2016 Ductless Concealed Duct Single Zone Heat Pump Submittal

Ductless Split Systems
Concealed Duct Heat Pumps
PURCHASER
P.O. #
PROJECT
LOCATION
ENGINEER
ARCHITECT
SUBMITTED BY
FOR APPROVAL
ITEM
PLAN DESIGNATION
QUANTITY
DATE
FOR REFERENCE
COOLING BTU/H
VOLTAGE
FRIEDRICH MODEL
Features
• Inverter technology (variable speed compressor)
• Internal condensate pump with 27 ½" lift* included
• Cooling/Heating/Fan Mode
• Dry Mode
• 3 Fan speeds
• 24-hour on/off timer
• Auto restart
• Auto changeover
MD24Y3J, MD36Y3J
• Sleep mode
• Control lock function
• External Static Pressure Range(ESP)
- 24,000 (0.1 - 0.78) WC
- 36,000 (0.15 - 0.6) WC
• BLDC Motors
* Lift from drain pan to drain outlet. Use external drain
pump for installations requiring condensate lift
exceeding 27 1/2"
All Inverter line
PRECISION
PARTS
WARRANTY
COMPRESSOR
WARRANTY
MR24UY3J
Ductless_Concealed_Duct_Heat Pumps_Submittal_2016
MR36UY3J
SPECIFICATIONS
PERFORMANCE RATINGS
Single Zone Concealed Ducted - Heat Pumps
24k
SYSTEM MODEL NO.
INDOOR MODEL
OUTDOOR MODEL
36k
D24YJ
D36YJ
MD24Y3J
MD36Y3J
MR24UY3J
MR36UY3J
SPECIFICATIONS
CAPACITY COOLING (RATED)
Btu
24,000
36,000
CAPACITY COOLING (MIN~MAX)
Btu
9,700~26,700
16,000~41,400
40,000
CAPACITY HEATING @ 470F (RATED)
Btu
27,000
CAPACITY HEATING @ 170F (RATED)
Btu
17,600
24,600
CAPACITY HEATING (MIN~MAX)
Btu
10,900~30,000
17,500~48,000
COOLING AMPS
15.1
20.8
HEATING AMPS
15.1
21.4
SENSIBLE HEAT RATIO
.68
.67
SEER
17.0
17.6
EER
12.0
12.1
HSPF
10.0
9.2
ENERGY STAR
No
No
Pts/h
7.0
10.6
MOISTURE REMOVAL
AIRFLOW (LOW, MED, HIGH )
CFM
530 / 618 / 688
706 / 953 / 1,130
SOUND RATING - INDOOR H/M/L
dB(A)
38/36/35
39/38/37
SOUND RATING - OUTDOOR
dB(A)
62
67
OPERATING RANGE (COOLING)
°F
5~118
5~118
OPERATING RANGE (HEATING)
°F
-4~64
-4~64
EST. YEARLY OPERATING COST
$
180
268
Your operating costs will depend on your
utility rates and use. The estimated operating cost is based on a electricity cost of $
.115 per kWh. For more information, visit
www.ftc.gov/energy. Due to continuing
research in new energy-saving technology,
specifications are subject to change without notice.
Refrigeration line sets*
USED WITH
9000 and 12000
BTU indoor units
18000 BTU indoor units
24000, 30000 and 36000
BTU indoor units
Length Ft. Liquid Suction
Kit#
15’
1/4”
3/8”
T32150
35’
1/4”
3/8”
T32350
15’
1/4”
1/2”
T42150
35’
1/4”
1/2”
T42350
15’
3/8”
5/8”
T53150
35’
3/8”
5/8”
T53350
ELECTRICAL DATA
208/230/60/1
208/230/60/1
MINIMUM AMPACITY
POWER SOURCE
A
18.1
24.5
COOLING WATTS
W
2000
2910
MAX. TD FUSE/BREAKER
A
30
40
4 x 14
4 x 14
POWER AND COMMUNICATION CABLE
No. x AWG
REFRIGERATION SYSTEM
REFRIGERANT
COMPRESSOR TYPE
CONNECTIONS
R410A
R410A
Twin Rotary
Twin Rotary
Flare
Flare
LIQUID LINE O.D.
in
3/8
3/8
SUCTION LINE O.D.
in
5/8
5/8
FACTORY PRECHARGE
ft
25
25
REFRIGERANT CHARGE
oz
71
120
MIN./MAX. LINE LENGTH
ft
25~164
25~246
MAX. HEIGHT DIFFERENCE
ft
98
98
in
46-9/16 x 11-3/4 x 17-3/4
48-1/2 x 15 x 23-1/4
DIMENSIONS & WEIGHT
INDOOR UNIT
WXHXD
NET WEIGHT
lbs
73
125
SHIPPING WEIGHT
lbs
95
139
*Insulated line sets are available for all
Friedrich split systems in 15 ft. and 35
ft. lengths. Each line set is equipped
with flare nuts on both ends. Both
liquid and suction lines are insulated.
Line sets can be joined together with
field supplied double male connectors.
Each system requires one line set for
each indoor unit installed. On multizone systems, line sets should be
ordered based on individual indoor unit
capacities not total system capacity.
Thermostat
* WIRED
CONTROLLER
OUTDOOR UNIT
WXHXD
in
37-7/16 x 32-7/8 x 13
37-7/16 x 54-3/8 x 13
NET WEIGHT
lbs
132
203
SHIPPING WEIGHT
lbs
146
227
TOTAL NET WEIGHT
lbs
205
327
TOTAL SHIPPING WEIGHT
lbs
240
366
Ductless_Concealed_Duct_Heat Pumps_Submittal_2016
*Used with all models.
DIMENSIONAL DRAWINGS
INDOOR UNITS / MD24Y3J
Item No.
Part Name
Description
1
Air Intake
-
2
Air Outlet
-
3
Power and Communication cable & Wired Remote Controller
Wire Routing Hole
-
4
Drain Pipe Connection
-
5
Liquid Pipe Connection
-
6
Gas Pipe Connection
-
7
Inspection Hole
-
8
Drain Pump (accessory) Installation Hole
Knock out Type
Note
Symbols
View Direction
Datum Line
1. Unit should be installed in compliance with the installation manual in the product box.
2. Unit should be grounded in accordance with the local regulations or applicable national codes.
3. All electrical components and materials to be supplied from the site must comply with the
local regulations or international codes.
4. Electric characteristsics chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
Ductless_Concealed_Duct_Heat Pumps_Submittal_2016
DIMENSIONAL DRAWINGS
INDOOR UNITS / MD36Y3J
Item No.
Part Name
Description
1
Air Intake
-
2
Air Outlet
-
3
Power and Communication cable & Wired Remote Controller
Wire Routing Hole
-
4
Drain Pipe Connection
-
5
Liquid Pipe Connection
-
6
Gas Pipe Connection
-
7
Inspection Hole
-
8
Drain Pump (accessory) Installation Hole
Knock out Type
Note
Symbols
View Direction
Datum Line
1. Unit should be installed in compliance with the installation manual in the product box.
2. Unit should be grounded in accordance with the local regulations or applicable national codes.
3. All electrical components and materials to be supplied from the site must comply with the
local regulations or international codes.
4. Electric characteristsics chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
Ductless_Concealed_Duct_Heat Pumps_Submittal_2016
DIMENSIONAL DRAWINGS
OUTDOOR UNITS / MR24UY3J
Item No.
Part Name
Description
1
Air Intake
-
2
Air Outlet
-
3
Power and Communication cable & Wired Remote Controller
Wire Routing Hole
-
4
Drain Pipe Connection
-
5
Liquid Pipe Connection
-
6
Gas Pipe Connection
-
7
Inspection Hole
-
8
Drain Pump (accessory) Installation Hole
Knock out Type
Note
Symbols
Datum Line
Piping Direction
1. Unit should be installed in compliance with the installation manual in the product box.
2. Unit should be grounded in accordance with the local regulations or applicable national codes.
3. All electrical components and materials to be supplied from the site must comply with the
local regulations or international codes.
4. Electric characteristsics chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
Ductless_Concealed_Duct_Heat Pumps_Submittal_2016
DIMENSIONAL DRAWINGS
OUTDOOR UNITS / MR36UY3J
Item No.
Part Name
Description
1
Air Intake
-
2
Air Outlet
-
3
Power and Communication cable & Wired Remote Controller
Wire Routing Hole
-
4
Drain Pipe Connection
-
5
Liquid Pipe Connection
-
6
Gas Pipe Connection
-
7
Inspection Hole
-
Datum Line
8
Drain Pump (accessory) Installation Hole
Knock out Type
Piping Direction
Note
Symbols
1. Unit should be installed in compliance with the installation manual in the product box.
2. Unit should be grounded in accordance with the local regulations or applicable national codes.
3. All electrical components and materials to be supplied from the site must comply with the
local regulations or international codes.
4. Electric characteristsics chapter should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
Ductless_Concealed_Duct_Heat Pumps_Submittal_2016