FX20/FX60 Supervisory Controllers Product

FX20/FX60 Supervisory Controllers Product
Product Bulletin
Issue Date
FX20/FX60
August 26, 2009
FX20/FX60 Supervisory Controllers
The FX20 and FX60 are Web-based
supervisory-class controllers in the Facility Explorer
product family. The FX20/FX60 manages networks of
field controllers using open communication protocols,
such as N2, LONWORKS®, and BACnet® protocols.
The FX20/FX60 supports a full set of building
automation features specifically designed for
commercial facilities such as scheduling, alarming,
histories, data sharing, energy management,
totalization, and customized control routines.
In addition, the FX20/FX60 hardware and software
design is modular, so you can add accessories such
as communications cards, input and output modules,
and software options if needed. This also allows you
to select the controller most appropriate for the size of
your facility and those options best needed to
control it.
The FX20/FX60 includes a graphical system user
interface and configuration tool that you can access
with a Web browser. Remote access is easily
achieved from an Internet, intranet, or dial-up
connection. Multiple users can concurrently connect
to the FX20/FX60. Security and presentation
preferences are managed through user profiles, logon
IDs, and passwords.
The FX20 and FX60 are very similar in physical size
and overall capabilities. The main difference between
the controllers is the superior capacity of the FX60.
Figure 1: FX60 Supervisory Controller
Features and Benefits
Web-Based User Interface
Provides rich, graphical displays for system
operation and analysis.
Adoption of Industry Standard
Communication Protocols
Allows for the integration of a wide variety of field
controllers. This includes Facility Explorer field
controllers and controllers provided by others
without intermediate gateways or translators.
Embedded Configuration Tool
Requires no proprietary or desktop software to
configure the FX20/FX60. You only need a Web
browser for basic configuration and monitoring.
Modular Design
Allows you to select only those components
needed to meet specific project requirements.
Small, Compact Design
Installs easily.
FX Workbench
Reduces engineering and installation time by
easily and quickly creating the FX20/FX60
database from field controller configurations.
© 2009 Johnson Controls, Inc.
Code No. LIT-12011406
1
Table 1: FX20/FX60 Ordering Information
Part Number
Description
LP-FX2011N-0
FX20: includes 128 MB RAM, 64 MB Flash, 2 Ethernet ports, 1 non-isolated RS-485 port, 1 RS-232
port, 1 NiagaraAX Direct Input/Output (NDIO) port, 2 communication card slots, Niagara driver, oBIX®
driver, N2 driver, embedded FX Workbench, embedded Web UI
LP-FX6011N-0
FX60: includes 128 Mb RAM, 128 Mb Flash, 2 Ethernet ports, 1 non-isolated RS-485 port, 1 RS-232
port, 1 NDIO port, 1 Universal Serial Bus (USB) port, 2 communication card slots, Niagara driver,
oBIX driver, N2 driver, embedded FX Workbench, embedded Web UI
Table 2: FX Workbench Ordering Information
Part Number
Description
LP-FXTSPE-0
FX Tools Supervisor Pro Software on CD-ROM: End user version. Includes FX Workbench,
FX Workbench Pro, and FX Alarm Portal.
LP-FXTSPE-6
FX Tools Supervisor Pro Software Upgrade on CD-ROM. Used to upgrade any copy of FX Tools
Supervisor Pro which is within the software maintenance agreement period.
LP-FXALMPTL-0
FX Alarm Portal Client Software on CD-ROM. Provides Alarm Portal functions only.
LP-FXSWMA-0
License file enabling 1 year of software maintenance for one copy of FX Tools Supervisor Pro.
LP-FXSWUPG-0
License file enabling a one-time software upgrade for one copy of FX Tools Supervisor Pro.
Table 3: FX20/FX60 Hardware Accessories Ordering Information
Part Number
Description
LP-FXNDIO16-0
16 channel input/output module for FX20/FX60: Includes 8 universal inputs, 4 relay outputs, and 4
0-10 V analog outputs, maximum of 4 per FX20/FX60, or 2 if combined with NDIO34
LP-FXNDIO34-0
34 channel input/output module for FX20/FX60: Includes 16 universal inputs, 10 relay outputs, and 8
0-10 V analog outputs, maximum of 1 per FX20/FX60. Also provides power to FX20/FX60 using
externally connected 24 VAC transformer or 24 VDC power supply.
LP-FXLONFTT-0
LON communication card for FX20/FX60: 78 kbps, FTT-10A, 2-position removable screw-terminal
connector plug
LP-FXRS485-0
Dual port RS-485 communication card for FX20/FX60: electrically isolated, two 3-position removable
screw-terminal connector plugs
LP-FXWTC-0
Wireless TEC Option Card includes option card, mounting bracket, and direct-mount antenna
TEC20-A-1
Replacement antenna for Wireless TEC Option Card
TEC20-RA-1
Remote antenna for Wireless TEC Option Card when it is installed inside a metal cabinet or when
remote antenna mounting is required by physical installation, includes 0.53 m (1.75 ft) cable
LP-FXRS232-0
Single port RS-232 communication card for FX20/FX60: 115,200 max baud rate, DB-9M connector
LP-FXMDM-0
56 kbps, auto-dial/auto-answer modem for FX20/FX60: RJ-11 connector, disables onboard RS-232
port, maximum of one per FX20/FX60
LP-FXPMUS-0
Power module for FX20/FX60: 90-240 VAC, 50/60 Hz, U.S. wall adapter
LP-FXPMEU-0
Power module for FX20/FX60: 90-240 VAC, 50/60 Hz, European wall adapter
LP-FXPMUK-0
Power module for FX20/FX60: 90-240 VAC, 50/60 Hz, U.K. wall adapter
LP-FXPM24-0
Power module for FX20/FX60: 24 VAC/DC, DIN rail mountable
LP-FXPM263-0
Power module for FX20/FX60: 90-263 VAC/DC, 50/60 Hz DIN rail mountable
6 FX20/FX60 Supervisory Controllers Product Bulletin
Table 4: FX20/FX60 Software Accessories Ordering Information
Part Number
Description
LP-FX60EX256-0
License enabling 256 Mb memory expansion for one FX60
LP-FXBACIPC-0
License enabling BACnet IP client (import) driver for one FX20/FX60
LP-FXBACIPS-0
License enabling BACnet IP server (export) driver for one FX20/FX60
LP-FXBACMS-0
License enabling BACnet MS/TP driver for one FX20/FX60
LP-FXLONIP-0
License enabling LONWORKS IP driver for one FX20/FX40/FX60
LP-FXMBUS-0
License enabling M-Bus driver for one FX20/FX40/FX60
LP-FXMDBRTU-0
License enabling MODBUS RTU client (import) driver for one FX20/FX40/FX60
LP-FXMDBRTUS-0
License enabling MODBUS RTU server (export) driver for one FX20/FX40/FX60
LP-FXMDBTCP-0
License enabling MODBUS TCP client (import) driver for one FX20/FX40/FX60
LP-FXMDBTCPS-0
License enabling MODBUS TCP server (export) driver for one FX20/FX40/FX60
LP-FXSNMP-0
License enabling Simple Network Management Protocol (SNMP) driver for one FX20/FX40/FX60
LP-FXSMS-0
License enabling Simple Messaging Service driver for one FX20/FX40/FX60
LP-FXSSL-0
License enabling Secure Socket Layer (SSL) for one FX20/FX40/FX60
LP-FX40MA-0
License enabling one year of annual software maintenance for one FX20/FX40/FX60. Includes new
releases and interim service releases for 1 year from the date of purchase.
LP-FX40UPG-0
License enabling one-time, new release software upgrade for one FX20/FX40/FX60
Technical Specifications
Table 5: FX20/FX60 Controller
Product Codes
LP-FX2011N-0, LP-FX6011N-0
Power Requirements
See Ordering Codes for approved power modules
Environment
• Operating Temperature: 0 to 50°C (32 to 122°F)
• Storage Temperature: 0 to 60°C (32 to 140°F)
• Relative Humidity: 5 to 95%, noncondensing
Platform
FX20:
• IBM® PowerPC™ 405EP 250 MHz processor
• 128 MB Synchronous Dynamic Random Access Memory (SDRAM), 64 Mb Serial Flash
FX60:
• IBM PowerPC 440 524 MHz processor
• 128 MB SDRAM, 128 MB Serial Flash
• Optional 256 Mb DDR RAM
Battery backup: 5 minutes typical, shutdown begins within 10 seconds
Real-time clock: 3 month backup maximum (via battery)
Operating System
• QNX Real Time Operating System (RTOS)
• IBM J9 Java® Virtual Machine (JVM)
• Niagara
Continued on next page . . .
FX20/FX60 Supervisory Controllers Product Bulletin 7
Communications (Cont.)
• Two 10/100 Mb Ethernet ports, RJ-45 connectors
• One RS-232 port: 9-pin, D-shell connector
• One RS-485 non-isolated port: 3-position, removable, screw-terminal connector plug
• See Ordering Codes for optional communication cards
Chassis
• Mounting: DIN rail or screw mount
• Cooling: Internal air convection
• Dimensions: 6.315 x 4.820 x 2.437 in. (16.04 x 12.24 x 6.19 cm)
Agency Listing
• United States – UL Listed, File E107041, CCN PAZX, under UL 916, Energy
Management Equipment
• FCC compliant to CFR 47, part 15, subpart B, class A
• Canada - UL Listed, File E107041, CCN PAZX7, under CSA C22.2 No. 205, Signal
Equipment
• Industry Canada compliant to ICES-003
• Europe – CE Mark
• EMC Standards Applied:
− EN 61000-6-4 EMC Emissions Generic (Complies)
− EN 61000-6-2 and EN 61000-6-1 EMC Immunity (Complies, as documented below)
− EN50081-2 Generic Emissions Standard for Residential, Commercial, and Light
Industrial Environment
− CISPR-11 Limits of Radio Disturbance-Radiated Emissions (Pass Class A)
− CISPR-11 Limits of Radio Disturbance-Conducted Emissions (Pass Class A)
− IEC 61000-4-2 ESD (Pass Criteria B)
− IEC 61000-4-3 Radiated Field Immunity (Pass Criteria A)
− IEC 61000-4-4 Electrical Fast Transients Immunity-Signal Ports (Pass Criteria B)
− IEC 61000-4-4 Electrical Fast Transients Immunity -AC Power (Pass Criteria B)
− IEC 61000-4-5 Surge Immunity (Pass Criteria A)
− IEC 61000-4-6 Conducted Immunity (Pass Criteria A)
− IEC 61000-4-11 Voltage Dips (Pass Criteria A)
− IEC 61000-4-11 Voltage Interrupts (Pass Criteria A)
− IEC 61010-10-1: 90 + A1:92 + A2:95 Safety requirement for electrical equipment for
measurement, control, and laboratory use (Pass)
8 FX20/FX60 Supervisory Controllers Product Bulletin
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising