Kromschroder PFU 760 Technical Information

Add to my manuals
65 Pages

advertisement

Kromschroder PFU 760 Technical Information | Manualzz

Burner control unit PFU 760

Technical Information · GB

6.2.1.4 Edition 05.11

• For directly ignited burners of unlimited capacity in intermittent operation or in continuous operation pursuant to EN 746-2

• Plug-in function unit for mounting in 19" module subracks

• Flame control by UV, ionization or a further option of using the furnace chamber temperature

• Display of the program status, unit parameters and flame signal;

Manual mode for burner adjustment and for diagnostic purposes

• Visualization and adaptation to the specific application via the PC programming and diagnostic software BCSoft to simplify logistics management

• Air valve control relieves the furnace control

• Connection to PROFIBUS-DP via field bus interface PFA

• Certified for systems up to SIL 3 and compliant with PL e

www.kromschroeder.com

Contents

Burner control unit PFU 760 . . . . . . . . . . . . . . . . . . . . . . . . . 1

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.1 Examples of application. . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.1.1 Staged On/Off burner control . . . . . . . . . . . . . . . . . . . . . . . . .6

1.1.2 Staged High/Low burner control . . . . . . . . . . . . . . . . . . . . . .7

1.1.3 Two-stage-controlled burner . . . . . . . . . . . . . . . . . . . . . . . . 8

1.1.4 Modulating-controlled burner . . . . . . . . . . . . . . . . . . . . . . . .9

1.1.6 PFU for PROFIBUS-DP with PFA 700 . . . . . . . . . . . . . . . . . . .10

1.1.5 PFU 760..D: High temperature equipment . . . . . . . . . . . . .10

2 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

3 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

3.1 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

3.1.1 PFU 760 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

3.1.2 PFU 760..K1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

3.1.3 PFU 760..K2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

3.2 PFU 760 program sequence . . . . . . . . . . . . . . . . . . . . 15

3.3 Program status and fault messages . . . . . . . . . . . . . . 17

4 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

4.1 Scanning the parameters . . . . . . . . . . . . . . . . . . . . . . . 19

4.2 Flame control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

4.2.1 Burner flame signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

4.2.2 Program status when the most recent fault occurred. . . 20

4.2.3 Switch-off threshold of the flame amplifier . . . . . . . . . . . 20

4.2.4 High temperature operation with PFU..D . . . . . . . . . . . . . 21

4.2.5 UVS check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

4.3 Behaviour in start-up position/standby. . . . . . . . . . . . 25

4.3.1 Flame simulation check in start-up position/standby . . . 25

4.3.2 Minimum burner pause time t

BP

. . . . . . . . . . . . . . . . . . . 26

4.4 Behaviour during start-up . . . . . . . . . . . . . . . . . . . . . . 27

4.4.1 Safety time on start-up t

SA

4.4.2 Flame proving period t

FS

. . . . . . . . . . . . . . . . . . . . . . . . . .27

. . . . . . . . . . . . . . . . . . . . . . . . . . .27

4.4.3 Minimum combustion time t

B

. . . . . . . . . . . . . . . . . . . . . .27

4.4.4 Burner start-up attempts . . . . . . . . . . . . . . . . . . . . . . . . . . 28

4.5 Behaviour during operation . . . . . . . . . . . . . . . . . . . . . 29

PFU 760 · Edition 05.11

4.5.1 Safety time during operation t

SB

for V1 and V2. . . . . . . . . 29

4.5.2 Fault lock-out or restart . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

4.6 Switchable gas valve V2 on PFU..L . . . . . . . . . . . . . . . 31

4.7 Air valve control PFU..L . . . . . . . . . . . . . . . . . . . . . . . . . 32

4.7.1 Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

4.7.2 Cooling in start-up position/standby . . . . . . . . . . . . . . . . 32

4.7.3 Burner start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

4.7.4 Air valve opens in the case of external activation (not during start-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

4.7.5 Air valve opens in the case of external activation (even during start-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

4.7.6 Air valve opens with valve V1 . . . . . . . . . . . . . . . . . . . . . . 35

4.7.7 Air valve opens with valve V2 . . . . . . . . . . . . . . . . . . . . . . 36

4.7.8 Low fire over run time t

KN

after a controlled shut-down . .37

4.7.9 Behaviour of the air valve in the event of a fault lock-out 38

4.8 Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

4.8.1 Manual mode limited to 5 minutes. . . . . . . . . . . . . . . . . . 39

4.9 Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

4.10 Multi-flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

5 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

5.1 Safety time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

5.1.1 Calculating the safety time t

SA

. . . . . . . . . . . . . . . . . . . . . . . 41

5.2 Selection table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

5.3 Type code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

6 Project planning information . . . . . . . . . . . . . . . . . . . . . 43

6.1 Cable selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6.1.1 Ignition cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6.1.2 Ionization cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6.1.3 UV cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6.2 Ignition electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6.2.1 Electrode gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6.2.2 Star electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6.3 Minimum combustion time . . . . . . . . . . . . . . . . . . . . . 44

6.4 Safety interlocks (Limits) . . . . . . . . . . . . . . . . . . . . . . . . 44

6.5 Emergency stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

t

= To be continued

2

6.5.1 In the event of fire or electric shock. . . . . . . . . . . . . . . . . . 44

6.5.2 Via the safety interlocks (limits) . . . . . . . . . . . . . . . . . . . . . 44

6.6 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

6.6.1 Parallel reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

6.6.2 Permanent remote reset . . . . . . . . . . . . . . . . . . . . . . . . . . 45

6.6.3 Automatic remote reset (PLC) . . . . . . . . . . . . . . . . . . . . . . 45

6.6.4 Burner start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

6.6.5 Restart and start-up attempts. . . . . . . . . . . . . . . . . . . . . . 45

6.7 Fault signalling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

6.8 Protecting the burner from overload . . . . . . . . . . . . . . 46

6.9 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

6.10 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

6.10.1 UVS sensor wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

6.11 PFU switched off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

6.12 Furnace control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

6.13 Note on EC type-examination. . . . . . . . . . . . . . . . . . . 47

6.14 Mains switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

6.15 Changing parameters. . . . . . . . . . . . . . . . . . . . . . . . . 47

7 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

7.1 With ionization sensor . . . . . . . . . . . . . . . . . . . . . . . . . . 48

7.2 With UV sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

7.3 Via the temperature in high temperature equipment 48

8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

8.1 High-voltage cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

8.2 BCSoft. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

8.3 Stickers for labelling . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

8.4 “Changed parameters” stickers. . . . . . . . . . . . . . . . . . 49

8.5 Radio interference suppressed electrode adapters . 50

8.6 Socket connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

8.7 Module subracks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

8.8 Power supply PFP 700 . . . . . . . . . . . . . . . . . . . . . . . . . 51

8.9 Relay module PFR 704 . . . . . . . . . . . . . . . . . . . . . . . . . 52

8.10 Flame detector PFF 704 . . . . . . . . . . . . . . . . . . . . . . . . 53

8.11 Field bus interface PFA 700 . . . . . . . . . . . . . . . . . . . . . 54

3

8.12 Impulse system MPT 700 . . . . . . . . . . . . . . . . . . . . . . 55

9 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

9.1 Safety-specific characteristic values. . . . . . . . . . . . . . . 58

9.2 Operating controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

10 Maintenance cycles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

11 Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

12 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

12.1 Waiting time t

W

. . . . . . . . . . . . . . . . . . . . . . . . . . . 62

12.2 Safety time on start-up t

12.3 Ignition time t

Z

SA

. . . . . . . . . . . . . . . . . . . . . 62

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

12.4 Flame simulation/Flame simulation delay time t

LV

12.5 Safety time during operation t

SB

. 62

. . . . . . . . . . . . . . 62

12.6 Flame signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

12.7 Fault lock-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

12.8 Safety interlocks (Limits) . . . . . . . . . . . . . . . . . . . . . . . . 63

12.9 Pilot gas valve V1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

12.10 Main gas valve V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

12.11 Continuous operation . . . . . . . . . . . . . . . . . . . . . . . . . 63

12.12 Air valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

12.13 Diagnostic coverage DC . . . . . . . . . . . . . . . . . . . . . . 64

12.14 Mode of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

12.15 Safe failure fraction SFF . . . . . . . . . . . . . . . . . . . . . . . 64

12.16 Probability of dangerous failure PFH

D

. . . . . . . . . . . 64

12.17 Mean time to dangerous failure MTTF d

. . . . . . . . . . 64

Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

PFU 760 · Edition 05.11

t

= To be continued

1 Application

The burner control units PFU 760 control, ignite and monitor gas burners for intermittent or continuous operation. As a result of their fully electronic design they react quickly to

various process requirements and are therefore also suitable for frequent cycling operation.

The PFU 760 can be used for directly ignited industrial burners.

The burners may be modulating or stage-controlled.

On industrial furnaces, the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner, for example it ensures that the burner always ignites in a safe condition after it has been restarted.

The burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners.

Module subrack

BGT for instance serves to accommodate several function units. It is provided with a backplane with screw terminals for simple, reliable wiring.

The air valve control on the burner control unit PFU 760L assists the furnace control for cooling, purging and output control tasks.

The program status, the unit parameters and the level of the flame signal can be read directly from the unit. The burner can be controlled manually for commissioning and diagnostic purposes.

If the local requirements on the burner control unit change, the

PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interface.

The service personnel is supported by a convenient visualization system of the input and output signals and the error history.

To reduce the installation and wiring costs, Elster Kromschröder offers the field bus interface PFA 700 to transfer the control signals and feedbacks via PROFIBUS-DP.

PFU 760 · Edition 05.11

4

Application

Bogie hearth forging furnace in the metallurgical industry

Intermittent shuttle kiln in the ceramics industry

Walking beam furnace with overhead firing

5

PFU 760 · Edition 05.11

Application

L1, N, PE

DI

SPS

PLC

API

P

PFU 760L

DI

22a 10c 26e

P

30e

A

10a

ϑ1

10e

µC

22e 16c 28c 26a

TZI

UV

VAG

VR..R

2e

4e

2c

4c

6

1 .1 Examples of application

1 .1 .1 Staged On/Off burner control

The burner can be started with reduced capacity.

A UV sensor monitors the flame signal from the burner. UV sensor UVD 1 is used for continuous operation, UV sensor UVS for intermittent operation.

PFU 760 · Edition 05.11

Application > Examples of application

L1, N, PE

DI

SPS

PLC

API

P

PFU 760L

DI

22a 10c 26e

P A

30e 10a

ϑ1

10e

µC

22e 16c

VAS..N

GIK..B

28c 26a

TZI

VR..R

2e

4e

2c

4c

7

1 .1 .2 Staged High/Low burner control

The burner starts at low-fire rate. When the operating state is reached, the

PFU 760L advises the control unit. The

PLC can now pulse the air valve in order to control the burner output.

PFU 760 · Edition 05.11

Application > Examples of application

L1, N, PE

DI

SPS

PLC

API

P

PFU 760L

DI

22a 10c 26e

P

30e

A

10a

ϑ1

10e

µC

22e 18e 16c 28c 26a

VBY

TZI

VAG

4

7

M

BVA + IC 40

2e

4e

2c

4c

PFU 760 · Edition 05.11

8

1 .1 .3 Two-stage-controlled burner

Control: ON/OFF with ignition via bypass

The burner starts at low-fire rate. When the operating state is reached, the

PFU 760L issues the Enable signal for the maximum burner output.

Application > Examples of application

PFU 760

DI

22a

10c 26e

L1, N, PE

DI mA

SPS

PLC

API

P

ϑ1

10e

µC

16c 28c

26a

TZI

BIO

BIC

VAG

M

BVA+IC 20

2e

4e

2c

4c

9

1 .1 .4 Modulating-controlled burner

Control: continuous

The external control system moves the butterfly valve for air BVA to ignition

position. The burner starts at low-fire rate, and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled.

PFU 760 · Edition 05.11

Application > Examples of application

L1, N, PE

DI

SPS

PLC

API

P

BUS

PFU 760..D

µC

22a

DI

18a

PROFIBUS-DP

BUS

STW

>750 °C

L1

PFU 760..D

µC

22a

DI

18a

10

1 .1 .6 PFU for PROFIBUS-DP with PFA 700

The bus system transfers the control signals for starting, resetting and for controlling the air valve from the control system (PLC) to the PFU 760 via the PFA 700.

In the opposite direction it sends information on the operating status. Control

signals that are relevant for safety, such as the safety interlocks and digital input, are transferred independently of the bus communication by separate cables.

1 .1 .5 PFU 760 . .D: High temperature equipment

Indirect flame control using the temperature. During the start-up process, as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods.

When the working temperature has

exceeded 750°C, the safety temperature monitor (STW) takes over the indirect flame control.

PFU 760 · Edition 05.11

2 Certification

Certified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508

Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be used up to PL e.

EC type-tested and certified

AGA approved

AGA

Australian Gas Association, Approval No.: 5597 www.aga.asn.au/product_directory pursuant to

– Gas Appliances Directive (2009/142/EC) in conjunction with EN 298:2004-01,

Meets the requirements of the

– Low Voltage Directive (2006/95/EC),

– EMC Directive (2004/108/EC).

PFU . .T is FM approved

Factory Mutual Research Class: 1997.

Suitable for applications pursuant to NFPA 86. www.fmglobal.com

Products and Services

Product Certification

Approval Guide

PFU 760 · Edition 05.11

11

L1 (L1)

P

30e

Z

N (L2)

I

DI

26e

22a

N

30a

20c

230 V

32c

24c

28c

26a

PFF 704

24 V

0 V

24 V

0 V

8a

8c

8e

ϑ1

A

10e

12e

10a

12a

10c

12c

8a

8c

8e

F1

(

sk1

PFU 760L)

PFU 760

22e

16c

18e

V1

V2

N

µC

A

S

SK a

2a

4a s

2e

4e m

2c

4c

N

28c

26a

UVS

26a

20c

24c

N

28c

PFU 760 · Edition 05.11

12

3 Function

3 .1 Connection diagram

For cable selection and wiring, see page 43 (Project planning information).

3 .1 .1 PFU 760

For the explanation of symbols, see page 61 (Legend).

Function > Connection diagram

( PFU 760L..K1)

PFU 760..K1

L1 (L1)

DI

P

30e

26e

22a

F2

F1 sk1

22e

16c

18e

Z

N (L2)

I

N

30a

20c

230 V

32c

24c

28c

26a a

2a

4a s

2e

4e m

2c

4c

PFF 704

24 V

0 V

24 V

0 V

8a

8c

8e

ϑ1

A

10e

12e

10a

12a

10c

12c

8a

8c

8e

µC

A

S

SK

UVS 2

3

26a

20c

24c

N

28c

26a

N

28c

PFU 760 · Edition 05.11

V1

V2

N

3 .1 .2 PFU 760 . .K1

As a replacement unit for burner control unit PFS/PFD 778.

For the explanation of symbols, see page 61 (Legend).

13

Function > Connection diagram

Z

L1 (L1)

N (L2)

I

PFF 704

24 V

0 V

24 V

0 V

8a

8c

8e

ϑ1

A

P

30e

DI

26e

22a

N

30a

20c

230 V

32c

24c

28c

26a

(

F1

PFU 760L..K2)

PFU 760..K2

22e sk1

16c

18e a

2a

4a s

2e

4e m

2c

4c

10e

12e

10a

12a

10c

12c

8a

8c

8e

µC

A

S

SK

UVS

1

3

26a

20c

24c

N

28c

26a

N

28c

V1

V2

N

PFU 760 · Edition 05.11

3 .1 .3 PFU 760 . .K2

As a replacement unit for burner control unit PFU 778.

For the explanation of symbols, see page 61 (Legend).

14

Function

00

Switch on

PFU 760

In the event of fault signal:

Reset

Safety interlocks (Limits)

Start-up position/standby

01

Start-up with ϑ signal

Wait until min. burner pause time t

BP has elapsed (P21)

If parameter P15 = 0:

Flame simulation check

02

If parameter P15 = 1:

Flame simulation check

Safety time t

SA running (P22), ignition in process,

V1 opens and min. combustion time t starts to elapse (P20)

B

If no flame detected: next start-up attempt (P10) or fault lock-out

Flame proving period t running (P23)

FS

04

In the event of flame failure: fault lock-out

Operation signalling contact closes and V2 opens

In the event of flame failure: restart or fault lock-out

04

Controlled shut-down via ϑ signal

00

If min. combustion time t has elapsed:

Operation signalling contact opens,

V1 and V2 close,

B min. burner pause time t starts to elapse (P21)

BP

PFU 760L

with air valve control features the following additional functions.

In start-up position, the air valve can be opened for cooling

A

.

Using parameter 31, it can be determined whether the air valve can be activated externally

during start-up.

The air valve can be set to open together with V1 (display A2 ) via parameter 30.

15

3 .2 PFU 760 program sequence

Normal start-up

If an “old” fault is still being signalled after switching on, it will be necessary to reset this first.

When the safety interlocks are closed, the PFU reverts to start-up position and conducts a self-test. If it does not determine a malfunction of the internal electronic circuitry or of the flame sensor, the burner can be started.

The flame simulation check is conducted during start-up position or after applying the start-up signal (

ϑ), depending on parameter 15.

After the min. burner pause time t

BP

has elapsed, the PFU opens valve V1 and ignites the burner. The ignition time t

Z is constant.

If a flame is detected during the safety time t

SA

, the flame proving period t

FS starts after this safety time has elapsed.

Valve V2 opens and the operation t

signalling contact between terminals

2c and 4c closes. This completes startup. An adjustable min. combustion time

B

ensures that the burner burns for a defined period even if the start-up signal

(

ϑ) is switched off beforehand.

t

00

Switch on

PFU 760

In the event of fault signal:

Reset

Safety interlocks (Limits)

Start-up position/standby

01

Start-up with ϑ signal

Wait until min. burner pause time t

BP has elapsed (P21)

If parameter P15 = 0:

Flame simulation check

02

If parameter P15 = 1:

Flame simulation check

Safety time t

SA running (P22), ignition in process,

V1 opens and min. combustion time t starts to elapse (P20)

B

If no flame detected: next start-up attempt (P10) or fault lock-out

Function > PFU 760 program sequence

03

Flame proving period t running (P23)

FS

04

In the event of flame failure: fault lock-out

Operation signalling contact closes and V2 opens

In the event of flame failure: restart or fault lock-out

04

Controlled shut-down via ϑ signal

00

If min. combustion time t has elapsed:

Operation signalling

B contact opens,

V1 and V2 close, min. burner pause time t starts to elapse (P21)

BP

The air valve can also be set to open with V2 or to be activated externally (display  A4 ) via

parameter 30.

16

The burner can also be started manually with the aid of the button on the PFU.

Voltage must be applied continuously to terminals 10e, 26e and 30a in order for this to occur.

The PFU can also be operated in Manual mode for start-up.

Start-up without flame signal

If no flame is detected during the safety time t

SA

, either a fault lock-out occurs or up to three further start-up attempts occur. The required functions and, if

applicable, the number of start-up

attempts must be specified when ordering. (Parameter 10, “Burner start-up attempts”).

Behaviour in the event of flame failure during operation

If the flame fails during operation, either an immediate fault lock-out occurs or a restart occurs. This procedure can be set via the optical interface (parameter

12, “Burner restart”).

PFU 760 · Edition 05.11

Function

3 .3 Program status and fault messages

During operation, the 7-segment display shows the program status. In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault.

The burner control unit can be reset using the Reset button or the remote reset.

Program status

Start-up position/standby

Cooling

Waiting time/Pause time

Burner safety time on start-up

Burner flame proving period

Burner operation

Purge

Air valve

High temperature operation**

DISPLAY

Fault message (blinking*)

00

A0

1

2

3

4

P0

A

Flame simulation, pilot burner

Burner start-up without flame signal

Flame failure during burner flame proving period

Flame failure during operation, pilot burner

. .

10

32

Faulty remote reset

Supply voltage too low

33

35

Faulty parameterization

Short-circuit on a valve output

36

Short-circuit on ignition or valve output

51

Safety interlock failure

52

Permanent reset

53

Time between two start-ups is too short

* In Manual mode, two dots will blink on the display in program status 0104.

** Optionally available.

17

PFU 760 · Edition 05.11

4 Parameters

Description

Burner flame signal

Program status when the most recent fault occurred

Burner switch-off threshold

Burner start-up attempts

Burner restart

Safety time during operation for V1 and V2 t

SB

Flame simulation check in start-up position/standby

Minimum combustion time t

B

Minimum burner pause time t

BP

Burner safety time on start-up t

SA

Burner flame proving period t

FS

Switchable gas valve V2 (only on PFU..L)

Air valve control

Air valve can be activated externally on start-up

Air valve closed/can be activated in the event of malfunction

High temperature operation ** t

Parameter Value range Factory default

15

20

21

22

23

26

30

31

32

33

01

03

04

10

12

14

0 – 30 μA x0 – x8

1 – 20 µA

1 – 4

0; 1

1; 2 s

0; 1

25 s

0 – 250 s

3; 5; 10 s

0 – 25 s

0; 1

0; 1; 2

0; 1

0; 1

2; 3

1 µA

0 s

0

0

0

1

1

0

1 s

1 t

SA

0 s

Adjustable*

18

PFU 760 · Edition 05.11

Parameters

Description

Manual mode limited to 5 minutes

UVS check (1 x in 24 hours)

Low fire over run time

Purge

Multi-flame control

Password

* Adjustable using BCSoft software and a PC opto-adapter.

** Please quote in your order.

0 = Function inactive,

1 = Function active.

On parameterization, ensure that the program sequence matches the application. Select the parameters so that the burner can be operated as intended in all operating phases.

4 .1 Scanning the parameters

During operation, the 7-segment display shows the program status.

The flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the

Reset/Information button (for 2 s).

In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault in coded form.

Parameter Value range Factory default

34

35

36

0; 1

0; 1

0; 3; 5; 10; 15;

25; 60 s

1

0

0 s

42

45

50

0; 1

0; 1

0000 – 9999

1

0

1234

Adjustable*

19

PFU 760 · Edition 05.11

Parameters

4 .2 Flame control

4 .2 .1 Burner flame signal

Parameter 01

Flame signal of the burner, display in µA, measuring range:

0 – 30 µA.

4 .2 .2 Program status when the most recent fault occurred

Parameter 03

This indicates the program status in which the last burner fault occurred (e.g. the unit indicates that a flame simulation has been detected with a blinking 01.

In parameter 03, it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 ).

Result: A flame simulation was detected during the waiting time or standby.

20

4 .2 .3 Switch-off threshold of the flame amplifier

Parameter 04, burner switch-off threshold

The sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 µA.

Example: In the case of UV control with the UV sensor UVS, the signal of the burner to be monitored is influenced by other burners.

The set value can be incremented in parameter 04 so that only the flame of the system’s “own” burner is detected.

The measured flame signal of the system’s “own” burner should be at least 3 µA (empirical value) higher than the set switchoff threshold.

PFU 760 · Edition 05.11

Parameters > Flame control

4 .2 .4 High temperature operation with PFU . .D

Parameter 33

Operation of firing systems at temperatures above 750°C. The

PFU features a safety-relevant DI input (Digital Input). This input supports the “High temperature operation” function. If firing systems are operated above 750°C, the system is considered to be a high temperature equipment (see EN 746-2). Flame control must be in operation until the furnace wall temperature has exceeded 750°C. Note the requirements of the Standards!

Flame control can be dispensed with during high temperature operation to improve the system availability. This means that no incorrect flame signals, e.g. signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation, may lead to faults.

When the DI input is activated, the burner control unit reverts to High temperature mode. This means: the PFU operates without evaluation of the flame signal. The safety function of the device-internal flame control system is placed out of operation.

In High temperature mode, the gas valves are opened without flame control.

The precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature. For this purpose, we recommend a safety temperature monitor with twin thermocouple (DIN 3440). Sensor discontinuity, sensor short-circuit, failure of a component or mains failure must set the installation to a safe state.

21

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750°C. The PFU starts the burner as usual, without monitoring the presence of the flame.

00 02 03 04

t

Z t

SA t

FS

88

30a

26e

10e

ϑ

DI

16c

26a

2c–4c

18e

2e–4e

V1

V2 t

If the temperature in the furnace chamber drops below 750°C, the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system.

t

PFU 760 · Edition 05.11

Parameters > Flame control > High temperature operation with PFU . .D

The PFU then responds, depending on setting:

Parameter 33 = 1 (PFU 760..K2 only)

Parameter 33 = 2

04 01 02

04 01 02 03 04 88

30a

26e

10e

28c

22a

ϑ

DI

26a

2c–4c

18e

2e–4e

2a–4a

V1

V2 t FA t

W t

Z t

SA t

FS

If the flame fails during high temperature operation, the ready contact opens for the duration of the flame failure (FA).

When High temperature mode is ended, the PFU switches off the burner and restarts with flame simulation check (recommended in the case of UV control with UVS).

t

W t

Z t

SA

03

t

FS

04 88

30a

26e

10e

28c

22a

ϑ

26a

2c–4c

18e

2e–4e

2a–4a

DI

V1

V2 t

22

When High temperature mode is ended, the PFU switches off the burner and restarts with flame simulation check (recommended in the case of UV control with UVS).

On programming parameter 33, ensure that the program sequence matches the application. Select the parameters so that the burner can be operated as intended in all operating phases.

t

PFU 760 · Edition 05.11

Parameters > Flame control > High temperature operation with PFU . .D

Parameter 33 = 3

04 04

88

30a

26e

10e

ϑ

DI

16c

26a

2c–4c

18e

2e–4e

V1

V2 t

When High temperature mode is ended, the burner remains in operation and the PFU performs flame control again

(recommended in the case of ionization control or UV control with UVD).

If no flame signal is present when High temperature mode is ended, the burner control unit performs a fault lock-out, regardless of parameter 33.

04 04 88

30a

26e

10e

ϑ

26a

2c–4c

18e

2e–4e

DI

V1

V2 t

Parameter 33 = 4 (PFU 760..K2 only)

04

FA

04 88

30a

26e

10e

28c

22a

16c

26a

2c–4c

18e

DI

2e–4e

2a–4a

ϑ

V1

V2 t

23

If the flame fails during high temperature operation, the ready contact is opened for the duration of the flame failure.

When High temperature mode is ended, the burner remains in operation and the PFU performs flame control again

(recommended in the case of ionization control or UV control with UVD).

PFU 760 · Edition 05.11

Parameters > Flame control

4 .2 .5 UVS check

Parameter 35

An automatic restart of the burner control unit can be activated every 24 hours via this parameter. The time starts each time the start-up signal (

ϑ) is applied.

Parameter 35 = 0: Unlimited burner operation.

Parameter 35 = 1: An automatic restart is activated once every

24 hours.

It must be ensured in this case that the program sequence started matches the application. This parameter may be set in this way only if the burner can restart as intended in all operating phases.

24

PFU 760 · Edition 05.11

Parameters

4 .3 Behaviour in start-up position/standby

4 .3 .1 Flame simulation check in start-up position/standby

Parameter 15

This defines the instant for the flame simulation check.

00 01 02 . . . 88

00 01

t

W

02 . . . 88

t

V1

Parameter 15 = 0: The flame simulation check is conducted

00

W after applying the start-up signal ( t

ϑ) during the waiting time t

W

.

00 02 . . . 88

t

V1 t

Parameter 15 = 1: The flame simulation check is conducted provided no start-up signal (

ϑ) is applied (during the so-called start-up position/standby). This allows fast start-up of the burner since there is no waiting time t

W

.

The burner must have been switched off for at least 4 s before start-up in order for the flame simulation check to be conducted correctly.

25

What is an extraneous signal?

00 01

88

30a

26e

10e

28c

26a

16c

ϑ

V1

V2

2e–4e t t

LV

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence. If the PFU 760 notices such an extraneous signal during the flame simulation check, it starts the flame simulation delay time t

LV

. If the extraneous signal is discontinued during this period, the burner can start up.

Otherwise, a fault lock-out occurs. 01 blinks on the display.

The flame simulation check of the burner is active until valve

V1 is enabled.

PFU 760 · Edition 05.11

Parameters > Behaviour in start-up position/standby

4 .3 .2 Minimum burner pause time t

BP

Parameter 21

Programmable time between 0 and 250 s.

04 00 01 02

t

BP t

Z t

SA

03

t

FS

04 88

1

5

4 ϑ

7

9

12

V1

14

V2

16-17

18-19 t

An immediate restart of the main burner after a controlled shut-down, a start-up attempt, restart, cooling or purging is prevented by the pause time. The pause time starts when the air valve is switched off. If a start-up signal (

ϑ) is applied before expiry of this time, the start-up is delayed until the end of the pause time.

After the pause time, the burner is started if the start-up signal

(

ϑ) is applied.

The minimum burner pause time t

BP

serves to adapt the program sequence to the requirements of the application.

The time should be set such that the system can be moved to ignition position, i.e. butterfly valves can be closed and, possibly, gas can be flared off, before a restart occurs.

See examples of application Staged On/Off burner control,

Staged High/Low burner control oder Two-stage-controlled burner.

PFU 760 · Edition 05.11

26

Parameters

4 .4 Behaviour during start-up

4 .4 .1 Safety time on start-up t

SA

Parameter 22

00 02 03 04

t

Z t

SA t

FS

Safety time on start-up t

SA

for the burner.

88

30a

26e

10e

28c

16c

18e

2e–4e

ϑ

V1

V2 t

4 .4 .2 Flame proving period t

FS

Parameter 23

00 02 03 04

88

30a

26e

28c

16c

18e

ϑ

V1

V2 t

Z t

SA t

FS t

Programmable time between 0 and 25 s.

This time elapses before the PFU starts the next program step so as to give the flame time to stabilize.

27

4 .4 .3 Minimum combustion time t

Parameter 20

B

Programmable time in the range from minimum safety time start-up t

SA

to maximum 25 s during which the burner remains in operation.

In the case of brief activation of the start-up signal input (

ϑ)

(e.g. with a pulse), the combustion time t

B

is started, and the burner remains in operation for at least this period.

PFU 760 · Edition 05.11

Parameters > Behaviour during start-up

4 .4 .4 Burner start-up attempts

Parameter 10

This indicates the number of possible start-up attempts of the burner.

In accordance with EN 746-2, three start-ups are permitted in specific cases in the event of flame failure during start-up, if the safety of the installation is not impaired. Note the requirements of the Standards!

If no flame is detected during start-up, either a fault lock-out is performed or further start-up attempts in accordance with

EN 746-2 occur.

Pursuant to NFPA 86, only one start-up attempt is permitted in the event of flame failure during start-up. For units approved by FM Approval (see type label), it is only possible to select one start-up attempt.

1 start-up attempt

Parameter 10 = 1

00 02

t

Z t

SA

02 88

30a

26e

10e

ϑ1

28c

26a

16c

18e

2e–4e

V1

V2 t

If no flame forms during start-up, a fault lock-out is performed after expiry of time t of the fault.

SA

. The display blinks and shows the cause

28

2 or 3 start-up attempts

Parameter 10 = 2, 3

00 02 88

30a

26e

10e

28c

ϑ

16c

18e

2c–4c

2e–4e

V1

V2 t t

Z t

SA t

Z t

SA

If several start-up attempts are set and if the PFU detects a flame failure during start-up, it closes valve V1 after the safety time t

SA

has expired and attempts to start up again. After the last programmed start-up attempt has been completed, the burner control unit conducts a fault lock-out. The display blinks and shows the cause of the fault.

PFU 760 · Edition 05.11

Parameters

4 .5 Behaviour during operation

4 .5 .1 Safety time during operation t

SB

Parameter 14

for V1 and V2

This indicates the safety time during operation t

SB

for valves V1 and V2. The default in accordance with EN 298 is 1 s. The PFU t has also the available option of a safety time during operation

SB

of 2 s. Prolonging the time increases the installation availability in the case of brief-duration signal fades (e.g. fades of the flame signal). In accordance with EN 746-2, the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards).

29

4 .5 .2 Fault lock-out or restart

Parameter 12

This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information).

Immediate fault lock-out following flame failure

Parameter 12 = 0:

04 04

88

30a

26e

28c

ϑ

16c

18e

2c–4c

2e–4e

V1

V2 t t

SB

After a fault lock-out, the burner control unit can be reset, either with the button on the front panel or using an external button. Several burner control units can be reset in parallel using the external button.

The PFU cannot be reset by mains failure. The fault signalling contact does, however, open as soon as the mains voltage fails.

See also parameter 32, Behaviour of the air valve in the event of a fault lock-out.

t

PFU 760 · Edition 05.11

Parameters > Behaviour during operation > Fault lock-out or restart

Restart following flame failure

Parameter 12 = 1:

Restart following flame failure.

04

1x

01 03

>2 s

04

88

30a

26e

10e

28c

16c

2c–4c

ϑ

V1 t

SB t

W t

Z t

SA t

FS t

If the PFU detects a flame failure after a minimum operating time of 2 s, the valves are closed and the operation signalling contact is opened within time t

SB

.

The burner control unit now attempts to restart the burner once. If the burner does not function, a fault lock-out occurs.

The display blinks and shows the cause of the fault.

In accordance with EN 746-2, a restart may be conducted only if the safety of the installation is not impaired. Restart is recommended for burners which occasionally display unstable behaviour during operation.

The precondition for a restart is that activation of the restart

allows the burner to restart as intended (in all operating

phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.

PFU 760 · Edition 05.11

30

Parameters

4 .6 Switchable gas valve V2 on PFU . .L

Parameter 26

Parameter 26 = 0: Gas valve V2 opens with the operating signal.

Parameter 26 = 1: Gas valve V2 opens with the air valve during operation

L1, N, PE

DI

SPS

PLC

API

P

PFU 760L

DI

22a 10c 26e

P

30e

A

10a

ϑ1

10e

µC

2e

4e

2c

4c

22e 18e 16c 28c

VBY

TZI

26a

VAG

4

7

M

BVA + IC 40

A switchable gas solenoid valve V2 can be activated with the

PFU..L. If Parameter 26 is set to 1, gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a/12a).

PFU 760 · Edition 05.11

31

Parameters

4 .7 Air valve control PFU . .L

Parameter 30, Behaviour of the air valve during operation

Parameter 31, Behaviour of the air valve during start-up

Parameter 32, Behaviour of the air valve in the event of a fault lock-out

The PFU..L features an adjustable air valve control. The display shows that purging is currently being carried out with or heating.

P 0

.

A

indicates that the air valve is being activated for cooling

The PFU..L supports the following functions:

– Purge

– Cooling in start-up position/standby

– Switching of the burner between low and high burner

output during operation via the air valve

– To start up the burner as intended, external activation of the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the

central control system).

– Controlling the air valve so that it

– opens with valve V1

– opens with valve V2

– Low fire over run time t

KN

after a controlled shut-down

32

4 .7 .1 Purge

Parameter 42 = 0: The air valve is closed when voltage is applied to terminal 30e.

Parameter 42 = 1: The air valve is opened when voltage is applied to terminal 30e.

In the case of multiple burner applications, burners with

mechanical combustion air supply are used. The air for combustion and pre-purge is supplied by a central fan controlled by a separate logic. This logic determines the purging time.

The PFU..L supports centrally-controlled pre-purge or postpurge. The PFU..L is informed that purging is currently being performed by input 30e. It then opens the air valve, regardless of the status of the other inputs (purging has priority). The display indicates

P 0

.

4 .7 .2 Cooling in start-up position/standby

The air valve can be activated externally via input 10a for cooling in the start-up position. During activation of the air valve the display shows being carried out.

A 0

, indicating that cooling is currently

4 .7 .3 Burner start

Parameters 30 and 31 determine the behaviour of the air valve during burner start.

PFU 760 · Edition 05.11

Parameters > Air valve control PFU . .L

4 .7 .4 Air valve opens in the case of external activation (not during start-up)

00 A0 02 03 A4

88

30a

26e

28c

16c

18e

10a

ϑ

V1

A

V2 t

Z t

SA t

FS t

33

Parameter 30 = 0: The air valve opens if it is activated externally by input 10a.

Parameter 31 = 0: The air valve remains closed during start-up even if it is activated externally.

These settings are required on burners on which the gas/air ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire, e.g. on two-stagecontrolled burners. In this case, activation of the air valve during burner start via input 10a must be prevented.

External control allows switchover between low fire and high fire during operation.

The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.

L1

ϑ

PFU 760L

A

P

SPS

PLC

API

VAS..N

GIK..B

TZI

VR..R

PFU 760 · Edition 05.11

Parameters > Air valve control PFU . .L

4 .7 .5 Air valve opens in the case of external activation (even during start-up)

00 A0 00 A0 A2

t

Z t

SA

A3 A4

88

30a

26e

10e

ϑ1 t

FS

18e

10a

22e

2e–4e

V1

A

V2 t

34

Parameter 30 = 0: The air valve opens if it is activated externally via input 10a.

Parameter 31 = 1: The air valve can be activated even during start-up.

These settings may be selected only if the burner can start with full air capacity.

The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.

L1

ϑ

PFU 760L

A

P

SPS

PLC

API

TZI

VG..L

EKO

GEH

VR..R

LEH

BICR

EKO

PFU 760 · Edition 05.11

Parameters > Air valve control PFU . .L

4 .7 .6 Air valve opens with valve V1

00 A0 00 A0 A2

t

Z t

SA

A3 A4

88

30a

26e

10e

ϑ1 t

FS

18e

10a

22e

2e–4e

V1

A

V2 t

L1

ϑ

PFU 760L

A

P

SPS

PLC

API

TZI

VG..L

EKO

GEH

VR..R

LEH

BICR

EKO

35

Parameter 30 = 1:

The air valve opens simultaneously with valve V1.

Application: Single-stage-controlled burner is switched

ON/OFF via the

ϑ input.

The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.

PFU 760 · Edition 05.11

Parameters > Air valve control PFU . .L

4 .7 .7 Air valve opens with valve V2

00 A0 00 02

t

Z t

SA

L1

ϑ

A

P

PFU 760L

t

FS

03 A4

88

30a

26e

28c

ϑ

16c

18e

10a

22e

2c–4c

V1

A

V2 t

SPS

PLC

API

VAG

VR..R

TZI

UV

36

Parameter 30 = 2:

The air valve opens simultaneously with valve V2.

Application: Two-stage-controlled burner is switched ON/OFF via the

ϑ input.

The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.

PFU 760 · Edition 05.11

Parameters > Air valve control PFU . .L

4 .7 .8 Low fire over run time t

KN

after a controlled shut-down

A4

00

t

KN

88

30a

26e

28c

ϑ

V1

2c–4c

18e

22e

2e–4e

V2 t

L1

ϑ

PFU 760L

A

P

VAG

TZI

SPS

PLC

API

UV

37

Parameter 36

Settings: 0; 3; 5; 10; 15; 25 or 60 (low fire over run time in seconds)

This parameter is applicable to systems with a pneumatic ratio control system and On/Off control.

Parameter 36 = 0 (low fire over run time t

KN

= 0 s): Without low fire over run, the gas side is closed immediately owing to the quick-closing gas valve in the case of On/Off control. The air side closes more slowly. The air flowing in during the closing time increases the O

2

content in the combustion chamber.

t

Parameter 36 = 3; 5; 10; 15; 25 or 60 (low fire over run time

KN

= 3, 5, 10, 15, 25 or 60 s):

The air valve closes slowly after the activation signal has been switched off. The gas valve remains open for t

KN.

This means that the burner, after deactivation of the start-up signal (

ϑ), is initially adjusted down to low fire and then switched off completely.

Using the low fire over run function reduces the O

2 the furnace atmosphere.

content in

Flame control is still operational. Can be used only in the case of a pneumatic air/gas ratio control system and On/Off control.

Its must be ensured that no excess gas occurs.

VR..R

PFU 760 · Edition 05.11

Parameters > Air valve control PFU . .L

4 .7 .9 Behaviour of the air valve in the event of a fault lock-out

Parameter 32

This determines whether the air valve can be activated in the case of a fault lock-out.

Parameter 32 = 0:

The air valve is closed in the event of a fault. It cannot be activated externally via terminal 10a.

Parameter 32 = 1:

The air valve can be activated externally via input 10a even during a fault, e.g. for cooling.

38

PFU 760 · Edition 05.11

Parameters

4 .8 Manual operation

For convenient setting of the burner or analyzing faults.

The parameter display is not available in Manual mode.

Manual mode can be accessed only if the unit was not in

Fault state before switching off. The following times/functions are not active in Manual mode: start-up attempts, restart, minimum combustion time and cycle lock.

If the Reset/Information button is pressed for 2 s during switchon, the PFU reverts to Manual mode. Two dots blink on the display.

In this operating mode, the burner control unit operates independently of the status of the inputs (apart from the pre-purge input and the safety interlocks. These are of higher priority and will be processed first).

Each time after the button is pressed again, the PFU moves to the next section of the program sequence and stops there.

After approx. 3 s, the flame signal will be displayed instead of the program parameter. Briefly pressing the Reset/Information button (< 1 s) displays the relevant Manual mode step. If there is flame simulation during the start-up, the flame signal is displayed immediately.

On units with air valve control, the air valve can be opened and closed repeatedly by pressing the button during operation.

Manual mode can be terminated by switching off the PFU

(On/Off button).

39

4 .8 .1 Manual mode limited to 5 minutes

Parameter 34

Parameter 34 determines when Manual mode is terminated.

Parameter 34 = 0: Manual mode is not limited in time. If this function has been selected, operation of the furnace may be continued manually in the event of failure of the central control system.

Parameter 34 = 1: Manual mode ends automatically five

minutes after the last time the button was pressed. The PFU then moves abruptly back to start-up position/standby.

4 .9 Password

Parameter 50

(Four-digit) password saved to protect parameter settings.

To prevent unauthorized changes to parameter settings, a password is stored in parameter 50. Changes to parameter settings can only be made once this number has been entered.

The password can be changed using BCSoft.

Note the effect of parameter settings on the safe functioning of your system.

The password set at the factory can be found in the delivery note supplied.

PFU 760 · Edition 05.11

Parameters

4 .10 Multi-flame control

Parameter 45

2e

2a

30e

UVS

L1

8e

8a

30e

N

UVS

Z

Z

N

L1

18e

18a

30e

UVS

L1

24e

24a

30e

N

UVS

Z

Z

N

L1

L1

N

L1

N

Z

L1

N

Z

L1

N

Z

L1

N

Z

I

30a

32c

30e

2a

230V

2e

I

8a

230V

8e

I

18a

230V

18e

I

24a

230V

24e

PFF 704

Parameter 45 = 0: Multi-flame control is switched off.

Parameter 45 = 1: Multi-flame control is switched on. The parameter must be set to 1 to ensure that the flames are monitored.

6a

4c

4e

6e

12a

10c

10e

12e

22a

20c

20e

22e

28a

26c

26e

28e

24 V

UVS

1

2

3

L1 (L1)

26a

20c

24c

Z

P

30e

N

28c

N (L2)

I

DI

26e

22a

N

30a

20c

230 V

32c

24c

28c

26a

F1

(

sk1

PFU 760L)

PFU 760

22e

16c

18e

V1

V2

N a

2a

4a s

2e

4e m

2c

4c

0 V

24 V

0 V

ϑ1

A

8a

8c

8e

10e

12e

10a

12a

10c

12c

µC

A

S

SK

40

PFU 760 · Edition 05.11

5 Selection

5 .1 Safety time

Please quote the safety time t

SA

when ordering.

EN 746-2

P

N

≤ 70 kW

> 70 kW* t

SA

5 s

3 s

≤ 350 kW

10 s

> 350 kW**

5 s

0 ➔

*

10 s

* P

** P

Z

0,1 x P

Z

0,33 x P

N

, P

N

Zmax

, P

= 350 kW

Zmax

= 350 kW t

SA

= 3 s, 5 s or 10 s

P

N

= Rated heat output

P

Z

= Ignition capacity

The safety time of the burner control unit depends on the burner type, the burner output and the respective application.

5 .1 .1 Calculating the safety time t

SA

Burner with mechanical combustion air supply

Natural draught burner with direct ignition

Natural draught burner with pilot burner

Burner output

Safety time on start-up t

SA

1.00

3 kW s

Ignition burner input rating at a level of 10 % of nominal heat input with a maximum of 350 kW.

41

PFU 760 · Edition 05.11

Selection

5 .2 Selection table

Type

PFU 760

L*

T

N

* If “none”, this specifi cation is omitted.

= standard,  = available

Order example

PFU 760LT

D*

U*

K1*

K2*

42

5 .3 Type code

Code

L*

T

N

D*

U*

K1*

K2*

* If “none”, this specifi cation is omitted.

Description

Air valve control

Mains voltage

220 – 240 V AC, -15/+10%, 50/60 Hz

110 – 120 V AC, -15/+10%, 50/60 Hz

Digital input to interrupt fl ame control

Preparation for UV sensor for continuous operation UVD 1

Compatible with PFS/PFD

PFU 778

PFU 760 · Edition 05.11

6 Project planning information

6 .1 Cable selection

Use mains cable suitable for the type of operation and complying with local regulations. Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields.

6 .1 .1 Ignition cable

Use unscreened high-voltage cable see page 49 (Accessories).

Cable length: max. 5 m, recommended < 1 m. Screw the ignition cable securely into the ignition transformer and run to the burner by the shortest possible route.

The longer the ignition cable, the lower the ignition capacity.

Only use radio interference suppressed electrode adapters

(with 1 kΩ resistor) for ignition electrodes see page 49 (Accessories). Do not lay UV/ionization cable and ignition cables

together and lay them as far apart as possible.

6 .1 .2 Ionization cable

Use unscreened high-voltage cable see page 49 (Accessories).

Cable length: max. 100 m. Avoid external electrical interference. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several ionization cables can be routed together.

43

6 .1 .3 UV cable

Cable length: max. 100 m. Avoid external electrical interference.

Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several UV cables can be routed together.

6 .2 Ignition electrode

6 .2 .1 Electrode gap

Gap between electrode and burner ground:

2 mm ± 0.5 mm.

6 .2 .2 Star electrodes

We recommend using 7.5 kV ignition transformers on burners with star electrodes.

PFU 760 · Edition 05.11

Project planning information

6 .3 Minimum combustion time

Even if the start-up signal (

ϑ) is applied only briefly, the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a fault.

The minimum combustion time t

B

the safety time t

SA

to max. 25 s.

can be extended beyond

6 .4 Safety interlocks (Limits)

The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application, e.g. safety temperature limiter, minimum and maximum gas pressure, tightness control) must isolate terminal 26e from the voltage supply. If the safety interlock is interrupted, this is indicated by a blinking 51 on the display.

If the safety interlocks fail, an immediate program abort with switch-off of all outputs occurs (even during the safety time).

If the safety interlocks are operational again or the unit is switched back on, the program run is restarted in standby.

6 .5 Emergency stop

6 .5 .1 In the event of fire or electric shock

If there is a risk of fire, electric shock or similar, inputs L1, N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply – this should be reflected in the wiring on site.

6 .5 .2 Via the safety interlocks (limits)

The safety interlock turns off the power to input 26e, such as in the event of air deficiency or similar.

PFU 760 · Edition 05.11

44

Project planning information

6 .6 Reset

6 .6 .1 Parallel reset

Several burner control units can be reset in parallel using the external button. The PFU cannot be reset by mains failure.

6 .6 .2 Permanent remote reset

Permanent remote reset gives rise to a malfunction. If a remote reset signal is permanently applied to terminals 10c/12c, 52 flashes on the display to indicate a fault.

Reset with a pulse < 1 s.

6 .6 .3 Automatic remote reset (PLC)

In the case of automatic remote reset (PLC), the reset pulse duration should not exceed 1 second. Check compliance with standards.

If a fault is acknowledged by remote reset too often, error 10

(Too many remote resets) is displayed. The error can only be acknowledged with the Reset/Information button on the unit.

The burner malfunction must be remedied. The malfunction can not be remedied by changing the method of activation.

45

6 .6 .4 Burner start

A furnace start may only be initiated, if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustion/processing chamber, in the connected areas or in the exhaust gas system (heat exchanger, dust collector). This can be achieved by pre-purge, which

occurs immediately before ignition or within the period specified in the operating instructions.

In the case of multiple burner applications, pre-purge is not necessary after a controlled burner shut-down.

Note the requirements of the Standards. For exceptions, see

Standards.

6 .6 .5 Restart and start-up attempts

The precondition for a restart/start-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.

Note the requirements of the Standards. For exceptions, see

Standards.

PFU 760 · Edition 05.11

Project planning information

6 .7 Fault signalling

The fault signalling contact opens, as soon as the mains voltage fails.

6 .8 Protecting the burner from overload

To protect the unit against overload by frequent cycling, the maximum number of start-ups per minute is limited for the

PFU. Excessive cycling triggers a fault message (blinking 53 ).

The max. number of start-ups per minute depends on the safety time t

SA

: t

SA

3

[s] Ignition transformer TZI Max. start-ups/min.

5-15/100 6

5

10

5-15/100

5-15/100

5

4

46

6 .9 Installation

Installation position: any.

Installation in 19" module subracks only, see page 50 (Module subracks).

Install in clean environment ensuring enclosure IP 54 or higher, whereby no condensation is permitted.

Cable length between PFU and burner: max. 100 m.

6 .10 Wiring

The PFU is suitable for hard wiring only. Do not reverse phase and neutral conductor. Different phases of a three-phase

current system must not be installed at the PFU. No voltage may be connected to the valve and ignition outputs.

6 .10 .1 UVS sensor wiring

Connect the UVS sensor directly to the PFU. Operating the sensor with incorrect polarity or voltage can lead to destruction of the sensor.

6 .11 PFU switched off

The PFU cannot be activated when no mains voltage is applied or when it is switched off. The fault signalling contact is only closed when the unit is supplied with voltage and switched on.

If the unit is switched off, an immediate program abort with switch-off of all outputs occurs (even during the safety time).

When the unit is switched on, the program run is restarted in standby.

PFU 760 · Edition 05.11

Project planning information

47

6 .12 Furnace control

Switch on the system to start up the furnace, then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended. To shut down the furnace, first disconnect the burner control unit from the temperature control (burner

ON signal), then disconnect the safety interlocks and finally switch off the system.

6 .13 Note on EC type-examination

Since EN 298 (1993) does not describe all functions of the PFU, the operator is responsible for ensuring that all parameters and functions are matched to the respective application.

6 .14 Mains switch

The mains switch in the unit isolates the PFU on two poles from the mains. It does not meet the requirements of EN 50156-

1:2004 (5.2.2 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply. Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156, it does allow the burner to be isolated functionally from the central control system. This function is required for manual operation and, in the case of PROFIBUS units, to switch off the unit without causing BUS errors. Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only, in accordance with

Standard EN 50156.

6 .15 Changing parameters

In certain cases, it may be necessary to change the default settings. Using a separate software package and a PC optoadapter, it is possible to modify certain parameters on the PFU, such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failure.

The software package with PC opto-adapter, as well as

“Changed parameters” stickers, are available as accesso-

ries – see section entitled “Accessories”.

The unit parameters set at the factory are specified in the delivery note.

Document changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentation.

If a replacement is ordered for a PFU with changed parameters, refer to the protocol for details.

PFU 760 · Edition 05.11

48

7 Flame control

7 .1 With ionization sensor

The PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground. The flame rectifies

this voltage. Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame

signal.

A flame cannot be simulated. Ignition and monitoring with a single electrode is possible.

7 .2 With UV sensor

A UV tube inside the UV sensor detects the ultraviolet light of a flame. It does not respond to sunlight, incandescent bulb light or infrared radiation emitted by hot workpieces or redhot furnace walls.

In the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage. As with ionization control, the burner control unit only detects this DC signal.

When using UV sensors of Type UVS, the burner control unit may be used for intermittent operation only. This means that operation must be interrupted at least once every 24 hours.

This can be programmed using parameter 35.

For further information, see brochure UVS.

The burner control unit PFU..U is prepared for UV sensor UVD 1.

This enables continuous operation. For further information, see

Technical Information Bulletin UVD.

7 .3 Via the temperature in high temperature equipment

High temperature equipment is defined as a thermoprocessing installation, in which the wall temperature of the combustion chamber and/or the processing chamber exceeds 750°C.

Burner control unit PFU..D features a special “High temperature operation” function. During heating up, standard monitoring methods (ionization or UV) must be used for flame control.

When the working temperature has exceeded 750°C, indirect flame control can be taken over by a central monitoring device.

When the DI input (terminal 22a) is activated, the burner control unit reverts to this operating mode.

Important: In “High temperature operation”, i.e. with the DI input being activated, burner control unit PFU..D does not evaluate the flame signal. The safety function of the burner control unit’s flame control is deactivated during this operating phase.

PFU 760 · Edition 05.11

8 Accessories

8 .1 High-voltage cable

FZLSi 1/7 up to 180°C,

Order No.: 04250410.

FZLK 1/7 up to 80°C,

Order No.: 04250409.

8 .2 BCSoft

49

8 .3 Stickers for labelling

For printing with laser printers, plotters or engraving machines, 27 × 18 mm or

28 × 17.5 mm.

Colour: silver

Brenner

1

Zone 3

Opto-adapter including BCSoft CD-ROM,

Order No.: 74960437.

The current software can be downloaded from our Internet site at www.docuthek.com. To do so, you need to register in the

DOCUTHEK.

8 .4 “Changed parameters” stickers

D-49018 Osnabrück, Germany

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory.

Achtung, geänderte Parameter!

Die Angaben auf dem Typenschild gelten nicht mehr in vollem Umfang.

Aktuelle Parameter direkt auslesen.

100 pcs,

Order No.: 74921492.

Important, changed parameters!

The details on the type label are no longer completely accurate. Read the current parameters direct from the unit.

Attention, paramètres modifiés !

Les informations figurant sur la plaque signalétique ne sont plus valables dans leur intégralité. Veuillez vous référer directement aux paramètres actualisés.

PFU 760 · Edition 05.11

Accessories

8 .5 Radio interference suppressed electrode adapters

Plug cap, 4 mm, interference-suppressed,

Order No. 04115308.

Straight adapter, 6 mm, interference-suppressed,

Order No. 04115306.

8 .6 Socket connectors

Type Order No.

Socket connector E, 48-pin solder tag connection 04120148

Socket connector E, 48-pin wire-wrap connection 04120158

8 .7 Module subracks

50

Module subrack BGT SM-8/1/1 for MPT 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear, single-zone operation for MPT 700 operating modes 1-4, twozone operation for MPT 700 operating modes 1-4, but max.

4 burners per zone.

Slot 1 for MPT 700, slots 2–9 for PFU 760, slot 10 for PFP 700

Order No. 84402282 (no illustration provided).

Module subrack BGT SA-9U/1DP for PFA 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear, relays and screw terminals for four free inputs and four free outputs.

Slot 1 for PFA 700, slots 2–10 for PFU 778 without digital input, connection to PROFIBUS-DP with D-Sub socket.

Order No. 84402283 (no illustration provided).

Module subracks BGT S-9U/1 for PFP 700, PFU 760 comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear.

Slots 1–9 for PFU 760, slot 10 for PFP 700

Order No. 84402281.

PFU 760 · Edition 05.11

Accessories

L1

N

PFP 700

S0

30a

F1

O

I

S1

230 V

115 V

8ace

32c

12ace

U I

24 V=

600 mA

0 V

PFU 760 · Edition 05.11

51

8 .8 Power supply PFP 700

For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704.

Operating status display on the front plate. PFP switches off in the event of an output overload.

Output voltage 24 V, output rating 14 VA.

Accessories

230 V~

115 V~

24 V=/~

0 V

230 V~

115 V~

24 V=/~

0 V

230 V~

115 V~

24 V=/~

0 V

230 V~

115 V~

24 V=/~

0 V

PFR 704

2e

2a

2c

1

4e

10e

10a

10c

2

12e

18e

18a

18c

20e

26e

26a

26c

3

4

28e

PFU 760 · Edition 05.11

24a

24e

22a

22e

22c

24c

32a

32e

30a

30e

30c

32c

16a

16e

14a

14e

14c

16c

6a

6e

8a

8e

8c

6c

52

8 .9 Relay module PFR 704

For contact multiplication, e.g. if several air valves are activated via one control signal for pre-purge, or for heating/cooling switchover when using an MPT. Switching status display on the front plate.

Input voltage:

110/120 V AC, -15/+10%, 50/60 Hz,

220/240 V AC, -15/+10%, 50/60 Hz,

24 V AC/DC, ± 10%.

Current per relay: 25 mA.

Contact rating of floating outputs: max. 2 A, 264 V (not fused internally).

Accessories

L1

2e

2a

30e

1

3

UVS

Z

N

L1

8e

8a

30e

1

3

UVS

Z

N

18e

18a

30e

1

3

UVS

L1

24e

24a

30e

N

2

3

UVS

Z

Z

N

L1

L1

N

L1

N

Z

L1

N

Z

L1

N

Z

L1

N

Z

I

PFF 7x4

S0

O

30a

32c

I

30e

2a

230V

2e

+

S1

230 V

115 V

1

P1

F2

I

8a

230V

8e

+

2 P2

F4

I

18a

230V

18e

+

3 P3

F6

I

24a

230V

24e

+

4 P4

F8

F1

12a

12c

10a

10c

F3 10e

12e

22a

22c

20a

20c

F5 20e

22e

6a

6c

4a

4c

4e

6e

28a

28c

26a

26c

F7 26e

28e

P1–P4: PFF 704

PFU 760 · Edition 05.11

53

8 .10 Flame detector PFF 704

For flame detection or multi-flame control in conjunction with

PFU, with 4 independent flame detectors. For intermittent operation with ionization or UV control.

Power consumption: 10 VA.

Ionization voltage: 230 V AC.

Max. flame signal cable length: 100 m.

Cut-off sensitivity of the flame amplifiers: adjustable between

1 µA and 10 µA (factory default setting: 1 µA).

Contact rating: max. 2 A.

Mains voltage: 110 – 240 V AC, 15/10%, 50/60 Hz.

Further information can be found in brochure PF 19”.

Accessories

PFU 760 · Edition 05.11

L1

N

µC

VP

RxD/TxD-P

RxD/TxD-N

DGND

8b

11b

12b

14b

24 V

24 V

0 V

24 V

24 V

18b

21b

22b

1

4

23b

26b

1

4

I/O

PFA 700

32b

30a

15b

16b

24 V=

0 V

ϑ

2

1

1a

9a

10a

18a

19a

23a

20c

23c

19c

17b

24 V

30c

1c

9c

10c

18c

1. PFU

9. PFU

1. PFU

9. PFU

1. PFU

9. PFU

1. PFU

9. PFU

1. PFU

5. PFU

6. PFU

9. PFU

PFU

L1 30e

26e

PFU

54

8 .11 Field bus interface PFA 700

For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using

PROFIBUS-DP, in order to transfer measuring, control and regulation signals as a bundle.

4 digital inputs:

24 V DC, ± 10%, < 10 mA,

4 digital outputs: relay contact, max. 1 A, 264 V (not fused internally).

Mains voltage: 110 – 240 V AC, -15/+10%, 50/60 Hz.

Further information can be found in brochure PFA.

Accessories

L1

N

PE mA

1 mA

2

GND

0 – 100%

GND

100% – 0

12–24 V

E1

E2

E3

0 V

14z

14d

16z

14b

16b

20z

20b

20d

18z

18b

18d

28z

28b

28d

32z

32b

32d

MPT 700

30z

30b

F1

30d

8888

88

µC

2b

4b

10b

12b

12–24 V

0 V

2z

2d

4z

4d

6z

6d

8z

8d

10z

10d

12z

6b

8b

A4

A5

A6

A7

A8

A1

A2

A3

/

/

1

2

COM

55

8 .12 Impulse system MPT 700

With 11 outputs for activation of burner control units PFU 780.

The furnace atmosphere is circulated thanks to intermittent operation, and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensured.

Mains voltage: 95 – 240 V AC, ± 10%, 50/60 Hz.

Power consumption: 10 VA.

Additional auxiliary voltage: 12 – 24 V DC, ± 10%, max. 1.1 A.

Controller inputs: 2 x 0(4) – 20 mA with common ground, floating, load impedance approx. 225 Ω.

Three-point step input: floating, 12 – 24 V DC, load impedance approx. 2.7 kΩ.

Digital inputs E1 – E3: with common ground, floating, 12 –

24 V DC, load impedance approx. 2.7 kΩ.

Further information can be found in brochure MPT.

PFU 760 · Edition 05.11

9 Technical data

Mains voltage:

220/240 V AC, -15/+10%, 50/60 Hz or

110/120 V AC, -15/+10%, 50/60 Hz, for grounded and ungrounded mains.

Power consumption: < 8 VA.

Control inputs:

Input voltage/current:

Burner, air valve, multi-flame control and remote reset:

24 V DC, ± 10%, < 7 mA per input.

Input voltage for safety interlocks, digital input DI and purge

= mains voltage.

Input voltage of signal inputs:

Rated value 110/120 V AC

Signal “1”

Signal “0”

Frequency

80 – 132 V

0 – 20 V

50/60 Hz

220/240 V AC

160 – 264 V

0 – 40 V

50/60 Hz

Rated value

Signal “1”

Signal “0”

Inherent current:

Signal “1”

24 V DC

24 V, ±10%

< 1 V typ. 5 mA

56

Output voltage for voltage-related outputs = mains voltage

Contact rating

Gas valve V1, V2 Max. 1 A resistive Max. 1 A cos ϕ 0.3

Air valve

Ignition

Number of operating cycles

Max. 1 A resistive Max. 1 A cos ϕ 0.3

Max. 1 A resistive Max. 1 A cos ϕ 0.3

Max. 1,000,000,

typically 400,000

Max. 250,000,

typically 100,000

Output current: max. 2 A per output, but total current for valves and ignition transformer max. 2.5 A.

Number of operating cycles:

Mains switch: 1000,

Reset/Information button: 1000.

t

PFU 760 · Edition 05.11

Technical data

Signalling contacts: max. 24 V, 1 A.

Flame control:

Sensor voltage: approx. 230 V AC.

Sensor current: > 1 μA,

Length of sensor cable: max. 100 m.

Fuse in unit:

F1: 3.15 A, slow-acting, H pursuant to IEC 127-2/5,

F2: 3.15 A, slow-acting, H pursuant to IEC 127-2/5.

Ambient temperature:

-20 to +60°C (-4 to +140°F),

Climate: no condensation permitted.

Enclosure: IP 00 pursuant to IEC 529, after installing in a 19" module subrack according to the instructions, e.g. type BGT, the front corresponds to IP 20.

Input/Output safety circuit:

All the inputs and outputs marked “ ” (see connection diagrams) may be used for safety tasks.

Weight: approx. 650 g (23 oz)

PFU 760 · Edition 05.11

57

Technical data

9 .1 Safety-specific characteristic values

In the case of ionization control, suitable for Safety

Integrity Level

Diagnostic coverage DC

SIL 3

Type of subsystem

Mode of operation

97.9%

Type B to EN 61508-2,

7.4.3.1.4

High demand mode pursuant to EN 61508-4, 3.5.12

Mean probability of dangerous failure PFH

D

Mean time to dangerous failure MTTF d

Safe failure fraction SFF

1.34 x 10 -8 l/h

99.2%

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic).

Relationship between the Performance Level (PL) and the

Safety Integrity Level (SIL)

PL a b

SIL

1 c d e

1

2

3

Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be used up to PL e.

58

Max. service life under operating conditions:

20 years after date of production, plus max. 1/2 year in storage prior to first use.

For a glossary of terms, see page 62 (Glossary).

PFU 760 · Edition 05.11

Technical data

B

A

00

D

C

E

F1

F2

59

9 .2 Operating controls

A: 2-digit 7-segment display

B: Reset/Information button to reset the system after a fault or to scan parameters on the display.

C: Mains switch

D: Optical interface

E: Type label

PFU 760 · Edition 05.11

10 Maintenance cycles

Burner control unit PFU requires little servicing.

60

PFU 760 · Edition 05.11

11 Legend

88

Display

88

Blinking display

DI

Ready

Safety interlocks (Limits)

Burner start-up signal

Digital input

Ignition transformer

Gas valve

1 t

LV t

FS t

B t

BP t

W t

SA t

SB t

Z

P

A

Air valve

Purge

Ext. air valve control

Flame signal

Burner operating signal

Fault signal

Reset

Input signal

Output signal

Flame simulation check

Waiting time

≥ 2 s

Safety time on start-up 3 s, 5 s or 10 s

Safety time during operation < 1 s or < 2 s

Ignition time 2 s, 3 s or 6 s

Flame simulation delay time 25 s

Flame proving period 0 – 25 s

Minimum combustion time t

SA

up to max. 25 s

Minimum burner pause time 0 – 250 s

PFU 760 · Edition 05.11

t

KN

Low fire over run time 0 s, 5 s, 15 s or 25 s

Input/Output safety circuit

61

62

12 Glossary

12 .1 Waiting time

t

W

01 02 02

30e

10e

28c

16c

26a

18e

2c–4c

2e–4e

88

L1

ϑ

V1

V2 tW tZ tSA t t

Once the start-up signal

ϑ has been applied, the waiting time

W

starts to elapse. During this time, a self-test is conducted to detect errors in internal and external circuit components. If no malfunction is detected, the burner will start up.

12 .2 Safety time on start-up t

SA

This refers to the period of time between switching on and switching off of the gas valve, when no flame signal is detected.

The safety time on start-up t

SA

(3, 5 or 10 s) is the minimum operating time of the burner and burner control unit.

12 .3 Ignition time t

Z

If no malfunction is detected during the waiting time t ignition time t

Z

W the pilot gas valve V1 and the ignition transformer and the burner is ignited. The duration of the ignition time is either 2,

3 or 7 seconds (depending on safety time t

SA

selected).

, the

then starts to elapse. Voltage is supplied to

t

12 .4 Flame simulation/Flame simulation delay time

LV

01 01

30e

10e

28c

16c

26a

18e

2c–4c

2e–4e

88

L1

ϑ

V1

V2 tW tLV t

An extraneous signal (flame simulation) is a flame signal that is detected, although there should be no flame according to the program sequence. If such an extraneous signal is

detected, the flame simulation delay time t

If the flame simulation is discontinued during the flame simulation delay time t

LV

LV

starts to elapse.

, start-up can be initiated or operation continued. Otherwise, a fault lock-out occurs.

12 .5 Safety time during operation t

SB

04 04

tSB

30e

10e

28c

16c

26a

18e

2c–4c

2e–4e

88

L1

ϑ

V1

V2 t

If the flame fails during operation, the valve outputs are disconnected within the safety time t

SB

.

t

PFU 760 · Edition 05.11

Glossary

63

The default safety time during operation t

SB

in accordance with

EN 298 is 1 second. In accordance with EN 746-2, the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see “Project planning information”). Note the requirements of the Standards!

12 .6 Flame signal

If a flame is detected, the flame detector will supply a flame signal.

12 .7 Fault lock-out

In the event of a fault lock-out, all valves and the ignition transformer are disconnected from the electrical power supply, and a fault is signalled. Resetting must take place manually following a fault lock-out.

12 .8 Safety interlocks (Limits)

The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the

application, e.g. safety temperature limiter, minimum/maximum gas pressure) must isolate input from the voltage supply.

12 .9 Pilot gas valve V1

The start fuel flow rate for the burner is released by pilot gas valve V1. It opens when the safety time on start-up t

SA

starts to elapse. It remains open until the burner is switched off again by a normal shut-down or fault lock-out.

12 .10 Main gas valve V2

Once the safety time on start-up t switched off or a fault is signalled.

SA

has elapsed, the main gas valve V2 is opened. It remains open until the burner is

L1 (L1)

DI

P

30e

26e

22a

30a

F1

(

sk1

PFU 760L)

PFU 760

22e

16c

18e

V1

V2

N

N (L2)

20c

32c

24c a

2a

4a

12 .11 Continuous operation

The gas burner runs continuously for more than 24 hours.

Z

I

12 .12 Air valve

N

230 V

28c

26a s m

2e

4e

2c

4c

8a

8c

8a

8c

µC

A

S

0 V

8e

8e

– to control the burner output in ON/OFF mode and in High/

24 V

ϑ1

10e

SK

Low mode when using a pneumatic air/gas ratio control system.

A

12e

10a

12a

10c

12c

UVS 2

3

26a

20c

24c

PFU 760 · Edition 05.11

N

28c

26a

N

28c

Glossary

12 .13 Diagnostic coverage DC

Measure of the effectiveness of diagnostics, which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failures

NOTE: Diagnostic coverage can exist for the whole or parts of a safety-related system. For example, diagnostic coverage could exist for sensors and/or logic system and/or final elements. Unit: %.

from EN ISO 13849-1:2008

12 .14 Mode of operation

High demand mode or continuous mode

Operating mode, where the frequency of demands for operation made on a safety-related system is greater than one per year or greater than twice the proof-test frequency from EN 61508-4:2001

12 .15 Safe failure fraction SFF

Fraction of safe failures related to all failures, which are assumed to appear from EN 13611/A2:2011

12 .16 Probability of dangerous failure PFH

D

Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode.

Unit: 1/h from EN 13611/A2:2011

12 .17 Mean time to dangerous failure MTTF

d

Expectation of the mean time to dangerous failure from EN ISO 13849-1:2008

64

PFU 760 · Edition 05.11

65

Finally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we can improve our documents further and suit them to your needs.

Clarity

Found information quickly

Searched for a long time

Didn’t find information

What is missing?

No answer dsavsdvsdv

Comprehension

Coherent

Too complicated

No answer

Scope

Too little

Sufficient

Too wide

No answer

Use

To get to know the product

To choose a product

Planning

To look for information

Remarks

Navigation

I can find my way around

I got “lost”

No answer

My scope of functions

Technical department

Sales

No answer

sdvsdvsdv

Kromschröder AG

Michael Rehkamp [email protected]

Osnabrück

Contact

Elster GmbH

Postfach 2809 · 49018 Osnabrück

Strotheweg 1 · 49504 Lotte (Büren)

Germany

T +49 541 1214-0

F +49 541 1214-370 [email protected]

www.kromschroeder.com www.elster.com

The current addresses of our international agents are available on the Internet: www.kromschroeder.de/index.php?id=718&L=1

(Adobe Reader 7 or higher required) www.adobe.com

We reserve the right to make technical modifications in the interests of progress.

Copyright © 2007 – 2011 Elster Group

All rights reserved.

PFU 760 · Edition 05.11

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents