [▲]
Scrolls through the program numbers (PN)
Pressing > 1 s: Automatically starts cycle
Button [▼]
Pressing < 1 s: Selects or changes parameter
Button [▲]
Pressing < 1 s: Selects or changes parameter
Button [○]
Multi-function button
Selects functions (e.g. HOLD or TARE)
EN
6.2 Accessing and exiting programming mode
Accessing programming mode
▶▶ Press [☼].
⇒⇒Digital indicator is in programming mode
⇒⇒Lowest available program number is displayed.
→ Available program numbers are dependent upon the authorisation level, see chapter
7.6.1 “Authorisation levels”.
14053538.02 05/2017 EN
Exiting the programming mode
If no buttons are pressed within 7 seconds, the digital indicator switches back to display
mode.
WIKA operating instructions digital indicator, model DI35-M
21
6. Operation
6.3 Menu navigation
[☼]
EN
[☼] 1s
[▲/▼]
PN0
[☼]+[▲]
Parameter 1
Parameter 2
[☼]+[▼]
[☼]+[▲]
Parameter 3
[☼] 1s
[▲/▼]
PN1
[▲]
[▼]
-9999 … 99999
[☼]+[▼]
PN...
6.4 Changing numerical values
Parameter
[☼]
1. Zahl
[☼]
[▲] [▼]
2. Zahl
[▲] [▼]
[☼] 1s
6.5 Accessing or clearing MIN/MAX values
Accessing MIN value
▶▶ Press [▼].
⇒⇒MIN value is displayed 7 s.
Clearing MIN/MAX values
▶▶ Press [▼] + [▲].
⇒⇒Horizontal bars are displayed.
⇒⇒MIN/MAX values are cleared.
The MIN/MAX values are lost when the instrument is switched off.
22
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
Accessing MAX value
▶▶ Press [▲].
⇒⇒MAX value is displayed 7 s.
7. Description of program numbers
7.Description of program numbers
For an overview of the program numbers see appendix 1 “Overview of program numbers”
7.1 Setting the measuring input
7.1.1 Input signal
The digital indicator has a multi-function input, which can be used for a variety of input
signals.
PN
0
Function
Input signal
Parameter
Current
01 = 0 ... 20 mA
02 = 4 ... 20 mA
14053538.02 05/2017 EN
Voltage
03 = DC 0 ... 10 V
04 = DC 0 ... 5 V
05 = DC 0 ... 2,500 mV
06 = DC 0 ... 1,250 mV
07 = DC 0 ... 600 mV
08 = DC 0 ... 300 mV
09 = DC 0 ... 150 mV
10 = DC 0 ... 75 mV
11 = DC 0 ... 35 mV
12 = DC 0 ... 18 mV
Temperature measurement
13 = Pt100 (4-/2-wire)
14 = Pt100 (3-wire)
15 = Pt200 (4-/2-wire)
16 = Pt200 (3-wire)
17 = Pt500 (4-/2-wire)
18 = Pt500 (3-wire)
19 = Pt1000 (4-/2-wire)
20 = Pt1000 (3-wire)
21 = L
22 = J
23 = K
24 = B
25 = S
26 = N
27 = E
28 = T
29 = R
WIKA operating instructions digital indicator, model DI35-M
23
EN
PN
0
Function
Input signal
EN
Parameter
Resistance
30 = ≤ 100 Ω (4-/2-wire)
31 = ≤ 1 kΩ (4-/2-wire)
32 = ≤ 10 kΩ (4-/2-wire)
Sensor calibration
33 = 0/4 ... 20 mA
34 = DC -1 ... +10 V
35 = DC -1 ... + 5 V
36 = DC -500 ... +2,500 mV
37 = DC -500 ... +1,250 mV
38 = DC -500 ... +600 mV
39 = DC ±300 mV
40 = DC ±150 mV
41 = DC ±75 mV
42 = DC ±35 mV
43 = DC ±18 mV
44 = 0 ... 5 mA
45 = 0 ... 2 mA
Parameters 1 ... 29 Used for standardised input signals. There must be no signal
applied to the measuring input. The corresponding display values
can be manually assigned.
With parameter 1 ... 12, the input signal can be linearised.
→ For assigning display values see chapter 7.1.2 “Start and end
value”
Parameter ≥ 30
Used for non-standardised input signals. The signal must be
applied to the measuring input and the corresponding display value
manually assigned.
24
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
→ For assigning display values see chapter 7.1.2 “Start and end
value”
7. Description of program numbers
7.1.2 Start and end value
With this value pair, the measuring signal is assigned the desired indication value.
PN
Function
End value (end of measuring range)
-9999 ... 99999
2
Start value (start of measuring range)
-9999 ... 99999
1
Parameter
EN
Procedure for standard signals
▶▶ Set the corresponding display values.
Procedure for non-standard input signals
1. Apply the end value of the input signal to the measuring input.
2. Select PN1.
3. Set the display value.
4. Press [☼].
⇒⇒Input signal is associated with display value.
5. Apply the start value of the input signal to the measuring input.
6. Select PN2.
7. Set the display value.
14053538.02 05/2017 EN
8. Press [☼].
⇒⇒Input signal is associated with display value.
⇒⇒Display values are assigned.
WIKA operating instructions digital indicator, model DI35-M
25
7. Description of program numbers
7.1.3 Number of decimal places
Specifies the number of decimal places that are displayed on the screen. This
parameter has no influence on the scaling of the indication value.
PN
Function
Number of decimal places
Parameter
00000 ... 0.0000
(not for temperature measurement)
Resistance thermometers
(PN0 = 13 ... 20)
0 = 8888.8 (°C)1)
1 = 8888.8 (°F) 1)
2 = 8888 °C
3 = 8888 °F
4 = 888.8 °C (-99.9 ... 999.9)
5 = 888.8 °F (-99.9 ... 999.9)
1) Unit is not shown on the display.
Thermocouple
(PN0 = 21 ... 29)
0 = 8888.8 (°C)1)
1 = 8888.8 (°F) 1)
2 = 8888 °C
3 = 8888 °F
7.1.4 Offset adjustment
The input signal is shifted in parallel by the offset value.
PN
5
Function
Offset value
Parameter
Analogue/resistance measurements and sensor calibration
(PN0 = 1 ... 12 and 30 ... 45)
-9999 ... 99999
Temperature sensors
(PN0 = 13 ... 29)
Measuring range
This parameter can be altered directly by making a tare if this was
triggered through the multi-function button or the digital input.
26
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
3
7. Description of program numbers
7.1.5 Comparative measurement table (only with thermocouples)
The comparative measurement table can only be parameterised with thermocouples
(PN0 = 21 ... 29)
PN
6
Function
Comparative measurement table
Parameter
0 = deactivated
1 = activated
EN
A deactivation can be useful when the transfer point is maintained at a
very constant level via controlled terminal heating. In such a case, the
cabling to the measuring instrument can be made with simple copper
cable.
7.1.6 TARE function
The TARE function sets the display value to the set value of the taring. The difference
between the set point and the display value is stored as an offset value (PN5).
The TARE function overrides a previously programmed offset shift (PN5).
Should the TARE function be used during a measurement, the offset shift
has to be reprogrammed.
The TARE function can be activated through the following points under PN8.
PN
Function
Parameter
8
Trigger for taring
00 = none
01 = digital input
02 = multi-function button
03 = digital input without button
04 = system start
05 = combination 1 + 4
06 = combination 2 + 4
07 = combination 3 + 4
08 = temporarily via digital input
09 = quickly via digital input
10 = quickly via multi-function button
11 = quickly via multi-function button
and digital input
14053538.02 05/2017 EN
7
Set value for the taring
-9999 ... 99999
WIKA operating instructions digital indicator, model DI35-M
27
7. Description of program numbers
7.2 General settings
PN
12
Function
Averaging value
Parameter
0 = off
1 ... 100 measured values
7.2.2 Refresh rate
The refresh rate determines how often the display values are updated. With strongly
fluctuating input signals, it is recommended that the refresh rate is adjusted (refresh rate
> 1s).
The refresh rate acts only on the presentation of the display values. Switching outputs
and other functions are not affected.
PN
13
28
Function
Refresh rate
Parameter
0.1 ... 10.0 s (default 1 s)
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
7.2.1 Running averaging
The total averaging time is given from the multiplication of the measuring time (PN14)
and the registered averaging value (PN12). If one wants to see the running average on
the digital indicator, the display mode (PN15) must be programmed accordingly. This
must also be observed for the optional analogue output or with the switching outputs.
7.2.3 Measuring time
The measuring time determines how often the analogue and switching outputs are
updated. With strongly fluctuating input signals, it is recommended that the measuring
time is adjusted (measuring time > 0.2 ... 1s).
PN
14
Function
Measuring time
Parameter
EN
Current, voltage
(PN0 = 1 ... 12 or 33 ... 45)
0.02 ... 10
Resistance (4-/2-wire)
0.04 ... 10
Resistance (3-wire)
0.06 ... 10
Thermocouple
(PN0 = 21 ... 29)
0.04 ... 10
The updating of the analogue and switching outputs is made cyclically
with the set measuring time. If the measuring time is set very short, this
can, with an unsteady input signal, lead to jumps with analogue outputs
or to short switching of the switching outputs. The MIN/MAX memory
receives the values on the basis of the set measuring time. Should
the peaks in an unsteady input signal need to be determined, a short
measuring time can be useful.
7.2.4 Display mode
The display mode determines which value is shown on the digital indicator.
PN
14053538.02 05/2017 EN
15
Function
Display mode
Parameter
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
8 = trigger mode
WIKA operating instructions digital indicator, model DI35-M
29
7. Description of program numbers
Mode
Description
MIN value
The smallest display value occurring since the last MIN reset is
displayed. The MIN reset is triggered according to the configuration
(→ see chapter 7.2.5 “Trigger for MIN/MAX reset”).
MAX Value
The largest display value occurring since the last MAX reset is
displayed. The MAX reset is triggered according to the configuration
(→ see chapter 7.2.5 “Trigger for MIN/MAX reset”).
Running average
The running average is displayed. The total averaging time is given
from the multiplication of the measuring time (PN14) and the registered averaging value (PN12).
Totaliser value
The totaliser value is displayed
Absolute value
The value measured since the power supply was connected,
without calculation of a prior taring, is displayed.
Trigger mode
The instantaneous value is only updated by a rising edge via the
digital input.
Instantaneous value
7.2.5 Trigger for MIN/MAX reset
The value reset is only signalised briefly, following the actuation of the digital input or the
multi-function button by 5 dashes (“- - - - - ”). If the reset is made via the taring, this is not
signalled.
With the reset, only the MIN/MAX value currently visible in the digital display is reset.
PN
16
Function
Trigger for MIN/MAX reset
Parameter
0 = no trigger
1 = digital input
2 = multi-function button
3=d
igital input or multi-function
button
4 = on taring
Following the reset, in the “MIN/MAX value” display mode, the instantaneous value is displayed until the trigger is reset. This allows the instantaneous value to be observed for an extended period of time.
30
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
The last value measured is displayed.
7. Description of program numbers
7.2.6 Zero point suppression
A defined indication range is represented by 0000. With this function a fluctuating
indication of the zero point is avoided.
Example: Parameter 10 = indication range -10 ... +10 is displayed as 0000.
PN
18
Function
Zero point suppression
Parameter
EN
0 ... 99999
7.2.7 Display brightness
PN
19
Function
Display brightness
Parameter
0 ... 9 (0 = bright, 9 = dark)
7.3 Setting the analogue output (option)
The analogue output gives the measured values of the digital indicator as a standard
signal (DC 0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA).
7.3.1 Start and end value
The analogue output can be assigned any measuring input. The output signal is
updated simultaneously with the measuring input. The refresh rate is determined by
the configured measuring time. The start and end value for the analogue signal can be
assigned user-defined measured values.
The start and end values define at which display value the minimum and maximum
output signal will be given. The display value is dependent upon the setting of the input
signal (→ see chapter 7.1.1 “Input signal”)
PN
Function
Parameter
21
Start value
-9999 ... 99999
14053538.02 05/2017 EN
20
Full scale
-9999 ... 99999
WIKA operating instructions digital indicator, model DI35-M
31
7. Description of program numbers
7.3.2 Reference value
The reference value is the value which is given via the analogue output.
PN
22
Function
Reference value
EN
Parameter
0 = analogue output deactivated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
7.3.3 Output signal
PN
23
Function
Output signal
Parameter
0 = DC 0 ... 10 V
1 = 0 ... 20 mA
2 = 4 ... 20 mA
In addition, the output signal must be set via the DIP switch on the rear of
the instrument.
DC 0 ... 10 V = switch set to the right
0/4 ... 20 mA = switch set to the left
Example
A rotational speed of 0 ... 3,000 min-1 should be transmitted to a control room via
4 ... 20 mA. The rotational speed sensor is connected to measuring input 1.
1. Set the end value to 3,000.
2. Set the start value to 0.
3. Set the reference value to 1.
5. Set the DIP switch.
⇒⇒Analogue output is set.
32
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
4. Set the output signal to 2.
7. Description of program numbers
7.4 Setting the serial interface (option)
PN
34
Function
Interface properties
Parameter
0 = standard mode
1 = sending mode
Interface properties
Standard mode
(= configuration mode)
EN
Description
In this mode, the digital indicator can be configured. Responses
will only be transmitted on request.
The current measured value can be queried via “A↵”.
Sending mode
Measured values are sent cyclically. The cycle corresponds to
the set measuring time.
Cancel sending mode
The sending mode is cancelled on receipt of “> ↵” and the instrument returns to standard mode.
Activate sending mode
Restart the digital indicator or transmit the command “S ↵”.
Protocol structure
Display values are transmitted in ASCII format. Minus signs and decimal points can
be displayed directly on a terminal display or processed by a PLC. Leading spaces
are disabled with transmission. With an over- or underrange, hyphens are transmitted
“- - - - - ↵”.
Example: “0.00 ↵”; “-9.99 ↵” ; “999.99 ↵”; “-123.45”; “ - - - - - ↵”; “Lbr ↵”
The display values can be processed or stored on a PC via a terminal program.
Settings
Point-to-point connection
Transmission rate 9,600 baud
8 data bits
without parity
1 stop bit
14053538.02 05/2017 EN
■■
■■
■■
■■
■■
WIKA operating instructions digital indicator, model DI35-M
33
7. Description of program numbers
7.5 Setting user authorisations
7.5.1 Authorisation levels
Via the user authorisation, it is possible to limit which settings can be made by the
operator. The authorisations can be allocated in different authorisation levels.
Function
PN
Authorisation level
1
2
3
4
5
6
7
8
Changing the display brightness
19








Allocating the locking code
50








Reading the serial number
200








Changing switch points
61, 71, 81, 91







-
Setting the switching output
59 ... 95






-
-
Setting the interface
32 ... 34




-
-
-
-
Setting the analogue output
20 ... 22




-
-
-
-
Setting measuring inputs
0 ... 18



-
-
-
-
-
Carrying out a linearisation
100 ... 130



-
-
-
-
-
Inputting a release code
51

-
-
-
-
-
-
-
Changing the authorisation level
52
-
-
-
-
-
-
-
-
The authorisation levels can only be changed if the release code corresponds to the
locking code (password protection). On delivery, both parameters are set to the value
0000, whereby the programming lockout is deactivated.
The control level is selected via PN53. The simple control level serves as the basic
setting. Only those program numbers which sufficiently enable the digital indicator to
be put into operation are displayed. With this, the assigned start and end values for
the measuring signal are automatically transferred to the analogue output. (→ For the
accessible program numbers see appendix “Program number table”)
The professional control level allows access to all program numbers and enables the
programming of complex applications.
PN
Function
Parameter
51
Release code
0000 ... 9999
52
Authorisation level
0 ... 8
53
Control level
1 = simple
2 = professional
50
34
Locking code
0000 ... 9999
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
7. Description of program numbers
7.5.2 Cancelling the password protection
The password protection is cancelled when the release code corresponds to the locking
code.
If the locking code is lost, the instrument can be reset by the
manufacturer.
EN
7.6 Setting the switching outputs
The switching outputs can be configured independently.
7.6.1 Flashing display on reaching the switch points
A switch point being exceeded can be signalled via a simultaneous flashing of the
7-segment display and switch point display.
PN
59
Function
Flashing display
Parameter
0 = not flashing
1 = at switch point 1
2 = at switch point 2
3 = at switch point 3
4 = at switch point 4
5 = at switch point 1 + 2
6 = at switch point 3 + 4
7 = at switch point 1 + 2 + 3 + 4
Reading the switching status
The switching status of the switching outputs can be read from the switch point display.
14053538.02 05/2017 EN
Switch point display
WIKA operating instructions digital indicator, model DI35-M
35
7. Description of program numbers
7.6.2 Reference value
The reference value is the value to which the switching output reacts.
PN
Function
70
Reference value, switching output 2
80
Reference value, switching output 3
90
Reference value, switching output 4
60
0 = deactivated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
7.6.3 Switch points
PN
Function
Parameter
71
Switch point, switching output 2
-9999 ... 99999
81
Switch point, switching output 3
-9999 ... 99999
91
Switch point, switching output 4
-9999 ... 99999
61
36
Switch point, switching output 1
-9999 ... 99999
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
Reference value, switching output 1
Parameter
7. Description of program numbers
7.6.4 Switch behaviour
PN
Function
72
Hysteresis, switching output 2
82
Hysteresis, switching output 3
92
Hysteresis, switching output 4
63
Switching function, switching output 1
73
Switching function, switching output 2
83
Switching function, switching output 3
93
Switching function, switching output 4
64
Switching delay, switching output 1
74
Switching delay, switching output 2
84
Switching delay, switching output 3
94
Switching delay, switching output 4
14053538.02 05/2017 EN
62
Hysteresis, switching output 1
65
Delay type, switching output 1
75
Delay type, switching output 2
85
Delay type, switching output 3
95
Delay type, switching output 4
67
Switch point acknowledgement, switching
output 1
77
Switch point acknowledgement, switching
output 1
87
Switch point acknowledgement, switching
output 1
97
Switch point acknowledgement, switching
output 1
Parameter
1 ... 99999
EN
0 = normally closed
1 = normally open
0 ... 10 seconds
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on and switch-off delay
4 = s uppression via activated digital
input
0 = no lock
1 = s witch-off lock via multi-function
button
2 = s witch-off lock via digital input
3 = s witch-off lock via multi-function
button or digital input
4 = no lock
5 = s witch-on lock via multi-function
button
6 = s witch-on lock via digital input
7 = s witch-on lock via multi-function
button or external input
WIKA operating instructions digital indicator, model DI35-M
37
7. Description of program numbers
Measured value
Messwert
Switch point
Schaltpunkt
Hysterese
Hysteresis
Time
Zeit
Switching status
Schaltzustand
on
ein
aus
off
38
Time
Zeit
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
Normally open
Below the switch point, the switching output is switched off. On reaching the switch
point, the switching output is switched off.
switch point, the switching output is switched on.
The switching output is switched off only when the switch point, less the hysteresis, is
reached.
7. Description of program numbers
Normally closed
Below the switch point, the switching output is switched on. On reaching the switch
point, the switching output is switched off.
The switching output is switched on only when the switch point, less the hysteresis, is
reached.
Measured value
Messwert
Schaltpunkt
Switch point
Hysterese
Hysteresis
Time
Zeit
Switching status
Schaltzustand
on
ein
14053538.02 05/2017 EN
aus
off
WIKA operating instructions digital indicator, model DI35-M
Time
Zeit
39
EN
7. Description of program numbers
Switch-on delay
The switching output is switched on only when the input signal remains above the switch
point for at least the set switching delay.
This function prevents an unwanted switching of the switching output as a result of a
short-term fluctuation of the input signal.
Measured value
Messwert
Schaltpunkt
Switch point
Time
Zeit
Switching status
Schaltzustand
on
ein
aus
off
Time
Zeit
Einschaltverzögerung
Switching delay
40
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
7. Description of program numbers
Switch-off delay
The switching output is switched off only when the input signal remains under the switch
point for at least the set switching delay.
This function prevents an unwanted switching of the switching output as a result of a
short-term fluctuation of the input signal.
EN
Measured value
Messwert
Schaltpunkt
Switch point
Time
Zeit
Switching status
Schaltzustand
on
ein
aus
off
Time
Zeit
14053538.02 05/2017 EN
Ausschaltverzögerung
Switching delay
WIKA operating instructions digital indicator, model DI35-M
41
7. Description of program numbers
7.7 Linearising sensors
Non-linear sensors can be linearised with up to 30 interpolation points per measuring
input.
At each interpolation point, the input signal is manually assigned a new display value.
The analogue output is also linearised since it is proportional to the display values.
Each interpolation point must have a higher input signal than the previous. The corresponding display values can be freely assigned.
PN
Function
Parameter
101 ... 130
Display value for interpolation point
-9999 ... 99999
100
Number of interpolation points
0 ... 30
Procedure
1. Set the number of interpolation points under PN 100/PN 140.
2. Apply the input signal for the first interpolation point, PN 101/PN 141, at the
measuring input.
3. Set the desired display value under PN 101/PN 141.
⇒⇒Input signal is associated with display value.
4. Repeat steps 2 + 3 for all interpolation points.
⇒⇒Input signal is linearised.
42
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
7. Description of program numbers
Example
Linearisation of a pressure transmitter for 0 ... 100 mbar with an output signal of
0 ... 20 mA.
■■ Programming with 5 interpolation points.
■■ Non-linear range 0 ... 75 mbar.
Interpolation
point
Pressure
[mbar]
Transmitter output signal [mA]
Display value [mbar]
PN 2
0
0.5
2.5
0.0
PN 101
15
3.3
16.5
15.0
after linearisation
before
linearisation
PN 102
30
6.2
31.0
30.0
PN 103
40
9.2
46
40.0
PN 104
60
11.4
57
60.0
PN 105
75
14.7
73.5
75.0
PN 1
100
20
100.0
100.0
For PN 101 this means:
With a pressure of 15 mbar, the transmitter delivers an output signal of 3.3 mA instead
of 3.0 mA. Therefore, before correction, the display shows 16.5 mbar. This value is
adjusted to 15.0 mbar using the interpolation point.
Anzeigewert
Display value
100
90
80
105
70
60
104
50
40
30
14053538.02 05/2017 EN
Mit Linearisierung
With
linearisation
103
Ohne Linearisierung
Without
linearisation
102
20
Stützpunkte points
Interpolation
101
10
10
20
30
40
50
60
70
80
90
WIKA operating instructions digital indicator, model DI35-M
100
110
Druck
Measured
value
43
EN
7. Description of the program number
7.8 Totaliser function
The totaliser function sums measuring results which are determined as the result of a
programmable calculation. The measuring results are summed until a reset is carried
out.
PN
Function
Parameter
181
Time basis of the display value
0 = second
1 = minute
2 = hour
182
Factor in powers of 10
0 = 1 ... 6 = 1,000,000
183
Decimal place
00000 ... 0.0000
180
Totaliser function
0 = off
1 = t otaliser function without permanent storage (reset on restart)
2 = t otaliser function with permanent
storage
In order to calculate a totaliser value, the time basis and the unit are of particular
importance. The flow is defined in volume per time and the speed with distance per time.
Through parameterisation of the time basis (PN181), the totaliser value is summed.
Example
If a sensor measures 1,200 l/h, with a measurement time of 1 s, one must only sum a
3,600th fraction of the litres counted, which, in this case, would be approx. 0.333 litres
per measuring cycle. Despite this very small size, the totaliser value can sum up to an
extremely high value within a timespan of one year. In this example, that means there
were approximately 10,512,000 litres in one year.
An indication in cubic metres would be useful here. In order to realise this, one must
define a factor - in our example PN182 = 3 (10-3). With this, the value in litres can be
converted into cubic metres.
If one only wishes to integrate the quantity only over one month, one can still add a
decimal point to the visualisation as cubic metres under PN183.
If one now parameterises the factor PN182 = 2 and the decimal point PN183 = 1, this
would lead to a display of 864.0 cubic metres at the end of a month.
44
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
7.8.1 Calculation
7. Description of the program number
7.8.2 Reset
PN
Function
Parameter
185
Trigger for reset
0 = no trigger
1 = multi-function button
2 = digital input
3=m
ulti-function button or digital
input
4 = [ ▲] or [▼] while totaliser value is
displayed
184
Reading value, start value
0 ... 99999
7.8.3 Display change to totaliser value
PN
186
Function
Trigger for display change
Parameter
0 = no trigger
1 = multi-function button
2 = digital input
7.9 Reading the serial number
PN
200
Function
Serial number
Parameter
0 ... 99999
7.10 Restore factory settings
The factory settings can only be restored if the programming lock PN 50 allows access
to all PNs or HELP is displayed. All application-specific data will be lost.
1. Switch off the power supply.
2. Press the multi-function button.
14053538.02 05/2017 EN
3. Apply power supply and hold the multi-function button for 2 s.
⇒⇒Factory settings are restored.
WIKA operating instructions digital indicator, model DI35-M
45
EN
8. Faults
8.Faults
CAUTION!
Physical injuries and damage to property and the environment
If faults cannot be eliminated by means of the measures listed above, the
instrument must be taken out of operation immediately.
▶▶ Ensure that pressure or signal is no longer present and protect against
accidental commissioning.
▶▶ Contact the manufacturer.
▶▶ If a return is needed, follow the instructions given in chapter 10.2
“Returns”.
EN
Faults
Instrument shows permanent
overrange
Causes
One of the measuring inputs
has a very high measured
value
Measures
Check measuring path
With a measuring input with
a small voltage signal, this is
only connected on one side or
the input is open
Not all activated interpolation
points are parameterised
Check relevant parameter
The arithmetic result gives an
overrange
Instrument shows a permanent underrange
One of the measuring inputs
has a very small measured
value
Check measuring path
With a measuring input with
a small voltage signal, this is
only connected on one side or
the input is open
Not all activated interpolation
points are parameterised
Check relevant parameter
Instrument displays “HELP”
Error in the configuration
memory
Restore factory settings and
re-enter the settings
Display values are changing in
very large jumps
With a division, the measured
value of the divisor is very
small
small
Check measuring path
46
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
The arithmetic result gives an
underrange
8. Faults
Faults
Program numbers are not
available
Causes
Access through user authorisation denied
Measures
Set sensor type is preventing
the desired program number
from being parameterised
EN
The analogue output is an
option. If this is not implemented, then the
Program numbers greyed out
Instrument displays “Err1”
Contact the manufacturer
Digital input does not react
Measure input current of
digital input. It should lie
between 1 ... 3 mA.
14053538.02 05/2017 EN
Illustration of overrange
Illustration of underrange
WIKA operating instructions digital indicator, model DI35-M
47
9. Maintenance and cleaning
9.Maintenance and cleaning
9.2 Cleaning
DANGER!
Danger to life caused by electric current
Upon contact with live parts, there is a direct danger to life.
▶▶ Only clean the case and contacts when the current is disconnected.
CAUTION!
Unsuitable cleaning agents
Cleaning with unsuitable cleaning agents may damage the instrument
and the product label.
▶▶ Do not use any aggressive cleaning agents.
▶▶ Do not use any hard or pointed objects.
▶▶ Do not use any abrasive cloths or sponges.
1. Disconnect the digital indicator from the supply.
2. Wipe the instrument surface using a soft, damp cloth.
48
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
9.1 Maintenance
This digital indicator is maintenance-free.
Repairs must only be carried out by the manufacturer.
10. Dismounting, return and disposal
10.Dismounting, return and disposal
10.1 Dismounting, version for control panel
1.
2.
3.
4.
Disconnect the digital indicator from the supply.
Disconnect the electrical connection.
Remove the mounting elements.
Pull the digital indicator out of the control panel.
EN
10.2 Return
Strictly observe the following when shipping the instrument:
All instruments delivered to WIKA must be free from any kind of hazardous substances
(acids, bases, solutions, etc.) and must therefore be cleaned before being returned.
When returning the instrument, use the original packaging or a suitable transport
packaging.
Information on returns can be found under the heading “Service” on our
local website.
14053538.02 05/2017 EN
10.3 Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally
compatible way and in accordance with the country-specific waste disposal regulations.
WIKA operating instructions digital indicator, model DI35-M
49
11. Specifications
11.Specifications
Digital indicator
EN
Principle
7-segment LED, red, 5-digit, brightness adjustable in 10
gradations
Character size
14 mm
Indication range
-9999 ... 99999
Display rate
0.1 ... 10.0 seconds
Memory
EEPROM (parameter memory), data preservation > 100 years
Inputs
Inputs
1 x multi-function input
digital input
< 2.4 V off, > 10 V on, max. DC 30 V, Ri approx. 5 kΩ
Input signals
See the following tables “Accuracy/measuring errors of the input
signals”
Input configuration
Selectable via terminal connections and menu-driven
programming
Accuracy
See the following tables “Accuracy/measuring errors of the input
signals”
Temperature error
50 ppm/K, at ambient temperature TU < 20 °C or
TU > 40 °C
Measuring principle
Sigma/delta
Resolution
24 bit (with 1 second measuring time)
Measuring time
0.02 ... 10.0 s
Transmitter power supply
DC 24 V, max. 50 mA, galvanically isolated
Analogue output (option)
Number and type
1 analogue output (galvanically isolated)
Output signal
4 ... 20 mA (12-bit), load ≤ 500 Ω
0 ... 20 mA (12-bit), load ≤ 500 Ω
DC 0 ... 10 V (12-bit), load ≥ 100 kΩ
Error
0.1 % in the range 20 ... 40 °C
50 ppm/K outside temperature error
Internal resistance
100 Ω (with measuring input DC 0 ... 10 V)
50
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
Specifications
11. Specifications
Specifications
Switching output (option)
Number and type
2 or 4 switch contacts (relays), freely programmable
Load capacity
AC 250 V, 5 A (resistive load)
DC 30 V, 5 A (resistive load)
Number of switching
operations
0.5 ∙105 at max. contact load
5 ∙ 106 mechanical
Isolation in accordance with DIN EN 50178
Parameters in accordance with DIN EN 60255
Voltage supply
Power supply
See product label
Power supply galvanically isolated
AC 100 ... 240 V, 50/60 Hz, DC 100 ... 240 V
DC 10...40 V, AC 18 ... 30 V, 50/60 Hz
Overvoltage category II
Power consumption
Max. 15 VA
Electrical connection
Removable plug-in terminal
Wire cross-section up to 2.5 mm²
Serial interface (option)
Interface
EN
See product label
■■ RS-232 (not galvanically isolated)
■■ RS-232 (galvanically isolated)
■■ RS-485 (not galvanically isolated, only for point-to-point
connection)
■■ RS-485 (galvanically isolated, only for point-to-point connec-
tion)
Protocol
Manufacturer-specific ASCII
Baud rate
9,600 baud, no parity, 8 data bits, 1 stop bit
Cable length
RS-232: max. 3 m
RS-485: max. 1,000 m
14053538.02 05/2017 EN
Case
Material
Glass-fibre reinforced polycarbonate, black
Ingress protection
Front: IP65, rear: IP00 (per IEC 60529)
Weight
approx. 350 g
Recommended mounting grid
120 mm horizontal, 96 mm vertical
Mounting
Sliding mounting elements, fixed via screws, for wall
thicknesses up to 15 mm
WIKA operating instructions digital indicator, model DI35-M
51
11. Specifications
Specifications
Operating conditions
Operation: 0 ... 50 °C
Storage: -20 ... +80 °C
Humidity
0 ... 75 % r. h. annual mean, without condensation
Requirements for the installation location
■■ Pollution degree 2
■■ No direct sunlight or proximity to hot objects
■■ No mechanical vibration, mechanical shock (putting it down
hard)
■■ No soot, vapour, dust or corrosive gases
Accuracy/measuring errors of the input signals
Inputs with factory calibration
Input signals
Measuring
span
Current signals
0 ... 20 mA
Voltage signals
52
Measuring error
Minimum measuring
in % of the
time
measuring span 1)
≤ ±0.02 % ±1 digit
4 ... 20 mA
≤ ±0.02 % ±1 digit
DC 0 ... 18 mV
≤ ±0.06 % ±1 digit
DC 0 ... 35 mV
≤ ±0.06 % ±1 digit
DC 0 ... 75 mV
≤ ±0.04 % ±1 digit
DC 0 ... 150 mV
≤ ±0.03 % ±1 digit
DC 0 ... 300 mV
≤ ±0.03 % ±1 digit
DC 0 ... 600 mV
≤ ±0.03 % ±1 digit
DC 0 ... 1,250 mV
≤ ±0.03 % ±1 digit
DC 0 ... 2,500 mV
≤ ±0.03 % ±1 digit
DC 0 ... 5 V
≤ ±0.02 % ±1 digit
DC 0 ... 10 V
≤ ±0.01 % ±1 digit
0.02 s
0.02 s
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
Permissible ambient
temperatures
11. Specifications
Input signals
Measuring
span
Measuring error
Minimum measuring
in % of the
time
measuring span 1)
Type B, PtRh-PtRh
-100 ... +1,810 °C
≤ ±0.10 % ±1 digit
Type E, NiCr-CuNi
-260 ... +1,000 °C
≤ ±0.06 % ±1 digit
Type J, Fe-CuNi
-210 ... +1,200 °C
≤ ±0.05 % ±1 digit
Type K, NiCr-Ni
-250 ... +1,271 °C
≤ ±0.05 % ±1 digit
Type L, Fe-CuNi
-200 ... +900 °C
≤ ±0.06 % ±1 digit
Type N, NiCrSi-NiSI
-250 ... +1,300 °C
≤ ±0.06 % ±1 digit
Type R, PtRh-Pt
0 ... 1,760 °C
≤ ±0.07 % ±1 digit
Type S, PtRh-Pt
0 ... 1,760 °C
≤ ±0.06 % ±1 digit
Type T, Cu-CuNi
-240 ... +400 °C
≤ ±0.07 % ±1 digit
Thermocouples
Resistance thermometer
0.04 s
EN
2)
Pt100 (2-/4-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.04 s
Pt100 (3-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.06 s
Pt200 (2-/4-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.04 s
Pt200 (3-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.06 s
Pt500 (2-/4-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.04 s
Pt500 (3-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.06 s
Pt1000 (2-/4-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.06 s
Pt1000 (3-wire)
-200 ... +850 °C
≤ ±0.04 % ±1 digit
0.04 s
14053538.02 05/2017 EN
1) The indication of the measuring error applies to ambient temperatures of 20 ... 40 °C and the measuring time
of 1 second.
2) The indications for Pt100 3-/4-wire apply at a max. lead resistance of 10 Ω.
WIKA operating instructions digital indicator, model DI35-M
53
11. Specifications
Inputs for sensor calibration
Input signals
Voltage signals
Resistance (2-, 3-,
or 4-wire)
0 ... 2 mA
Measuring error
in % of the
measuring span 1)
≤ ±0.02 % ±1 digit
0 ... 5 mA
≤ ±0.02 % ±1 digit
0 ... 20 mA
≤ ±0.02 % ±1 digit
4 ... 20 mA
≤ ±0.02 % ±1 digit
DC -18 ... +18 mV
≤ ±0.06 % ±1 digit
DC -35 ... +35 mV
≤ ±0.06 % ±1 digit
DC -75 ... +75 mV
≤ ±0.04 % ±1 digit
DC -150 ... +150 mV
≤ ±0.03 % ±1 digit
DC -300 ... +300 mV
≤ ±0.03 % ±1 digit
DC -500 ... +600 mV
≤ ±0.03 % ±1 digit
DC -500 ... +1,250 mV
≤ ±0.03 % ±1 digit
DC -500 ... +2,500 mV
≤ ±0.03 % ±1 digit
DC -1 ... +5 V
≤ ±0.02 % ±1 digit
DC -1 ... +10 V
≤ ±0.01 % ±1 digit
0 Ω ... 100 Ω
≤ ±0.04 % ±1 digit
0 Ω ... 1 kΩ
≤ ±0.04 % ±1 digit
0 Ω ... 10 kΩ
≤ ±0.04 % ±1 digit
Minimum
measuring time
0.02 s
0.02 s
0.04 s
1) The indication of the measuring error applies to ambient temperatures 20 ... 40 °C and the measuring time of
1 second.
54
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
Current signals
Measuring span
11. Specifications
Dimensions in mm
inc
luedins
inchglie 10
fißxlich 7,0
ingBe
afettstig
acung
hm
e
0,0
12
EN
nts
DI3
5
3,0
DS
ice
hta
unli
gn
48,0
g
96
,0
om
cktlie
uess
cnhnl
s
o
n
gh Ac
dßilnic
hlulie ,0
nnscc 139
i
i
e
h
efte
tip
adue
innb
rtiEo
l
na
mi
er
nmte
e
14053538.02 05/2017 EN
Ins
WIKA operating instructions digital indicator, model DI35-M
55
Appendix 1: Overview of program numbers
Appendix 1: Overview of program numbers
PN
Measuring input 1
0
Measuring input
Parameter
Factory
setting
Authorisation level
Control
level
Current
01 = 0 ... 20 mA
02 = 4 ... 20 mA
3
2
1
Voltage
03 = DC 0 ... 10 V
04 = DC 0 ... 5 V
05 = DC 0 ... 2,500 mV
06 = DC 0 ... 1,250 mV
07 = DC 0 ... 600 mV
08 = DC 0 ... 300 mV
09 = DC 0 ... 150 mV
10 = DC 0 ... 75 mV
11 = DC 0 ... 35 mV
12 = DC 0 ... 18 mV
Temperature measurement
13 = Pt100 (4-/2-wire)
14 = Pt100 (3-wire)
15 = Pt200 (4-/2-wire)
16 = Pt200 (3-wire)
17 = Pt500 (4-/2-wire)
18 = Pt500 (3-wire)
19 = Pt1000 (4-/2-wire)
20 = Pt1000 (3-wire)
21 = L
22 = J
23 = K
24 = B
25 = S
26 = N
27 = E
28 = T
29 = R
56
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
Function
Appendix 1: Overview of program numbers
PN
Function
Parameter
0
Measuring input
Resistance
30 = ≤ 100 Ω (4-/2-wire)
31 = ≤ 1 kΩ (4-/2-wire)
32 = ≤ 10 kΩ (4-/2-wire)
Factory
setting
3
Authorisation level
2
Control
level
1
EN
14053538.02 05/2017 EN
Sensor calibration
33 = 0/4 ... 20 mA
34 = DC -1 ... +10 V
35 = DC -1 ... + 5 V
36 = DC -500 ... +2,500 mV
37 = DC -500 ... +1,250 mV
38 = DC -500 ... +600 mV
39 = DC ±300 mV
40 = DC ±150 mV
41 = DC ±75 mV
42 = DC ±35 mV
43 = DC ±18 mV
44 = 0 ... 5 mA
45 = 0 ... 2 mA
1
Full scale
-9999 ... 99999
10000
2
1
2
Start value
-9999 ... 99999
0
2
1
3
Number of decimal
places
00000 ... 0.0000
(not for temperature measurement)
00000
2
1
Resistance thermometers
(PN0 = 13 ... 20)
0 = 8888.8 (°C)
1 = 8888.8 (°F)
2 = 8888 °C
3 = 8888 °F
4 = 888.8 °C (-99.9 ... 999.9)
5 = 888.8 °F (-99.9 ... 999.9)
2
2
2
Thermocouple
(PN0 = 21 ... 29)
0 = 8888.8 (°C)1)
1 = 8888.8 (°F) 1)
2 = 8888 °C
3 = 8888 °F
2
2
2
WIKA operating instructions digital indicator, model DI35-M
57
Appendix 1: Overview of program numbers
PN
Function
Parameter
5
Offset value
Analogue/resistance
measurements and sensor
calibration
EN
Factory
setting
Authorisation level
Control
level
0
2
2
Temperature sensors
(PN0 = 13 ... 29)
Measuring range
0
2
2
6
Comparative
measurement table
0 = deactivated
1 = activated
1
2
2
7
Set value for the
taring
-9999 ... 99999
0
2
2
8
Trigger for taring
00 = none
01 = digital input
02 = multi-function button
03 = digital input without
button
04 = system start
05 = combination 1 + 4
06 = combination 2 + 4
07 = combination 3 + 4
08 = temporarily via digital
input
09 = quickly via digital input
10 = quickly via multi-function
button
11 = quickly via multi-function
button and digital input
0
2
2
General settings
12
Running averaging
0 = off
1 ... 100 measured values
0
2
2
13
Refresh rate
0.1 ... 10.0 s
1.0
2
2
58
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
(PN0 = 1 ... 12 and 30 ... 45)
-9999 ... 99999
Appendix 1: Overview of program numbers
PN
Function
Parameter
14
Measuring time
Current, voltage
(PN0 = 1 ... 12 or 33 ... 45)
0.02 ... 10
Factory
setting
1.0
Authorisation level
2
Control
level
2
Resistance (4-/2-wire)
0.04 ... 10
EN
Resistance (3-wire)
0.06 ... 10
Thermocouple
(PN0 = 21 ... 29)
0.04 ... 10
15
Display mode
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
8 = trigger mode
1
2
2
16
Trigger for MIN/MAX 0 = no trigger
reset
1 = digital input
2 = multi-function button
3 = digital input or multifunction button
4 = on taring
2
2
2
18
Zero point suppression
0 ... 99999
10000
4
2
19
Display brightness
0 ... 9 (0 = bright, 9 = dark)
3
8
2
-9999 ... 99999
1000
2
2
Analogue output (option)
14053538.02 05/2017 EN
20
Full scale
21
Start value
-9999 ... 99999
0
2
2
22
Reference value
0 = deactivated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
1
4
2
23
Output signal
0 = DC 0 ... 10 V
1 = 0 ... 20 mA
2 = 4 ... 20 mA
2
4
1
WIKA operating instructions digital indicator, model DI35-M
59
PN
Function
Interface
34
EN
Interface properties
User authorisation
Parameter
Factory
setting
Authorisation level
Control
level
0 = standard mode
1 = transmission mode
0
4
2
50
Locking code
0000 ... 9999
0000
8
2
51
Release code
0000 ... 9999
0000
0
2
52
Authorisation level
0 ... 8
8
0
2
53
Control level
1 = simple
2 = professional
1
2
1
0 = deactivated
1 = at switch point 1
2 = at switch point 2
3 = at switch point 3
4 = at switch point 4
5 = at switch point 1 + 2
6 = at switch point 3 + 4
7 = at switch point 1 + 2 + 3
+4
0
6
2
0 = deactivated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
1
6
1
Special functions
59
Flashing display
Switching output 1
60
Reference value
61
Switch point
-9999 ... 99999
1000
6
1
62
Hysteresis
1 ... 99999
1
6
1
63
Switching function
0 = normally closed
1 = normally open
1
6
1
64
Switching delay
0 ... 10.0 seconds
0.0
6
1
65
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on and switch-off
delay
4 = suppression via activated
digital input
1
6
1
60
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
Appendix 1: Overview of program numbers
Appendix 1: Overview of program numbers
PN
Function
Parameter
67
Switch point
acknowledgement
0 = no lock
1 = switch-off lock via multifunction button
2 = switch-off lock via digital
input
3 = switch-off lock via multifunction button or digital
input
4 = no lock
5 = switch-on lock via multifunction button
6 = switch-on lock via digital
input
7 = switch-on lock via multifunction button or external
input
0
0 = deactivated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
1
Switching output 2
14053538.02 05/2017 EN
70
Reference value
Factory
setting
Authorisation level
6
Control
level
2
EN
6
1
71
Switch point
-9999 ... 99999
1000
6
1
72
Hysteresis
1 ... 99999
1
6
1
73
Switching function
0 = normally closed
1 = normally open
1
6
1
74
Switching delay
0 ... 10.0 seconds
0.0
6
1
75
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on and switch-off
delay
4 = suppression via activated
digital input
1
6
1
WIKA operating instructions digital indicator, model DI35-M
61
Appendix 1: Overview of program numbers
Function
Parameter
77
Switch point
acknowledgement
0 = no lock
1 = switch-off lock via multifunction button
2 = switch-off lock via digital
input
3 = switch-off lock via multifunction button or digital
input
4 = no lock
5 = switch-on lock via multifunction button
6 = switch-on lock via digital
input
7 = switch-on lock via multifunction button or external
input
0
6
2
0 = deactivated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
1
6
1
EN
Switching output 3
80
Reference value
Factory
setting
Authorisation level
Control
level
81
Switch point
-9999 ... 99999
1000
6
1
82
Hysteresis
1 ... 99999
1
6
1
83
Switching function
0 = normally closed
1 = normally open
1
6
1
84
Switching delay
0 ... 10.0 seconds
0.0
6
1
85
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on and switch-off
delay
4 = suppression via activated
digital input
1
6
1
62
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
PN
Appendix 1: Overview of program numbers
PN
Function
Parameter
87
Switch point
acknowledgement
0 = no lock
1 = switch-off lock via multifunction button
2 = switch-off lock via digital
input
3 = switch-off lock via multifunction button or digital
input
4 = no lock
5 = switch-on lock via multifunction button
6 = switch-on lock via digital
input
7 = switch-on lock via multifunction button or external
input
0
0 = deactivated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = running average
6 = totaliser value
7 = absolute value
1
Switching output 4
14053538.02 05/2017 EN
90
Reference value
Factory
setting
Authorisation level
6
Control
level
2
EN
6
1
91
Switch point
-9999 ... 99999
1000
6
1
92
Hysteresis
1 ... 99999
1
6
1
93
Switching function
0 = normally closed
1 = normally open
1
6
1
94
Switching delay
0 ... 10.0 seconds
0.0
6
1
95
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on and switch-off
delay
4 = suppression via activated
digital input
1
6
1
WIKA operating instructions digital indicator, model DI35-M
63
Appendix 1: Overview of program numbers
Function
Parameter
97
Switch point
acknowledgement
0 = no lock
1 = switch-off lock via multifunction button
2 = switch-off lock via digital
input
3 = switch-off lock via multifunction button or digital
input
4 = no lock
5 = switch-on lock via multifunction button
6 = switch-on lock via digital
input
7 = switch-on lock via multifunction button or external
input
EN
Linearisation
100 Number of interpola- 0 ... 30
tion points
Measuring input 1
101 Display value for
...
interpolation point
130
Totaliser function
Factory
setting
Authorisation level
Control
level
0
6
2
0
2
2
2
2
-9999 ... 99999
180 Totaliser function
0 = off
1 = totaliser function without
permanent storage (reset
on restart)
2 = totaliser function with
permanent storage
0
3
2
181 Time basis of the
display value
0 = second
1 = minute
2 = hour
0
3
2
182 Factor in powers
of 10
0 = 1 ... 6 = 1,000,000
0
3
2
183 Decimal place for
totaliser value
00000 ... 0.0000
0
3
2
184 Reading value, start
value
0 ... 99999
0
3
2
64
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
PN
Appendix 1: Overview of program numbers
PN
Function
185 Trigger for reset
186 Trigger for display
change
Serial number
14053538.02 05/2017 EN
200 Reading the serial
number
Parameter
Factory
setting
Authorisation level
0 = no trigger
1 = multi-function button
2 = digital input
3 = multi-function button or
digital input
4 = [▲] or [▼] while totaliser
value is displayed
0
0 = no trigger
1 = multi-function button
2 = digital input
0
3
2
0 ... 99999
0
8
2
WIKA operating instructions digital indicator, model DI35-M
3
Control
level
2
EN
65
66
WIKA operating instructions digital indicator, model DI35-M
14053538.02 05/2017 EN
EN
14053538.02 05/2017 EN
EN
WIKA operating instructions digital indicator, model DI35-M
67
14053538.02 05/2017 EN
WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30
63911 Klingenberg • Germany
Tel. +49 9372 132-0
Fax +49 9372 132-406
[email protected]
www.wika.de
68