advertisement
▼
Scroll to page 2
of 108
BA 206F/00/en/04.04 Nr. 52006307 Valid as of software version: V 01.02.00 (amplifier) V 01.02.00 (communication) micropilot S FMR 530 Level-Radar Operating Instructions Brief operating instructions Micropilot S FMR 530 Brief operating instructions KA 161F/00/a2/12.01 52006294 000 measured value - + Micropilot S - Quick Setup Contrast: + or + 009 history reset E Group selection + - 002 tank shape 003 medium property 004 process cond. 01 safety settings - flat ceiling - stilling well … - input E input F - standard only for (see sketch) (see sketch) bypass + - calm surface stilling well - add. agitator … basic setup 03 mounting calibr. 04 linearisation unknown <1.9 1.9 … 4 4 … 10 >10 030 tank gauging 033 dip table mode 005 empty calibr. 0A diagnostics 0C system parameters 007 pipe diameter 008 dist./ meas value D and L are displayed (see sketch) 051 check distance 052 range of mapping - confirm suggestion or specify range ok too small too big unknown manual 053 start mapping flange: reference point of measurement history reset (= 555) - dip table - auto correct. dip table first point corrects offset further points correct linearity 06 output - 006 full calibr. 034/035 dip table 05 extended calibr. 09 display E E 00 basic setup + 008 dist./ meas value E D 092 language 0A0 present error … … 0A1 previous error 09B recording curve - envel. curve - single curve - cyclic - incl. FAC - incl. cust. map 0A3 reset 09A plot settings E F L 0A4 unlock parameter … … 555 = History Reset = 100: unlocked (333 = reset customer parameters) ≠ 100: locked 52006294 Note! This operating manual explains the installation and initial start-up for the level transmitter measuring device. All functions that are required for a typical measuring task are taken into account here. In addition, the Micropilot S provides many other functions that are not included in this operating manual, such as optimising the measuring point and converting the measured values. An overview of all device functions can be found on Page 92. The operating manual BA 217F/00/en provides an extensive description of all device functions – Description of the device functions for Micropilot S, which can also be found on the enclosed CD-ROM. 2 Endress+Hauser Micropilot S FMR 530 Table of Contents Table of Contents 1 Safety instructions . . . . . . . . . . . . . . . . . 4 6 Commissioning . . . . . . . . . . . . . . . . . . . 45 1.1 1.2 1.3 1.4 1.5 Designated use . . . . . . . . . . . . . . . . . . . . . . . . Installation, commissioning and operation . . . Operational safety . . . . . . . . . . . . . . . . . . . . . . Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Notes on safety conventions and symbols . . . 2 Identification . . . . . . . . . . . . . . . . . . . . . . 7 6.1 6.2 6.3 6.4 6.5 6.6 6.7 Function check . . . . . . . . . . . . . . . . . . . . . . . . 45 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . 45 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Basic Setup with the VU 331 . . . . . . . . . . . . . 48 Mounting calibration with VU 331 . . . . . . . . . . 56 Basic Setup with the ToF Tool . . . . . . . . . . . . . 66 Mounting calibration with the ToF Tool . . . . . . 71 2.1 2.2 2.3 2.4 Device designation . . . . . . . . . . . . . . . . . . . . . 7 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . 10 Certificates and approvals . . . . . . . . . . . . . . . 10 Registered trademarks . . . . . . . . . . . . . . . . . 10 7 Maintenance . . . . . . . . . . . . . . . . . . . . . . 73 8 Accessories . . . . . . . . . . . . . . . . . . . . . . . 74 3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . 11 9 Trouble-shooting . . . . . . . . . . . . . . . . . 76 3.1 3.2 3.3 3.4 3.5 Quick installation guide . . . . . . . . . . . . . . . . . Incoming acceptance, transport, storage . . . Installation Conditions . . . . . . . . . . . . . . . . . . Installation instructions . . . . . . . . . . . . . . . . . Post-installation check . . . . . . . . . . . . . . . . . . 4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 4.1 4.2 4.3 4.4 4.5 4.6 Quick wiring guide . . . . . . . . . . . . . . . . . . . . . Connecting the measuring unit . . . . . . . . . . . Equipotential bonding . . . . . . . . . . . . . . . . . . Degree of protection . . . . . . . . . . . . . . . . . . . Overvoltage protector . . . . . . . . . . . . . . . . . . Post-connection check . . . . . . . . . . . . . . . . . 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9 Trouble-shooting instructions . . . . . . . . . . . . . 76 System error messages . . . . . . . . . . . . . . . . . 77 Application errors . . . . . . . . . . . . . . . . . . . . . . 79 Orientation of the Micropilot . . . . . . . . . . . . . . 81 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Software history . . . . . . . . . . . . . . . . . . . . . . . 86 Contact addresses of Endress+Hauser . . . . . 86 10 Technical data . . . . . . . . . . . . . . . . . . . . 87 5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . 33 5.1 5.2 5.3 5.4 5.5 Quick operation guide . . . . . . . . . . . . . . . . . . Display and operating elements . . . . . . . . . . Local operation . . . . . . . . . . . . . . . . . . . . . . . Display and acknowledging error messages HART communication . . . . . . . . . . . . . . . . . . 4 4 4 5 6 11 12 13 19 27 28 30 32 32 32 32 33 35 38 41 42 10.1 Technical data at a glance . . . . . . . . . . . . . . . 87 11 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . 92 11.1 Operating menu HART (Display modul), ToF Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 11.2 Operating matrix HART / Commuwin II . . . . . . 94 11.3 Description of functions . . . . . . . . . . . . . . . . . 95 11.4 Function and system design . . . . . . . . . . . . . . 96 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Endress+Hauser 3 1 Safety instructions Micropilot S FMR 530 1 Safety instructions 1.1 Designated use The Micropilot S FMR 530 is a compact radar level transmitter for the continuous, contactless measurement of liquids, pastes and sludge in stilling wells. The device can also be freely mounted outside closed metal vessels because of its operating frequency of about 6 GHz and a maximum radiated pulsed energy of 1mW (average power output 1 µW). Operation is completely harmless to humans and animals. 1.2 Installation, commissioning and operation The Micropilot S has been designed to operate safely in accordance with current technical, safety and EU standards. If installed incorrectly or used for applications for which it is not intended, however, it is possible that application-related dangers may arise, e.g. product overflow due to incorrect installation or calibration. For this reason, the instrument must be installed, connected, operated and maintained according to the instructions in this manual: personnel must be authorised and suitably qualified. The manual must have been read and understood, and the instructions followed. Modifications and repairs to the device are permissible only when they are expressly approved in the manual. 1.3 Operational safety Hazardous areas Measuring systems for use in hazardous environments are accompanied by separate "Ex documentation", which is an integral part of this Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory. • Ensure that all personnel are suitably qualified. • Observe the specifications in the certificate as well as national and local regulations. FCC-approval This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. " 4 Caution! Changes or modifications not expressly approved by the part responsible for compliance could void the user’s authority to operate the equipment. Endress+Hauser Micropilot S FMR 530 1 Safety instructions 1.4 Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser for repair: • Always enclose a duly completed "Declaration of contamination" form. Only then can Endress +Hauser transport, examine and repair a returned device. • Enclose special handling instructions if necessary, for example a safety data sheet as per EN 91/155/EEC. • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present. This is especially important if the fluid is dangerous to health, e.g. corrosive, poisonous, carcinogenic, radioactive, etc. Endress+Hauser ! Note! A copy of the “Declaration of contamination” is included at the end of this operating manual. " Caution! • No instrument should be sent back for repair without all dangerous material being completely removed first, e.g. in scratches or diffused through plastic. • Incomplete cleaning of the instrument may result in waste disposal or cause harm to personnel (burns, etc.). Any costs arising from this will be charged to the operator of the instrument. 5 1 Safety instructions Micropilot S FMR 530 1.5 Notes on safety conventions and symbols In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin. Safety conventions Explosion protection Electrical symbols 6 Symbol Meaning # Warning! A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the instrument " Caution! Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or incorrect functioning of the instrument ! Note! A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation or may lead to an instrument response which is not planned 0 Device certified for use in explosion hazardous area If the Micropilot has this symbol embossed on its name plate it can be installed in an explosion hazardous area - Explosion hazardous area Symbol used in drawings to indicate explosion hazardous areas. – Devices located in and wiring entering areas with the designation “explosion hazardous areas” must conform with the stated type of protection . Safe area (non-explosion hazardous area) Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. – Devices located in safe areas still require a certificate if their outputs run into explosion hazardous areas. % Direct voltage A terminal to which or from which a direct current or voltage may be applied or supplied & Alternating voltage A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or supplied ) Grounded terminal A grounded terminal, which as far as the operator is concerned, is already grounded by means of an earth grounding system * Protective grounding (earth) terminal A terminal which must be connected to earth ground prior to making any other connection to the equipment + Equipotential connection (earth bonding) A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice Endress+Hauser Micropilot S FMR 530 2 Identification 2 Identification 2.1 Device designation 2.1.1 Nameplate The following technical data are given on the instrument nameplate: max. measuring range in tank ENDRESS+HAUSER MICROPILOT S II1/2 G EEx ia IIC T6...T3 D00676-F Registration No ATEX if modification see sep. label Messbereich max. Measuring range PN max. TAntenne max. PTB 00 ATEX U: 16...30 VDC 4...20 mA / 16...30 VDC TA > 70°C: t >85°C x= measuring range 0560 °C Anschlusswerte u.Temp.-Klasse siehe/ Connection values and temp.-classific.see Dat./Insp.: X X X X X X max permissible temperature on the antenna Safety information Fig. 1 L00-FMR53xxx-18-00-00-en-003 Order Code: Ser.-No.: XXXXXXXXXXX 0032 79689 Maulburg Degree of protection Made in Germany Order No (see Order Information) Information on the nameplate of the Micropilot S FMR 530 (example) Year of construction Tank reference height Certification no Tank-no. Hersteller / Producer : ENDRESS+HAUSER MICROPILOT S FMR Zertifikat-Nr. Certification no. Baujahr Year of constr. D00748-C Certificated Measuring range Fig. 2 from ... to ... min. environment temperature °C max. environment temperature L00-FMR53xxx-18-00-00-en-004 T5754 Tankreferenzhöhe m Tank reference height Tank-Nr. Tank-no. Zert.Messbereich/Cert.Measuring range TUmgeb./Environm. von bis max m min from to Information on the NMi type plate for custody transfer applications of the Micropilot S FMR 530 (example) Year of construction Tank reference height Tank-no. Hersteller / Producer : ENDRESS+HAUSER Approval number MICROPILOT S FMR 4.413 Year and month of type approval Fig. 3 Endress+Hauser Tankreferenzhöhe m Tank reference height Tank-Nr. Tank-no. Zert.Messbereich/Cert.Measuring range TUmgeb./Environm. von bis max m min from to from ... to ... min. environment temperature °C max. environment temperature L00-FMR53xxx-18-00-00-en-005 01.06 D00549-B Certificated Measuring range Baujahr Year of constr. Information on the PTB type plate for custody transfer applications of the Micropilot S FMR 530 (example) 7 2 Identification Micropilot S FMR 530 2.1.2 Ordering structure Ordering structure Micropilot S FMR 530 10 20 30 Certificates A For non-hazardous areas G ATEX II 3G EEx nA II T6 K TIIS Ex ia IIC T3 L TIIS Ex ia IIC T6 S FM IS - Class I, Division 1, Group A-D U CSA IS - Class I, Division 1, Group A-D 1 ATEX II 1/2 G EEx ia IIC T6 6 ATEX II 1/2 G EEx ia IIC T6 + WHG Y Special version Antenna type Type A Horn antenna C Horn antenna D Horn antenna E Horn antenna G Horn antenna H Horn antenna I Horn antenna K Horn antenna L Horn antenna M Horn antenna P Horn antenna R Horn antenna U Horn antenna W Horn antenna X Horn antenna Y Special version 50 60 FMR 530- 8 Additional weight Size 150 mm / 6" 150 mm / 6" 150 mm / 6" 250 mm / 10 " 250 mm / 10" 250 mm / 10" 100 mm / 4" 100 mm / 4" 100 mm / 4" 80 mm / 3" 80 mm / 3" 80 mm / 3" 200 mm / 8" 200 mm / 8" 200 mm / 8" for non-conductive media, gas-tight for non-conductive media, gas-tight for conductive media, gas-tight for non-conductive media, gas-tight for non-conductive media, gas-tight for conductive media, gas-tight for non-conductive media, gas-tight for non-conductive media, gas-tight for conductive media, gas-tight for non-conductive media, gas-tight for non-conductive media, gas-tight for conductive media, gas-tight for non-conductive media, gas-tight for non-conductive media, gas-tight for conductive media, gas-tight Process connection Flange Dia/Pressure ALJ 3"/150 lbs/RF AMJ 3"/300 lbs/RF APJ 4"/150 lbs/RF AQJ 4"/300 lbs/RF AVJ 6"/150 lbs/RF A3J 8"/150 lbs/RF A5J 10"/150 lbs/RF CMJ DN80 PN10 / 16 C Norm ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 CNJ DN80 PN25 / 40 C CQJ DN100 PN10 / 16 C CRJ Sealing Viton Kalrez PTFE Viton Kalrez PTFE Vitron Kalrez PTFE Vitron Kalrez PTFE Vitron Kalrez PTFE 0.5 kg 0.5 kg 0.5 kg 1.3 kg 1.3 kg 1.3 kg 0.3 kg 0.3 kg 0.3 kg 0.2 kg 0.2 kg 0.2 kg 0.9 kg 0.9 kg 0.9 kg EN 1092,1, B11) Material 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316L 5.0 kg 6.8 kg 7.0 kg 11.5 kg 11.3 kg 19.6 kg 28.8 kg 4.8 kg EN 1092,1, B11) 316L 5.9 Kg EN 1092,1, B11) 316L 5.8 kg DN100 PN25 / 40 C EN 1092,1, B11) CWJ DN150 PN10 / 16 C EN 1092,1, B11) 316L 316L 7.6 kg 10.6 kg CXJ DN200 PN10 / 16 C EN 1092,1, B11) 316L 16.5 kg C6J DN250 PN16 C KA2 KD2 KH2 KV2 K52 10 K 80A / RF 10 K 200A / RF 10 K 100A / RF 10 K 150A / RF 10 K 250A / RF 316L EN 1092,1, B11) JIS B2210 SS316Ti JIS B2210 SS316Ti JIS B2210 SS316Ti JIS B2210 SS316Ti JIS B2210 SS316Ti 1) agreeable to DIN2527 Form C YY9 40 Basic weight 7.1 kg 25.6 kg 3.7 kg 13.8 kg 4.5 kg 9.9 kg 22.5 kg Special version Output and operation A 4…20 mA HART with VU 331, 4-line alphanumeric display Y Special version Housing C Aluminium T12-housing with separate connection compartment, coated, IP65 Y Special version Gland / Entry 1 Pg13.5 cable gland 2 M20x1.5 cable gland 3 G ½ cable entry 4 ½ NPT cable entry 9 Special version Product designation (Part 1) Endress+Hauser Micropilot S FMR 530 2 Identification 70 80 FMR 530- Endress+Hauser Custody transfer approvals A NMi, PTB type and test rig approval, weights&measures approved (< 1 mm) F NMi initial verification, type and test rig approval, weighth&measures approved (< 1 mm) G PTB initial verification, type and test rig approval, weights&measures approved (< 1 mm) R Inventory Control Version, not weights&measures approved (3 mm) Y Special approval for custody transfer Additional options A Without additional options S GL (German Lloyd) marine certificate Y Special version Complete product designation 9 2 Identification Micropilot S FMR 530 2.2 " Scope of delivery Caution! It is essential to follow the instructions concerning the unpacking, transport and storage of measuring instruments given in the chapter »Incoming acceptance, transport, storage« on page 12 The scope of delivery consists of: • Assembled instrument • ToF Tool (operating program) • Accessories (s. Chapter 8) Accompanying documentation: • Short manual (basic equalisation/troubleshooting): housed in the instrument • Operating manual (this manual) • Operating manual: Description of the instrument functions • Approval documentation: if this is not included in the operating manual. 2.3 Certificates and approvals CE mark, declaration of conformity The instrument is designed to meet state-of-the-art safety requirements, has been tested and left the factory in a condition in which it is safe to operate. The instrument complies with the applicable standards and regulations in accordance with EN 61010 "Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures". The instrument described in this manual thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark. 2.4 Registered trademarks KALREZ ®, VITON ®, TEFLON ® Registered trademark of the company E.I. Du Pont de Nemours & Co., Wilmington, USA TRI-CLAMP ® Registered trademark of the company Ladish & Co., Inc., Kenosha, USA HART ® Registered trademark of HART Communication Foundation, Austin, USA ToF ® Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany PulseMaster ® Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany PhaseMaster ® Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany 10 Endress+Hauser Micropilot S FMR 530 # 3 Mounting 3 Mounting 3.1 Quick installation guide Observe orientation when installing! Installation in tank (free space): Mark on process connector facing the nearest tank wall! Turn housing The housing can be turned in order to simplify access to the display and the terminal compartment 90 ° marker at instrument flange 90 ° T12 housing 2 ° 90 ±2° 90 DN150 ANSI 6” ° 0… 2° DN200…250 ANSI 8…10” 3 90 ° 1 Installation in stilling well: Mark on process connector pointed towards the slots or vent holes! Allen key 4 mm tighten strongly by hand DN50 ANSI 2” Endress+Hauser DN80…150 ANSI 3…6” L00-FMR530xx-17-00-00-en-010 90 ° marker at instrument flange 11 3 Mounting Micropilot S FMR 530 3.2 Incoming acceptance, transport, storage 3.2.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order. 3.2.2 " Transport Caution! Follow the safety instructions and transport conditions for instruments of more than 18 kg. Do not lift the measuring instrument by its housing in order to transport it. 3.2.3 Storage Pack the measuring instrument so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C…+80 °C. 12 Endress+Hauser Micropilot S FMR 530 3 Mounting 3.3 Installation Conditions 3.3.1 Dimensions T12 housing 94 (3.7") ENDRESS+HAUSER Micropilot II for non-conducting media 161 (6.34") 65 (2.56") 85 (3.35") Ø 129 (5.08") 68 (2.68") 1) antenna extension 86 (3.39") L L1 86 (3.39") DIN ANSI JIS L Ød 40 (1.57") ØD Ød for conducting media 86 (3.39") ØD L00-FMR530xx-06-00-00-en-002 L 21 (0.83") antenna extension: L1 = 100 mm (3.98") / 200 mm (7.87") / 300 mm (11.81") / 400 mm (15.75") … Ød ØD Fig. 4 Dimensions Micropilot S FMR 530 1) Antenna extension see Page 20, 65, 74. Flange to EN1092-1 *) Antenna type (ØD) DN80 / 3" DN100 / 4" DN150 / 6" DN200 / 8" DN250 / 10" d [mm (inch)] 76 (3") 96 (3.78") 146 (5.75") 191 (7.52") 241 (9.49") L [mm (inch)] 74 (2.91") 119 (4.69") 204 (8.03") 289 (11.38") 379 (14.92") *) compatible with DIN 2527 Endress+Hauser 13 3 Mounting Micropilot S FMR 530 Engineering hints Orientation • Recommended distance (1) wall – outer edge of nozzle: ~ 1/6 of tank diameter. • Mount the Micropilot S at a position where the tank movement due to filling/ emptying of the tank is of low influence. • Not in the centre (3), interference can cause signal loss. • Not above the fill stream (4). • It is recommended to use a weather protection cover (2) in order to protect the transmitter from direct sun or rain. Assembly and disassembly is simply done by means of a tension clamp (see »Accessories« on page 74). L00-FMR53xxx-17-00-00-yy-004 3.3.2 Optimization options • Antenna size: the bigger the antenna, the smaller the beam angle, the less interference echoes. • Mapping: the measurement can be optimized by means of electronic suppression of interference echoes. • Antenna alignment: refer to "optimum mounting position" • Stilling well: a stilling well can always be used to avoid interference. The FMR 532 with planar antenna is recommended for stilling wells with a diameter DN150 (6”) and larger. L00-FMR53xxx-17-00-00-yy-005 Tank installations • Avoid any installations (1), like limit switches, temperature sensors, etc., inside the signal beam (refer to beam angle). • It is essential that HiHi alarm is below the blocking distance (BD) and teh safety distance (SD) (see page 16). • Symmetrical installations (2), e.g. vacuum rings, heating coils, baffles, etc., can also interfere with the measurement. Please contact Endress+Hauser for further information. 14 Endress+Hauser Micropilot S FMR 530 3 Mounting Beam angle The beam angle is defined as the angle α where the energy density of the radar waves reaches half the value of the maximum energy density (3dB-width). Microwaves are also emitted outside the signal beam and can be reflected off interfering installations. Beamwidth diameter W as function of antenna type (beam angle α) and measuring distance D: Antenna size Beam angle α Measuring distance (D) Endress+Hauser FMR 530 DN150 DN200 DN250 23° 19° 15° Beamwidth diameter (W) DN150 DN200 DN250 3 m / 10 ft 1.22 m / 4.07 ft 1.00 m/ 3.35 ft 0.79 m / 2.63 ft 6 m / 20 ft 2.44 m / 8.14 ft 2.01 m / 6.69 ft 1.58 m / 5.27 ft 9 m / 30 ft 3.66 m / 12.21 ft 3.01 m / 10.04 ft 2.37 m / 7.90 ft 12 m / 40 ft 4.88 m / 16.26 ft 4.02 m / 13.39 ft 3.13 m / 10.53 ft 15 m / 49 ft 6.10 m / 19.94 ft 5.02 m / 16.40 ft 3.95 m / 12.90 ft 20 m / 65 ft 8.14 m / 26.45 ft 6.69 m / 21.75 ft 5.27 m / 17.11 ft 25 m / 82 ft 10.17 m / 33.37 ft 8.37 m / 27.44 ft 6.58 m / 21.59 ft D W 15 3 Mounting Micropilot S FMR 530 Measuring conditions • The measuring range begins where the beam hits the tank bottom. Particularly with dish bottoms or conical outlets the level cannot be detected below this point. • In case of media with a low dielectric constant (groups A and B), the tank bottom can be visible through the medium at low levels. In order to guarantee the required accuracy in these cases, it is recommended to position the zero-point at a distance C above the tank bottom (see Fig.). • In principle it is possible to measure up to the tip of the rod and horn antenna. However, due to considerations regarding accuracy corrosion and build-up, the end of the measuring range should not be chosen any closer than 50 mm (2”) to the tip of the rod and horn antenna (see A in Fig.). • For overspill protection, it is possible to define a safety distance (SD) additionally to the blocking distance (BD). • By default, this safety distance (SD) is set to 0.1 m (4") and generating an alarm in case the level rises inside the safety distance. • Distance B defined the smallest recommended measurement range. • Tank diameter and height should be at least dimensioned such that a reflection of the radar signal on both sides of the tank can be ruled out (see »Beam angle«). • Depending on its consistence, foam can either absorb microwaves or reflect them off the foam surface. Measurement is possible under certain conditions. 100% BD A SD max. level L00-FMR53xxx-17-00-00-en-002 B C 0% reference: flange / BD (cf. picture) FMR 530 (horn) reference: antenna tip (cf. picture) Blocking distance Safety distance BD [m / ft] SD [m / ft] A [mm / inch] B [m / ft] C [mm / inch] horn length 0.1 / 0.3 50 / 2 0.5 / 1.64 150…300 / 6…12 recommended additional settings Behaviour if measuring range is exceeded The behaviour in case of the measuring range being exceeded can be freely set: the default setting is a current of 22 mA and the generation of a digital warning (E681). 16 Endress+Hauser Micropilot S FMR 530 3 Mounting Measuring range The usable measuring range depends on the size of the antenna, the reflectivity of the medium, the mounting location, and eventual interference reflections. The following tables describe the groups of media as well as the achievable measuring range as a function of application and media group. If the dielectric constant of a medium is unknown, it is recommended to assume media group B to ensure a reliable measurement. Product class DK (εr) A 1.4 … 1.9 B 1.9 … 4 non-conducting liquids, e.g. benzene, oil, toluene, … C 4 … 10 e.g. concentrated acids, organic solvents, esters, aniline, alcohol, acetone, … D > 10 conducting liquids, e.g. aqueous solutions, dilute acids and alkalis Examples non-conducting liquids, e.g. liquefied gas 1) 1) Treat Ammonia NH3 as a medium of group A, e.g. always use a stilling well. Measuring range depending on product class for Micropilot S FMR 530: Product class Stilling well/ Bypass Free space (Storage tank) Measuring range Measuring range FMR 530 DN80/100 2) FMR 530 DN 150/200/250 A DK(εr)=1,4…1,9 20 m/65 ft — B DK(εr)=1,9…4 20 m/65 ft DN150: 10 m/33 ft DN200/250: 20 m/65 ft C DK(εr)=4…10 20 m/65 ft DN150: 15 m/50 ft DN200/250: 20 m/65 ft D DK(εr)>10 20 m/65 ft DN150: 20 m/67 ft DN200/250: 25 m/82 ft max. measuring range with custody transfer approvals —— DN150: 20 m/67 ft DN200/250: 25 m/82 ft 2) For bigger Stilling wells we recommend the Micropilot S FMR 532 with Planar antenna. ! Endress+Hauser Note! The FMR 530 (DN 80/100) allows millimetre accuracy in free field up to 10 m. 17 3 Mounting Micropilot S FMR 530 L00-FMR53xxx-15-00-00-en-002 Blocking distance The blocking distance (= BD) is the minimum distance from the reference point of the measurement (mounting flange) to the medium surface at maximum level. Blocking distance (BD) from flange ! 18 Stilling well / Bypass Free space (Storage tank) FMR 530 FMR 530 Length of horn (see Page 13) Length of horn (see Page 13) Note! If an antenna extension is used, its length has to be added. Inside the blocking distance a reliable measurement can not be guaranteed. Endress+Hauser Micropilot S FMR 530 3 Mounting 3.4 Installation instructions 3.4.1 Mounting kit In addition to the tool needed for flange mounting, you will require the following tool: • 4 mm Allen wrench for turning the housing or mounting an FAR 10 antenna extension. 3.4.2 Installation in tank (free space) L00-FMR530xx-17-00-00-en-001 Optimum mounting position Standard installation Antenna size Endress+Hauser 150 mm / 6" 200 mm / 8" L00-FMR530xx-17-00-00-en- When mounting in tank, please observe engineering hints on Page 14 and the following points: • Marker is aligned towards tank wall. • The marker is always exactly in the middle between two bolt-holes in the flange. • The device shall not be mounted in a slant towards the tank wall. • After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. • The horn antenna must extend below the nozzle, otherwise use antenna extension FAR 10. • The horn antenna must be aligned vertically. Attention! Do not point radar beam towards tank wall (see figure). 250 mm / 10" D [mm / inch] 146 / 5.8 191 / 7.5 241 / 9.5 H [mm / inch] <205 / <8.1 <290 / <11.5 <380 / <15 19 Micropilot S FMR 530 Antenna extension FAR 10 When mounting an antenna extension, please note the following points: • The antenna extension has to be selected such that the horn extends below the nozzle. • If the horn diameter is greater than the nominal width of the nozzle, the antenna including the extension is mounted from inside the vessel. The bolts are tightened from outside, with the instrument lifted up. The extension has to be selected such that the instrument can be lifted by at least 100 mm (4”). • Offset correction is to be performed (see page 65). L00-FMR230xx-17-00-00-en-003 3 Mounting The horn is bigger than the nozzle diameter If the horn is bigger than the nozzle diameter, proceed as follows: • Screw the extension tube and horn together (1) • Insert the fixing screws of the extension two to three turns into the process connection • Position the Micropilot on the nozzle • Invert the extension flange via the fixing screws from inside the vessel and then turn it clockwise (2). The extension hangs loosely from the process connection • Lift the Micropilot and tighten up the fixing screws with a 4 mm Allen wrench (3) • Fix the Micropilot onto the nozzle. 20 L00-FMR230xx-17-00-00-en-009 The horn fits the nozzle If the horn fits the nozzle, proceed as follows: • Screw the extension tube and horn together (1) • Insert the fixing screws of the extension two to three turns into the process connection • Invert the extension flange using the fixing screws and then turn it clockwise(2) • Tighten up the fixing screws • Tighten up the flange Endress+Hauser Micropilot S FMR 530 3 Mounting 3.4.3 Installation in stilling well L00-FMR530xx-17-00-00-en-003 Optimum mounting position for FMR 530 Standard installation For installations in a stilling well, follow the engineering hints on Page 14 and note the following points: • The marker is always exactly in the middle between two bolt-holes in the flange. • After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. • Horn- or planar axis vertical to flange, align markers toward slots. • Measurements can be performed through an open ball valve without any problems. Recommendations for the stilling well • Metal (no enamel coating, plastic on request). • Constant diameter. • Weld seam as smooth as possible and on the same axis as the slots. • Slots offset 180° (not 90°). • Slot width respectively diameter of holes max. 1/10 of pipe diameter, de-burred. Length and number do not have any influence on the measurement. # Endress+Hauser Note at Horn antenna: • Select horn antenna as big as possible. For intermediate sizes (e.g. 180 mm) select next larger antenna and adapt it mechanically. • At any transition (e.g. when using a ball valve or mending pipe segments), no gap may be created exceeding 0.1 mm in case of FMR 530. • The stilling well must be smooth on the inside (average roughness Rz ≤ 30). Use extruded or parallel welded stainless steel pipe. An extension of the pipe is possible with welded flanges or pipe sleeves. Flange and pipe have to be properly aligned at the inside. • Do not weld through the pipe wall. The inside of the stilling well must remain smooth. In case of unintentional welding through the pipe, the weld seam and any unevenness on the inside need to be carefully removed and smoothened. Otherwise, strong interference echoes will be generated and material build-up will be promoted. • Particularly on smaller nominal widths it needs to be observed that flanges are welded to the pipe such that they allow for a correct orientation (marker aligned toward slots). 21 3 Mounting Micropilot S FMR 530 Examples for the construction of stilling wells Micropilot S FMR 530 e.g. welding neck flange DIN 2633 sample hatch for manual gauging stilling well with slots marker 100 % < 1/10 Ø Rohr inside of holes deburred 0% 22 L00-FMR53xxx-17-00-00-en-006 100 % gap < 0.1 < 0.004” 150…500 6”…20” hole < 1/10 Ø pipe diameter, single sided or drilled through Endress+Hauser Micropilot S FMR 530 3 Mounting 3.4.4 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: • Undo the fixing screws (1) • Turn the housing (2) in the required direction • Tighten up the fixing screws (1) T12 housing 2 Allen key 4 mm tighten strongly by hand Endress+Hauser L00-FMR530xx-17-00-00-en-011 1 23 3 Mounting Micropilot S FMR 530 3.4.5 Mounting with Roof reflector Reflector Measurements on floating roofs are not recommended for highly accurate measurements due to the unsteady movements of the floating roofs. A special reflector can be used for applications on floating roofs (not for FMR 532 with planar antenna!). Construction hints Note! The roof reflector is not part of the standard offering from Endress+Hauser. L00-FMR53xxx-06-00-00-en-002 ! 24 Endress+Hauser Micropilot S FMR 530 3 Mounting Optimum mounting position Positioning of the reflector on a floating roof: • The upper edges of the reflector have to be aligned horizontally. • For slanted locations (e.g. domeshaped floating roof), the feet must be extended accordingly. L00-FMR530xx-17-00-00-en-012 Please contact Endress+Hauser for further information. Endress+Hauser 25 3 Mounting Micropilot S FMR 530 3.4.6 Mounting with Inclination device Installation hints The inclination can be adjusted up to 6° by means of an inclination device. The purpose is to align the antenna axis such, that the radar beam does not touch the tank wall. Note! The inclination device is not part of the standard offering from Endress+Hauser. t 3° t/2 ! 3 pins O-ring groove (buttom inclination ring only) 30+5 ° flange 2 deep bores for secure placement of level pins inclination ring components: 2 inclination rings 1 O-ring (Viton) 3 pins H max. = 200 O-ring O-ring groove inclination ring L00-FMR530xx-06-00-00-en-003 flange 26 Endress+Hauser Micropilot S FMR 530 3 Mounting 3.5 Post-installation check After the measuring instrument has been installed, perform the following checks: • Is the measuring instrument damaged (visual check)? • Does the measuring instrument correspond to the measuring point specifications such as process temperature/pressure, ambient temperature, measuring range, etc.? • Is the flange marking correctly aligned? (see Page 11 ff.) • Have the flange screws been tightened up with the respective tightening torque? • Are the measuring point number and labeling correct (visual check)? • Is the measuring instrument adequately protected against rain and direct sunlight (see Page 74 ff.)? Endress+Hauser 27 4 Wiring Micropilot S FMR 530 4 Wiring 4.1 Quick wiring guide When grounding conductive screens, the corresponding directives EN 60079-14 and EN 1127-1 must be observed. Recommendation for safe grounding of conductive screens: Before connection please note the following: ● Caution! ● ● Switch off power supply before connecting up the device. PTB 00 ATEX 1 Messbereich max. Measuring range PN max. 3 TAntenne max. 4 8 II1/2 G EEx ia IIC T6...T3 Connect Equipotential bonding to transmitter ground terminal before connecting up the device. U: 16...30 VDC 4...20 mA / 16...30 VDC TA > 70°C: t >85°C Dat./Insp.: X X X X X X Tighten the locking screw: It forms the connection between the antenna and the housing ground potential. 0560 5 if modification x= see sep. label 1 Order Code: Ser.-No.: XXXXXXXXXXX D00676-F ● ENDRESS+HAUSER MICROPILOT S The power supply must be identical to the data on the nameplate (1). 2 °C Anschlusswerte u.Temp.-Klasse siehe/ Connection values and temp.-classific.see 7 Made in Germany " 0032 79689 Maulburg Wiring 2 When you use the measuring system in hazardous areas, make sure you comply with national standards and the specifications in the safety instructions (XA’s). Make sure you use the specified cable gland. - Connect up the Micropilot S as follows: Before unscrew housing cover (2) at seperate connection room turn off the power supply! ● Insert cable through gland (3). Use screened, twisted wire pair.. Only ground screening of the line (5) on sensor side. ● Make connection (see pin assignment). ● Tighten cable gland (4). ● Screw off housing cover (2). ● Switch on power supply. 4 3 power: 24 VDC (16…30 V) signal: 24 VDC 5 1 2 3 4 1 2 3 4 plant ground 5 A Micropilot S situated in a hazardous area is connected as a single device to a power supply unit and transmitter situated outside of the hazardous area. In this case, it is recommended that the screen be connected directly to the Micropilot at the housing's earth, whereby the Micropilot S and the power supply unit are connected to the same potential matching line (PML). 28 L00-FMR53xxx-04-00-00-en-007 1 2 3 4 5 Endress+Hauser Micropilot S FMR 530 4 Wiring Before connection please note the following: ● Caution! ● ● 1 Order Code: Ser.-No.: XXXXXXXXXXX PTB 00 ATEX 1 Switch off power supply before connecting up the device. 8 II1/2 G EEx ia IIC T6...T3 D00676-F ● ENDRESS+HAUSER MICROPILOT S The power supply must be identical to the data on the nameplate (1). Connect Equipotential bonding to transmitter ground terminal before connecting up the device. U: 16...30 VDC 4...20 mA / 16...30 VDC TA > 70°C: t >85°C Dat./Insp.: X X X X X X x= 0560 5 if modification see sep. label Messbereich 2 max. Measuring range PN max. 3 TAntenne max. °C 4 Anschlusswerte u.Temp.-Klasse siehe/ Connection values and temp.-classific.see 7 Made in Germany " 0032 79689 Maulburg Wiring with Tank Side Monitor NRF 590 2 Tighten the locking screw: It forms the connection between the antenna and the housing ground potential. When you use the measuring system in hazardous areas, make sure you comply with national standards and the specifications in the safety instructions (XA’s). Make sure you use the specified cable gland. Tank Side Monitor NRF590 Connect up the Micropilot S as follows: Before unscrew housing cover (2) at seperate connection room turn off the power supply! ● Insert cable through gland (3). Use screened, twisted wire pair. ● Make connection (see pin assignment). ● Tighten cable gland (4). ● Screw off housing cover (2). ● Switch on power supply. 4 3 intrinsicaly safe board terminal NRF 590 i.s. terminal board 16 17 18 19 D+ S+ SD- 20 21 22 23 OPT1 OPT2 OPT3 OPT4 24 25 26 27 + H + H - 28 29 30 31 + -H + P - RTD grounding not on Micropilot S grounding single sided on Tank Side Monitor NRF590 i.s. module wiring Internally HART interconnected sensor as one HART fieldbus loop + 4 - 3 + 2 - 1 1 2 3 4 1 2 3 4 5 1 2 3 4 plant ground 5 Micropilot S Endress+Hauser The Micropilot S is - possibly in combination with other devices - connected to a tank side monitor in a hazardous area. In this case, it is recommended that you ground the cable screen centrally at the Tank Side Monitor and connect all devices to the same potential matching line (PML). If, for functional reasons, a capacitive coupling is required between local earth and screen (multiple grounding), ceramic condensers with a dielectric strength of min. 1500 Vef f must be used, whereby the total capacitance of 10 nF must not be exceeded. Notes on grounding interconnected intrinsically safe devices are provided by the FISCO model. L00-FMR53xxx-04-00-00-en-006 For Micropilot only for S-series only! 29 4 Wiring Micropilot S FMR 530 4.2 Connecting the measuring unit L00-FMR53xxx-04-00-00-en-001 Terminal compartment The housing comes with a separate terminal compartment. Load HART Minimum load for Hart communication: 250 Ω Cable entry Cable gland: M20x1.5 or Pg13.5 Cable entry: G ½ or ½ NPT Supply voltage Direct current voltage: 16…36 VDC . Communication Power supply Terminal voltage minimal maximal Standard U (20 mA) = 16 V 36 V Ex U (20 mA) = 16 V 30 V U (4 mA) = 11,5 V 30 V U (20 mA) = 11,5 V 30 V Signal Ex Power consumption Max. 330 mW at 16 V, max. 500 mW at 24 V, max. 600 mW at 30 V. Current consumption Max. 21 mA (50 mA inrush current). Power supply For stand alone operation recommended via e.g. E+H RN 221 N. mm accuracy For measurements with mm accuracy the measured variable must be transmitted using HART protocol to ensure the necessary resolution. 30 Endress+Hauser Micropilot S FMR 530 4 Wiring 4.2.1 Connection to Tank Side Monitor NRF590 See Page 29. 4.2.2 HART connection with two E+H RN 221 N - ToF Tool FXA 193 power supply 4...20 mA signal dsdmdm df das. asdas fa asas la. DELTABAR: * * * * * * * * ONLINE 1 QUICK SETUP 2 OPERATING MENU 3 PV 4 SV 1 2 3 5 4 352 mbar 0 °C SAVE 9 - COMMUWIN II - ToF Tool 6 Page Up Bksp Delete Page On #%& ABC 1 DEF 3 2 Copy Paste GHI JKL 4 5 Hot Key MNO 6 Insert PQRS + Hot Key TUV W XY Z 8 7 L00-FMR53xxx-04-00-00-en-004 HELP 9 ,()‘ _<> +*/ . 0 - HART 375 FIELD COMMUNICATOR HART handheld DXR 375 4.2.3 Commubox FXA 191 HART connection with other supplies - ToF Tool DC voltage FXA 193 or PLC power supply 4...20 mA signal ≥ 250 Ω dsdmdm df das. asdas fa asas la. DELTABAR: * * * * * * * * ONLINE 1 2 3 4 5 352 mbar 0 °C SAVE 9 Page Up Bksp 6 Delete Page On #%& ABC 1 2 Copy Paste GHI 3 JKL MNO 6 5 4 Insert PQRS + Hot Key TUV W XY Z 8 7 - COMMUWIN II - ToF Tool DEF Hot Key 9 ,()‘ _<> +*/ . 0 - HART 375 FIELD COMMUNICATOR HART handheld DXR 375 " Endress+Hauser Commubox FXA 191 L00-FMR53xxx-04-00-00-en-005 1 QUICK SETUP 2 OPERATING MENU 3 PV 4 SV HELP Caution! If the HART communication resistor is not built into the supply unit, it is necessary to insert a communication resistor of 250 Ω into the 2-wire line. 31 4 Wiring Micropilot S FMR 530 4.3 Equipotential bonding Connect the Equipotential bonding to the external ground terminal of the transmitter. " Caution! In Ex applications, the instrument must only be grounded on the sensor side. Further safety instructions are given in the separate documentation for applications in explosion hazardous areas. 4.4 Degree of protection • housing: IP 65, NEMA 4X (open housing: IP20, NEMA 1) • antenna: IP 68 (NEMA 6P) 4.5 Overvoltage protector • The level transmitter FMR 53x is equipped with an internal overvoltage protector (600 Vrms electrode). Connect the metallic housing of the Micropilot FMR 53x to the tank wall directly with an electrically conductive lead to ensure reliable potential matching. • Installation with additional overvoltage protector HAW 262 Z (see XA 081F-A "Safety instructions for electrical apparatus certified for use in explosion-hazardous areas"). – Connect the external overvoltage protector and the Micropilot FMR 53x transmitter to the local potential matching system. – Potentials shall be equalised both inside and outside the explosion hazardous area. – The cable connecting the overvoltage protector and the Micropilot FMR 53x transmitter shall not exceed 1 m in length; – The cable shall be protected e.g. routed in an armoured hose. 4.6 Post-connection check After wiring the measuring instrument, perform the following checks: • Is the terminal allocation correct (see Page 28 ff.)? • Is the cable gland tight? • Is the housing cover screwed tight? • If auxiliary power is available: Is the instrument ready for operation and does the liquid crystal display show any value? 32 Endress+Hauser Micropilot S FMR 530 5 Operation 5 Operation 5.1 Quick operation guide ENDRESS + HAUSER – + X E F 2x X O basic setup safety settings F ... S X tank shape O linearisation extended calibr. X S dome ceiling F horizontal cyl >3 s medium property O DC: 1.9 ... 4 DC: 4 ... 10 S Group Selection DC: < 1.9 stilling well sphere Return to unknown bypass flat ceiling ... DC: > 10 ... Selection and configuration in Operation menu: 1.) Change from Measured Value Display to Group Selection by pressing F 2.) Press S or O to select the required Function Group (e.g.. "basic setup (00)") and confirm by pressing F ➜ First function (e.g. "tank shape (002)") is selected. Note! The active selection is marked by a in front of the menu text. 3.) Activate Edit mode with O or S. Selection menus: a) Select the required Parameter in selected function (e.g. "tank shape (002)") with S or O. b) F confirms selection ➜ appears in front of the selected parameter c) F confirms the edited value ➜ system quits Edit mode d) O + S (= X) interrupts selection ➜ system quits Edit mode 4) Press F to select the next function (e.g. "medium property (003)") 5) Press O + S (= X) once ➜ return to previous function (e.g. "tank shape (002)") Press O + S (= X) twice ➜ return to Group selection 6) Press O + S (= X) to return to Measured value display Endress+Hauser L00-FMR2xxxx-19-00-00-en-001 Typing in numerals and text: a) Press O or S to edit the first character of the numeral / text (e.g. "empty calibr. (005)") b) F positions the cursor at the next character ➜ continue with (a) until you have completed your input c) if a symbol appears at the cursor, press F to accept the value entered ➜ system quits Edit mode d) O + S (= X) interrupts the input, system quits Edit mode 33 5 Operation Micropilot S FMR 530 5.1.1 General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the instrument are split up roughly into different function groups. The function groups that are available include, e.g.: "basic setup", "safety settings", "output", "display", etc. • Functions (001, 002, 003, …, 0D8, 0D9): Each function group consists of one or more functions. The functions perform the actual operation or parameterisation of the instrument. Numerical values can be entered here and parameters can be selected and saved. The available functions of the “basic setup (00)” function group include, e.g.: "tank shape (002)", "medium property (003)", "process cond. (004)", "empty calibr. (005)", etc. If, for example, the application of the instrument is to be changed, carry out the following procedure: 1. Select the “basic setup (00)” function group. 2. Select the "tank shape (002)" function (where the existing tank shape is selected). 5.1.2 Identifying the functions L00-FMRxxxxx-07-00-00-en-005 For simple orientation within the function menus (see Page 92 ff.), for each function a position is shown on the display. The first two digits identify the function group: • basic setup 00 • safety settings 01 • linearisation 04 … The third digit numbers the individual functions within the function group: • basic setup 00 → • tank shape 002 • medium property 003 • process cond. 004 … Here after the position is always given in brackets (e.g. "tank shape" (002)) after the described function. 34 Endress+Hauser Micropilot S FMR 530 5 Operation Display and operating elements L00-FMR53xxx-07-00-00-en-003 5.2 Fig. 5 5.2.1 Layout of the display and operating elements Display Liquid crystal display (LCD): Four lines with 20 characters each. Display contrast adjustable through key combination. Headline Position indicator ENDRESS + HAUSER Symbol – + Main value Bargraph Unit E Help text +21dB Envelope curve Fig. 6 Endress+Hauser 0.00 2.305m 09C 10.00 L00-FMRxxxxx-07-00-00-en-003 Selection list Display 35 5 Operation Micropilot S FMR 530 5.2.2 Display symbols The following table describes the symbols that appear on the liquid crystal display: Symbols Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning. LOCK_SYMBOL This lock symbol appears when the instrument is locked,i.e. if no input is possible. COM_SYMBOL This communication symbol appears when a data transmission via e.g. HART, PFOFIBUS-PA or Foundation Fieldbus is in progress. Calibration to regulatory standards disturbed If the instrument is not locked or it cannot guarantee the calibration to regulatory standards, the situation will be indicated on the display via the symbol. Tab. 1 Meaning of the symbols Light emitting diods (LEDs): There is a green and a red LED besides the Liquid Crystal Display. 36 LED Meaning red LED continuously on Alarm red LED flashes Warning red LED off No alarm green LED continuously on Operation Green LED flashes Communication with external device Endress+Hauser Micropilot S FMR 530 5 Operation 5.2.3 Key assignment The operating elements are located inside the housing and are accessible for operation by opening the lid of the housing. Function of the keys Key(s) Meaning O or V Navigate upwards in the selection list Edit numeric value within a function S or W Navigate downwards in the selection list Edit numeric value within a function X or Z F or M O and F or S and F O and S and F Tab. 2 Navigate to the left within a function group Navigate to the right within a function group, confirmation. Contrast settings of the LCD Hardware lock / unlock After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. Function of the keys Custody locking switch Access to the electronics can be prevented by means of a custody locking switch that locks the device settings, cf fig. 4 on Page 35. The custody locking switch can be sealed for custody transfer applications. Software reliability The software used in the radar instruments FMR 53x fulfills the requirements of OIML R85. This particularly includes: • cyclical test of data consistency • non-volatile memory • segmented data storage The radar instruments Micropilot S continuously monitor the compliance with accuracy requirements for custody transfer measurements according to OIML R85. If the accuracy cannot be maintained, a specific alarm is generated on the local display and via the digital communication Endress+Hauser 37 5 Operation Micropilot S FMR 530 5.3 Local operation 5.3.1 Locking of the configuration mode The Micropilot can be protected in two ways against unauthorised changing of instrument data, numerical values or factory settings: "unlock parameter" (0A4): A value <> 100 (e.g. 99) must be entered in "unlock parameter" (0A4) in the "diagnostics" (0A) function group. The lock is shown on the display by the symbol and can be released again either via the display or by communication. Hardware lock: The instrument is locked by pressing the O and S and F keys at the same time. The lock is shown on the display by the symbol and can only be unlocked again via the display by pressing the O and S and F keys at the same time again. It is not possible to unlock the hardware by communication. All parameters can de displayed even if the instrument is locked. ⇒ ⇓ O and S and F press simultaneous ⇓ The LOCK_SYMBOL appears on the LCD. 38 Endress+Hauser Micropilot S FMR 530 5 Operation 5.3.2 Unlocking of configuration mode If an attempt is made to change parameters when the instrument is locked, the user is automatically requested to unlock the instrument: "unlock parameter" (0A4): By entering the unlock parameter (on the display or via communication) 100 = for HART devices the Micropilot is released for operation. Hardware lock: After pressing the O and S and F keys at the same time, the user is asked to enter the unlock parameter 100 = for HART devices. ⇒ O and S and F press simultaneous ⇓ Please enter unlock code and confirm with F. ⇓ " Endress+Hauser Caution! Changing certain parameters such as all sensor characteristics, for example, influences numerous functions of the entire measuring system, particularly measuring accuracy. There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the E+H service organization. Please contact Endress+Hauser if you have any questions. 39 5 Operation Micropilot S FMR 530 5.3.3 " Factory settings (Reset) Caution! A reset sets the instrument back to the factory settings. This can lead to an impairment of the measurement. Generally, you should perform a basic setup again following a reset. A reset is only necessary: • if the instrument no longer functions • if the instrument must be moved from one measuring point to another • if the instrument is being de-installed /put into storage/installed ⇒ User input ("reset" (0A3)): • 333 = customer parameters • 555 = History 333 = reset customer parameters This reset is recommended whenever an instrument with an unknown 'history' is to be used in an application: • The Micropilot is reset to the default values. • The customer specific tank map is not deleted. • A linearisation is switched to "linear" although the table values are retained. The table can be reactivated in the "linearisation" (04) function group. List of functions that are affected by a reset: • tank shape (002) • empty calibr. (005) • full calibr. (006) • pipe diameter (007) • output on alarm (010) • output on alarm (011) • outp. echo loss (012) • ramp %span/min (013) • delay time (014) • safety distance (015) • in safety dist. (016) • Tank Gauging (030) • Autokorrektur (031) • level/ullage (040) • • • • • • • • • • • • • • linearisation (041) customer unit (042) diameter vessel (047) range of mapping (052) pres. Map dist (054) offset (057) low output limit (062) fixed current (063) fixed cur. value (064) simulation (065) simulation value (066) format display (094) distance unit (0C5) download mode (0C8) 555 = History Reset After mounting and aligning the equipment, carry out a history reset before switching on the function "auto correction" (031) (see page 56). The tank map can also be reset in the "cust. tank map" (055) function of the "extended calibr." (05) function group. This reset is recommended whenever an instrument with an unknown 'history' is to be used in an application or if a faulty mapping was started: • The tank map is deleted. The mapping must be recommenced. 40 Endress+Hauser Micropilot S FMR 530 5 Operation 5.4 Display and acknowledging error messages Type of error Errors that occur during commissioning or measuring are displayed immediately on the local display. If two or more system or process errors occur, the error with the highest priority is the one shown on the display. The measuring system distinguishes between two types of error: • A (Alarm): Instrument goes into a defined state (e.g. MAX 22 mA) Indicated by a constant symbol. (For a description of the codes, see Table 9.2 on Page 77) • W (Warning): Instrument continue measuring, error message is displayed. Indicated by a flashing symbol. (For a description of the codes, see Table 9.2 on Page 77) • E (Alarm / Warning): Configurable (e.g. loss of echo, level within the safety distance) Indicated by a constant/flashing symbol. (For a description of the codes, see Table 9.2 on Page 77) ⇒ Error messages Error messages appear as four lines of plain text on the display. In addition, a unique error code is also output. A description of the error codes is given on Page 77. • The "diagnostics (0A)" function group can display current errors as well as the last errors that occurred. • If several current errors occur, use O or S to page through the error messages. • The last occurring error can be deleted in the "diagnostics (0A)" function group with the funktion"clear last error" (0A2). Endress+Hauser 41 5 Operation Micropilot S FMR 530 5.5 HART communication Apart from local operation, you can also parameterise the measuring instrument and view measured values by means of a HART protocol. There are two options available for operation: • Operation via the universal handheld operating unit, the HART Communicator DXR 375. • Operation via the Personal Computer (PC) using the operating program (e.g. ToF Tool or Commuwin II) (For connections, see Page 31 ff.). • Operation via the Tank Side Monitor NRF590. 5.5.1 Handheld unit DXR 375 All device functions can be adjusted via menu operation with the handheld unit DXR 375. dsdmdm df das. asdas fa asas la. dsdmdm df das. asdas fa asas la. FMR531: LIC0001 ONLINE 1 GROUP SELECT 2 PV 1 GROUP SELECTION 2 PV Delete 8.7 m SAVE H 9 Page Up Bksp 6 ABC Bksp 2 3 Paste Hot Key JKL MNO PQRS 1 2 3 4 5 CALIBRATION LINEARISATION EXT. CALIBRATION SERVICE OPERATING MODE Delete DEF 1 Copy GHI 4 dsdmdm df das. asdas fa asas la. FMR531: LIC0001 GROUP SELECTION SAVE Delete Page On #%& HELP 5 6 Insert + Hot Key TUV W XY Z 7 8 9 ,()‘ _<> +*/ . 0 - H SAVE HOME Bksp FMR531: LIC0001 CALIBRATION 1 2 3 4 5 MEASURED VALUE EMPTY CALIBRATION FULL CALIBRATION APPLICATION PARAMETER OUTPUT DAMPING 375 FIELD COMMUNICATOR SAVE Fig. 7 ! HOME dsdmdm df das. asdas fa asas la. Page Up Page On L00-FMR53xxx-07-00-00-xx-001 HELP 8.7 m FMR531: LIC0001 ONLINE Menu operation with the DXR 375 handheld instrument Note! • Further information on the HART handheld unit is given in the respective operating manual included in the transport bag of the instrument. 5.5.2 ToF Tool operating program The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle. It is used to support commissioning, securing of data, signal analysis and documentation of the instruments. It is compatible with the following operating systems: Win95, Win98, WinNT4.0, Win2000 and Windows XP. The ToF Tool supports the following functions: • Online configuration of transmitters • Signal analysis via envelope curve • Loading and saving of instrument data (Upload/Download) • Documentation of measuring point ! 42 Note! Further information you may find on the CD-ROM, which is enclosed to the instrument. Endress+Hauser Micropilot S FMR 530 5 Operation Menu-guided commissioning Signal analysis via envelope curve Connection options: • Service-interface with adapter FXA 193 (see Page 31) • HART with Commubox FXA 191 (see Page 31) Endress+Hauser 43 5 Operation Micropilot S FMR 530 5.5.3 Commuwin II-Operating Programm Commuwin II is an operating software with graphical support for intelligent transmitters with the communication protocols Rackbus, Rackbus RS 485, INTENSOR, HART or PROFIBUS-PA. It is compatible with the operating systems Win 3.1/3.11, Win95, Win98 and WinNT4.0. All functions of Commuwin II are supported. The configuration is made via operating matrix or graphic surface. A envelope curve can be displayed in ToF Tool. ! Note! Further information on Commuwin II is given in the following E+H documentation: • System Information: SI 018F/00/en “Commuwin II” • Operating Manual: BA 124F/00/en “Commuwin II” operating program Connection The table provides an overview of the Commuwin connections. ! 44 Interface Hardware Server Device list HART Commubox FXA 191 to HART Computer with RS-232C interface HART Connected instrument Interface FXN 672 Gateway for MODBUS, PROFIBUS, FIP, INTERBUS, etc. Computer with RS-232C interface or PROFIBUS card ZA 673 for PROFIBUS ZA 672 for other List of all rack bus modules: the required FXN 672 must be selected Note! The Micropilot S can also be operated locally using the keys. If operation is prevented by the keys being locked locally, parameter entry via communication is not possible either. Endress+Hauser Micropilot S FMR 530 6 Commissioning 6 Commissioning 6.1 Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist “Post installation check” (see Page 27 ff.). • Checklist “Post connection check” (see Page 32 ff.). 6.2 Commissioning 6.2.1 Switching on the measuring device When the instrument is switched on for the first time, the following messages appear on the display: ⇒ ⇓ After 5 s, the following message appears ⇓ After 5 s or after you have pressed F the following message appears Select the language (this message appears the first time the instrument is switched on) ⇓ Select the basic unit (this message appears the first time the instrument is switched on) ⇓ ⇒ ⇓ The current measured value is displayed After F is pressed, you reach the group selection. This selection enables you to perform the basic setup Endress+Hauser 45 6 Commissioning Micropilot S FMR 530 6.3 Basic Setup Commissioning flange: reference point of measurement BD measuring cond. basic setup (standard) SD D measuring cond. E F empty calibr. L full calibr. pipe diameter (for bypass/stilling well) E = empty calibr. (= zero) settings in 005 D = distance (distance flange / product) display in 0A5 SD = safety settings settings in 015 mounting calibr. mapping F = full calibr. (= span) settings in 006 L = level display in 0A6 BD = blocking dist. settings in 059 first point corrects offset further points correct linearity safety settings ... 46 L00-FMR530xx-19-00-00-en-001 extended calibr. (description see BA 217F) option linearisation Endress+Hauser Micropilot S FMR 530 6 Commissioning To successfully commission a precise measurement to the nearest mm, it is important you carry out a history reset on first installation after mechanical installation and after the basic setup of the device (see Page 55). Only after a history reset the mounting calibration is carried out. Enter the measurement offset as the first point in the dip table for the mounting calibration. When a value is dipped at a later date, make a second entry into the dip table, again using the semi-automatic mode. This way, you can easily carry out a linearisation of the measurement. When configuring the function in "basic setup" (00) please take into account the following notes: • Select the functions as described on Page 33. • Some functions can only be used depending on the parameterisation of the instrument. For example, the pipe diameter of a stilling well can only be entered if "stilling well" was selected beforehand in the "tank shape" (002) function. • Certain functions (e.g. starting an interference echo mapping (053)) prompt you to confirm your data entries. Press O or S to select "YES" and press F to confirm. The function is now started. • If you do not press a key during a configurable time period (→ function group "display (09)"), an automatic return is made to the home position (measured value display). Endress+Hauser ! Note! • The instrument continues to measure while data entry is in progress, i.e. the current measured values are output via the signal outputs in the normal way. • If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimised. • If the power supply fails, all preset and parameterised values remain safely stored in the EEPROM. " Caution! All functions are described in detail, as is the overview of the operating menu itself, in the manual “Description of the instrument functions – BA 217F”, which is a separate part of this operating manual. 47 6 Commissioning Micropilot S FMR 530 6.4 Basic Setup with the VU 331 Function "measured value" (000) ⇒ This function displays the current measured value in the selected unit (see "customer unit" (042) function). The number of digits after decimal point can be selected in the "no.of decimals" (095) function. The length of the bargraph corresponds to the percental value of the present measured value with regard to the span. " Caution! When using an FAR 10 antenna extension, carry out an offset correction before the basic setup. Enter the value into the funktion "offset" (057) (see Page 65 ff.). 6.4.1 Function group "basic setup" (00) ⇒ Function "tank shape" (002) ⇒ This function is used to select the tank shape. L00-FMR230xx-14-00-00-en-007 Selection: • dome ceiling • horizontal cyl • bypass • stilling well • flat ceiling (Typical ceiling of storage tanks: a slight slope of only a few degrees can be neglected.) • sphere 48 Endress+Hauser Micropilot S FMR 530 6 Commissioning Function "medium property" (003) ⇒ This function is used to select the dielectric constant. Selection: • unknown • < 1.9 • 1.9 ... 4 • 4 ... 10 • > 10 Product class DK (εr) A 1,4 … 1,9 B 1,9 … 4 non-conducting liquids, e.g. benzene, oil, toluene, … C 4 … 10 e.g. concentrated acids, organic solvents, esters, aniline, alcohol, acetone, … D > 10 conducting liquids, e.g. aqueous solutions, dilute acids and alkalis Examples non-conducting liquids, e.g. liquefied gas 4) 3) Treat Ammonia NH3 as a medium of group A, i.e. always use a stilling well. Endress+Hauser 49 6 Commissioning Micropilot S FMR 530 Function "process cond." (004) ⇒ This function is used to select the process conditions. Selection: • standard • calm surface • turb. surface • agitator • fast change • test:no filter standard ! 50 calm surface For all applications that do not fit into any of the following groups. Storage tanks with immersion tube or bottom filling The filter and output damping are set to average values. The averaging filters and output damping are set to high values. -> steady meas. value -> precise measurement -> slower reaction time Note! The phase evaluation of the Micropilot S (see »Function "auto correction" (031)« on page 56) is only activated if you select the measuring conditions "standard" or "calm surface". We strongly recommend that, in the case of rough product surfaces or rapid filling, you activate the appropriate application parameters. Endress+Hauser Micropilot S FMR 530 6 Commissioning Function "empty calibr." (005) ⇒ L00-FMR2xxxx-14-00-06-en-008 This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero). " Caution! For dish bottoms or conical outlets, the zero point should be no lower than the point at which the radar beam hits the bottom of the tank. Function "full calibr." (006) ⇒ L00-FMR2xxxx-14-00-06-en-009 This function is used to enter the distance from the minimum level to the maximum level (=span). In principle, it is possible to measure up to the tip of the antenna. However, due to considerations regarding corrosion and build-up, the end of the measuring range should not be chosen any closer than 50 mm (2”) to the tip of the antenna. Endress+Hauser 51 6 Commissioning Micropilot S FMR 530 ! Note! If bypass or stilling well was selected in the "tank shape" (002) function, the pipe diameter is requested in the following step. Function "pipe diameter" (007) ⇒ L00-FMR230xx-14-00-00-xx-011 This function is used to enter the pipe diameter of the stilling well or bypass pipe. Microwaves propagate slower in pipes than in free space. This effect depends on the inside diameter of the pipe and is automatically taken into account by the Micropilot. It is only necessary to enter the pipe diameter for applications in a bypass or stilling well. Function "dist./ meas. value (008)" ⇒ The distance measured from the reference point to the product surface and the level calculated with the aid of the empty adjustment are displayed. Check whether the values correspond to the actual level or the actual distance. The following cases can occur: • Distance correct – level correct -> continue with the next function, "check distance" (051) • Distance correct – level incorrect -> Check "empty calibr." (005) • Distance incorrect – level incorrect -> continue with the next function, "check distance" (051) 52 Endress+Hauser Micropilot S FMR 530 6 Commissioning Function "check distance" (051) ⇒ L00-FMR2xxxx-14-00-06-en-010 This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available for selection: Selection: • distance = ok • dist. too small • dist. too big • dist. unknown • manual distance = ok • mapping is carried out up to the currently measured echo • The range to be suppressed is suggested in the "range of mapping (052)" function Anyway, it is wise to carry out a mapping even in this case. dist. too small • At the moment, an interference is being evaluated • Therefore, a mapping is carried out including the presently measured echoes • The range to be suppressed is suggested in the "range of mapping (052)" function dist. too big • This error cannot be remedied by interference echo mapping • Check the application parameters (002), (003), (004) and "empty calibr." (005) dist. unknown If the actual distance is not known, no mapping can be carried out. manual A mapping is also possible by manual entry of the range to be suppressed. This entry is made in the "range of mapping (052)" function. " Endress+Hauser Caution! The range of mapping must end 0.5 m (20") before the echo of the actual level. For an empty tank, do not enter E, but E – 0.5 m (20"). 53 6 Commissioning Micropilot S FMR 530 Function "range of mapping" (052) ⇒ This function displays the suggested range of mapping. The reference point is always the reference point of the measurement (see Page 46 ff.). This value can be edited by the operator. For manual mapping, the default value is: 0 m. Function "start mapping" (053) ⇒ This function is used to start the interference echo mapping up to the distance given in "range of mapping" (052). Selection: • off: no mapping is carried out • on: mapping is started 54 Endress+Hauser Micropilot S FMR 530 6 Commissioning Display "dist./meas.value (008)" ⇒ The distance measured from the reference point to the product surface and the level calculated with the aid of the empty alignment are displayed again. Check whether the values correspond to the actual level or the actual distance. The following cases can occur: • Distance correct – level correct -> basic setup completed • Distance incorrect – level incorrect -> a further interference echo mapping must be carried out "check distance" (051). • Distance correct – level incorrect -> check "empty calibr." (005) Function "history reset" (009) ⇒ By this function a history reset of the device is performed, i.e. the correspondance table between level an index values is deleted. A new correspondance table will be filled and stored after the history reset, cf. Page 56. " Caution! Perform only after first installation (see »Function "auto correction" (031)« on page 56). In this case also effect a reset of the dip table in function "dip table mode" (033). ⇒ ⇓ ! Endress+Hauser After 3 s, the following message appears Note! After basic calibration, it is wise to evaluate the measurement using the envelope curve (function group "display" (09)). 55 6 Commissioning Micropilot S FMR 530 6.5 Mounting calibration with VU 331 6.5.1 Function group "mounting calibr." (03) ⇒ Function "tank gauging" (030) ⇒ Using this function, you can either enter a dip table or carry out an auto-correction. Function "auto correction" (031) ⇒ When measuring levels with radar systems, so-called "multipath reflections" can affect the level signal giving rise to serious measuring errors. "Multipath reflections" also include radar beams which are received by the radar system, which have not been reflected directly by the medium surface. They may reach the antenna via the basin wall and the medium surface. This phenomenon is particularly noticeable with devices mounted near to walls, as soon as the conical radar beam strikes the basin wall. The Micropilot S can automatically discover and correct measuring errors due to this "multiple path" propagation. This is because it uses two independent sets of information when evaluating reflection signals: • Firstly, it evaluates the amplitude of the reflected energy using the so-called envelope curve system. • Secondly, it evaluates the phase of the reflected energy. The decisive factor for a constant output signal is to assign the phase values to the associated level values. This assignment is ensured using a correspondence table (index correction table). The Micropilot S learns this for the specific application after installation (learning period). Therefore, after mounting the device, and after completing the basic calibration, a history reset must be performed (enter "yes" in the "history reset" (009) function in the "basic setup " (00) function group). Do not switch off the radar system during filling and emptying operations during the teach-in phase. Switching off when there are only negligible level changes produces no error. 56 Endress+Hauser Micropilot S FMR 530 6 Commissioning " Caution! During the learning period, fast filling/emptying or turbulent surfaces can result in switching off and on the phase evaluation. Subsequently observed measurement errors will disappear as soon as tank levels come back to areas measured by Micropilot S previously with activated phase evaluation. If the observed measurement errors are correted by dip table entries, the Micropilot S will take care of these corrections and automatically adjust the index correction table. Do NOT correct any settings in the basic calibration or the extended calibration. ! Note! Immediately after installation, the Micropilot S measures with the specified mmaccuracy. Until the level range has been completely covered by the medium (setting up the correction table), the maximum permissible filling speed is 100 mm level change / min. After this, the fill speed has no limitation. Function"pipe diam. corr." (032) (only relevant for FMR 532) ⇒ For level measurement in stilling wells, radar systems require highly precise pipe inner diameter data. An mm-exact level measurement cannot be guaranteed for deviations from the actual stilling well inner diameter of more than ± 0.1mm to the value entered in the function group "basic setup" (00). The errors which occur as a result are linear and can be corrected with a dip table containing at least two entries. The Micropilot S FMR 53x also has an automatic pipe inner diameter correction. This adjusts the entered stilling well inner diameter (input in the function group "basic setup" (00)) to the actual values. However, this presupposes that the value entered in the function group "basic setup" (00) matches the actual pipe inner diameter accurately as possible. The user-defined value entered in the function group "basic setup" (00) can be corrected with this value. In order to do this, switch on the "pipe diam. corr." (032) function, after a level change of at least 5 m has occured since start-up. The pipe diameter, which the instrument determines automatically, will then be transmitted to the "pipe diameter" (007) function. ! Endress+Hauser Note! Only if the "pipe diameter" (007) function has changed its value, it is necessary to perform a "history reset" (009) and to delete the dip table after activation of the "pipe diam. corr." (032) function. Otherwise the level change of 5 m has not yet been exceeded. The "pipe diam. corr." (032) function must be deactivated again and the procedure should be repeated at a later point of time. 57 6 Commissioning Micropilot S FMR 530 Display "custody mode" (0A9) ⇒ This indicates the instrument calibration mode. The calibration mode (active) can be set using the hardware security lock on the electronics (see Page 35). Selection: • inactive • active pos. • active neg. active pos. The custody mode (instrument is lead-sealed and accurate to the nearest mm) is active and is held. active neg. Custody mode (instrument is lead-sealed and accurate to the nearest mm) is activated and not held, e.g. because the signal-to-noise ratio is less than 10 dB (refer to function "echo quality" (056) in the function group "extended calibr." (05)). " 58 Caution! After entering all the values and completing mounting and aligning work, enter the Reset Code "555" in the function "reset" (0A3) to reset the instrument history for autocorrection. Endress+Hauser Micropilot S FMR 530 6 Commissioning Dip table The dip table is used to correct the level readings of the Micropilot S using independently taken hand dips. The dip table is used in particular to adapt the level gauge to the specific application conditions as mechanical offset and tank/stilling well design. Depending on national regulations, national inspectors will dip the tank at one to three levels during a calibration run and check the level readings. Only one value pair must be entered into the dip table to correct the measurement offset. If a second value pair is entered into the dip table, the Micropilot S accepts the corrected measured values identically for both value pairs. All other measured values are determined by linear extrapolation. If you enter more than two value pairs, the system carries out a linear interpolation between adjacent value pairs. Outside these value pairs, extrapolation is also linear. basic setup history reset dip table alternatives Fig. 8 hand dip and immediate offset correction in semi-automatic mode collect hand dip and measurement data over full measurement range collect further hand dip data; if deviation from measurements > 4 mm and level change > 2 m: enter a new dip value into dip table using the semi-automatic mode evaluate collected data; enter characteristic value pairs into the dip table using the manual mode L00-FMR53xxx-19-00-00-en-014 preferred choice: Alternative procedures to fill the dip table. To collect and enter data into the dip table, two alternative procedures may be carried out. In order not to mix up measurement values corrected by the offset or linearisation of the dip table with uncorrected measurement values, it is recommended to use the semi-automatic mode of the dip table to enter new data pairs. In this case, the first dip value should be entered immediately after the basic calibration. Further linearization points should be entered only after a level change of at least 2 m (cf. Fig. 8, preferred choice) and a deviation between the "uncorrected measurement value" and the hand dip value of at least 4mm. If this procedure can not be followed, then NO value pair should be entered into the dip table after basic calibration. Measurement data and hand dip values should be collected over the full measurement range and be evaluated with regard to a good linear fit. Only then characteristic value pairs should be entered into the dip table using the "manual mode" (cf. Fig. 8, right side). If further linearisation is needed, further hand dip values should be entered using only the "semi-automatic mode". Endress+Hauser 59 6 Commissioning Micropilot S FMR 530 ! Note! The offset should NOT be determined and entered within the close range of the antenna (conf. definition of the safety distance) or immediately in the range of the tank bottom, because within these ranges interferences of the radar signal may occur. ! Note! The dip table can be printed out using the ToF-Tool. Before doing this, the ToF Tool must be reconnected to the instrument in order to update the values within the ToF Tool. ! Note! Make your inputs into the dip table in semi-automatic mode. We advise you to leave "auto correction" (031) activated ("on") while you enter your inputs. " Caution! After entering one or more points into the dip table, make sure that the dip table is activated and left in the "table on" dip table mode. Function "dip table state" (037) ⇒ This function displays the dip table status. Display: • table on • table off table on Indicates whether the dip table is active. table off Indicates whether the dip table is not active. Function "dip table mode" (033) ⇒ The dip table can be switched on or off using this function. Selection: • manual • semi-automatic • table on • table off • clear table • view 60 Endress+Hauser Micropilot S FMR 530 6 Commissioning manual The value pairs in the dip table can be read and written. You can enter the measured value and the dip value. – uncorrected measured value: This is the measured value supplied by the instrument, NOT corrected by the dip table. The choice of measured value, level or remaining fill height is dependent on the instrument setting. – Dip value: This is the level or distance to flange respectively, given by the hand dip. This value should be used to correct the measured value. The "manual mode" of the dip table can be used to enter collected data after a series of data pairs taken at different tank levels. ! Note! The bigger the distance between the different levels while taking hand dips, the more accurate the linearisation of the dip table will be. semi-automatic The value pairs in the dip table can be read. You can enter the dip value only. When there are new value pairs, the current level or distance is accepted as the measured value. table on The dip table is switched on. table off The dip table is switched off. clear table The complete dip table is deleted. The table is switched off. The number of free table entries is set to the maximum value (= 32). View The value pairs in the dip table can only be read. You can still select this menu option, even if there is no dip table available. In this case, the number of free table entries is at maximum value (= 32). Function "dip table" (034) ⇒ This function edits measured variable. The number behind the entry "remain" indicates the current number of remaining free value pairs. The maximum number of value pairs is 32; after each entry, the remaining number is decremented. " Note! The uncorrected measured value is displayed in the "dip table" (034) function. This may differ considerably from the measured values when a dip table is activated. Function "dip table" (035) ⇒ This function edits the dip value. Endress+Hauser 61 6 Commissioning Micropilot S FMR 530 Function "dip table handl." (036) ⇒ Use this function to enter the dip value (level or distance) which will correct the measurement values. Selection: • new point • edit point • store point • delete point • return • next point • previous point General procedure: To enter a new point into the dip table, use "new point" to enter the value (pairs), "store point" to sort the new value (pairs), "return" to go to the dip table mode and "table on" to activate the dip table. new point You can enter a new point. A suggested value is displayed for the measured variable, the dip value of the current level or distanz. With semi-automatic inputs, the current level or the current remaining fill height is displayed as proposed dip value. The new value pair can be altered without selecting the "edit point" parameter. If the table is full, you can still select this parameter. In this case, the number of free table entries stands at minimum value (= 0). edit point The displayed value pair can be changed. Only the dip value can be changed with semi-automatic input mode. " Caution! To accept the value pair in the table, confirm it with "store point". store point The displayed value pair is sorted in the table. ! " Note! For sorting, the following criteria must be met: • Measured variables may not be equal but have different dip values. • A measured variable available in the table is recognised as equal when it is closer than 1 mm to the sorting value. • After successful sorting, the setting remains at "edit point" and the number of free table entries is decremented. Caution! If the value cannot be sorted, the setting remains at the previous menu option. No warning or error message is generated. However, the number of remaining table entries is not decremented. delete point The currently displayed point is deleted from the table. After deletion, the previous point is displayed. If the table only consisted of one point before deletion, then the current measured variable is displayed as a value pair. 62 Endress+Hauser Micropilot S FMR 530 6 Commissioning return By selecting this point, you return to the function "dip table mode" (033). next point This scrolls down in the table. If the table is empty, you can still select this option. However, the displayed value does not change. previous point This scrolls up in the table. If the table is empty, you can still select this option. However, the displayed value does not change. " Endress+Hauser Caution! After entering one or more points into the dip table, make sure that the dip table is activated in the "table on" dip table mode. 63 6 Commissioning Micropilot S FMR 530 6.5.2 Envelope curve with VU 331 After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("display" (09) function group) is recommended. Function "plot settings" (09A) ⇒ L00-FMRxxxxx-07-00-00-en-004 Here you can select which information is shown on the display: • envelope curve • env. curve+FAC (for FAC see BA 217F) • env. curve+cust.map (i.e. the tank map is also displayed) Function "recording curve" (09B) This function determines whether the envelope curve is read as: • single curve or • cyclic ⇒ 64 ! Note! If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimised. ! Note! If the level of echo is very weak or there is a heavy interference echo, an orientation of the Micropilot can contribute to an optimisation of the measurement (increase of the level echo/reduction of the interference echo) (see »Orientation of the Micropilot«). Endress+Hauser Micropilot S FMR 530 6 Commissioning 6.5.3 Antenna extension If an FAR10 antenna extension is used, an offset correction must be carried out before the basic setup. The value is entered in the "offset" (057) function. It depends on the length of the antenna extension and is calculated as follows: offset (m) = 0.395 * length of the FAR 10 in m For the standard lengths of the FAR10, this results in: Length of the FAR 10 Correction value [m] Endress+Hauser 100 mm (4") 200 mm (8") 300 mm (12") 400 mm (16") 0.0395 0.0790 0.1185 0.1580 65 6 Commissioning Micropilot S FMR 530 6.6 Basic Setup with the ToF Tool To carry out the basic setup with the ToF Tool operating program, proceed as follows: • Start the ToF Tool operating program and establish a connection • Select the "basic setup" function group in the navigation bar " Caution! If an FAR 10 antenna extension is used, carry out an offset correction before the basic setup (see Page 65). The following display appears on the screen: Basic Setup step 1/5: • Status image • Enter the measuring point description (TAG number). Change to the next page ! 66 Note! • Each parameter that is changed must be confirmed with the RETURN key! • The "Next" button moves you to the next screen display: Endress+Hauser Micropilot S FMR 530 6 Commissioning Basic Setup step 2/5: • Enter the application parameters: – tank shape (for a description, see Page 48) – medium property (for a description, see Page 49) – process cond. (for a description, see Page 50) Basic Setup step 3/5: If "dome ceiling" is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. (for a description, see Page 51) • full calibr.(for a description, see Page 51) Endress+Hauser 67 6 Commissioning Micropilot S FMR 530 If "horizontal cyl" or "sphere" is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. (for a description, see Page 51) • full calibr. (for a description, see Page 51) If "stilling well" or "bypass" is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. (for a description, see Page 51) • full calibr. (for a description, see Page 51) • Diameter of bypass / stilling well (for a description, see Page 52) ! 68 Note! You can also specify the pipe diameter in this display. Endress+Hauser Micropilot S FMR 530 6 Commissioning If "flat ceiling" is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. (for a description, see Page 51) • full calibr. (for a description, see Page 51) Basic Setup step 4/5: • This step starts the tank mapping • The measured distance and the current measured value are always displayed in the header • A description is given on see Page 55 measured value distance Step 5/5: After the first installation of the device, initialise the index correction table (compare Page 56) by activating the history reset 555. Endress+Hauser 69 6 Commissioning Micropilot S FMR 530 6.6.1 Envelope curve with the ToF Tool After the basic setup, an evaluation of the measurement using the envelope curve is recommended. ! Note! If the level of echo is very weak or there is a heavy interference echo, an orientation of the Micropilot can help optimise the measurement (increase of the useful echo/ reduction of the interference echo) (see »Quick installation guide«). 6.6.2 User-specific applications (operation) For details of setting the parameters of user-specific applications, see separate documentation BA 217F/00/en - description of the instrument functions of the Micropilot S. 70 Endress+Hauser Micropilot S FMR 530 6 Commissioning 6.7 Mounting calibration with the ToF Tool To carry out the basic setup with the ToF Tool operating program, proceed as follows: • Start the ToF Tool operating program and establish a connection • Select the "mounting calibr." function group in the navigation bar The following display appears on the screen: Mounting calibration step 1/2: • auto correction (description see Page 56) • pipe diam. corr. (description see Page 57) change to next page ! Endress+Hauser Note! • Each parameter that is changed must be confirmed with the RETURN key! • the "Next" button moves you to the next screen display: 71 6 Commissioning Micropilot S FMR 530 Mounting calibration step 2/2: • dip table mode (description see Page 60) • meas. v. (description see Page 61) • dip value (see Page 61) • dip table handl. (description see Page 62) • dip table state (description see Page 60) • left dip t.entr. (description see Page 60) 72 Endress+Hauser Micropilot S FMR 530 7 Maintenance 7 Maintenance The Micropilot S measuring instrument requires no special maintenance. Exterior cleaning When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing and the seals. Replacement After a complete Micropilot or electronic module has been replaced, the parameters can be downloaded into the instrument again via the communication interface. Prerequisite to this is that the data were uploaded to the PC beforehand using the ToF Tool / Commuwin II. Measurement can continue without having to carry out a new setup. • You may have to activate linearisation (see BA 217F) • You may need to record the tank map again (siehe Grundabgleich) After an antenna component has been replaced, a new calibration must be carried out. Endress+Hauser 73 8 Accessories Micropilot S FMR 530 8 Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Micropilot S. L00-FMR53xxx-00-00-06-en-001 Weather protection cover A Weather protection cover made of stainless steel is available for outdoor mounting (order code: 543199-0001). The shipment includes the protective cover and tension clamp. L00-FMRxxxxx-06-00-00-en-002 Antenna extension FAR 10 (for FMR 530) Dimensions: Ordering information: 10 80 FAR 10- 74 Material 2 1.4571 4 2.4600/Hastelloy B3 5 2.4610/Hastelloy C4 6 316L 9 Special material Overall length L1 A 100 mm / 4" B 200 mm / 8" C 300 mm / 12" D 400 mm / 16" Y Special length Additional weight 0.3 kg 0.5 kg 0.7 kg 1.0 kg Complete product designation Endress+Hauser Micropilot S FMR 530 8 Accessories Commubox FXA 191 HART For intrinsically safe communication with ToF Tool or Commuwin II via the RS 232Cinterface. Service adapter FXA 193 For communication with ToF Tool via the display connector. (Bestell-Nr.: 50095566). Commuwin II Operating software for intelligent instruments. Endress+Hauser 75 9 Trouble-shooting Micropilot S FMR 530 Trouble-shooting 9.1 Trouble-shooting instructions L00-FMR53xxx-19-00-00-en-010 9 76 Endress+Hauser Micropilot S FMR 530 9 Trouble-shooting 9.2 Code Description Possible cause Remedy A102 checksum error general reset & new calibr.required device has been powered off before data could be stored; emc problem; E²PROM defect reset; avoid emc problem; if alarm prevails after reset, exchange electronics W103 initialising - please wait E²PROM storage not yet finished wait some seconds; if warning prevails, exchange electronics A106 downloading please wait processing data download wait until warning disappears A110 checksum error general reset & new calibr.required device has been powered off before data could be stored; emc problem; E²PROM defect reset; avoid emc problem; if alarm prevails after reset, exchange electronics A111 electronics defect RAM defective reset; if alarm prevails after reset, exchange electronics A113 electronics defect ROM defective reset; if alarm prevails after reset, exchange electronics A114 electronics defect E2PROM defective reset; if alarm prevails after reset, exchange electronics A115 electronics defect general hardware problem reset; if alarm prevails after reset, exchange electronics A116 download error repeat download checksum of stored data not correct restart download of data A121 electronics defect no factory calibration existant; E²PROM defective contact service W153 initialising - please wait initialisation of electronics wait some seconds; if warning prevails, power off device and power on again A155 electronics defect hardware problem reset; if alarm prevails after reset, exchange electronics A160 checksum error general reset & new calibr.required device has been powered off before data could be stored; emc problem; E²PROM defect reset; avoid emc problem; if alarm prevails after reset, exchange electronics A164 electronics defect hardware problem reset; if alarm prevails after reset, exchange electronics A171 electronics defect hardware problem reset; if alarm prevails after reset, exchange electronics A231 sensor 1 defect check connection HF module or electronics defective exchange HF module or electronics Tab. 3 Endress+Hauser System error messages System error messages 77 9 Trouble-shooting Micropilot S FMR 530 Code Description Possible cause Remedy A270 custody switch undef check position switch for custody transfer may be defective check position of custody switch exchange electronics inconsistency between phase and amplitude evaluation inconsistent microfactor inconsistent index mapping check basic calibration check mounting calibration check echo quality reset history "555" check stilling pipe diameter switch off autocorrection # A272 electrinics defect amplifier inconsistency in amplification exchange electronics W275 electronics defect factory setting ofset drift of A/D commuter exchange electronics W511 no factory calibration ch1 factory calibration has been deleted record new factory calibration A512 recording of mapping please wait mapping active wait some seconds until alarm disappears W601 linearisation ch1 curve not monotone linearization not monotonously increasing correct linearisation table W611 less than 2 linearisation points for channel 1 number of entered linearization points < 2 correct linearisation table W621 simulation ch. 1 on simulation mode is active switch off simulation mode E641 no usable echo channel 1 check calibr. echo lost due to application conditions of built up on antenna check installation; optimize orientation of antenna; clean antenna (cf. BA) E651 level in safety distance - risk of overspill level in safety distance alarm will disappear as soon as level leaves safety distance; A671 linearisation ch1 not complete, not usable linearisation table is in edit mode activate linearisation table W681 current ch1 out of range current out of range (3,8 mA ... 21,5 mA) check calibration and linearisation Tab. 3 78 System error messages Endress+Hauser Micropilot S FMR 530 9 Trouble-shooting 9.3 Application errors Error Output Possible cause Remedy A warning or alarm has occurred. Depending on the configuration See table of error messages (see page 77) 1. See table of error messages (see page 77) Measured distance (008) OK? D m/ft (008) Measured value (00) is incorrect F m/ft yes → 1. Check empty calibr. (005) and full calibr. (006). 2. Check linearisation: → level/ullage (040) → max. scale (046) → diameter vessel (047) → Check table 20 mA/100% expected no ↓ actual E m/ft t→ 4 mA/0% Measurement in bypass or stilling well? yes → 1. Is bypass or stilling well selected in tank shape (002)? 2. Is the pipe diameter (007) correct? no ↓ Is an FAR 10 antenna extension being used? no ↓ An interference echo may have been evaluated. No change off measured value on filling/emptying Interference echo from installations, nozzle or extension on the antenna 20 mA/100% yes → 1. offset (057) correctly set? yes → 1. Carry out tank mapping → basic setup 1. Carry out tank mapping → basic setup 2. If necessary, clean antenna 3. If necessary, select better mounting position actual expected 4 mA/0% Endress+Hauser t→ 79 9 Trouble-shooting Error If the surface is not calm (e.g. filling, emptying, agitator running), the measured value jumps sporadically to a higher level Micropilot S FMR 530 Output 20 mA/100% actual Possible cause Remedy Signal is weakened by the rough surface — the interference echoes are sometimes stronger 1. Carry out tank mapping → basic setup 3. Increase the output damping (058) 4. Optimise the orientation (see Page 81) expected 5. If necessary, select a better mounting position and/or larger antenna t→ 4 mA/0% 2. Set the process cond. (004) to "turb. surface" or "agitator" 20 mA/100% actual expected t→ 4 mA/0% During filling/ emptying the measured value jumps downwards Multiple echoes 20 mA/100% yes → 1. Check the tank shape (002), e.g. "dome ceiling" or "horizontal cyl" 2. In the range of the blocking dist. (059) there is no echo evaluation → Adapt the value actual 3. If possible, do not select central installation position expected 4. Perhaps use a stilling well t→ 4 mA/0% Level echo is too weak. Possible causes: • Rough surface due to filling/ emptying • Agitator running • Foam E 641 (loss of echo) 20 mA/100% actual yes → 1. Check application parameters (002), (003) and (004) 2. Optimise alignment (see Page 81) 3. If necessary, select a better installation position and/or larger antenna E 641 expected 4 mA/0% t→ E 641 (loss of If the instrument is configured to Hold by loss echo) after turn on of echo the output is set to any the power supply value/current. 80 noise level during the initialisation phase to high. Repeat once more empty calibr. (005). Caution! Before conformation change with O or S to the edit mode. Endress+Hauser Micropilot S FMR 530 9 Trouble-shooting 9.4 Orientation of the Micropilot For orientation a marker is found on the flange or threaded boss of the Micropilot. During installation this must be oriented as follows: • In tanks: to the vessel wall • In stilling wells: to the slots • In bypass pipes: vertical to the tank connectors After commissioning the Micropilot, the "echo quality" (056) indicates whether a sufficiently large measuring signal is obtained. If necessary, the quality can be optimised later. Vice versa, the presence of an interference echo can be used to minimise this by optimum orientation. The advantage of this is that the subsequent tank mapping uses a somewhat lower level that causes an increase in the strength of the measuring signal. Proceed as follows: # Warning! Subsequent alignment can lead to personal injury. Before you unscrew or loosen the process connection, make sure that the vessel is not under pressure and does not contain any injurious substances. L00-FMRxxxxx-19-00-00-en-002 1. It is best to empty the container so that the bottom is just covered. However, alignment can be carried out even if the vessel is empty. 2. Optimisation is best carried out with the aid of the envelope graph in the display or the ToF Tool. 3. Unscrew the flange or loosen the threaded boss by a half a turn. 4. Turn the flange by one hole or screw the threaded boss by one eighth of a turn. Note the echo quality. 5. Continue to turn until 360° is reached. 6. Optimum alignment: a) Vessel partly full, no interference echo obtained: L00-FMRxxxxx-19-00-00-en-003 b) Vessel partly full, interference echo obtained: Endress+Hauser 81 9 Trouble-shooting Micropilot S FMR 530 L00-FMRxxxxx-19-00-00-en-004 c) Vessel empty, no interference echo: L00-FMRxxxxx-19-00-00-en-005 d) Vessel empty, interference echo obtained: 7. Fix the flange or threaded boss in this position. If necessary, replace the seal. 8. Carry out tank mapping, siehe Kapitel 6.1 bzw. 6.2. 82 Endress+Hauser Micropilot S FMR 530 9 Trouble-shooting 9.5 Spare parts ! Note! You can order spare parts directly from your E+H service organization by giving the order code and the serial number which is printed on the measuring transducer nameplate (see Page 7 ff.). The corresponding spare part number also appears on each spare part. Installation instructions are given on the instruction card that is also delivered. " Caution! If the calibration seal is broken, the national calibration authority should normally be informed within 24 hours. Spare parts Micropilot S, FMR 530 Housing T12 with separate wiring compartment Housing T12 complete pre-mounted without cover Cablegland/ entry Pg13,5 G½ NPT½ M20 x 1,5 Standard EEx ia The customer may exchange modular assemblies in accordance with Endress+Hauser instructions! 5200 5681 5200 5682 5200 5683 5200 5684 The spare parts listed are generally suitable for use in Ex-devices. Nameplate for regulatory standards inclusive seal, seal-wire and screws NMI 5200 8958 PTB 5200 8959 Cover 518 710 - 0020 Terminal module 5 pin for Housing T12, 5200 5586 Cover plate T12 5200 5643 C O-ring Electronic module, complete with RF-module HART 5200 9431 IP T A >7 0°C 65 : t >8 5°C Made in Germany Me bere asu ic ring h ran ge U1 ma x. 2 4...26...36 0m 0m VD A C Maulburg EN D MIC RES Ord er RO S+H Se Cod PIL AU r.-N e o.: : OT SE FM R Me R ss Operating and display module VU 331 5200 5585 (Cover with sight glass required) Retaining screw Stop screw EN DR ES S+ US HA ER O-ring A O-ring B RF-module For using in Ex zones cable glands of the generation > B must be required! Besides attention the permissible temperature area (> 75° C). Endress+Hauser Insertion cover (pertains to the electronic) Gasket set 5200 5628 consist of: 5 O-ring 49,21 x 3,53 EPDM, Pos. A 5 O-ring 113,9 x 3,53 NBR, Pos. B 5 O-ring 72,0 x 3,0 NBR Pos. C Cover with sight glass 5200 5936 L00-FMR53xxx-00-00-06-en-002 Antenna, see next page! 83 Micropilot S FMR 530 L00-FMR530xx-00-00-06-en-002 9 Trouble-shooting 84 Endress+Hauser Micropilot S FMR 530 9 Trouble-shooting Modification nameplate When ordering parts that are listed in the product structure (see Page 8 ff.) , a check must be made as to whether the instrument description on the nameplate is still valid, e.g. for: • an antenna component, • an electronics module, • an RF module, • a VU 331 operating and display module, • a housing cover with window. Housing T12 The complete order code must be specified when ordering the replacement housing so that the correct nameplate can be delivered, e.g. • FMR 530-A4VCW2AA2A You must label the nameplate yourself. " Caution! • It is not possible to convert a standard instrument into an Ex instrument by simply exchanging parts. • When repairing certified instruments, the relevant regualtions must be followed. • For FM approved instruments, it is forbidden to make any changes to the instrument that are not expressly authorised in the operating manual. Contravening this prohibition can invalidate the approval for operation of the instrument. 9.6 Return If you need to send a Micropilot back to Endress+Hauser for repair, please send a completed copy of the form printed on the last page. • • • • An exact description of the application. The chemical and physical characteristics of the product. A short description of the error that occurred. If necessary, give the error code. Please carry out the measures described in Chapter 1.4 before sending a Micropilot back for repair. 9.7 Disposal In case of disposal please seperate the different components according to their material consistence. Endress+Hauser 85 9 Trouble-shooting Micropilot S FMR 530 9.8 Software history Software version / Date Software changes V 1.00.00 / 12.2000 Original software. Operated via: – ToF Tool – Commuwin II (from version 2.05.03) – HART communicator DXR 375 with Rev. 1, DD 1. V 01.02.00 / 03.2002 simplyfied commissioning history reset in basic calibration Katakana. Operated via: – ToF Tool (V3.0) – Commuwin II (from version 2.05.03) – HART communicator DXR 375 with Rev. 1, DD 1. 9.9 Documentation changes Contact addresses of Endress+Hauser The addresses of Endress+Hauser are given on the back cover of this operating manual. If you have any questions, please do not hesitate to contact your E+H representative. 86 Endress+Hauser Micropilot S FMR 530 10 Technical data 10 Technical data 10.1 Technical data at a glance Application Application The Micropilot S is used for highly accurate level measurement in storage tanks and can be applied in custody transfer applications. It meets the relevant requirements according to OIML R85 and API 3.1B. • The FMR 530 with horn antenna is suitable for free space applications that disallow the use of a parabolic antenna due to tank/nozzle geometry. Function and system design Measuring principle The Micropilot is a "downward-looking" measuring system, operating based on the time-of-flight method. It measures the distance from the reference point (process connection) to the product surface. Radar impulses are emitted by an antenna, reflected off the product surface and received again by the radar system. Equipment architecture The Micropilot S can be used for measurement in a stilling well as well as in free space. The different instrument versions are applied as follows: • The Micropilot S FMR 530 with horn antenna can be used in stilling wells with a diameter <150 mm. However, for these diameters no custody transfer approval is available. • The Micropilot S FMR 533 with parabolic antenna is preferred for freespace measurements. The Micropilot S FMR 530 with horn antenna can be used as an alternative for small nozzle diameters . • The instruments are equipped with a passive 4…20 mA output with HART protocol. Input Endress+Hauser Measured variable The measured variable is the distance between a reference point (mounting flange) and a reflective surface (e.g. medium surface). The measured value and all parameters are displayed using either metrical SI-units or US/UK-units (inch, ft, …). The level is calculated based on the tank height entered. The level can be converted into other units (volume, mass) by means of a linearization. In order to compensate for non-linear effects like movement of the tank roof, an additional correction table (diptable) can be entered. Measuring range see Page 17 ff. 87 10 Technical data Micropilot S FMR 530 Output Output signal 4…20 mA with HART protocol: this version can be operated via the PC operating software ToF Tool and Commuwin II. The instrument supports both point-to-point and multidrop operation. Signal on alarm Error information can be accessed via the following interfaces: • Local display: – Error symbol (see Page 36) – Plain text display – LED’s: red LED continuously on = alarm, red LED flashes = warning • Current output • Digital interface Galvanic isolation 500 V towards ground. 500 V between power supply and signal Auxiliary energy Electrical connection Housing T 12 with separate terminal compartment. Load HART Minimum load for HART communication: 250 Ω Cable entry Cable gland: M20x1.5 or Pg13.5 Cable entry: G ½ or ½ NPT Supply voltage see Page 30 ff. Power consumption Max. 330 mW at 16 V, max. 500 mW at 24 V, max. 600 mW at 30 V. Current consumption Max. 21 mA (50 mA inrush current). Power supply For stand alone operation recommended via e.g. E+H RN 221 N/Z. Performance characteristics 88 Reference operating conditions According to OIML R85: Maximum measured error Absolute accuracy: 0.5 mm (2σ value) Inventory Control Versios: ±3 mm Proof of accuracy for custody transfer versions The accuracy of each Micropilot S is established through a calibration certificate that records the absolute and relative error at 10 equidistant points during the final test. A Laser Interferometer (Jenaer Messtechnik ZLM 500) with an absolute accuracy of 0.1 mm is used as a reference for the free space measurements with FMR 530. Each Micropilot S is delivered with the PTB and NMi type approval. Additional initial factory verifications for custody applications are available on demand for all radar instruments FMR 53x. Maximum fill speed By the first pass trough of measuring range: 100 mm/min., thereafter unlimited. Non-repeatability 0,3 mm (1/64") Hysteresis 0.3 mm • Temperature = –25…+55 °C (-13…+131 °F) • Atmospheric pressure • Relative humidity (air) = 65 % ±15% • Medium properties: e.g. medium with good reflectivity and calm surface. • Tank diameter: signal beam hits the tank wall only at one side. Note! No major interference reflections inside the signal beam. Endress+Hauser Micropilot S FMR 530 10 Technical data Resolution digital: 0.1 mm analogue: 0.03 % of measuring range Settling time Typical 15 sec Long-term drift The long-term drift is within the specified accuracy. Influence of ambiente temperature Within the specified accuracy according to OIML R85. Software reliability The software used in the radar instruments FMR 53x fulfills the requirements of OIML R85. This particularly includes: • cyclical test of data consistency • non-volatile memory • segmented data storage The radar instruments Micropilot S continuously monitor the compliance with accuracy requirements for custody transfer measurements according to OIML R85. If the accuracy cannot be maintained, a specific alarm is generated on the local display and via the digital communication. Inventory Control Versions All device types can be delivered as "Inventory Conctrol Versions" with a reduced accuracy of ± 3mm (under reference conditions). To these versions, the calibration certificate or custody transfer type approval is NOT attached. The "Inventory Control Versions" can be selected by choosing the option »R« in feature »70« in the order code section »Custody transfer approvals« on page 9 ff. Operating conditions Operating conditions Installation instructions see Page 14 ff. Beam angle see Page 15 ff. Environment Ambient temperature range Ambient temperature for the transmitter: • Standard: -40 °C … +80 °C (-40 °F … +176 °F) • For calibration to regulatory standards: -25 °C ... +60 °C (-30 °F…+140 °F) With Tu<-20 °C and Tu>+60 °C the operability of the LC-display is reduced. A weather protection cover should be used for outdoor operation if the instrument is exposed to direct sunlight. Storage temperature -40 °C ... +80 °C (-40 °F … +176°F) Climate class DIN EN 60068-2-38 (test Z/AD) Degree of protection • housing: IP 65, NEMA 4X (open housing: IP20, NEMA 1) • antenna: IP 68 (NEMA 6P) Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20…2000 Hz, 5 (m/s²)²/Hz Cleaning of the antenna See »Technical Information« TI 344F Electromagnetic compatibility • emissions according to EN 61326; equipment class B • compatibility according to EN 61326; appendix A (industrial area, 10 V/m) and Namur recommendation EMC (NE 21). Process conditions Endress+Hauser Process temperature range See »Technical Information« TI 344F Process temperature limits See »Technical Information« TI 344F 89 10 Technical data Micropilot S FMR 530 Process pressure limits See »Technical Information« TI 344F Dielectric constant • in a stilling well: εr ≥ 1.4 • in free space: εr ≥ 1.9 Wetted parts • Standard / Viton -20...+200 °C, for non-conductive media Antenna cone: PTFE Wetted parts: PTFE and 1.4571 • Standard / EPDM -40...+150 °C, for non-conductive media Antenna cone: PTFE Wetted parts: PTFE and 1.4571 • Standard / Kalrez 0...+200 °C, for non-conductive media Antenna cone: PTFE Wetted parts: PTFE and 1.4571 • Standard -20...+200 °C PTFE Seal (non wetted Viton O-Ring) gas-tight, for conductive media Antenna cone: PTFE Wetted parts: PTFE and 1.4571 Note! The gas-tight horn version (for conductive media) is resistant to hot vapour! Mechanical construction Design, dimensions see Page 13 Weight Approx 6 kg + weight of flange Material see Page 8 Process connection see Page 8 All process connections dispose of a gas-tight glass feed-through to prevent any gas leakage to the inside of the housing. Human interface Operation concept see Page 33 Display see Page 33 Certificates and approvals 90 CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark. RF approvals R&TTE 1999/5/EG, FCC CRF 47, part 15 Overspill protection PTB , NMi and many other national approvals External standards and guidelines EN 60529 Protection class of housing (IP-code) EN 61010 Safety regulations for electrical devices for measurement, control, regulation and laboratory use. EN 61326 Emissions (equipment class B), compatibility (appendix A – industrial area) NAMUR Standards committee for measurement and control in the chemical industry API (American Petroleum Institute) Particularly "Manual of Petroleum Measurement Stadards". OIML R85 (Organisation Internationale de Metrologie Legale) Ex approval XA 081F-A Installation Micropilot S FMR 53x (T12 / EEx ia IIC T6…T1) PTB 00 ATEX 2067 X, Equipment marking: (II 1/2 G) Endress+Hauser Micropilot S FMR 530 10 Technical data Ordering Information The E+H service organisation can provide detailed ordering information an information on the order codes on request. Accessories see Page 74 Supplementary Documentation Supplementary Documentation Endress+Hauser • System Information Micropilot (SI 019F/00/en) • Technical Information (TI 344F/00/en) • Operating Instructions "Description of instrument functions" (BA 217F/00/en) 91 11 Appendix Micropilot S FMR 530 11 Appendix 11.1 Operating menu HART (Display modul), ToF Tool basic setup 00 tank shape 002 dome ceiling horizontal cyl. bypass stilling well flat ceiling sphere safety settings 01 output on alarm medium property 003 process cond. 004 standard calm surface turb. surface add. agitator fast change test: no filter unknown DK: < 1.9 DK: 1.9 … 4 DK: 4 … 10 DK: > 10 010 outp. echo loss MIN -10% 3.6mA MAX 110% 22mA hold output on alarm 011 tank gauging 030 dip table mode enter value 012 delay time ramp %/min ramp %MB/min 013 dip table state 037 dip table 034 dip table handl. meas.v. 034 035 next point previous point new point edit point store point delete point dip value dip table state 037 auto correct. 04 014 in case of echo loss max. 4000 sec. default: 30 s 033 table on table off clear table linearisation 006 enter value enter value view manual semi-automatic dip table full calibr. pipe diameter enter value 03 005 enter value alarm hold user specific mounting calibr. empty calibr. 036 return level/ullage 040 linearisation 041 level CU ullage CU 040 manual semi-automatic table on 041 customer unit 042 horizontal cyl customer unit 042 linear customer unit 042 check distance 051 next point linearisation table no. input level input volume 043 044 045 yes range of mapping 052 start mapping 045 no reset table extended calibr. 05 level DU ullage DU 040 selection 050 dist./meas value 008 D and L are displayed mapping input of mapping range distance = ok dist. too small manual dist. unknown dist. too big 053 off on common extended map.. pres. Map dist 054 is displayed output 06 commun. address 060 no. of preambels 061 low output limit 062 language 09 092 back to home 0A present error 0A0 previous error 0A1 clear last error 063 on 093 format display 094 0A2 reset 0A3 tag no. 0C0 protocol+sw-no. 0C2 software no. 064 no. of decimals 095 unlock parameter 0A4 for reset code see manual for reset code see manual system parameter 0C fixed cur. value x x.x x.xx x.xxx decimal 1/16” enter time default: 100 s diagnostics 055 inactive active reset off off on display fixed current cust. Tank map 0C3 serial no. 0C4 custody transfer Note! The default values of the parameters are typed in boldface. 92 Endress+Hauser 007 Micropilot S FMR 530 dist./meas.value 11 Appendix 008 check distance 051 D and L are displayed range of mapping 052 start mapping 053 off on input of mapping range distance = ok dist. too small dist. too big manual history reset 009 no yes dist. unknown safety distance 015 from blocking distance default: 0.1m auto correction in safety dist. 016 031 pipe diam. corr. ackn. alarm 017 no yes alarm warning self holding overspill protection 018 standard german WHG 032 max. scale 046 max. scale 046 dist./meas.value 008 diameter vessel 047 echo quality 056 Return to Group Selection off on off on D and L are displayed simulation offset 057 will be added to the measured level is displayed 065 output damping 058 enter value default: 5 s output current 067 plot settings 09A blocking dist. 059 is displayed sim. off sim. level sim. volume sim. current sep. character 096 . point , comma measured dist. simulation value 066 display test 097 envelope curve env.curve+FAC env.curve+cust.map off on 0A5 measured level 0A6 recording curve application par. not modified modified distance unit 0C5 download mode Endress+Hauser 09B single curve cyclic 0A8 custody mode 0A9 inaktiv aktiv positiv aktiv negativ 0C8 93 94 V-CWII V0 V1 V2 V3 V4 V5 V6 V7 V9 VA Function group 00 basic setup 01 safety settings 03 mounting calibr. 04 linearisation 05 extended calibr. 06 output 09 display 0D service 0A diagnostics 0C system parameter check distance tag no. present error previous error no. Of preambels range of mapping linearisation level/ullage commun. Address customer unit auto correction tank gauging protocol+sw-no. software no. reset back to home language clear last error fixed current start mapping table no. dip table mode ramp %span/min medium property H3 low output limit pipe diam. corr. outp. echo loss output on alarm output on alarm H2 tank shape H1 measured value H0 Operating Matrix HART / COMMUWIN II serial no. unlock parameter format display fixed current pres. Map dist input level dip table delay time process cond. H4 distance unit measured dist. no. of decimals simulation cust. Tank map input volume dip table safety distance empty calibr. H5 measured level sep. character simulation value echo quality max. scale dip table handl. in safety dist. full calibr. H6 output current offset diameter vessel dip table state ackn. alarm pipe diameter H7 download mode application par. output damping overspill protection H8 custody mode blocking dist. H9 11 Appendix Micropilot S FMR 530 11.2 Operating matrix HART / Commuwin II Endress+Hauser Micropilot S FMR 530 11 Appendix 11.3 Description of functions ! Endress+Hauser Note! A detailed description of the function groups, functions and parameters is given in the documentation BA 217F/00/en - a description of the instrument functions of the Micropilot S. 95 11 Appendix Micropilot S FMR 530 11.4 Function and system design 11.4.1 Measuring principle L00-FMR53xxx-15-00-00-en-001 The Micropilot is a "downward-looking" measuring system, operating based on the timeof-flight method. It measures the distance from the reference point (process connection) to the product surface. Radar impulses are emitted by an antenna, reflected off the product surface and received again by the radar system. Input The reflected radar impulses are received by the antenna and transmitted into the electronics. A microprocessor evaluates the signal and identifies the level echo caused by the reflection of the radar impulse at the product surface. The unambiguous signal identification is accomplished by the PulseMaster® software based on many years of experience with time-of-flight technology. The mm-accuracy of the Micropilot S is achieved with the patented algorithms of the PhaseMaster® software. The distance D to the product surface is proportional to the travel time t of the impulse: D = c · t/2, with c being the speed of light. Based on the known empty distance E, the level L is calculated: L=E–D Reference point for "E" is the lower surface of the process connection. The Micropilot is equipped with functions to suppress interference echoes. The user can activate these functions. They ensure that interference echoes (e.g. from edges and weld seams) are not interpreted as level echo. 96 Endress+Hauser Micropilot S FMR 530 11 Appendix Output The Micropilot is commissioned by entering an empty distance E (=zero), a full distance F (=span), and an application parameter. The application parameter automatically adapts the instrument to the measuring conditions. The data points “E” and “F” correspond with 4mA and 20mA for instruments with current output. They correspond with 0 % and 100 % for digital outputs and the display module. A linearization with max. 32 points, based on a table entered either manually or semiautomatically, can be activated locally or remotely. This function provides a measurement in engineering units and a linear output signal for spheres, horizontal cylindrical tanks, and vessels with conical outlet. 11.4.2 Equipment architecture Stand-alone The Micropilot S can be used for measurement in a stilling well as well as in free space. The different instrument versions are applied as follows: • The Micropilot S FMR 532 with planar antenna is the preferred device in stilling wells ≥ 150 mm. • The Micropilot S FMR 530 with horn antenna can be used in stilling wells with a diameter <150 mm. However, for these diameters no custody transfer approval is available. • The Micropilot S FMR 533 with parabolic antenna is preferred for free-space measurements. The Micropilot S FMR 530 with horn antenna can be used as an alternative for small nozzle diameters . • The Micropilot S FMR 531 with rod antenna (PTFE) should be used for measurements of highly aggressive media (e.g. sulphur). • The instruments are equipped with a passive 4…20 mA output with HART protocol. The complete measuring system consists of: SPS - ToF Tool - COMMUWIN II - ToF Tool Service-Adapter FXA 193 HART Commubox FXA 191 HART Anzeige- und Bedienmodul VU 331 dsdmdm df das. asdas fa asas la. DELTABAR: * * * * * * * * ONLINE 1 QUICK SETUP 2 OPERATING MENU 3 PV 4 SV HELP 352 mbar 0 °C SAVE 9 Page Up Bksp 6 Delete Page On 1 2 Paste MNO 6 5 4 + Hot Key Insert W XY Z TUV 8 7 Endress+Hauser 3 Hot Key JKL GHI PQRS FXA 191 oder DXR 375 DEF ABC #%& Copy 9 ,()‘ _<> +*/ . 0 - 375 FIELD COMMUNICATOR HART-Handbediengerät DXR 375 ENDRESS + HAUSER % – + E L00-FMR53xxx-14-00-06-en-002 2x Messumformerspeisegerät RN 221 N 97 11 Appendix Micropilot S FMR 530 On-site operation: • with display and operating module VU 331, • with a Personal Computer, FXA 193 and the operating software ToF Tool. The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided microimpulse). It assists with commissioning, securing data, trouble shooting, and documentation of the measuring point. Remote operation: • with HART handheld DXR 375, • with a Personal Computer, Commubox FXA 191 and the operating software COMMUWIN II respectively ToF Tool. • With a Personal Computer, TSM (Tank Side Monitor) and the operating software FuelsManager. L00-FMR53xxx-14-00-06-en-003 System integration via Rackbus Multiple transmitters Micropilot S (or other instruments) can be connected to a higherlevel bus system via a Gateway ZA: • Every HART transmitter via one interface module FXN 672 each. • Gateways are available for MODBUS, FIP, PROFIBUS, INTERBUS etc. • Both on-site as well as remote operation are possible. Integration into the Asset Management System The HART interface allows the integration into the AMS® (Asset Management System) from Fisher-Rosemount. 98 Endress+Hauser Micropilot S FMR 530 11 Appendix 11.4.3 Custody transfer mode Micropilot S is a weight and measure approved level transmitter. Either the innage or the ullage can be selected as the custody transfer variable. The selected variable is the basis for the subsequent calculation of the current amount of product in a tank, along with other measured variables such as (average) temperature and pressure. This opens up numerous application options in custody transfer: • Quantity calculation of mineral oils • Quantity calculation of alcohols 11.4.4 Weight and measure approval, Standards Authorities approval, Compulsory reapproval The type approvals for custody transfer issued by the PTB and NMi, a copy of which is enclosed with every device, prove the fundamental suitability of the various types for custody transfer. In addition to this, the accuracy of every single device is documented using a calibration certificate, which is issued in the factory after the device has been tested on a reference test rig. On request, a separate Initial verification of the devices can be carried out with a National Standards Authorities inspector present, who issues a preliminary test certificate for every device. In the initial verification, the device is tested to ensure that it complies with the limit of error in legal metrology, which lies at +-2mm for radar measuring devices in Germany. Essentially, this proves that the devices are weight and measure approved. The devices must not, however, be used in custody transfer mode straight away. The measuring device is not approved until after the approval after installation by the Standards Authorities. For this, the device's level measurement is compared with the tank gauging by a National Standards Authorities inspector using manual dips (also "Initial verification"). As a rule, a quiescent tank gauging is dipped by hand three times in a row and then compared with the value displayed by the level radar. Depending on national regulations, the transfer error limit, calculated as the arithmetic mean of the absolute deviations of all three measurements, must not exceed double the limit of error in legal metrology (compare, for example, the German "Eichordnung" or the American "API 3.1B", in which the necessary procedures are also defined). Depending on national regulations, this test is repeated with various tank gaugings. Using linearisation tables to compensate any non-linearities that occur in measurement is permitted. For this, the Micropilot S level radar offers a special dip table, compare Chapter 6.5. After the measurement has been approved by an inspector, he seals the level radar at the stamp position and thereby also secures the programming status of the device. Those operating an approved level transmitter are obligated to obtain reapproval in accordance with the applicable national regulations from the Standards Authorities. Endress+Hauser 99 11 Appendix Micropilot S FMR 530 11.4.5 Particularities in "approved" operation The Micropilot S level radar is set to custody transfer mode after commissioning using a custody locking switch (see Page 37). The position of the custody locking switch is secured and sealed using the sealing pin. During custody transfer measurement, all custody transfer-relevant functions for operation are automatically locked, so that the device software can not be used, either via local operation or via digital communication settings. This locked status is displayed by the key symbol ( ). Micropilot S radar devices continuously monitor the compliance with accuracy requirements for custody transfer measurements according to OIML R85. If, for example, the accuracy cannot be maintained due to quick surface movements, this is reported via a separate alarm in the local display (displays "#" symbol) and via digital communication. 11.4.6 Definition of terms For definitions and procedures please refer to the following documents: • Manual of Petroleum Measurement Standards, Chapter 3 - Tank Gauging, Section 1.B - Standard Practice for Level Measurement of Liquid Hydrocarbons in Stationary Tanks by Automatic Tank Gauging, American Petroleum Institute, second edition, 2001 • OIML R 85, Organisation Internationale de Métrologie Légale, International Recommendation R 85, edition 1998 (E) 100 Endress+Hauser Micropilot S FMR 530 11 Appendix 11.4.7 Integrated on tank gauging system The Endress+Hauser Tank Side Monitor NRF 590 provides integrated communications for sites with multiple tanks, each with one or more sensors on the tank, such as radar, spot or average temperature, capacitive probe for water detection and/or pressure sensors. Multiple protocols out of the Tank Side Monitor guarantee connectivity to nearly any of the existing industry standard tank gauging protocols. Optional connectivity of analog 4...20 mA sensors, digital I/O and analog output simplify full tank sensor integration. Use of the proven concept of the intrinsically safe HART bus for all on-tank sensors yields extremely low wiring costs, while at the same time providing maximum safety, reliability and data availability. Fuels Manager Software Micropilot S Prothermo HART 4 wire RTU 8130 (remote terminal unit) Tank Side Monitor Pressure Endress+Hauser L00-FMR53xxx-14-00-06-en-004 Supply voltage: 16…253 VAC 101 11 Appendix Micropilot S FMR 530 This product may be protected by at least one of the following patents. Further patents are pending. • • • • • • • • • • • • • 102 US 5,387,918 i EP 0 535 196 US 5,689,265 i EP 0 626 063 US 5,659,321 US 5,614,911 i EP 0 670 048 US 5,594,449 i EP 0 676 037 US 6,047,598 US 5,880,698 US 5,926,152 US 5,969,666 US 5,948,979 US 6,054,946 US 6,087,978 US 6,014,100 Endress+Hauser Micropilot S FMR 530 Endress+Hauser 11 Appendix 103 11 Appendix 104 Micropilot S FMR 530 Endress+Hauser Micropilot S FMR 530 Index Index A Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Antenna extension . . . . . . . . . . . . . . . . . . . . . . . . . . Antenna size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Approval after installation . . . . . . . . . . . . . . . . . . . . . Auto-correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 41 74 13 99 56 46 48 18 17 C Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Calibration to regulatory standards disturbed . . . . . 36 CE approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Check distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Cleaning agents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Communication symbol . . . . . . . . . . . . . . . . . . . . . . 36 Commuwin II . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44, 75 Commuwin II-Operating Programm . . . . . . . . . . . . . 44 Contact addresses . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Contrast settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Current consumption . . . . . . . . . . . . . . . . . . . . . . . . 30 Custody locking switch . . . . . . . . . . . . . . . . . . . . 35, 37 Custody mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Customer unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 D Declaration of conformity . . . . . . . . . . . . . . . . . . . . . 10 Declaration of contamination . . . . . . . . . . . . . . . . . . . 5 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . 32 Diameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Dielectric constant . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Dip Table Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Dip table status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Dip value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46, 52 E Echo quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Empty calibration . . . . . . . . . . . . . . . . . . 46, 51, 67–69 Engineering hints . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Envelope curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Error messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 F Foam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Foam surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Free space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Endress+Hauser G Green LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Group selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 H B Basic Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Setup VU 331 . . . . . . . . . . . . . . . . . . . . . . . . . Blocking distance . . . . . . . . . . . . . . . . . . . . . . . . . . . Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Full calibration . . . . . . . . . . . . . . . . . . . . . 46, 51, 67–69 Function groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Handheld unit DXR 275 . . . . . . . . . . . . . . . . . . . . . . . 42 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30–31, 42 Housing T12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 I Inclination device . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Initial verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Installation in stilling well . . . . . . . . . . . . . . . . . . . . . . 11 Installation in tank (free space) . . . . . . . . . . . . . . . . . 11 Interference echo. . . . . . . . . . . . . . . . . . . . . . . . . 53, 81 Interference echo mapping . . . . . . . . . . . . . . 53–54, 69 K Key assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 L Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46, 52 Liquid crystal display (LCD) . . . . . . . . . . . . . . . . . . . 35 Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 M Mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53–54 Marker at instrument flange . . . . . . . . . . . . . . . . . 19, 21 Maximum measured error . . . . . . . . . . . . . . . . . . . . . 88 Measure value actualisation . . . . . . . . . . . . . . . . . . . 47 Measured value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Measured value display . . . . . . . . . . . . . . . . . . . . . . . 33 Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Medium conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Minimum level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Modification nameplate . . . . . . . . . . . . . . . . . . . . . . . 85 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Mounting calibration . . . . . . . . . . . . . . . . . . . . . . 56, 71 Mounting kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 N Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 No.of decimals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Notes on safety conventions and symbols . . . . . . . . . 6 Nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 O Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33, 38 105 Index Micropilot S FMR 530 Optimisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Ordering structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 P Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Phase evaluation . . . . . . . . . . . . . . . . . . . . . . 50, 57, 59 Pipe diam. corr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Pipe diameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Positioning of the reflector. . . . . . . . . . . . . . . . . . . . . 25 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . 27 Power consumption. . . . . . . . . . . . . . . . . . . . . . . . . . 30 Power supply fails . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Process conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Product class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Q Quick wiring guide . . . . . . . . . . . . . . . . . . . . . . . . . . 28 R Range of mapping . . . . . . . . . . . . . . . . . . . . . . . . . . Reapproval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommendations for the stilling well. . . . . . . . . . . . Red LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reference point of measuring. . . . . . . . . . . . . . . . . . Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset customer parameters . . . . . . . . . . . . . . . . . . . Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RF approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Roof reflector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 99 21 36 46 73 40 40 85 90 24 S Safety conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Sealing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Select the language . . . . . . . . . . . . . . . . . . . . . . . . . 45 106 Selection menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Service adapter FXA 193 . . . . . . . . . . . . . . . . . . . . . 75 Signal beam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Slot width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Smallest possible measuring range . . . . . . . . . . . . . 16 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Stilling well . . . . . . . . . . . . . . . . . . . . . . . . . . 17, 21, 52 Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Switching on the measuring device . . . . . . . . . . . . . 45 T Tank Gauging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Tank installations . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Tank shape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48, 67 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Terminal compartment . . . . . . . . . . . . . . . . . . . . . . . 30 Tip of the antenna . . . . . . . . . . . . . . . . . . . . . . . . . . 16 ToF Tool . . . . . . . . . . . . . . . . . . . . . . . 42, 66, 70–71, 92 Trademarks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Trouble-shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Trouble-shooting instructions . . . . . . . . . . . . . . . . . . 76 Turn housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11, 23 U Unlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Unlock parameter. . . . . . . . . . . . . . . . . . . . . . . . . 38–39 W Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weather protection cover . . . . . . . . . . . . . . . . . . . . . Weight and measure approved . . . . . . . . . . . . . . . . Weld seam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 74 99 21 28 Endress+Hauser Micropilot S FMR 530 Index Declaration of contamination Dear costumer, Because of legal determinations and for the safety of our employes and operating equipment we need this “Declaration of contamination” with your signature before your order can be handled. Please put the completely filled in declaration to the instrument and to the shipping documents in any case. Add also safety sheets and/or specific handling instructions if necessary. type of instrument / sensor: __________________________________ serial number: _______________________ medium / concentration: __________________________________ temperature: ______ pressure: _______ cleaned with: __________________________________ conductivity: ______ viscosity: _______ :DUQLQJKLQWVIRUPHGLXPXVHG SAFE o o o o o o o o radioactive explosive caustic poisonous harmful of health biological hazardous inflammable safe Please mark the appropriate warning hints. 5HDVRQIRUUHWXUQ BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB &RPSDQ\GDWD company: ______________________________ contact person: ______________________________ address: _________________________ _________________________ ______________________________ department: _________________________ ______________________________ phone number: _________________________ ______________________________ Fax/E-Mail: _________________________ ______________________________ your order no.: _________________________ I hereby certify that the returned equipment has been cleaned and decontaminated acc. to good industrial practices and is in compliance with all regulations. This equipment poses no health or safety risks due to contamination. _______________________________ ___________________________________ (Date) (company stamp and legally binding signature) More information about services and repairs: www.services.endress.com Endress+Hauser 107 Europe Austria – Wien ❑ Endress+Hauser Ges.m.b.H. Tel. (01) 88 05 60, Fax (01) 88 05 63 35 Belarus – Minsk Belorgsintez Tel. (017) 2 50 84 73, Fax (017) 2 50 85 83 Belgium / Luxembourg – Bruxelles ❑ Endress+Hauser S.A. / N.V. Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53 Bulgaria – Sofia Intertech-Automation Ltd. Tel. (02) 9 62 71 52, Fax (02) 9 62 14 71 Croatia – Zagreb ❑ Endress+Hauser GmbH+Co. Tel. (01) 6 63 77 85, Fax (01) 6 63 78 23 Cyprus – Nicosia I+G Electrical Services Co. Ltd. Tel. (02) 48 47 88, Fax (02) 48 46 90 Czech Republic – Praha ❑ Endress+Hauser Czech s.r.o. Tel. (02) 66 78 42 00, Fax (026) 66 78 41 79 Denmark – Søborg ❑ Endress+Hauser A/S Tel. (70) 13 11 32, Fax (70) 13 21 33 Estonia – Tartu Elvi-Aqua OÜ Tel. (7) 30 27 32, Fax (7) 30 27 31 Finland – Helsinki ❑ Metso Endress+Hauser Oy Tel. (204) 8 31 60, Fax (204) 8 31 61 France – Huningue ❑ Endress+Hauser S.A. Tel. (389) 69 67 68, Fax (389) 69 48 02 Germany – Weil am Rhein ❑ Endress+Hauser Messtechnik GmbH+Co. KG Tel. (07621) 9 75 01, Fax (07621) 97 55 55 Norway – Lierskogen ❑ Endress+Hauser A/S Tel. 32 85 98 50, Fax 32 85 98 51 Colombia – Bogota D.C. Colsein Ltda. Tel. (01) 2 36 76 59, Fax (01) 6 10 78 68 Israel – Netanya Instrumetrics Industrial Control Ltd. Tel. (09) 8 35 70 90, Fax (09) 8 35 06 19 Poland – Wroclaw ❑ Endress+Hauser Polska Sp. z o.o. Tel. (071) 7 80 37 00, Fax (071) 7 80 37 60 Costa Rica – San Jose Euro-Tec S.A. Tel. 2 20 28 08, Fax 2 96 15 42 Japan – Tokyo ❑ Sakura Endress Co. Ltd. Tel. (0422) 54 06 11, Fax (0422) 55 02 75 Portugal – Cacem ❑ Endress+Hauser Lda. Tel. (21) 4 26 72 90, Fax (21) 4 26 72 99 Ecuador – Quito Insetec Cia. Ltda. Tel. (02) 2 26 91 48, Fax (02) 2 46 18 33 Jordan – Amman A.P. Parpas Engineering S.A. Tel. (06) 5 53 92 83, Fax (06) 5 53 92 05 Romania – Bucharest Romconseng S.R.L. Tel. (021) 41 12 50 1, Fax (021) 41 01 63 4 El Salvador – San Salvador Automatizacion y Control Industrial de El Salvador, S.A. de C.V. Tel. 2 60 24 24, Fax 2 60 56 77 Kazakhstan – Almaty BEI Electro Tel. (72) 30 00 28, Fax (72) 50 71 30 Russia – Moscow ❑ Endress+Hauser GmbH+Co Tel. (095) 78 32 85 0, Fax (095) 78 32 85 5 Slovak Republic – Bratislava Transcom Technik s.r.o. Tel. (2) 44 88 86 90, Fax (2) 44 88 71 12 Slovenia – Ljubljana ❑ Endress+Hauser (Slovenija) D.O.O. Tel. (01) 5 19 22 17, Fax (01) 5 19 22 98 Spain – Sant Just Desvern ❑ Endress+Hauser S.A. Tel. (93) 4 80 33 66, Fax (93) 4 73 38 39 Sweden – Sollentuna ❑ Endress+Hauser AB Tel. (08) 55 51 16 00, Fax (08) 55 51 16 55 Switzerland – Reinach/BL 1 ❑ Endress+Hauser Metso AG Tel. (061) 7 15 75 75, Fax (061) 7 11 16 50 Turkey – Levent/Istanbul Intek Endüstriyel Ölcü ve Kontrol Sistemleri Tel. (0212) 2 75 13 55, Fax (0212) 2 66 27 75 Ukraine – Kiev Photonika GmbH Tel. (44) 2 68 81 02, Fax (44) 2 69 07 05 Yugoslavia Republic – Beograd Meris d.o.o. Tel. (11) 4 44 29 66, Fax (11) 3 08 57 78 Guatemala – Ciudad de Guatemala Automatizacion y Control Industrial, S.A. Tel. (03) 34 59 85, Fax (03) 32 74 31 Honduras – San Pedro Sula, Cortes Automatizacion y Control Industrial de Honduras, S.A. de C.V. Tel. 5 57 91 36, Fax 5 57 91 39 Mexico – México, D.F ❑ Endress+Hauser (México), S.A. de C.V. Tel. (5) 5 55 68 24 07, Fax (5) 5 55 68 74 59 Nicaragua – Managua Automatización y Control Industrial de Nicaragua, S.A. Tel. 2 22 61 90, Fax 2 28 70 24 Peru – Miraflores Corsusa International Tel. (1) 44 41 20 0, Fax (1) 44 43 66 4 USA – Greenwood, Indiana ❑ Endress+Hauser Inc. Tel. (317) 5 35 71 38, Fax (317) 5 35 84 98 USA – Norcross, Atlanta ❑ Endress+Hauser Systems & Gauging Inc. Tel. (770) 4 47 92 02, Fax (770) 4 47 57 67 Venezuela – Caracas Controval C.A. Tel. (212) 9 44 09 66, Fax (212) 9 44 45 54 Korea, South – Seoul ❑ Endress+Hauser (Korea) Co. Ltd. Tel. (02) 26 58 72 00, Fax (02) 26 59 28 38 Kuwait – Safat United Technical Services Est. For General Trading Tel. 2 41 12 63, Fax 2 41 15 93 Lebanon – Jbeil Main Entry Network Engineering Tel. (3) 94 40 80, Fax (9) 54 80 38 Malaysia – Shah Alam, Selangor Darul Ehsan ❑ Endress+Hauser (M) Sdn. Bhd. Tel. (03) 78 46 48 48, Fax (03) 78 46 88 00 Pakistan – Karachi Speedy Automation Tel. (021) 7 72 29 53, Fax (021) 7 73 68 84 Philippines – Pasig City, Metro Manila ❑ Endress+Hauser (Phillipines) Inc. Tel. (2) 6 38 18 71, Fax (2) 6 38 80 42 Saudi Arabia – Jeddah Anasia Trading Est. Tel. (02) 6 53 36 61, Fax (02) 6 53 35 04 Singapore – Singapore ❑ Endress+Hauser (S.E.A.) Pte. Ltd. Tel. (65) 66 82 22, Fax (65) 66 68 48 Sultanate of Oman – Ruwi Mustafa & Sultan Sience & Industry Co. L.L.C. Tel. 63 60 00, Fax 60 70 66 Great Britain – Manchester ❑ Endress+Hauser Ltd. Tel. (0161) 2 86 50 00, Fax (0161) 9 98 18 41 Africa Asia Greece – Athens I & G Building Services Automation S.A. Tel. (01) 9 24 15 00, Fax (01) 9 22 17 14 Algeria – Annaba Symes Systemes et Mesures Tel. (38) 88 30 03, Fax (38) 88 30 02 Azerbaijan – Baku Modcon Systems - Baku Tel. (12) 92 98 59, Fax (12) 99 13 72 Hungary – Budapest ❑ Endress+Hauser Magyarország Tel. (01) 4 12 04 21, Fax (01) 4 12 04 24 Egypt – Heliopolis/Cairo Anasia Egypt For Trading (S.A.E.) Tel. (02) 2 68 41 59, Fax (02) 2 68 41 69 Iceland – Reykjavik Sindra-Stál hf Tel. 5 75 00 00, Fax 5 75 00 10 Morocco – Casablanca Oussama S.A. Tel. (02) 22 24 13 38, Fax (02) 2 40 26 57 Brunei – Negara Brunei Darussalam American International Industries (B) Sdn. Bhd. Tel. (3) 22 37 37, Fax (3) 22 54 58 United Arab Emirates – Dubai Descon Trading L.L.C. Tel. (04) 2 65 36 51, Fax (04) 2 65 32 64 Ireland – Clane / County Kildare ❑ Flomeaco Endress+Hauser Ltd. Tel. (045) 86 86 15, Fax (045) 86 81 82 Rep. South Africa – Sandton ❑ Endress+Hauser (Pty.) Ltd. Tel. (011) 2 62 80 00, Fax (011) 2 62 80 62 Cambodia – Khan Daun Penh, Phom Penh Comin Khmere Co. Ltd. Tel. (23) 42 60 56, Fax (23) 42 66 22 Uzbekistan – Tashkent Im Mexatronika-Tes Tel. (71) 1 91 77 07, Fax (71) 1 91 76 94 Italy – Cernusco s/N, Milano ❑ Endress+Hauser S.p.A. Tel. (02) 92 19 21, Fax (02) 92 19 23 62 Tunisia – Tunis CMR Controle, Maintenance et Regulation Tel. (07) 17 93 07 7, Fax (07) 17 88 59 5 China – Shanghai ❑ Endress+Hauser (Shanghai) Instrumentation Co. Ltd. Tel. (021) 54 90 23 00, Fax (021) 54 90 23 03 Vietnam – Ho Chi Minh City Tan Viet Bao Co. Ltd. Tel. (08) 8 33 52 25, Fax (08) 8 33 52 27 Australia + New Zealand Latvia – Riga Elekoms Ltd. Tel. (07) 33 64 44, Fax (07) 33 64 48 America China – Beijing ❑ Endress+Hauser (Beijing) Instrumentation Co. Ltd. Tel. (010) 65 88 24 68, Fax (010) 65 88 17 25 Lithuania – Kaunas UAB Agava Ltd. Tel. (03) 7 20 24 10, Fax (03) 7 20 74 14 Argentina – Buenos Aires ❑ Endress+Hauser Argentina S.A. Tel. (11) 45 22 79 70, Fax (11) 45 22 79 09 Hong Kong – Tsimshatsui / Kowloon ❑ Endress+Hauser (H.K.) Ltd. Tel. 8 52 25 28 31 20, Fax 8 52 28 65 41 71 Macedonia – Beograd Meris d.o.o. Tel. (11) 44 42 96 6, Fax (11) 30 85 77 8 Brazil – Sao Paulo ❑ Samson Endress+Hauser Ltda. Tel. (011) 50 33 43 33, Fax (011) 50 31 30 67 India – Mumbai ❑ Endress+Hauser (India) Pvt. Ltd. Tel. (022) 56 93 83 33, Fax (022) 56 93 88 330 Moldavia – Chisinau S.C. Techno Test SRL Tel. (02) 22 61 60, Fax (02) 22 83 13 Canada – Burlington, Ontario ❑ Endress+Hauser Canada Ltd. Tel. (905) 68 19 29 2, Fax (905) 68 19 44 4 Indonesia – Jakarta PT Grama Bazita Tel. (21) 7 95 50 83, Fax (21) 7 97 50 89 Netherlands – Naarden ❑ Endress+Hauser B.V. Tel. (035) 6 95 86 11, Fax (035) 6 95 88 25 Chile – Santiago de Chile ❑ Endress+Hauser (Chile) Ltd. Tel. (02) 3 21 30 09, Fax (02) 3 21 30 25 Iran – Tehran Patsa Industry Tel. (021) 8 72 68 69, Fax (021) 8 71 96 66 http://www.endress.com ❑ Members of the Endress+Hauser group BA 206F/00/en/04.04 52006307 CCS / FM+SGML 6.0 05.03 Taiwan – Taipei Kingjarl Corporation Tel. (02) 27 18 39 38, Fax (02) 27 13 41 90 Thailand – Bangkok 10210 ❑ Endress+Hauser (Thailand) Ltd. Tel. (2) 9 96 78 11-20, Fax (2) 9 96 78 10 Australia – North Ryde NSW 2113 ❑ Endress+Hauser Australia Pty. Ltd. Tel. (02) 88 77 70 00, Fax (02) 88 77 70 99 New Zealand – Auckland EMC Industrial Group Ltd. Tel. (09) 4 15 51 10, Fax (09) 4 15 51 15 All other countries ❑ Endress+Hauser GmbH+Co. KG Instruments International Weil am Rhein, Germany Tel. (07621) 9 75 02, Fax (07621) 97 53 45
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project