APC SUA500PDRI-H uninterruptible power supply (UPS) Installation guide

Add to my manuals
14 Pages

advertisement

APC SUA500PDRI-H uninterruptible power supply (UPS) Installation guide | Manualzz

Installation and Operation

Smart-UPS

SUA500PDR

Mount the UPS on DIN Rail

This unit is designed to mount on a heavy duty DIN rail or on the back panel of an enclosure. For details on

DIN rail installation refer to the DIN rail installation guide included in the DIN rail package. The DIN rail kit is not included.

su o0

74

8a

When mounting on the back panel of an enclosure, select screws that are appropriate for the weight of this unit and the mounting surface material.

Six screws must be used when mounting this unit in an enclosure. Three screws in the top of the bracket and three screws in the bottom of the bracket. Failure to follow these instructions may result in damage to the unit.

su o0

74

8b

Battery Installation

The UPS battery is shipped in a separate carton.

Refer to the installation guide included with the replacement battery for installation instructions.

Front Panel

120 V model depicted.

8 N O

7 C OM

6 N C

5 N O

O N

B AT TER Y

4 C OM

3 N C

2 EP O CO M

1 EP O

LO W

B AT TER Y

PUSH

RESET

INPUT

2 0 8 / 2 2 0 -2 4 0 V~ 5 0 /6 0 H z , 7 A MA X

G ROU ND NE UT R AL

N

L INE

L

Te st

OUTPUT

2 3 0 V ~ 5 0 / 6 0 H z , 5 0 0 VA

3 2 5 W , 2 .7 A M AX

G ROU ND NE UTR AL

N

L INE

L

Connect Power and Equipment to the UPS

Hardwiring should be performed by a qualified electrician. Use appropriate size wires.

1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the front panel. The

TVSS screw is used for connecting the ground lead on surge suppression devices such as telephone and network line protectors.

Prior to connecting the grounding cable, ensure that the UPS is NOT connected to AC or battery power.

2. Hardwire the UPS.

– In 230 V applications the UPS must be protected with a circuit breaker that complies with

European standards for branch rated protection per the country of installation.

120 V models

– In 208 V applications, the SUA500PDRI must be protected by a dual pole, 10 A branch rated circuit breaker with UL489 rating.

– The 120 V SUA500PDR has supplementary circuit breaker protection. The unit should be protected by a single pole, 15 A branch rated circuit breaker with a UL489 rating. Ensure that the branch circuit breaker is off prior to wiring the unit.

INPUT OUTPUT

208/230 V models

INPUT OUTPUT

NEUTRAL

N

LINE

L L2/N L1 L2/N L1

2

3. Connect equipment to the UPS.

4. Add optional accessories to the SmartSlot located on the front panel.

5. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected equipment is switched on.

6. Press the Test button on the front panel to start the UPS.

– The battery charges to 90% capacity during the first four hours of normal operation.

Do not expect full battery run capability during this initial charge period.

7. For optimal computer system security, install PowerChute

monitoring software included with the UPS.

Connectors

Communication Port

SERIAL PORT

A standard serial interface cable is incompatible with the UPS.

Use the cable supplied with the unit.

Contact Closure Port

8 NO

7 COM

ON

BATTERY

6 NC

5 NO

4 COM

3 NC

2 EPO COM

1 EPO

LOW

BATTERY

Output Contact Ratings:

The relays are connected from the common (COM) to the normally closed (NC) pins.When the unit enters a low battery or on battery state, the appropriate relay will transition and connect the common (COM) to the normally open (NO) pin.

The Contact Closure Port connection will automatically disable when a

Network Management Card or the Serial Port connection are used.

Parameter Value nominal switching capacity maximum switching power maximum switching voltage maximum switching current

1 A @ 30 VDC

30 W

60 VDC

2 ADC maximum carrying current 2 ADC surge ratings 2 kV per Bellcore TA-NWT-001089

1.5 kV per FCC part 68

Emergency Power Off

The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizing of connected equipment from a remote location, without switching to battery operation.

Use a normally-open contact to connect the EPO COM terminal to the EPO terminal.

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the AC power source. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit.

Use one of the following cable types to connect the UPS to the EPO switch.

• CL2: Class 2 cable for general use.

• CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

• CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

• CLEX: Limited use cable for use in dwellings and for use in raceways.

• For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).

• For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.

3

4

Operation

Operation

UPS Display Panel

120 V models

Test

208/230 V models

Test

INPUT

208/220-240V~ 50/60Hz, 7A MAX

GROUND

NEUTRAL

N

LINE

L

OUTPUT

23 0V~ 50/60Hz, 500VA

325W, 2.7A MAX

NEUTRAL LINE

GROUND

N L

INPUT

208/220-240V~ 50/60Hz, 7A MAX

L2/N L1

23

OUTPUT

0V~ 50/60Hz, 500VA

325W, 2.7A MAX

L2/N L1

Display Panel Indicators and Function Buttons

Indicator

LED

Indicator Title

On-Line

AVR Trim

Description

The UPS is supplying AC power to the connected equipment

(see Troubleshooting).

The UPS is compensating for a high AC voltage (see Troubleshooting).

AVR Boost

On Battery

The UPS is compensating for a low AC voltage (see Troubleshooting).

The UPS is supplying battery power to the connected equipment.

Overload The connected equipment is drawing more than the UPS power rating allows

(see Troubleshooting).

Replace Battery/Battery

Disconnected

The battery is disconnected or must be replaced (see Troubleshooting).

Operation

Battery

Charge

Diagnostic Utility

Voltage

The UPS has a diagnostic feature that indicates the AC voltage.

The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display.

Press and hold the Test button to view the AC voltage bar graph indicator.

After a few seconds, this five-LED Battery Charge indicator on the right of the display panel will show the AC input voltage.

Refer to the figure on the left for the voltage reading (values are not listed on the UPS).

The indicator on the UPS shows the voltage is between the displayed value on the list and the next higher value (see Troubleshooting).

Feature

Button

Feature Title

Power On

Test

Power Off

Function

Press this button to turn on the UPS. Continue reading for additional capabilities.

Press this button to turn off the UPS.

Self-Test

Test

Test

Cold Start

Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery.

Manual: Press and hold the Test button for a few seconds to initiate the self-test.

When there is no AC power and the UPS is off, the cold start feature will switch the UPS and connected equipment onto battery power

(see Troubleshooting).

5

6

User Configurable Items

User Configurable Items

UPS settings

Settings are adjusted through PowerChute

software or optional Network Management Card.

Function

Factory

Default

User Selectable

Choices

Automatic

Self-Test

UPS ID

Every 14 days

(336 hours)

UPS_IDEN

• Every 7 days

(168 hours)

• On start up only

• No self-test

Up to eight characters

(alphanumeric)

Date of Last

Battery

Replacement

Minimum Capacity

Before Return from

Shutdown

Manufacture

Date

0 percent mm/dd/yy

• 0%

• 15%

• 30%

• 45%

• 60%

• 75%

• 90%

Voltage Sensitivity High sensitivity High sensitivity

Medium sensitivity

Low sensitivity

Alarm Delay

Control

Enable

Description

Set the interval at which the UPS will execute a self-test.

Uniquely identify the UPS (i.e. server name or location) for network management purposes.

Reset this date when you replace the battery module.

Specify the percentage to which batteries will be charged following a low battery shutdown before powering connected equipment.

The UPS detects and reacts to line voltage distortions by transferring to battery operation to protect the connected equipment.

In situations of poor power quality, the UPS may frequently transfer to battery operation. If the connected equipment can operate normally under such conditions, reduce the sensitivity setting to conserve battery capacity and service life.

Mute ongoing alarms or disable all alarms permanently.

Shutdown Delay 90 seconds

• Enable

• Mute

• Disable

• 0 s

• 90 s

• 180 s

• 270 s

• 360 s

• 450 s

• 540 s

• 630 s

Set the interval between the time when the UPS receives a shutdown command and actual shutdown.

User Configurable Items

Function

Low Battery

Warning

Synchronized

Turn-on Delay

Output Voltage

230 V models

Factory

Default

2 minutes

0 seconds

High Transfer Point 120 V models:

127 VAC

230 V models:

253 VAC

Low Transfer Point 120 V models:

106 VAC

230 V models:

208 VAC

230 VAC

User Selectable

Choices

Description

2, 5, 8, 11, 14,

17, 20, 23 minutes

• 0 s

• 60 s

• 120 s

• 180 s

• 127 VAC

• 130 VAC

• 253 VAC

• 257 VAC

• 97 VAC

• 100 VAC

• 196 VAC

• 200 VAC

• 220 VAC

• 230 VAC

PowerChute

software interface provides automatic, unattended shutdown when approximately two minutes of battery operated run time remains.

The low-battery warning beeps are continuous when two minutes of run time remain.

Change the low battery warning interval setting to the time that the operating system or system software requires to safely shut down.

Specify the time the UPS will wait after the return of AC power before start up (to avoid branch circuit overload).

• 240 s

• 300 s

• 360 s

• 420 s

• 133 VAC

• 136 VAC

To avoid unnecessary use of the battery where

AC voltage is chronically high, set the high transfer point higher if the connected equipment can tolerate this condition.

• 261 VAC

• 265 VAC

• 103 VAC

• 106 VAC

• 204 VAC

• 208 VAC

• 240 VAC

To avoid unnecessary use of the battery where

AC voltage is chronically low, set the low transfer point lower if the connected equipment can tolerate this condition.

The SUA500PDRI ships ready for 230 V sources. When operating the UPS in 208 V applications, the UPS low transfer voltage settings are adjusted through PowerChute

™ software or the Network Management Card.

The proper setting for low transfer voltage is

196 V.

Refer to the PowerChute

user guide or the

Network Management Card instructions for setting adjustment details.

230 V models only: Sets the output voltage of the UPS while operating on battery.

7

8

Storage, Maintenance, Transport

Storage, Maintenance, Transport

Storage

Store the UPS covered in a cool, dry location with the batteries fully charged.

At 5° to 86° F (–15° to 30° C), charge the UPS battery every six months.

At 86° to 113° F (30° to 45° C), charge the UPS battery every three months.

Replacing the Battery Module

This UPS uses a replaceable, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure.

Ensure battery replacement every 2-4 years.

APCRBC135: Standard (40° C) battery

APCRBC136: High Temperature (50° C) battery

Once the batteries are disconnected the connected equipment is not protected from power outages.

Refer to the appropriate replacement battery installation guide for battery module installation instructions. See your dealer for information on replacement battery modules.

Be sure to deliver the spent battery(s) to a recycling facility or ship it to the address specified in the replacement battery literature.

Troubleshooting

Troubleshooting

Use this chart to solve minor installation and operation problems.

Problem and/or Possible Cause Solution

UPS will not turn on

The battery is not connected properly.

Check that the battery connector is fully engaged.

Press the Test button once to power-up the UPS and connected equipment.

Test

button not pushed.

The UPS is not connected to AC power supply.

Check that the UPS is properly connected to AC power.

UPS will not turn off

The UPS is experiencing an internal fault

UPS beeps occasionally

Normal UPS operation when running on battery.

Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.

None: The UPS is protecting the connected equipment. Press the Test button to silence this alarm.

UPS is not providing expected backup time

The UPS battery(s) are weak due to a recent power outage or battery(s) are near the end of their service life.

Charge the battery(s). Batteries require recharging after extended outages.

Batteries can wear faster when put into service often or when operated at elevated temperatures. If the battery(s) are near the end of their service life, consider replacing the battery(s) even if the replace battery LED is not yet illuminated.

Left half, Right half, or Center section of front panel is flashing

The UPS is experiencing an internal fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.

All LEDs are illuminated and the UPS emits a constant beeping

The UPS is experiencing an internal fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.

Front panel LEDs flash sequentially

The UPS has been shut down remotely through software or an optional accessory card.

None: The UPS will restart automatically when AC power returns.

9

Troubleshooting

Problem and/or Possible Cause Solution

All LEDs are off and the UPS is wired to input AC power

The UPS is shut down or the battery is discharged from an extended outage.

None: The UPS will restart automatically when AC power is restored and the battery has a sufficient charge.

The Overload LED is illuminated and the UPS emits a sustained alarm tone

The UPS is overloaded.

The connected equipment exceeds the specified “maximum load” as defined in Specifications listed on the rating label located on the UPS.

The alarm remains on until the overload is removed. Disconnect nonessential equipment from the UPS to eliminate the overload condition.

The UPS continues to supply power as long as it is online and the circuit breaker does not trip; the UPS will not provide power from batteries in the event of a AC voltage interruption.

The Replace Battery/Battery Disconnected LED is illuminated

The Replace Battery/Battery

Disconnected LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected.

Weak battery

Check that the battery connectors are fully engaged.

Failure of a battery self-test: Replace

Battery/Battery Disconnected LED illuminates and the UPS emits short beeps for one minute. The UPS repeats the alarm every five hours.

Allow the battery to recharge for 24 hours and perform a self-test. If the problem persists after recharging, replace the battery.

Allow the battery to recharge for 24 hours. Perform the self-test procedure to confirm the replace battery condition. The alarm stops and the LED clears if the battery passes the self-test.

If the battery fails again, it must be replaced. The connected equipment is unaffected.

The input circuit breaker trips

The connected equipment exceeds the specified “maximum load” as defined in Specifications listed on the rating label located on the UPS.

Unplug all nonessential equipment from the UPS.

Reset the circuit breaker.

The AVR Boost or AVR Trim LEDs are illuminated

The system is experiencing very high or low AC voltage.

Have a qualified service personnel check your facility for electrical problems. If the problem persists, contact the AC company for further assistance.

10

Troubleshooting

Problem and/or Possible Cause Solution

There is no AC power

There is no AC power and the UPS is off

Use the cold start feature to supply power to the connected equipment from the UPS battery(s).

Press and hold the Test button. The unit will emit two beeps, one short beep and one long beep. Release the button during the second beep.

UPS operates on battery although line voltage exists

The UPS input circuit breaker trips.

Your system is experiencing very high, low or distorted line voltage.

Unplug all nonessential equipment from the UPS.

Reset the circuit breaker.

Move the UPS to a different outlet on a different circuit: Inexpensive fuel powered generators may distort the voltage. Test the input voltage with the

AC voltage display, (see Operation). If acceptable to the connected equipment, reduce the UPS sensitivity.

Battery Charge and Load LEDs flash simultaneously

The UPS has shut down

The internal temperature of the UPS has exceeded the allowable threshold for safe operation.

Check that the room temperature is within the specified limits for operation.

Check that the UPS is properly installed, allowing for adequate ventilation.

Allow the UPS to cool down. Restart the UPS.

Diagnostic AC voltage

All five LEDs are illuminated.

There is no LED illumination.

The line voltage is extremely high and should be checked by an electrician.

If the UPS is plugged into a properly functioning AC power outlet, the line voltage is extremely low and should be checked by an electrician.

On-Line LED

There is no LED illumination.

The LED is blinking.

The UPS is running on battery, or it must be turned on.

The UPS is running an internal self-test.

Software/Network integration problems

Network Management Card difficulties.

Refer to the Network Management Card user guide on the CD shipped with the Network Management Card.

Communication problems between the

UPS and PowerChute

software.

Ensure the correct communication cable (940-1524D) is being used.

Refer to the PowerChute

user manual on the CD shipped with the software.

11

Service

Service

If the unit requires service, do not return it to the dealer. Follow these steps:

1. Review the Troubleshooting section of the manual to eliminate common problems.

2. If the problem persists, contact APC by Schneider Electric Customer Support through the APC Web site,

www.apc.com.

a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.

b. Call APC by Schneider Electric Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization

Number (RMA#).

c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the APC Web site for country specific instructions.

3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.

a. Always DISCONNECT THE UPS BATTERY before shipping in compliance with U.S.

Department of Transportation (DOT) and IATA regulations. The battery may remain in the unit.

b. Internal batteries may remain connected in the XLBP during shipment, if applicable, not all units have

XLBPs.

4. Write the RMA# provided by Customer Support on the outside of the package.

5. Return the unit by insured, pre-paid carrier to the address provided by Customer Support.

Transport the unit

1. Shut down and disconnect all connected equipment.

2. Disconnect the unit from AC power.

3. Disconnect all internal and external batteries (if applicable).

4. Follow the shipping instructions outlined in the Service section of this manual.

APC by Schneider Electric IT Worldwide

Customer Support

Go to the APC Web site, www.apc.com for country specific customer support.

12

Warranty

Warranty

The standard warranty is two (2) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical

Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT.

SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

13

© 2013 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.

EN 990-4412A

04/2013