SICK CLP 100 Bar Code Reader Operating Instructions

SICK CLP 100 Bar Code Reader Operating Instructions

Below you will find brief information for Bar Code Reader CLP 100. The CLP 100 is a barcode reader that is used to automatically detect and decode barcodes. It is installed as a reading station and reads barcodes on objects, such as those in a clinical automatic analyzer. The CLP 100 transmits the decoded bar code information via its host interface to a host computer for further processing.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Bar Code Reader CLP 100 Operating Instructions | Manualzz
CLP 100
Bar Code Reader
O
P E R A T I N G
I
N S T R U C T I O N S
Operating Instructions
CLP 100 Bar Code Reader
Described software state
Software/Tool
Function
Revision index
CLP 100
Firmware
From V 1.10
CLP Setup
User interface (window-based)
From V 1.10
CLP Setup Help
On-line help (HTML)
From V 1.10
I-ViewPro™
Off-line browser (HTML)
V 2.38
Abbreviations used
CLP
Code Leser Parallel (Code Reader Parallel)
CCD
Charge Coupled Device
PLC
Progammable Logic Controller
HTML
Hyper Text Markup Language
LED
Light Emitting Diode
Production state of the CLP 100
Device type
Revision index
CLP 100-0010
0000
CLP 100-2010
0000
CLP 100-0110
0000
CLP 100-2110
0000
Windows 95™, Windows 98™, Windows NT™ and Internet Explorer™ are registered
trademarks or trademarks of the Microsoft Corporation in the USA and other countries.
I-ViewPro™ is a registered trademark of the EnReach Technology, Inc., USA.
2
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Contents
CLP 100 Bar Code Reader
Contents
1
Notes on this document...................................................................................................... 5
1.1
Function ................................................................................................................................... 5
1.2
Target audience.................................................................................................................... 5
1.3
Information content ............................................................................................................. 5
1.4
Symbols used ........................................................................................................................ 5
2 Safety information................................................................................................................. 5
2.1
Authorized users................................................................................................................... 5
2.2
Intended use.......................................................................................................................... 6
2.3
General safety instructions............................................................................................... 6
2.4
Quick- Stop and Quick-Restart ........................................................................................ 6
2.5
Environmental information ................................................................................................ 7
3 Product description .............................................................................................................. 7
3.1
Design....................................................................................................................................... 7
3.2
Working method of the device........................................................................................ 9
3.3
Display and operating elements..................................................................................... 9
4 Installation.............................................................................................................................10
4.1
Installation sequence....................................................................................................... 10
4.2
Preparations for installation........................................................................................... 10
4.3
Installation and adjustment of the device................................................................ 13
4.4
Installing the reading-pulse sensor............................................................................. 14
4.5
Disassembling the device.............................................................................................. 15
5 Electrical installation .........................................................................................................15
5.1
Electrical connections...................................................................................................... 15
5.2
Pin assignment of the connection plug or wire colors of the cable end...... 15
5.3
Planning the electrical installation ............................................................................... 16
5.4
Carry out the electrical installation.............................................................................. 16
6 Operation ...............................................................................................................................19
6.1
Startup steps ...................................................................................................................... 19
6.2
Default setting .................................................................................................................... 19
6.3
Quick-Start ........................................................................................................................... 20
6.4
Operating modes and output of the read result ................................................... 21
6.5
Parameterization................................................................................................................ 21
6.6
Switching off the CLP 100 ............................................................................................. 26
7 Maintenance.........................................................................................................................26
7.1
Maintenance during operation ..................................................................................... 26
7.2
Maintenance ....................................................................................................................... 27
7.3
Disposal ................................................................................................................................ 27
8 Troubleshooting...................................................................................................................28
8.1
Possible errors and faults .............................................................................................. 28
8.2
Troubleshooting table...................................................................................................... 29
8.3
SICK support....................................................................................................................... 30
9 Technical data......................................................................................................................31
9.1
Data sheet CLP 100 ........................................................................................................ 31
9.2
Dimensional drawings...................................................................................................... 32
10 Appendix ................................................................................................................................33
10.1 Appendix overview............................................................................................................ 33
10.2 Installation and handling of the CLP Setup software........................................... 33
10.3 Reading area diagram ..................................................................................................... 38
10.4 Calculation of the number of scans ........................................................................... 39
10.5 Calculation of the code length of a bar code ......................................................... 40
10.6 Command language for CLP bar code readers..................................................... 41
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
3
Tables and figures
Operating Instructions
CLP 100 Bar Code Reader
Tables
Tab. 3-1:
Tab. 3-2:
Tab. 4-1:
Tab. 5-1:
Tab. 5-2:
Tab. 5-3:
Tab. 5-4:
Tab. 5-5:
Tab. 5-6:
Tab. 6-1:
Tab. 8-1:
Tab. 9-1:
Tab. 10-1:
Tab. 10-2:
Tab. 10-3:
Variants of the CLP 100......................................................................................................7
Meaning of the LED displays ..........................................................................................10
Permissible angle occurring between the scan line and the bar code bars 12
Pin assignment of the connection plug ......................................................................15
Assignment of the wire colors of the cable end......................................................16
Maximum cables lengths between the CLP 100 and the host.........................16
Communication parameters of the host interface (default setting) ................17
Characteristic data of the "Sensor" switching input ..............................................18
Characteristic data of the "Result" switching output.............................................19
Default setting of the parameters of the CLP 100 ................................................20
Troubleshooting table........................................................................................................29
Technical specification of the CLP 100......................................................................31
Default settings of CLP Setup ........................................................................................34
Auxiliary table for calculating the code length of a bar code..............................40
Command language for CLP bar code readers.......................................................41
Figures
Fig. 3-1:
Fig. 3-2:
Fig. 3-3:
Fig. 4-1:
Fig. 4-2:
Fig. 4-3:
Fig. 4-4:
Fig. 4-5:
Fig. 4-6:
Fig. 4-7:
Fig. 5-1:
Fig. 5-2:
Fig. 5-3:
Fig. 5-4:
Fig. 6-1:
Fig. 6-2:
Fig. 6-3:
Fig. 7-1:
Fig. 9-1:
Fig. 9-2:
Fig. 10-1:
Fig. 10-2:
Fig. 10-3:
Fig. 10-4:
4
Design of the CLP 100 with face-end light emission ...............................................8
Design of the CLP 100 with side light emission.........................................................8
Function of the CLP 100 .....................................................................................................9
Position of the threaded holes at CLP 100 ..............................................................11
Reading distance to the object......................................................................................11
90° angle between the scan line and the bar code bars ...................................12
Reading angle occurring between the scan line and the bar code bars.......12
Angle between the emitted light and the bar code
(tilted to the perpendicular).............................................................................................13
Adjustment of the CLP 100 in order to avoid reflections;
a: With front-end light emission, b: With side-end light emission .....................13
Installation site for the reading-pulse sensor and the reflector
(b smaller than a)................................................................................................................14
Wiring the host interface ..................................................................................................17
Wiring the terminal interface...........................................................................................18
Wiring of the "Sensor" switching input........................................................................18
Wiring of the "Result" switching output (NPN) .........................................................19
Bar code sample (code 39, 0.35 mm, printing ratio 2:1)...................................21
Terminal emulator with input of a command string ...............................................23
Terminal emulator with reading results of the CLP 100
in diagnosis mode...............................................................................................................25
CLP 100 with front-end reading window (a) and
side-end reading window (b) ..........................................................................................26
Dimensions of the CLP 100 with front-end light emission in mm....................32
Dimensions of the CLP 100 with side-end light emission in mm.....................32
User interface of the CLP Setup software .................................................................36
Reading area diagram .......................................................................................................38
Calculation example: Number of scans for ladder positioning
of the bar code bars ..........................................................................................................39
Calculation example: Number of scans for fencing positioning
of the bar code bars ..........................................................................................................39
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Notes on this document
Operating Instructions
Chapter 1
CLP 100 Bar Code Reader
1
Notes on this document
1.1
Function
This document instructs you on using the CCD bar code reader CLP 100.
It contains information on
• Device installation and electrical installation
• Startup
• Operation and configuration (parameterization)
• Maintenance
1.2
Target audience
The target audience for this document consists of electricians, service technicians and
engineers.
1.3
Information content
This document contains all the information required for the installation, electrical installation
and startup of the bar code reader CLP 100 with the default setting in our works.
All actions are described step-by-step.
Parameterization of the CLP 100 for the application-specific reading configuration is
carried out with the CLP Setup user interface. Installation and use of the software are
described in the appendix.
Further information on the construction of the bar code reader as well as the bar code
technology can be obtained from SICK AG, Auto Ident Division.
1.4
Symbols used
Some information in this document is emphasized.
Note
Recommendation
Hint
A "Note" informs on exceptional features.
A "Recommendation" provides information on how to carry out an action optimally.
A "Hint" explains the setting possibilities in the CLP Setup software.
THIS FONT characterizes a term used in the user interface of the CLP Setup software (for
example, menu item, tab card).
2
Safety information
2.1
Authorized users
The CLP 100 must be installed and operated by qualified personnel in order to ensure that
it functions correctly and safely. The following qualifications are required for the various
activities:
Installation and maintenance
• Practical electrical training
• Knowledge of the common safety instructions at the workplace
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
5
Chapter 2
Safety information
Operating Instructions
CLP 100 Bar Code Reader
Electrical installation and replacing devices
• Practical electrical training
• Knowledge of the common electrical safety instructions
• Knowledge of the operation and handling of the devices of the respective application
(for example, packaging machines, clinical automatic analyzer, access control)
Startup, operation and configuration
• Knowledge of the operation and handling of the devices of the respective application
(for example, packaging machines, clinical automatic analyzer, access control)
• Basic knowledge of Windows 95™, Windows 98™ or Windows NT™
• Basic knowledge of a HTML browser (for example, Netscape Navigator™)
• Basic knowledge of serial data transmission
• Basic knowledge of bar code technology
2.2
Intended use
The CLP 100 is used for the automatic detection and decoding of bar codes. It is installed
as a reading station and reads, for example, bar codes on objects of a clinical automatic
analyzer. The CLP 100 transmits the decoded bar code information via its host interface to
a host computer for further processing.
The user forfeits any warranty claims against SICK AG in case of any other use as well as in
case of changes to the device, also during device installation and electrical installation .
2.3
General safety instructions
Read the general safety instructions thoroughly and observe them strictly at all activities
at the bar code reader. This also applies to the warnings before the handling instructions
in the individual chapters of this document.
LED lighting can endanger your eyes!
The CLP 100 uses an LED illumination line. The retina can be damaged if you look too long
into the beam.
Do not look directly into the LED illumination line.
2.4
Quick- Stop and Quick-Restart
2.4.1
Switching off the CLP 100
Switch off the supply voltage.
At the most the last read result is lost.
2.4.2
Switching on the CLP 100 again
Switch on the supply voltage.
The CLP 100 resumes operation with the last parameter set saved.
6
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Product description
Chapter 3
CLP 100 Bar Code Reader
2.5
Environmental information
The CLP 100 is designed so that it harms the environment as little as possible. It does not
contain or emit any substances harmful to the environment and is not a source of faults for,
for example, coating wetting in paint shops.
The maximum power consumption of the CLP 100 amounts to 2 W.
2.5.1
Disposal after final removal from service
Dispose of unusable or irreparable devices in accordance with the respective state
regulations on waste disposal in a manner compatible with the environment. The CLP 100
design allows it to be separated into recyclable secondary raw materials (housing) and
hazardous waste (electronic scrap). Also refer to Section 7.3, Page 27. At present, SICK AG
does not take back devices which have become unusable or irreparable.
3
Product description
3.1
Design
3.1.1
Scope of delivery
The packing of the CLP 100 contains the following:
• One bar code reader CLP 100
• One information sheet (notes on device) with connection diagram and Quick-Start
Depending on the number of devices ordered one or more of the following are included:
• These CLP 100 operating instructions in English and German
• A set of DOS-formatted diskettes (3.5") containing the CLP Setup operating software for
Windows™, the CLP Setup Help on-line help system and the HTML browser I-ViewPro™
3.1.2
Variants
At present the CLP 100 is available in the following variants:
Device
Light emission
Connection
CLP 100-0010
Front
9-pin D-Sub plug
CLP 100-2010
Side
9-pin D-Sub plug
CLP 100-0110
Front
Open cable end
CLP 100-2110
Side
Open cable end
Tab. 3-1: Variants of the CLP 100
3.1.3
System requirements
The following are required to start-up and operate the CLP 100:
• A public supply system device with an output voltage of 5 V DC ± 5 % in accordance with
IEC 742 (functional extra-low voltage) and at least 2 W power output
• In the case of external reading pulsing via the "Sensor" switching input: A suitable sensor
for signaling an object with bar code, for example, a reflection photoelectric switch
• A PC with Windows 95™, Windows 98™ or Windows NT™ and a serial interface
("COM x" port)
• An RS-232 data connection cable (TxD and RxD transposed)
• In order to use a CLP Setup Help on-line help system an HTML browser, for example,
Netscape Navigator™ or the enclosed I-ViewPro™ (refer to Section 3.1.1 Scope of
delivery)
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
7
Product description
Chapter 3
Operating Instructions
CLP 100 Bar Code Reader
3.1.4
! !
Design
"
§
! !
$
! !
$
Legend:
! Threaded hole M 3, 5 mm deep
" Connection cable
§ Reading window
$ LED status display
Fig. 3-1:
Design of the CLP 100 with face-end light emission
! !
"
§
Legend:
! Threaded hole M 3, 5 mm deep
" Connection cable
§ Reading window
$ LED status display
Fig. 3-2:
8
Design of the CLP 100 with side light emission
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Product description
Chapter 3
CLP 100 Bar Code Reader
3.2
Working method of the device
The CCD bar code reader CLP 100 detects bar codes in an illuminated scan field (scan line)
and decodes the bar codes. The CLP 100 transmits this data via the serial host interface to
a host/PC for further processing. Refer to Figure 3-3 for an overview of the functionality of
the CLP 100.
CLP 100
CCD line with lighting
Decoder
Host
Interface
Photoelectric
switch
Reading
pulse
Result function
"Sensor"
"Host"
e.g. Good Read/
No Read
"Result"
"Terminal"
DC 5 V ± 5 %
PC
--- Cable if required
Fig. 3-3:
Function of the CLP 100
The CLP 100 derives useful data for diagnostics from the reading processes. The quality of
the reading data can be checked in the diagnosis mode.
The CLP 100 requires suitable pulsing (triggering) in order to start a reading process when
there is an object in the reading area. This results in a time window for the reading process
being opened in the CLP 100. Triggering is carried out either with an external sensor or with
a command string via the host interface. Both options are active in the default setting.
The switching input ("Sensor" input) informs the CLP 100 when it must start a reading
process. The switching output ("Result" output) can have result functions assigned to them
and triggers external devices such as, for example, a PLC input.
3.3
Display and operating elements
The CLP 100 is operated or parameterized via the host interface by using the CLP Setup
PC software or with command strings. The CLP 100 is adapted to various applications by
means of parameterization. The CLP Setup software is used, for example, to carry out the
following settings:
• Configuration of the code types to be read
• Read, evaluation and output properties
• Communication parameters of the host interface
• Structure of the data output strings of the host interface
• Function of the auxiliary interface (terminal interface)
Section 10.2, Page 33 describes the installation and handling of the CLP Setup software.
The procedure for parameterizing the CLP 100 with the software is explained in Section 6.5,
Page 21.
An LED status display ("Monitor") with two LEDs (red and green) on the rear of the CLP 100
indicates the current operating state of the device. The meaning of the display for the
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
9
Installation
Chapter 4
Operating Instructions
CLP 100 Bar Code Reader
respective operating mode is shown in Table 3-2. The display can be parameterized
differently in some operating modes. The table lists all the possible meanings.
:
Operating mode
Display
Function
Start
Green/
red
• Light up during the switching on phase if the self-test is
successful
• Extinguish when changing to the read standby state
Reading mode
Adjusting mode
Matchcode
operation
Green/
red
• Light up when the signal for reading is given, until the
Green
• Lights up after successful reading ("Good Read")
Red
• Extinguishes after successful reading ("Good Read")
Green
• Extinguishes after unsuccessful reading ("No Read")
Red
• Lights up after unsuccessful reading ("No Read")
Green/
red
• Extinguish, when there was no signal for reading and there
Red
• Lights up at "No Read" or "Read & No Match"
beginning of the next reading cycle
is no read result
or in accordance with the parameterization
• Lights up at "No Read" or "Read & Match"
Green
• Lights up at "Read & Match"
or in accordance with the parameterization
• Lights up at "Read & No Match"
Tab. 3-2: Meaning of the LED displays
4
Installation
4.1
Installation sequence
• Select the installation site for the CLP 100
• Connect the power supply
• Align the CLP 100 to the bar code
• Install the CLP 100
• Adjust the CLP 100
• Install the external sensor for the reading pulse
4.2
Preparations for installation
4.2.1
Laying out the components to be installed ready
• CLP 100 bar code reader
4.2.2
Laying out the required tools ready
• 2 screws for fixing the CLP 100 to the installation site
Screw diameter: 3 mm,
Screw length depends on the wall thickness of the base.
Screws may not be screwed more than 5 mm into the CLP 100
• Tool
• Measuring tape
• Angulometer
10
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Installation
Chapter 4
CLP 100 Bar Code Reader
4.2.3
Selecting the installation site
When selecting the installation site take the distance between the CLP 100 and the host as
well as the distance between the CLP 100 and the bar code into consideration. The angle
between the scan line and bar code is selected, so that a good reading is possible. The
optimal setting of the angle is described further below.
The CLP 100 is fastened by means of two threaded holes (M 3) to the top or bottom of the
device (refer to Figure 4-1). The complete housing dimensions are shown in Section 9.2,
Page 32.
! !
Fig. 4-1:
! !
Position of the threaded holes !at CLP 100
Distance between the CLP 100 and the host
The maximum distance between the CLP 100 and the host when extension cables are used
amounts to 12 m (host interface RS-232).
Distance between the CLP 100 and the bar code
The distance a between the reading window of the CLP 100 and the bar code must amount
to 20 to 70 mm depending on the width of the bar code (refer to Figure 4-2). Section 10.3,
Page 38 shows the width of the reading area of the CLP 100 in relation to the reading
distance for various resolutions (module widths).
a
Fig. 4-2:
8 008 912/0000/16-11-99
Reading distance to the object
© SICK AG · Auto Ident · Germany · All rights reserved
11
Chapter 4
Installation
Operating Instructions
CLP 100 Bar Code Reader
Angle alignment of the CLP 100
The optimum alignment of the CLP 100 is reached at an angle of 90° between the scan line
and the bar code bars (refer to Figure 4-3). Possible reading angles which can arise
between the scan line and the bar code bars must be taken into consideration (refer to
Figure 4-4 and Table 4-1).
Fig. 4-3:
90° angle between the scan line and the bar code bars
Fig. 4-4:
Reading angle occurring between the scan line and the bar code bars
Angle
Limit
Tilt α
0° ± 2°
Pitch β
0° ± 5°
Skew γ
10° ± 5°
Tab. 4-1: Permissible angle occurring between the scan line and the bar code bars
12
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Installation
Operating Instructions
Chapter 4
CLP 100 Bar Code Reader
Note
If the light of the scan line falls exactly vertically on the surface of the bar code, disturbing
reflections can occur when the reflected light is received. In order to avoid this effect the
CLP 100 must be installed so that the emitted light is tilted relative to the perpendicular
(refer to Figure 4-5).
Front-end light emission
Side-end light emission
10°
10°
Bar code
8
15
Bar code
Reading
Distance
Fig. 4-5:
Reading
Distance
Angle between the emitted light and the bar code (tilted to the perpendicular)
4.3
Installation and adjustment of the device
4.3.1
Installing the CLP 100
1. Align the CLP 100 so that the angle between the scan line and the bar code bars
amounts to 90°. Take any possible reading angle occurring into consideration (refer to
Figure 4-4).
2. In order to avoid disturbing reflections align the CLP 100 so that the emitted light impacts
on the bar code at an angle of 100° (refer to Figures 4-5 and 4-6).
Damage to the housing
The screws may not be screwed more than 5 mm into the CLP 100. Longer screws may
damage the housing.
Use screws with a suitable length.
3. Screw the screws through the base to which the CLP 100 is fastened into the threaded
hole.
4. Tighten the screws slightly.
5. Adjust the CLP 100 as described below.
a
b
100°
Fig. 4-6:
8 008 912/0000/16-11-99
100°
Adjustment of the CLP 100 in order to avoid reflections;
a: With front-end light emission, b: With side-end light emission
© SICK AG · Auto Ident · Germany · All rights reserved
13
Chapter 4
Installation
Operating Instructions
CLP 100 Bar Code Reader
4.3.2
Adjusting the CLP 100
The adjusting operating mode supports the adjustment of the CLP 100. In this operating
mode the green LED extinguishes if the reading process fails ("No Read"). If the green LED
does not light up, the CLP 100 cannot read the bar code. If the green LED flickers, the CLP
100 can only read the bar code badly. If the green LED shows steady light, the CLP 100 is
aligned optimally. The scanning frequency in adjusting mode amounts to 500 Hz.
1. Connect the CLP 100 to the supply voltage and switch on the supply voltage.
2. Connect the CLP 100 to the PC.
3. Call up the CLP Setup user interface (refer to Section 10.2, Page 33).
4. In the CLP Setup select the DEVICE CONFIGURATION tab card.
5. Click in the OPERATING MODE field and select ADJUSTING MODE.
6. Click in the LED DISPLAY field and select NO READ/GOOD READ.
7. Carry out the download to the CLP 100 (refer to Section 6.5.1, Page 21).
8. Guide objects with bar codes realistically into the reading area of the CLP 100. Ensure
that the permitted reading angle is not exceeded.
9. Start the reading pulse: Cover the optical path of the sensor or make connection (refer
to Section 4.4).
10. Align the CLP 100 so that the green LED lights up steadily as far as possible (reading
result "Good Read").
11. Tighten the screws.
The CLP 100 is aligned optimally to the bar code.
4.4
Installing the reading-pulse sensor
If the CLP 100 is triggered via an external sensor, the sensor and a reflector have to be
installed near the CLP 100. Figure 4-7 shows an example of the installation site of the
sensor.
a
b
Fig. 4-7:
14
Installation site for the reading-pulse sensor and the reflector (b smaller than a)
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Electrical installation
Chapter 5
CLP 100 Bar Code Reader
1. Install the reading-pulse sensor at the installation site.
2. Connect the reading-pulse sensor to the CLP 100 (refer to Section 5.4.5, Page 18).
3. Call up the CLP Setup and check the read result with the terminal emulator (refer to
Section 6.5, Page 21).
4. Check whether the reading process of the CLP 100 is synchronized with the incoming
objects.
4.5
Disassembling the device
1. Switch off the supply voltage.
2. Disconnect the cable connection.
3. Screw off the CLP 100.
4. Dispose of the CLP 100 ecologically friendly (refer to Section 7.3, Page 27).
5
Electrical installation
5.1
Electrical connections
The electrical connection of the CLP 100 is carried out either via a 9-pin D-Sub cable plug
or the open cable end.
5.2
Pin assignment of the connection plug or wire colors of
the cable end
1
6
5
9
Pin
Signal
1
Sensor
2
RxD (Host)
3
TxD (Host)
4
Result "GO/NG"
5
GND
6
Not assigned
7
RxD (Terminal), TTL
8
TxD (Terminal), TTL
9
+5 V
Tab. 5-1: Pin assignment of the connection plug
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
15
Electrical installation
Chapter 5
Operating Instructions
CLP 100 Bar Code Reader
Wire color open
cable end
Signal
Pink
Sensor
Brown
RxD (Host)
Gray
TxD (Host)
White
Result "GO/NG"
Black
GND
Yellow
RxD (Terminal), TTL
Orange
TxD (Terminal), TTL
Red
+5 V
Blue
RTS
Green
CTS
Tab. 5-2: Assignment of the wire colors of the cable end
5.3
Planning the electrical installation
5.3.1
Requirements for the host interface
The host interface of the CLP 100 is operated as an RS-232 interface. For the pin
assignment refer to Table 5-1 or Table 5-2.
Table 5-3 shows the recommended maximum cable lengths as a function of the data
transmission rate.
.
Interface type
Transmission rate
Max. distance to the host
RS-232
Up to 19,200 bits/s
12 m
Tab. 5-3: Maximum cables lengths between the CLP 100 and the host
Recommendation
In order to avoid interferences, do not lay the cable parallel to the power-supply and motor
cables (for example in cable ducts).
5.3.2
Supply voltage
For operation the CLP 100 requires a supply voltage of 5 V DC ± 5 % in accordance with
IEC 742 (functional extra-low voltage). The power supply unit must also fulfil IEC 742 and
output a continuous output of 2 W.
5.4
Carry out the electrical installation
5.4.1
Installation steps
• Connecting the supply voltage
• Wiring the host interface (Connecting the PC)
• Wiring the "Sensor" switching input
• Wiring the "Result" switching output
5.4.2
16
Connecting the supply voltage
Connect the supply voltage to Pin 5 and Pin 9 of the 9-pin plug (refer to Table 5-1,
Page 15).
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Electrical installation
Chapter 5
CLP 100 Bar Code Reader
5.4.3
Wiring the host interface (Connecting the PC)
The CLP 100 is operated and configured with the CLP Setup software. For this purpose it
must be connected to the PC via the host interface.
When the PC is connected, the communications parameters are set as described in
Section 6.5.1, Page 21.
Figure 5-1 shows the wiring of the RS-232 host interface.
*) 9-pin internal D-Sub plug to PC
Fig. 5-1:
Wiring the host interface
Damage to the interface module in the CLP 100!
Electronic components in the CLP 100 can be damaged if the host interface is wired
incorrectly.
Recommendation
Wire the host interface correctly in accordance with Figure 5-1.
Check the wiring before switching on the CLP 100.
Connect the host interface of the CLP 100 EMC-compatibly to the host by means of
shielded cables (refer to Figure 5-1). Observe the maximum cable lengths (refer to
Table 5-3, Page 16).
Apply the shielding at one end.
1. Switch off the PC and the supply voltage of the CLP 100.
2. Connect the desired port "COM x" of the PC to the CLP 100. To this purpose use an
RS-232 data connection cable (RxD and TxD transposed).
3. Switch on the PC and the supply voltage of the CLP 100.
4. Set the communication parameters of the PC (refer to Section 10.2.3, Page 34).
In the default setting the CLP 100 communicates via the RS-232 interface with the host
using the values listed in Table 5-4.
Parameter
Host interface value
Terminal interface value
Data transmission
rate
9600 bits/s
9600 bits/s
Data bit
8
8
Parity
None
None
Stop bit
1
1
Protocol
SICK:
Sending start characters: STX
Sending stop characters: ETX
Repeat request: None
Timeout: 50 ms
SICK:
Sending start characters: STX
Sending stop characters: ETX
Repeat request: None
Timeout: 50 ms
Tab. 5-4: Communication parameters of the host interface (default setting)
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
17
Electrical installation
Chapter 5
Operating Instructions
CLP 100 Bar Code Reader
5.4.4
Wiring the terminal interface
As an alternative the PC may be connected to the terminal interface.
Figure 5-2 shows the wiring of the terminal interface.
Note
The terminal interface is a TTL level interface.
7
3*
8
2*
5
5*
*) 9-pin internal D-Sub plug to PC
Fig. 5-2:
5.4.5
Wiring the terminal interface
Wiring the "Sensor" switching input
If a reading process is to be triggered via an external sensor, connect the sensor to the
"Sensor" switching input. This triggering type is selected as the default setting of the CLP
100. Figure 5-3 shows the wiring of the "Sensor" switching input. Table 5-5 lists the
characteristic data of this switching input.
5V
"Sensor"
1
GND
5
CLP 100
Fig. 5-3:
Sensor
Wiring of the "Sensor" switching input
Connect the sensor as described in Figure 5-3.
Switching
performance
Connecting GND to the input starts the read port of the CLP 100 (low)
Properties
Not electrically separated
Electrical values
Low
(Read port active):
0 V ≤ V S ≤ 0.8 V
High
(Read port inactive):
2.4 V ≤ V S ≤ 5 V
I ≤ 1.5 µA
I ≤ 1.5 µA
Tab. 5-5: Characteristic data of the "Sensor" switching input
Hint
18
The DEVICE CONFIGURATION tab card of the CLP Setup software can be used to modify the
response time of the "Sensor" input (debouncing).
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operation
Operating Instructions
Chapter 6
CLP 100 Bar Code Reader
5.4.6
Wiring the "Result" switching output
The switching output can have various result functions assigned to it. If the corresponding
event occurs during a reading process, the switching output becomes live for the selected
pulse duration. Figure 5-4 shows the wiring of the "Result" switching output. Table 5-5 lists
the characteristic data of the switching output.
Fig. 5-4:
Recommendation
Wiring of the "Result" switching output (NPN)
In order to check the switching functions wire the switching output to a load and measure
the voltage with a high-voltage digital voltmeter. This avoids the display of incorrect
voltage values and switching states.
Wire the switching output as described in Figure 5-4.
Switching performance
NPN switching against GND
Properties
Not electrically separated
Electrical values
5V ≤ U ≤ 30V
I ≤ 50mA
Tab. 5-6: Characteristic data of the "Result" switching output
Hint
6
The DEVICE CONFIGURATION tab card of the CLP Setup software can be used to modify the
function assignment, the pulse duration and the output instant of the signal.
Operation
6.1
Startup steps
• Startup of the CLP 100 with the default setting set by factory (Quick-Start).
The CLP 100 can be operated without a connection to the PC in this configuration.
• Connecting the PC (refer to Section 5.4.4, Page 18) and installing the CLP Setup software
(refer to Section 10.2, Page 33).
• Parameterizing of the CLP 100 with the CLP Setup software or with command strings.
6.2
Default setting
Table 6-1 shows an overview of the default setting of our works for the CLP 100. The
parameters in the default setting are selected so that the CLP 100 can be used directly for
many applications in this configuration. With the default setting no PC is required for starting
up.
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
19
Chapter 6
Operation
Operating Instructions
CLP 100 Bar Code Reader
Parameter
Default setting
Active code type
Code 39
Code length
Free
Multiple reading
2
Number of codes
1
Reading direction
Both
Send start/stop characters
Not active
Check digit
None
Reading pulse generation
Active low (unchangable)
Switching output
Not active
Host interface
RS-232 (unchangable)
Protocol
Start characters STX, Stop characters ETX
Transmission rate
9600 bits/s
Data format
8 data bits, no parity, 1 stop bit
Output instant
Immediately
No Read message
BR
Tab. 6-1: Default setting of the parameters of the CLP 100
If the CLP 100 is connected to a PC, the current parameters can be changed by using the
CLP Setup software. The parameter set of the default setting is saved in the CLP Setup and
in the CLP 100 and can be re-activated at any time.
The complete default setting can be viewed by using the CLP Setup software and printed
out, if required:
1. In order to save the current settings: Select the SAVE AS menu item in the FILE menu bar
and enter the file name.
2. Click on
in the toolbar.
The default setting is loaded and is displayed in the tab cards.
3. Click on
in the toolbar.
The FILE PRINT dialog box is opened.
4. Enter the comment for the header of the output and click on OK.
The dialog box for the print settings is opened.
5. Enter the settings for printing and click on OK.
CLP Setup prints out the default settings.
6.3
Quick-Start
1. Carry out the electrical installation in accordance with Chapter 5, Page 15. A PC does not
have to be connected if the CLP 100 is operated with the default setting.
2. Switch on the supply voltage.
The LEDs of the CLP 100 light up and are extinguished after the self-test has been
completed successfully.
3. Present the bar code sample from Figure 6-1 to the CLP 100 at a distance of approx.
35 mm.
4. Start the reading pulse: Cover the optical path of the sensor (close the switch).
Both LEDs light up.
20
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Operation
Chapter 6
CLP 100 Bar Code Reader
5. End the reading pulse: Unmask the optical path of the sensor (open the switch).
If the reading has been successful, the red LED is extinguished, the green LED lights up.
The CLP 100 is ready to operate with the default setting of our works.
The CLP 100 can be switched off without the configuration data being lost, since no changes
were carried out to the parameter set.
0
Fig. 6-1:
6.4
1
2
3
4
1
2
3
4
5
Bar code sample (code 39, 0.35 mm, printing ratio 2:1)
Operating modes and output of the read result
When parameterizing the CLP 100, it is possible to choose between the following operating
modes:
• Reading mode
• Diagnostic mode
• Adjusting mode
• On-line test mode
In reading mode the CLP 100 detects the presented bar codes and emits the read result at
the end of the reading pulse via the host and terminal interface.
In diagnosis mode the quality of the bar code readings is judged. These are brought
statistically into the read field of the CLP (no transport movement). The output is emitted via
the host and terminal interface. For details on the diagnosis mode refer to Section 6.5.8,
Page 24.
In adjusting mode the CLP 100 is adjusted to the bar code (refer to Section 4.3.2, Page 14).
In the on-line test mode the CLP 100 emits the read result only via the terminal interface
and not via the host interface.
When outputting the read result, it is possible to choose between the normal reading
function and the code comparison function (matchcode). The matchcode function allows
the comparison of the read bar codes with a code which is entered at the CLP 100. It is
possible to select between complete or partial matching of the codes.
6.5
Parameterization
The CLP 100 is adapted to the specifc applications by means of the parameterization.
Parameterization is carried out either with the CLP Setup software or with command strings.
To this purpose a PC has to be connected and the CLP Setup has to be installed. Connection
of the PC to the CLP 100 is described in Section 5.4.4, Page 18. Installation and handling
of the CLP Setup software are described in the appendix (Section 10.2, Page 33).
6.5.1
Transferring the parameter set between the CLP Setup and CLP 100
In order to edit the current parameter set of the CLP 100 it must first be copied from the
CLP 100 to the CLP Setup. This process is designated as uploading.
Changes to the parameter set carried out in the CLP Setup are not effective until they have
been transferred to the CLP 100. CLP Setup always copies the complete parameter set.
Saving the parameters to the CLP 100 is designated as downloading.
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
21
Operation
Chapter 6
Operating Instructions
CLP 100 Bar Code Reader
Uploading the parameter set from the CLP 100
Click on
in the CLP Setup toolbar.
CLP Setup copies the parameter set last saved in the CLP 100 from the CLP 100 into its
database and displays its values in the tab cards.
If the CLP Setup software does not recognize the loaded parameters during uploading, a
warning is emited. Unknown parameters can be edited in the terminal emulator under
observance of the conventions for command strings. These parameters are also taken into
consideration when the parameter set is saved.
Downloading the parameter set to the CLP 100
Click on
in theCLP Setup toolbar.
The new parameter set is saved in the CLP 100.
Saving the parameter set in the CLP Setup
1. Select the SAVE AS menu item in the FILE menu bar in order to save the modified
parameter set as the new configuration file in the CLP Setup or to overwrite an existing
file.
The SAVE CLP FILE dialog box is opened.
2. Enter the path and file name in the dialog box (extension of the file name: "*.scl") and
click on OK.
The new parameter set is saved in the CLP Setup.
6.5.2
Parameterize the CLP 100 with command strings
The CLP 100 can be parameterized for example by means of the terminal emulator by
entering command strings. Parameters which are unknown to the CLP Setup can also be
used.
The command language of the CLP 100 accesses the command interpreter of the device
directly. Figure 6-2 shows a view of the terminal emulator. A0 is entered as an example in
the framed text field for entering commands. This input is repeated in the large output
window. For a full description of the command language refer to Table 10-3, Page 41.
1. Click on
in the CLP Setup toolbar.
The terminal emulator window opens.
2. Enter the command in the framed text field and press the Return key.
The command is transmitted to the CLP 100.
Note
22
The CLP 100 does not transmit an answer, but reacts immediately to the command.
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Operation
Chapter 6
CLP 100 Bar Code Reader
Fig. 6-2:
Terminal emulator with input of a command string
6.5.3
Selecting reading mode
After being switched on the CLP 100 carries out a self-test and then changes over to the
reading mode (default setting). Reading mode can be selected as follows if the CLP 100 is
in another operating mode:
1. In the CLP Setup select the DEVICE CONFIGURATION tab card.
2. Click in the OPERATING MODE field and select READING MODE.
3. Carry out the download to CLP 100.
The CLP 100 is in reading mode.
6.5.4
Adjusting the reading pulse
In the CLP 100 default setting the reading pulse (trigger) is supplied by an external sensor.
Debouncing of the sensor and the type of reading pulse end (through a time window or a
sensor signal) can be set by means of the CLP Setup software.
1. In the CLP Setup select the DEVICE CONFIGURATION tab card.
2. Select the settings in the READING PULSE or READING PULSE END field.
3. Carry out the download to CLP 100.
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
23
Chapter 6
Operation
Operating Instructions
CLP 100 Bar Code Reader
6.5.5
Triggering the reading pulse
In its default setting the CLP 100 receives the reading pulse (trigger) via an external sensor
or a command string (software trigger). For test purposes, the reading pulse can also be
triggered directly via the terminal emulator.
1. Click on
in the CLP Setup toolbar.
The terminal emulator window opens. The CLP 100 is in reading mode.
2. Click on START READING.
3. Present the bar code.
4. Click on STOP READING.
The CLP 100 outputs the read result in the window of the terminal emulator.
6.5.6
Setting the structure of the read result
In its default setting the CLP 100 sends the data contents of the bar code to the host as
the read result. In the default setting this data string is STX-/ETX-framed.
The structure of the data string can be selected by means of the HOST INTERFACE and READING
CONFIGURATION tab cards.
1. In the CLP Setup select the READING CONFIGURATION tab card.
2. Click in the SEND PREFIX list box and select a prefix from the list (A-Z, 1-0).
3. Select the HOST INTERFACE tab card.
4. Click in the SEPARATOR list field and select a separator.
5. Carry out the download to CLP 100.
The CLP 100 operates with the new settings.
6.5.7
Setting the matchcode function
The matchcode function allows the comparison of the read bar codes with a code which is
entered manually at the CLP 100 or trained in automatically (matchcode).
1. In the CLP Setup select the DEVICE CONFIGURATION tab card.
2. Click in the ACTIVE box in the COMPARE CODE field.
3. Enter the code which is to be used for comparison in the MATCHCODE text field.
4. If only a part of the code has to agree, enter the partial code in the PARTIAL COMPARISON
OF THE MATCHCODE text field, and complete the field with question marks or @ characters.
5. Selection the function of the switching output in the SWITCHING OUTPUT AT CODE COMPARISON
field.
6. Carry out the download to CLP 100.
The CLP 100 outputs a result either at agreement of the read codes with the matchcode
or at non-agreement.
6.5.8
Setting the diagnosis mode
In diagnosis mode the quality of the bar code readings is judged. These are brought
statistically into the read field of the CLP 100 (no transport movement). The CLP 100 carries
out 100 readings after the reading pulse and evaluates them.
The data string in the diagnosis mode is STX-/ETX-framed. The data string contains the bar
code information (data) at the first place, followed by a slash and a three-digit identifier. The
data string is followed by the combination of slash and identifier repeated thrice (a total of
four identifiers separated by slashes):
<STX>Data/www/xxx/yyy/zzz<ETX>.
24
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Operation
Chapter 6
CLP 100 Bar Code Reader
The maximum value of an identifier is 100. If the value is lower (one- or two-digit number),
the leading blanks will be filled with spaces. If the DISPLAY CONTROL CODE function is activated,
a space is displayed as <SPC>. The identifiers mean:
www = Number of successful readings ("Good reads")
xxx
= Number of successful decoding processes (with misinterpretations)
yyy
= Number of successful indentifications of a start or stop character (depending on
the scan direction)
zzz
= Number of readings carried out (the CLP 100 carries out 100 readings each in
the diagnosis mode)
Error-free reading and decoding of a bar code would thus have the following form:
<STX>Data/100/100/100/100<ETX>.
A reading with some failed decodings has, for example, the following form:
<STX>Data/<SPC>67/<SPC>67/100/100<ETX>.
If the CLP 100 has only recognized the start character, it transfers a question mark instead
of the data string:
<STX>?/<SPC><SPC>0/<SPC><SPC>0/100/100<ETX>.
Figure 6-3 shows further examples of reading results in the diagnosis mode:
Fig. 6-3:
Terminal emulator with reading results of the CLP 100 in diagnosis mode
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
25
Maintenance
Chapter 7
Operating Instructions
CLP 100 Bar Code Reader
The diagnosis mode can be selected directly in the terminal emulation window or set via the
tab cards:
If the terminal emulator window is active: Click in the DIAGNOSTIC MODE box and present
the bar code.
The reading process is started automatically. The CLP 100 scans the bar code once per
second.
- or -
1. If the terminal emulator window is not active: In the CLP Setup select the DEVICE
CONFIGURATION tab card.
2. Click in the OPERATING MODE field and select DIAGNOSTIC MODE.
3. Carry out the download to CLP 100.
The CLP 100 is in diagnosis mode.
4. Click on
in the CLP Setup toolbar.
The terminal emulator window opens.
5. Click on START READING.
6. Present the bar code.
The CLP 100 outputs the read result in the window of the terminal emulator.
7. In order to return to reading mode proceed as described in Section 6.5.3.
6.6
Switching off the CLP 100
1. If the parameter set was changed, download the parameter set to the CP 100 and save
the parameter set as a configuration file in the CLP Setup.
2. Switch off the supply voltage.
The last parameter set saved in the CLP 100 remains valid.
7
Maintenance
7.1
Maintenance during operation
The CLP 100 reading window is made of glass. The reading window (Figure 7-1) must be
clean in order to achieve the complete reading performance of the CLP 100. Check the
reading window regularly for dirt in particular in case of dirty or humid environments.
a
Fig. 7-1:
b
CLP 100 with front-end reading window (a) and side-end reading window (b)
If a sensor is used for triggering, its window and the reflector have to be cleaned regularly.
This avoids incorrect switching performance.
26
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Maintenance
Chapter 7
CLP 100 Bar Code Reader
LED lighting can endanger your eyes!
The CLP 100 uses an LED illumination line. The retina can be damaged if you look too long
into the laser beam.
Do not look directly into the LED illumination line.
Damage to the reading window!
Scratches and streaks on the reading window impair the reading performance.
Use a mild detergent without scouring agents.
Avoid cloths or sponges which scratch.
Clean the reading window carefully.
Clean the reading window with a soft, non-fluffing cloth and mild detergent without
scouring agents, for example antistatic glass cleaning fluid.
If necessary, clean the LED display on the device rear.
If necessary, clean the sensor window and reflector.
7.2
Maintenance
The CLP 100 operates maintenance-free.
7.3
Disposal
After removal from service dispose of unusable or irreparable devices in a manner which is
not harmful to the environment. Observe the respective state regulations on waste disposal.
1. Remove the CLP 100 housing.
2. Remove the electronic modules and connection cable.
3. Recycle the housing.
4. Dispose of electronic modules and connection cable as hazardous waste.
5. Dispose of the glass as recycled glass.
At present, SICK AG does not take back devices which have become unusable or
irreparable.
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
27
Chapter 8
Troubleshooting
Operating Instructions
CLP 100 Bar Code Reader
8
Troubleshooting
8.1
Possible errors and faults
8.1.1
Installation faults
• CLP 100 aligned unfavorably to the bar code (for example, reflections).
• Reading-pulse sensor positioned incorrectly
8.1.2
Faults during the electrical installation
• Interfaces of the CLP 100 wired incorrectly
8.1.3
Parameterization errors
• Functions not adapted to the local conditions, for example, communication parameters
of the host interface set incorrectly
8.1.4
Faults during operation
• Device fault (hardware/software)
28
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Troubleshooting
Chapter 8
CLP 100 Bar Code Reader
8.2
Troubleshooting table
Aids during troubleshooting:
• These operating instructions
• Multimeter for measuring voltage and current
Fault
Possible cause
Check
Remedy
1.
When the supply voltage is
applied to the CLP 100:
The LEDs do not light up
(LEDs must light up for
three seconds after
voltage is applied if the
self-test is successful)
1.1 CLP 100 without supply
voltage
1.1 Check the supply voltage
1.1 Check the wiring and
measure the supply
voltage (DC 5 V ± 5 %)
1.2 CLP 100 has diagnosed a
device fault during the
self-test
1.2 Switch the device off and
on again. Do the LEDs light
up?
1.2 If the LEDs do not light up,
contact the SICK service
(refer to Section 8.3,
Page 30)
CLP 100 cannot be
started via the external
sensor, Scan field of the
CLP 100 (red light) is not
displayed
or
LEDs do not light up after
an executed signal for
reading
2.1 External sensor connected
incorrectly
2.1 Check the wiring of the
external sensor
2.1 Measure the output signal
of the external sensor and
the input signal at the
CLP 100 (active low)
2.2 Photoelectric switch not
aligned to the reflector or
Optical path covered (light
scanner or inductive
sensor is not dampened)
2.2 Check the external sensor
for functionality and a free
optical path
2.2 Re-align the external
sensor
2.3 CLP 100 does not receive
command string for
pulsing via the host
interface
2.3 Check the data
connection between the
host and the CLP 100.
Check the command
strings of the host
computer
2.3 Carry out the connection
in accordance with Section
5.4, Page 16 and observe
the pin assigment. Carry
out an upload in the CLP
Setup. On the HOST
INTERFACE tab card set the
data format, protocol, start
and stop characters, baud
rate correctly. Carry out
the download to the CLP
100
3.1 No bar code in the reading
area during the reading
process
3.1 Check the interval
between the reading pulse
and presence of the bar
code in the reading area
3.1 Refer to Item 2
3.2 Scan field does not
contact the bar code
3.2 Check the adjustment. Is
the bar code in the middle
of the scan field?
3.2 Readjust the CLP 100
(refer to Section 4.3.2,
Page 14)
3.3 Reading distance incorrect
3.3 Check the reading
distance
3.3 Set the correct reading
distance, but take the
module width into
consideration (refer to
Section 10.3, Page 38)
3.4 Evaluation criteria for the
code type set incorrectly
3.4 Check the code type and
code length
3.4 Enter correct code type in
CLP Setup. Carry out
download to CLP 100
3.5 Reading angle under
which the bar code
appears is too large
3.5 Check the reading angle
3.5 Readjust the CLP 100
while ensuring that the
maximum reading angle is
observed (refer to Figure
4-4, Page 12)
2.
3.
Green LED does not light
up after the end of the
reading pulse (reading not
successful)
Tab. 8-1: Troubleshooting table
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
29
Chapter 8
Troubleshooting
Operating Instructions
CLP 100 Bar Code Reader
Fault
–continued–
3. Green LED does not light
up after the end of the
reading pulse (reading not
successful)
4.
CLP 100 does not transfer
read results after the end
of the reading pulse
Possible cause
Check
Remedy
3.6 Fault due to reflection of
the light at the bar code
3.6 Check the angle
3.6 Readjust the CLP 100 and
tilt it relative to the vertical
(refer to Figure 4-5,
Page 13)
3.7 Bar code quality is
insufficient
3.7 Check the printing
contrast, idle zones and
print tolerances of the bar
code
3.7 Have the bar code
checked (for example by
the SICK service (refer to
Section 8.3, Page 30))
4.1 No reading pulse occurred
4.1 Do the LEDs light up after
the reading pulse?
4.1 Refer to Item 2
4.2 Data connection cable
wired incorrectly
4.2 Check the wiring
4.2 Carry out the wiring in
accordance with the pin
assignment and the
connection scheme
4.3 Voltage level incorrect
4.3 Check the voltage level
4.3 Correct the voltage level
4.4 Host interface
parameterized incorrectly
4.4 Check the data format,
protocol, start and stop
characters
4.4 Carry out an upload in the
CLP Setup. On the HOST
INTERFACE tab card set the
data format, protocol, start
and stop characters, baud
rate correctly. Carry out
the download to the CLP
100
Tab. 8-1: Troubleshooting table
8.3
SICK support
The device may be defective if the error cannot be eliminated by means of the above
measures. The CLP 100 does not have any components whose functionality can be
restored by the user after a failure.
Please contact your local SICK office or subsidiary:
• The telephone and fax numbers are listet on the rear cover of this manual.
30
Please contact SICK before submitting the device for repair.
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Technical data
Chapter 9
CLP 100 Bar Code Reader
9
Technical data
9.1
Data sheet CLP 100
Type
CLP 100
Scanner design
CCD bar code reader
Light source
Visible red light (λ = 630 nm)
Artificial light compatability
0 ... 100 000 lux
Scanning/Decoding frequency
500 Hz
Reading distance/Resolution
30 ... 40 mm: 0.125 mm
30 ... 45 mm: 0.15 mm
25 ... 50 mm:
0.2 mm
25 ... 55 mm: 0.25 mm
20 ... 60 mm: 0.35 mm
25 ... 65 mm:
0.5 mm
20 ... 70 mm:
1 mm
Reading area width
80 mm (at a reading distance of 40 mm)
Minimum resolution
0.125 mm
Code types
All common bar codes
Optical displays
Status display with two LEDs (red and green)
Data interfaces
2 x (RS-232)
supply voltage
5 V DC ± 5 %
Power consumption for reading
operation
350 mA
Power consumption for standby
mode
150 mA
Housing
Metal
Enclosure rating
IP 40
EMC test
In accordance with IEC 801
Weight
Approx. 200 g
Temperature
(ambient service/storage)
0 °C ... +40 °C / −20 °C ... +70 °C
Maximum relative humdity
30 ... 85 %, non-condensing
Tab. 9-1: Technical specification of the CLP 100
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
31
Technical data
Chapter 9
Operating Instructions
CLP 100 Bar Code Reader
9.2
Dimensional drawings
55
10
5
4.5
10
5
4.5
15±1
10
4.5
5
24
24
47
10°
20
Fig. 9-1:
Dimensions of the CLP 100 with front-end light emission in mm
55
5
Fig. 9-2:
32
10
4.5
24
24
55
11±1
10°
20
Dimensions of the CLP 100 with side-end light emission in mm
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Appendix
Chapter 10
CLP 100 Bar Code Reader
10
Appendix
10.1
Appendix overview
• Installation and handling of the CLP Setup software
• Reading area diagram
• Calculation of the number of scans
• Calculation of the code length of a bar code
• Command language for CLP bar code readers
10.2
Installation and handling of the CLP Setup software
The scope of delivery of the CLP 100 includes a set of diskettes (3.5") with the CLP Setup
software. A PC with the operating system Windows 95™, Windows 98™ or Windows NT™
is required in order to use the software. The memory requirement on the hard disk amounts
to approx. 6.5 MB for the installation of CLP Setup, CLP Setup Help and I-ViewPro™.
10.2.1
Preparing the installation
1. Have the diskettes at hand.
2. Connect the PC to the host interface of the CLP 100 (refer to Section 5.4.3, Page 17).
3. Switch on the supply voltage of the CLP 100.
4. Switch on the PC and start Windows.
10.2.2
Carrying out the installation
During the installation of CLP Setup the installation program creates a main directory with
subdirectories and the required links. CLP Setup can be removed completely from the PC
by using the Uninstaller which is automatically installed as well.
First installation
1. Shut down all the applications under Windows.
2. Insert the diskette into the floppy disk drive.
3. Call up the RUN dialog box in Windows and enter the following command in the OPEN input
field: "A:\CLP_xxxx.exe" (replace xxxx by the diskette label text). Click on OK.
- or Open the Explorer, open drive A and double-click on the file "CLP_xxxx.exe" (xxxx stands
for the diskette label text).
The installation program starts and guides you through the installation with screen
messages. Die CLP Setup software and the CLP Setup Help on-line help are installed.
4. If required, install the I-ViewPro™ HTML browser (is prompted).
5. Observe the the latest information on the CLP Setup given in the Readme file.
6. Click on OK to confirm the final installation message.
Die CLP Setup software and the CLP Setup Help on-line help are installed and ready for
use.
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
33
Chapter 10
Appendix
Operating Instructions
CLP 100 Bar Code Reader
Updating an installation
There are two possibilities of installing a new version of CLP Setup:
• Installation of the new version in addition to the old version
- or • Installation of the new version instead of the old version (overwriting)
Installation of the new version in addition to the old version
When the new version is installed in addition to the old version the new CLP Setup software
is installed as described under First installation. When prompted for the target directory you
have to enter a new directory. Both software versions are available parallel, but may not be
started simultaneously. The configuration files of the old version can continue to be used in
the new version.
Installation of the new version instead of the old version
When the new version is installed instead of the old one, the files of the old version have to
be removed – with the exception of the configuration files "*.scl". The "*.scl" files contain
the parameter sets of the CLP 100.
The Uninstaller removes the program files. The Uninstaller can be used to remove either all
the files (with the exception of the configuration files) or only selected files. The default
setting is the complete removal (the configuration files are not removed). In the case of
user-specific removal the files are listed and only the selected files are removed. When
selecting files ensure that the main directory together with the "*.scl" files is not deleted.
1. Select the Uninstaller for CLP Setup in the start menu of Windows under PROGRAMS.
The Uninstaller starts and guides you through the removal with screen messages.
2. Select the type of removal (complete or user-specific).
3. The new version of CLP Setup is installed as described under First installation. Select the
same directory.
The new version of CLP Setup is installed. The configuration files of the old version can
continue to be used.
10.2.3
Starting the CLP Setup software
The CLP Setup software starts with the following default setting:
Communication
COM 1, 9600 bauds, 8 data bits, 1 stop bit, no parity
Linear measures
Metric
Language
English
Browser
Not assigned
Directory for files
"Data" (configuration files for CLP 100)
Tab. 10-1: Default settings of CLP Setup
1. Switch on the PC and start Windows.
2. Select CLP Setup in the start menu.
The introductory dialog box is displayed after the identifier for the SICK software.
3. Click on OK.
CLP Setup checks whether a bar code reader is connected to the port "COM 1" of the
PC and whether the values of the communication parameters between the bar code
reader and the PC agree. If the values agree, CLP Setup enters CONNECTED in the top
34
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Appendix
Chapter 10
CLP 100 Bar Code Reader
right-hand of the status bar.
The software loads the internal description of the bar code reader and the default setting
of the parameters from the database and displays it in the tab cards. Then the software
copies the last set saved permanently in the CLP 100 from the CLP 100. Afterwards this
is displayed in the tab cards.
The current parameter set can be edited in the tab cards.
Help in cases of problems
If the CLP Setup displays the message NO CONNECTION in the top right-hand of the status bar,
the software could not establish a connection to the CLP 100. This can have two causes.
The CLP 100 is not connected, or the communication parameters of the CLP 100 and the
PC do not agree.
1. Connect the PC to the host interface of the CLP 100 as described in Section 5.4.3,
Page 17.
2. Click on
.
The AUTO BAUD DETECT dialog box is displayed. CLP Setup checks whether a bar code
reader is connected to the port "COM 1" of the PC and whether the values of the
communication parameters between the bar code reader and the PC agree. If the values
agree, the CLP Setup displays the values of the communication parameters.
3. If CLP Setup still cannot establish a connection, click on CANCEL and select the
SERIAL INTERFACE menu item in the OPTIONS menu.
CLP Setup displays the current settings of the communication parameters.
4. Set the following communication parameters: Connected COM port, 9600 bauds,
8 data bits, 1 stop bit, no parity.
5. Click on OK.
6. Click on
.
The AUTO BAUD DETECT dialog box is displayed. CLP Setup attempts again to communicate
with the CLP 100. If this is successful, CLP Setup displays the values of the
communication parameters between the bar code reader and the PC.
7. Click on OK.
The dialog box prompts you whether the parameters of the connected device are to be
loaded.
8. In order to copy the current parameter set to the CLP Setup click on Y ES.
CLP Setup displays CONNECTED. The current parameter set can be edited in the tab cards.
10.2.4
User interface
The user interface is largely self-explanatory. The online help describes how to use the user
interface under HELP in the menu item PROGRAM INFORMATION. Figure 10-1 shows a view of
the user interface.
The user interface consists of the following elements:
• Title bar displaying the program name (CLP Setup) and the current configuration file
• Menu bar with pull-down menus
• Toolbar with icons which trigger a function when clicked on
• Status bar (top right) with scanner selection field and status field for displaying the
connection to the bar code reader
• 3 tab cards (READING CONFIGURATION, DEVICE CONFIGURATION, HOST INTERFACE).
Further dialog boxes are opened in the tab cards, if necessary
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
35
Chapter 10
Appendix
Operating Instructions
CLP 100 Bar Code Reader
Fig. 10-1: User interface of the CLP Setup software
10.2.5
Functions
The CLP Setup software provides the following functions:
• Loading of the default setting of the parameter set from the database
• Automatic attempt to communicate with the CLP 100 when the program is started
• Uploading of the parameter set which is saved in the CLP 100
• Modifying the parameters
• Downloading the modified parameter set to the CLP 100
• Saving the modified parameter set in the CLP Setup as the configuration file
• Direct access to the CLP 100 by means of a terminal emulator (parameterizing via
command strings, selection of the operating mode and triggering of the CLP 100 reading
function)
• Selection of the COM ports for adapting the data transmission parameters
• Selection menu for units used
• Selection menu for the displayed language
• Display of the last 10 edited configuration files
• Context-specific help via <F1>
36
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Appendix
Chapter 10
CLP 100 Bar Code Reader
10.2.6
Using the CLP Setup Help on-line help
The CLP Setup Help on-line help helps you in using the CLP Setup software. The help runs
under an HTML browser (for example, Netscape Navigator™, Microsoft Internet-Explorer™
or the supplied I-ViewPro™). The help can be called up context-specifically for the
parameter being edited and describes the function of the parameter and possible values
for the parameter.
Press <F1> key.
The browser window opens and the help topic is displayed.
If the browser is not found, enter the path for the browser in the opened dialog box (for
example "Iviewpro32.exe" in the directory "I-ViewPro").
In order to avoid multiple opening of the browser use the key combination
<ALT>+<TAB> or the Windows status bar to toggle between the CLP Setup and the
CLP Setup Help.
In order to call up the help overview click on the CONTENTS menu item under HELP in the
menu bar of the CLP Setup.
In the upper horizontal frame it is possible to also click on a tab tard. The parameters are
then displayed in the left-hand vertical frame. These can be selected by clicking on them.
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
37
Chapter 10
Appendix
Operating Instructions
CLP 100 Bar Code Reader
10.3
Reading area diagram
The reading area diagram shows the reading width as a ratio of the reading distance for
various resolutions. Disturbing optical effects (distortions) which can occur when the
distance is too great are taken into account when specifying the reading width.
The module width is the narrowest bar of a bar code which is still resolved.
Reading Conditions:
Test Code:
Print Ratio:
Print Contrast:
Pitch/Tilt
39
3:1
90 %
0°
Fig. 10-2: Reading area diagram
38
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Appendix
Chapter 10
CLP 100 Bar Code Reader
10.4
Calculation of the number of scans
The maximum possible number of scans for a bar code depends on the transporting speed
v. Figures 10-3 and 10-4 display one calculation example each for the possible number of
scans at ladder and fencing positionings of the bar code bars.
s
v = --t
IS
lS
v = -----------------------n ⋅ t Sc an
with
1
t Sc an = --f
lS
v = ---- ⋅ f
n
lS
n = ---- ⋅ f
v
v
0.02 m
1
n = ------------------- ⋅ 500 --m
s
1.5 ---s
Specified values:
Number of scans n = ?
Transporting speed v = 1.5 m/s
Bar length lS = 20 mm
Scanning frequency f = 500 Hz
Coding 100 % readable
n = 6.7
n = 6
Recommended minimum value n = 5
Fig. 10-3: Calculation example: Number of scans for ladder positioning of the bar code bars
s
v = --t
IC
lL H – lC
v = -----------------------n ⋅ t Sc an
ILH
v
Specified values:
Number of scans n = ?
Transporting speed v = 2 m/s
Code length with idle zone lC = 150 mm
Reading area height lLH = 400 mm
Scanning frequency f = 500 Hz
Coding 100 % readable, all scans on the code
Code window s = lLH– lC
with
1
t Sc an = --f
l LH – l C
v = ------------------ ⋅ f
n
lL H – lC
n = ------------------ ⋅ f
v
( 0.4 – 0.15 )m
1
n = ------------------------------------- ⋅ 500 --m
s
2 ---s
n = 63.5
n = 62
Recommended minimum value n = 5
Fig. 10-4: Calculation example: Number of scans for fencing positioning of the bar code bars
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
39
Appendix
Chapter 10
Operating Instructions
CLP 100 Bar Code Reader
10.5
Calculation of the code length of a bar code
The code length of a bar code corresponds to the number of used characters in the printing
image including the check digits (if they exist). The fixed code length can be specified in the
CLP Setup.
The code length can be determined by counting the bars and gaps if the code type of a bar
code is known. The respective equation for calculation is shown in Table 10-2.
1. Count the bars and possibly gaps as specified in Table 10-2. Also count the start and
stop characters.
2. Calculate the code length in accordance with the equation specified in the table.
3. Carry out the input in the CLP Setup as specified in Column 4 of Table 10-2.
Calculation of the code length1)2)
Code type
Count
Input in the CLP Setup
Code 39
Number of bars
Number – 10
I Code = ---------------------------------5
Calculated code length
2/5 Interleaved
Number of wide elements
(bars and gaps)
Number – 1
I Code = --------------------------------2
Calculated code length
EAN
Not applicable
13 characters (normal version)
8 characters (short version)
activate 13-digit
activate 8-digit
UPC
Not applicable
12 characters (UPC A, normal version)
8 characters (UPC E, short version)
Activate Version A
Activate Version E
Codabar
Number of bars
Number – 8
I Code = --------------------------------4
Calculated code length
Code 128
(character set A)
Number of bars
Number – 10
I Code = -----------------------------------3
Calculated code length
EAN 128
Number of bars
Number – 10
I Code = -----------------------------------3
Calculated code length
1) Check digit optional for Code 39, 2/5 Interleaved, Codabar.
Check digit always integrated in the bar code print at EAN, UPC, Code 128, EAN 128 in accordance with specification
(is suppressed automatically at the output of the read result of the CLP 100)
2) With few exceptions each printed character corresponds to an ASCII character which has to be decoded.
In the case of Code 39 extended, Code 128 and EAN 128 the number of characters in the data string of the CLP 100 can exceed the number of characters in the printing
image because it consists of several character sets.
Tab. 10-2: Auxiliary table for calculating the code length of a bar code
40
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Appendix
Chapter 10
CLP 100 Bar Code Reader
10.6
Command language for CLP bar code readers
Table 10-3 lists the commands of the command language for CLP bar code readers. The
default settings of the respective parameters are printed in bold.
Parameter
Character
Value
Sensor Input
A
0: LEVEL 0,mm: EDGE mm s (mm = 1-60 ms)
1: OFF
Code Type
B
0: ALL CODES
1: CODE 39
2: ITF
4: JAN (UPC)
5: ITF-B
7: CODE 128
Check Digits
C
0: NO CHECK
1: SEND C/D
3: NOT SEND C/D
(Codabar Only)
0: NO CHECK
1: SEND M16
2: SEND 7DR
3: NOT SEND M16
4: NOT SEND 7DR
Reading Direction
D
0: NOT SPECIFIED
1: FORWARD
2: REVERSE
Option (Code 128)
E
0: NOT SEND
1: SEND THROUGH
2: SEND TRANSLATED
Baud Rate
F
0: 1200
1: 2400
3: 9600
4: 19200
Cs Control
H
0: NO CONTROL
1: CONTROL
Transmit Leading
Character
K
0:
NONE
2,“N“: C = 0-9 (30h-39h) & Upper Character
Memory
M
0: DEFAULT
1: RECALL N. V. MEMORY
2: WRITE N. V. MEMORY
Code Length
N
0:
FREE
1-32: Specified Digits (1-32)
Data/Parity/Stop
Bits
P
0: 7O1
1: 7O2
2: 7E1
3: 7E2
4: 8N1
5: 8N2
6: 8O1
7: 8O2
8: 8E1
9: 8E2
10: 7N1
11: 7N2
Tab. 10-3: Command language for CLP bar code readers
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
41
Chapter 10
Appendix
Operating Instructions
CLP 100 Bar Code Reader
Parameter
Character
Value
Error String
R
0: NOT SEND
1: BR
2: ?
3: <CAN>
4: ERROR
Transmit Start/
Stop
S
0: SEND
1: NOT SEND
Terminator
T
0: NONE
1: <SX>/<EX>
2: /<CR><LF>
3: /<CR>
4: <SX>/<EX><CR>
5: <EX>/<CR>
Read Out
W
0: VERSION INFORMATION
4: BAUD RATE/FRAME (1 STOP)
5: BAUD RATE/FRAME (2 STOP)
Multiple Reads
X
1-10: 1-10 Times
2:
2 Times
End Of Reading
Interval
Y
0: GENERATED BY TRIGGER
Y1,nn: 01-99 BY TIMER
Number Of Codes
UA
0:
FREE
1-10: 1-10 Labels to be read with one Sens.
Output On Good
Read
UB
0: AFTER SENSOR
1: AFTER READ
Operation Mode
UC
0: READING MODE
1: DIAGNOSIS MODE
2: ONLINE TESTING MODE
3: ADJUSTMENT MODE
Minimum Time
Between Labels
UD
0: NOT READ nn: 01-99 = Prohibition Time 10-990 ms
Result Output Time
UE
0:
HOLD
1-99: 10-990 ms
10:
100 ms One Shot
Result Output
Timing
UF
0: AFTER READ
1: AFTER SENSOR OFF
Host Interface
UH
0:
LED Control
UI
0: CCD ON (Red) & READING GATES ON (Green)
1: NO READ (Red) & GOOD READ (Green)
Result Function
UJ
0: DISABLED
1: GOOD READ
2: NO READ
Code Comparison
UN
0: NO
1: YES
Result Output On
Code Comparison
UQ
0: ACTIVE HIGH ON READ & MATCH
1: ACTIVE HIGH ON READ & NO MATCH
Teach In Code
Comparison
UR
0: NO
1: YES
Codabar Start/
Stop Character
US
0: LOWER CASE
1: UPPER CASE
RS-232C
Tab. 10-3: Command language for CLP bar code readers
42
© SICK AG · Auto Ident · Germany · All rights reserved
8 008 912/0000/16-11-99
Operating Instructions
Appendix
Chapter 10
CLP 100 Bar Code Reader
Parameter
Character
Value
Separator
UT
0: NONE
1: &
2:
3: FS
4: GS
5: SP
Debouncing Sensor
UY
0: 1 ms
1: 5 ms
2: 10 ms
Tab. 10-3: Command language for CLP bar code readers
8 008 912/0000/16-11-99
© SICK AG · Auto Ident · Germany · All rights reserved
43
Australia
Phone +61 3 9497 4100
(008) 33 48 02–toll free
Fax
+61 3 9497 1187
Italy
Phone +390 11/2 23 66 01
Fax
+390 11/2 23 66 09
Austria
Phone +43 22 36/62 28 8-0
Fax
+43 22 36/62 28 85
Japan
Phone +81 3 3358 1341
Fax
+81 3 3358 0586
Belgium/Luxembourg
Phone +32 24 66 55 66
Fax
+32 24 66 60 26
Netherlands
Phone +31 30 229 25 44
Fax
+31 30 229 39 94
8 008 912/0000/16-11-99 · TDL <FM 5.5> · RPF · Printed in Germany · Subject to change without prior notice · AftE2705sw
Laser Measurement Systems:
Phone +32 9 2240 394
Fax
+32 9 2235 645
Laser Measurement Systems:
Phone +31 73 599 50 44
Fax
+31 73 599 47 18
Brazil
Phone +55 11 5561 2683
Fax
+55 11 535 4153
Norway
Phone +47 67 56 75 00
Fax
+47 67 56 66 10
China/Hong Kong
Phone +85 2 2763 6966
Fax
+85 2 2763 6311
Poland
Phone +48 2 26 44 83 45
Fax
+48 2 26 44 83 42
Czech Republic
Phone +42 02-579 11 850
+42 02-578 10 561
Fax
+42 02-578 10 559
Singapore
Phone +65 744 3732
Fax
+65 841 77 47
Denmark
Phone +45 45 82 64 00
Fax
+45 45 82 64 01
Spain
Phone +34 93 4 80 31 00
Fax
+34 93 4 73 44 69
Finland
Phone +358 9-728 85 00
Fax
+358 9-72 88 50 55
Sweden
Phone +46 8-680 64 50
Fax
+46 8-710 18 75
France
Phone +33 1 64 62 35 00
Fax
+33 1 64 62 35 77
Switzerland
Phone +41 41 61 92 93 9
Fax
+41 41 61 92 92 1
Germany
Phone (+49 2 11) 53 01-0
Fax
(+49 2 11) 53 01-1 00
Taiwan
Phone +886 2 2365-6292
Fax
+886 2 2368-7397
Great Britain
Phone +44 17 27-83 11 21
Fax
+44 17 27-83 67 67
USA
Phone +1(612) 941-6780
Fax
+1(612) 941-9287
Representatives and agencies in all major industrial countries.
SICK AG · Auto Ident · Nimburger Straße 11 · 79276 Reute · http://www.sick.de

advertisement

Key Features

  • CCD bar code reader
  • RS-232 interface
  • Default setting for many applications
  • Decoding various bar code types
  • Reading distance up to 70 mm
  • Parameterization via CLP Setup software
  • External sensor triggering
  • Diagnosis mode for quality check
  • Switching output for control purposes

Frequently Answers and Questions

What are the system requirements for operating the CLP 100?
The CLP 100 requires a 5V DC power supply, a PC with Windows 95, 98 or NT and a serial interface, an RS-232 data connection cable, a sensor for object detection (if external reading pulsing is used), and an HTML browser for the CLP Setup Help on-line help system.
How do I connect the external reading pulse sensor to the CLP 100?
Connect the sensor to the "Sensor" switching input on the CLP 100. The wiring diagram is provided in the document.
What is the default setting of the CLP 100?
The default setting includes Code 39 as the active code type, free code length, multiple reading of 2, reading direction of both, no check digit, active low reading pulse generation, inactive switching output, RS-232 host interface with STX start characters and ETX stop characters, 9600 bits/s transmission rate, 8 data bits, no parity, 1 stop bit, and "BR" as the No Read message.
How do I adjust the CLP 100 to the bar code?
Use the adjusting mode in the CLP Setup software to align the CLP 100 for optimal reading results. The green LED will light up steadily when the CLP 100 is aligned correctly.
How do I change the communication parameters of the host interface?
You can change the communication parameters using the CLP Setup software. The default settings are 9600 bits/s transmission rate, 8 data bits, no parity, and 1 stop bit.
How do I dispose of the CLP 100?
Dispose of the unusable or irreparable device ecologically friendly by separating it into recyclable secondary raw materials (housing) and hazardous waste (electronic scrap) according to local regulations.

Related manuals