Rosemount Flow Computer

Rosemount Flow Computer
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
Rosemount Flow Computer
• “EZ Setup”- Guided Setup for First Time
Users
• Liquid, Gas, Steam, Mass Flow, Heat Flow,
and Corrected Volume Equations
• NX19 Gas Equations, Stacked DP
Transmitters
• Isolated Pulse and Analog Outputs Standard
• RS-232 Port Standard, RS-485 Optional
Windows™ Setup Software
• Internal Data Logging
• Remote Metering by Modem Available
• Wall Mount Enclosures Available
• Applications
-Utility Metering / Billing
-Compensated Mass Flow
-Energy Mass Balance
Content
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
www.rosemount.com
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
Expand the Capability of Flow Measurement Technology
Expand Capabilities
Steam Mass Flow
The Rosemount Flow Computer satisfies the
instrument requirements for a variety of flowmeter
types in liquid, gas, steam and heat applications.
Multiple flow equations are available in a single
instrument with many advanced features.
Flow Computer
Easy To Use
The alphanumeric display offers measured
parameters in an easy to understand format. Manual
access to measurements and display scrolling is
supported.
Versatile
Flowmeter
The versatility of the Flow Computer permits a wide
measure of capabilities within the instrument
package. The various hardware inputs and outputs
can be “soft” assigned to meet a variety of common
application needs. The user “soft selects” the usage
of each input/output while configuring the instrument.
Pressure
Transmitter
Temperature
Transmitter
Steam Net Heat
Flow Computer
Water
Adaptability
The isolated analog output can be chosen to follow
the volume flow, corrected volume flow, mass flow,
heat flow, temperature, pressure, or density by
means of a menu selection. Most hardware features
are assignable by this method.
Steam
Flow
The user can assign the standard RS-232 Serial Port
for external data logging, transaction printing, or for
connection to a modem for remote meter reading.
Simplified Verification
A Service or Test mode is provided to assist the user
during start-up system check out by monitoring
inputs and exercising outputs. The system setup can
also be printed.
Flowmeter
Pressure
Temperature
Transmitter Transmitter
Liquid Delta Heat
T2
Temperature
Transmitter
Warm
Flow Computer
Water
Steam
Cold
Flowmeter
2
Temperature
Transmitter
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
SPECIFICATIONS
Environmental
Current Loop Broken
Operating Temperature: -4 to 131 °F
Calibration: Operator assisted learn mode
Storage Temperature: -40 to +85 °C (-40 to 185 °F)
Extended calibration: Learns Zero and Full Scale of each range
Humidity: 0-95% Non-condensing
Fault Protection:
Materials: UL, CSA, VDE approved
Fast Transient: 500 V Protection (capacitive clamp)
Reverse Polarity: No ill effects
Display
Over-Voltage Limit: 50 VDC Over voltage protection
Type: 2 lines of 20 characters
Over-Current Protection: Internally current limited protected to
24VDC
Types: Backlit LCD
Character Size: 0.3” nominal
User selectable label descriptors and units of measure
Pulse Inputs:
Number of Flow Inputs: one
Keypad
Input Impedance: 10 k Ohms nominal
Keypad Type: Membrane Keypad
Trigger Level: (menu selectable)
Keypad Rating: Sealed to NEMA 4
High Level Input
Number of keys: 16
Logic On: 2.5 to 30 VDC
Logic Off: 0 to 2 VDC
Enclosure
Enclosure Options: Panel, Wall Mount NEMA 4, Wall Mount NEMA
12/13
Size: See Dimensional Drawings on page 8
Depth behind panel: 6.5” including mating connector
Type: DIN
Low Level Input (mag pickup)
Selectable sensitivity: 10 mV and 100 mV
Minimum Count Speed: 0.25 Hz (to maintain rate display)
Maximum Count Speed: Selectable: 0 to 50 kHz
Overvoltage Protection: 50 VDC
Materials: Plastic, UL94V-0, Flame retardant
Temperature, Pressure, Density Inputs
Bezel: Textured per matte finish
The compensation inputs usage are menu selectable for
temperature, temperature (  temp) 2, pressure, density, or not
used.
Power Input
The factory equipped power option is internally fused. An internal
line to line filter capacitor is provided for added transient
suppression. MOV protection for surge transient is also supported.
Universal AC Power: 85 to 276 Vrms, 50/60 Hz
DC Power Option: 24 VDC (16 to 48 VDC)
Power Consumption
AC Power: 6.5 V/A (6.5W)
DC Power: 300 mA max.
Flow Meter Types:
Linear: Vortex, Turbine, Positive Displacement, Magnetic and
others
Square Law: Orifice, Venturi, Nozzle, Wedge, Averaging Pitot,
Target and others
Multi-Point Linearization: May be used with all flowmeter types.
Including: 16 point, dynamic compensation
Calibration: Operator assisted learn mode
Operation: Ratiometric
Accuracy: 0.02% FS at 20° C
Basic Measurement Resolution: 16 bit
Update Rate: 2 updates/sec minimum
Automatic Fault detection:
Signal Over-range/under-range
Current Loop Broken
RTD short
RTD open
Reverse Polarity: No ill effects
Over-Current Limit (current input) Internally limited to protect
input to 24 VDC
Available Input Ranges
Current: 4-20 mA, 0-20 mA
Resistance: 100 Ohms DIN RTD
100 Ohm DIN RTD (DIN 43-760, BS 1904):
Flow Inputs:
Analog Input:
Accuracy: 0.02% FS at 20° C
Ranges
Voltage: 0-10 VDC, 0-5 VDC, 1-5 VDC
Current: 4-20 mA, 0-20 mA,
4-20 mA stacked, 0-20 mA stacked
Basic Measurement Resolution: 16 bit
Update Rate: 4 updates/sec
Automatic Fault detection: Signal over/under range,
Three Wire Lead Compensation
Internal RTD linearization learns ice point resistance
1 mA Excitation current with reverse polarity protection
Temperature Resolution: 0.1°C
Temperature Accuracy: 0.25°C
Stored Information (ROM)
Steam Tables (saturated & superheated),
Fluid Properties: Water, Air, Natural Gas, A Variety of User
Entered Industrial Fluids or Generic User Entry
3
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
User Entered Stored Information
(EEPROM /Nonvolatile RAM)
Transmitter Ranges, Signal Types
Fluid Properties
(reference density, expansion factor, specific heat, viscosity,
isentropic exponent, combustion heating value, Z factor)
Units Selections (English/Metric)
Excitation Voltage
24 VDC @ 100 mA (fault protected with self resetting fuse)
Data Logging
The data logger captures print list information to internal storage
for approximately 5000 transactions. This information can be used
for later uploading or printing. Storage format is selectable for
Comma-Carriage Return or Printer formats.
Isolated Pulse output
The isolated pulse output is menu assignable to Uncompensated
Volume Total, Compensated Volume Total, Heat Total or Mass
Total.
Pulse Output Form (menu selectable): Open Collector
Relay Outputs
NPN or 24 VDC voltage pulse
The relay outputs usage is menu assignable to (Individually for
each relay) Hi/Lo Rate Alarm, Hi/Lo Temperature Alarm, Hi/Lo
Pressure Alarm, Pulse Output (pulse options), Wet Steam or
General purpose warning (security).
Nominal On Voltage: 24 VDC
Number of relays: 2 (3 optional)
Saturation Voltage: 0.4 VDC
Contact Style: Form C contacts (Form A with 3 Relay option)
Pulse Duration: User selectable
Contact Ratings: 240 V, 5 amp
Pulse output buffer: 8 bit
Analog Outputs
The analog outputs are menu assignable to correspond to the
Uncompensated Volume Rate, Corrected Volume Rate, Mass
Rate, Heat Rate, Temperature, Density, or Pressure.
Number of Outputs: 2
Type: Isolated Current Sourcing (shared common)
Available Ranges: 0-20 mA, 4-20 mA (menu selectable)
Resolution: 16 bit
Accuracy: 0.05% FS at 20 °C
Update Rate: 5 updates/sec
Temperature Drift: Less than 200 ppm/°C
Maximum Load: 1000 ohms
Compliance Effect: Less than °.05% Span
60 Hz rejection: 40 dB minimum
EMI: No effect at 3 V/M
Calibration: Operator assisted Learn Mode
Averaging: User entry of DSP Averaging constant to cause a
smooth control action
Listing: CE Compliant, UL/C-UL Pending
Serial Communication
The serial port can be used for printing, datalogging, modem
connection, two way paging and communication with a computer.
RS-232:
Device ID: 01-99
Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200
Parity: None, Odd, Even
Handshaking: None, Software, Hardware
Print Setup: Configurable print list and formatting
RS-485: (optional 2nd COM port)
Device ID: 01-247
Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200
Parity: None, Odd, Even
Protocol: Modbus RTU (Half Duplex)
4
Maximum Sink Current: 25 mA
Maximum Source Current: 25 mA
Maximum Off Voltage: 30 VDC
Fault Protection
Reverse polarity: Shunt Diodes
Over-current Protected
Over-voltage Protected
Real Time Clock
The Flow Computer is equipped with a nonvolatile real time clock
with display of time and date.
Format:
24 hour format for time
Day, Month, Year for date
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
DIMENSIONAL DRAWINGS
FIGURE 1. Panel Mount Dimensions
FIGURE 3. Wall Mount (NEMA 12/13) Dimensions
5.67 (144)
9.4 (238)
RATE
147.43 GPM
TOTAL 267395.749 GAL
2.83
(72)
6.18 (157)
7.3 (184)
RATE
147.43 GPM
TOTAL 267395.749 GAL
TOTAL
1
RATE
2
ALARM1
3
TEMP
4
GRAND
6
SCROLL
7
ALARM2
8
PRES
9
PRINT
5
TIME
0
–
CLEAR
MENU
HELP
•
ENTER
Security
Tag
Provisions
0.385
(9.8)
8.4 (213)
Dotted Line Shows Optional Bezel Kit
0.59
(9.8)
0.5
(13)
6.15 (156)
0.28 (7.2)
0.625-in. 0.75-in. 5 places
4.72 (120)
3.43
(87)
4.13 (105)
2.33 (59)
0.75-in. Conduit
Knockouts (5 Places)
1.06 1.10 1.10 1.10 1.10
(27) (28) (28) (28) (28)
1.10 1.10 1.10 1.10
(28) (28) (28) (28)
0.4 (10)
7.8 (198)
5.43 (138)
FIGURE 4. Standard Terminal Layout
2.68
(68)
Panel
Cutout
RS-232
RS-485
Phone
1 2 3 4
1 2
5 4 3 2 1
9 8 7 6
FIGURE 2. Terminal Designations
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
DC OUTPUT
PRESSURE
RTD EXCIT (+)
(TEMP 2)
RTD SENS (+)
IN
Iin (+)
RTD SENS (-)
PULSE OUTPUT (+)
PULSE OUTPUT (-)
ANALOG OUTPUT 1 (+)
ANALOG OUTPUT 2 (+)
ANALOG OUTPUT COMMON (-)
17
18
19
20
21
22
NO
COM RLY1
NC
NC
COM RLY2
NO
DC OUTPUT
PULSE IN
---------COMMON
RTD EXCIT (+)
RTD SENS (+)
RTD SENS (-)
23 AC LINE
24 AC LINE
Vin (+)
Iin (+)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
FLOW
IN
TEMPERATURE
IN
Iin (+)
FIGURE 5. RS-232 DB-9 Pinout
5 4 3 2 1
9 8 7 6
1. Handshake Line (cd in)
2. Transmit (tx)
3. Receive (rx)
4. Do Not Use
5. Ground
6. Do Not Use
7. RTS Out
8. Do Not Use
9. DC Power Out*
DC (+)
DC (-)
POWER IN
*8 VDC Power supplied on Pin 9 to power modem
5
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
FIGURE 6. Wall Mount (NEMA 4) Dimensions
11.85 (301)
(4) Each #10-32 Brass Inserts &
Plated Carbon Steel Screws
1.75 (44)
A
B
B
13.73
(349)
5.35 (136)
6.00 (152)
6.75 (171)
7.21 (183)
A
(4) .34 dia.
(8.74)
8.31 (211)
9.01 (229)
BACK VIEW
SECTION A-A
11.20 (285)
9.85 (250)
Closed Cell Neoprene Gasket
S. St’L. Hinge
(2) S. St’L. Lockable Snap
Latch & Keeper Plate
Hinged Front Panel
shown Alum. - .09 Th’k
(4) S. St’L.
Mounting Feet
13.08 11.72
(332) (298)
11.50
(292)
(4) Each #10-32 Brass Inserts &
Plated Carbon Steel Screws
SECTION B-B
9.5 (241)
.47 (11.9) TYP
FRONT VIEW WITH LID REMOVED
FIGURE 7. NEMA 12/13 Terminal Designations
RATE
147.43 GPM
TOTAL 267395.749 GAL
TOTAL
1
RATE
2
PRE 1
3
TEMP
4
GRAND
6
SCROLL
7
PRE 2
8
DENS
9
RS-232
1
1
2
TIP
RING
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
23
24
6
DC OUTPUT
PULSE IN
---------COMMON
RTD EXCIT (+)
RTD SENS (+)
RTD SENS (-)
Vin (+)*
Iin (+)
FLOW
IN
TEMPERATURE
IN
Iin (+)
DC OUTPUT
PRESSURE
RTD EXCIT (+)
(TEMP 2)
RTD SENS (+)
IN
Iin (+)
RTD SENS (-)
PULSE OUTPUT (+)
PULSE OUTPUT (-)
ANALOG OUTPUT 1 (+)
ANALOG OUTPUT 2 (+)
ANALOG OUTPUT COMMON (-)
NO RLY1
COM RLY1
NC RLY1
NC RLY2
COM RLY2
NO RLY2
AC LINE
AC LINE
17
18
19
20
21
22
DC (+)
DC (-)
NO RLY1
COM RLY1
NO RLY2
COM RLY2
NO RLY3
COM RLY3
POWER IN
3 Relay Option
17
18
19
20
21
22
1
2
2
3
4
3
5
4
6
5
7
PRINT
5
TIME
0
–
CLEAR
MENU
HELP
•
ENTER
RS-485 Phone
6
8
1
2
3
4
1
2
9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
ORDERING INFORMATION
• Available
- Not Available
Rosemount Part Number
Description
Panel
NEMA 4
08800-0800-xxxx
Flow Computer
•
•
NEMA 12/13
•
1
3
AC (85 to 275 V)
DC (24 V)
•
•
•
•
•
•
0
1
None
RS-485
•
•
•
•
•
•
0
1
2
Panel
NEMA 4 Wall Mount
NEMA 12/13 Wall Mount
•
-
•
-
•
0
1
2
No Additional Option(1)
3 Relays
Internal Modem(2)
•
•
•
•
•
•
•
•
•
Input Type (Power Supply)
Network Card
Mounting
Options
Typical Part Number: 08800-0800-1000
(1) Note: Peak Demand, AGA NX 19, Stacked DP, Data Logging, Manifold Flowmeter Control, Modem Power, and Extended Temp Display are Standard.
(2) Note: Internal Modem cannot be ordered in combination with RS-485 Card for NEMA 12/13 Mounting.
7
Product Data Sheet
00813-0100-4005, Rev BA
October 2009
Rosemount Flow Computer
Standard Terms and Conditions of Sale can be found at www.rosemount.com/terms_of_sale
The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.
All other marks are the property of their respective owners.
© 2009 Rosemount, Inc. All rights reserved.
Emerson Process
Management
Rosemount Measurement
8200 Market Boulevard
Chanhassen, MN 55317 USA
T (U.S.) 1-800-999-9307
T (International) (952) 906-8888
F (952) 949-7001
00813-0100-4005 Rev BA, 10/09
Emerson Process Management Flow
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0)318 495555
F +31 (0)318 495556
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947
Enquiries@AP.EmersonProcess.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising