SmartPro 120V 700VA 450W Medical-Grade
Line-Interactive Tower UPS with 4 Outlets, Full
Isolation, USB, DB9
MODEL NUMBER: SMART700HG
Highlights
Supports a half load up to 42 minutes; full load up to 18 minutes
Four hospital-grade outlets and hospital-grade plug
480 joule surge suppression rating protects connected equipment
Alarm mute/alarm quiet control is ideal for use around patients
Package Includes
SMART700HG 700VA/450W
Medical-Grade Tower UPS
System
USB monitoring cable, 6 ft.
DB9 serial monitoring cable, 6 ft.
Owner’s Manual
Description
Tripp Lite’s SMART700HG medical-grade UPS system provides dependable battery backup and is fully compliant with UL 60601-1 regulations when plugged into a hospital-grade outlet, making it ideal for use in patient-care vicinities. The 700VA/450W capacity provides up to 42 minutes of runtime for a half load, or
18 minutes for a full load so you can work through short power failures and perform an orderly system shutdown in a prolonged blackout.
Built-in line-interactive voltage regulation corrects brownouts as low as 81V and overvoltages as high as 143V to normal 120V nominal output, without drawing battery power. The SMART700HG’s built-in isolation transformer with Faraday shield offers full isolation and removes common mode noise while maintaining full AC surge suppression in all modes.
This UPS system features four NEMA 5-15R-HG hospital-grade outlets and has a hospital-grade NEMA 5-15P-HG plug with a 6 ft. cord for flexibility in placement. All four outlets provide both backup protection and surge protection, rated to 480 joules.
The SMART700HG also features diagnostic LEDs, as well as a USB port and a DB9 serial port that work with Tripp Lite’s free downloadable PowerAlert software for safe, unattended system shutdown and file saves in the event of a prolonged power failure.
Features
Provides Ideal UPS Backup in Healthcare Facilities
Compliant with UL 60601-1 standards for use in patient-care vicinities, when plugged into a hospital-grade outlet
Built-in isolation transformer with Faraday shield offers full isolation and removes common mode noise
Hospital-grade plug with 6 ft. cord provides flexibility in placement so healthcare workers can focus on treating the patient
Battery Backup and Full Surge Protection
42 minutes runtime for half load (225W); 18 minutes for full load (450W)
All four hospital-grade outlets provide surge protection rated to 480 joules
EMI/RFI noise filtering ensures equipment runs smoothly without line noise interference
1 / 5
Resistant to electrostatic discharge
LEDs and Audible Alarms Keep You Aware of Power Status
Indicator lights on the front of the unit show you when the UPS is on and supplying utility power, when operating in voltage correction mode or in battery mode, relative load level and low-battery warning
Audible alarms alert you to power failure, overload and low battery conditions; the alarm’s mute/quiet mode ensures patients are not disturbed
Saves Your Files, Even When You’re Away
Works with Tripp Lite PowerAlert software (available as a free download) to enable safe, unattended system shutdown and files saves during prolonged power failures
Connects to your computer via either the DB9 port or USB port
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output Watt Capacity (Watts)
Power Factor
Nominal Output Voltage(s)
Supported
Frequency Compatibility
Output Voltage Regulation (Line
Mode)
700
450
0.6
115V; 120V
60 Hz
-18%, +8%
Output Voltage Regulation (Battery
Mode)
Output Receptacles
Output Receptacle Details
115V (+/- 5%)
(4) 5-15R
Hospital grade output receptacles
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) PWM sine wave
INPUT
Rated input current (Maximum Load) 5.5A
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-15P-HG
Input Circuit Breakers
UPS Input Cord Length (ft.)
UPS Input Cord Length (m)
Recommended Electrical Service
Input Cord Length (ft.)
10A
6
1.8
15A 120V
6
2 / 5
Input Cord Length (m)
Input Phase
1.83
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
Expandable Runtime
18 min. (450w)
42 min. (225w)
36
Less than 4 hours from 10% to 90%
RBC53
Battery access door
Hot-swappable, user replaceable batteries
No
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Severe Undervoltage Correction
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 81 to 143
Input voltages between 126 and 143 are reduced by 9%
Input voltages between 96 and 106 are boosted by 10%
Input voltages between 81 and 95 are boosted by 21%
USER INTERFACE, ALERTS & CONTROLS
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
Audible Alarm
LED Indicators
Audible alarm indicates power-failure, overload and low-battery conditions
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
UPS AC Suppression Response
Time
EMI / RFI AC Noise Suppression
AC Suppression Joule Rating
AC Suppression Response Time
480
Instantaneous
Yes
480
Instantaneous
ISOLATION
Output Isolation Transformer Hospital grade load isolation transformer
3 / 5
Leakage Current Equal to 100 microamps
PHYSICAL
Installation Form Factors Supported with Optional Accessories
Primary Form Factor
UPS Power Module Dimensions
(hwd, in.)
Wallmount(
Tower
UPSWM
12.8 x 7.5 x 9
UPS Power Module Dimensions
(hwd, cm)
UPS Power Module Weight (lbs.)
UPS Power Module Weight (kg)
32.4 x 19 x 22.9
44.2
20.05
UPS Shipping Dimensions (hwd / in.) 18.2 x 11.8 x 13.5
UPS Shipping Dimensions (hwd / cm)
46.4 x 29.8 x 34.3
- tower mounting kit)
Shipping Weight (lbs.)
Shipping Weight (kg)
Cooling Method
UPS Housing Material
Primary UPS Height (mm)
Primary UPS Width (mm)
Primary UPS Depth (mm)
Shipping Height (mm)
Shipping Width (mm)
Shipping Depth (mm)
325
190
229
462
49
22.2
Fan
PVC
300
343
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
Battery Mode BTU / Hr. (Full Load)
AC Mode Efficiency Rating (100%
Load)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
97.7
189.1
94%
COMMUNICATIONS
Communications Interface USB; DB9 Serial
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
4 / 5
PowerAlert Software
Communications Cable
For local monitoring via the UPS’s built-in communication ports , download PowerAlert Local software at http://www.tripplite.com/poweralert
USB and DB9 serial cabling included
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
2-4 milliseconds
81
143
SPECIAL FEATURES
Grounding Lug
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Grounding lug
Cold-start operation supported
Hot swappable batteries
Greater than 95% efficiency - GREEN UPS
CERTIFICATIONS
UPS Certifications
Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances); Tested to CSA (Canada);
Tested to UL1778 (USA); Tested to UL60601-1 (medical grade)
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
© 2017 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies: https://www.tripplite.com/products/product-certification-agencies
5 / 5
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement