- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- BlueWalker
- PowerWalker VFI 10000C LCD
- Operating instructions
BlueWalker PowerWalker VFI 6000C LCD Operating instructions
Add to my manuals
27 Pages
BlueWalker PowerWalker VFI 10000C LCD is a reliable and efficient online UPS system designed to protect critical loads from power disturbances. With its advanced features and robust design, it offers exceptional power quality and long-lasting backup support, making it ideal for various applications such as data centers, telecommunications, and industrial environments.
advertisement
Online UPS
PowerWalker 6000C LCD / PowerWalker 10000C LCD
PowerWalker VFI 6000C/R LCD / PowerWalker VFI 10000C/R LCD
EN
Manual (EN)
Uninterruptible Power Supply System
EN
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
1
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS ................................................................................................................... 3
1-1.
T
RANSPORTATION AND
S
TORAGE
............................................................................................................................. 3
1-2.
P
REPARATION
................................................................................................................................................... 3
1-3.
I
NSTALLATION
................................................................................................................................................... 3
1-4.
O
PERATION
...................................................................................................................................................... 4
1-5.
S
TANDARDS
..................................................................................................................................................... 4
2. INSTALLATION AND OPERATION .................................................................................................................... 5
2-1.
U
NPACKING AND
I
NSPECTION
................................................................................................................................. 5
2-2.
R
EAR
P
ANEL
V
IEW
.............................................................................................................................................. 5
2-3.
S
INGLE
UPS I
NSTALLATION
................................................................................................................................... 7
2-4.
S
OFTWARE
I
NSTALLATION
..................................................................................................................................... 9
3. OPERATIONS .................................................................................................................................................. 10
3-1.
B
UTTON
O
PERATION
......................................................................................................................................... 10
3-2.
LED I
NDICATORS AND
LCD P
ANEL
........................................................................................................................ 10
3-3.
A
UDIBLE
A
LARM
.............................................................................................................................................. 12
3-4.
S
INGLE
UPS O
PERATION
.................................................................................................................................... 13
3-5.
A
BBREVIATION
M
EANING IN
LCD D
ISPLAY
................................................................................................................ 15
3-6.
LCD S
ETTING
................................................................................................................................................. 16
3-7.
O
PERATING
M
ODE
/S
TATUS
D
ESCRIPTION
................................................................................................................ 21
3-8.
F
AULT
C
ODE
................................................................................................................................................... 22
3-9.
W
ARNING
I
NDICATOR
........................................................................................................................................ 23
4. TROUBLE SHOOTING ..................................................................................................................................... 24
5. STORAGE AND MAINTENANCE ....................................................................................................................... 25
5-1.
S
TORAGE
....................................................................................................................................................... 25
5-2.
M
AINTENANCE
................................................................................................................................................ 25
6. SPECIFICATIONS ........................................................................................................................................... 26
EN
2
EN
1. Safety and EMC instructions
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1-1. Transportation and Storage
Please transport the UPS system only in the original package to protect against shock and impact.
The UPS must be stored in the room where it is ventilated and dry.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment.
The UPS system must be absolutely dry before being installed. Please allow at least two hours for the
UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)) to the UPS output sockets or terminal.
Place cables in such a way that no one can step on or trip over them.
Do not block air vents in the housing of UPS. The UPS must be installed in a location with good ventilation. Ensure enough space on each side for ventilation.
UPS has provided earthed terminal, in the final installed system configuration, equipotential earth bonding to the external UPS battery cabinets.
The UPS can be installed only by qualified maintenance personnel.
An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation.
An integral single emergency switching device which prevents further supply to the load by the
UPS in any mode of operation should be provided in the building wiring installation.
Connect the earth before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical laws and regulations.
3
1-4. Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.
1-5. Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2
Radiated Emission..................................:IEC/EN 62040-2
*EMS
Category C3
Category C3
ESD.........................................................:IEC/EN 61000-4-2 Level 4
RS........................................................ ...:IEC/EN 61000-4-3 Level 3
EFT......................................................... :IEC/EN 61000-4-4 Level 4
SURGE................................................... :IEC/EN 61000-4-5 Level 4
CS........................................................... :IEC/EN 61000-4-6 Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8 Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning:
This is a product for commercial and industrial application in the second environment-installation restrictions or additional measures may be needed to prevent disturbances.
EN
4
EN
2. Installation and Operation
There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
Model Type Model Type
6K
6KR
10K
10KR
Standard model
6KL
6KRL
10KL
10KRL
Long-run model
2-1. Unpacking and Inspection
Unpack the package and check the package contents. The shipping package contains:
● One UPS
● One user manual
● One monitoring software CD
● One RS-232 cable (option)
● One USB cable
● One battery cable (option)
NOTE:
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts. Please keep the original package in a safe place for future use.
2-2. Rear Panel View
Diagram1: 6K/10K Rear Panel
5
Diagram 2: 6KL/10KL Rear Panel Diagram 3: 6K(L)/10K(L) Input/Output Terminal
Diagram 4: 6KR(L)/10KR(L) Rear Panel Diagram 5: Rack Input/Output Terminal
Diagram 6: Rack Battery Pack Rear Panel
1.
External battery connector
2.
RS-232 communication port
3.
Intelligent slot
4.
USB communication
5.
Emergency power off function connector (EPO connector)
6.
Cooling fan
7.
Input circuit breaker
8.
Input/Output terminal (Refer to Diagram 3 and 5 for the details)
9.
Maintenance bypass switch
10.
Output terminal
6
EN
EN
11.
Grounding terminal
12.
Utility input terminal
13.
External maintenance bypass switch port
14.
Battery pack output circuit breaker
2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following instructions by professional personnel.
1) Make sure the mains wire and breakers in the building are in compliance with the standard of rated capacity of UPS to avoid the hazards of electric shock or fire.
NOTE:
Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
6K
6KL
10K
10KL
Input
10
10
8
8
Wiring spec (AWG)
Output Battery
10
10
8
8
10
8
Ground
10
10
8
8
NOTE 1:
The cable for 6K/6KL should be able to withstand over 50A current. It is recommended to use 10AWG or thicker wire for safety and efficiency.
NOTE 2:
The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to use 8AWG or thicker wire for safety and efficiency.
NOTE 3:
The selections for color of wires should be followed by the local electrical laws and regulations.
5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!)
Output Line
Output Neutral
Input Neutral
Input Line
Ground
Terminal Block wiring diagram for 6K(L)/10K(L)
NOTE 1:
Make sure that the wires are connected tightly with the terminals.
7
NOTE 2:
Please install the output breaker between the output terminal and the load, and the breaker should be qualified with leakage current protective function if necessary.
6) Put the terminal block cover back to the rear panel of the UPS.
Warning:
(Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the external battery. The battery type and voltage and numbers may be different. If you connect them together, it maybe causes the hazard of electric shock or fire!
EN
Warning:
(Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
Warning:
● For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But for other external battery pack, make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
NOTE:
Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the numbers of the battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
● Pay highly attention to the polarity marking on external battery terminal block, and make sure the correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
8
EN
● Make sure the protective earth ground wiring is correct. The current spec, color, position, connection and conductance reliability of wire should be checked carefully.
● Make sure the utility input & output wiring is correct. The current spec, color, position, connection and conductance reliability of wire should be checked carefully. Make sure the L/N terminal is correct, not reverse or short-circuited.
2-4. Software Installation
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
9
3. Operations
3-1. Button Operation
Button
ON/Enter Button
OFF/ESC Button
Function
Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS.
Enter Key: Press this button to confirm the selection in setting menu.
Turn off the UPS: Press and hold the button more than 0.5s to turn off the UPS.
Esc key: Press this button to return to last menu in setting menu.
Test/Up Button
Mute/Down Button
Battery test: Press and hold the button more than 0.5s to test the battery while in AC mode, or CVCF mode.
UP key: Press this button to display next selection in setting menu.
Mute the alarm: Press and hold the button more than 0.5s to mute the buzzer.
Please refer to section 3-4-9 for details.
Down key: Press this button to display previous selection in setting menu.
Test/Up +
Mute/Down Button
Press and hold the two buttons simultaneous more than 1s to enter/escape the setting menu.
* CVCF mode means converter mode.
3-2. LED Indicators and LCD Panel
LCD panel
EN
LED Indicators:
There are 4 LEDs on front panel to show the UPS working status:
Mode LED Bypass Line
UPS Startup
Bypass mode
AC mode
Battery mode
CVCF mode
Battery Test
Fault
●
●
○
○
○
●
○
●
○
●
○
●
●
○
Note:
●
means LED is lighting, and
○
means LED is faded.
Battery
●
○
●
○
●
○
○
LED indicators
Fault
●
○
○
○
○
○
●
10
EN
LCD Panel:
Display Function
Backup time information
Indicates the backup time in numbers.
H: hours, M: minutes, S: seconds
Fault information
Indicates that the warning and fault occurs.
Indicates the fault codes, and the codes are listed in details in section 3-9.
Mute operation
Indicates that the UPS alarm is disabled.
Output & Battery voltage information
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the output is short.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
Indicates the Inverter circuit is working.
Indicates the output is working.
11
Battery information
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
3-3. Audible Alarm
Description
UPS status
Bypass mode
Battery mode
Fault mode
Warning
Overload
Low battery
Battery unconnected
Over charge
EPO enable
Fan failure/Over temperature
Charger failure
IP fuse broken
Overload 3 times in 30min
EPO status
Cover of maintain switch is open
Fault
Bus start failure
Bus over
Bus under
Bus unbalance
Inverter soft start failure
High Inverter voltage
Low Inverter voltage
Inverter output short circuited
Negative power fault
Battery SCR short circuited
Inverter relay short circuited
Over temperature
CPU communication failure
Overload
Buzzer status
Beeping once every 2 minutes
Beeping once every 4 seconds
Beeping continuously
Beeping twice every second
Beeping once every second
Beeping continuously
Muted
Yes
No
Yes
EN
12
EN
3-4. Single UPS Operation
1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the step only available for long-run model). Then set the input breaker at “ON” position. At this time the fan is running and the UPS supplies power to the loads via the bypass. The UPS is operating in
Bypass mode.
NOTE:
When UPS is in Bypass mode, the output voltage will directly power from utility after you switch on the input breaker. In Bypass mode, the load is not protected by UPS. To protect your precious devices, you should turn on the UPS. Refer to next step.
2) Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.
3) A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will operate in Battery mode without interruption.
NOTE:
When the UPS is running out battery, it will shut down automatically at Battery mode. When the utility power is restored, the UPS will auto restart in AC mode.
2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press and hold the “ON” button for 0.5s to turn on the UPS, and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
3. Connect devices to UPS
After the UPS is turned on, you can connect devices to the UPS.
1) Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total load level.
2) If it is necessary to connect the inductive loads such as a printer, the in-rush current should be calculated carefully to see if it meets the capacity of the UPS, because the power consumption of this kind of loads is too big.
3) If the UPS is overload, the buzzer will beep twice every second.
4) When the UPS is overload, please remove some loads immediately. It is recommended to have the total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system safety.
5) If the overload time is over acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is over acceptable time listed in spec at Battery mode, the UPS will become fault status. At this time, if bypass is enabled, the UPS will power to the load via bypass. If bypass function is disabled or the input power is not within bypass acceptable range, it will cut off output directly.
4. Charge the batteries
1) After the UPS is connected to the utility power, the charger will charge the batteries automatically except in Battery mode or during battery self-test.
2) Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than expected time.
13
3) Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for detailed setting) is consistent to real connection.
4) The charging current can be changed from 0.5A to 6A via LCD or software. Please make sure that the charging current is suitable to battery specification.
5. Battery mode operation
1) When the UPS is in Battery mode, the buzzer will beep according to different battery capacity. If the battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery voltage drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that the battery is at low level and the UPS will shut down automatically soon. Users could switch off some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no more load to be switched off at that time, you have to shut down all loads as soon as possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer.
3) The backup time of the long-run model depends on the external battery capacity.
4) The backup time may vary from different environment temperature and load type.
5) When setting backup time for 16.5 hours (default value from LCD panel), after discharging 16.5 hours, UPS will shut down automatically to protect the battery. This battery discharge protection can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section)
6. Test the batteries
1) If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you could press the “Test” button to let the UPS do battery self-test.
2) Users also can set battery self-test through monitoring software.
7. Turn off the UPS with utility power supply in AC mode
1) Turn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once. The UPS will turn into Bypass mode.
NOTE 1:
If the UPS has been set to enable the bypass output, it will bypass voltage from utility power to output sockets and terminal even though you have turned off the UPS (inverter).
NOTE 2:
After turning off the UPS, please be aware that the UPS is working at Bypass mode and there is risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the input breaker. A few seconds later, there is no display shown on the display panel and UPS is complete off.
8. Turn off the UPS without utility power supply in Battery mode
1) Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once.
2) Then UPS will cut off power to output and there is no display shown on the display panel.
9. Mute the buzzer
1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the buzzer is muted, the buzzer will beep again.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the details.
EN
14
EN
10. Operation in warning status
1) When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems for UPS operation. Users can get the fault code from LCD panel. Please check the trouble shooting table in chapter 4 for details.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the details.
11. Operation in Fault mode
1) When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the UPS. Users can get the fault code from display panel. Please check the trouble shooting table in chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output immediately to avoid more risk or danger.
12. Operation of changing battery numbers
1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the input breaker, and switch off the battery breaker (only available for long-run model), or disconnect battery wire for standard model.
4) Remove the cabinet cover, and then modify the jumpers (JP1, JS3) on the control board to set the battery numbers as following table:
Battery Number
16
17
18
19
20 pin1 & pin2
X
X
X
X
X pin3 & pin4
X
X
X
X
X
JP1
Pin5 & pin6
0
1
0
1
1 pin7 & pin8
0
1
0
0
1
JS3
0
0
1
1
1
Note : 1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5) Modify the battery pack for the setting number carefully. After complete it, put the cover back, and switch on the battery breaker for long-run model.
6) Switch on the input breaker and the UPS will enter Bypass mode. If the UPS is in maintenance
Bypass mode, turn the maintenance switch to “UPS” position and then turn on the UPS.
3-5. Abbreviation Meaning in LCD Display
Abbreviation
ENA
DIS
ATO
BAT
Display content
15
Meaning
Enable
Disable
Auto
Battery
NCF
CF
SUB
ADD
ON
OFF
FBD
OPN
RES
Normal mode (not CVCF mode)
CVCF mode
Subtract
Add
On
Off
Not allowed
Allow
Reserved
3-6. LCD Setting
There are three parameters to set up the UPS. Refer to following diagram.
Parameter 1
Parameter 1: It’s for program alternatives. Refer to below table for the programs to set up.
Parameter 2 and parameter 3 are the setting options or values for each program.
Note:
Please select “
Up
” or “
Down
” button to change the programs or parameters.
Parameter 2 Parameter 3
13
14
15
16
17
18
06
07
08
09
10
11
12
Programs available list for parameter 1:
Code Description
01
Output voltage
02
Output frequency
03
04
05
Voltage range for bypass
Frequency range for bypass
Reserved
Reserved
Reserved
Bypass mode setting
Battery maximum discharge time setting
Reserved
Reserved
Reserved
Battery voltage Calibration
Charger voltage adjustment
Inverter voltage Calibration
Reserved
Reserved
Charger maximum current setting
Bypass
Y
Y
Y
Y
Y
Y
Y
Y
Y
AC CVCF Battery Battery Test
Y
Y
Y
Y
Y
Y Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
EN
16
EN
19 Battery capacity and groups setting
20 Backup time calibration
*Y means that this program can be set in this mode.
01: Output voltage
Interface
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208:
Presents output voltage is 208Vac
220:
Presents output voltage is 220Vac
230:
Presents output voltage is 230Vac
240:
Presents output voltage is 240Vac
02: Output frequency
Interface
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
Setting
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three options in parameter 2:
50.0Hz:
The output frequency is setting for 50.0Hz.
60.0Hz:
The output frequency is setting for 60.0Hz.
ATO:
If selected, output frequency will be decided according to the latest normal utility frequency. If it is from 46Hz to 54Hz, the output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output frequency will be 60.0Hz. ATO is default setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You may choose following two options in parameter 3:
CF:
Setting UPS to CVCF mode. If selected, the output frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2.
The input frequency could be from 46Hz to 64Hz.
NCF:
Setting UPS to normal mode (not CVCF mode). If selected, the output frequency will synchronize with the input frequency within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to setting in parameter 2. If 50 Hz selected in parameter 2, UPS will transfer to battery mode when input frequency is not within
46~54 Hz. If 60Hz selected in parameter 2, UPS will transfer to battery mode when input frequency is not within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will show the current frequency.
03: Voltage range for bypass
Interface Setting
Parameter 2:
Set the acceptable low voltage for bypass. Setting range is from 110V to 209V and the default value is 110V.
Parameter 3:
Set the acceptable high voltage for bypass. Setting range is from 231V to 276V and the default value is 264V.
17
04: Frequency range for bypass
Interface Setting
Parameter 2:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3:
Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
05: reserved
Interface Setting reserved
EN
06: reserved
Interface Setting reserved
07: reserved
Interface Setting reserved
08: Bypass mode setting
Interface Setting
Parameter 2:
OPN
: Bypass allowed. When selected, UPS will run at Bypass mode depending on bypass enabled/disabled setting.
FBD
: Bypass not allowed. When selected, it’s not allowed for running in Bypass mode under any situations.
Parameter 3:
ENA
: Bypass enabled. When selected, Bypass mode is activated.
DIS
: Bypass disabled. When selected, automatic bypass is acceptable, but manual bypass is not allowed. Manual bypass means users manually operate UPS for Bypass mode. For example, pressing OFF button in AC mode to turn into Bypass mode.
18
EN
09: Battery maximum discharge time setting
Interface Setting
Parameter 3:
000~999:
Set the maximum discharge time from 0min to
999min. UPS will shut down to protect battery after discharge time arrives. The default value is 990min.
DIS:
Disable battery discharge protection and backup time will depend on battery capacity.
10: reserved
Interface Setting reserved
Interface
11: reserved
12: reserved
Interface
Setting reserved
Setting reserved
13: Battery voltage calibration
Interface Setting
Parameter 2:
Select “
Add
” or “
Sub
” function to calibrate battery voltage to real figure.
Parameter 3:
the voltage range is from 0V to 5.7V, the default value is 0V.
19
14: Charger voltage adjustment
Interface Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust charger voltage
Parameter 3:
the voltage range is from 0V to 6.4V, the default value is 0V.
15: Inverter voltage calibration
Interface Setting
Parameter 2:
you may choose
Add
or
Sub
to calibrate inverter voltage
Parameter 3:
the voltage range is from 0V to 6.4V, the default value is 0V.
16: reserved
Interface Setting reserved
EN
17: reserved
Interface Setting reserved
18: Charger maximum current setting
Interface Setting
Parameter 3:
The maximum charging current could be adjusted.
Default value is 4A for long run model and 1A for standard model.
The setting range is 0.5A~6A for long run model, and 0.5A~2A for standard model
Note:
Any modification should be suitable to battery specifications.
If input voltage is below 200VAC, the UPS will reduce charging current to 4A automatically even though the setting is 6A.
20
EN
19: Battery capacity and groups setting
Interface Setting
Parameter 2:
Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH,
26AH, 40AH, 65AH, 100AH and so on.
The default value is 9AH.
Parameter 3:
Set battery group range from 1 to 6.
The default value is 1 group.
These parameters are for the battery backup time calculation
20: Backup time calibration
Interface Setting
Parameter 3:
Calibrate the displayed backup time by adjusting this multiplier factor. The formulation is listed below:
Displayed backup time=Original calculated backup time x
Multiplier factor
The default value of multiplier factor is 1.0, and the range is from
0.5 to 2.
3-7. Operating Mode/Status Description
Operating mode/status
AC mode Description When the input voltage is within acceptable range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery at
AC mode.
LCD display
CVCF mode Description When input frequency is within 46 to 64Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode.
LCD display
21
Battery mode Description When the input voltage is beyond the acceptable range or power failure,
UPS will backup power from battery and alarm will beep every 4 seconds.
LCD display
EN
Bypass mode Description When input voltage is within acceptable range and bypass is enabled, turn off the UPS and it will enter Bypass mode. Alarm beeps every two minutes.
LCD display
Battery Test Description When UPS is in AC mode or CVCF mode, press “Test” key for more than
0.5s. Then the UPS will beep once and start “Battery Test”. The line between I/P and inverter icons will blink to remind users. This operation is used to check the battery status.
LCD display
Fault status Description When UPS has fault happened, it will display fault messages in LCD panel.
LCD display
3-8. Fault Code
Fault event
Bus start failure
Bus over
Bus under
Bus unbalance
Inverter soft start failure
High Inverter voltage
Low Inverter voltage
Fault code Icon Fault event
01 None Inverter output short
02
03 circuited
None Negative power fault
None Battery SCR short circuited
None Inverter relay short circuited 04
11
12
13
None Over temperature
None CPU communication failure
None Overload
Fault code Icon
14
1A
21
24
41
42
43
None
None
None
None
None
22
EN
3-9. Warning Indicator
Warning
Battery low
Overload
Battery unconnected
Icon (flashing) Alarm
Beeping every second
Beeping twice every second
Beeping every second
Over charge
EPO enable
Fan failure/Over temperature
Charger failure
I/P fuse broken
Overload 3 times in 30min
Beeping every second
Beeping every second
Beeping every second
Beeping every second
Beeping every second
Beeping every second
23
4. Trouble Shooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom Possible cause Remedy
No indication and alarm in the front display panel even though the mains is normal.
The AC input power is not connected well.
Check if input cable firmly connected to the mains.
The icon and the warning code
flash on LCD display and alarm beeps every second.
EPO function is enabled.
Set the circuit in closed position to disable EPO function.
The icon and flash on
LCD display and alarm beeps every second.
The external or internal battery is incorrectly connected.
Check if all batteries are connected well.
UPS is overload.
Remove excess loads from UPS output.
The icon and
LCD display and alarm beeps twice every second.
lights on LCD display and alarm beeps continuously.
Fault code is shown as 14, the icon
lights on LCD display, and alarm beeps continuously.
flash on
Fault code is shown as 43. The icon
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass.
After repetitive overloads, the
UPS is locked in the Bypass mode. Connected devices are fed directly by the mains.
UPS is overload too long and becomes fault. Then UPS shut down automatically.
The UPS shut down automatically because short circuit occurs on the UPS output.
Remove excess loads from UPS output.
Remove excess loads from UPS output first. Then shut down the UPS and restart it.
Remove excess loads from UPS output and restart it.
Check output wiring and if connected devices are in short circuit status.
Other fault codes are shown on LCD display and alarm beeps continuously.
A UPS internal fault has occurred.
Contact your dealer
Battery backup time is shorter than nominal value
The icon and flash on LCD display and alarm beeps every second.
Batteries are not fully charged
Batteries defect
Charge the batteries at least 7 hours and then check capacity.
If the problem still persists, consult your dealer.
Contact your dealer to replace the battery.
Fan is locked or not working; or the UPS temperature is too high.
Check fans and notify dealer.
EN
24
EN
5. Storage and Maintenance
5-1. Storage
Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C
40°C - 45°C
Every 3 months
Every 2 months
1-2 hours
1-2 hours
5-2. Maintenance
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still connected to the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools with insulated grips and handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries must be rightly deposed according to local regulation.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
25
6. Specifications
MODEL
CAPACITY*
INPUT
Low Line Loss
Voltage Range
Low Line Comeback
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range (Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Transfer Time
Line
Inverter
EFFICIENCY
AC mode
Battery Mode
BATTERY
Battery
Bypass
Type & Numbers
PowerWalker
6000
PowerWalker VFI
6000C/R LCD
6000 VA / 4800 W
208/220/230/240VAC
± 1%
46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 10min
、
110%~130%: 1min
、
>130% : 1sec
100%~110%: 30sec
、
110%~130%: 10sec
、
>130% : 1sec
3:1 max
≦
3 % @ 100% Linear Load;
≦
6 % @ 100% Non-linear Load
0 ms
0 ms
> 89%
> 88%
PowerWalker
10000
PowerWalker VFI
10000C/R LCD
10000 VA / 8000 W
110 VAC ± 3 % at 50% Load;
176 VAC ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC ± 3 %
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Single phase with ground
≧
0.99 at 100% Load
> 90%
> 89%
12 V / 9 Ah x 16 12 V / 9 Ah x 20
Standard
Model
Long-run
Model
Recharge Time
Charging Current
Charging Voltage
Type
Numbers
Charging Current
Charging Voltage
9 hours recover to 90% capacity 9 hours recover to 90% capacity
Default : 1 A ± 10%
Max.: 2A ± 10%
218.4 VDC ± 1%
Depending on applications
273 VDC ± 1%
16 – 20 (adjustable)
Note:
When using internal batteries from 16 to 19, the unit will de-rate according to the following formula: P = P
Rating
x N/20.
Default: 4 A ± 10%
Max.: 6A ± 10%
273 VDC ± 1% (based on 20pcs batteries)
PHYSICAL
Standard
Model
Dimension,DXWXH(mm)
Net Weight (kgs)
369 x 190 x 688
72
UPS unit: 580 x 438 x 88 [2U]
Battery pack: 580 x
438 x 133 [3U]
UPS unit: 15
Battery pack: 48
442x 190 x 688
82
UPS unit: 668 x 438 x 88 [2U]
Battery pack: 580 x
438 x 133 [3U]
UPS unit: 18
Battery pack: 63
Long-run
Model
Dimension, DXWXH(mm) 369 x 190 x 318 580 x 438 x 88 [2U] 442x 190 x 318 668 x 438 x 88 [2U]
Net Weight (kgs) 21 15 23 18
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
0 ~ 40°C
(battery life cycle will be shorten when temperature is above 25°C)
<95 % and non-condensing
<1000m
Less than 55dB @ 1 Meter Less than 58dB @ 1 Meter
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and
MAC
Optional SNMP Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
26
EN
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement