F-Series Fire Alarm Control Panel Compatibility List

F-Series Fire Alarm Control Panel Compatibility List
F-Series Fire Alarm Control
Panel Compatibility List
UL compatibility list
Compatible detectors [1]
Manufacturer
Catalog number
Description
UL identifier Compatible base
Max. per
IDC
Edwards
6249B
Ionization smoke detector and base
001
N/A
48
6250B
Ionization smoke detector
001
6249B-001,
6251B-001A
48
6269B
Photoelectric smoke detector and base
001
N/A
4
6269B-003
Photoelectric smoke-heat detector and base
001
N/A
4
6270B
Photoelectric smoke detector
001
6249B-001,
6251B-001A
4
6270B-003
Combination photoelectric smoke-heat
detector
001
6249B-001,
6251B-001A
4
EC10U-3 [2][3]
Ionization smoke detector
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
60
EC30U-3 [2][3]
Photoelectric smoke detector
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
48
EC20FTU-3 [3]
Fixed temperature heat detector,
135°F (58°C)
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
EC20RRU-3 [3]
Rate of rise heat detector,
135°F (58°C)
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
2M-PD
Photoelectric smoke detector
(12/24 VDC)
S10A
N/A
30
2M-PDC [3]
Photoelectric smoke detector
(12/24 VDC)
S10A
N/A
30
2M-PDHC
Photoelectric smoke detector
(12/24 VDC) and dual heat sensor (FT-RoR)
S10A
N/A
30
2M-PDHRC
Photoelectric smoke detector (8.5 to
33 VDC) with dual FT-RoR heat sensor, and
auxiliary relay
S11A
N/A
1
429C
Photoelectric smoke detector
(12/24 VDC)
S10A
N/A
30
429CT
Photoelectric smoke detector
(12/24 VDC) and dual heat sensor (FT-RoR)
S10A
N/A
30
ESL
P/N 3101019-EN • REV 07 • ISS 30JAN14
1
Manufacturer
Mirtone
Edwards Signaling
2
Catalog number
Description
UL identifier Compatible base
Max. per
IDC
511C
Photoelectric smoke detector (12/24 VDC)
S10A
N/A
30
521B
Photoelectric smoke detector (12/24 VDC)
S10A
N/A
30
521BXT
Photoelectric smoke detector (12/24 VDC)
and dual heat sensor (FT-RoR)
S10A
N/A
30
711U
Photoelectric smoke detector (12/24 VDC)
S10A
701U, 702E, 702U
30
711UT
Fast response photoelectric smoke detector
(12/24 VDC) with heat sensors
S10A
701U, 702E, 702U
30
713-5U
Two-wire rate-of-rise and 57°C (135°F) fixed
temperature heat detector
S10A
701U, 702E, 702U
30
721UT
Fast response photoelectric smoke detector
(12/24 VDC) with remote alarm/trouble LED
S10A
701U, 702E, 702U
30
731U
Photoelectric smoke detector (12/24 VDC)
with auxiliary relay
S11A
701U, 702E, 702RE,
702RU, 702U
1
73494U
Ionization smoke detector and base
001
N/A
48
73495U
Ionization smoke detector
001
73486U
48
73575U
Photoelectric smoke detector and base
001
N/A
4
73576U
Combination photoelectric smoke-heat
detector and base
001
N/A
4
73595U
Photoelectric smoke detector
001
73486U
4
73596U
Photoelectric smoke-heat detector
001
73486U
4
MC10U-3 [2][3]
Ionization smoke detector
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
60
MC30U-3 [2][3]
Photoelectric smoke detector
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
48
MC20FTU-3 [3]
Fixed temperature heat detector,
135°F (58°C)
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
MC20RRU-3 [3]
Rate of rise heat detector,
135°F (58°C)
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
M2M-PD
Photoelectric smoke detector
(12/24 VDC)
S10A
N/A
30
M2M-PDC [3]
Photoelectric smoke detector (12/24 VDC)
S10A
N/A
30
M2M-PDHC
Photoelectric smoke detector (12/24 VDC)
and dual heat sensor (FT-RoR)
S10A
N/A
30
SC10U-3 [2][3]
Ionization smoke detector
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
60
SC30U-3 [2][3]
Photoelectric smoke detector
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
48
2420
Ionization smoke detector
001
N/A
48
2430
Photoelectric smoke detector
001
N/A
4
2432B
Combination photoelectric smoke-heat
detector
001
N/A
4
SC20FTU-3 [3]
Fixed temperature heat detector,
135°F (58°C)
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
SC20RRU-3 [3]
Rate of rise heat detector,
135°F (58°C)
A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
ED2M-PD
Photoelectric smoke detector
(12/24 VDC)
S10A
N/A
30
F-Series Fire Alarm Control Panel Compatibility List
Manufacturer
Catalog number
Description
UL identifier Compatible base
Max. per
IDC
ED2M-PDC [3]
Photoelectric smoke detector (12/24 VDC)
S10A
N/A
30
ED2M-PDHC
Photoelectric smoke detector (12/24 VDC)
and dual heat sensor (FT-RoR)
S10A
N/A
30
[1] You can install automatic detectors on Class A or Class B alarm-unverified circuits with dry contact devices. You can’t install automatic detectors
on Class A alarm-verified circuits with dry contact devices. You may install automatic detectors on Class B alarm-verified circuits with dry contact
devices, unless noted otherwise.
[2] Do not install on Class B alarm-verified circuits unless installed in a resistive base.
[3] Do not install on Class B alarm-verified circuits with dry contact devices.
Compatible duct smoke detectors [1][2]
Manufacturer
Catalog
number
Description
UL
identifier
Compatible base/housing
Max.
per IDC
Edwards
6264B-001
Ionization duct smoke detector
001
6251B-001A/6260A-100
48
6266B-001
Photoelectric duct smoke detector
001
6251B-001A/6260A-100
4
ESD-2W [1][2]
SuperDuct photoelectric duct smoke
detector
0.0
N/A
15
73405U-001
Ionization duct smoke detector
001
73486U/73401A
48
73594U-001
Photoelectric duct smoke detector
001
73486U/73401A
4
2435P
Photoelectric duct smoke detector
001
Included
4
SD-2W [1][2]
SuperDuct photoelectric duct smoke
detector
0.0
N/A
15
Mirtone
Edwards Signaling
[1] Do not install on alarm-verified circuits.
[2] Do not install with dry contact devices on the same circuit.
Compatible notification appliances
Manufacturer
Catalog number
Description
Audible
sync
Visible
sync
Edwards
202-3A-T, 202-3A-TW, 202-5A-T,
202-5A-TW, 202-6A-T,
202-6A-TW202-7A-T, 202-7A-TW,
202-8A-T, 202-8A-TW,
Integrity synchronized strobe
N/A
Y
202-15PS, 202-15PSW, 202-75PS,
202-75PSW,
Power saver synchronized strobe
N/A
Y
405-3A-T, 405-3A-TW, 405-5A-T,
405-5A-TW, 405-6A-T, 405-6A-TW,
405-7A-T, 405-7A-TW, 405-8A-T,
405-8A-TW,
Integrity synchronized strobe
N/A
Y
405-15PS, 405-15PSW, 405-75PS,
405-75PSW,
Power saver synchronized strobe
N/A
Y
757-1A-C, 757-1A-CW,
Integrity chime
N/A
N/A
757-3A-CS, 757-3A-CSW, 757-5A-CS,
757-5A-CSW, 757-7A-CS, 757-7A-CSW,
757-8A-CS, 757-8A-CSW
Integrity synchronized chime-strobe
N/A
Y
757-1A-T, 757-1A-TW
Integrity synchronized temporal horn
Y
N/A
757-3A-T, 757-3A-TW, 757-5A-T,
757-5A-TW, 757-7A-T, 757-7A-TW,
757-8A-T, 757-8A-TW
Integrity synchronized temporal horn-strobe
Y
Y
757-1A-H, 757-1A-HW
Horn
N
N/A
F-Series Fire Alarm Control Panel Compatibility List
3
Manufacturer
4
Catalog number
Description
Audible
sync
Visible
sync
757H-15PS, 757H-15PSW, 757H-75PS,
757H-75PSW
Power saver synchronized temporal horn-strobe
Y
Y
G1-HD, G1R-HD, G1F-HD, G1RF-HD
Genesis temporal horn
Y
N/A
G1-HDVM, G1R-HDVM, G1F-HDVM,
G1RF-HDVM
Genesis temporal horn-strobe, 15 to 110 cd
Y
Y
G1-VM-A
Genesis strobe, 15 to 110 cd, selectable lenses
N/A
Y
G1-VM-RCC
Genesis strobe, ceiling mount, 15 to 110 cd,
private mode only
N/A
Y
G1-HDVM-A
Genesis temporal horn-strobe, 15 to 110 cd,
selectable lenses
Y
Y
G1-HDVM-RCC
Genesis temporal horn-strobe, ceiling mount
15 to 110 cd, private mode only
Y
Y
G1F-V1575
Genesis 15/75 strobe, 15 or 75 cd
N/A
Y
G1F-CV1575
Genesis 15/75 chime-strobe, low or high dbA,
15 or 75 cd
N/A
Y
G1F-HDV1575
Genesis 15/75 temporal horn-strobe,
low or high dbA, 15 or 75 cd
Y
Y
G1R-VM-RCW
Genesis strobe, wall mount, 15 to 110 cd,
private mode only
N/A
Y
G1R-HDVM-RCW
Genesis temporal horn-strobe, wall mount
15 to 110 cd, private mode only
Y
Y
G1-H, G1R-H, G1-HO, G1R-HO, G1F-HO,
G1RF-HO
Genesis temporal horn
Y
N
G1-V15, G1R-V15, G1F-V15, G1RF-V15
Genesis strobe, 15 cd
N/A
Y
G1-V30, G1R-V30, G1F-V30, G1RF-V30
Genesis strobe, 30 cd
N/A
Y
G1-V60, G1R-V60, G1F-V60, G1RF-V60
Genesis strobe, 60 cd
N/A
Y
G1-V75, G1R-V75, G1F-V75, G1RF-V75
Genesis strobe, 75 cd
N/A
Y
G1-V110, G1R-V110, G1F-V110,
G1RF-V110
Genesis strobe, 110 cd
N/A
Y
G1-HV15, G1R-HV15
Genesis temporal horn-strobe,
low dbA, 15 cd
Y
Y
G1-HV30, G1R-HV30
Genesis temporal horn-strobe,
low dbA, 30 cd
Y
Y
G1-HV60, G1R-HV60
Genesis temporal horn-strobe,
low dbA, 60 cd
Y
Y
G1-HV75, G1R-HV75
Genesis temporal horn-strobe,
low dbA, 75 cd
Y
Y
G1-HOV15, G1R-HOV15, G1F-HOV15,
G1RF-HOV15
Genesis temporal horn-strobe,
high dbA, 15 cd
Y
Y
G1-HOV30, G1R-HOV30, G1F-HOV30,
G1RF-HOV30
Genesis temporal horn-strobe,
high dbA, 30 cd
Y
Y
G1-HOV60, G1R-HOV60, G1F-HOV60,
G1RF-HOV60
Genesis temporal horn-strobe,
high dbA, 60 cd
Y
Y
G1-HOV75, G1R-HOV75, G1F-HOV75,
G1RF-HOV75
Genesis temporal horn-strobe,
high dbA, 75 cd
Y
Y
G1-HOV110, G1R-HOV110, G1F-HOV110,
G1RF-HOV110
Genesis temporal horn-strobe,
high dbA, 110 cd
Y
Y
F-Series Fire Alarm Control Panel Compatibility List
Manufacturer
Audible
sync
Visible
sync
Genesis temporal horn-strobe,
52 cd, private mode only
Y
Y
G1-P, G1R-P, G1F-P, G1RF-P
Genesis horn
Y
N/A
G1-VM, G1R-VM, G1F-VM, G1RF-VM
Genesis strobe, 15 to 110 cd
N/A
Y
G1-C, G1R-C, G1F-C, G1RF-C
Genesis chime
N/A
N/A
G1-CVM, G1R-CVM, G1F-CVM,
G1RF-CVM
Genesis chime-strobe, 15 to 110 cd
N/A
Y
GC-VM, GCF-VM
Genesis ceiling strobe, 15 to 95 cd
N/A
Y
GC-VMH, GCF-VMH
Genesis ceiling strobe, 95 to 177 cd
N/A
Y
GC-S2VM, GCF-S2VM
Genesis ceiling speaker-strobe,
25 Vrms, 15 to 95 cd
N/A
Y
GC-S7VM, GCF-S7VM
Genesis ceiling speaker-strobe,
70 Vrms, 15 to 95 cd
N/A
Y
GC-S2VMH, GCF-S2VMH
Genesis ceiling speaker-strobe,
25 Vrms, 95 to 177 cd
N/A
Y
GC-S7VMH, GCF-S7VMH
Genesis ceiling speaker-strobe,
70 Vrms, 95 to 177 cd
N/A
Y
GC-HDVM, GCF-HDVM
Genesis ceiling horn-strobe,
15 to 95 cd
Y
Y
GC-HDVMH, GCF-HDVMH
Genesis ceiling horn-strobe,
95 to 177 cd
Y
Y
G4LFRF-H, G4LFRN-H, G4LFWF-H,
G4LFWN-H
Genesis Low Frequency (520 Hz) horn, temporal
or steady, low or high dB
Y
N/A
G4LFRF-HVM, G4LFRN-HVM,
G4LFWF-HVM, G4LFWN-HVM
Genesis Low Frequency (520 Hz) horn-strobe,
temporal or steady, low or high dB, 15 to 110 cd
Y
Y
G4-S2VM, G4R-S2VM, G4F-S2VM,
G4RF-S2VM
Genesis speaker-strobe, 25 Vrms, 15 to 110 cd
N/A
Y
G4-S7VM, G4R-S7VM, G4F-S7VM,
G4RF-S7VM
Genesis speaker-strobe, 70 Vrms, 15 to 110 cd
N/A
Y
GL1RF-HD, GL1RN-HD, GL1WF-HD,
GL1WN-HD
Genesis GL-Series horn,
temporal or steady, low or high dB
Y
N/A
GL1RF-HDVMC, GL1RN-HDVMC,
GL1WF-HDVMC, GL1WN-HDVMC
Genesis GL-Series horn-strobe,
temporal or steady, low or high dB, LED strobe, 15
to 110 cd
Y
Y
GL1RF-VMC, GL1RN-VMC, GL1WF-VMC,
GL1WN-VMC
Genesis GL-Series strobe,
LED strobe, 15 to 110 cd
N/A
Y
WG4RF-SVMC, WG4RN-SVMC,
WG4WA-SVMC, WG4WF-SVMC,
WG4WN-SVMC
Outdoor Genesis speaker-strobe, 25/70 VRMS,
15/29/70/87 cd [1]
N/A
Y
WG4RF-SVMHC, WG4RN-SVMHC,
WG4WA-SVMHC,WG4WF-SVMHC,
WG4WN-SVMHC
Outdoor Genesis speaker-strobe. 25/70 VRMS,
102/123/147/161 cd [1]
N/A
Y
WG4RF-HVMC, WG4RN-HVMC,
WG4WF-HVMC, WG4WN-HVMC
Outdoor Genesis horn-strobe, 15/29/70/87 cd [1]
Y
Y
WG4RF-HVMHC, WG4RN-HVMHC,
WG4WF-HVMHC, WG4WN-HVMHC
Outdoor Genesis horn-strobe, 102/123/147/161 cd
[1]
Y
Y
WG4RF-H, WG4WF-H, WG4RN-H,
WG4WN-H
Outdoor Genesis horn [1]
Y
N
Catalog number
Description
G1-HOV110R
F-Series Fire Alarm Control Panel Compatibility List
5
Manufacturer
Catalog number
Description
Audible
sync
Visible
sync
Edwards Signaling
2440S-15-R, 2440S-15-W, 2440S-30-R,
2440S-30-W, 2440S-60-R, 2440S-60-W,
2440S-15/75-R, 2440S-15/75-W,
2440S-110-R, 2440S-110-W
Integrity synchronized strobe
N/A
Y
2441S-15-R, 2441S-15-W, 2441S-30-R,
2441S-30-W, 2441S-60-R, 2441S-60-W,
2441S-15/75-R, 2441S-15/75-W,
2441S-110-R, 2441S-110-W
Integrity synchronized strobe
N/A
Y
2447TH-R
Horn
Y
N/A
2452THS-15, 2452THS-15/75,
2452THS-30, 2452THS-15/75,
2452THS-110
Horn-strobe
Y
Y
2455C-R, 2455C-W
Integrity chime
N/A
N/A
2457CS-15-R, 2457CS-15-W,
2457CS-30-R, 2457CS-30-W,
2457CS-15/75-R, 2457CS-15/75-W,
2457CS-110-R, 2457CS-110-W
Integrity synchronized chime-strobe
N/A
Y
EG1-HD, EG1R-HD, EG1F-HD,
EG1RF-HD
Genesis temporal horn
Y
N/A
EG1-HDVM, EG1R-HDVM, EG1F-HDVM,
EG1RF-HDVM
Genesis temporal horn-strobe, 15 to 110 cd
Y
Y
EG1-VM-A
Genesis strobe, 15 to 110 cd, selectable lenses
N/A
Y
EG1-VM-RCC
Genesis strobe, ceiling mount, 15 to 110 cd,
private mode only
N/A
Y
EG1-HDVM-A
Genesis temporal horn-strobe, 15 to 110 cd,
selectable lenses
Y
Y
EG1-HDVM-RCC
Genesis temporal horn-strobe, ceiling mount
15 to 110 cd, private mode only
Y
Y
EG1F-V1575
Genesis 15/75 strobe, 15 or 75 cd
N/A
Y
EG1F-CV1575
Genesis 15/75 chime-strobe, low or high dbA,
15 or 75 cd
N/A
Y
EG1F-HDV1575
Genesis 15/75 temporal horn-strobe,
low or high dbA, 15 or 75 cd
Y
Y
EG1R-VM-RCW
Genesis strobe, wall mount, 15 to 110 cd,
private mode only
N/A
Y
EG1R-HDVM-RCW
Genesis temporal horn-strobe, wall mount
15 to 110 cd, private mode only
Y
Y
EG1-H, EG1R-H, EG1-HO, EG1R-HO,
EG1F-HO, EG1RF-HO
Genesis temporal horn
Y
N
EG1-HOV15, EG1R-HOV15,
EG1F-HOV15, EG1RF-HOV15
Genesis temporal horn-strobe,
high dbA, 15 cd
Y
Y
EG1-HOV30, EG1R-HOV30,
EG1F-HOV30, EG1RF-HOV30
Genesis temporal horn-strobe,
high dbA, 30 cd
Y
Y
EG1-HOV60, EG1R-HOV60,
EG1F-HOV60, EG1RF-HOV60
Genesis temporal horn-strobe,
high dbA, 60 cd
Y
Y
EG1-HOV75, EG1R-HOV75,
EG1F-HOV75, EG1RF-HOV75
Genesis temporal horn-strobe,
high dbA, 75 cd
Y
Y
EG1-HOV110, EG1R-HOV110,
EG1F-HOV110, EG1RF-HOV110
Genesis temporal horn-strobe,
high dbA, 110 cd
Y
Y
EG1-HOV110R
Genesis temporal horn-strobe,
52 cd, private mode only
Y
Y
6
F-Series Fire Alarm Control Panel Compatibility List
Manufacturer
Mirtone
Catalog number
Description
Audible
sync
Visible
sync
EG1-P, EG1R-P, EG1F-P, EG1RF-P
Genesis horn
Y
N/A
EG1-VM, EG1R-VM, EG1F-VM,
EG1RF-VM
Genesis strobe, 15 to 110 cd
N/A
Y
EG1-C, EG1R-C, EG1F-C, EG1RF-C
Genesis chime
N/A
N/A
EG1-CVM, EG1R-CVM, EG1F-CVM,
EG1RF-CVM
Genesis chime-strobe, 15 to 110 cd
N/A
Y
EGC-VM, EGCF-VM
Genesis ceiling strobe, 15 to 95 cd
N/A
Y
EGC-VMH, EGCF-VMH
Genesis ceiling strobe, 95 to 177 cd
N/A
Y
EGC-S2VM, EGCF-S2VM
Genesis ceiling speaker-strobe,
25 Vrms, 15 to 95 cd
N/A
Y
EGC-S7VM, EGCF-S7VM
Genesis ceiling speaker-strobe,
70 Vrms, 15 to 95 cd
N/A
Y
EGC-S2VMH, EGCF-S2VMH
Genesis ceiling speaker-strobe,
25 Vrms, 95 to 177 cd
N/A
Y
EGC-S7VMH, EGCF-S7VMH
Genesis ceiling speaker-strobe,
70 Vrms, 95 to 177 cd
N/A
Y
EGC-HDVM, EGCF-HDVM
Genesis ceiling horn-strobe,
15 to 95 cd
Y
Y
EGC-HDVMH, EGCF-HDVMH
Genesis ceiling horn-strobe,
95 to 177 cd
Y
Y
EG4-S2VM, EG4R-S2VM, EG4F-S2VM,
EG4RF-S2VM
Genesis speaker-strobe, 25 Vrms, 15 to 110 cd
N/A
Y
EG4-S7VM, EG4R-S7VM, EG4F-S7VM,
EG4RF-S7VM
Genesis speaker-strobe, 70 Vrms, 15 to 110 cd
N/A
Y
INT-C, INT-CW
Integrity chime
N/A
N/A
INT-3AC, INT-3ACW, INT-5AC,
INT-5ACW, INT-7AC, INT-7ACW,
INT-8AC, INT-8ACW
Integrity synchronized chime-strobe
N/A
Y
INT-T, INT-TW
Integrity temporal horn
Y
N/A
INT-3AT, INT-3ATW, INT-5AT, INT-5ATW,
INT-7AT, INT-7ATW, INT-8AT, INT-8ATW
Integrity synchronized temporal horn-strobe
Y
Y
INTH-15PS, INTH-15PSW, INTH-75PS,
INTH-75PSW
Power saver synchronized temporal horn-strobe
Y
Y
MHS-3AR, MHS-3AW, MHS-5AR,
MHS-5AW, MHS-7AR, MHS-7AW,
MHS-8AR, MHS-8AW
Mini horn-strobe
Y
Y
MS-15PS, MS-15PSW, MS-75PS,
MS-75PSW
Power saver synchronized strobe
N/A
Y
MS-3AR, MS-3AW, MS-5AR, MS-5AW,
MS-6AR, MS-6AW, MS-7AR, MS-7AW,
MS-8AR, MS-8AW
Integrity synchronized strobe
N/A
Y
MG1-HD, MG1R-HD, MG1F-HD,
MG1RF-HD
Genesis temporal horn
Y
N/A
MG1-HDVM, MG1R-HDVM, MG1F-HDVM,
MG1RF-HDVM
Genesis temporal horn-strobe, 15 to 110 cd
Y
Y
MG1-VM-A
Genesis strobe, 15 to 110 cd, selectable lenses
N/A
Y
MG1-VM-RCC
Genesis strobe, ceiling mount, 15 to 110 cd,
private mode only
N/A
Y
F-Series Fire Alarm Control Panel Compatibility List
7
Manufacturer
8
Audible
sync
Visible
sync
Genesis temporal horn-strobe, 15 to 110 cd,
selectable lenses
Y
Y
MG1-HDVM-RCC
Genesis temporal horn-strobe, ceiling mount
15 to 110 cd, private mode only
Y
Y
MG1F-V1575
Genesis 15/75 strobe, 15 or 75 cd
N/A
Y
MG1F-CV1575
Genesis 15/75 chime-strobe, low or high dbA,
15 or 75 cd
N/A
Y
MG1F-HDV1575
Genesis 15/75 temporal horn-strobe,
low or high dbA, 15 or 75 cd
Y
Y
MG1R-VM-RCW
Genesis strobe, wall mount, 15 to 110 cd,
private mode only
N/A
Y
MG1R-HDVM-RCW
Genesis temporal horn-strobe, wall mount
15 to 110 cd, private mode only
Y
Y
MG1-H, MG1R-H, MG1-HO, MG1R-HO,
MG1F-HO, MG1RF-HO
Genesis temporal horn
Y
N
MG1-V15, MG1R-V15, MG1F-V15,
MG1RF-V15
Genesis strobe, 15 cd
N/A
Y
MG1-V30, MG1R-V30, MG1F-V30,
MG1RF-V30
Genesis strobe, 30 cd
N/A
Y
MG1-V60, MG1R-V60, MG1F-V60,
MG1RF-V60
Genesis strobe, 60 cd
N/A
Y
MG1-V75, MG1R-V75, MG1F-V75,
MG1RF-V75
Genesis strobe, 75 cd
N/A
Y
MG1-V110, MG1R-V110, MG1F-V110,
MG1RF-V110
Genesis strobe, 110 cd
N/A
Y
MG1-HV15, MG1R-HV15
Genesis temporal horn-strobe,
low dbA, 15 cd
Y
Y
MG1-HV30, MG1R-HV30
Genesis temporal horn-strobe,
low dbA, 30 cd
Y
Y
MG1-HV60, MG1R-HV60
Genesis temporal horn-strobe,
low dbA, 60 cd
Y
Y
MG1-HV75, MG1R-HV75
Genesis temporal horn-strobe,
low dbA, 75 cd
Y
Y
MG1-HOV15, MG1R-HOV15,
MG1F-HOV15, MG1RF-HOV15
Genesis temporal horn-strobe,
high dbA, 15 cd
Y
Y
MG1-HOV30, MG1R-HOV30,
MG1F-HOV30, MG1RF-HOV30
Genesis temporal horn-strobe,
high dbA, 30 cd
Y
Y
MG1-HOV60, MG1R-HOV60,
MG1F-HOV60, MG1RF-HOV60
Genesis temporal horn-strobe,
high dbA, 60 cd
Y
Y
MG1-HOV75, MG1R-HOV75,
MG1F-HOV75, MG1RF-HOV75
Genesis temporal horn-strobe,
high dbA, 75 cd
Y
Y
MG1-HOV110, MG1R-HOV110,
MG1F-HOV110, MG1RF-HOV110
Genesis temporal horn-strobe,
high dbA, 110 cd
Y
Y
MG1-HOV110R
Genesis temporal horn-strobe,
52 cd, private mode only
Y
Y
MG1-P, MG1R-P, MG1F-P, MG1RF-P
Genesis horn
Y
N/A
MG1-VM, MG1R-VM, MG1F-VM,
MG1RF-VM
Genesis strobe, 15 to 110 cd
N/A
Y
MG1-C, MG1R-C, MG1F-C, MG1RF-C
Genesis chime
N/A
N/A
Catalog number
Description
MG1-HDVM-A
F-Series Fire Alarm Control Panel Compatibility List
Manufacturer
Catalog number
Description
Audible
sync
Visible
sync
MG1-CVM, MG1R-CVM, MG1F-CVM,
MG1RF-CVM
Genesis chime-strobe, 15 to 110 cd
N/A
Y
MGC-VM, MGCF-VM
Genesis ceiling strobe, 15 to 95 cd
N/A
Y
MGC-VMH, MGCF-VMH
Genesis ceiling strobe, 95 to 177 cd
N/A
Y
MGC-S2VM, MGCF-S2VM
Genesis ceiling speaker-strobe,
25 Vrms, 15 to 95 cd
N/A
Y
MGC-S7VM, MGCF-S7VM
Genesis ceiling speaker-strobe,
70 Vrms, 15 to 95 cd
N/A
Y
MGC-S2VMH, MGCF-S2VMH
Genesis ceiling speaker-strobe,
25 Vrms, 95 to 177 cd
N/A
Y
MGC-S7VMH, MGCF-S7VMH
Genesis ceiling speaker-strobe,
70 Vrms, 95 to 177 cd
N/A
Y
MGC-HDVM, MGCF-HDVM
Genesis ceiling horn-strobe,
15 to 95 cd
Y
Y
MGC-HDVMH, MGCF-HDVMH
Genesis ceiling horn-strobe,
95 to 177 cd
Y
Y
MG4-S2VM, MG4R-S2VM, MG4F-S2VM,
MG4RF-S2VM
Genesis speaker-strobe, 25 Vrms, 15 to 110 cd
N/A
Y
MG4-S7VM, MG4R-S7VM, MG4F-S7VM,
MG4RF-S7VM
Genesis speaker-strobe, 70 Vrms, 15 to 110 cd
N/A
Y
WG4RF-HVMC, WG4RN-HVMC,
WG4WA-HVMC, WG4WF-HVMC,
WG4WN-HVMC
Outdoor Genesis horn-strobe, 15/29/70/87 cd [1]
Y
Y
WG4RF-HVMHC, WG4RN-HVMHC,
WG4WA-HVMHC, WG4WF-HVMHC,
WG4WN-HVMHC
Outdoor Genesis horn-strobe. 102/123/147/161 cd
[1]
Y
Y
WG4RF-H, WG4WF-H, WG4RN-H,
WG4WN-H
Outdoor Genesis horn
Y
N
[1] When metallic conductors are installed that extend beyond one building, the circuit(s) are required to be protected with UL497B listed transient
protectors with the appropriate voltage ratings for the circuit being protected. When notification appliances are installed outside of a building (e.g.
mounted on an exterior wall) and are connected to an interior circuit that may not have transient protection, it is recommended that these circuits
also be protected with UL497B listed transient protection with the appropriate voltage ratings for the circuit being protected. Consult applicable
codes for further information.
Compatible control relays
Manufacturer
Catalog number
Description
Air Products &
Control, Ltd.
MR-101/T, MR-101/C
Single SPDT multivoltage control relay with track mounting hardware (/T), or mounted in
metal enclosure (/C)
MR-104/T, MR-104/C
Four SPDT multivoltage control relays with track mounting hardware (/T), or mounted in
metal enclosure (/C)
MR-201/T, MR-201/C
Single DPDT multivoltage control relay with track mounting hardware (/T), or mounted in
metal enclosure (/C)
MR-204/T, MR-204/C
Four DPDT multivoltage control relays with track mounting hardware (/T), or mounted in
metal enclosure (/C)
PAM-1
Encapsulated multivoltage control relay with wire leads
F-Series Fire Alarm Control Panel Compatibility List
9
Compatible accessories
Manufacturer
Catalog number
Description
Installation sheet
Edwards
CTM
City Tie Module
3101025
BC-3 and BC-3R
Battery Cabinet
3101026
FSUIM
Universal Interface Module
3101030
FSRZI-A and FSRZI-SA
Remote Zone Indicator
3101032
FSRSI
Remote System Indicator
3101034
F-XTR120 and F-XTR230
F-Series Power Expander Transformer
3101035
F-DACT and F-DACT(F)
Digital Alarm Communicator Transmitter
3101038
FSRRM24
Remote Relay Module
3101058
FSRA10 and FSRA10C
F-Series Remote Annunciator
3101146
AVSM-R
Synchronization control module, Red
N/A
AVSM-W
Synchronization control module, White
N/A
Gentex
Compatible booster supplies
Manufacturer
Catalog number
Description
Manual
Edwards
BPS6A
6.5 A booster power supply
3100485
BPS6A/230
6.5 A booster power supply
3100485
BPS6AC
6.5 A booster power supply
3100485
BPS6CAA
6.5 A booster power supply
3100485
MIRBPS6A
6.5 A booster power supply
3100485
MIRBPS6A/230
6.5 A booster power supply
3100485
XLS-BPS6A
6.5 A booster power supply
3100485
XLS-BPS6A/230
6.5 A booster power supply
3100485
EBPS6A
6.5 A booster power supply
3100485
EBPS6A/230
6.5 A booster power supply
3100485
BPS10A
10 A booster power supply
3100485
BPS10A/230
10 A booster power supply
3100485
BPS10AC
10 A booster power supply
3100485
BPS10CAA
10 A booster power supply
3100485
MIRBPS10A
10 A booster power supply
3100485
MIRBPS10A/230
10 A booster power supply
3100485
XLS-BPS10A
10 A booster power supply
3100485
XLS-BPS10A/230
10 A booster power supply
3100485
EBPS10A
10 A booster power supply
3100485
EBPS10A/230
10 A booster power supply
3100485
10
F-Series Fire Alarm Control Panel Compatibility List
ULC compatibility list
Compatible detectors [1]
Manufacturer
Catalog number
Description
ULC
Identifier
Edwards
EC30U-3 [2][3]
Photoelectric smoke detector
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
48
EC20FTU-3 [3]
Fixed temperature heat detector,
135°F (58°C)
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
EC20RRU-3 [3]
Rate of rise heat detector,
135°F (58°C)
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
6249C
Ionization smoke detector and base
N/A
N/A
48
6250C
Ionization smoke detector
N/A
6249C-001,
6251C-001A
48
6269C
Photoelectric smoke detector and base
N/A
N/A
4
6269C-003
Photoelectric smoke-heat detector and base
N/A
N/A
4
6270C
Photoelectric smoke detector
N/A
6249C-001,
6251C-001A
4
6270C-003
Combination photoelectric smoke-heat
detector
N/A
6249C-001,
6251C-001A
4
EDW1400A [3]
Ionization smoke detector
N/A
N/A
24
EDW1451A [3]
Photoelectric smoke detector
N/A
EDWB401B
24
EDW2400A [3]
Photoelectric smoke detector
N/A
N/A
24
EDW2151A [3]
Photoelectric smoke detector
N/A
EDWB110LP
24
EDW2451A [3]
Photoelectric smoke detector
N/A
EDWB401B
24
C2M-PDC [3]
Photoelectric smoke detector (12/24 VDC)
N/A
N/A
30
C2M-PDHC
Photoelectric smoke detector (12/24 VDC)
and dual heat sensor (FT-RoR)
N/A
N/A
30
C2M-PDHRC
Photoelectric smoke detector (8.5 to 33
VDC) with dual FT-RoR heat sensor, and
auxiliary relay
N/A
N/A
30
528B [3]
Photoelectric smoke detector (12/24 VDC)
N/A
N/A
30
528BXT
Photoelectric smoke detector (12/24 VDC)
and dual heat sensor (FT-RoR)
N/A
N/A
30
528CRXT
Photoelectric smoke detector (8.5 to 33
VDC), with dual FT-RoR heat sensor, and
auxiliary relay
N/A
N/A
30
MC30U-3 [2][3]
Photoelectric smoke detector
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
48
MC20FTU-3 [3]
Fixed temperature heat detector,
135°F (58°C)
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
MC20RRU-3 [3]
Rate of rise heat detector,
135°F (58°C)
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
73494
Ionization smoke detector and base
N/A
N/A
48
73495
Ionization smoke detector
N/A
73486
48
73575
Photoelectric smoke detector and base
N/A
N/A
4
73576
Combination photoelectric smoke-heat
detector
N/A
N/A
4
73595
Photoelectric smoke detector
N/A
73486
4
ESL
Mirtone
F-Series Fire Alarm Control Panel Compatibility List
Compatible base
Max.
per IDC
11
Manufacturer
Edwards Signaling
Catalog number
Description
ULC
Identifier
Compatible base
Max.
per IDC
73596
Photoelectric smoke-heat detector
N/A
73486
4
MT1400A [3]
Ionization smoke detector
N/A
N/A
21
MT1451A [3]
Ionization smoke detector
N/A
EDWB401B
21
MT2400A [3]
Photoelectric smoke detector
N/A
N/A
24
MT2151A [3]
Photoelectric smoke detector
N/A
EDWB110LP
24
MT2451A [3]
Photoelectric smoke detector
N/A
EDWB401B
24
CM2M-PDC [3]
Photoelectric smoke detector (12/24 VDC)
N/A
N/A
30
CM2M-PDHC
Photoelectric smoke detector (12/24 VDC)
and dual heat sensor (FT-RoR)
N/A
N/A
30
SC30U-3 [2][3]
Photoelectric smoke detector
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
48
SC20FTU-3 [3]
Fixed temperature heat detector,
135°F (58°C)
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
SC20RRU-3 [3]
Rate of rise heat detector,
135°F (58°C)
N/A
CSBU-1, CSBU-3,
CSB4U-1, CRB4U-1
46
[1] You can install automatic detectors on Class A or Class B alarm-unverified circuits with dry contact devices. You can’t install automatic detectors
on Class A alarm-verified circuits with dry contact devices. You may install automatic detectors on Class B alarm-verified circuits with dry contact
devices, unless noted otherwise.
[2] Do not install on Class B alarm-verified circuits unless installed in a resistive base.
[3] Do not install on Class B alarm-verified circuits with dry contact devices.
Compatible duct smoke detectors [1][2]
Manufacturer
Catalog
number
Description
Edwards
6264C-001
Mirtone
Edwards Signaling
ULC
identifier
Compatible base/housing
Max.
per IDC
Ionization duct smoke detector
6251C-001A/6260A-100
48
6266C-001
Photoelectric duct smoke detector
6251C-001A/6260A-100
4
ESD-2W [1][2]
SuperDuct photoelectric duct smoke
detector
N/A
15
73405-001
Ionization duct smoke detector
73486/6260A-100
46
73594-001
Photoelectric duct smoke detector
73486/6260A-100
4
SD-2W [1][2]
SuperDuct photoelectric duct smoke
detector
N/A
15
0.0
0.0
[1] Do not install on alarm-verified circuits.
[2] Do not install with dry contact devices on the same circuit.
Compatible control relays
Manufacturer
Catalog number
Description
Air Products
Control, Ltd.
MR-101/T, MR-101/C
Single SPDT multivoltage control relay with track mounting hardware (/T), or mounted in
metal enclosure (/C)
MR-104/T, MR-104/C
Four SPDT multivoltage control relays with track mounting hardware (/T), or mounted in
metal enclosure (/C)
MR-201/T, MR-201/C
Single DPDT multivoltage control relay with track mounting hardware (/T), or mounted in
metal enclosure (/C)
MR-204/T, MR-204/C
Four DPDT multivoltage control relays with track mounting hardware (/T), or mounted in
metal enclosure (/C)
PAM-1
Encapsulated multivoltage control relay with wire leads
12
F-Series Fire Alarm Control Panel Compatibility List
Compatible accessories
Manufacturer
Catalog number
Description
Installation sheet
Edwards
CTM
City Tie Module
3101025
BC-3 and BC-3R
Battery Cabinet
3101026
FSUIM
Universal Interface Module
3101030
FSRZI-A and FSRZI-SA
Remote Zone Indicator
3101032
FSRSI
Remote System Indicator
3101034
F-XTR120 and F-XTR230
F-Series Power Expander Transformer
3101035
F-DACT and F-DACT(F)
Digital Alarm Communicator Transmitter
3101038
FSRRM24
Remote Relay Module
3101058
FSRA10(F) and FSRA10C(F)
F-Series Remote Annunciator
3101146
Compatible booster supplies
Manufacturer
Catalog number
Description
Manual
Edwards
BPS6A
6.5 A booster power supply
3100485
BPS6A/230
6.5 A booster power supply
3100485
BPS6AC
6.5 A booster power supply
3100485
BPS6CAA
6.5 A booster power supply
3100485
MIRBPS6A
6.5 A booster power supply
3100485
MIRBPS6A/230
6.5 A booster power supply
3100485
XLS-BPS6A
6.5 A booster power supply
3100485
XLS-BPS6A/230
6.5 A booster power supply
3100485
EBPS6A
6.5 A booster power supply
3100485
EBPS6A/230
6.5 A booster power supply
3100485
BPS10A
10 A booster power supply
3100485
BPS10A/230
10 A booster power supply
3100485
BPS10AC
10 A booster power supply
3100485
BPS10CAA
10 A booster power supply
3100485
MIRBPS10A
10 A booster power supply
3100485
MIRBPS10A/230
10 A booster power supply
3100485
XLS-BPS10A
10 A booster power supply
3100485
XLS-BPS10A/230
10 A booster power supply
3100485
EBPS10A
10 A booster power supply
3100485
EBPS10A/230
10 A booster power supply
3100485
F-Series Fire Alarm Control Panel Compatibility List
13
Contact information
For contact information, see www.edwardsutcfs.com.
Copyright © 2014 UTC Fire & Security Americas Corporation, Inc.
All rights reserved.
14
F-Series Fire Alarm Control Panel Compatibility List
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising