Toshiba V-series Ver2

Integrated Controller
Integrated Controller
V
-series
model 1000/2000/3000
S2/C2/L2
S3/C3/L3
1
L1
Sequence control
model 2000/3000
HIgh-Speed processing
The IEC language processor installed in the sequence control module supports ladder diagrams, integer functions, and floating-point functions. Scanning rates are greatly accelerated, at just 40 ns per contact (model 3000) and 40 ns per integer addition (model 3000).
Realtime Online Trace
The processor can store process data calculations for use by the engineering tool in monitoring of realtime values, calculation flow, and the logic timing.
Computer Link
An RS-485 serial communications port built into the sequence control module facilitates connection to a computer or an operator interface device.
Network support
Powerful communications provisions enable networking with other systems via Ethernet, control network TC-net, TOSLINE-S20/S20LP,
TOSLINE-F10, DeviceNet, and RS-232C /
RS-485 serial interfaces.
Basic configuration
IF721
PS791
S3PU45
BU744
Main base
Power supply module
Expansion interface
Control module
RS-485
BU719
PS792/PS736
IF721/IF741
S3PU21
Main base
Power supply module
Expansion interface
Control module
TC-net
Ethernet
BU744/BU746/BU748
PS791
IF721/IF741
S3PU45/S3PU55
CN711/CN712
EN711/EN721/EN731/EN741
S2PU72
PS692
IF661
BU648E
Main base
Power supply module
Expansion interface
Control module
Main base
Power supply module
Expansion interface
Control module
TC-net
Ethernet
RS-485
BU668/BU666/BU664
PS692
IF661
S2PU22/S2PU32
BU648E
PS692
IF661
S2PU72
CN611/CN612
EN611/EN621/EN631/EN641
2
Loop control
model 1000/2000/3000
Hyper PID Control
The loop control module can be used for process loop control, sequence control, and batch control applications. This module provides the hyper PID control that was developed by pursuing the essentials of the PID control algorithm with double-cross limit combustion control and separate feedfoward/feedback control. The module is very effective for controlling plant disturbance problems.
Monitoring
Wide range
The loop control module supports the connection with the OIS1200 operator station through the
Ethernet control LAN. Control loop data can also be easily linked to a SCADA package by the system tag.
Model 3000 can handle as many as 256 control loops; model 2000 can handle up to 96 control loops; and model 1000 can handle up to 8 control loops.
Maintainability
In the model 2000 or model 3000, a redundant controller configuration and redundant network ensure a highly reliable system, permitting online maintenance.
Basic configuration
PS791
BU744
L3PU11
IF735
SV
BU643D
PS692
L2PU11
PV: normal PID control
PV: hyper PID control
L1PU11
EN531
Main base
Power supply module
Expansion interface
Control module
Ethernet
TC-net
Fan Unit
BU744/BU746/BU748
PS791
IF735
L3PU11
EN711/EN721/EN731/EN741
CN711/CN712
FA714
FA714
Main base
Power supply module
Control module
Ethernet
TC-net
BU648E/BU643D
PS692
L2PU11/L2PU12
EN611/EN621
EN631/EN641
CN611/CN612
Power module
Control module
Ethernet
PS591
L1PU11
EN531
3
Computer
model 2000/3000
IBM PC/AT Compatible
The computer module is an industrialized
PC/AT-compatible personal computer (PC) that runs on the main base. This module share the common memory data with the other control modules via the station bus.
The computer module can access the I/O module directly, making micro control applications possible.
Windows NT OS
The operating system for the computer module is Windows NT(version 4.0) or Windows 2000.
You can use many popular Windows application packages.
Sequence control
Loop control
Useful Web Server
The computer module includes a station bus communication that allows data exchange between a sequence control module and a standard Windows application package. Web server application for remote monitoring & operation is easily realized.
Factory
Process
Internet
Office
Basic configuration
IF721
C3PU62
PS791S
BU744
BU648E
PS691
C2PU61
FA714
Main base
Power supply module
Expansion interface
Control module
TC-net
Fan Unit
BU744/BU746/BU748
PS791S
IF721/IF741
C3PU62/C3PU63
CN711/CN712
FA714
4
IF661
Main base
Power supply module
Expansion interface
Control module
TC-net
BU648E/BU643D
PS691
IF661
C2PU61/C2PU62/C2PU63
CN611/CN612
Typical configuration
Main unit Configuration
L1PU11
EN531
LD511
LD512
Expansion I/O system
RS-485
model 1000
Two types of control modules are available. The L1PU11 supports the Ethernet module, and the L1PU12 has a built-in TOSLINE-S20LP (double-loop fiber optics system). The main unit operates on 24 Vdc; power supply module PS591 is provided for use on 100-120/200-240
Vac. The main unit contains two serial communication ports: an RS-232C port for programming, and an RS-485 port for HMI. The RS-485 port can be used to communicate with the LD511 loop display units, a touch panel, or a computer. Up to 16 process I/O units can be connected to the main unit.
Power module
Control module
Ethernet
Loop display unit
PS591
L1PU11/L1PU12
EN531
LD511/LD512
The control module supports IOBUS suitable for distributed process I/O system. The I/O terminal unit connects Process I/O modules to IOBUS. Up to 16 process I/O modules can be connected to one IOBUS.
3Y8A2156G001
Power module
Control module
I/O terminal unit
PS591
L1PU11/L1PU12
3Y8A2156G001
IOBUS:Maximum 1km
RS-485 Computer Link
LD511/LD512 LD511/LD512 model 1000
A maximum of eight loop display units can be connected to one model 1000 station through RS-485 link. Multiple model 1000 stations can be connect to graphic panel or
PC-based HMI.
Operator Interface
RS-485
5
Typical configuration
Integrated System configuration
S2PU72
PS691
L2PU11
C2PU61
CN611
EN621
model 2000
In the integrated system configuration, the model 2000 rack provides for a maximum of 5 control modules and network modules. Sequence control modules, loop control modules, and computer modules can be freely combined on the main base (BU648E). Each control module has a common memory, and a data link is available between control modules.
Main base
Power supply module
Expansion interface
Sequence control module
Loop control module
Computer module
TC-net
Ethernet
BU648E
PS691
IF661
S2PU72
L2PU11/L2PU12/L2PU13
C2PU61/C2PU62/C2PU63
CN611/CN612
EN611/EN621/EN631/EN641
Direct I/O expansion system
IF661
Up to three expansion units can be connected to the main unit. In the maximum configuration, the model 2000 provides 32 slots for direct I/O modules.
Main unit
Expansion base
Power supply module
Expansion interface
Expansion cable
BU668
PS692
IF661
CS6R3/CS6R5/CS6*1
IF661
Expansion unit
CS6*1
Process I/O expansion system
Process I/O bus
SBIF1
The loop control module supports the process I/O bus.
L2PU11 module have a one-channel process I/O bus port, and L2PU12 modules have a three-channel process
I/O bus port. Up to 15 communications modules can be connected to one process I/O bus, and up to 14 process
I/O modules can be connected to each communications module. Depending on I/O modules and types of terminal blocks, two types of communication modules or communication bases are available for each.
Communication module
Communication base
SBIF1/SBIF2
USCB1/USCB2
6
Typical configuration
model 3000
Integrated System configuration
S3PU45
IF721
PS791S
L3PU11
C3PU62
IF735
FA714
In the integrated system configuration, the model 3000 rack provides for a maximum of 8 control modules, expansion interface modules, and network modules.
Sequence control, loop control, and computer modules can be freely combined on the main base. Each control module has a common memory, and a data link is available between control modules.
Main base
Power supply module
Expansion interface
Sequence control module
Loop control module
Computer module
TC-net
Process I/O interface
Ethernet
Fan unit
BU744/BU746/BU748
PS791S
IF721/IF741
S3PU45/S3PU55
L3PU11
C3PU62/C3PU63
CN711/CN712
IF735
EN711/EN721/EN731/EN741
FA714
Direct I/O expansion system
IF721
Main unit
There are two expansion I/O interfaces for the model
3000: IF721 supports 2 channel-expansion buses, and
IF741 supports 4 channel-expansion buses. A maximum of 7 expansion units can be connected to each expansion bus.
Expansion base
Power supply module
Expansion interface
Expansion cable
BU35B/BU356
PS361/PS332
IF351
CS3R5/CS301/CS302
IF351
Expansion unit
CS302
Process I/O expansion system
L3PU11 IF735
The loop control module supports the process I/O bus.
L3PU11 module has a one-channel process I/O bus port, and the additional expansion interface, IF735, has a three-channel process I/O bus. Up to 15 communication modules can be connected to one process I/O bus, and up to 14 process I/O modules can be connected to each communication module. Depending on I/O modules and types of terminal blocks, two types of communication modules or communication bases are available for each.
Process I/O bus
Communication module
Communication base
SBIF1/SBIF2
USCB1/USCB2
7
Typical Configuration / Network
Duplex System Support
Open Network Support
Duplex system Configuration with Direct I/O and Process I/O
Integrated Controller V series is ready to have redundant configuration on fundamental parts of the system such as main unit control module, control network, and Process I/O for model 3000 and model 2000. Duplex configuration is available at each part of the system so that optimal system reliability balancing requirement and cost is realized.
PLC-oriented Direct I/O and DCS-oriented Process I/O are available, which can be handled by one station. A system making use of each I/O's features, Direct I/O for discrete control and Process I/O for continuous loop control and ready for on-line replacement, for example, is configurable.
Ethernet (Duplex option)
TC-net (Duplex option)
V series
V series
(Duplex option)
Process I/O bus (Duplex)
Direct I/O bus
Direct I/O
Chassis
TOSHIBA
TB1
TOSHIBA TOSHIBA TOSHIBA
TB1
CN1
TB1
CN1
OP1
TOSHIBA
OP2
TOSHIBA
TB2
CN2
CN1
TB1
OP1
CN1
TOSHIBA
OP2
TOSHIBA
TB2
CN2
Comm.Unit
(Duplex option)
IOBUS
(Duplex)
Process I/O
Analog
(Duplex option)
V series
Direct I/O bus
V series
V series
V series
(Duplex option)
Process I/O bus (Duplex)
TOSHIBA
TB1
TOSHIBA TOSHIBA TOSHIBA
TB1
CN1
TB1
CN1
OP1
TOSHIBA
CN1
TB1
OP1
CN1
TOSHIBA
OP2
TOSHIBA
TB2
CN2
OP2
TOSHIBA
TB2
CN2
Comm.Unit
(Duplex option)
IOBUS
(Duplex)
Process I/O
Analog
(Duplex option)
Network configuration
V-series integrated controllers provide flexible network system, including Ethernet, control network TC-net, TOSLINE-S20, TOSLINE-F10, DeviceNet, process I/O bus, and RS-485 computer link.
Industrial PC
Panel PC
Remote I/O unit
8
Network
Ethernet
Ethernet / TC-net
In the V-series integrated controllers, Ethernet supports PCMP, IRCP, TCP/IP, and UDP/IP protocols just as it does in the TOSDIC-
CIE1200 and PROSEC-T series controllers. A multi-host, multi-port function and a multi-cast transmission function are supported for send/receive request processing from multiple hosts. Network path redundancy ensures high reliability.
Typical configuration of single bus
10BASE2
3D2Vcable
EN631
EN731
RUN
HLTH
L-A
TOOL
10BASE2
EN-A
EN731
Standard
Transmission rate
Topology
Max. cable segment length
(
*
)
Protocol
Transmission mode
Multiple hosts
Multiple ports
IEEE802.3
10Mbps / 100Mbps
Bus
100 m for 100BASE-TX /10BASE-T
500 m for 10BASE5
185 m for 10BASE2
TCP/IP, UDP/IP, PCMP, IRCP
Point to point transmission
Multi-cast transmission
Broadcast transmission
Inter-hierarchy communications
Maximum of 4
Maximum of 4
(
*
) Extendable by switch / repeater
EN531 model 2000 model 3000
Standard
10BASE5
10BASE2
100BASE-TX
& 10BASE-T
model 1000
type
Single
Dual
Single
Dual
Single
Dual model 3000
EN711
EN721
EN731
EN741
EN751
EN761 model 2000
EN611
EN621
EN631
EN641
(EN651)
(EN661) model 1000
--
--
EN531
--
--
--
(EN651 / EN661 are under development)
Control network TC-net
In V-series integrated controllers, the control network (TC-net) supports both scan transmission for realtime data exchange and event-driven message transmission among controllers. Scan transmission includes both high-speed and medium-speed scans.
Network path redundancy ensures high reliability.
Typical configuration of single bus
3D2Vcable
CN711
CN611
Transmission rate
Topology
Max. cable length
Number of nodes
Cable
Communication service
Response
Number of module
10 Mbps
Bus
400 m per segment
10 km per system (with repeater)
Maximum of 64 per system
Maximum of 30 per segment
10D-2V:trunk cable
3D-2V:drop cable
Scan data transmission
Message transmission
10 ms (High-speed scan)
Maximum of 4 per main unit
model 2000
type
Single
Dual model 3000
CN711
CN712 model 2000
CN611
CN612 model 1000
--
--
model 3000
9
Network
TOSLINE / DeviceNet
TOSLINE-S20/20LP
TOSLINE-S20/20LP supports scan transmission for realtime data exchange and event-driven message transmission among
Toshiba controllers and variable-frequency drive systems. Either coaxial cable or fiber optic cable can be selected as the transmission medium. A double-loop fiber optic system provides excellent reliability.
Typical configuration of single bus
Transmission rate
Topology
Maximum cable length
Number of nodes
Scan data
Communication service
Update time
Device
Connection
2 Mbps
Bus
1 km per coaxial cable
1 km per fiber optic cable
10 km per total system
Maximum of 64 station
Maximum of 1024 w
Scan data transmission
Message transmission
25 ms/1024 w
PLC(T3H,T3,T2E,T2N,T2)
FA-PC(FA3100,G200)
Plant driver, Inverter
Direct I/O bus type
TOSLINE-S20
TOSLINE-S20LP
Coaxial
Fiber model 3000
SN321
SN322A
SN325 model 2000
SN611
SN612
-model 1000
--
--
L1PU12
SN321
5D2V cable model 2000 model 3000
TOSLINE-F10
TOSLINE-F10 is a field network suitable for a distributed I/O system, which provides a data link between Toshiba controllers and variable-frequency drive systems.
Remote I/O Units (TOSLINE-F10 model )
Item Specification
FDI633
FDO633
FRO663
DC input: dry contact input 24 Vdc, 10 mA, 16 points
DC output: 12 to 24 Vdc, 1 A, 16 points
Relay output: 24 Vdc/240 Vdc, 2 A, 16 points
DeviceNet
DeviceNet is an open-standard field network suitable for a distributed I/O system. The
DN611 and DN311 are DeviceNet scanner modules for controllers model 2000 and model 3000 respectively. These modules can read and write data to any manufacturer's ODVA-certified devices, such as I/O blocks, inverters, and motor starters.
10
SN611
T3
Fiber
SN323
SN222A
T2
Transmission rate
Topology
Maximum cable length
Number of nodes
Scan data
Communication service
Update time
Device
Connection
750 kbps or 250 kbps
Bus
500 m (750 kbps)
1 km (250 kbps)
Maximum of 32 stations
Maximum of 32 w
Scan data transmission
7 ms (750 kbps)
PLC(T3H,T3,T2E,T2N,T2)
Inverter, remote I/O set
Direct I/O bus
Transmission rate
Topology
Max. cable length
Number of slaves
Scan data capacity
Device
Connection
500 kbps, 250 kbps, or 125 kbps
Bus
500 m (thick cable, 125 kbps)
250 m (thick cable, 250 kbps)
100 m (thick cable, 500 kbps)
100 m (thin cable),
Maximum of 64 station
Input 128 w, Output 128 w (DN611)
Input 378 w, Output 378 w (DN311)
DN311: model 3000
DN611: model 2000
Direct I/O bus
Programming
Programming Language
IEC 61131-3 is the worldwide language standard for sequence control and loop control modules, covering ladder diagram, function block diagram, and sequential function chart programming. Multiple programming languages give you the flexibility and usability needed to use the right tool for each job.
Graphical Language
Ladder diagrams, function block diagrams, and sequential function charts can be written and monitored in a single program. This means that one worksheet can employ the most useful language for each portion.
Global Variable
V-series integrated controllers can be programmed with symbolic addresses only, allowing you to program without concern for
Program Editor hardware configuration or logical addresses.
Both global and local variables are fully supported, with three hierarchical layers of global variables: controller globals, station globals, and LAN globals. A LAN global variable can be accessed from any station or controller that is connected to the control network TC-net. A station global variable can be accessed from any controller that is mounted on the same station. A controller global variable is used in only one controller, so such a variable has no effect on other controllers and stations.
Local Variable
Local variables are used in only one program or function block. The same name thus can be used in different function blocks or programs, with each local variable of that name operating independently.
User-Defined Function Block
The engineering tool integrates user programs into user-defined function blocks. A function block that has been so constructed can then be used in any part of the programs.
Function Block
FB 1
RUN
STOP
IL
ES
ST
FB 2 FB 3 FB 4
FB 1
FB 2 FB 3
RUN STOP IL ES ST
ST
Program 1
FB
FB FB
FB FB
Local variable
Program 2
FB
FB
FB
FB
FB
FB
Program 3
FB FB FB
FB FB FB
11
Programming
Engineering
Engineering Tool
The engineering tool offers practical functions for development and documentation of projects compatible with IEC61131-3.
Engineering tool software lets you program, monitor, and manage RAS information for V-series integrated controllers.
This tool enables several stations to be handled in a single project, supporting sophisticated applications that may involve several multi-controller, multitasking systems.
CPU
OS
Main Memory
HDD
Network
CD-ROM
Pentium 200 MHz as minimum
Windows NT4.0+SP5+IE4/IE5 or Windows 2000
64 MB minimum.128MB preferred.
300MB free space
Ethernet/RS-232C/RS-485
For Installation
Product View
Sets the hierarchical structures in terms of systems, stations, and controllers.
Configuration Editor
Defines the station's hardware configuration, allowing the setting of configuration and parameters for control modules and I/O modules.
Symbol Editor
Assigns symbolic names as global variables to the signals of Direct I/O modules.
Program Editor
Graphical language can be incorporated in the program editor so that each application can make use of the most suitable language, even on a single worksheet.
Configuration Editor
Tag Editor
Configures tag database for Loop control module, which consist of tag name, instrument range, Process I/O address, PID parameter, etc.
Client / Server Package(option)
In addition to stand-alone tool, client/server tool is available to realize group work all through system lifetime.
stand-alone model 3000/2000 client/server model 3000/2000
Product View
Symbol Editor
PC
PC
PC
PC PC PC
12
Specifications
model 2000/3000
General specifications
Power source
Power consumption
Retentive power interruption
Operating temperature
Ambient humidity
Noise immunity
Withstand voltage
Vibration immunity
Shock immunity
Atmosphere
Cooling
100 to 120/200 to 240 Vac (+10/-15%), 50/60 Hz model 3000: 80 VA max, model 2000: 50 VA max
20 ms or less
0 to 55°C(S and L module,C module flash disk type),
5 to 40°C(C module HDD type)
5 to 95% RH without condensation(S and L module,C module flash disk type),
10 to 90% RH without condensation(C module HDD type)
1500 V p-p, 1 micro-second
1500 Vac, 1 minuite
16.7 Hz, 3mm p-p
98m/s
2
, X,Y,Z direction, 3 times
No corrosive gas, dust concentration of 10mq/cubic-m or less
L3 and C3 module should apply Fan unit FA714
Sequence control modules
S3PU45
S2PU72
Model
Item
Max No. of programs
Max. program capacity
Station bus link
Variable Local/Global
Data register
Specified register
Station global
I/O register
Index register
Scan cycle setting
model 3000
S3PU65
128kw
1kw
8kw
S3PU55
405POUs
112ks
Yes
S3PU45
64kw
1kw
5kw
S3PU21
64ks
model 2000
S2PU72 S2PU32
309POUs
No
Yes
No
S2PU22
32ks
48kw
4kw
0.5kw
No
3kw
8 registers
1kw
8kw 5kw
No
3kw
1-1000 ms for Ultra High speed scan task and high speed scan task, floating or 1-500 ms for main scan task
512POUs 128POUs Max No. of User functions/
Function blocks
Duplex System
Execution speed
Serial communication port
Memory Type
Network (Station bus link)
Network (I/O bus link)
Option
[Bit] 40 ns/contact, 80 ns/coil
[Floating] 200 ns/add & multiple,
80 ns/load, 120 ns/store
No (Option) No
[Bit] 80 ns/contact. 160 ns/coil
[Floating] 400 ns/add & multiple,
160 ns/load, 320 ns/store
RS-232C: Programming port
RS-485: Computer link protocol (1 to n, Toshiba oriented)
Ethernet
TC-net
TOSLINE-S20/S20LP
Flash ROM and SRAM
No
Ethernet
TC-net
No
TOSLINE-F10/F10M
DeviceNet
TOSLINE-S20
TOSLINE-F10
DeviceNet
(Redundancy of S2PU72 is under development. Please check availability when quoting)
13
Specifications
Loop control modules
Computer modules
Loop control modules
L3PU11
L2PU12
Model
Module
Max No. of programs
Max program capacity
Approximate scan rate
(reference)
Scan
Cycle setting
Execution speed
Tag Indicater
Loop
Pushbutton
Sequence
Duplex system
Process Standard
I/O Bus Expansion
Network
HMI
Computer link
model 3000
L3PU21 L3PU11
2048POUs
512ks
model 2000
L2PU11 L2PU12
512POUs
64ks
32 loop/100ms
(L2PU13)
10 to 500 ms for Ultra High speed and high speed task, 100 to 1000 ms for main scan task
[Bit] 3400 ns/contact, 2500 ns/coil
[Floating] 5000 ns/add & multiple, 4200 ns/load,
3400 ns/store
768
256
1024
128
Option
1
3
Ethemet
(ONS)
768
256
768
64
128
32
128
16
Option
1
No
Ethernet
288
96
288
48
Option
3
No
OIS-DS
(L2PU13 is under development. Please check availability when quoting.)
OIS 1200
No
128
32
128
16
Yes
1
No
model 1000
L1PU11 L1PU12
64POUs
6ks
8 loop/500 ms
50 to 5000 ms for main scan task
N / A
Ethemet
128
8
32
None
No
1
No
TL-S20LP
OIS1200
Yes(RS-485)
FIX
Computer modules
C3PU62
C2PU61
Model
Item
OS
CPU
Memory Cash
Main
Flash
Ras
Operation interface
FDD interface
Storage
RS-232C
Ethernet
CRT-IF
PC-Card IF
Ras function model 3000
C3PU63
128MB
C3PU62 C2PU63 C2PU62
Windows NT4.0
AMD K6-2EL 166 MHz
64KB(in CPU), 512KB(Extended) model 2000
C2PU61
64MB
(C2PU65) (C2PU75)
Windows
2000
Mobile Pentium 3
500 MHz
L1: 32KB & L2:
256KB (in CPU)
128MB
64MB
128MB
2Mbyte
128kbyte
Keyboard, Mouse(PS/2)
Connector
4.8GB HDD 160MB
Flash
4.8GB HDD
1ch DB-9P:300 to 19200 bps
10BASE-T
100BASE-TX
/10BASE-T
1ch RGB DB-15S
Type 2: 2 slots No
WDT: 512/128/2ms selectable, Temperature of MPU,
Voltage check (DC Power supply,Battery)
Type 2: 2 slots
(C2PU65 and C2PU75 are under development, Please check availability when quoting.)
14
Specifications
model 3000 Direct I/O module
Digital input modules
L
DI335
1
0 1 2 3 4 5 6 7
8 9 A B C D E F
0 1 2 3 4 5 6 7
H
8 9 A B C D E F
L
H
2
0 1 2 3 4 5 6 7
8 9 A B C D E F
0 1 2 3 4 5 6 7
8 9 A B C D E F
5/12/24VVdc IN
2 1
LH LH
DO335
DI335
Item
DI334
DI334H
DI335
DI335H
DI344
IN354
IN364 dc dc ac ac
Type dc dc dc
24
48
120
220
Voltage
Category
12/24
12/24
24
Rated
Current
10 mA
10 mA
5 mA
5 mA
4.8mA
10 mA
10 mA
64
32
32
32
Number of Inputs
32
32
64
Signal
Delay (max.) on = 10ms off = 15ms on = 1ms off = 1.5ms
on = 10ms off = 15ms on = 1ms off = 1.5ms
on = 10ms off = 15ms on = 15ms off = 15ms on = 15ms off = 15ms
Operating
Voltage on = 9.6V
off = 3.5V
on = 9.6V
off = 3.5V
on = 16V off = 5V on = 16V off = 5V on =29V off = 10V on = 70V off = 25V on = 140V off = 50V
Backplane
Current
100 mA
100 mA
170 mA
170 mA
100mA
120 mA
120 mA
Digital output modules
Item Type
L
DO335
1
0 1 2 3 4 5 6 7
8 9 A B C D E F
0 1 2 3 4 5 6 7
H
8 9 A B C D E F
2
0 1 2 3 4 5 6 7
L
H
8 9 A B C D E F
0 1 2 3 4 5 6 7
8 9 A B C D E F
5/12/24VVdc OUT
2 1
LH
LH
DO335
DO335
DO333
DO334
DO335
DO344
AC363
AC364 ac ac
RO363S
RO364 dc ac dc ac dc dc dc dc
Voltage
Category
12/24
12/24
12/24
48
120/240
120/240
30
250
30
250
Current per
Output
2 A
Current per
Common
5 A
0.5 A
0.1 A
0.5A
2 A
0.5 A
2 A
2 A
5 A
0.8 A
5A
5 A
3.2 A
2 A
5 A
Number of
Outputs
16
32
64
32
16
32
16 isolated
outputs
32
Signal
Delay (max.) on = 1 ms off = 1 ms on = 1 ms off = 1 ms on = 1 ms off = 1 m on = 1ms off = 1ms on = 1 ms off = 0.5 cycle on = 1 ms off = 0.5 cycle on = 10 ms off = 10 ms on = 10 ms off = 10 ms
Backplane
Current
320 mA
210 mA
400 mA
210mA
530 mA
800 mA
100 mA
170 mA
Analog input modules
Item
0 1 2 3 4 5 6 7
8 9 A B C D E F
0 1 2 3 4 5 6 7
AD368
Number of
Input
8 single-ended inputs
AD318
Voltage
Range
0-5 Vdc
0-10 Vdc
±5 Vdc
±10 Vdc
0-5 Vdc
AD328
AD338
8 isolated inputs
8 isolated inputs
8 isolated inputs
N/A
±10 Vdc
AD368
Current
Range
4-20 mA
0-20 mA
N/A
0-20 mA
N/A
Data
Format
Binary
0-4000 or
±2000
Binary
0-4000
Binary
0-4000
Binary
±2000
Input
Impedance
Voltage:
1 kΩ
Current:
250Ω
500 kΩ
Channel
Update
2.5 ms/ch.
0.31 ms/ch.
250Ω
500 kΩ
0.31 ms/ch.
0.31 ms/ch.
Backplane
Current
450 mA
600 mA
600 mA
600 mA
15
Specifications
model 3000 Direct I/O module
Analog output modules
Item
DA364
DA374
Number of
Outputs
4 single-ended outputs
4 single-ended outputs
Voltage
Range
0-5 Vdc
0-10 Vdc
±5 Vdc
±0 Vdc
N/A
Current
Range
N/A
4-20 mA
0-20 mA
Data
Format
Binary
0-4000 or
±2000
Binary
0-4000
DA364
Change detect module
Item
CD332
Type dc
Max . Load
20 mA
Channel
Update
2.5 ms/ch.
Backplane
Current
180 mA
550 Ω 2.5 ms/ch.
180 mA
Voltage
Category
12/24
Rated
Current
10 mA
Number of Inputs
8
Signal
Delay (max.) on = 3/30 ms off = 3.5/35 ms
Operating
Voltage on = 9.6 V off = 3.5 V
Backplane
Current
300 mA
Pulse input module
Function
Up/down counter, Speed counter
Auto reset universal counter
Position control module
MC352 lets you program accelerations, decelerations, constant velocities, and final positions in single moves or combinations of moves to suit a variety of motion applications. Programmable motion data:
500 maximum.
Communication module
AS311
16
Item
Number of counters
Maximum Input pulse rate
Pulse input rating
Maximum count
Comparator output
Backplane current
PI312
2
50 kpps
5/12 Vdc
16,777,215
24 Vdc/100 mA
800 mA
PI312
MC352
Item
Control axis
Control type
Position range
Position unit
Pulse output rate
Output rating
Backplane current
MC352
2
Pulse output
±8,388,607 (unit)
Pulse, mm, inch, degree
200 kpps max.
5-24 Vdc 100 mA
900 mA
Item
Interface
Communication rates
Communication code
Framing Start bit
Data bit
Parity
Message length
Backplane current
AS311
RS-232C, RS-485; 2 ports
300, 600, 1200, 2400,
4800, 9600,or 19200 bps
ASCII
1 bit
7 or 8 bits
Odd, even, none
896 bytes maximum
1000 mA
Specifications
Digital input modules
DI635
Item
DI633
DI634
DI635
Type dc dc dc
(DI635H) dc
IN653
IN663 ac ac
model 2000 Direct I/O module
24
120
220
Voltage
Category
12/24
24
24
Rated
Current
8 mA
5 mA
4 mA
4 mA
7 mA
6 mA
( DI635H is under development. Please check availability when quoting. )
Digital output modules
Item Type
DO633 dc
Voltage
Category
12/24
Current per
Output
1 A
DO635
RO663
DO633P
DO634
DO635
AC663
RO662S
RO663 dc ac dc ac dc dc dc ac
12/24
12/24
12/24
120/240
12/24
240
12/24
240
1 A
0.1 A
0.1 A
0.5 A
2 A
2 A
Analog input modules
Item
AD624L
Number of
Inputs
4 single-ended inputs
Voltage
Range
1-5 Vdc
AD634L
AD624
AD624
AD674
Current
Range
4-20 mA
4 single-ended inputs
4 single-ended inputs
0-10 Vdc
1-5 Vdc
N/A
4-20 mA
4 single-ended inputs
±10 Vdc N/A
Signal
Delay(max.) on = 10 ms off = 10 ms on = 10 ms off = 10 ms on = 10 ms off = 15 ms on = 1 ms off = 1.5 ms on = 20 ms off = 15 ms on = 20 ms off = 15 ms
Operating
Voltage on = 9.6 V off = 3.5 V on = 18 V off = 6 V on = 16 V off = 5 V on = 16 V off = 5 V on = 80 V off = 30 V on = 160 V off = 80 V
Backplane
Current
15 mA
80 mA
100 mA
100 mA
15 mA
15 mA
Number of
Outputs
16
16
32
64
12
8
16
Signal
Delay(max.) on = 1m s off = 1m s on = 1m s off = 1m s on = 1m s off = 2m s on = 1m s off = 1m s on = 1m s off = 0.5 cycle on = 10 ms off = 15 ms on = 10 ms off = 15 ms
Backplane
Current
60 mA
60 mA
250 mA
250 mA
140 mA
40 mA
90 mA
Input
Impedance
Voltage:
500 kΩ
Current:
250 Ω
500 kΩ
Channel
Update
4 ms/4 ch.
4 ms/4 ch.
Backplane
Current
50 mA
50 mA
Voltage:
1 MΩ
Current:
250 Ω
1 MΩ
9.6 ms/4 ch.
50 mA
9.6 ms/4 ch.
50 mA
17
Specifications
model 2000 Direct I/O module
Analog output modules
DA622
Item
DA622L
DA622
DA672
Number of
Outputs
2 single-ended outputs
2 single-ended outputs
2 single-ended outputs
Voltage
Range
0-5 Vdc
1-5 Vdc
0-10 Vdc
1-5 Vdc
±10 Vdc
Current
Range
4-20 mA
4-20 mA
NA
Data
Format
Binary
0-250
Binary
0-4000
±2000
Max. Load
V: 5 kΩ
I : 600 Ω
V: 5 kΩ
I : 600 Ω
5 kΩ
Channel
Update
1 ms/chan.
1 ms/chan.
1ms/chan.
Backplane
Current
70 mA
170 mA
170 mA
Pulse input modules
Item
PI631
PI632
1
2
Number of
Counters
PI672 2
PI632
Maximum Input
Pulse Rate
100 kpps
50 kpps: encoder mode
100 kpps: counter mode
50 kpps: encoder mode
100 kpps: counter mode
Pulse Input
Rating
5/12 Vdc
5/12/24 Vdc
RS422
Maximum
Count
16,777,215
16,777,215
16,777,215
Comparator
Output
None
24 Vdc
30 mA
24 Vdc
30 mA
Backplane
Current
80 mA
500 mA
650 mA
Position control modules
Communication module
Item
Control axis
Control type
Position range
Position unit
Pulse output rate
Output rating
Backplane current
MC611
1
Pulse output
±999,999(unit)
Pulse, mm, inch, degree
200kpps maximum
5-24 Vdc, 50 mA
200 mA
MC612
2
Pulse output
±9,999,999 (unit)
Pulse, mm, inch, degree
200 kpps maximum
5-24 Vdc 50 mA, RS-485
700 mA
Item
Interface
Communication rates
Communication code
Framing Start bit
Data bit
Parity
Message length
Backplane current
CF611
RS-232C, 1 port
300, 600, 1200, 2400,
4800, 9600,or 19200 bps
ASCII
1 bit
7 or 8 bit
Odd, even, none
320 bytes maximum
550 mA
18
Specifications
model 1000/2000/3000 Process I/O module
Analog input modules
Item
SAI01
SAI02
Number of Inputs
8 single
-ended inputs
4 isolated inputs
Voltage Range
±10 mV, ±20 mV, ±50 mV
±100 mV,1-5 Vdc,
±1 Vdc, ±5 Vdc
1-5 Vdc
Current
Range
4-20 mA
(*)
Input
Impedance
Voltage: 1 MΩ
Current: 250Ω
4-20 mA
(*)
Voltage:1 MΩ
Current: 250Ω
Accuracy
0.1%
System
Power
24V dc
50mA
External
Power
_
0.1%
24V dc
60mA
_
SAI03
4 isolated inputs
1-5 Vdc
4-20 mA
(*)
Voltage: 1 MΩ
Current: 250Ω
0.1%
24V dc
300mA _
SAI06
(**)
8 single
-ended inputs
±10 mV, ±20 mV, ±50 mV
±100 mV,1-5 Vdc,
±1 Vdc, ±5 Vdc,
4-20 mA
(*)
(*) with external 250 ohm load or option card of Type 1 terminal block
(**) High comm.rate and duplex-ready type. Apply SBIF2 comm module
Analog output modules
Item
SAO01
SAO02
SAO06
(**)
Number of Outputs
8 single-ended outputs
4 isolated outputs
4 single-ended outputs
Current Range
4-20 mA
4-20 mA
4-20 mA
(**) High comm.rate and duplex-ready type. Apply SBIF2 comm module
Max. Load
750Ω
750Ω
750Ω
Voltage: 1 MΩ
Current: 250Ω
Accuracy
0.2%
0.2%
0.2%
0.1%
24V dc
50mA
_
System Power
24V dc, 300 mA
24V dc, 200 mA
24V dc, 200 mA
External Power
_
_
_
RTD input module
Item
SRT01
Number of Inputs
4 RTD isolated
inputs
(three-wire)
Input
Pt100
(Pt385 Pt3916)
Range
0 to 150°C, 0 to 300°C
0 to 500°C, -50 to 100°C,
-150 to 50°C
Accuracy
0.1%
System Power
24V dc 70mA
External Power
_
Thermocouple input module
Item
STC01
Number of Inputs
8 TC isolated inputs
Input Type
J, K, T, E, R, S, B with cold-junction compensation
Accuracy
0.2%
System Power
24V dc 70mA
External Power
_
Pulse input modules
Item
SPI01
Number of Inputs
4 single-ended
Maximum Input Frequency
Dry contact input:50Hz
SPI06
(**) inputs
4 single-ended
Voltage input: 10kHz
Dry contact input: 50Hz inputs Voltage input: 10kHz
(**) High comm.rate and duplex-ready type. Apply SBIF2 comm module
Pulse output module
Item Number of Outputs
SPO01 4 single-ended outputs
Maximum output
Frequency
28Hz / 111Hz selectable
Load
24V dc
100mA
Counter
16-bit up counter
16-bit up counter
System Power
24V dc 150mA
24V dc 70mA
External Power
24V dc 50mA
24V dc 70mA
Output Pulse Width System Power External Power
72ms / 9ms selectable
24V dc 100mA 24V dc 10mA
SAI01
SAI06
19
SAO01 SRT01
STC01
SPO01
Specifications
Digital input module
model 1000/2000/3000 Process I/O module model 1000/2000/3000 Terminal Block for Process I/O module
Item
SDI01
Voltage
Category
24V dc
SDI01
Digital output module
Item
SDO01
Voltage
Category
24V dc
Rated
Current
5mA
Load
Current
100mA max.
SDO01
Distributor module
Item
SDA01
Voltage
Category
24V dc
Load
Current
35mA max.
Number of Inputs
32
Input
Type
Dry contact
Signal
Delay (max.) on = 10ms off = 10ms
Number of Outputs
32
Output Type
Source
(sink load)
Number of Outputs
8 for sensor
Function
Current limiting
Update period
10ms
Alarm
Output
24V dc
100mA
Update period
10ms
System
Power
24V dc
50mA
System
Power
24V dc
50mA
System
Power
24V dc
35mA
External
Power
24V dc
280mA
External
Power
24V dc
25mA
External Power
24V dc
25mA + Load current
Loop input/output modules (for model 1000 only)
LP01
Item
MV output type
Analog input
Digital input
Analog output
Digital output
Isolation
LP01
Current output (4-20mA)
Load maximum (600Ω )
4 channels, 1-5V dc
3 points (Dry contact, 24V dc, 5mA)
2channels , 1-5V dc
3 points (Source, 24V dc, 100mA)
Single-ended input and output
LP02
Pulse output (30V dc, 0.1A )
Pulse width minimum 9 ms
Loop input/output modules are used for model 1000
Terminal Block for Process I/O system
Terminator
Process I/O units system
(Type 1 terminal block) model 3000/model 2000
L module with serial I/F
Process I/O bus
Integrated Controller V series has following four types of terminal blocks for Process I/O system:
RUN
ALM
A
B
A
B
Max. 30m
TB1
Communication base
USCB1: 15unit Max.
Communication unit
SBIF1, SBIF2
IOBUS cable
(7m: standard)
OBUS terminal
Process I/O module
14unit Max.
Terminal block
Type 1: Vertical & Screw type
Type 2: Horizontal & Flat type
Type 3: Horizontal & European type
Type 4: Horizontal & Screw type
Loop control modules for model 3000, model
2000 and model 1000 supports Process I/O system. For model 3000/model 2000 application, apply USCB1 base for type 1 terminal block, USCB2 base for type 2, 3 and 4.
IOBUS with USCB2 is extendable up to 1km, and needs to be terminated with one of the type
2 terminal block including UITU5.
I/V converter board
Model 1000 supports type 2, 3 and 4 terminal blocks only.
20
Specifications
Terminal Block for Process I/O module
Terminal block
T
Y
P
E
1
P
E
T
Y
2
T
Y
P
E
3
T
Y
P
E
4
UTBA1
UTBA2
UTBA3
UTBA6
UTBA61
UTBD1
UTRC1
UABU1
UABU3
UDBU1
UITU5
EC352AI0151
EC352AI0171
EC352AI0251
EC352AI0271
EC352AI0351
EC352AI0371
EC352TC0151
EC352RT0151
EC352AO0151
EC352AO0251
EC352PI0151
EC352DI0151
EC352DO0151
EC352DO0161
UITU5
3Y8A2156G001
UT5L12
EC352AI02C1
EC352AI02D1
EC352AO02C1
UITU5
3Y8A1467G001
C
O
M
Comm module
SBIF1
SBIF2
SSIF1
L1PU11/12
Comm module
Comm module (High-speed type)
Comm module (for PLC)
Model 1000
Description
For 8ch analog I/O and 4ch pulse I/O, two modules mounted
For 4ch analog I/O, two modules mounted
For 8ch analog input and distributor unit, one module mounted
For dupe analog I/O, one pair of modules mounted
For dupe analog I/O pulse input, one pair of modules mounted
For digital I/O, one module mounted
For digital I/O connecting relay terminal, two modules mounted
For 8ch analog I/O and 4ch pulse I/O, two modules mounted
For dupe analog I/O pulse input, one pair of modules mounted
For digital I/O connecting relay terminal, two modules mounted
For IOBUS extension & termination.
8 channel analog input, voltage input, cable connect
8 channel analog input, Current/voltage input, cable connect
4 channel analog input, voltage input, cable connect
4 channel analog input, Current/voltage input, cable connect
4 channel analog input, voltage input, cable connect
4 channel analog input, Current/voltage input, cable connect
8 channel Thermo couple input, cable connect
4 channel RTD input, cable connect
8 channel analog output, cable connect
4 channel analog output, cable connect
4 channel pulse input, cable connect
32 points digital input, cable connect
32 points digital output, cable connect
32 points digital output, connector connect
For IOBUS extension & termination (model 2000/3000).
For IOBUS extension, (model 1000)
One Loop module input & output (model 1000 only)
4 channel analog input, voltage input, Terminal block
4 channel analog input, Current/voltage input, Terminal block
4 channel analog output, Terminal block
For IOBUS extension & termination (model 2000/3000).
For IOBUS extension, (model 1000)
S
A
I
0
1
0
I
S
A
2
S
A
I
0
3
S
T
C
0
1
S
R
T
0
1
S
A
O
0
1
S
A
O
0
2
S
P
I
0
1
S
P
O
0
1
S
D
0
I
1
S
D
O
0
1
0
I
S
A
6
S
A
O
0
6
0
I
S
P
6
S
D
A
0
1
S
S
I
F
1
0
1
L
P
0
2
L
P
C
B
U
S
1
U
S
C
B
2
C
B
U
S
3
T
B
5
*
*
UABU 1
(Type 2)
EC352AI 0151
(Type 3)
UT5L12 + LP01
(Type 4)
For type 1 terminal blocks, I
OBUS
terminator
FSTM1 is attached to every comm base
USCB1.
For type 2 terminal block, I
OBUS
termination switch is on each terminal block and UITU5.
For type 3 and 4, terminating switch on each terminal block and 3Y8A**** is for model 1000 only.
Use UITU5 for use with model 2000/model
3000 application.
21
Specification
F-series Process I/O system mode 2000/3000
F series Process I/O system realizes faster I/O update rate, offering wide variety of signal conditioning options with channel to channel isolation.
Depending on application requirement, F-series Process
I/O can be fully applied, or mixed with conventional
Process I/O on the same
Process I/O bus realizing flexible I/O configuration.
Comparison between conventional series and F-series
Pulse I/O module
Output for monitoring
Comm Rate
Maximum I/O points
(in theory)
Analog I/O redundancy
Process I/O
Available
Not available
19.2kbps or 375kbps
1,680 all analogs or
6720 all digitals
Option
I/O modules
Name
Analog input comm module
Analog output comm module
Digital input comm module
Digital output comm module
Type
SAIF1
SAOF1
SDIF1
SDOF1
F-series Process I/O
Not available
Available
1Mbps
960 all analogs or
3840 all digitals
Option
Specification
16 points ready for duplex
16 points ready for duplex
32 points
32 points
Analog I/O system
SAIF 1(on-line)
UTBA 7
SAIF 1(stand-by)
Terminal units
Name
AI terminal block
AO terminal block
Digital base unit
Type
UTBA7
UTBA8
UDBU2
Specification
For SAIF1
For SAOF1
For SDIF1/SDOF1 OMRON
G7TC-ID16-5 &G7TC-OC16 applicable
Signal wiring
Terminals
Signal
Conditioner
IOBUS
Terminal Block
24V dc
Terminal Block
Digital I/O system
SDIF 1
UDBU 2
Relay
2nd output connector
Power/IO bus
Terminal Block
Isolators
Name mV input isolator
Current input isolator
Voltage input isolator
Distributor isolator
TC input isolator
RTD input isolator
CT input isolator
Current output isolator
Type
CISO5
CISO6
CISO7
CDIS7
CTC**
CRTD*
CCIT1
CISO8
Specification
0-10mV, 0-20mV, 0-50mV,
0-100mV, 0-200mV
4-20mA
1-5V
4-20mA, 24Vdc distributor for transmitter
Types K, T, R, S, B, J, E
PT385(Pt100) and
Pt3916(JPt100)
0-1Aac, 0-5Aac
4-20mA, line cut detection
Signal wiring
Terminals
Signal wiring cable connector
G7TC realy terminal
Transceiver
Name
Line transceiver module
Transceiver base unit
Type
SLTR 5
USCB 5
Specification
For extension of serial bus by 30m
For SLTR 5
DIN rail
22
Human Interface Station
Integrated Control System TOSDIC-CIE DS
Integration with
Human Interface Station
Integrated Controller V series is ready for conventional DCS applications.
Toshiba's integrated control systems
TOSDIC-CIE DS and TOSDIC-CIE1200 supports control stations of V series.
TOSDIC-CIE DS is for large or medium system application with tag points up to
20,000, with the system configuration of 22 human interface stations and 32 control stations. Equipped with pre-configured user menu, faceplates and real-DCS tag database, the package offer top-down, easy-to-navigate screen operations with touch-screen, mouse and dedicated operator's keyboard suitable for multi-loop operation. For medium size application up to 8,000 tag points or 8 human interface stations, economical package embedding
SVR-DS functionality into OIS-DS is also available.
System name
OIS(HMI) type
TOSDIC-CIE DS
OIS-DS52 plus
SVR-DS
20,000
20,000
TOSDIC-CIE
1200
OIS-DS52 plus
OIS-DS62
8,000
8,000
OIS1200
4,096
2,048
System tag points
Max monitoring tag points per HMI
No. of OIS(HMI)
No. of Control stations
Applicable control modules
Historical trend points
Realtime trend points
Control LAN
(Ethernet module)
22
32
L3PU21
L2PU22
5,000 /system,
5sec-1day cycle
1,024/system
Fast Ethernet
(FN***)
8
2,500 /system,
1min-1day cycle
1,024 /system
4
8
L3PU11
L2PU11 / 12
L1PU11
1,024 /system,
1min-30min cycle
256 /system
Ethernet
(EN***)
Note: PC/workstation hardware platform for OIS series is based on standard business models available in the market. Please consult with local representative or distributor for applicable model.
OIS-DS OIS-DS OIS-DS OIS-DS
SVR-DS
Ethernet
OPC-DS
Fast Ethernet model 3000 (Duplex)
Main base
Power supply
L module
Ethernet module
Tracking module
Tracking cable
Fan unit
BU784:1
PS791S:2
L3PU21:2
FN711:2
IF719:2
CX:2 CY:2
FA724:1 model 2000 (Duplex)
Main base
Power supply
L module
Ethernet module
Tracking module
Tracking cable
BU643D:2
PS692:2
L2PU22:2
FN611:2
IF619:2
CX:2 CY:2
TOSDIC-CIE DS system configuration example
PLC server
PLC
(OPC Client)
23
Human Interface Station
Integrated Control System TOSDIC-CIE 1200
Integration with Human
Interface Station and OPC
TOSDIC-CIE1200, is for medium or small size application with up to 4,096 tag points, 4 human interface stations and 8 control stations. Based on Intellution's FIX MMI, configuration and operation of human interface is user-friendly and easy. Customized database dynamo realizes integrated operation on this open SCADA platform, which includes pre-configured menu, faceplates and real-DCS tag database.
(OPC Client)
OIS-1200 OIS-1200 OIS-1200
OIS-1200 with
OPC-Server
Ethernet
Ethernet model 3000
Main base
Power supply
L module
Ethernet module
BU734
PS791S
L3PU11
EN731 model 2000
Main base
Power supply
L module
Ethernet module
BU643D
PS692
L2PU11
EN631 model 1000
Power supply
L module
Ethernet module
Terminal blocks
Terminal blocks
PS591
L1PU11
EN531
TB511
TB522
TOSDIC-CIE1200 system configuration example
In addition, Integrated Controller V series is ready to communicate with open SCADA packages, distributors for details.
OPC support
OPC(OLE for Process Control) is a de-facto standard of data access protocol for process automation systems. Both TOSDIC-CIE DS and 1200 support OPC so that process data managed in the controllers can be shared or utilized in corporation systems via OPC client software.
In addition, V series model
3000/model2000 stations themselves are capable of having OPC server with computer module talking to other control modules so that OPC-based data integrity in controller-level is realized.
OIS-DS
OPC client
OPC server
Ethernet
OPC server
OIS1200
OPC-DS
ONS Ethernet Ethernet
Integrated
Controller
Integrated
Controller
24
Dimensions
model 3000/2000/1000
Main unit / Expansion unit
4 - ø6
BU748,BU746,BU744
BU742,BU719,BU35B
Expansion unit
BU356
4 - ø6
V series
450.5
465
480
Main unit / Expansion unit
BU648E,BU668
V series
402.5
417
CPU unit
L1PU11
L1PU11,L1PU12
250
120
40
Loop Display unit
LD511
160
286
302
Expansion unit
BU643D
223
240
I/O unit
TOSHIBA
LP01
90
60
160
110
135
163
115
143
168
72 150
25
68
(Unit:mm)
Safety Precaution
This product is intended to be used for the control of Industrial machines and processes.
Misuse of this product can result in property damage or human injury.
Read related manuals carefully before using this product.
IBM is a registered trademark of International Business Machines Corporation.
MS-DOS and Windows are registered trademarks of Microsoft Corporation.
Ethernet is a registered trademark of Xerox Corporation.
DeviceNet is a trademark of the Open DeviceNet Vender Association,Inc.
For further information, please contact your nearest Toshiba Representative or
International Operations-Producer Goods.
The data given in this brochure are subject to change without notice.
In Touch with Tomorrow
TOSHIBA CORPORATION
SOCIAL INFRASTRUCTURE SYSTEMS COMPANY
Industrial Equipment Department
1-1, Shibaura 1-Chome, Minato-ku, Tokyo 105-8001, Japan
Tel. +81-3-3457-4900 Fax. +81-3-5444-9268
Printed in Japan
EG16004A
2001-06(JM)
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement