- Industrial & lab equipment
- Electrical equipment & supplies
- Johnson Controls
- 3500 MIG3500
- User manual
- 48 Pages
Johnson Controls 300 MIG300, 3500 MIG3500, 35 NAE35, 45 NAE45, 55 NAE55, NCM, NIE, ADS, ADX Commissioning Guide
Below you will find brief information for Metasys Integrator 3500 MIG3500, Metasys Integrator 300 MIG300, Network Automation Engine 35 NAE35, Network Automation Engine 45 NAE45, Network Automation Engine 55 NAE55. This device is used for integrating third-party equipment with the Metasys® Building Automation System (BAS), which allows operators to monitor and control these third-party devices from a single Metasys workstation. The documentation describes how to configure the communication ports, download vendor tables, and verify data communications with third-party devices. It also outlines the procedure for integrating vendor equipment into the Metasys network.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Metasys Integrator® 3500 Series
Commissioning Guide
MS-MIG3520-0
Code No. LIT-12011439
Software Release 10.0
Issued October 6, 2008
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
MIG3500 Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Comparison between Metasys Integrator 300 and 3500 Series . . . . . . . . . . . . . . . . . . . 8
Communication Port Comparison: MIG300 and MIG3500 Series . . . . . . . . . . . . . . . . . . . . . 9
Metasys Integrator® 3500 Series Commissioning Guide 1
Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installing DOWNPC and Vendor Communication Tables . . . . . . . . . . . . . . . . . . . . . . . 25
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2 Metasys Integrator® 3500 Series Commissioning Guide
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Metasys Integrator® 3500 Series Commissioning Guide 3
4 Metasys Integrator® 3500 Series Commissioning Guide
Metasys Integrator® 3500 Series
Commissioning Guide
Introduction
This document explains how to commission a Metasys Integrator® 3500
(MIG3500) Series unit. Included is how to inspect the installation, download the
MIG3500 firmware, download vendor communication tables (.VCT), add/modify/ delete vendor devices, and verify device communication.
This document does not describe how to mount, wire, or power the MIG3500.
Also, this document does not contain specific details about integrating vendor equipment (for example, cable pinouts and point mapping tables). For that information, refer to the vendor-specific application notes available separately on
QuickLit. For information on vendor controllers, see vendor documentation
(obtainable from your vendor representative).
Related Documentation
Table 1 lists documents related to the Metasys system.
Table 1: Related Documentation
For Information On See Document
Features and Benefits of the MIG3500
Metasys Integrator® MIG3500 Series
Product Bulletin
Installing the MIG3500 and Replacing an Existing MIG300
Mounting an EN-EWC25-0 Enclosure
Metasys Integrator MIG3500 Series
Installation Instructions
Universal Packaging Module Technical
Bulletin
Metasys Integrator Application Notes
Specific Vendor Application
Information
Supported Vendor Equipment
Understanding How the N2 Bus Is
Integrated to the MIG3500
Overview of N2 Bus Controllers
Metasys Integrator 300/3500 Series
Product Bulletin Supplement
N2 Communications Bus Technical
Bulletin
Technical Bulletin for each N2 Bus field controller
LIT or Part Number
LIT-12011440
Part No. 24-10050-30
LIT-6363070
LIT-6295xxx
1
LIT-629075
LIT-636018
Various
1.
For the LIT numbers of specific documents, refer to the Metasys Integrator section on QuickLit.
Metasys Integrator® 3500 Series Commissioning Guide 5
MIG3500 Commissioning Overview
About the MIG3500 Metasys Integrator
The MIG3500 is an interface device that connects third-party devices to a
Metasys® Building Automation System (BAS). Operators can monitor and control third-party devices along with the entire BAS from a single Metasys workstation.
Using a computer with terminal emulation software, you can download the drivers for the equipment you want to integrate. You can choose from many third-party products currently supported. The MIG3500 can integrate two different sets of vendor equipment.
The MIG3500 uses the same hardware platform as the Network Automation
Engine (NAE) 35/45 models, but with different firmware. The firmware on the electronics board contains:
• commissioning software (for selecting and configuring vendor integrations)
• vendor and N2 open protocol support software
In addition, there is a Metasys Integrator CD-ROM containing the Metasys MIG
Update Utility, download software, .VCT files, the N2 Bus Checkout Tool, and software models in Data Definition Language (DDL) syntax for all applications.
6 Metasys Integrator® 3500 Series Commissioning Guide
Metasys Network with the MIG3500
The MIG3500 exists on the N2 Bus portion of the Metasys network. Figure 1
shows an example of this type of configuration. As shown, the MIG3500 may connect to the N2 Bus on an NAE55 or NAE35/45. The MIG3500 is added as an
N2 device at the Application and Data Server (ADS) or Extended Application and
Data Server (ADX). With the addition of a Network Integration Engine (NIE), an older Metasys Integrator model (MIG300) that communicates to a Network
Control Module (NCM) can report to the same ADS/ADX as the newer NCM3500 model.
M5 Operator
Workstation
Web Browser
(Primary User Interface)
ADS or ADX
IP Network
NCM
IP Network
NAE55
NIE
NAE55
NAE35/45
N2
Bus
MIG300
FC Bus
(MS/TP)
VMA1620
Network
Sensor
IOM
FC Bus
(N2)
DX-9100
FC Bus
(N2)
DX-9100
Vendor
Port A
Vendor
Port B
Third-Party Devices
VAV
MIG3500
FEC2610
Network
Sensor
SA Bus
IOM
MIG3500
VAV
Vendor
Port B*
Vendor
Port A*
Vendor
Port B*
Vendor
Port A*
Third-Party Devices
Third-Party Devices
*
Vendor Port A: Native RS485
Vendor Port B: Native RS232
Figure 1: MIG3500 with Other System Components
Metasys Integrator® 3500 Series Commissioning Guide 7
Comparison between Metasys Integrator 300 and 3500 Series
For those who are familiar with the Metasys Integrator 300 Series, the following section outlines the most important similarities and differences between the older model and the MIG3500. If you are looking specifically for details on the
communication options, see Table 2.
• The MIG3500 model supports vendor tables that the MIG300 supports
(version 9.0 and above).
• The MIG3500 is also powered with a 24 VAC power transformer, ordered separately. The adapter requires a standard power outlet near the MIG3500.
The 24 VAC power connector on the MIG3500 has a different style and therefore is incompatible with the MIG300 power connector.
• Unlike the MIG300, the firmware for the MIG3500 is updated over an Ethernet connection. Similar to the MIG300, the vendor tables are downloaded over the
RS-232 commissioning port from a computer running the DOWNPC software.
The DOWNPC software transfers VCT files from the computer to the
MIG3500.
• The MIG3500 offers four communication ports labeled as follows:
•
Config Port - RS232C: Configuration/commissioning port
•
Vendor A - RS485: RS-485 vendor communications port
•
Vendor B - RS232C: RS-232 vendor communications port
•
N2 - RS485 - N2 Bus communications port
• If you have a second RS-232 or RS-485 vendor device to connect, you can use a signal converter with the appropriate MIG3500 vendor port and gender changer/adapter if required. The type of signal converter you need depends on the requirements of the vendor device. Some devices can use the
MM-CVT101-1, AS-CVTPROx00-1, or IU-9100-8401 (Europe only)
Johnson Controls® converters, while others may require a different converter.
For assistance with selecting an appropriate converter, refer to the specific vendor Metasys Integrator Application Note or contact the Systems Integration
Services (SIS) team at Johnson Controls.
• The code for the MIG3500 is downloaded and updated with a tool called the
MIG Update Utility, available on the Metasys Integrator CD-ROM. (The code download process described in the Downloading Metasys Integrator 300
Series Code Application Note [LIT-6933500] is not used.) This tool is also used to return the MIG3500 to factory condition. Whenever the device is reflashed, all vendor tables in the device must be redownloaded because the flash process erases the tables.
• If a VCT table in the MIG3500 becomes corrupt, causing the unit to reboot continuously, first reflash the unit with the MIG Update Utility, then redownload the tables with the DOWNPC software. With the MIG300, you only needed to remove the power and battery, then restart the unit.
8 Metasys Integrator® 3500 Series Commissioning Guide
• The MIG3500 is a bit longer than the MIG300. If the MIG3500 is replacing an older MIG300, the new unit can fit in the same location as the MIG300 that it is replacing.
• The N2 Bus terminal connection on the MIG3500 is called N2 - RS485.
Similar to the MIG300, this connector has four terminals, including a termination for an optional shield. The MIG300 N2 Bus connector is compatible with the RS485A (N2 Bus) terminal block on the MIG3500.
• The Fault Light-Emitting Diode (LED) on the MIG3500 indicates failure. For
Communication Port Comparison: MIG300 and MIG3500 Series
Table 2 is a comparison chart that shows the choices for each MIG3500 port as
compared to the MIG300 Series.
Note: A vendor device using RS-232 communication and connected to Vendor
Port A (Port 2) on the MIG300 can be moved to Vendor B - RS232C port on the MIG3500. A device using RS-232 communication and connected to
Vendor Port B (Port 3) on the MIG300 can be moved to Vendor A - RS485 port on the MIG3500 (with the use of a converter). A device using RS-485 communication and connected to either port on the MIG300 can be moved to Vendor A - RS485 port on the MIG3500 (no converter required).
Table 2: Communications Port Comparison between Models
Port
Number
MIG300
Label
MIG3500
MIG3500 Use
Port 0
Port 1
N2 N2 - RS485
Commissioning Port Config - RS232C
N2 Bus connection
Configuration/commissioning port
Port 2 Vendor A - RS485 Vendor A connection; RS-485 protocol
Port 3
N/A
Vendor Port A
1
Vendor Port B
N/A
Vendor B - RS232C Vendor B connection; RS-232 protocol
Ethernet
Ethernet connection
2
1.
Vendor Port A and Vendor Port B on the MIG300 are both native RS232 ports.
2.
The Ethernet connection is used exclusively for firmware updates to the MIG3500. The unit does not broadcast as a node over the Ethernet network.
Required Hardware
The MIG3500 requires the following hardware:
• laptop or desktop computer for downloading the vendor tables and reflashing the firmware (if required)
• RS-232 null modem cable for connecting the computer to the Metasys
Integrator unit for commissioning purposes
• Cable for connecting the Metasys Integrator unit to vendor equipment (RS-232 or RS-485 cable, depending on equipment interface). You can find pinouts for this cable in the vendor-specific application note. (For example, cable pinouts for connecting Fireye® equipment are in the Metasys Integrator Fireye
Application Application Note [LIT-6295280].)
Metasys Integrator® 3500 Series Commissioning Guide 9
• N2 Bus cable for connecting the Metasys Integrator unit to a Metasys supervisory controller. Refer to the N2 Integration with the NAE Technical
Bulletin (LIT-1201683).
Required Software
The MIG3500 requires the following software:
• VT100 Terminal Emulation software for commissioning and setting up the
Metasys Integrator unit
• DOWNPC, commissioning software for selecting and downloading vendor configuration tables, provided on the Metasys Integrator CD-ROM
• vendor and N2 open protocol support software
• Metasys Integrator software CD-ROM labeled Tables and Models
(MS-MIGSWO-0). Use software CDs with a revision number 9.00 or higher with the MIG3500 Release 10 firmware.
In addition, there is one Metasys Integrator CD-ROM containing the Metasys MIG
Update Utility, download software, .VCT files, the N2 Bus Checkout Tool, and software models in DDL syntax for all applications.
10 Metasys Integrator® 3500 Series Commissioning Guide
MIG3500 Components
Figure 2 illustrates the basic components of the MIG3500. The Metasys Integrator
unit has an N2 terminal, commissioning port, Ethernet port, and two vendor ports.
The power terminal requires an external 24 VAC power supply.
Battery
Compartment
Restart Switch
Access Hole
24 VAC
Power Terminal
System Status
(Commissioning)
Light-Emitting Diodes
(LEDs)
Config Port - RS-232C
Port
Vendor B
RS232C
Port
RJ-45 8-Pin
Ethernet
Port
N2 Bus
RS485
Port
N2
End-of-Line
Switch
Vendor A
RS485
Port
RS485B
End-of-Line
Switch
Figure 2: MIG3500 Components
Metasys Integrator® 3500 Series Commissioning Guide 11
System Status LEDs
Figure 3 shows the designation of the LED status indicators on the MIG3500.
Table 3 describes the purpose of each LED.
POWER
FAULT
N2 PORT TX
VENDOR A TX
VENDOR B TX
VENDOR B RX
ETHERNET
10 LINK
100 LINK
RUN
Figure 3: MIG3500 LED Status Indicators
Table 3:
MIG3500 LED Designations, Normal Status, and Descriptions
LED Designation Normal Status Descriptions/Other Conditions
POWER (Green) On Steady On Steady = Unit is getting power from the 24 VAC supply.
Off Steady = Unit is shut down.
FAULT (Red) Off Steady
N2 PORT TX
(Green)
Flicker
Flicker Once, Then Device Continually Restarts = Internal fault has occurred.
Flicker = Normal communications; the MIG3500 is transmitting data.
Flickers are generally in sync with data transmission, but should not be used to indicate specific transmission times.
Off Steady = the MIG3500 is not responding to N2 Bus communication.
Flicker = Data is being transmitted from the MIG3500 to the vendor device connected to the Vendor A - RS485 port.
VENDOR A TX
(Green)
VENDOR B TX
(Green)
Flicker
Flicker
VENDOR B RX
(Green)
Flicker
ETHERNET (Green) Flicker
Flicker = Data is being transmitted from the MIG3500 to the vendor device connected to the Vendor B - RS232C port.
Flicker = Data is being received by the MIG3500 from the vendor device connected to the Vendor B - RS232C port.
10/LINK (Green)
100/LINK (Green)
RUN (Green)
On Steady
On Steady
On Steady
Flicker = Data is transferring on the Ethernet connection. This LED is only active when the MUU is downloading the firmware to the unit.
Off Steady = No Ethernet traffic on the Ethernet connection, indicating the MUU is not in use or is not downloading the firmware to the unit.
On Steady = Ethernet connection is established at 10 Mbps.
On Steady = Ethernet connection is established at 100 Mbps.
On Steady = MIG3500 software is fully initialized.
Off = MIG3500 unit is not powered or is starting up.
On 0.5 seconds, Off 0.5 seconds = MIG3500 software is starting up.
Config Port - RS232C
This RS-232C serial port is used for downloading the vendor tables into the
MIG3500 using a laptop computer and the DOWNPC software. This port is also used to configure the device with Microsoft® HyperTerminal. These communication baud rates are supported: 300; 600; 1200; 2400; 4800; 9600;
19,200; 38,400; 57,600; and 115,200 bps.
12 Metasys Integrator® 3500 Series Commissioning Guide
Vendor B - RS232C Port
This RS232C serial port is used for interfacing to a vendor device that communicates with RS-232C signals. These communication baud rates are supported: 300; 600; 1200; 2400; 4800; 9600; 19,200; 38,400; 57,600; and
115,200 bps.
RJ-45 8-Pin Ethernet Port
The Ethernet connector on the MIG3500 allows for the unit to be flashed with its firmware over an IP connection. Communication occurs at 10 or 100 Mbps, depending on the capabilities of the computer’s network card.
N2 Bus RS485 Port
This is an N2 Bus termination block (N2 - RS-485) that allows the MIG3500 to communicate vendor data to a supervisory controller over the N2 Bus at 9600 bits per second. Devices on the N2 Bus constitute a local network controlled by a supervisory controller. Each vendor device is assigned an N2 Bus address when you commission the MIG3500.
Each end of the N2 Bus is terminated with an End-of-Line (EOL) termination resistor provided by a switch. For information on setting the N2 EOL switch, see
Setting the N2 Bus and RS485B End-of-Line Switches on page 25.
Vendor A - RS485 Port
This RS-485 serial port is used for interfacing to a vendor device that communicates with RS-485 signals. These communication baud rates are supported: 300; 600; 1200; 2400; 4800; 9600; 19,200; 38,400; 57,600; and
115,200 bps.
Battery
A battery is located under the battery cover of the MIG3500. Its purpose is to maintain the current date and time when the unit is turned off. The battery does not serve any other function. It is field replaceable.
Power Up/Power Down Behavior
When the MIG3500 is turned on, it runs through a series of diagnostic checks. If an internal fault is detected after the unit is fully operational, the FAULT LED turns on red momentarily, then the unit continually restarts. The LEDs do not indicate any particular error condition code.
When the MIG3500 is turned off, either manually or by a power failure, the firmware and vendor tables are retained within the flash image. When power is restored, the unit restarts and comes back online.
Metasys Integrator® 3500 Series Commissioning Guide 13
Resetting the MIG3500
The MIG3500 can be manually reset by depressing the Restart Switch located on top of the unit. You can access the switch by inserting a small opened paper clip
into the access hole (Figure 2 on page 11). An MIG3500 reset simply restarts the
unit. The restart process takes about 2 minutes to complete. The firmware and vendor tables are not affected by a manual reset.
Communication Cabling
Configuration Port Cabling
Figure 4 shows the connection between a laptop computer and the configuration
port on the Metasys Integrator unit.
Laptop Computer
(running VT100 Emulation software)
Metasys Integrator
Null Modem
Cable
Serial Port
(COM1/COM2)
Config Port - RS-232C
(Commissioning)
Figure 4: Connecting Computer to MIG3500 Config Port
As indicated, an RS-232 null modem cable is required between the Metasys
Integrator configuration port (Config Port - RS232C) and the computer’s serial port (for example, COM1). Total distance between the Metasys Integrator unit and
the computer can be 13 feet. Figure 5 shows cable pinouts for a computer with
either a 9 pin serial port or a 25-pin serial port.
If the computer has a 9-pin port, use this cable: If the computer has a 25-pin port, use this cable:
Config Port - RS232C on Metasys Integrator
DB-9 Female
Signal Pin
DCD
RD
TD
DTR
GND
DSR
RTS
CTS
COM1 or COM2 on Computer
DB-9 Female
Pin Signal
Config Port - RS232C on Metasys Integrator
DB-9 Female
Signal Pin
COM1 or COM2 on Computer
DB-25 Female
Pin Signal
RS-232 RS-232
1
6
7
8
4
5
2
3
4
6
8
7
1
5
3
2
DTR
TD
RD
DCD
GND
DSR
CTS
RTS
DCD
RD
TD
DTR
GND
DSR
RTS
CTS
1
6
7
8
4
5
2
3
(13 ft maximum) (13 ft maximum)
Figure 5: Cables for Connecting Computer to MIG3500 Config Port
20
6
5
4
8
7
2
3
DTR
TD
RD
DCD
GND
DSR
CTS
RTS
14 Metasys Integrator® 3500 Series Commissioning Guide
Vendor Port Cabling
The MIG3500 has two vendor ports: Vendor A - RS485 and Vendor B - RS232C.
If the vendor communications interface uses RS-485, you need an RS-485 cable between the Metasys Integrator Vendor A - RS485 terminal block and the vendor communications interface. If the vendor device uses RS-232, you need an RS-232 cable between the Metasys Integrator Vendor B - RS232C port and the vendor communications interface. For RS-232 cable pinouts, refer to the vendor-specific application note for the vendor equipment you are integrating. These application notes are available on the Johnson Controls QuickLit Product Literature Web site.
If the vendor equipment requires a second RS232 port, use the RS485B terminal block with the appropriate signal converter.
The RS-232 cable length between the Metasys Integrator unit and the vendor communications interface may not exceed 50 feet. The maximum length for
RS-485 cabling is 5,000 feet maximum without repeaters or 15,000 maximum with repeaters (or as instructed by the vendor equipment manufacturer).
IMPORTANT: For baud rates faster than 19,200 bps, the serial cables must be
shorter than 4 m (13 ft).
VT100 Terminal Emulator Setup
You can use any terminal emulation software, such as HyperTerminal, provided it
supports the VT100 Terminal type. See Table 4 for the settings that the MIG3500
requires. For more information on terminal emulation software setup, see the respective terminal emulator literature.
Table 4: VT100 Emulation Software Setup Parameters
Setting Value
Baud Rate
Data Bits
57600
8
Parity
Stop Bits
Flow Control
Terminal Emulation
No
1
None
VT100, VT102, or ANSI
Vendor Communication Tables (.VCT)
The .VCT files provided on the Metasys Integrator CD contain information that allows the Metasys Integrator unit to communicate with vendor equipment. The
Metasys Integrator unit can store up to 36 .VCT files.
Note: Refer to the vendor-specific application documents for the name of the
.VCT files you need to download. These documents are available on
QuickLit.
Advanced Diagnostics
You can view the Metasys Integrator’s operational status by selecting Advanced
Diagnostics from the Commissioning main menu (Figure 21).
Metasys Integrator® 3500 Series Commissioning Guide 15
Resetting the Metasys Integrator
The reset function available under Advanced Diagnostics in the Commissioning
main menu restarts the Metasys Integrator software. See Resetting the Metasys
Integrator on page 16. The Error Log screen helps you to determine the cause of
the last reset.
Recommissioning the Metasys Integrator
The Metasys Integrator unit must be recommissioned in the following circumstances:
•
upgrading to a new firmware revision (see Downloading the MIG3500 Code on page 17)
• downloading updates to an existing application
Error Log
Pressing F2 from the Advanced Diagnostics screen (Figure 29) accesses the Error
Log screen. The Error Log displays the cause of the last reset, as well as any other serious errors that may have occurred since the log was last cleared.
Note: If the error log contains an Exception Occurred! error, contact the Field
Support Center.
The log contains up to 256 entries. Once the error log reaches 256 entries, it no longer adds new entries. To allow for new entries, you must clear a full error log by selecting Yes from the Clear Error Log prompt.
Commissioning Overview
MIG3500 commissioning includes inspecting the installation, loading the Flash image (if required), setting the EOL switches, and connecting the communication
cables. These procedures are covered within the Detailed Procedures section.
Configuration Overview
MIG3500 configuration steps include downloading the vendor tables, configuring the ports, and verifying communication to the vendor equipment. These
procedures are covered within the Detailed Procedures section.
16 Metasys Integrator® 3500 Series Commissioning Guide
Detailed Procedures
To perform the following procedures, you should have:
• a laptop or desktop computer with the Metasys MIG Update Utility, which is available on the Metasys Integrator CD or the Johnson Controls Portal intranet site
• 1 FS10x 10/100 Netgear® switch (for example, FS105NA Netgear 5 Port or
10/100 is CompuCom #464163, Model FS105NA), or 1 W-Linx 5-port 10/100
Mini Hub (Universal Serial Bus [USB]) E63746 (part number SW-005CM-X), or 1 Netgear 5 Port or 10/100 Desktop switch (model FS605) connected to your computer
Note: Do not use any other hub or dual-speed hub.
• the Media Access Control (MAC) address of each MIG3500 you want to update (MAC address sticker located on the unit)
• null-modem serial cable (9- or 25-pin female)
• 2 RJ45 Ethernet patch cables (equivalent to CompuCom #131740, Model
A3L791-07)
• VT100 emulation software, such as HyperTerminal
Inspecting the Installation
To inspect the connections and wire terminations on the electronics board:
IMPORTANT: Prevent any static electric discharge to the MIG3500. Static
electric discharge can damage the unit and void any warranties.
1. If the Metasys Integrator unit is in an enclosure, open the enclosure door.
2. Examine the N2 terminal block for stray wire strands; loose screw terminals; and nicked, loose, or broken wires.
3. Check the wire insulation to ensure that it has not been stripped back so far as to cause a short, or that it is not tucked under a screw terminal.
4. Verify the wire polarity of the N2 Bus connection. (Check that each screw terminal of the N2 block has the same wire color entering as it does exiting.)
5. Verify that the power cable is properly connected.
Downloading the MIG3500 Code
This step is only required if the MIG3500 has lost its factory-installed code (flash image) or if a code update is required. If you cannot communicate with the
MIG3500 using the VT100 interface, then another download may be required to return the unit to its factory state. A tool called the Metasys MIG Update Utility is
used. If an update to the flash image is not required, go to the next section, Setting
the N2 Bus and RS485B End-of-Line Switches.
The MIG Update Utility has the following characteristics:
Metasys Integrator® 3500 Series Commissioning Guide 17
• must be run on a computer that has the Microsoft Windows® 2000
Professional, Microsoft Windows XP®, or Microsoft Windows Server 2003 operating system and Microsoft .NET Framework 1.1 or later installed
• updates only one MIG3500 at a time
• only one instance of the MIG Update Utility should be running in computer memory
• should not be used across a building network
• no other devices besides the computer and MIG3500 should be connected to the Ethernet switch or hub during the update process
• the cables used to connect to the switch or hub should be Category 5 computer network cables; crossover cables should not be used
• the FAULT LED is On during the update process, which is normal
To download or update the code for the MIG3500:
1. Connect the computer and MIG3500 to the Ethernet switch or hub. Turn on power to the MIG3500, the computer, and switch or hub.
2. After a few minutes, verify that the computer has received an IP address from the operating system. (If not, restart the computer once more.)
3. Start the Metasys MIG Update Utility on the computer. The Welcome screen
Figure 6: Metasys MIG Update Utility Welcome Screen
18 Metasys Integrator® 3500 Series Commissioning Guide
4. Click the Next button to continue. The Connection screen appears (Figure 7).
Figure 7: Connection Screen
Metasys Integrator® 3500 Series Commissioning Guide 19
5. Click the Next button to continue. The MAC Address Entry screen appears
Figure 8: MAC Address Entry Screen
Note: A selection for Update type is given, with Quick as the default. The
Extended update takes much longer to complete; do not use this
update unless Technical Support requests that you do so.
6. Select Quick and enter the MAC address of the MIG3500 you want to flash.
Refer to the MAC address sticker on the unit.
20 Metasys Integrator® 3500 Series Commissioning Guide
7. Press the Next button. The Update Device screen appears (Figure 9).
Figure 9: Update Device Screen
8. Click the View Log button if you want to display the log window that shows progress messages. Click Update Device. The Waiting for Response Screen
Metasys Integrator® 3500 Series Commissioning Guide 21
9. Cycle power to the MIG3500. Within a minute or so, the update process starts.
If you get the message Device will begin downloading necessary files and the files do not begin to download, cycle power on the MIG3500 again to restart the process.
Figure 10: Waiting for Response Screen
Note: If the device does not respond within a minute, a Warning message appears
(Figure 11). Try again by cycling power on the MIG3500, then clicking
Yes to continue. Or, click No to cancel the update and return to the
Welcome screen.
Figure 11: MIG3500 Not Responding to Update Request
22 Metasys Integrator® 3500 Series Commissioning Guide
During the update, a Progress screen indicates the approximate time left in the
Figure 12: Download Progress Screen
Metasys Integrator® 3500 Series Commissioning Guide 23
If the update was successful, the Completion screen appears (Figure 13). If the
update was unsuccessful, this screen indicates that the MIG3500 update
failed. Recheck the cable connections and try again.
Figure 13: Completion Screen
10. If you need to update another MIG3500, click Continue, which returns you to
the Welcome screen (Figure 6). If you have no other devices to update, click
Exit.
Within a few minutes, the RUN LED on the MIG3500 should stop flashing,
indicating it is ready for the next step. Go to Setting the N2 Bus and RS485B
24 Metasys Integrator® 3500 Series Commissioning Guide
Setting the N2 Bus and RS485B End-of-Line Switches
Network and field devices at either end of the N2 Bus and RS-485 network must be set as network terminated devices. The MIG3500 model has an EOL switch for
each of the two RS-485 terminal blocks (Figure 2). The switch labeled EOL A
applies to the N2 - RS485 (N2 Bus) terminal and the one labeled EOL B applies to the Vendor A - RS485 terminal. The MIG3500 is shipped with the EOL switch in
the factory default, ON (up) position (Figure 14). Set the EOL switches to the
appropriate positions for each MIG3500 in your network. For more details, refer to the N2 Communications Bus Technical Bulletin (LIT-636018).
EOL A
1
EOL B
1
RS485A
(N2 Bus)
RS485B
(Vendor A)
Figure 14: End-of-Line Switches on MIG3500
Installing DOWNPC and Vendor Communication Tables
You need to install the DOWNPC software on the commissioning computer before downloading the .VCT files. Be sure to have the Metasys Integrator CD-ROM labeled Tables and Models on hand.
To install the download software on your computer:
1. Insert the Metasys Integrator CD-ROM labeled Tables and Models in the
CD-ROM drive.
2. Run the setup.exe file on the CD-ROM and follow the on-screen instructions.
Alternatively, you can manually copy the files that you need from the Tables
and Models CD-ROM. If you do not know what files you need, run setup.exe.
Downloading Vendor Communication Tables
After installing the DOWNPC software, you can download the appropriate .VCT files to the Metasys Integrator unit. Up to 36 .VCTs may be downloaded.
Metasys Integrator® 3500 Series Commissioning Guide 25
To download the .VCT files:
1. Connect a null modem cable between the serial port on the laptop computer
(COM1 or COM2) and Config Port - RS232C on the MIG3500 (Figure 15). Do
not use the Vendor B - RS232C port.
Laptop Computer
(running VT100 Emulation software)
Metasys Integrator
Null Modem
Cable
Serial Port
(COM1/COM2)
Config Port - RS-232C
(Commissioning)
Figure 15: Connecting a Laptop Computer to the MIG3500
2. Using the computer, open a Disk Operating System (DOS) window.
3. At the command prompt, change to the directory where you installed the
DOWNPC software. The default is C:\MIG10\Tables.
4. Type DOWNPC (case insensitive) to start the Metasys Integrator Download
Utility. The following appears (Figure 16):
Figure 16: DOWNPC Utility - Selecting Serial Port
5. Accept the default (COM1) serial port or type COM2 to select this port on the computer that connects to Metasys Integrator commissioning port. (Note:
Serial ports COM3 and COM4 are not supported.)
26 Metasys Integrator® 3500 Series Commissioning Guide
6. Press Enter with the correct port selected. The screen shown in Figure 17
appears, prompting for the baud rate.
Figure 17: DOWNPC Utility - Selecting Baud Rate
7. Accept the 57600 default baud rate and press Enter. The screen shown in
Figure 18 appears, displaying currently available vendor communication table
files.
Figure 18: DOWNPC Utility - Selecting Vendor Table
8. Select a .VCT file to download in one of two ways:
• Type the name of the file to download in the File Name field. This name must match the name in the .VCT file as displayed on the Download screen.
• Select the file name from the .VCT file list by pressing the Tab key once,
then using the function keys listed in Table 5.
Table 5: Download Select Function Keys (Part 1 of 2)
Key Function
Tab
Backspace
Highlights the next file name in the list.
Highlights the previous file name in the list.
Metasys Integrator® 3500 Series Commissioning Guide 27
Table 5: Download Select Function Keys (Part 2 of 2)
Key Function
A through Z
Highlights the first file name beginning with that letter, if one exists.
PGUP (Page Up)
PGDN (Page Down)
Space Bar
F1 Key or Esc
Displays the previous page of file names.
Displays the next page of file names.
Highlights the next file name in the list.
Exits without downloading.
9. Press Enter. The screen shown in Figure 19 appears, briefly describing the
selected file.
Figure 19: Download Confirmation Screen
10. Press N to return to the .VCT file name list shown in Figure 18. Press Y to
begin downloading. The screen in Figure 20 appears.
Figure 20: Download in Progress Screen
The solid bar moves across the screen as the download continues. When complete, the following appears:
Download completed without errors
Press Any Key To Exit Download
If an error occurs, attempt the download again.
28 Metasys Integrator® 3500 Series Commissioning Guide
11. Press any key.
12. To download another table, type DOWNPC and start the procedure again.
Note: Do not download the same table more than once. A single table can be used
for multiple vendor devices of the same type.
13. Restart the VT100 Terminal emulation software.
14. Press F1 to refresh the Commissioning menu.
Configuring the MIG3500 with VT100 Interface
A VT100 emulation software program is used to communicate with and configure a new or updated MIG3500. Use the VT100 interface to establish the MIG3500’s configuration and parameters in flash memory.
Establishing Communication with MIG3500
To establish communication with the MIG3500:
1. Connect a null modem cable between the serial port on the laptop computer
(COM1 or COM2) and Config Port - RS232C on the MIG3500 (Figure 15). Do
not use the Vendor B - RS232C port.
2. Start the VT100 emulation software on the computer, using the settings listed
in Table 4. The Commissioning Menu appears (Figure 21). All commissioning
steps occur from this menu. This menu also lists contact information in case you need assistance with the product.
Note: The date and time displayed on the menu are not set until the MIG3500
is connected to the N2 Bus.
Figure 21: Metasys Integrator Commissioning Menu
Metasys Integrator® 3500 Series Commissioning Guide 29
Setting up Ports
To set up ports:
1. From the Commissioning menu (Figure 21), select Port Configuration. The
Port Configuration screen appears (Figure 22).
Figure 22: Port Configuration Screen
2. Either type the information or use the space bar to scroll through the valid options to enter information into each field. To move between fields, press
Enter or Tab, or use the arrow keys. The help line at the bottom of the screen displays information about the field you have currently selected.
• The N2 Port (P0) has fixed settings; do not change these settings.
• The P1 Commissioning port settings must match the VT-100 Emulator software settings.
• The Vendor A (P2/RS485) and Vendor B (P3/RS232C) settings must match the vendor equipment settings. The vendor equipment settings are listed in the vendor-specific application note.
• If your application has an RS-485 interface but you need to use the
RS232C port (P3), set the vendor port to RS485 and use an external signal converter. This converter is described in the vendor-specific application note.
3. Press F2 to save the information to Metasys Integrator database. The
Commissioning menu appears.
30 Metasys Integrator® 3500 Series Commissioning Guide
Connecting Vendor-Specific Cabling
To connect vendor-specific cabling:
• Refer to the vendor-specific application notes located in QuickLit for the cable pinouts.
• Assemble and connect the cabling between the Metasys Integrator unit and the vendor equipment.
Adding Vendor Devices to the Network
Note: See the vendor-specific application note for the correct vendor address and
timeout values.
Note: To add a vendor device to the network, you must have already downloaded
its vendor communication table. For details, see Downloading Vendor
Communication Tables on page 25.
To add a device to the network:
1. To avoid annoying messages at the Metasys system, disconnect the N2 Bus connection from the Metasys Integrator unit until proper communication with
the vendor equipment has been verified (see Verifying Vendor Device
Communications on page 33 and Verifying Point Data on page 35).
2. From the Commissioning menu, select the Network Modify/Add/Delete
option. The screen shown in Figure 23 appears.
Figure 23: Network Modify/Add/Delete Screen
3. Specify the network configuration for each of the vendor devices.
Metasys Integrator® 3500 Series Commissioning Guide 31
• To enter information in a field, you can either type the information or use the space bar to scroll through the valid options. To move between fields, press Enter or Tab, or use the arrow keys. The help line at the bottom of the screen displays information about the field that you have selected.
Note: N2 Address 0 can be defined at the Metasys Integrator unit, but cannot be
used at the Metasys system.
• To display the next screen of network addresses, press F3. Pressing F3 also saves the current screen of data.
• To go to a specific N2 address, press F4. Pressing F4 also saves the current screen of data.
4. Press F2 to save the information to the Metasys Integrator database and return to the Commissioning menu.
Modifying Vendor Devices
To modify the settings for a vendor device, add the device with the new settings:
1. Move the cursor to the Interface Type field of the device whose settings you
Note: If you need to change the Interface Type or Port selection, you need to
first delete the device, then re-add it selecting an appropriate Interface
Type or Port.
2. Press the space bar to scroll through the options until a blank name is selected.
3. Press F2 to delete the device.
4. Add the device by filling in the new settings.
5. Press F2 to save the changes.
Note: If communication is still in progress with the device deleted in Step 3, the
Metasys Integrator unit displays the following error message: Cannot add
until previous delete is completed.
Deleting Vendor Devices
To delete a device:
1. Move the cursor to the Interface Type field of the device you want to delete
2. Press the space bar to scroll through the options until a blank name is selected.
3. Press F2 to save the changes.
Note: If a scan is in progress for a deleted device, it is deleted after the scan is
complete.
32 Metasys Integrator® 3500 Series Commissioning Guide
Verifying Vendor Device Communications
To verify vendor device communication:
1. From the Commissioning menu, select the Device Diagnostics option. The
screen shown in Figure 24 appears.
Figure 24: Device Diagnostic Screen
2. Enter the device’s N2 address and press Tab or Enter twice.
3. If the vendor device is offline, press F2 to display the device specific Data
Analyzer to determine if there is any communication.
4. Press F3 to view the statistics for the next N2 address that has been defined at this Metasys Integrator unit.
Metasys Integrator® 3500 Series Commissioning Guide 33
5. If no devices for the vendor port are online, display the Vendor and N2 Port
Diagnostics screen (Figure 25) for vendor port statistics.
Figure 25: Vendor and N2 Bus Diagnostic Screen
6. From the Vendor and N2 Port Diagnostics screen, press F2 or F3 to display the
Port Analyzer. This helps you determine if communication occurs with any vendor device on the port.
7. For additional information on diagnostics fields, see Table 6 and Table 12. For
additional information on the serial data analyzer, see Using the Serial Data
Table 6: Diagnostic Fields (Part 1 of 2)
Field
N2 Address
Online
Description Normal
Readings
Device Vendor and
N2 Port
Vendor Device Statistics for Selected N2 Address
Selected N2 Address (with vendor table name)
Indicates whether device is currently online
Yes
X
X
Writes
X
Commands
Retries
Errors
Number of general communications messages
Number of commands to device
Number of retries for polls and writes for online devices only
Number of times a returned message from vendor device had an error (for example, a CRC or checksum error)
0 is ideal
0 is ideal
X
X
X
34 Metasys Integrator® 3500 Series Commissioning Guide
Table 6: Diagnostic Fields (Part 2 of 2)
Field
Offline
Reset Statistics
Transmissions per
Minute
Description Normal
Readings
0 is ideal Number of online to offline transitions for device at this vendor address
Allows you to reset statistics to zero
No is default
Port Statistics
Number of polls and writes that occurred in last minute
Depends on vendor device response time and poll delay
Point Scan Time
(seconds)
Port Buffer
Overruns
Suspect Bytes
Received
Framing Errors
Parity Errors
Number of seconds it takes for all points on this vendor trunk to be scanned
Depends on transmissions per minute, vendor device response time, and poll delay
0 is ideal Number of Vendor Port A,
Vendor Port B, and N2 Port input buffer overruns on the
UART’s First In-First Out
(FIFO)
Line Status Errors
Number of line status errors in general
Number of line status errors caused by framing errors
0 is ideal
0 is ideal
Number of line status errors caused by parity errors
0 is ideal
Device Vendor and
N2 Port
X
X
X
X
X
X
X
X
X
X
X
Verifying Point Data
Before mapping vendor points to the Metasys network, verify that vendor equipment and processes are operating properly. Use the Show Point Data screen to display current point data in the vendor controllers.
To view point data:
1. From the Commissioning menu, select the Show Point Data option. The following fields appear, prompting you to specify a point:
N2 Address [1] Point Type [AI] Point Address [1]
2. Enter the point’s network address, point type, and point address. To accept the default, press Enter. (If the cursor is in the N2 Address field, press Enter three times to accept the default.)
3. To move between fields, press Enter or Tab, or use the arrow keys. To scroll through the Point Type options (AI, BI, AO, BO, ADF, ADI, BD), press the space bar repeatedly when the cursor is in the Point Type field.
Metasys Integrator® 3500 Series Commissioning Guide 35
4. After you have specified the point, press Enter. The Show Point Data screen
appears. Figure 26 shows an example of a Show Point Data screen for an AI
point. (Each Show Point Data screen displays data appropriate to the point type.)
Figure 26: Show Point Data Screen
5. Press F3 to view the next point, which scrolls through the points. When the last point of a type is reached, the first point of the next type is displayed.
6. Press F1 to return to the Commissioning menu.
Saving Metasys Integrator Configuration
Record the settings for Metasys Integrator configuration. You can do this
manually, or use a screen capture utility. See Collecting Screen Data on page 43
for additional information.
Restarting Metasys Integrator Software
To restart Metasys Integrator software:
1. From the Advanced Diagnostics screen in the main menu, press F3. The Reset screen appears.
36 Metasys Integrator® 3500 Series Commissioning Guide
2. Change the reset option by using the space bar. Table 7 lists the Reset types
available.
Table 7: Types of Software Resets Available
Title Description
Reset Only
Resets Metasys Integrator unit without any effect on the firmware or vendor tables.
Reset and Destroy Metasys
Integrator Database
Cancel and Return to Main
Menu
Resets Metasys Integrator unit, but also erases the database that is currently stored in the unit. If you select this option, you need to recommission the unit by reloading all vendor tables.
Cancels this procedure and returns you to the Commissioning menu.
3. Press Enter to select and execute the option you choose.
Connecting MIG3500 to the Metasys System
After you have configured the MIG3500, you can connect it to the Metasys N2
Bus network. The MIG3500 is connected as a device on the N2 Bus that terminates to an NAE or Network Control Engine (NCE). Connect the MIG3500 to the N2
Bus network, then follow the instructions in Metasys Help for adding it as a new field device. Select the MIG device type and specify the correct N2 Bus address.
Also, be sure to use the resource file (.VCT file) for each vendor device that is connected to the MIG3500, so that you can easily select which points to map to the supervisory controller. For more details on the set of points that you can map, refer to the vendor-specific application notes available on QuickLit.
Verifying Online Status of MIG3500, Devices, and Objects
Follow these steps to verify the status of the MIG3500, its devices and objects:
1. Log on to the Metasys Site Management Portal User Interface (UI).
2. Locate the MIG3500 on the Navigation map and double-click on its name to verify its status is Online.
3. Open the summary of points under the MIG3500 and verify that each is online.
4. Resolve any issues for those points that are reporting offline.
Replacing a MIG300 Series with a MIG3500 Series
This section describes how to replace a MIG300 Series Metasys Integrator unit with the MIG3500 Series. Follow these steps:
1. Using your VT100 software, open the Port Configuration menu and record the communication port settings configured for the MIG300. Also, record the vendor tables currently in use by the MIG300. You need to configure the new
MIG3500 with these same settings and tables in a later step.
2. Put any critical equipment in manual mode while replacing the MIG300.
3. Disconnect all wiring from the MIG300 and remove the unit.
Metasys Integrator® 3500 Series Commissioning Guide 37
4. Install the MIG3500, referring to the MIG3500 Series Network Control Module
Installation Instructions (Part No. 24-10050-30) for details.
5. Connect the N2 Bus, any serial devices, and the MIG3500 power supply.
Neatly reroute wires and cables as necessary.
6. Turn on the MIG3500 and connect a computer directly to the Config Port -
RS232C port with a serial cable. Use VT100 interface software to configure
the MIG3500, using the settings recorded in Step 1. Also download vendor
tables; see Downloading Vendor Communication Tables on page 25 for details.
7. After configuration is complete, verify that the MIG3500 is communicating with the vendor equipment.
Replacing a Defective MIG3500
If an MIG3500 fails and must be replaced with a new MIG3500, the steps to swap out the old unit with a new one are relatively straightforward. Follow these steps:
1. Record the port and network settings used on the old unit.
2. Power down the old unit.
3. Disconnect all wiring from the old unit.
4. Unscrew the old unit from the enclosure.
5. Install the new unit in the same location as the old one.
6. Reconnect all wiring to the new unit.
7. Power up the new unit.
8. Commission the new unit with the same settings as the old one, including the download of the previous Metasys Integrator vendor table(s).
9. Verify that the new MIG3500 is communicating with the vendor equipment.
38 Metasys Integrator® 3500 Series Commissioning Guide
Troubleshooting
This section describes some of the most common problems encountered when setting up and operating the MIG3500. This section also provides general solution guidelines, and references to procedures and documents for resolving these
common problems. Table 12 provides a list of common MIG3500 problems and
their solutions.
This section is not a troubleshooting guide for Metasys system networks, customer
Local Area Networks (LANs), BAS networks, or the field devices connected to the
MIG3500. Troubleshooting field devices is covered in the field device documentation. Refer to the appropriate field device documentation for additional information.
Corrupted MIG3500 Memory
Corruption of MIG3500 flash memory may render an MIG3500 inoperable.
Corrupted flash memory may occur for a variety of reasons, and the typical recovery procedure is to redownload the MIG3500 code with the MIG Update
Utility. This procedure returns the unit to its factory default setting. When you return a unit to its factory condition, you must redownload the vendor tables as well. Once you complete this task, the unit should be back to an operational state.
Verifying N2 Bus Communication
The N2 network is confirmed when you open the Metasys Site Management Portal
UI software, define vendor devices and points, and display information about the points on the workstation screen.
If something does not work correctly:
• Verify that the vendor equipment is energized. If the vendor equipment is not online and communicating, the Metasys Integrator unit appears offline to the
NAE.
• Verify that the vendor points are appropriately defined in software.
• Recheck the N2 wiring connections throughout the network, including the N2 terminal blocks on the Metasys Integrator unit.
Using the N2 Bus Checkout Tool
Some Metasys Integrator jobs require extensive end-to-end checkout on site with vendor equipment and a supervisory system. The N2 Bus Checkout Tool allows engineers to do the checkout at the Metasys Integrator unit with a tool that uses the same table loaded in the Metasys Integrator unit. You can check out the vendor system and its interface with the Metasys Integrator unit from the Metasys
Integrator N2 terminals to the vendor equipment. The user interface accepts any
N2 address and a Release 5.0 or greater .VCT table as inputs.
Metasys Integrator® 3500 Series Commissioning Guide 39
The N2 Bus Checkout Tool requires the following:
• laptop computer with an available serial port or an available Universal Serial
Bus (USB) port for use with a USB-to-serial adapter
• RS-232 to RS-485 converter
•
RS-232 cable configured as shown in Figure 27
Serial Port 1 or 2 on Laptop Computer
RS-232 Connector on Converter
DB-9 Female
Signal Pin
DB-25 Male
Pin
Signal
RS-232
RD
TD
GND
RTS
2
3
5
7
3
2
7
4
RD
TD
GND
RTS
(50 ft maximum)
Figure 27: Cable Pinouts for N2 Bus Checkout Tool
Connect the cable between the serial port on the laptop computer to the serial connector on the converter. Then attach the RS-485 (N2) wires from the converter to the Metasys Integrator N2 Bus terminal connection.
Table 8 shows the available mouse sensitive operation fields displayed between the
dashed delimiter lines. Click the mouse on these items to execute the function.
Table 8: Mouse Sensitive Function Keys
Function Key Operation Performed
AI
BI
Select AI points for display.
Select BI point for display.
AO
BO
ADF
ADI
BD
RSt
NuAdr
NuVct
Pgdn
PgUp
Exit
Select AO points for display.
Select BO points for display.
Select ADF points for display.
Select ADI points for display.
Select BD points for display.
Reset N2 statistics.
Select a new N2 address (1 to 255).
Select a new .VCT file name.
Page down the points list.
Page up the points list.
Return to DOS (the Alt-X key does the same).
40 Metasys Integrator® 3500 Series Commissioning Guide
Table 9 shows point counts and Table 10 shows the statistics that are displayed on
the right-hand side of the screen. The N2 Statistics values roll over at 65535.
Table 9: Point Counts
Point
AI
Description
Count of Analog Inputs in current table
BI
AO
BO
ADF
ADI
BD
Count of Binary Inputs in current table
Count of Analog Outputs in current table
Count of Binary Outputs in current table
Count of Analog Data Floats in current table
Count of Analog Data Integers in current table
Count of Binary Data (Byte) in current table
Table 10: N2 Statistics
N2 Statistics
Poll
Data
OvrC
RelC
COSs
NAks
CksE
LnSE
RTry
OffL
Description
Number of polls
Number of data requests
Number of override commands
Number of release commands
Number of change-of-state responses
Number of negative acknowledge responses
Number of checksum errors
Number of line status errors
Number of retries
Number of offline occurrences
Figure 28 shows a screen snapshot of the tool in use.
To perform the check:
1. Remove all N2 connections other than the RS-485 connection from the converter that is attached to the Metasys Integrator unit.
2. Start the N2 Bus Checkout Tool from the DOS command line by typing the command N2CHECK 1 for COM1 or N2CHECK 2 for COM2.
3. Click NuAdr to select an N2 address.
4. Click NuVct to select the same .VCT that you downloaded into the Metasys
Integrator unit.
5. Use the mouse to select the point type you want to inspect or command.
6. Command AO and BO point types by clicking on the point line and entering a new value.
7. Click on the point line and press the Esc key to perform a release command.
8. Press the Alt+X key to exit to DOS.
Metasys Integrator® 3500 Series Commissioning Guide 41
Metasys Integrator N2 Bus Checkout Tool at address 1 using rileyhsp.vct
--------------------------------------------------------------------------
AI BI AO BO ADF ADI BD RSt NuAdr NuVct PgDn PgUp Exit
---------------------------------------------------------------------------
AO 1 67.100 PICU 1 Supply Airflow Setpoint........ | -Pt Count-
AO 2 0.000 PICU 1 Min Exhaust Airflow Setpoint... | AI 30
AO 3 0.000 PICU 2 Supply Airflow Setpoint........ | BI 16
AO 4 0.000 PICU 2 Min Exhaust Airflow Setpoint... | AO 32
AO 5 0.000 Anteroom Supply 1 Airflow Setpoint.... | BO 0
AO 6 0.000 Anteroom Supply 2 Airflow Setpoint.... | ADF 0
AO 7 0.000 Anteroom Min Exhaust Airflow Setpoint. | ADI 0
AO 8 0.000 PICU 1 Pressure Setpoint.............. | BD 0
AO 9 0.000 PICU 2 Pressure Setpoint.............. |
AO 10 0.000 Anteroom Pressure Setpoint............ | -N2 Stats-
AO 11 0.000 Iso-Tek 0 High Alarm Setpoint......... | Poll 0
AO 12 0.000 Iso-Tek 0 Low Alarm Setpoint.......... | Data 0
AO 13 0.000 Iso-Tek 1 High Alarm Setpoint......... | OvrC 0
AO 14 0.000 Iso-Tek 1 Low Alarm Setpoint.......... | RelC 0
0 AO 15 0.000 Iso-Tek 2 High Alarm Setpoint......... | COSs 0
0 AO 16 0.000 Iso-Tek 2 Low Alarm Setpoint.......... | Naks 0
AO 17 0.000 PICU 3 Supply Airflow Setpoint........ | CksE 0
AO 18 0.000 PICU 3 Min Exhaust Airflow Setpoint... | LnSE 0
X AO 19 0.000 PICU 4 Supply Airflow Setpoint........ | RTry 100
Figure 28: Show Point Data Screen
Using the Serial Data Analyzers
The commissioning software provides serial data analyzers for troubleshooting communication between the Metasys Integrator unit and the vendor devices. The serial data analyzers collect data from the devices on a vendor port. This data aids in establishing whether communication occurs. The available operations are as follows:
• To access the device specific serial data analyzer from the Device Diagnostics screen, enter F2.
• To access the vendor port serial data analyzer from the Port Diagnostic screen, enter F2 for Vendor Port A or F3 for Vendor Port B.
• To pause the flow of data, press F4. To resume the flow of data, press F4 again.
To exit the serial data analyzer, press F1.
• To return to the Diagnostics screen, press F2.
• To view a log of the last abnormal events that occurred on a particular port, press F3 from that port’s serial data analyzer screen.
• To capture the data being sent to the screen in a text file, copy the contents of the screen and paste into a text file.
If you need help interpreting the data, call your product supplier.
42 Metasys Integrator® 3500 Series Commissioning Guide
Collecting Screen Data
You may need to collect Metasys Integrator screen data when getting help from a technical support person. Use the capture text function of Microsoft
HyperTerminal to save incoming data to a text file. E-mail this file to your technical support representative using the contact information that appears on the
MIG3500 Commissioning Menu.
Using Advanced Diagnostics
Table 11 provides information on advanced diagnostics fields.
Table 11: Advanced Diagnostics Fields (Part 1 of 2)
Field
MAC Address
IP Address
Date of Manufacture
Description Normal or
Example Reading
Metasys Integrator 300 Flash Statistics
Similar to a serial number, every
MIG3500 Series has a unique
6-byte Media Access Control (MAC) address (displayed in dotteddecimal notation).
Identifies the IP address assigned to the MIG3500.
Note: Typically, the IP address consists of all zeros, because an Ethernet connection is not used for device communication, unless its firmware is being updated.
The date the Metasys Integrator firmware was manufactured.
00.10.8D.01.A1.45
000.000.000.000
July 5 2008
Application Revision
10.0.0.0000
OS Revision
CPU Usage
Current Free
1
N2 Database Using
Revision number of the firmware application.
Revision number of the operating system.
CPU Utilization
Percentage of total task utilization
Allocated Memory Statistics
Memory available for tables and N2 database in bytes, and as a percentage of the total allocated.
Memory used for the N2 database in bytes and as a percentage of total allocated. The N2 database stores point data for all vendor points.
Memory is used as follows: 119 bytes overhead for each N2 address added, plus:
• 27 bytes for each AI point
• 5 bytes for each ADF point
• 3 bytes for each BI point
• 3 bytes for each BO point
• 3 bytes for each ADI point
• 7 bytes for each AO point
• 2 bytes for each BD point
2.1.20.4
0 to 100
447158
89.4%
8160
1.6%
Metasys Integrator® 3500 Series Commissioning Guide 43
Table 11: Advanced Diagnostics Fields (Part 2 of 2)
Field
VCTs Using
Total
Lowest Free
Current Free
Largest Block Free
Total
Lowest Free
Description
Amount of memory used for the downloaded vendor communication control tables in bytes and as a percentage of total allocated
Total amount of allocated memory in use.
Smallest block of free acquired memory currently available.
Acquired Memory Statistics
Memory available for tables and N2 database in bytes, and as a percentage of the total acquired.
Largest block of free acquired memory currently available.
Total amount of acquired memory in use.
Smallest block of free acquired memory currently available.
Normal or
Example Reading
20951
4.2%
500000
447158
89.4%
150000
100%
150000
100%
150000
149708
99.8%
1.
The current free allocated memory should not be less than 10%.
Figure 29 shows an example of an Advanced Diagnostics screen.
Figure 29: Advanced Diagnostics Screen Example
44 Metasys Integrator® 3500 Series Commissioning Guide
MIG3500 Troubleshooting Guide
Use the information in Table 12 to assist in diagnosing and solving potential
MIG3500 operational problems.
Table 12: MIG3500 Troubleshooting Guide (Part 1 of 3)
Symptom Cause Solution
Metasys MIG Update
Utility fails to download the device.
MIG3500 was not power cycled or reloaded.
Incorrectly defined
MAC address.
After clicking the Update Device button, you need to cycle power on the MIG3500 to continue the update process.
Verify that the MAC address of the device you specified is correct. A MAC address sticker on the unit indicates the correct address to use.
VT100 Terminal
Emulation software is unable to connect to the Metasys Integrator unit
Metasys Integrator unit cannot talk to the vendor device
Point is unreliable (use
Show Point Data menu option).
Point values are incorrect, but point is reliable.
Crossover cable is used directly between the computer and
MIG3500.
Bad patch cables
Computer has no IP address.
Use a standard Ethernet patch cable with a network switch or hub between the computer and the MIG3500.
Use reliable patch cables between the devices.
Restart the computer and wait a few minutes for the operating system to assign an IP address. Addresses are handed out to any two computers set for dynamic addressing and connected via an Ethernet switch.
Remove all devices from the network switch or hub except the computer and MIG3500.
Communication problem
VT100 settings are not correct.
There is incorrect cabling.
Cable is not connected.
Incorrect cable is being used.
• Verify that the computers’ settings match the commissioning port settings, which should be: 57600,8,1,N.
• Verify that the Terminal emulation mode is set to VT100, not
Auto.
• Verify that the computer is connected to the commissioning port (P1 connector) on the electronics board.
• Verify that the RS-232 cable pinouts are correct as described
• Verify that the cables are properly plugged into vendor ports.
• Verify that the vendor device is connected and powered up.
Verify that the cable between the Metasys Integrator unit and vendor device matches the cable specified in the vendor application document.
Verify that the vendor port setup matches the settings specified in the vendor application document.
Incorrect settings on the Port
Configuration screen.
An incorrect vendor address is entered in the Network Modify/
Add/Delete screen.
Verify that the vendor address entered in the Network Modify/
Add/Delete screen is left justified.
The device is offline.
Verify that the device is online.
The point does not exist at the vendor device.
Verify that the point exists at the vendor device.
Custom firmware has not been downloaded.
Commissioned with an incorrect .VCT.
Vendor equipment setup is incorrect.
If using a custom application that requires custom firmware, verify that this firmware has been downloaded.
Verify that the correct vendor communication table (.VCT) is being used.
Refer to vendor documents.
Metasys Integrator® 3500 Series Commissioning Guide 45
Table 12: MIG3500 Troubleshooting Guide (Part 2 of 3)
Symptom Cause Solution
Metasys Integrator unit resets automatically.
The Metasys
Integrator unit has encountered a serious software error.
• View the Error Log screen (from the Advanced Diagnostics screen, press F2).
• Call the Field Support Center.
Metasys Integrator unit resets cyclically.
Reflash the unit and reload the VCTs.
If this behavior continues, save the error log file, then contact the
Field Support Center.
Device repeatedly toggles online and offline.
The Metasys
Integrator unit has encountered a serious software error.
Commissioned with incorrect .VCT.
The 485 converter is malfunctioning.
The vendor device does not support commands.
Battery may be dead.
Verify that the correct application for the device is being used.
If a 485 or 422 port-powered converter is being used, use a converter that includes a power supply.
If you are sending commands, verify that the device is commissioned to support commands. Be aware that the Auto
Restore functions of Metasys NCM, Companion, or N30 resends commands as devices report online.
Replace the battery with Panasonic® CR2025 or equivalent.
Current date and time are not retained after a restart or shutdown.
Continuous line status errors occur for an
RS-485 vendor trunk.
The vendor communication trunk is experiencing excessive noise or is unbalanced.
Various
Verify End-of-Line (EOL) resistor and cable shield requirements and installation.
MIG3500 is offline to the supervisory controller.
N2 address mismatch.
Be sure that 24 VAC power is connected correctly and that the
RUN LED is on steady.
Be sure that communication terminal blocks and other communication connectors are firmly in place.
Check that the wiring is the correct size
(18 AWG minimum for power, 18 AWG for N2 Bus, 26 AWG for
Ethernet communication).
Check that you have set the correct baud rate on each connected device.
Check the integrity of the wires and cables.
Be sure that the vendor equipment is online.
Check the N2 address defined on the Network Modify/Add/
Delete screen of the Metasys Integrator unit to verify it matches the N2 address defined at the supervisory controller.
46 Metasys Integrator® 3500 Series Commissioning Guide
Table 12: MIG3500 Troubleshooting Guide (Part 3 of 3)
Symptom Cause Solution
Devices on MIG3500’s
N2 Bus are offline.
N2 Bus not connected or wired incorrectly.
Verify that the N2 Bus is connected to the RS485A (N2 Bus) terminal and securely wired in correct polarity.
N2 EOL switches not set properly.
Check that the MIG3500’s N2 End-of-Line (EOL) switch is set correctly. Refer to the Setting Terminations section of the N2
Communications Bus Technical Bulletin
(LIT-636018) for details on N2 EOL terminations.
Check power and wiring to the vendor device.
Vendor device is offline.
Continual application failure.
Call the Field Support Center for assistance.
MIG3500 continually resets every few minutes.
FAULT LED flickers, then unit restarts.
Continues to restart repeatedly.
RUN LED continues to blink once every second, even several minutes after MIG3500 was turned on.
Internal fault has occurred.
MIG3500 is waiting to be commissioned.
Call Field Support Center for assistance.
Update the controller with the Metasys MIG Update Utility, then try to communicate with it again using the VT100 emulation program.
Technical Specifications
MIG3500 Model (Part 1 of 2)
Product Code Number
MS-MIG3520-0
Power Requirement
Power Consumption
Ambient Operating Temperature
Ambient Operating Conditions
Ambient Storage Temperature
Ambient Storage Conditions
Battery
Processor
Memory
Operating System
Network and Serial Interfaces
Dimensions
(Height x Width x Depth)
Dedicated nominal 24 VAC, Class 2 power supply (North America), Safety
Extra-Low Voltage (SELV) power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum)
25 VA maximum
0 to 50
°C (32 to 122°F)
10 to 90% RH, 30
°C (86°F) maximum dew point
-40 to 70
°C (-40 to 158°F)
5 to 95% RH, 30
°C (86°F) maximum dew point
Panasonic CR2025 - Lithium non-rechargeable battery: 3.0 V 160 mAh, with a typical life of 5 to 7 years at 21
°C (70°F)
192 MHz Renesas™ SH4 7760 RISC 32-bit processor
128 MB Flash nonvolatile memory
128 MB Synchronous Dynamic Random Access Memory (SDRAM)
Microsoft Windows CE embedded Release 5.0
One Ethernet port; 10/100 Mbps; 8-pin RJ-45 connector
One optically isolated RS-485 port; 9600 bps; pluggable and keyed 4-position terminal block (for N2 Bus connection)
One optically isolated RS-485 port; pluggable and keyed 4-position terminal block
(for vendor device connection)
One RS232C serial port with standard 9-pin sub-D connector
(for commissioning purposes only)
One RS232C serial port with standard 9-pin sub-D connector
(for vendor device connection)
131 x 270 x 62 mm (5.2 x 10.6 x 2.5 in.)
Minimum space for mounting: 210 x 350 x 110 mm (8.3 x 13.8 x 4.3 in.)
Metasys Integrator® 3500 Series Commissioning Guide 47
MIG3500 Model (Part 2 of 2)
Housing
Mounting
Compliance
Shipping Weight
Plastic housing material: ABS + polycarbonate
Protection: IP20 (IEC60529)
On flat surface with screws on three mounting clips or a single 35 mm DIN rail
(DIN rail mount recommended)
United States
UL Listed (PAZX), UL 916
FCC compliant, CFR47, Part 15, Class B
Canada
UL Listed (PAZX7), CAN/CSA C22.2 No. 205
Industry Canada compliant
Europe
EMC Directive, 89/336/EEC
Australia/New Zealand
C-Tick mark compliant
1.2 kg (2.7 lb)
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2008 Johnson Controls, Inc.
Metasys Integrator® 3500 Series Commissioning Guide 48
Published in U.S.A.
www.johnsoncontrols.com
advertisement
Key Features
- Integrates third-party devices with Metasys
- Allows monitoring and control of third-party devices from a single Metasys workstation
- Supports multiple vendor devices
- Communication via RS-232 and RS-485 ports
- Download vendor tables for device configuration
- Advanced Diagnostics feature for troubleshooting
- Firmware upgrade capability
Frequently Answers and Questions
How do I connect a vendor device to the Metasys Integrator 3500?
What vendor communication tables are needed for my equipment?
How can I troubleshoot communication issues with a vendor device?
Related manuals
advertisement
Table of contents
- 5 Introduction
- 5 Related Documentation
- 6 MIG3500 Commissioning Overview
- 6 About the MIG3500 Metasys Integrator
- 7 Metasys Network with the MIG3500
- 8 Comparison between Metasys Integrator 300 and 3500 Series
- 9 Communication Port Comparison: MIG300 and MIG3500 Series
- 9 Required Hardware
- 10 Required Software
- 11 MIG3500 Components
- 12 System Status LEDs
- 12 Config Port - RS232C
- 13 Vendor B - RS232C Port
- 13 RJ-45 8-Pin Ethernet Port
- 13 N2 Bus RS485 Port
- 13 Vendor A - RS485 Port
- 13 Battery
- 13 Power Up/Power Down Behavior
- 14 Resetting the MIG3500
- 14 Communication Cabling
- 14 Configuration Port Cabling
- 15 Vendor Port Cabling
- 15 VT100 Terminal Emulator Setup
- 15 Vendor Communication Tables (.VCT)
- 15 Advanced Diagnostics
- 16 Resetting the Metasys Integrator
- 16 Recommissioning the Metasys Integrator
- 16 Error Log
- 16 Commissioning Overview
- 16 Configuration Overview
- 17 Detailed Procedures
- 17 Inspecting the Installation
- 17 Downloading the MIG3500 Code
- 25 Setting the N2 Bus and RS485B End-of-Line Switches
- 25 Installing DOWNPC and Vendor Communication Tables
- 25 Downloading Vendor Communication Tables
- 29 Configuring the MIG3500 with VT100 Interface
- 29 Establishing Communication with MIG3500
- 30 Setting up Ports
- 31 Connecting Vendor-Specific Cabling
- 31 Adding Vendor Devices to the Network
- 32 Modifying Vendor Devices
- 32 Deleting Vendor Devices
- 33 Verifying Vendor Device Communications
- 35 Verifying Point Data
- 36 Saving Metasys Integrator Configuration
- 36 Restarting Metasys Integrator Software
- 37 Connecting MIG3500 to the Metasys System
- 37 Verifying Online Status of MIG3500, Devices, and Objects
- 37 Replacing a MIG300 Series with a MIG3500 Series
- 38 Replacing a Defective MIG3500
- 39 Troubleshooting
- 39 Corrupted MIG3500 Memory
- 39 Verifying N2 Bus Communication
- 39 Using the N2 Bus Checkout Tool
- 42 Using the Serial Data Analyzers
- 43 Collecting Screen Data
- 43 Using Advanced Diagnostics
- 45 MIG3500 Troubleshooting Guide
- 47 Technical Specifications
- 47 MIG3500 Model (Part 2 of 2)