APC NetShelter SV 42U User manual
Add to my manuals
34 Pages
APC NetShelter SV 42U is a versatile and secure cabinet designed to store industry-standard 19-inch rack-mount equipment, providing a reliable and organized solution for your IT infrastructure. With its sturdy construction and customizable features, it offers optimal protection and efficient use of space for your valuable equipment.
advertisement
User Manual
NetShelter SV
This manual is available in English on the APC Web site (www.apc.com).
Dieses Handbuch ist in Deutsch auf der APC Webseite (www.apc.com) verfügbar.
Este manual está disponible en español en la página web de APC (www.apc.com).
Ce manuel est disponible en français sur le site internet d’APC (www.apc.com).
Questo manuale è disponibile in italiano sul sito web di APC (www.apc.com).
本マニュアル<各国の言語に対応する>は APC ウェブサイト (www.apc.com) からダウンロードできま
す
。
Instrukcja obslugi w jezyku polskim jest dostepna na stronie internetowej APC (www.apc.com).
Данное руководство на русском языке доступно на сайте APC (www.apc.com)
Bu kullanim klavuzunun Türkçesi APC web sayfasinda (www.apc.com) mevcuttur.
在 APC 公司的网站上 (www.apc.com) 有本手册的中文版。
Este manual está disponível em português no site da APC (www.apc.com).
Disclaimer
The information presented in this manual is not warranted by APC by Schneider Electric to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, APC by Schneider Electric assumes no liability for damages, violations of codes, improper installation, or any other problems that could arise based on the use of this publication.
The information contained in this publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction. This publication has been compiled in good faith by APC by Schneider Electric. However, no representation is made or warranty given, either express or implied, as to the completeness or accuracy of the information this publication contains.
IN NO EVENT SHALL APC BY SCHNEIDER ELECTRIC, OR ANY AFFILIATE OR
SUBSIDIARY COMPANY OF SCHNEIDER ELECTRIC OR THEIR RESPECTIVE
OFFICERS, DIRECTORS, OR EMPLOYEES BE LIABLE FOR ANY DIRECT, INDIRECT,
CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING,
WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE,
DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING
OUT OF, OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS
PUBLICATION OR THE CONTENT, EVEN IF APC BY SCHNEIDER ELECTRIC HAS BEEN
EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. APC BY SCHNEIDER
ELECTRIC RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT
TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY
TIME WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio, video, text, and photographs) rests with APC by Schneider Electric or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information.
This publication shall not be for resale in whole or in part.
Please Note:
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
No responsibility is assumed by APC by Schneider Electric for any consequences arising from the use of this material.
Contents
General Information ........................................................ 1
Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Receiving and Unpacking .............................................. 3
Please Recycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Moving the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Component Identification............................................... 5
Equipment Installation Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Tools (provided) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Tools (not provided) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Cabinet Installation ......................................................... 7
Moving the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Secure the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ground the Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Bonding Location on the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Customize the Cabinet ................................................. 10
Reverse the Front Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Remove and install side panels . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NetShelter SV User Manual i
Equipment Installation .................................................. 14
Adjust Vertical Mounting Flanges. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installing Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Vertical Mounting Flange Cutouts . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cable Management........................................................ 18
Adjust Vertical 0 U Accessory Mounting Brackets . . . . . . . . . . . . . 18
Specifications ................................................................ 19
42 U Cabinets, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
42 U Cabinets, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
48 U Cabinets, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
APC Limited Factory Warranty..................................... 24
Terms of Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Non-transferable Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Warranty Claims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ii NetShelter SV User Manual
General Information
Introduction
The NetShelter
®
SVcabinet is for storage of industry-standard (EIA/ECA-310), 19-inch rack-mount hardware, which includes servers and voice, data, networking, internetworking, and APC by Schneider
Electric power protection equipment.
This manual provides installation and customization instructions for the following:
• NetShelter SV 42 U, 600 mm (23.6 in) wide, 1000 mm (39.4 in) deep cabinet (AR2200)
• NetShelter SV 42 U, 600 mm (23.6 in) wide, 1060 mm (41.7 in) deep cabinet (AR2400)
• NetShelter SV 42 U, 600 mm (23.6 in) wide, 1060 mm (41.7 in) deep cabinet without side panels (AR2401)
• NetShelter SV 42 U, 600 mm (23.6 in) wide, 1200 mm (47.2 in) deep cabinet (AR2500)
• NetShelter SV 42 U, 800 mm (31.5 in) wide, 1000 mm (39.4 in) deep cabinet (AR2280)
• NetShelter SV 42 U, 800 mm (31.5 in) wide, 1060 mm (41.7 in) deep cabinet (AR2480)
• NetShelter SV 42 U, 800 mm (31.5 in) wide, 1200 mm (47.2 in) deep cabinet (AR2580)
• NetShelter SV 48 U, 600 mm (23.6 in) wide, 1060 mm (41.7 in) deep cabinet (AR2407)
• NetShelter SV 48 U, 600 mm (23.6 in) wide, 1200 mm (47.2 in) deep cabinet (AR2507)
• NetShelter SV 48 U, 800 mm (31.5 in) wide, 1060 mm (41.7 in) deep cabinet (AR2487)
• NetShelter SV 48 U, 800 mm (31.5 in) wide, 1200 mm (47.2 in) deep cabinet (AR2587)
NOTICE
• NetShelter SV cabinets are intended for use with approved equipment. If you install other than approved equipment, fully evaluate the safety of your configuration.
• Use qualified personnel to install the cabinet.
NetShelter SV User Manual 1
Safety
Important Safety Information
Read the instructions carefully to become familiar with the equipment before trying to assemble, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, can result in moderate injury.
NOTICE
Addresses practices not related to physical injury including certain environmental hazards, potential damage or loss of data.
2 NetShelter SV User Manual
Receiving and Unpacking
NOTICE
APC by Schneider Electric is not responsible for damage sustained during shipment of this product.
Inspection
Upon receipt, inspect the package and contents for damage. Verify the contents are complete.
Report missing contents, damage, or other problems immediately to APC by Schneider Electric or your
APC reseller. Keep all packaging for inspection if damage is found.
Please Recycle
The shipping materials are recyclable. Save them for later use, or dispose of them appropriately.
Moving the Equipment
Recommended tools for moving the equipment while it is still on the pallet:
Forklift
Pallet Jack
NetShelter SV User Manual 3
Unpacking
WARNING
TIP HAZARD
This cabinet is easily tipped. Use extreme caution when unpacking or moving.
• Use at least two people to unpack and move the cabinet.
• Before moving the cabinet on its casters, load 158 kg (350 lbs) of equipment into the bottom of the cabinet for extra stability.
• When moving on its casters, make sure the leveling feet are up and push the cabinet from the front or rear.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1. Move the shipping pallet to a firm, level surface.
2. Inspect for visible signs of shipping damage. If damage has been detected, contact APC
Customer Support using the contact information on the back cover of this manual.
3. Remove the plastic stretch wrap, cardboard corners, and polyethylene bag surrounding the equipment.
4. Use the Torx T30/#2 Phillips wrench (provided) and 13 mm wrench (not provided) to remove the four pallet mounting brackets. Save these mounting brackets if you plan to bolt the cabinet to the floor.
5. Carefully roll the equipment off the pallet and onto the floor.
4 NetShelter SV User Manual
Component Identification
Item Description Qty Item
Roof 1
Rear Frame
1
Grounding wire
Rear Split Doors
3
2
Side Panels
Horizontal Side Braces
Leveling Feet
2
6
Accessory Mounting Brackets
4
Base 1
4
Description
Casters
Front Frame
Hardware Bag
Door and Side Panel Keys
Door Handles
Front Door
APC Nameplate
Vertical Mounting Flanges
Roof/Base Access Panels
Qty
1
4
2
1
2
1
2
4
1
NetShelter SV User Manual 5
Equipment Installation Hardware
Plastic cup washers (30)
M6 x 16 Phillips head screws (30)
Cage nuts (30) Joining Brackets for
24 in centers (4)
M5 x 12 screws (4)
Tools (provided)
Tools (not provided)
Torx® T30/#2 Phillips wrench Cage nut tool
Torque wrench Open end wrench
6 NetShelter SV User Manual
Cabinet Installation
Moving the Cabinet
WARNING
TIP HAZARD
This cabinet is easily tipped. Use extreme caution when unpacking or moving.
• Use at least two people to unpack and move the cabinet.
• Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom equipment mounting space of the cabinet for extra stability.
• When moving on its casters, make sure the leveling feet are up and push the cabinet from the front or rear.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Casters: To move the cabinet on its casters, the equipment load must be evenly distributed, must not exceed 460 kg (1,014 lb) and the equipment must not be installed above the 20 U height.
Level the Cabinet
NOTICE
The leveling feet provide a stable base if the floor is uneven, but cannot compensate for a steeply sloped surface.
The front door may need to be reversed. See “Reverse the Front Door” on page 10 for removal and
installation instructions.
1. Using a 13 mm wrench, lower each leveling foot until in makes contact with the floor.
2. Adjust each foot until the equipment is level and plumb.
NetShelter SV User Manual 7
Joining Cabinets
Cabinets can be joined with or without side panels installed to provide for alignment and some stability.
The cabinets are shipped with preinstalled joining brackets for 600 mm centers. To join on 24 in centers, the cabinet is provided with 24 in joining brackets in the hardware bag.
WARNING
TIP HAZARD
Joining cabinets provides limited stability. Ensure the cabinet is secured to the floor before installing equipment.
Failure to follow these instructions can result in serious injury or equipment damage.
1. Remove the front and rear doors.
2. The cabinet is preinstalled with 600 mm centers. To join with 24 in centers, replace the preinstalled joining brackets with 24 in joining brackets (provided in the hardware bag).
3. Align the cabinets and join them using one M5 x 12 flat-head screw (provided in the hardware bag) per bracket—two brackets for the front and two brackets for the rear.
4. Reinstall the doors.
600 x 4
8 NetShelter SV User Manual
Secure the Cabinet
NOTICE
Bolt-down brackets secure the cabinet to the pallet during shipment. Remove them from the cabinet and pallet and save them to secure the cabinet to the floor during installation.
WARNING
TIP HAZARD
Secure the cabinet to the floor before installing equipment.
Failure to follow these instructions can result in serious injury or equipment damage.
To secure the cabinet to the floor, use fastener locations on the outside or inside of the cabinet and the bolt-down brackets (provided).
Ground the Cabinet
Each cabinet should be bonded directly to a common ground using the designated grounding location
(two M6 threaded inserts) at the bottom rear of the cabinet.
• Use a Common Bonding Network Jumper kit (not provided). For example, Listed [KDER]
Panduit
®
RGCBNJ660PY or equivalent.
• Use paint-piercing washers between ground terminal and cabinet frame or remove paint on frame under ground terminals per NEC NFPA 70 Article 250.12
• Torque screws to (60 in-lb, 6.8 N-m).
Bonding Location on the Cabinet
NetShelter SV User Manual 9
Customize the Cabinet
Reverse the Front Door
You can reverse the front door so that the door is hinged on the opposite side.
1. Remove the handle using the Torx T30/#2 Phillips wrench (provided).
2. Unfasten the ground wire from the cabinet and door, then remove the door.
3. Rotate and reinstall the door to the opposite side. Remove any plastic hole plugs and reinstall the ground wire to the door and cabinet.
10 NetShelter SV User Manual
4. Remove and reinstall the latch and washer oriented as shown using a Torx T30/#2 Phillips wrench. The washer is rotated 90 degrees from its original orientation, and the latch is rotated
180 degrees.
5. Reinstall the handle to the door. Torque the screws to 28 - 30 in-lb (3.2 - 3.4 N-m).
NetShelter SV User Manual 11
Side Panels
Remove and install side panels
Rear Doors
Removal
1. Disconnect the grounding wires attached to the rear doors at the connector.
x 2
2. Remove the left and right rear doors by pulling the top hinge pin down to release the pin from the hole securing it to the frame.
3. Lift the door to remove the bottom hinge pin from the hole in the cabinet base. x 2
12 NetShelter SV User Manual
Installation
1. Install the left and right rear doors by aligning the bottom hinge pin to the hole in the cabinet base.
2. Pull the top hinge pin down, align with the hole in the roof, then release.
3. Connect the grounding wires. x 2 x 2
NetShelter SV User Manual 13
Equipment Installation
NOTICE
NetShelter SV cabinets are intended for use with Listed equipment. If you install un-Listed equipment, you should evaluate the safety of your configuration.
Adjust Vertical Mounting Flanges
Vertical mounting flanges come factory-installed in the proper location for use with rack-mountable equipment. The mounting flanges are adjustable towards the front or the rear of the cabinet to fit different rails or equipment with other depths to accommodate a wide variety of networking and telecommunications equipment.
14
Adjustable Vertical Mounting Flange
Cabinet Depth Factory Installed Minimum Depth Maximum Depth
1000 mm
1060 mm
1200 mm
678 mm (26.7 in)
738 mm (29.1 in)
878 mm (34.6 in)
168 mm (6.6 in)
168 mm (6.6 in)
258 mm (10.2 in)
718 mm (28.3 in)
778 mm (30.6 in)
918 mm (36.1 in)
NOTICE
If the vertical mounting flanges are adjusted from their factory mounting position more than 60 mm (2.4 in), the vertical mounting flanges attach to the cabinet side brace using
cage nuts and fasteners. Refer to the instructions on page 15.
NetShelter SV User Manual
Installation
1. Use the Torx T30/#2 Phillips wrench (provided) to adjust a vertical mounting flange. Remove the
T30 screws at the top, middle, and bottom of the vertical mounting flange. Save the screws for adjustment and reinstallation in the new position.
600 mm cabinet
800 mm cabinet
CAUTION
STABILITY HAZARD
When adjusting vertical mounting flanges, ensure that no equipment is installed on the vertical mounting flanges.
Failure to follow these instructions can result in injury or equipment damage.
NOTICE
• Vertical mounting flange attachment positions are in 10 mm (0.4 in) increments.
• If the vertical mounting flanges are adjusted from their factory mounting position more than 60 mm (2.4 in), the vertical mounting flanges attach to the cabinet side brace using cage nuts and fasteners.
NetShelter SV User Manual 15
2. Move the mounting flange to the desired location and reinstall the T30 fastener at the top, middle and bottom to secure the vertical mounting flange.
3. Perform the vertical mounting flange adjustment to the opposite side of the cabinet. Ensure that the same mounting position is used at the top, middle and bottom. Torque to 28 - 30 in-lb (3.2 -
3.4 N-m).
16
NOTICE
Verify that all Vertical Mounting Flanges are properly aligned before installing equipment in place.
NetShelter SV User Manual
Installing Equipment
WARNING
TIP HAZARD
This cabinet is easily tipped. Follow the precautions below during and after equipment installation.
• Make sure you have secured the cabinet to the floor before installing equipment.
• Install the heaviest equipment first toward the bottom of the cabinet to prevent the cabinet from becoming top-heavy.
• Do not extend equipment on sliding rails until you have installed 158 kg (350 lbs) of equipment into the bottom of the cabinet for stability or until you have installed the bolt-down brackets. Do not extend more than one piece of equipment on sliding rails at a time.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To install rack-mount equipment in the cabinet: 7
1. Review the equipment manufacturer’s installation instructions.
2. Locate the top and bottom U-space on the vertical mounting rails.
Every third hole on the mounting rail is numbered to indicate the middle of a U-space.
3. Install the cage nuts on the interior of the vertical mounting rail; then install the equipment. (To remove a cage nut, squeeze the sides to release it from the square hole.)
1 U 6
5
Vertical Mounting Flange Cutouts
For NetShelter SV 800 mm (31.5 in) wide cabinets with equipment requiring side airflow, remove the vertical mounting flange cutouts from the side of the cabinet nearest the air intake for the equipment.
Once the cutouts are removed, if requirements change, a selection of accessories can be used to cover the holes for airflow and cable management. Get more accessory information at the website (www.apc.com).
NetShelter SV User Manual 17
Cable Management
Route, secure, and organize cables using the multiple cable access openings on the cabinet roof, sides, and bottom, the accessory mounting brackets included with the cabinet, plus the variety of cable management accessories available.
Adjust Vertical 0 U Accessory Mounting Brackets
The vertical 0 U accessory mounting brackets (four included) provide toolless mounting capabilities for
APC by Schneider Electric Rack Power Distribution Units (PDUs) and cable management. They also provide tie-off locations for cables.
The factory-default position for the vertical 0 U accessory brackets is in the rear of the cabinet. The brackets are positioned for full-height vertical Rack PDUs.The bracket can be moved up or down to accommodate different accessories. Additional brackets are available for purchase as requirements change.
1. Use the Torx
®
T30/#2 Phillips wrench (provided) to remove the two T30 screws.
2. Move to the desired position, and reinstall the brackets.
18 NetShelter SV User Manual
Specifications
42 U Cabinets
Height
Width
Depth
Net weight
Total open area front door
Total open area rear door
Open area per U front door
Open area per U rear door
Perforation pattern
Perforation pattern front door
Perforation pattern rear door
Clearance (for wiring between front door and vertical mounting flange)
AR2200
2057 mm (80.9 in)
600 mm (23.6 in)
1000 mm (39.4 in)
108.8 kg (239.9 lb)
778 176 mm
2
(30,637 in
2
)
805 637 mm
2
(31,718 in
2
)
18 528 mm
2
(730 in
2
)
19 182 mm
2
(755 in
2
)
69.4 % open area
69.3 %
71.7 %
14.0 mm (0.6 in)
AR2400
2057 mm (80.9 in)
600 mm (23.6 in)
1060 mm (41.7 in)
112.2 kg (247.4 lb)
778 176 mm
2
(30,637 in
2
)
805 637 mm
2
(31,718 in
2
)
18 528 mm
2
(730 in
2
)
19 182 mm
2
(755 in
2
)
69.4 % open area
69.3 %
71.7 %
14.0 mm (0.6 in)
Weight rating: static (leveling feet) load
Weight rating: dynamic (casters) load
†
1000 kg (2,205 lb)
460 kg (1,014 lb)
1000 kg (2,205 lb)
460 kg (1,014 lb)
1000 kg (2,205 lb)
460 kg (1,014 lb)
Weight rating: cabinet roof cable load
45 kg (99 lb) 45 kg (99 lb) 45 kg (99 lb)
†
To move the cabinet on its casters, the equipment load must be evenly distributed, must not exceed 460 kg (1,014 lb) and the equipment must not be installed above the 20 U height.
AR2401
2057 mm (80.9 in)
600 mm (23.6 in)
1060 mm (41.7 in)
85.0 kg (187.4 lb)
778 176 mm
2
(30,637 in
2
)
805 637 mm
2
(31,718 in
2
)
18 528 mm
2
(730 in
2
)
19 182 mm
2
(755 in
2
)
69.4 % open area
69.3 %
71.7 %
14.0 mm (0.6 in)
NetShelter SV User Manual 19
42 U Cabinets, continued
Height
Width
Depth
Net weight
Total open area front door
Total open area rear door
Open area per U front door
Open area per U rear door
Perforation pattern
Perforation pattern front door
Perforation pattern rear door
Clearance (for wiring between front door and vertical mounting flange)
AR2500
2057 mm (80.9 in)
600 mm (23.6 in)
1200 mm (47.2 in)
121.3 kg (267.4 lb)
778 176 mm
2
(30,637 in
2
)
805 637 mm
2
(31,718 in
2
)
18 528 mm
2
(730 in
2
)
19 182 mm
2
(755 in
2
)
69.4 % open area
69.3 %
71.7 %
14.0 mm (0.6 in)
AR2280
2057 mm (80.9 in)
800 mm (31.5 in)
1000 mm (39.4 in)
126.7 kg (279.3 lb)
1 137 330 mm
2
(44,777 in
2
)
1 171 657 mm
2
(46,128 in
2
)
27 079 mm
2
(1,066 in
2
)
27 897 mm
2
75.8 %
78.0 %
(1,098 in
2
69.4 % open area
14.0 mm (0.6 in)
)
Weight rating: static (leveling feet) load
Weight rating: dynamic (casters) load
†
1000 kg (2,205 lb)
460 kg (1,014 lb)
1000 kg (2,205 lb)
460 kg (1,014 lb)
Weight rating: cabinet roof cable load 45 kg (99 lb) 45 kg (99 lb)
†
To move the cabinet on its casters, the equipment load must be evenly distributed, and must not exceed 460 kg (1,014 lb) and equipment must not be installed above the 20 U height.
20 NetShelter SV User Manual
42 U Cabinets, continued
Height
Width
Depth
Net weight
Total open area front door
Total open area rear door
Open area per U front door
Open area per U rear door
Perforation pattern
Perforation pattern front door
Perforation pattern rear door
Clearance (for wiring between front door and vertical mounting flange)
Weight rating: static (leveling feet) load
Weight rating: dynamic (casters) load †
Weight rating: cabinet roof cable load
AR2480
2057 mm (80.9 in)
800 mm (31.5 in)
1060 mm (41.7 in)
130.5 kg (287.7 lb)
1 137 330 mm
2
(44,777 in
2
)
1 171 657 mm
2
(46,128 in
2
)
27 079 mm
2
(1,066 in
2
)
27 897 mm
2
(1,098 in
2
)
69.4 % open area
75.8 %
78.0 %
14.0 mm (0.6 in)
1000 kg (2,205 lb)
460 kg (1,014 lb)
45 kg (99 lb)
AR2580
2057 mm (80.9 in)
800 mm (31.5 In)
1200 mm (47.2 in)
139.5 kg (307.5 lb)
1 137 330 mm
2
(44,777 in
2
)
1 171 657 mm
2
(46,128 in
2
)
27 079 mm
2
(1,066 in
2
)
27 897 mm
2
(1,098 in
2
)
69.4 % open area
75.8 %
78.0 %
14.0 mm (0.6 in)
1000 kg (2,205 lb)
460 kg (1,014 lb)
45 kg (99 lb)
†
To move the cabinet on its casters, the equipment load must be evenly distributed, and must not exceed 460 kg (1,014 lb) and equipment must not be installed above the 20 U height.
NetShelter SV User Manual 21
48 U Cabinets
Height
Width
Depth
Net weight
Total open area front door
Total open area rear door
Open area per U front door
Open area per U rear door
Perforation pattern
Perforation pattern front door
Perforation pattern rear door
Clearance (for wiring between front door and vertical mounting flange)
Weight rating: static (leveling feet) load
Weight rating: dynamic (casters) load
Weight rating: cabinet roof cable load
†
AR2407
2324 mm (91.5 in)
600 mm (23.6 in)
1060 mm (41.7 in)
123.5 kg (272.3 lb)
900 609 mm
2
(35,457in
2
)
917 858 mm
2
(36,136 in
2
)
187 63 mm
2
(739.4 in
2
)
19 122 mm
2
(753 in
69.4 % open area
70.3 %
71.6 %
14.0 mm (0.6 in)
1000 kg (2,205 lb)
460 kg (1,014 lb)
45 kg (99 lb)
2
)
AR2507
2324 mm (91.5 in)
600 mm (23.6 in)
1200 mm (47.2 in)
131.2 kg (289.2 lb)
900 609 mm
2
(35,457in
2
)
917 858 mm
2
(36,136 in
2
)
187 63 mm
2
(739.4 in
2
)
19 122 mm
2
70..3 %
71.6 %
45 kg (99 lb)
(753 in
2
69.4 % open area
14.0 mm (0.6 in)
1000 kg (2,205 lb)
460 kg (1,014 lb)
)
†
To move the cabinet on its casters, the equipment load must be evenly distributed, and must not exceed 460 kg (1,014 lb) and equipment must not be installed above the 20 U height.
22 NetShelter SV User Manual
48 U Cabinets, continued
Height
Width
Depth
Net weight
Total open area front door
Total open area rear door
Open area per U front door
Open area per U rear door
Perforation pattern
Perforation pattern front door
Perforation pattern rear door
Clearance (for wiring between front door and vertical mounting flange)
Weight rating: static (leveling feet) load
Weight rating: dynamic (casters) load
Weight rating: cabinet roof cable load
†
AR2487
2324 mm (91.5 in)
800 mm (31.5 in)
1060 mm (41.7 in)
143.8 kg (317.0 lb)
1 316 270 mm
2
(51,286 in
2
)
1 334 498 mm
2
(52,539.4 in
2
)
27 422 mm
2
(1,080 in
2
)
27 802 mm
2
(1,095 in
69.4 % open area
76.9 %
78.0 %
14.0 mm (0.6 in)
1000 kg (2,205 lb)
460 kg (1,014 lb)
45 kg (99 lb)
2
)
AR2587
2324 mm (91.5 in)
800 mm (31.5 in)
1200 mm (47.2 in)
152.8 kg (336.9 lb)
1 316 270 mm
2
(51,286 in
2
)
1 334 498 mm
2
(52,539.4 in
2
)
27 422 mm
2
(1,080 in
2
)
27 802 mm
2
(1,095 in
2
)
69.4 % open area
76.9 %
78.0 %
14.0 mm (0.6 in)
1000 kg (2,205 lb)
460 kg (1,014 lb)
45 kg (99 lb)
†
To move the cabinet on its casters, the equipment load must be evenly distributed, and must not exceed 460 kg (1,014 lb) and equipment must not be installed above the 20 U height.
NOTICE
It is prohibited to ship a NetShelter SV cabinet while the unit is loaded with any equipment.
NetShelter SV User Manual 23
APC Limited Factory Warranty
The limited warranty provided by APC by Schneider Electric in this Statement of Limited Factory
Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business.
Terms of Warranty
APC by Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of five years (two years in Japan) from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its sole discretion, any such defective products. This warranty does not apply to equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified in any way. Repair or replacement of a defective product or part thereof does not extend the original warranty period. Any parts furnished under this warranty may be new or factory- remanufactured.
Non-transferable Warranty
This warranty applies only to the original purchaser who must have properly registered the product.
Product may be registered at http://www.warranty.apc.com.
Exclusions
APC by Schneider Electric shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation or testing. Further, APC by Schneider Electric shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere, repair, installation, start-up by non-APC designated personnel, a change in location or operating use, exposure to the elements, Acts of God, fire, theft, or installation contrary to APC by Schneider Electric recommendations or specifications or in any event if the APC by Schneider Electric serial number has been altered, defaced, or removed, or any other cause beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR
OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS
AGREEMENT OR IN CONNECTION HEREWITH. APC BY SCHNEIDER ELECTRIC
DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND
FITNESS FOR A PARTICULAR PURPOSE. APC BY SCHNEIDER ELECTRIC EXPRESS
WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO
OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC BY SCHNEIDER ELECTRIC
RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH
THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE
AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET
FORTH ABOVE CONSTITUTE APC BY SCHNEIDER ELECTRIC SOLE LIABILITY AND
PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC
WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD
PARTIES.
24 NetShelter SV User Manual
IN NO EVENT SHALL APCBY SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL,
CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR
INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN
CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY
OR WHETHER APC BY SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF
THE POSSIBLY OF SUCH DAMAGES. SPECIFICALLY, APC BY SCHNEIDER ELECTRIC
IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF
EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC BY SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY
TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC BY
SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Warranty Claims
Customers with warranty claims issues may access the APC by Schneider Electric worldwide customer support network by visiting http://www.apc.com/support. Select your country from the country selection pull-down menu. Open the Support tab at the top of the web page to obtain contact information for customer support in your region.
NetShelter SV User Manual 25
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact the APC Customer Support Center by telephone or e-mail.
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
For information on how to obtain local customer support, contact the APC representative or other distributors from whom you purchased your APC product.
© 2013 APC by Schneider Electric. APC, the APC logo, and NetShelter are owned by Schneider Electric
Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.
990-4823-001 1/2013
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Disclaimer
- 3 Please Note:
- 7 General Information
- 7 Introduction
- 8 Safety
- 8 Important Safety Information
- 9 Receiving and Unpacking
- 9 Inspection
- 9 Please Recycle
- 9 Moving the Equipment
- 10 Unpacking
- 11 Component Identification
- 12 Equipment Installation Hardware
- 12 Tools (provided)
- 12 Tools (not provided)
- 13 Cabinet Installation
- 13 Moving the Cabinet
- 13 Level the Cabinet
- 14 Joining Cabinets
- 15 Secure the Cabinet
- 15 Ground the Cabinet
- 15 Bonding Location on the Cabinet
- 16 Customize the Cabinet
- 16 Reverse the Front Door
- 18 Side Panels
- 18 Remove and install side panels
- 18 Rear Doors
- 18 Removal
- 19 Installation
- 20 Equipment Installation
- 20 Adjust Vertical Mounting Flanges
- 21 Installation
- 23 Installing Equipment
- 23 Vertical Mounting Flange Cutouts
- 24 Cable Management
- 24 Adjust Vertical 0 U Accessory Mounting Brackets
- 25 Specifications
- 25 42 U Cabinets
- 26 42 U Cabinets, continued
- 27 42 U Cabinets, continued
- 28 48 U Cabinets
- 29 48 U Cabinets, continued
- 30 APC Limited Factory Warranty
- 30 Terms of Warranty
- 30 Non-transferable Warranty
- 30 Exclusions
- 31 Warranty Claims